UPS Adira (10kVA, 20kVA 3/1 phase) Table of Contents
Table of Contents
1. Introduction ..................................................................................................................... 5
1.1 Introduction ....................................................................................................................... 5
1.2 Validity .............................................................................................................................. 6
1.3 Storage ............................................................................................................................. 6
1.4 Symbols in this Manual ..................................................................................................... 6
1.5 Information Obligation ..................................................................................................... 10
1.6 Warranty Conditions ....................................................................................................... 10
1.7 Transport and Storage .................................................................................................... 12
1.8 Positioning ...................................................................................................................... 13
2. Safety Instructions ........................................................................................................ 14
2.1 Introduction ..................................................................................................................... 14
2.2 Proper Use...................................................................................................................... 14
2.3 Avoiding Personal Injury / Property Damage ................................................................... 15
2.4 Protecting the Environment ............................................................................................. 15
2.5 Connection...................................................................................................................... 16
2.6 Operation ........................................................................................................................ 17
2.7 Working with Accumulators ............................................................................................. 17
2.8 Maintenance, Service and Malfunctions .......................................................................... 18
3. Device description of the UPS ..................................................................................... 19
3.1 Elements on the front of the device ................................................................................. 20
3.2 Elements on the back of the device ................................................................................. 25
3.3 Components ................................................................................................................... 29
4. Storage and Unpacking ................................................................................................ 32
4.1 Storage of the UPS ......................................................................................................... 32
4.2 Moving the UPS to the installation site ............................................................................ 32
4.3 Unpacking of the device .................................................................................................. 32
5. System Description....................................................................................................... 36
6. UPS Installation and Connection ................................................................................. 38
6.1 Notes on the installation .................................................................................................. 38
6.2 Connecting the UPS ....................................................................................................... 39
6.3 Communication port of the UPS ...................................................................................... 40
6.4 Connection sequence ..................................................................................................... 40
6.5 Configuration of the EPO-port ......................................................................................... 41
6.6 Operating procedure for the connection with an external battery .................................... 42
6.7 Feedback protection ....................................................................................................... 43
Adira series 3
UPS Adira (10kVA, 20kVA 3/1 phase) Table of Contents
7. Operation .......................................................................................................................45
7.1 Operation of the UPS ......................................................................................................45
7.2 UPS operating instructions ..............................................................................................50
7.3 Menu ...............................................................................................................................54
8. Troubleshooting ............................................................................................................66
8.1 Troubleshooting according to warning indication .............................................................66
9. Software .........................................................................................................................69
10. Maintenance and Service ..............................................................................................70
10.1 Measuring the backup-time (support time) .......................................................................70
10.2 Replacing the accumulators ............................................................................................71
10.3 Service-Log .....................................................................................................................72
10.4 Service-Hotline ................................................................................................................73
10.5 Maintenance and service contracts .................................................................................73
11. Technical Data ...............................................................................................................74
12. Scope of Delivery / (Optional) Accessories ................................................................76
12.2 Wearing parts list.............................................................................................................77
13. Conformity Declarations ...............................................................................................78
13.1 Adira 3/1 10kVA ..............................................................................................................78
13.2 Adira 3/1 20kVA ..............................................................................................................79
Adira series 4
UPS Adira (10kVA, 20kVA 3/1 phase) Introduction
1. Introduction
1.1 Introduction
Dear Operator,
You are about to operate an uninterruptible power supply.
This operating manual should provide you with support for working responsibly
and basic information about the uninterruptible power supply, namely how it op-
erates, its application and what you should do in the event of malfunctioning.
Furthermore, this operating manual contains instructions for the transport and
storage as well as the handling and installation of the uninterruptible power sup-
ply.
The plan guidelines in this operating manual only relate to special requirements
for the uninterruptible power supply. During installation, make sure you follow
the national and local requirements for electrical installations.
The content of this device description may change due to technological pro-
gress. We have tried to present the content correctly and clearly. If, however,
we have made errors, we would be grateful for information about this.
We do not assume any liability for errors in this operating manual or any conse-
quences resulting thereof.
The uninterruptible power supply is intended to protect sensitive electronic sys-
tems from interferences that could occur due to bad electric quality or grid fail-
ures.
Please read this operating manual carefully and take note particularly of
the safety instructions!
If you have questions about the device, the technical supervisor in your com-
pany or our employees will be glad to help you.
Your
EFFEKTA Regeltechnik GmbH
Adira series 5
UPS Adira (10kVA, 20kVA 3/1 phase) Introduction
1.2 Validity
The descriptions in this operating manual relate solely to the
1.3 Storage
This operating manual for the device must be stored in the vicinity of the device
at all times so it is immediately available if need be.
Adira series 6
UPS Adira (10kVA, 20kVA 3/1 phase) Introduction
Adira series 7
UPS Adira (10kVA, 20kVA 3/1 phase) Introduction
Adira series 8
UPS Adira (10kVA, 20kVA 3/1 phase) Introduction
Adira series 9
UPS Adira (10kVA, 20kVA 3/1 phase) Introduction
– Disposal
of this device.
EFFEKTA Regeltechnik GmbH is not liable for damage incurred or caused
by staff who have not been trained or who have been insufficiently
trained!
In the event of defects caused by: freight damage, accident, natural catastro-
phes, misuse, vandalism, improper use, defective maintenance or incorrect re-
pair by third parties.
– Improper use such as plugging the device into unsuitable energy sources,
attempts to overload the UPS, use in an unsuitable environment, etc.
– In the event of failure to follow instructions in the provided documentation.
Adira series 10
UPS Adira (10kVA, 20kVA 3/1 phase) Introduction
– In the event that the product is incompatible due to possible technical inno-
vations or regulations that occur after the purchase.
– In the event of incompatibility or malfunctioning that was caused by product
components we did not install.
– In the event of developments that are related to the normal aging process
of the product (wear parts).
– In the event of defects that were caused by external fixtures.
The warranty period for replaced and/or repaired parts as part of this warranty
expires together with the original warranty for the product.
Devices that are supplied without accessories are replaced without accessories.
The return of the device is only accepted if this is done in the original packaging.
Adira series 11
UPS Adira (10kVA, 20kVA 3/1 phase) Introduction
Adira series 12
UPS Adira (10kVA, 20kVA 3/1 phase) Introduction
1.8 Positioning
Do not install in an area in which combustible vapours arise e.g. from pet-
rol tanks, engine compartments, etc.
The UPS is designed for operation in ventilated rooms with an ambient tempera-
ture of 0° to 40°C.
If the UPS is exposed to severe and quick temperature changes, there is danger
of condensation. Before you take additional steps, an acclimatization period of
at least 2 hours is to be observed.
Never place or operate the device in a moist environment. Keep liquids away
from the device.
The UPS may not be placed in the vicinity of heat sources.
Adira series 13
UPS Adira (10kVA, 20kVA 3/1 phase) Safety Instructions
2. Safety Instructions
2.1 Introduction
The UPS is a device that has been produced according to the rules and regula-
tions of technology for an uninterruptible power supply.
The device is safe when used properly and under consideration of the safety re-
quirements and instructions provided in this operating manual.
The UPS and its related components may only be used for purposes in accor-
dance with its design – to provide a short-term supply for electrical devices (230
V AC) with the nominal power not exceeding the total.
Any other use is considered improper and can lead to personal injury or damage
to the device!
Improper Use:
The device is not designed for use in
– explosive,
– dusty,
– radioactive or
– biologically or chemically contaminated atmospheres!
Adira series 14
UPS Adira (10kVA, 20kVA 3/1 phase) Safety Instructions
Adira series 15
UPS Adira (10kVA, 20kVA 3/1 phase) Safety Instructions
2.5 Connection
The UPS is connected via the connection terminals on the back of the de-
vice. The PE (protective earth conductor) must be connected without fail.
The device may not be used without the PE under any circumstances.
Keep the cable length as short as possible.
Adira series 16
UPS Adira (10kVA, 20kVA 3/1 phase) Safety Instructions
2.6 Operation
Before the appliances are connected to the outlet, the basic configuration must
be completed. Especially the output voltage is of high importance regarding the
appliances.
The UPS-system contains an energy storage (accumulators). This means that
the outlet can be current-carrying even when the UPS is not connected to the
mains input terminal.
To completely shut-down the UPS, first disconnect the mains connection and
then hold the "OFF" button pressed for more than 3 seconds. Wait for the UPS
to turn off, before disconnecting the power connection (feeder cable between
the UPS and the appliance). Ensure that no liquids or foreign matter enters the
UPS. Avoid a constant load of more than 80% on the output to protect the UPS.
The displayed output load should only be taken as a reference point, separate
measuring is necessary to determine the exact output load.
Adira series 17
UPS Adira (10kVA, 20kVA 3/1 phase) Safety Instructions
Adira series 18
UPS Adira (10kVA, 20kVA 3/1 phase) UPS Device Description
Adira series 19
UPS Adira (10kVA, 20kVA 3/1 phase) UPS Device Description
Adira series 20
UPS Adira (10kVA, 20kVA 3/1 phase) UPS Device Description
3.1.1 LCD-Display
1 Status-Display
2 LCD-Display
3 "Select"-button
4 "Menu Down/Next"-button
5 "Menu Up/ Back"-button
6 "ON/ OFF"-button
The back-lighting of the LCD-Display changes its colour depending on the de-
vice status.
Colour Meaning
Adira series 21
UPS Adira (10kVA, 20kVA 3/1 phase) UPS Device Description
Adira series 22
UPS Adira (10kVA, 20kVA 3/1 phase) UPS Device Description
1 power-on mode △ △ △ △
(activation)
2 bypass mode ★ ↑
(without output)
3 bypass mode ● ↑
(with output)
4 line mode ● ↑
(line-mode)
5 battery mode ● ● ↑
6 battest mode △ △ △ △
(battery test
mode)
7 HE mode ● ● ↑
(high efficiency
mode)
8 warning ↑ ↑ ↑ ★
9 fault mode ↑ ●
Remarks:
●: permanently lit
★: flashing
Adira series 23
UPS Adira (10kVA, 20kVA 3/1 phase) UPS Device Description
3.1.3 Button
Selection
Functions:
Functions:
By pushing the button for about one second you can scroll
through the currently active menu.
Back:
Push this button for about one second to switch to the next higher menu or
to go back step by step.
ON / OFF
Functions:
By pushing this button you can turn the device on or off.
If you push this button while you are in the main menu, the display will
switch to the standard display.
Adira series 24
UPS Adira (10kVA, 20kVA 3/1 phase) UPS Device Description
Adira series 25
UPS Adira (10kVA, 20kVA 3/1 phase) UPS Device Description
321 5
6 4
10
9 11
1 USB-port
2 RS 232
3 "EPO"-port
4 Communication interface („Intelligent Slot“)
5 Parallel port
6 AS 400-port
7 Connection terminals mains-input and UPS-output
8 Circuit Breaker mains-input
9 Feedback protection
10 Fan
11 Bypass switch
Adira series 26
UPS Adira (10kVA, 20kVA 3/1 phase) UPS Device Description
321 5
6 4
10
9 11
1 USB-port
2 RS 232
3 "EPO"-port
4 Communication interface („Intelligent Slot“)
5 Parallel port
6 AS 400-port
7 Connection terminals mains-input and UPS-output
8 Circuit Breaker mains-input
9 Feedback protection
10 Fan
11 Bypass switch
Adira series 27
UPS Adira (10kVA, 20kVA 3/1 phase) UPS Device Description
1 Fuses
2 UPS Connection
Fig. 3-5 Back panel external battery bank for 10 & 20 kVA 3/1-phase
Adira series 28
UPS Adira (10kVA, 20kVA 3/1 phase) UPS Device Description
3.3 Components
3.3.1 RS232/USB ports
These ports serve to connect the UPS to a PC. A simultaneous use of the USB
and the RS232 interface is not possible.
3.3.2 EPO-port
The EPO-port serves for an emergency shut-down of the connected appliances.
This function can be used to shut down connected appliances in the case of an
emergency.
The EPO-port may not be connected to circuits that are directly connected with
the mains power supply.
Adira series 29
UPS Adira (10kVA, 20kVA 3/1 phase) UPS Device Description
3.3.4 AS400
After unscrewing the cover, the AS400 extension card can be installed.
Adira series 30
UPS Adira (10kVA, 20kVA 3/1 phase) UPS Device Description
1 16
2 15
3 14
4 13
5 12
6 11
7 10
8 9
3.3.9 Fan
Fan to cool the device.
Adira series 31
UPS Adira (10kVA, 20kVA 3/1 phase) Storage and Unpacking
Adira series 32
UPS Adira (10kVA, 20kVA 3/1 phase) Storage and Unpacking
Remove the packaging following the sequence illustrated in Fig. 4-1 to Fig. 4-4.
Tools
Phillips screw-
Lifter
driver
Wrench –
Scissors
Spanner
Adira series 33
UPS Adira (10kVA, 20kVA 3/1 phase) Storage and Unpacking
Adira series 34
UPS Adira (10kVA, 20kVA 3/1 phase) Storage and Unpacking
The shipping materials are recyclable. After unpacking, save them for later use
or dispose of them appropriately.
Inspect the appearance of the UPS to see if there was any damage in-
curred during transportation. Do not turn on the unit and notify the carrier
and dealer immediately if there is any damage or if any parts are missing.
Adira series 35
UPS Adira (10kVA, 20kVA 3/1 phase) System Description
5. System Description
The UPS runs in continuous operation according to the double converter princi-
ple. It serves for the processing of the mains current and provides an uninterrup-
tible and interference-free one-phase voltage for operations critical appliances.
In addition to providing power to the appliance, it also maintains the internal ac-
cumulators in charged condition. In the case of a mains failure or interference,
the UPS continues to provide a clean supply voltage from the UPS-output with-
out interruption. During the backup mode, power is provided from the accumula-
tors.
On-line UPS
The block diagram visualizes the individual modules of the device and illustrates
their interaction.
Adira series 36
UPS Adira (10kVA, 20kVA 3/1 phase) System Description
If a mains failure continues beyond the backup time of the UPS, the UPS shuts
down to avoid a total discharge of the accumulators. As soon as the mains
power supply returns, the UPS automatically turns on again, supplies electricity
to the appliance and controls the charging of the battery bank.
Prominent performance features of the UPS are:
– No interruption or signal change when the primary mains supply fails.
– Perfect sine-wave voltage on the UPS-output.
– Process controlled bypass mode.
– "Power Factor“ correction on the input side (> 0,99).
– LCD-Display for status and operation data display.
– Outstanding performance factor of 0.9.
– Efficient and extensive communication interfaces.
– USB standard
– Emergency stop contact "EPO" standard
Adira series 37
UPS Adira (10kVA, 20kVA 3/1 phase) UPS Installation and Connection
The system may only be installed and connected by trained authorized elec-
tricians in accordance with respective safety rules and regulations!
Adira series 38
UPS Adira (10kVA, 20kVA 3/1 phase) UPS Installation and Connection
Do not use a wall socket as input power source for the UPS, as its nominal
current is below the maximal input current of the UPS. The wall socket could
burn and get destroyed.
Connect the input and output cables with the respective input and output
terminals.
The protective earth conductor refers to the cable connection between
the parts that consume electric energy and the earth wire. The cable di-
ameter of the protective earth wire should at least have the measure-
ments mentioned above for cables for the individual models and a yellow
and green striped wire is to be used.
Check after completing the installation, if all the wiring is correct.
Please install the output circuit breaker between the output terminal and
the load, and the circuit breaker should be equipped with a fault current
protective function, if that is required.
To connect the load with the UPS, first switch off all loads, then establish
the connections and then switch the loads on again, one after the other.
Adira series 39
UPS Adira (10kVA, 20kVA 3/1 phase) UPS Installation and Connection
When connected with a USB-cable, the software can exchange data with the
UPS. The software collects detailed information about the status of the power
supply from the UPS. In the case of a supply emergency, the software en-
sures that all data is saved and all appliances are shut down properly.
Adira series 40
UPS Adira (10kVA, 20kVA 3/1 phase) UPS Installation and Connection
Leave the EPO-plug installed on the EPO-port of the UPS even if the EPO-
function is not needed.
Adira series 41
UPS Adira (10kVA, 20kVA 3/1 phase) UPS Installation and Connection
Adira series 42
UPS Adira (10kVA, 20kVA 3/1 phase) UPS Installation and Connection
Adira series 43
UPS Adira (10kVA, 20kVA 3/1 phase) UPS Installation and Connection
Operation
Reset
To reset the feedback logic, the UPS-system has to be turned off for a few
seconds.
Adira series 44
UPS Adira (10kVA, 20kVA 3/1 phase) Operation
7. Operation
7.1 Operation of the UPS
The operation of this equipment is characterized by various operating modes
and signals.
230 V
232 V
228 V
50 HZ
Fig. 7-1 line mode
Battery mode
In the event of a mains failure, the UPS switches to battery mode.
The display for battery mode looks as follows:
Adira series 45
UPS Adira (10kVA, 20kVA 3/1 phase) Operation
Bypass mode
The UPS switches into bypass mode e.g. when there is an inverter problem.
The mains input and power output are bypassed via a relay.
The display for bypass mode looks as follows:
Adira series 46
UPS Adira (10kVA, 20kVA 3/1 phase) Operation
In HE-mode the UPS is initially in bypass mode. The inverter is only activated in
the event of a mains failure. This results in a brief switch-over time in the milli-
second range.
The display for HE-mode looks as follows:
Converter mode
In converter mode the frequencies of the input and output can be configured.
The display for converter mode looks as follows:
230 V
232 V
228 V
50 HZ
Adira series 47
UPS Adira (10kVA, 20kVA 3/1 phase) Operation
Warning
In general, warnings are no fatal faults, but should be fixed as quickly as possi-
ble.
The UPS continues to operate when a warning occurs.
If there are any warnings pending at the UPS, the display looks as follows:
230 V
232 V
228 V
50 HZ
Fault
230 V
232 V
228 V
50 HZ
Adira series 48
UPS Adira (10kVA, 20kVA 3/1 phase) Operation
Other signals
230 V
232 V
228 V
50 HZ
230 V
232 V
228 V
50 HZ
Adira series 49
UPS Adira (10kVA, 20kVA 3/1 phase) Operation
If a fault is detected in the battery like e.g. "battery not connected" or "poor bat-
tery status", the display looks as follows:
230 V
232 V
228 V
50 HZ
Adira series 50
UPS Adira (10kVA, 20kVA 3/1 phase) Operation
Adira series 51
UPS Adira (10kVA, 20kVA 3/1 phase) Operation
230 V
232 V
228 V
50 HZ
Adira series 52
UPS Adira (10kVA, 20kVA 3/1 phase) Operation
Button Description
The description of this button can be found in chapter 3.1.2
Buttons.
The description of this button can be found in chapter 3.1.2
Buttons.
The description of this button can be found in chapter 3.1.2
Buttons.
The description of this button can be found in chapter 3.1.2
Buttons.
Parameters Description
Display "Alarm" The status messages menu displays the latest error messages
listed together with the count of the operating hours counter, the
alarm code and the plain text of the error message.
Display "Battery voltage The menu displays the condition of the battery.
and Load Status"
Display "Status and The menu displays the operating mode and the hours of operation
Running time" of the UPS. The value Para Num shows how many devices are
connected in parallel.
Adira series 53
UPS Adira (10kVA, 20kVA 3/1 phase) Operation
7.3 Menu
7.3.1 UPS status menu
230 V
232 V
228 V
50 HZ
Parameters Description
Display "Alarm" The status messages menu displays the latest error messages
listed together with the count of the operating hours counter, the
alarm code and the plain text of the error message. For further
details on fault warnings see chapter 8.
Display "Battery voltage The menu displays the condition of the battery.
and Load Status"
Display "Status and The menu displays the operating mode and the hours of operation
Running time" of the UPS. The value Para Num shows how many devices are
connected in parallel.
Adira series 54
UPS Adira (10kVA, 20kVA 3/1 phase) Operation
230 V
232 V
228 V
50 HZ
Parameters Description
Display "Event Log" The menu displays up to 50 warning / fault messages and re-
sults. In the event of more than 50 entries, the old entries will be
over-written.
Adira series 55
UPS Adira (10kVA, 20kVA 3/1 phase) Operation
230 V
232 V
228 V
50 HZ
Bypass Input
xxx V xx Hz
Adira series 56
UPS Adira (10kVA, 20kVA 3/1 phase) Operation
Parameters Description
Display "Output" Displays the power output of the UPS.
Left value = active power
Right value = apparent power
Display "Output" Displays the output current of the UPS.
Left value = output current
Right value = output current in % percent
Display "Output" Displays the output voltage of the UPS.
Left value = output voltage
Right value = output frequency
Display "Input" Displays the input phases.
Display "Battery" Displays the battery voltage and the charging status of the UPS.
Display "DC Bus" Displays the DC bus voltage of the UPS.
Display "Temperature" Displays the temperature of the UPS.
Adira series 57
UPS Adira (10kVA, 20kVA 3/1 phase) Operation
230 V
232 V
228 V
50 HZ
Adira series 58
UPS Adira (10kVA, 20kVA 3/1 phase) Operation
Adira series 59
UPS Adira (10kVA, 20kVA 3/1 phase) Operation
Adira series 60
UPS Adira (10kVA, 20kVA 3/1 phase) Operation
230 V
232 V
228 V
50 HZ
Type / Model:
Tower
3/1 10000 VA
Online
Parameters Description
Display "Type / Model" Displays the UPS type / model.
Display "Serial number" Displays the UPS's serial number.
Display "UPS firmware" Displays the current UPS firmware.
Adira series 61
UPS Adira (10kVA, 20kVA 3/1 phase) Operation
230 V
232 V
228 V
50 HZ
Adira series 62
UPS Adira (10kVA, 20kVA 3/1 phase) Operation
Adira series 63
UPS Adira (10kVA, 20kVA 3/1 phase) Operation
Adira series 64
UPS Adira (10kVA, 20kVA 3/1 phase) Operation
Adira series 65
UPS Adira (10kVA, 20kVA 3/1 phase) Troubleshooting
8. Troubleshooting
If the UPS system does not operate correctly, first check the operating infor-
mation on the LCD display.
Please attempt to solve the problem using the table below. If the problem still
persists, consult your dealer.
Adira series 66
UPS Adira (10kVA, 20kVA 3/1 phase) Troubleshooting
Error code: 19 CAN Communication fault Make sure the parallel port is
Adira series 67
UPS Adira (10kVA, 20kVA 3/1 phase) Troubleshooting
When you contact the service centre, please provide the following informa-
tion:
Model number, serial number.
Adira series 68
UPS Adira (6kVA, 6kVA XL, 10kVA, Software
10kVA XL 1-phase)
9. Software
With a suitable software package the configurations and operating statuses of
the UPS can be determined and processed via the communication interface.
The software packages are available from the manufacturer / dealer or through
the service hotline. Through these channels you can receive useful information
about the suitable software packages for your UPS to fit your needs.
See also our website:
http://www.effekta.com/
In the chapter "Scope of Delivery / (Optional) Accessories" you will find suitable
and tested software packages.
Adira series 69
UPS Adira (10kVA, 20kVA 3/1 phase) Maintenance and Service
At an ideal ambient temperature of about 22°C, the service life of the accumula-
tors
is typically around 4 years. Through the use of special
accumulators the service life can be significantly increased (about 8-10 years).
You should check periodically (every 6 - 12 months) whether the remaining
backup time is sufficient for the intended purposes. Once that is no longer the
case, the accumulators have to be replaced.
Before you begin this procedure, please make sure to save all open data. Fur-
thermore, inform all affected employees.
Basically there are two different methods for measuring the back-up time.
Method a)
measures the actual back-up time, which means that at the end of that backup
time the appliances would be without a power supply.
Method b)
allows to determine the residual capacity after a defined backup-period. In this
case the appliances will usually not be without power in the end.
To use either method, you have to force the UPS into backup mode, by simulat-
ing a mains failure (e.g. trip the fuse of the building). Do not, under any circum-
stances, remove the mains connection, as that would also disconnect the pro-
tective earth conductor. After the measurement has been carried out, turn the
circuit breaker back on and turn on the UPS as usual, with the ON-button.
Adira series 70
UPS Adira (10kVA, 20kVA 3/1 phase) Maintenance and Service
Remember that after the measuring the accumulators of the system will be dis-
charged. I.e. the UPS-system must operate in line mode or charging mode re-
spectively for several hours (min. 5 h), before it will again be operational at
about 80% capacity.
Adira series 71
UPS Adira (10kVA, 20kVA 3/1 phase) Maintenance and Service
10.3 Service-Log
Please always enter all maintenance and service work conducted on the UPS
into the service-log.
Adira series 72
UPS Adira (10kVA, 20kVA 3/1 phase) Maintenance and Service
10.4 Service-Hotline
If unexpected problems occur with the photovoltaic solar inverter or you need
safety information, please contact our service hotline by phone or fax:
ups@effekta.com
In addition you can contact the central area or branch office directly as listed on
our website:
http://www.effekta.com/html/kontakt.html
You can find the complete range of our services on-line at:
http://www.effekta.com/html/service.html
or contact us directly at the addresses given above.
Adira series 73
UPS Adira (10kVA, 20kVA 3/1 phase) Technical Data
Phase 3 to 1
Voltage 176~276VAC
Output
Voltage 200/208/220/230/240VAC*
45A/48,1A/45,5A/43,5A/4 90A/96,2A/90,9A/87A/83,
Current
1,7A 3A
50/60Hz ±10% in line mode
Frequency 50/60Hz ±0,1% of the normal frequency in
battery mode
Wave form sine wave
< 2% @ full linear load
THDV
<5% @ full non linear load
In Line mode**:
10 min 105~125%
1 min 125~150%
10 s >150%
Overload 100 ms >170%
In Battery mode:
2 min 105~125%
30 s 125~150%
100 ms >150%
*The load capacity is limited to 90% automatically, if the output voltage is set at
200 VAC.
Adira series 74
UPS Adira (10kVA, 20kVA 3/1 phase) Technical Data
Battery banks
Voltage 288VDC
Type and number of
24× 12V 9Ah 2x24× 12V 9Ah
batteries
Charging rate of a
33,6A 67,2A
battery pack
Environment
Maximum performance 100% 95% 91% 86% 82% 78% 74% 70% 67%
Standards
Safety EN 62040-1:2008
EMV EN 62040-2:2006
Adira series 75
UPS Adira (10kVA, 20kVA 3/1 phase) Scope of Delivery /
(Optional) Accessories
Adira series 76
UPS Adira (10kVA, 20kVA 3/1 phase) Scope of Delivery /
(Optional) Accessories
** For the wear part description of the accumulators please see the assembled
accumulators, or on contact us.
Adira series 77
13. Conformity Declarations
13.1 Adira 3/1 10kVA
UPS Adira (10kVA, 20kVA 3/1 phase) Notes
Adira series 79
EFFEKTA Regeltechnik GmbH
Rheinwaldstraße 34
D – 78628 Rottweil