P O W E R I N G T E C H N O L O G Y
DC DISTRIBUTION PANELS
16 Pluggable Breakers & Dual 150A Inputs
DESCRIPTION
UNIPOWER’s DPP1U Series of circuit breaker
panels provide distribution and overload
protection for 1 to 16 circuits with circuit
breakers that can be field installed/exchanged
without the need for any additional tools. The
panels are only one mounting position (1.75
inches) high.
www.unipowerco.com
NORTH AMERICA CALL: +1-954-346-2442 • EUROPE CALL: +44 1903 768200
DPP1U SERIES DC POWER DISTRIBUTION UNITS - 2
P O W E R I N G T E C H N O L O G Y
SPECIFICATIONS
Typical at 25oC Unless Otherwise Noted.
INPUT/OUTPUT ENVIRONMENTAL
Input/Output Ratings........................................................... 150A Max. @ 40°C, each side A & B Operating Temp. Range.......................................................................................................-10°C to +70°C
.125A Max. @ 50°C, each side A & B
Storage Temp. Range...........................................................................................................-40°C to + 85°C
.50A Max. @ 70°C, each side A & B
Humidity..................................................................................................... 0% to 95%, Non-Condensing
.See manual for details on CB deratings
Configuration........................................................................ 150A Single Bus with 1 to 16 Breakers
PHYSICAL SPECIFICATIONS
.300 A Dual Bus 1 to 8 Breakers Each Bus
Case Material.......................................................................................................................................................Steel
Breaker Capacity 1 ...............................................................................................................................1A to 30A
Finish...................................................................................................................................... Powder Coat Black
Voltage 1
Case Dimensions, Inches (mm)...............................................................1.74 H x 17.12 W x 8.94 D
24/48V Version................................................................................................................................. 21-60VDC
.(44.2 x 434.9 x 227.1)
12V Version.......................................................................................................................................10.5-15VDC
Weight................................................................................................................................... 10.30 lbs. ( 4.67 kg.)
Polarity .....................................................................................Neutral, Positive or Negative Ground
Rack Mounting............................................................................................................................. 19 or 23 Inch
ALARMS
CONNECTIONS
Alarm Indicator ...................................................................................................Dual Color LED Per Bus
Input Connections............................................................................Crimp Type Lug or ¼ - 20 Stud
LED Status Indication........................................................................................................ Green = Normal
Output Connections.................................................................... Barrier Terminal Strips, No. 6-32
..Red = CB Trip Alarm
Chassis Ground Connection...............................................................................................No. 8-32 Stud
Off = No Power
Alarm Relay Connections.................................................Spring Clamp Terminals,16-26AWG
Alarm Relays...........................................................................................Form C Contacts for each Bus
Notes:
SAFETY..............................................................UL60950-1 2nd Ed., CSA22.2 No. 60950-1 2nd Ed.,
1. See ordering guide to specify.
EN60950-1 2nd Ed.
FRONT VIEW
17.12 (434.9)
150A MAX PER BUS 150A MAX PER BUS
ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON
I I I I I I I I I I I I I I I I 1.74
O O O O O O O O O O O O O O O O
OFF OFF OFF OFF OFF OFF OFF OFF
ALARM OFF OFF OFF OFF OFF OFF OFF OFF (44.2)
A B
1 8 1 8
A Side Breakers Alarm LEDs B Side Breakers Case depth: 8.94 (227.1)
2.28
REAR VIEW (57.8)
ALM B ALM A
BAT BAT BAT BAT
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
NO-C-NC NO-C-NC
0.34” 0.65”
0.5”
0.32”
1.48”
Connectors are Phoenix Contact spring clamp type.
Crimp Lugs for input bus bars should be ordered Wires (16-26AWG) do not require any termination.
separately.
For a kit of 4 two-hole lugs for no. 6 AWG wire order
pt. no. 775-1434-0000.
NOTE: Single feed models DPP1U-A1-B1-S and DPP1U-A6-B6-S have both left and right side input bus bars fitted.
It is only necessary to connect the input feed to one side for correct operation.
dpp1u-ds-revG-0917.indd
The unused side is directly connected to the live input feed and can be used for supplying additional panels.
The total load must not exceed 150A on any one pair of bus bars in the chain.
UNIPOWER LLC • 3900 Coral Ridge Drive, Coral Springs, Florida 33065, USA • sales@unipowerco.com
North America: +1 954-346-2442 • Europe: +44 1903 768200