AD 305 deals with the requirements of bolted end-plate moment connections that
are assumed for design to be fully rigid up to the Ultimate Limit State. However,
since the publication of AD 305 the Advisory Desk has been asked whether these
connections, with their thick end plates & flanges and bolt failure (mode 3) etc,
have sufficient ductility or rotation capacity in various circumstances.
Moment connections are classified according to strength (moment resistance),
rigidity (rotational stiffness) and ductility (rotation capacity). Figure 1.2 in Joints
in Steel Construction: Moment Connections, (SCI-P-207) shows the various
moment-rotation curves used in connection classification. Strength and rotational
stiffness are the primary requirements for moment connections in steel
structures analysed elastically. Likewise, strength and rotational stiffness are the
primary requirements for moment connections in steel structures analysed
plastically where the connections are not at the plastic hinge locations in the
frame. The primary requirements for connections located at plastic hinges are
rotation capacity and strength, which may be either full or partial strength.
Strength, rigidity and ductility of connections are related to the deformation of
the components in the connection.
Traditional UK practice when designing single story portal frames plastically has
been to ensure that a plastic hinge does not form within the haunch and clauses
5.2.3.8 and 5.3.5.1 in BS 5950-1: 2000 are examples of this practice. Figure 1
shows the two options for the location of the plastic hinge around the eaves when
a plastic hinge does not form within the haunch.
Figure 2 shows the normal location of the plastic hinge in the rafter close to the
apex. In both cases the bolted moment connection is not at the plastic hinge
location and therefore the fully rigid connections described in AD 305 may be
used. However, industry practice is to use well proportioned connections
designed for strength alone to be treated as rigid in the analysis of single story
portal frames. Section 2.5 in SCI-P-207 permits this practice.
There is very little history in the UK of designing multi storey frames plastically
and using bolted moment connections to form the beam to column connections.
Therefore, it is not surprising that BS 5950-1: 2000 is silent on the issue of
connections design for this type of frame where plastic hinges occur at the beam
to column connection. However, other design codes offer the option of designing
these connections for 1.2 times the plastic moment of resistance of the beam
which implies that a small haunch will be required. The connection may then be
designed as described in AD 305. When this approach is used the ductility of the
connection is usually not checked because the plastic hinge will be displaced to
the steel beam.