DESIGN OF FLASH MIXER AT ARON - 4D

Density of water = 9.81 kN/m3


Density of concrete = 25 kN/m3
Density of soil = 18 kN/m3
S.B.C of Soil= 120 kN/m3

TOP LVL = 513.30 m


WSL = 512.80 m
N.G.L = 509.50 m
BED LVL = 508.50 m

L= 1 m
B= 1 m
H= 4.80 m
L/H = 0.208
MOMENT COEFFICIENT FOR WALL PANEL TOP FREE, BOTTOM & VERTICAL EDGE FIXED :
( Ref IS:3370 -Part IV)
Max Moment MH = -0.009 x 9.81 x 4.80 3 = -9.76 KNm
Max Moment MV = 0.004 x 9.81 x 4.80 3 = 4.34 KNm

a) CANTILEVERED WALKWAY DESIGN Span = 1.000 m


Let thickness = 150 mm
Self wt. = 3.750 KN/m2
LL = 5.0 KN/m2
Finishes = 1.0 KN/m2
Total Load = 9.750 KN/m2
M= 5.88 KNm
Duncracked = 67.23 mm
Provide ,Doverall = 150 mm deff = 120 mm
Ast = 235.47 mm 2

Dia. Of Bar used = 10 mm Astbar = 78.525 mm2


Spacing required = 333.485985 mm
Spacing Provided = 150 mm
Provide 10 mm dia @ 150 c/c as main bars & 8 mm dia @150 c/c as d/s bars.
Design Moment = 10.21 KNm
DESIGN OF TANK WALLS
For no crack section
Overall Depth of section required
D2= M*6*106/2.0*103
D= 175.1 mm
Provide D= 200 mm
d = 181 mm

AstV = 10.21 x 10 6 = 504.8 mm2


130 x 0.86 x 181
Provide 10mm dia @150 c/c vertically on inner face.

AstH = 9.76 x 10 6 = 482.52 mm2


130 x 0.86 x 181
Provide R/F 10 mm dia @ 150 c/c horizontally on both faces
Pr. At base lvl. due to earth= 9.81 x 1.00 + (18-9.81) x 1.000 x.333 = 12.54
Max BM = 0.0040 x 12.54 x 1.000 =2
0.05 KNm
Ast min = 0.24 x 200 x1000/100 = 480 mm2 (on both faces)
Provide R/F 8mm dia @ 175 c/c vertically on outer face.

BASE SLAB
Let thickness of base slab = 300 mm
Projection all around = 200 mm
Area of Base slab = 3.24 m2
length of salb = 1m
LOAD CALCULATONS
Due to Base slab = 0.300 x 25 = 7.50 kN/m2
Due to wt. of soil over base slab = 0.5 x 18 = 9.0 kN/m2
due to weight of water inside = 4.80 x 10 = 48.0 kN/m2
Total load = 64.50 kN/m2

considering as interior pannel : Ly/Lx = 1

Negetive moment at continuous edge = 2.064 kNm


Duncrack = 78.689 mm
Dprovided = 300 mm deff. = 250 mm
Astrequired = 78.40 mm2
Provide 8 mm dia. @150 c/c squiremesh.

DESIGN OF BASE BEAM :


Size Of Beam = 300 x 300 mm
c/c Length of beam = 1.3 m
Height of wall Above Beam= 3.00 m
Loads due to wall= 0.2 x 3 x 25 = 15 kN/m
Self weight of Beam= 0.3 x 0.3 x 25 = 2.25 kN/m
Load from Slab = 21.5 kN/m
Total Loads = = 38.75 kN/m

Muat support= 5.457 kNm


Muat midspan= 2.73 kNm
drequired = 233.6 mm
Doveral = 300 mm deff, provided = 250 mm
Astreq. = 207.30 mm2
Provide 12 mm dia bar. Astb = 113.076 mm2
Provided 3 nos of 12 mm dia bar equially distributed
Provided 8 mm dia bar @150 mm c/c as stirrup
Load on Column- C1
Load transferred by beam = 38.75 x 1.300 = 50.37
Self Wt. of Column = 0.3 x 0.3 x 2.8 x 25 = 6.3
Total Load = 56.67 kN
Total Wt. at the base of each col. = 56.67 kN
Checking of Slenderness ration of column
use longitudinal Bar= 12 mm
L= 2.8 m least lateral dimension= 192 mm
l= 2.24 m or, 300 mm
Slenderness Ratio= 7.47 < 12 we take 300 mm
(hence it is Short Column)

Assume Column SIZE = 300 x 300


Provide col. Size of dia. 300 mm with 8 - 12 mm dia bars
Ties : 8mm dia @ 100 c/c upto h/6 dist. from each support +rest @ 150 c/c

Load carrying capacity of sugg. size= (From IS 456 : 2000 cl B-3.1)


= 830362 N σ cc = 8 N/mm2 (M30)
= 830.36 kN > 56.7 kN σ sc = 130 N/mm2 (Fe500)
SAFE
KN/m2
kN
kN
DESIGN OF COMBINED FOOTING-FLASH MIXTURE-ARON
300 x 300 mm Fe 500
COLUMN SIZE
300 x 300 mm M 30
COLUMN LOADS :
P1 = 56.67 kN
P2 = 56.67 kN
Self Weight (10%) 11.335 kN
Total Load (P) 124.685 kN
S.B.C 120 (kN/m2)
Footing Area required 1.14 m2 Width 1.00 m
Provided Area 2 O.K Length 2.00 m
Net upward Pressure 62.34 kN/m2 62.34 kN/m2
SAFE <SBC

56.675 56.675
c c

0.4

1.00 m
0.3

0.4

CO CO
0.35 1.30 0.35

2
DESIGN OF FOOTING SLAB :
Span(L) = 0.4 m
Bending Moment = 3.82 kn-m
Depth Required = 107 mm

Provide D = 200 mm
Effective Depth = 150 mm
Ast Required = 241.75 mm2
Ast Minimum = 240 mm2
Provide Reiforecement = 10 mm dia bar
Ast of each bar = 78.5 mm2
Spacing Required = 324.71248 mm
Spacing Provided = 200 mm
Provided 10mm dia bar @200 mm c/c & 3 Nos 8 mm dia bar each side of beam as distribution Bar.
DESIGN OF FOOTING BEAM-FB-1:
Span L 1.30 m
B D
Beam of size 300 300 mm

Provided Load due to


Cantilever Slab 44 kN/m
Bending Moment= 6.15 kN-m

Depth Required= 106.7 mm


Depth provide = 300 mm
Effective Depth= 250 mm
Ast Required= 233.463683 mm2

PROVIDE 3-12 mm dia at top & at bottom of beam.


PROVIDE stirrups 8 mm dia. 2 L @ 100 c/c throughout

Check For One - Way shear :


Shear force F =po (a-.142) = 12.97 kN

τv =V/bd = 12967.24 = 0.086 N/mm2


1000 x150
p= Ast x 100 = 0.262 %
bd
For M-30 ,Permissible shear stress,τc = 1x 0.238 = 0.238 N/mm2
As τv < τc SAFE