TECHNICAL SPECIFICATIONS
FOR
11 kV & 66 kV
STATIC SHUNT CAPACITOR BANK
1. All the drawings, i.e. elevation, side view, plan, cross sectional view etc., in
AutoCAD format and manuals in PDF format, for offered item shall be
submitted. Also the hard copies as per specification shall be submitted.
2. The bidder shall submit Quality Assurance Plan for manufacturing process
and Field Quality Plan with the technical bid.
3. The bidder shall have to submit all the required type test reports for the
offered item. However, in the event of partial submission or reports older than
specified limit, bidder must submit his confirmation for those type test report/s
to be submitted in the event of an order, without affecting delivery schedule,
before commencement of supply, free of cost. In absence of this confirmation,
the evaluation shall be carried out accordingly as non submission of type test
reports.
4. The bidder must fill up all the point of GTP for offered item/s. Instead of
indicating “refer drawing, or as per IS/IEC”, the exact value/s must be filled in.
5. All the points other than GTP, which are asked to confirm in technical
specifications must be submitted separately with the bid.
7. Please note that the evaluation will be carried out on the strength of content of
bid only. No further correspondence will be made.
8. The bidder shall bring out all the technical deviation/s only at the specified
annexure.
9. The bidder should indicate manufacturing capacity by submitting latest
updated certificate of a Chartered Engineer (CE).
SECTION – I
11 kV & 66 kV STATIC SHUNT CAPACITOR BANK
1.1 SCOPE:
The major equipments for each shunt capacitor banks shall be as per
schedule – A of tender.
1.2 STANDARDS:
1.2.1. The shunt capacitor bank and its associated equipments shall conform
to the following standards.
All IS/IEC shall be read with latest amendments in vogue on the date of
technical bid opening.
1.3 DRAWINGS:
1.3.1 The following drawings illustrating the technical details of this capacitor
bank shall be submitted by each bidder.
a) General outlines dimensional drawings of all the equipments with all
technical details giving the net weights, ratings & capacity of
equipments and quantity.
b) Detailed sectional views, showing the general constructional and other
relevant features of various equipments.
c) Schematic connection diagrams for complete capacitor banks with
associated switchgear equipment.
d) All above drawings in soft.
1.3.2 In the event of an order, the successful bidder shall furnish the
following drawings, in triplicate, in spiral bound volume, for approval.
a) General dimensional outline drawings showing front and side
elevations and plan of Capacitor Units, banks, Circuit Breaker, etc.
b) Foundation drawings for structure of capacitor bank.
c) Elevated G.I. support structure drawings.
d) Internal arrangement and connections of capacitor unit.
(ii) The protective scheme shall be either by two step current relay
arranged as follows:
If the failure of one or more units causes an over voltage of less than
10% tolerable on the other remaining healthy units, then the unbalance
current shall cause in the first step to sound an alarm. But if more than
the above numbers of units fail causing a voltage rise of more than
10% then the unbalance current shall cause to trip and isolate the
capacitor bank instantaneously.
(iii) The per phase and individual star group rating shall be built up by
series parallel combination of individual units so as to achieve the
desired rating of the bank. The individual capacity ratings shall be as
per IS: 13925.
(iv) All parallel units in one series group shall preferably be arranged in
different tiers, that is, one series group shall be duly insulated from one
another by post insulators adequate to withstand the voltage that may
be impressed and shall be sufficient to withstand even in case of total
failure of all the parallel units in a series group. The complete assembly
shall also be duly insulated from the earth potential by supporting post
insulators.
(v) Although the tolerances in the output rating of each individual unit shall
be as per IS: 13925 yet it shall be ensured that in a completely
assembled bank, the departures from the nominal rating and within the
specified tolerances values shall not cause nuisance alarm or tripping
since such alarm or tripping shall be to meet only with the protective
requirements specified.
(vi) The tolerances in the output ratings shall not cause departures in the
line currents by that value specified in IS: 13925. Besides it shall also
be ensured that these unsymmetrical currents shall not cause
unsymmetrical voltage rises, whether for short periods or during
prolonged operation.
(vii Individual units shall be designed to meet with the requirements of the
permissible overloads as specified as per IS: 13925. Each unit shall
also be provided with internal discharge devices complying with the
requirements of the IS: 13925 part-I.
(viii) The rated voltage of the NCT shall be 12 kV and 72.5 kV, taking in to
consideration the voltage impressed on the NCT due to:
1.4.2.2 Each capacitor unit shall have scaled sheet steel container with suitable
mounting bracket which can easily be fixed to frame structures. The
container shall be built from heavy gauge Stainless Steel, 1.6 mm thick
sheet steel with welded seams, mechanically strong, rigid and
hermetically sealed. The container of capacitor Unit shall be designed
to allow for expansion and contraction due to all ambient & loading
conditions expected during the life of the unit.
1.4.2.3 The capacitor elements shall be thoroughly dried and impregnated with
an impregnant that has been completely refined so as not to leave any
gas or impurities which may cause deterioration of the dielectric. The
impregnant used shall have low viscosity and high chemical stability. It
should be non-PCB (NPCB). It shall be incombustible and have a high
dielectric constant. Capacitor dielectric shall be 100% polypropylene.
However, in case of 100% polypropylene capacitor the polypropylene
shall be hazy and aluminum foil should be embossed for proper
impregnation. The Characteristics of the oil used for impregnation shall
be furnished in the bid. The total thickness of dielectric (excluding
aluminum foil) should be clearly indicated in the bid. The nos of layers
of dielectric shall be three of more. The details of aluminum foil shall
also be furnished. The impregnation shall be carried out under high
vacuum & unit shall be totally sealed.
The raw material to be used for manufacturing of capacitor unit i.e.
polypropylene film, non PCB non toxic oil and aluminum foil shall be of
best quality. List of raw material sources shall be submitted with
technical bid.
1.4.2.4 Each unit shall have two bushing for terminal connection. The rating of
bushing should not be less than 15 kV, suitable for series / parallel
connection with other units to form capacitor bank at 50 Hz. The
bushing shall be of porcelain suitable for heavily polluted atmosphere
having required creepage distance not less than 375 mm.
1.4.2.5 The capacitor shall have low value of loss which shall not exceed 0.2
watt per KVAR. The loss value of discharge device/resistor and
capacitor unit shall be indicated in GTP. The tan delta characteristics
of the capacitor unit shall be furnished. The losses in watts for each
capacitor unit including losses in fuses and discharge resistors forming
integral part of the capacitors along with losses for series reactor shall
be guaranteed. If these figures of capacitor losses exceed 0.2W/KVAR,
the capacitors will be liable for rejection. Total losses shall be complied
as below:
6 x(W x n + losses in series reactor)
Where, n is number of capacitor units per phase of star connection and
W is the total loss in a capacitor unit.
The loss temperature characteristics, capacity temperature
characteristics and insulation resistance temperature characteristics
shall also be furnished. The use of P.C.B. as dielectric for capacitor
shall not be acceptable. The dielectric medium to be used shall be non-
poisonous and non-toxic in nature and shall not cause pollution of
environment.
1.4.2.6 The rating of capacitor cell for respective bank shall be as follow:
Sr. Particulars 11 kV 11 kV 66 kV
No. 1 x 3.6 MVAr bank 2 x 3.6 MVAr bank 1 x 14.4 MVAr bank
1 Rated voltage, V 7300 7300 7300
2 Rated kVAr 200 200 200
3 Rated current, A 27.4 27.4 27.4
4 Capacitance in nF 11.94 11.94 11.94
5 BIL, kVrms/kVp 38 / 95 38/95 38/95
1.4.3.2 The capacitor units shall be so arranged in the bank as to avoid bird
faults, by providing adequate clearance between the body of the
capacitor unit, of one phase, and the line terminal or the common bus
for the units of the adjacent other phases. Necessary bird guards at
required locations and insulating sleeve on conductor shall be
provided. The units shall be so arranged that uniform temperature of
complete bank is maintained when installed in open yard.
1.4.3.3 In case of protection by internal fuses, each unit shall be provided with
fuses for each of its element, so that the faulty element within the unit
is automatically out of circuit. The operation of the bank shall not be
disturbed (except change in capacity within the unit) in any way by
switching out of the faulty element.
1.4.6 STRUCTURES:
and height. The mounting racks shall be hot dip galvanised steel
sections, not below 40 x 40 x 5 mm size. Each end of the rack shall
have provision to receive incoming line connection. The racks shall be
complete with rack insulators, foundation bolts or any other hardware
etc. for assembly into complete bank. The height of the racks of
capacitor banks shall be such that for making electrical connections
with other equipment proper electrical clearances are maintained. The
capacitor bank along with its mounting racks and series reactor and
null CT shall be suitable for installation on the plinth and the enclosure
shall be suitably fenced and interlocked as per safety requirements.
The weight of structure, mass of zinc coating shall be indicated in GTP.
Minimum mass of zinc shall be 610 gm/m2.
1.5.1 The circuit breaker shall be outdoor type and shall be as per technical
specification attached with the respective tender. The 66 kV CB shall
be SF6 type and the 11 kV CB shall be vacuum type. Both CBs shall
be suitable for capacitor duties.
1.5.2 11 & 66 kV C&R panel shall be as per technical specification attached
with the respective tender.
1.5.3 66 kV outdoor isolators shall be as per technical specification attached
with the respective tender.
11 kV outdoor isolator shall be three phase double break out door type
as per clause no. 2.3.6.2.
1.5.4 66 kV solid core insulators shall be as per technical specification
attached with the respective tender.
1.5.5 66 kV outdoor current transformers shall be as per technical
specification attached with the respective tender. For 11 kV outdoor
CTs shall be used as per technical specification attached with the
tender.
1.5.6 66 kV outdoor NCT shall be as per technical specification attached with
the tender. 11 kV NCT shall be as per clause no. 2.3.4.
1.5.7 11 kV station type lightning arresters with suitable structure shall be
supplied. 66 kV lightning arresters with structure shall be as per
technical specification attached with the respective tender.
The series reactor of small size is required to limit the inrush current
during switching operation & suppress the harmonic currents. The
series reactor shall be aluminum wound, outdoor type, 50Hz, air
cored, non magnetically shielded or air cooled type and suitable for
operation in climatic conditions specified, conforms to IS:5553 (as
amended up to date). The reactor shall be natural air cooled coreless
type with one bushing each on incoming and outgoing side.
The series reactors shall confirm to type tests and shall be subjected to
routine tests as per IS: 5553.
1.7 ACCESSORIES:
A portable discharge device complete with clamps sticks cable
shall be provided with each capacitor bank for discharging the
capacitors manually whenever necessary. The device shall be
properly insulated. A printed booklet giving the safe working
instructions and safety measures along with maintenance
schedule and procedure to be followed shall be supplied.
1.9 TESTS :
a) Type Tests: The following type test reports shall be submitted with the
technical bid from NABL accredited laboratory not older than 5 years and
valid till expiry of validity of offer.
The capacitor Cells, Series reactor, structure, etc. shall be subject to the
various type routine and acceptance tests as per relevant IS or IEC
Publication (amended up-to-date). The capacitor offered must have been
also endurance tested as per IEC: 871-2/IS: 13925 and capacitor under
the package shall also be type tested as per relevant IS/IEC.
The copies of these type test reports should be submitted along with offer.
1. Capacitor Unit:
The following type test reports shall be submitted with technical bid for an
offered unit.
i) Thermal stability test
ii) Capacitor loss tangent (Tan Delta) measurement at elevated
temperature.
iii) AC voltage test between terminals & container.
iv) Lightning Impulse Voltage test between terminals & container.
v) Short Circuit Discharge test.
vi) Endurance test as per IEC: 871-2/IS:13925
vii) Sealing test: The test shall be carried out at 70 + 5ºC for a period of 12
hours.
2. Series Reactor:
a) Temp. Rise at rated continuous current Test
b) Short circuit Test
c) Impulse voltage withstand test.
a) Measurement of winding resistance
b) Measurement of Impedance
c) Measurement of Load losses
d) Separate source withstand test
e) Inter turn O/V.
f) Measurement of IR value
3. 11 kV Isolators:
(a) For 11 KV isolators and Isolator-cum-Earth Switches following type
test reports shall be submitted.
(1) Lighting impulse voltage withstands Test.
(2) Temperature Rise Test.
(3) Rated peak withstands current and rated short time
withstand current test.
(4) Mechanical endurance test.
(5) Power freq voltage (dry & wet) withstand test.
4) Other equipments:
Reports of all type tests as stipulated in respective technical specification or
as per applicable standards for all other associated equipments offered shall
be invariably submitted with technical bid.
The equipment shall comply with all routine and acceptance tests. Routine
and acceptance tests as per relevant IS shall be carried out on each
equipment in presence of GETCO representative, at manufacturer's works
only. All test reports should be submitted before dispatch of the
equipment.
1. Capacitor Unit:
2. Series Reactor
a) Measurement of winding resistance
b) Measurement of Impedance
c) Measurement of Load losses
d) Measurement of separate source withstand
e) Inter turn O/V or Imp.
f) Measurement of IR value
3. Structures:
As per IS for steel and hot dip galvanising
4. Isolator:
All routine/acceptance tests shall be carried out on each Isolator and
Isolator-cum-Earthing Switch and on insulators, as per technical
specification and applicable standards, in the presence of GETCO
representative.
5. Other equipments:
All routine/acceptance tests as stipulated in respective technical
specification for all other equipments offered shall be carried out
and report is submitted for approval before dispatch.
1.10 FOUNDATION :
1.10.1 The detailed foundation drawings showing complete particulars as
required for casting foundation for normal soil, for Capacitor Bank &
associated equipments shall be furnished by the successful bidders
along with the drawings. No deviation to this clause is permitted.
The manuals shall be spiral bound and shall contain all the printed
drawings, requisite information for erection, operation and maintenance
of the equipment. The manuals shall include all the required
details/drawings, along with the following particulars:
a) Marked erection prints identifying the component parts of the
equipment as dispatched with assembly drawings.
b) Detailed dimensions, assembly and description of all the
components and catalogues for operation of Capacitor Units and
switchgear equipment.
c) Complete list of spare parts.
d) Reduced drawings of all schematic control and wiring as finally
approved.
e) Complete details of tools tackles & their use and
f) Detailed foundation, erection etc. drawings for VCB & SF-6
Breaker & its associated parts & equipments.
1.13.3 The penalties shall be separately evaluated from the excess of the test
figure of losses in kilowatt, over the corresponding guaranteed value.
No tolerance shall be permitted over the test figures of the losses.
1.13.4 The penalties shall be calculated for excess of losses at the rate of
Rs.60,198/- per K.W. For the fraction of kilowatt, the penalties shall be
applied prorata. If the test figure of losses is less than the guaranteed
values, no bonus will be allowed. The bidders should note that values
assigned for loading of losses, are based on the present worth factor and,
therefore, capitalization of investment shall not be made separately.
1.14 ERECTION :
The bidder is required to assist the purchaser for erection and
commissioning of Capacitor Units and 11 KV & 66 KV Circuit
Breakers. The successful bidder is required to depute
erection/commissioning engineer at the request of purchase free of cost.
1.15 GUARANTEE :
The bidder shall guarantee the Capacitor Banks and associated
equipments for 36 months from date of commissioning and 42 months
from the dated of supply, whichever is earlier
SECTION – II
11 kV & 66 kV STATIC SHUNT CAPACITOR BANK
2.1 SCOPE :
2.1.1 This section covers the specific technical particulars, climatic and
Isoceraunic conditions and system particulars suiting with the static
shunt capacitor banks, circuit breakers, series reactors, neutral
current transformer, isolators, and Lightning arresters which shall
be offered as per the "General Technical Requirements" given in
Section-III of this specification and the "Schedule of Requirements"
specified herein.
2.3.1.2 The supplier shall include the means to protect the capacitor bank
against sustained over voltages more than 1.05 P.U.
sr Particulars 11 kV 11 kV 66 kV
no 1 x 3.6 MVAr 2 x 3.6 MVAr 1 x 14.4 MVAr
a) Rated voltage. 12 kV 12 kV 72.5 KV
BIL 28/75 kVp 28/75 kVp 140/350 kVp
b) Type Outdoor, dry Outdoor, dry Outdoor, dry
type, single type, single type, single
phase, air phase, air phase, air
cooled, cooled, cooled,
Aluminum Aluminum Aluminum
wound wound wound
e) Rated continuous current (Amps). 164.3 164.3 109.68
f) Rated KVAR. 1.2 1.2 4.8
g) Maximum permissible continuous 130% of rated continuous current of capacitor bank.
current.
h) Temperature rise in :
a) Oil (ºC) 40
b) Winding (ºC) 50
i) Rated short time symmetrical 16 times of 130% rated current of capacitor bank
rms. current & time. for 3 Sec.
j) Number of terminal bushing. As required.
k) Number of series reactor required 6 nos of 1 phase reactor
per cap Bank.
2.3.5.2 The 11 kV lightning arresters station duty type suitable to meet the
following requirements shall also be provided per phase:
Sr Particulars 11 KV
No
a) i) Rated voltage (KV) 12 KV
ii) Energy class. 3
b) i) Rated nominal discharge current (KA) (with 8/10 10 KA
micro second wave)
ii) MCOV (Minimum value) 12 KV
iii) Impulse Residual voltage (Max. value)
i) at 0.5 x NDC 38 kVp
ii) at 2 x NDC 45 kVp
iv) Residual voltage at steep current (Max) 45 kVp
v) Switching residual voltage (Max) at 2 KA. 35 kVp
c) Long duration current impulse test on heavy duty to As per : 3070-1974
10 KA Arrester.
d) Impulse withstand test voltage (KV peak) (with 1.2/50 75 KV
micro sec. wave)
2.3.5.3 The 11 kV arrester offered shall be gapless type & shall meet the
requirement of "IEC" latest Amendment on "Gapless Arresters". Full
Technical particulars of gapless arresters should be furnished.
2.3.6 Isolators:
2.3.6.1 The Technical requirement of 66 kV isolator shall be as per
technical specification attached separately with the tender.
2.3.6.2 The 11 kV isolators shall also comply with the following technical
requirements:
Sr Particulars 11 KV
No
a) Type Outdoor, manually operated, double
break structure mounted.
b) Rated continuous current (Amps) 800
c) Rated short time current (KA) 25 KA, 3 Sec.
d) Rated peak withstand current. 62.5 kAp
e) Rated Voltage. 12 kV
f) BIL 12/30/75 kVp
2.3.8 All the terminal connectors required for all the equipments
of capacitor bank shall be supplied in line with applicable
standard.
SECTION - III
BIDDER SCHEDULES
SCHEDULE A/1
11 KV 66 KV
1) Manufacturer's name.
3) Reference Standard.
i) per cell
ii) per phase
15 Type of impregnation.
18 Discharge time
Discharge internal device.
19 Total weight.
a) With resistor.
b) Without resistor.
22 Terminal arrangement.
Place :
BIDDER SCHEDULES
SCHEDULE A/2
1) Manufacturer's name.
2) Manufacturer's type, designation.
3) Reference Standard.
4) MVAr output at rated voltage
5) MVAr output at service voltage
6) Rated voltage.
7) Service Voltage.
8) Rated Frequency.
9) No. of Phases.
10) Insulation level :
a) 1-Minute power frequency
withstand voltage between
terminals shorted and phase/earth.
14 Tests:
All equipment will be subject to all
routine/acceptance and Type tests.
15 List of Fittings, support structures,
bolts, nuts, foundation bolts, clamp and
connectors accessories, included.
Place :
BIDDER SCHEDULES
SCHEDULE A/3
11 kV 66 KV
1 Manufacturer's name.
2 Manufacturer's type, designation.
3 Reference Standard.
4 Rated line voltage (KV)
5 No. of phases.
6 Rated frequency.
7 Reactance/Phase (Ohms)
Percentage impedance
8 Choke Voltage/Phase (Volts)
9 Rated continuous current.
10 Rated KVAR
11 i) Losses at Rated continuous current
at 75ºC (KW)
19 Tests :
a) Series reactor will be subjected to all
routine, acceptance and type tests as per
I.S.S.
21 Total weight.
22 Type of cooling
23 Whether series reactors will be provided with
the following fittings & accessories.
DATE:
SIGN:
SEAL of bidder