Académique Documents
Professionnel Documents
Culture Documents
João Siqueira
Field Application Engineer
Topics
• Growing new product family for critical and essential rotating equipment
• Application based and user-defined configurations
• For monitoring applications requiring high reliability and availability
• Bently Nevada quality and value
• Field proven, large installed base
3701 Platform: Product Overview
5
3701 Simplex Monitor Features
4-bolt/stud mount. Top holes
slotted. Cast aluminum base Dimensions:
Footprint: 178mm x 254mm (7” x 10”)
plate. Bulkhead mount. Module Height: 178mm (7”)
3701/40
3701/44
3701/46
3701/40-44-46
• Smaller Machines
• Multiple nX measurements
• EGD/Modbus
• Gearboxes support
3701/44 Aeroderivative Monitor
3701/46
• LM2500 and LM600 templates
3701/46 Hydro Monitor
3701/46
• Long alarm time delay
• Up to 5X Trip Multiply
• Cavitation Measurement
16
Comm Layout Example – 3701/40
SERVER System 1 Display System 1 Display System 1 Display
ROOM
...
Corporate Network
Ethernet
CONTROL
ROOM
Modbus
DCS
TCP/IP Firewall
(Evolution only)
Utility Network
Ethernet Relays
Emergency Shutdown System
(ESD)
3701/40
MDM
Relays
Final Shutdown
Element
Final Shutdown
TurbineElement
trip solenoids
Kph block assembly
4X 3X 2X 1X Turbine trip solenoids
4Y 3Y 2Y 1Y block assembly
Thrust – A
Motor
Turbine
Thrust - B
Gearbox
Generator 17 /
GE /
June 16, 2015
3701/55 - design and
features
Bently Nevada Asset Condition Monitoring
19 /
GE /
June 16, 2015
GE’s Bently Nevada: By the numbers
50 • 50+ years of condition monitoring experience
20 /
GE /
June 16, 2015
ADAPT ESD benefits
Mechanical overspeed upgrade and new machines
22
22/
GE /
June 16, 2015
3701/55 ESD: Overview
• Compact, robust, standalone, independent,
self-contained over-speed detection and
emergency shutdown device for most
rotating machinery types
• Triple Redundant
• Targeted specifically for API 670, API 612 and
IEC 61508 SIL3 applications
• Simple configuration and graphical logic
programming environment – Bently Nevada
Monitor Configuration software (BNMC)
• Modbus TCP for integration with unit or plant
automation systems
23 /
23 GE /
June 16, 2015
3701/55 ESD: Feature Summary
- Triple redundant processor and relay modules
- 2 sets of 3 speed inputs; magnetic pickup or proximity
probes
- 20 Isolated discrete inputs
- 12 Inputs configurable as isolated discrete or 4-20 mA
analog inputs
- Configurable trip logic
- Up to 500 logic blocks
- 2 ms logic execution time
- 8 ms relay response Form Factor
- 12 SPDT Relays Footprint: 253mm x 291mm (10.0” x 11.5”)
Height: 178mm (7”)
- 6 configurable as 2oo3 voted or 1oo1
Weight: 8.8 kg (19.4 lbs)
- 6 Independent 1oo1
- 3 independent SPDT OK/Fault relays
- Six 4–20 mA outputs (one per speed input)
- Dual Ethernet RJ45 connectors per processor module
- Bulkhead mount – front entry
- Redundant 24 VDC power
- Op Temp: -30 to +65 degC
24 /
GE /
June 16, 2015
Easy toto
Easy Configure
Configure in AESD
AESD*
in AESD
Step 2: Select
Connect functionblocks
the function blocksinputs
from &
Toolbar
outputs
Step 1: Open Editing Session
25 /
2
GE /
June 16, 2015
Comm Layout Example – 3701/40 + 3701/55
SERVER System 1 Display System 1 Display System 1 Display
ROOM
...
Corporate Network
Ethernet
CONTROL
ROOM
(Evolution only) DCS
Firewall
Modbus Modbus
TCP/IP TCP/IP
Utility Network
Generator 30 /
Overspeed GE /
transducers June 16, 2015
Release-4 New Capabilities
(Sept/15)
New Items for Release-4 (September/2015)
Power 1
+24V Processor Processor
Terminal Terminal
Power 2
Module 1 Module 2 Block Block
+24V Assembly Assembly
1 2
DCS
K X X X X X X K X X X X X X
D D D D D D D D D D D D
P C C C C C C
P C C C C C C
H R R R R R R H R R R R R R
GE Proprietary – for Internal Use Only
© 2014 General Electric Company - All rights reserved