L= 1 m
B= 1 m
H= 4.80 m
L/H = 0.208
MOMENT COEFFICIENT FOR WALL PANEL TOP FREE, BOTTOM & VERTICAL EDGE FIXED :
( Ref IS:3370 -Part IV)
Max Moment MH = -0.009 x 9.81 x 4.80 3 = -9.76 KNm
Max Moment MV = 0.004 x 9.81 x 4.80 3 = 4.34 KNm
BASE SLAB
Let thickness of base slab = 300 mm
Projection all around = 200 mm
Area of Base slab = 3.24 m2
length of salb = 1m
LOAD CALCULATONS
Due to Base slab = 0.300 x 25 = 7.50 kN/m2
Due to wt. of soil over base slab = 0.5 x 18 = 9.0 kN/m2
due to weight of water inside = 4.80 x 10 = 48.0 kN/m2
Total load = 64.50 kN/m2
56.675 56.675
c c
0.4
1.00 m
0.3
0.4
CO CO
0.35 1.30 0.35
2
DESIGN OF FOOTING SLAB :
Span(L) = 0.4 m
Bending Moment = 3.82 kn-m
Depth Required = 107 mm
Provide D = 200 mm
Effective Depth = 150 mm
Ast Required = 241.75 mm2
Ast Minimum = 240 mm2
Provide Reiforecement = 10 mm dia bar
Ast of each bar = 78.5 mm2
Spacing Required = 324.71248 mm
Spacing Provided = 200 mm
Provided 10mm dia bar @200 mm c/c & 3 Nos 8 mm dia bar each side of beam as distribution Bar.
DESIGN OF FOOTING BEAM-FB-1:
Span L 1.30 m
B D
Beam of size 300 300 mm