Académique Documents
Professionnel Documents
Culture Documents
I n = 1A 5A ( I 2 ) 2
f n = 50Hz I n = 1A 5A ( I 01 )
5
n STEP
80...265 V – 1 /n RESET
~
18...80 V –
2tp I n 02 / n
t >> [ s ]
2f / 1f 02
In
2 3 I >> Trip 2 I 01 > Trip 2 I > Trip 1 1 / n
>[ ]
In
2 2 / n
0029A
0021A
0023A
0199A
RS 621 Ser.No.
1MRS 750096-MUM EN
SPAD 346 C
Issued 1996-08-08
Modified 2002-04-12 Stabilized
Version F (replaces 34 SPAD 5 EN1)
Checked MK
Approved OL
Differential Relay
Data subject to change without notice
Contents Features
...................................................................................................................... .... 3
Application ........................................................................................
............................. 4
Description of function
.................................................................................................. 4
Three-phase stabilized differential relay module SPCD 3D53
................................... 4
Earth-fault relay module SPCD
2D55 ....................................................................... 6
Combined overcurrent and earth-fault relay module SPCJ
4D28 .............................. 8
Connection diagram
.......................................................................................................
9
Connections .......................................................................................
.......................... 10
Control input and output relay module
........................................................................ 11
Intermodular signals (modified 1997-10)
...................................................................... 12
Power supply module
................................................................................................... 13
Operation indicators
.....................................................................................................
14
Technical data (modified 2002-04)
............................................................................... 15
Recommendations for current transformers
.................................................................. 18
Circuit-breaker control
................................................................................................. 20
Application examples
.................................................................................................... 21
Setting instructions
.......................................................................................................
25
Commissioning ..................................................................................
.......................... 28
Testing .............................................................................................
............................ 28
Maintenance and service
............................................................................................... 33
Spare parts
........................................................................................................
............ 33
Delivery alternatives
.....................................................................................................
33
2 2
Order numbers
.........................................................................................................
.... 34
Information required with order
................................................................................... 34
Dimensioned drawings and mounting
.......................................................................... 35
Features Integrated three-phase differential relay, over- No interposing transformers are needed for the
current relay and earth-fault relay protection of two-winding transformers - nu-
merical vector group matching on HV and LV
Stabilized three-phase differential relay provid- side
ing winding short-circuit and interturn fault
protection for two-winding transformers and Wide CT ratio correction range - accurate cor-
generator-transformer units and winding rection allowed by digital setting
short- circuit protection for generators.
Sensitive phase current and phase angle
Earth-fault protection for transformer HV and displays facilitate the checking of
LV side windings according to the desired measurement circuit connection and vector
prin- ciple: the stabilized differential current group matching
princi- ple, the high-impedance principle,
the calcu- lated or measured residual current Four trip and four signal relay outputs
principle or the neutral current principle available to the protection design engineer
Three-stage overcurrent protection for trans- Five programmable external control inputs in-
formers and generators and two-stage back-up tended for the indication and retransmission
protection for earth-fault protection of alarm and trip signals of gas relays, oil
tempera- ture sensors and other sensors of
The operation characteristic of the differential transformer auxiliary devices
relay easily adapted for different applications
Adjustable CBFP operate time to improve
Short operate times, even with partially reli- ability of operation
satu- rated current transformers
Integrated disturbance recorder capable of re-
Stabilization prevents unwanted operations at cording currents and digital signals - signals to
faults outside the protected area and trans- be used for triggering selectable
former inrush currents
High immunity to electrical and electromag-
Blocking based on the ratio of the second har- netic interference allows the relay to be used
monic and the fundamental component of in severe environments
the differential current prevents unwanted
opera- tions at transformer inrush currents High availability and system reliability due to
continuous supervision of hardware and soft-
Blocking based on the ratio of the fifth har- ware
monic and the basic frequency component of
the differential current prevents operation in
harmless situations of transformer overexcitation
- can be eliminated if the ratio of the fifth
harmonic and the basic frequency component
increases at high overvoltages
Application The stabilized differential relay SPAD 346 C is against winding
designed to be used to protect two-winding short-circuit,
transformers and generator-transformer units
3 3
interturn fault, earth fault and short circuit generators against winding short-circuit and
and to protect short circuit. The relay can also be used for
the protection of a three-winding transformer
pro- vided 75% of the short circuit power is fed
from the same direction.
Description of The integrated differential relay SPAD 346 C LV side may use the same or different rated
operation includes three independent relay modules: a currents.
three-phase stabilized differential relay module
SPCD 3D53, an earth-fault relay module Below a short description of the features of
SPCD the protection relay modules. The manuals for
2D55 and a combined overcurrent and earth- the separate relay modules describe the
fault relay module SPCJ 4D28. The rated modules more in detail.
cur- rents of the relay are 1 A and 5 A. The
HV and
Three-phase The differential relay module SPCD 3D53 formers to obtain vector group matching and to
stabilized pro- vides protection for winding short- match the secondary currents of the main
differential circuit and interturn faults. The differential trans- formers. Interposing CTs have also been
relay module relay compares the phase currents on both used to eliminate the zero-sequence
SPCD 3D53 sides of the object to be protected. Should the components of the phase currents at earth
differential current of the phase currents in faults occurring outside the protected area. The
one of the phases exceed the setting of the differential current relay SPAD 346 C
stabilized operation character- istic or the eliminates the use of interposing transformers
instantaneous protection stage of the module, for the protection of two-winding
the module provides an operate signal. transformers as the differential relay module
Different amplitudes or phase difference of the allows the transformer vector group matching,
currents may be the reason for the differential the CT ratio correction and the elimination of
current. the zero-sequence component of the phase
cur- rents to be digitally implemented on the
Interposing current transformers have HV and/or the LV side.
normally been used in the differential
protection of trans-
Stabilized
differential or transformer inrush situations. Due to these
current stage In power transformer protection differential circumstances the operation of the differential
current is caused by CT errors, varying tap relay has been stabilized in respect of the load
changer positions, transformer no-load current, current. In a stabilized differential relay the
transformer inrush currents, transformer differential current required for relay
overexcitation in overvoltage and underfre- operation is higher, the higher the load
quency situations, and CT saturation at high current is. The stabilized operation
currents passing through the transformer. Dif- characteristic of the differ- ential relay module
ferential current caused by CT errors and tap- and the setting range of the characteristic is
changer position grows at the same per cent presented in the description of the differential
ratio as the load current increases. In the relay module SPCD 3D53.
protection of generators the differential
current is caused by CT errors and saturation The operation of the differential relay module
of the CTs in situa- tions where high SPCD 3D53 is based on the fundamental fre-
currents pass through the transformer. quency components. Operation based on fun-
damental frequency components is accurate
High currents passing through the object to be and stable: the DC component and harmonics
protected may be caused by short circuits out- of the current do not cause unwanted operation
side the protected area, large currents fed by of the protection stage.
the transformer or the generator in motor
start-up
Blocking based Transformer magnetizing inrush currents occur ferential current, which would cause the relay to
on the second har- when energizing the transformer after a period operate almost always when the transformer is
monic of the differen- of deenergization. The inrush current may be connected to the network. Typically, the inrush
tial current many times the rated current and the halving current contains a large amount of second har-
time may be up to several seconds. To the monics. Blocking of the operation of the stabi-
differential relay inrush current represents dif- lized stage of the relay at magnetizing inrush
4 4
current is based on the The blocking also prevents unwanted the protected transformer already connected to
ratio of the operation at recovery and sympathetic the network, being energized.
amplitudes of the magnetizing in- rush. At recovery inrush the
second harmonic magnetizing cur- rent of the transformer to The connection of the power transformer
digitally filtered from be protected increases momentarily when the against a fault inside the protected area does
the differential voltage returns to nor- mal after clearance of not delay the operation of the relay module,
current and the a fault outside the pro- tected area. because in such a situation the blocking
fundamental fre- Sympathetic inrush is caused by a based on the second harmonic of the
quency Id2f/Id1f. transformer, which runs in parallel with differential current is prevented by a separate
algorithm based on the waveform and the rate
of change of the differen- tial current.
Blocking based on Inhibition of relay operation in situations of matically eliminated by a separate blocking in-
the fifth harmonic of overexcitation is based on the ratio of the hibiting setting Id5f/Id1f>>. When required,
the differential fifth harmonic and the fundamental the blocking based on the second and fifth
current component of the differential current har- monic of the differential current can be
Id5f/Id1f. At dangerous levels of overvoltage disa- bled.
which may cause damage to the transformer,
the blocking can be auto-
Numerical stabilized The numerical differential current stage oper- The relay measures a differen- tial current as
differential current ates exclusively on earth faults occurring in the the difference between the re- sidual current
principle protected area, i.e. in the area between the of the phase currents and neutral current. An
phase CTs and the CT of the neutral external stabilizing resistor is not required.
connection. An earth fault in this area (See application example 1)
appears as a differential current between the
residual current of the phase currents and At an earth fault in the protected area the phase
the neutral current of the conductor between difference between the residual current of the
the star point of the trans- former and earth. phase currents and the neutral current is greater
5 5
than 90 , i.e. the protected so that the higher the average of the ate limit, an earth-fault has occurred in the
directions of the phase currents on the concerned side the protected area and the relay operates when the
residual current and higher is the differential current required for preset operate time has elapsed. Such a
the neutral current starting. situation may arise when the transformer is
are towards the connected to the network on the HV side
protected area. In the Should the residual current of the phase against an internal earth fault on the LV side.
calculation of the currents be zero the neutral current exceeding So, in this situation the LV side protection
differen- tial current the oper- will operate.
the directions of the
residual current and When the numerical stabilized differential cur-
the neutral current rent principle is used the ratio of the neutral
are so weighted that current and the residual current of the phase
operation is possible currents must be greater than the setting I01/
only if the phase I1 on the HV side and greater than the setting
difference between I02/ I2 on the LV side to allow starting of the
the residual current earth-fault protection on the respective side.
of the phase cur- The settings secure the selectivity of the
rent and neutral protec- tion taking into account the
current exceeds 90 . distribution of the earth-fault current
The smaller the between the transformer neutral and the
phase difference, i.e. network. The distribution of the earth-fault
the closer it is to current depends on the ratio of the zero-
90 , the higher the sequence impedances of the transformer and
differential current the supplying network and also on the
required for position of the earth fault in the winding. In
operation. addition, the number and the location of the
other star-points of the network influence the
The operation distribution of the earth
characteristic for the fault.
differential principle
is presented in the The transformation ratio correction settings
document describ- I01/In and I1/In allow correction of the
ing the earth-fault neutral connection CT and phase CT ratios on
relay module SPCD the HV side, whereas the settings I02/In and
2D55. The setting I2/In are used for the corresponding ratio
range of the basic corrections on the LV side.
settings P1/In and
P2/In is 5...50%. When the stabilized differential current princi-
The operation of the ple is used, the saturation of the current
numeri- cal trans- formers in asymmetrical inrush
differential current situations does not cause any problems, if the
principle is stabilized operation of the earth-fault relay is set to be
in respect of the blocked in inrush situations. This blocking is
phase currents (load based on the ratio of the second harmonic and
current) on the side the fundamental fre- quency component of
of the winding to be the neutral current I01 or I02.
High-impedance type Restricted earth-fault protection (REF protec- decreases when the current transformer is
protection tion) is often implemented by the high- saturated. The reactance of the magnetizing
imped- ance principle. When this principle is circuit of a fully saturated transformer is zero
employed the relay operates exclusively on and the impedance is formed of the winding
faults occurring within the protected area. resistance. Due to the resistor fitted in the
At external faults relay operation is inhibited differential current circuit the sec- ondary
by a stabilizing resis- tor mounted in the current of an unsaturated transformer
differential current circuit in series with the
matching transformer of the relay (see
application examples 2 and 3).
Residual overcurrent The residual overcurrent method can be used Earth-fault protection based on these
principle and for the earth-fault protection of delta- principles starts when the residual current or
neutral overcurrent connected windings connected to the neutral cur- rent exceeds the set start limit
principle network which in- cludes earthed neutral P1/In or P2/In. The operation has a definite-
points. Three phase cur- rent transformers are time characteristic.
used. The sum of the phase currents, i.e. the
sum of the zero-sequence cur- rents in the A blocking function based on the second har-
phases, is calculated in the relay module on monic of the neutral current I01 or I02 can
the basis of the phase currents linked to the be used in combination with the neutral
relay. The three phase currents will not sum current principle. This blocking can also be
to zero for internal earth faults. Special used if the the residual current of the phase
attention has to be paid to the operate time currents is formed via an external connection
settings in order to avoid unwanted by connect- ing the neutral terminals of the
operations, when the phase CTs saturate at windings of the relay’s phase current
external faults or in inrush situations. matching transformers to the 5 A or 1 A
terminal of the neutral current matching
Earth-fault protection based on neutral transformer I01 or I02. Should the residual
current can be used as back-up protection for current be numerically formed inside the
the earth- fault protection. relay module, this blocking function cannot be
used.
Operate time The definite operate time t01> and t02> can
be separately set for the the HV side and the
LV side in the range 0.03...100 s.
Disturbance recorder The earth-fault relay module SPCD 2D55 is recording is about 30 cycles and the capacity
provided with an integrated disturbance re- of the recording memory is one recording at
corder capable of recording six phase a time. The sampling frequency of the
currents, two neutral currents, the internal distur- bance recorder is 40 samples/cycle. A
start and block- ing signals of the module and PC pro- gram can be used for downloading
the control input signals. Recording can be the recording from the memory. The
triggered by the rising or falling edge of these recording memory has to be reset before a
signals. The length of the new recording is possible.
Combined over- The overcurrent unit of the combined directional earth- fault protection and it is well
current and earth- overcur- rent and earth-fault relay module suited for earth- fault back-up protection for
fault relay module SPCJ 4D28 is designed to be used for single- power transform- ers. The earth-fault unit is
SPCJ 4D28 phase, two-phase and three-phase short-circuit provided with two protection stages: a low-set
protection of power transformers and stage I0> and a high- set stage I0>>. The starting
generators. The overcurrent protection of the stage provides a start signal which can be
includes three overcurrent protec- tion linked to the desired output signal. If the
stages: stage I>, stage I>> and stage I>>>. An earth fault still persists, when the set operate
overcurrent stage starts once the current on time elapses, the concerned stage provides an
one of the phases exceeds the setting value operate signal.
of the stage. If the overcurrent situation
lasts long enough to exceed the operate time
set for the module, the stage that started
provides a trip signal to the circuit breaker.
SPA-ZC_
set stages only monitors the mini- mum and maximum relay module SPCJ 4D28 measures currents
have a definite phase current and calcu- lates the applied to the HV side phase current inputs
time mode of differential current I between the phases. IL1, IL2 and IL3 and the LV side neutral
operation. The The phase discontinuity protection unit can current input I02 of the relay.
operation of the be used for monitoring the condition of the
Circuit-breaker The relay modules SPCD 3D53, SPCD 2D55 lowing a secured circuit breaker trip system to
failure protection and SPCJ 4D28 are provided with be implemented.
integrated circuit-breaker failure protection
(CBFP), al-
Connection P2 P1 P1 P2
diagram L1
L2
L3 S1
S2 S1 S2
Rx Tx
S1 P1 P1 S1
S2 S2
P2 P2
+ (~) Uaux
- (~)
X0/1
X2/1
X0/38X0/37
A X0/25
X0/2
N
5X0/26
N
5A
U5
N
N
5A
5A
+ -
SERIAL
PORT
I/O
X2/16 IRF
X2/17
X2/18
IRF +
U6
X2/14
X2/15
Y/ U1 IRF SS1 +
SPAD 346 C SS1
SS2 X2/11
Y/ SS3 X2/12
8 8
Fig. 1. Connection diagram for the stabilized differential relay SPAD 346 C.
9 9
Terminals The terminals of the differential relay SPAD
346 C are as follows:
Terminal Contact
group interval
X0 1-2
X0 1-3
X0 4-5
X0 4-6
X0 7-8
X0 7-9
X0 13-14
X0 13-15
X0 16-17
X0 16-18
X0 19-20
X0 19-21
X0 25-26
X0 25-27
X0 37-38
X0 37-39
X1 1-2
X1 3-4
X1 5-6
X1 7-8
X1 9-10
X1 11-12-13-14
(heavy-duty two-pole relay, see "Circuit breaker control")
X1 15-16-17-18
X2 1-2
X2 3-4
X2 5-6
X2 7-8
X2 9-10
X2 11-12-13
X2 14-15
X2 16-17-18
The protection relay is connected to the optical fibres are connected to the counter
fibre- optic bus via a bus-connection con- tacts Rx and Tx of the module through
module, type SPA-ZC 17 or SPA ZC 21, snap-on connectors. The selector switches are
fitted to the D connector on the rear panel set in the position "SPA".
of the relay. The
1 13
X2 I L1 I'L1
2 14
TS2 Uaux 3 15
IRF SS1 SS2 SS3 SS4 TS1
4 16
IL2 5 17 IL' 2
Made in Finland Serial Port
6 18
7 19
SPA I L3 8 20 I'L3
9 21
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
18
I 01 26 38
02 I
X1 27 39
Fig. 2. Rear view of the stabilized differential relay SPAD 346 C
Control input and The control input and output relay module Five external inputs BS1, BS2, BS3, BS4
output relay of the differential relay SPAD 346 C is fitted to and
module the rear panel of the relay in the same BS5 are available to the differential relay
direction as the mother board. To remove the SPAD
module, the fixing screws have to be undone 346 C. For example, the alarm and trip signals
and the protec- tive earth cable of the module from the power transformer gas relay and the
plus the flat cable connecting the mother winding temperature sensor can be linked to
board to the module have to be the external control inputs. The external
disconnected. control inputs can be used for:
- blocking one or several protection stages of
The control input and output relay module the relay modules
contains the output relays (8 pcs + IRF), the - direct output relay
control circuits of the relays, the control
electronic circuits of the external control - the indication of the primary protection
inputs (5 pcs) and the D connector required relay signals or operations
for serial communica- tion. A flat cable links - resetting the operation indicators, latched
the output and input signals of the module to output relays, registers and recording memory
the mother board. The relay module - changing the actual setting values of the
locations U1, U2 and U3 are identical. relay modules. i.e.switching from main
setting val- ues to second setting values and
The output signals SS1...SS4 and TS1...TS4 vice versa.
of the mother board control an output relay
with the same designation. The operation The switchgroups of the relay modules are
of the protection stages of the relay module is used to specify the influence of the external
not fixed to any specific output relays, but the control inputs BS1...BS5 on the operation of
stages can be linked to the desired output the relay and the active state of the control
signals. In con- trast, the output relays TS1, inputs.
TS2, TS3 and TS4 are the only output
relays capable of circuit breaker control (see The activation of a protection stage, a
"Circuit-breaker control"). The configuration blocking function and an external control
of the output relay matrix switchgroups of input is indi- cated on the display of the relay
the relay modules is described in the manuals module by the red code representing the
of the relay modules. event. The codes are explained in the manuals
of the relay modules. Event information is also
received over the serial bus, when a protection
stage, a blocking func- tion, an external
control input or an output signal is
activated.
Intermodular The signals BS INT1, BS INT2 and BS INT3 for blocking the relay module SPCJ 4D28.
signals are blocking signals for the relay modules The figure below shows how the the external
(modified 97-10) SPCD control inputs, the start, operate and blocking
3D53 and SPCD 2D55. These blocking signals of the relay modules can be configured
signals allow one relay module to prevent the to obtain the desired functions of the relay
operation of another relay module fitted in modules. The switches to be used for selecting
another relay module location. An the active state of the signals and for
intermodular blocking sig- nal is activated configuring the latching feature of the output
when the corresponding block- ing signal of relays and the operation of the circuit-breaker
one relay module is activated. The blocking failure protection have been omitted.
signals BS INT1...3 are not capable of
controlling output relays, nor can they be
used
I>
SGR11
t>
SGR10
4
2
t >>
0
II 0>>
SGR9
3
2
>
SGR8
t 0>
2
0
SGR7
1
SGB3
6 SGF8
1 1
t>>>
SGR6
SGB2
I>>>
65
11
22
SGB1 SGR5
5
I>>
1
SGR4
4
2
t>>
I>
SPAD 346 C
SGR3
2
SGR2
12
12
11
22
t>
SGR1 X1/11
SGF6
SGF7
SS1
TS1
X1/12
X1/13
SPCJ 4D28 (U3)
AR2
AR1
X1/14
+
TS4
AR1
X2/7
8
X2/8
SGR11
AR2 7
+
SGR10
5 6 7
1 1 1
2 2 2
SS4
SGR9
8
SGR8
7
SGR7
2 3 4
2
X1/15
2
X1/17
SGB2 1
X1/18
+
SGR5
TS3
t02 >
I 02 >
2
SGR4
(HV harm.
2
SGR3
X2/9
2
3
3
2nd harm. blocking 2nd
X2/10
+
SS3
t01>
SGR2
2
I01>
SGR1
2
X2/3
SS1
SGF10 SGF9
TS3
TS4
SGF6
SGF7
SGF8
X2/4
SPCD 2D55 (U2)
+
TS4
TS2
SS4
TS3
AR1
AR3
SS3
TS2
SS2
TS1
SS1
X2/11
BS INT3
7 8
SS1
AR1
X2/13
TS3
TS4
6
+
4 5
SS2
6 7 8 SGR8
6 7 8
1 1 1
2 2 2
SGR7
3
SGR6
X2/5
1 2
SGR5
4 5
4 5
4 5
1 1
2 2
SGR4
X2/6
SGB2
+
TS1
SGR3
2nd or 5th harmonic blocking
2
SGR2 X2/14
3 I> 3 I>>
2 X2/15
+
SGR1
SS1
1
SGF10 1
2
IL1 , I L2, IL3
I'L1, I'L2 , I'L3
SGF6
SGF8
Fig. 3. The energizing inputs, external control inputs, intermodular signals, output signals and
output relays of the differential relay SPAD 346 C.
Power supply The power supply module forms the voltages The power supply module type SPGU 240
module required by the relay modules. The power A1 can be used for both ac voltage and dc
sup- ply module, which is a separate unit, is voltage, whereas type SPGU 48 B2 is
located behind the system front panel. The designed for dc voltage only. The voltage
module can be withdrawn after the system range of the power supply module of the
panel has been removed. relay is marked on the system panel of the
relay.
The power supply module is available in two
versions, SPGU 240A1 and SPGU 48B2 , The power supply module is a transformer con-
which have different input voltages: nected, i.e. galvanically isolated primary and
secondary side, flyback-type dc/dc
SPGU 240A1 converter. The primary side of the power
- rated voltage supply module is protected with a fuse, F1,
Un = 110/120/230/240 V ac located on the PVC board of the module.
Un = 110/125/220 V dc The fuse size of SPGU
- operation 240A1 is 1 A (slow) and that of SPGU 48B2
range is
U = 80...265 V ac/dc 4 A (slow).
SPGU 48B2
- rated voltage
Un = 24/48/60 V dc
- operation
range
U = 18...80 V dc
Uaux
80...265
18...80
+8V U ilized logics
n voltage
+12V s
t Operation amplifier
a voltage
-12V
b
Output relay coil
+24V
voltage
I n = 1A 5A ( I 2 ) 2
f n = 50Hz I n = 1A 5A ( I 01 )
5
n STEP
80...265 V –~ 1 / n RESET
18...80 V –
2tp In 02 / n
t >> [ s ]
2f / 1f 02
In
1 1/ n
0029A
0021A
0023A
0199A
RS 621 Ser.No.
Output relays
Heavy-duty output relays
Terminal numbers X1/11-12-13-14, 15-16-17-18
X2/3-4, 5-6
Rated voltage 250 V ac/dc
Continuous current carrying capacity 5A
Make and carry for 0.5 s 30 A
Make and carry for 3 s 15 A
Breaking capacity for dc when the control circuit
time constant L/R 40 ms at the control levels
48/110/220 V dc 5 A/3 A/1 A
Signal relays
Terminal numbers X2/7-8, 9-10, 11-12-13, 14-15
16-17-18
Rated voltage 250 V ac/dc
Continuous current carrying capacity 5A
Make and carry for 0.5 s 10 A
Make and carry for 3 s 8A
Breaking capacity for dc when the control circuit
time constant L/R 40 ms at the control levels
48/110/220 V dc 1 A/0.25 A/0.15 A
Control inputs
Terminal numbers X1/1-2, 3-4, 5-6, 7-8, 9-10
Control voltage
- rated voltages Un = 24/48/60/110/220 V dc
Un = 110/220 V ac
- operation range 18...265 V dc and 80...265 V ac
Current drain 2...20 mA
Selectable mode of activation in the relay modules
- input activated when Energized
- input activated when Non-energized
Time between activation of control input and
relay operation (control input active when energized,
to be programmed in the relay module) <30 ms
Time between activation of control input and
relay operation (control input active when
non-
energized, to be programmed in the relay module) <50 ms
Power supply module
Terminal numbers X2/1-2
Type SPGU 240A1
- rated voltages Un = 110/120/230/240 V ac
Un = 110/125/220 V dc
- operation range 80...265 V ac/dc
Type SPGU 48B2
- rated voltage Un = 24/48/60 V dc
- operation range 18...80 V dc
Current consumption under quiescent/operation
conditions about 10 W/15 W
Data communications
Transmission mode Fibre-optic serial bus
Coding ASCII
Data transfer rate 4800 or 9600 Bd
Optical bus connection module
- for plastic core cables SPA-ZC 21 BB
- for glass fibre cables SPA-ZC 21 MM
Optical bus connection module power from an
internal power source
- for plastic core cables SPA-ZC 17 BB
- for glass fibre cables SPA-ZC 17 MM
Insulation Tests *)
Dielectric test IEC 60255-5 2 kV, 50 Hz, 1 min
Impulse voltage test IEC 60255-5 5 kV, 1.2/50 s, 0.5
J Insulation resistance measurement IEC 60255-5 >100 M , 500 Vdc
Electromagnetic Compatibility Tests *)
High-frequency (1 MHz) burst disturbance test
IEC 60255-22-1
- common mode 2.5 kV
- differential mode 1.0 kV
Electrostatic discharge test IEC 60255-22-2 and
IEC 61000-4-2
- contact discharge 6 kV
- air discharge 8 kV
Fast transient disturbance test IEC 60255-22-4
and IEC 61000-4-4
- power supply 4 kV
- I/O ports
2 kV
Environmental Conditions
Specified service temperature range -10...+55 C
Transport and storage temperature range -40...+70 C
Temperature influence on the operating values
of the relay over the specified service
temperature range <0.2%/ C
Damp heat test, cyclic IEC 60068-2-30 +25...55 C, r.h. > 93%, 6 cycles
Degree of protection by enclosure
of the relay case when panel mounted IP
54
Weight of fully equipped relay 6 kg
*) The tests do not apply to the serial port, which is used exclusively for the bus connection
module.
Recommenda- The more important the object to be the current transformers are partially
tions for protected, the more attention should be saturated. The purpose of the following
current paid to the current transformers. current trans- former recommendations is
transformers Normally, it is not possible to to secure the stabil- ity of the relay at
dimension the current transformers so that high through-currents, and quick and
they repeat currents with high DC sensitive operation of the relay at faults
components with- out saturating, when occurring in the protected area, where the
the residual flux of the current fault currents may be high.
transformer is high. The differential
relay SPAD 346 C operates reliably, even
though
At faults Fa >
occurring 40
in the
and
protected Fa > 4 x
area on the Imax1
HV side of
the
The setting Id/In>> of the instantaneous
transforme
differ- ential current stage is used as the
r, the fault
factor Imax1.
currents
may be very
The use of auto-reclosing to clarify a
high
fault occur- ring outside the protected
compared
area may produce a substantial residual
to the rated
flux in the CT core. To guarantee that
currents of
the differential protection re- mains
the current
stable in an auto-reclose situation also at
transformer
large currents when the residual flux is
s. Thanks
great, the accuracy limit factors
to the in-
corresponding to the ac- tual burden of
stantaneous
the HV and LV side CTs should fulfill
stage of the
the requirements mentioned above and
differential
be of the same order, if possible.
relay mod-
The technical features of class X (BS where
3938) current transformers are n is the transformation ratio of the
determined by the knee- point voltage current transformer
and the resistance of the secondary Rin is the secondary resistance of the
winding. The knee-point voltage is the current transformer
value of the CT secondary voltage at RL is the total resistance of the longest
which a further loop measured (outgoing and return
10% increase in the secondary voltage lead)
would cause a 50% increase in the Imax2 is the setting of the instantaneous
excitation current. The knee-point differ- ential current stage Id/In>>
voltages Uk of current trans- formers multiplied by the rated current of
used in differential protection should the protected object.
fulfil the following requirement:
4 x Imax2 x (Rin + RL)
Uk>
n
Earth- The recommendations for current of the neutral current transformer should
fault transformers used in earth-fault be as close as possible to the accuracy
protectio protection based on the stabilized limit factor corresponding to the actual
n differential current principle are the same burden of the phase current transformers.
as for differential protection. The accuracy
limit factor corresponding to the actual
burden
Earth-fault The sensitivity and reliability of The sensitivity requirements for the
protection based on differential current protection stabilized protection are jeopardized if the
the high- through a resistor are strongly related to magnetizing current of the current
impedance type the current transformers used. The transformers is allowed to rise too much
protection number of turns of the current trans- compared to the knee-point voltage. The
formers that are part of the same Iprim value of the primary current at
differential current circuit should be the which the relay operates at certain settings
same. The current transformers should can be calculated as follows:
have the same transforma- tion ratio.
Iprim = n x (Ir + Iu + m
To be able to feed the differential current x Im )
circuit with the current required for
starting, when a fault occurs in the w
protected area, the current transformers he
need a knee-point voltage that is about re
twice the stabilizing voltage required from n = the transformation ratio of the
the relay at faults outside the protected current transformer
area. The stabilizing voltage Us of the relay Ir = the current value representing the
and the knee- point voltage Uk of the relay setting
current transformer is calculated as Iu = is the current flowing through the
follows: protec- tion varistor
m = the number of current transformers
Ifmax x (Rin + RL) in- cluded in the protection
Im = the magnetizing current of one
current
Us = transformer
n A protection varistor connected in parallel
Uk = 2 with the differential current prevents the
voltage gen- erated in the differential
x Us
circuit at faults occur- ring in the protected
area from rising too high. The resistance
where Ifmax is the maximum through-
of the varistor depends on the voltage
going fault current at which the
applied to it: the higher the voltage the
protection is not allowed to operate. The
smaller the resistance.
factor two is used when no operation
delay whatsoever is permitted for the
protection. To prevent the knee-point
volt- age of the current transformers to
grow too high, it is recommended to use
current transformers whose secondary
winding resistance is of the same level
as the resistance of the measurement
circuit.
Overcurre The recommendations for current those used in differential current protection,
nt transformers used in overcurrent i.e. there are no special requirements.
protection protection are the same as
Circuit- The opening of the circuit-breaker can be and X1/17 are connected to the open coil
breaker im- plemented as double-pole control or of the circuit breaker. If the heavy-duty
control single-pole control. The stabilized output relay TS4 is used for
differential relay SPAD
346 C is provided with two heavy-duty
one-pole relays (TS1 and TS2) and two
heavy-duty dou- ble-pole relays (TS3 and
TS4).
OPEN
X2 14 15
X2 11 12 13 X2 9 10
+ +
0
-
OPEN
X2 14 15
X2 11 12 13 X2 9 10
+ +
Example Differential relay SPAD 346 C used for the protection of a YNyn0-connected power
1. transformer.
P2 P1
L P1 P2
1
L
2
L S1
3 S2
S2 S1
S1 P1 P1 S1
Rx Tx
SPA-ZC_
2
S
2
P
2
P
2
X0/2X0/1
Uaux
- (~)
X0/25
X0/26
5 A NX0/37
X2/1
X0/38
U5
5AN
+ -
SERI
AL
I/O POR
T
5A N
5AN
5A
X2/16 IRF
X2/17
U6
IRF
X2/18
Y/ U1 SS X2/14
SPAD 346 C 1
Y/ IR
F
S
S X2/15
1 +
S
S2 X2/11
S
S3
X2/12
B 3I> SS X2/13
S1 SS
4 +
2
U4 B 3I>> TS
S2 1 X2/9
X1/1
B TS
S3 2
TS
B X2/10
3
S4 TS
BS 4 SS
X1/2 BS I/ 3 +
1 5
O
X1/3 X2/7
U2
SS
BS X2/8
X1/4 4
2 IR +
F
S
S
1
S
S2
S
S3 X2/5
X1/5 BS BS I 01 > SS TRIP X2/6
3 1 4
I 02 > TS +
BS TS 1
X1/6 2 1 X2/3
TS
BS
2
3 TS
X1/7 BS 3
4 TS
4
X1/8 BS BS U3 I/ TS TRIP
4 5 X2/
O 2 4
IR +
3I F
X1/9
B >I SS X1/15
S5 1 TRIP
BS SS
X1/10 1 I> 2 TS X1/16
BS SS
3 3
2 SS X1/17
BS 4
TS TRIP
3
1 X1/18
TS
2 TS
TS 4 +
3
TS X1/11
4
I/
O X1/12
X1/13
X1/14
+
Fig. 7. Application of example 1.
The stabilized stage and the poles of the LV side and serves as back-
instantaneous stage of the three-phase up at short circuits in the LV side busbar
differential relay module SPCD 3D53 system. A facility of automatic doubling
are used to protect the power of the setting value of the I>> stage at
transformer against winding short magnetizing inrush currents is available.
circuit and interturn faults. In an inrush The overcurrent stage I> of the module
situation the trip- ping of the stabilized can be employed as inverse time earth-
stage is inhibited by a blocking fault back-up protection for the LV side
function based on the second har- feeders.
monic of the differential current. In cases
where the transformer is not allowed Blocking based on the second harmonic of
to be discon- nected from the network the differential current of the relay module
in a situation of over- excitation, a SPCD
blocking arrangement based on the fifth 3D53 can be used for blocking the
harmonic of the differential current is overcurrent stages I> and I>> of the
used. relay module SPCJ
4D28 at transformer magnetizing inrush
The stabilized differential current cur- rents. The blocking is programmed in
principle or the high-impedance the relay module SPCD 3D53 for the
principle of the relay mod- ule SPCD desired output relay, from which it is
2D55 is employed for protecting the HV linked to the external control input BS1,
and LV side winding against earth BS2 or BS3. The concerned control input
fault. When the stabilized differential is programmed to block the opera- tion of
current princi- ple is used, the inverse the overcurrent stage I> and/or I>> of the
time stage I0> of the relay module SPCJ relay module SPCJ 4D28. The operation of
4D28 can be used as back-up the overcurrent stage I>>> will not be
protection on the LV side. The blocking blocked.
based on the ratio between the second
harmonic and the fundamental In combination with protection of YNyn-
frequency component of the neutral con- nected power transformers the phase
current is permitted both on the HV disconti- nuity protection I> of the relay
side and on the LV side. If the high- module SPCJ
impedance principle is used on the LV 4D28 can be used for network
side, no back-up protection can be supervision, at least as alarming
arranged for the earth-fault protection. protection. Then it should be noticed that
the phase discontinuity protection can
The relay module SPCJ 4D28 provides provide an alarm signal at earth fault as well.
three- phase, three-stage overcurrent
protection and earth-fault back-up The operate signals of the integrated
protection. The module measures the circuit- breaker failure protection of the
phase currents on the HV side and relay modules are linked to a heavy-duty
neutral current on the LV side. The output relay that is capable of operating
definite time overcurrent stage I>>> is the circuit breaker preced- ing the HV
set to operate on short circuits occurring side circuit breaker in the supply
on the HV side of the transformer. direction.
The overcurrent stage I>> is
configured to operate on short circuits
in the
Example Differential relay SPAD 346 C used for the protection of a YNd11-connected power
2. transformer.
The principle of the winding and the 4D28 serves as
interturn fault protection and the back-up for the
overcurrent protection is the same as in earth-fault
example 1. The high-imped- ance protection. Then
protection principle of the module the neutral
SPCD current from the
2D55 is used for protecting the HV side second neutral
windings against earth fault. connection
transformer on the
The stage I0>, operating with inverse time HV side is con-
char- acteristic, of the relay module SPCJ nected to the
terminals XO/37-38 or X0/37-39, as The neutral current principle is
illustrated in the figure. When the HV programmed to be used on the LV side
side star point is directly earthed the in the relay module SPCD 2D55. Then
definite time stage I0>> can also be used the blocking function based on the second
as earth-fault back- up protection. harmonic of the neutral current can be
used. The blocking function can be used
for blocking the stages I0> and I0>> of the
relay module SPCJ 4D28 in transformer
inrush situ- ations. In the relay module
SPCD 2D55 the blocking is programmed
to the desired output relay, from which it
is externally linked to the control input
BS1, BS2 or BS3. The concerned control
input is programmed to block the opera-
tion of the desired earth-fault stage of the
mod- ule SPCJ 4D28.
P2 P1
P2 P1 YNd11
L1
L2
L3 S1
S1 S2
S2
S1 P1 Rx Tx
SPA-ZC_
S2
P2
S1 P1
S2
P2
Uaux
- (~)
X0/25
X0/37
X0/1
X2/1
5 A NX0/26
5 A NX0/38
X0/2
5A N
U5
5AN
+ -
SERIAL
PORT
I/O
X2/16 IRF
X2/17
X2/18
+
IRF
U6
X2/14
X2/15
Y/ U1 IRF SS1 +
SPAD 346 C SS1
SS2 X2/11
Y/ SS3 X2/12
TS4 X2/10
X1/2 SS3
X1/3
BS2 SS1 SS4
X2/8
X1/4 SS2
BS1 I 01 > +
SS3
X1/5 BS2 I 02 > SS4
BS3 X2/5
BS3 TS1 TS1 X2/6
X1/6 TS2
BS4 +
TS3
X1/7 BS5 TS4 TRIP
BS4 X2/3
X1/8 I/O TS2 X2/4
U3
IRF +
X1/9 SS1
BS5 SS2
X1/10 3I> X1/15 TRIP
BS1 SS3 X1/16
I SS4
BS2 X1/17
I> TS1
BS3 TS3 X1/18
TS2
TS3 +
TS4
I/O X1/11 TRIP
X1/12
X1/13
TS4 X1/14
+
P1 P2
P2 P1 YNd1
L1 1
L2
L3 S1
S1 S2
S2
Rx Tx
S1 P1 S1 P1
SPA-ZC_
S2
P2 S2
P2
+ (~) U aux
- (~)
X0/13
X0/25
X0/1
X2/1
5AN
5AN
5 AN
U5
5 AN
N
5A
+ -
SERIA
L
I/O PORT
X2/16 IRF
X2/17
X2/18
+
IRF
U6
X2/14
Y/ IRF SS1 X2/15
U1
SPAD 346 C SS1 +
SS2 X2/11
Y/ SS3 X2/12
BS1 3 I> SS4 X2/13
SS2
BS2 +
U4 TS1
BS3 3 I>> TS2
X2/9
X1/1 BS4 TS3 X2/10
TS4 SS3
X1/2 BS1 BS5 +
I/O
X1/3 U2 IRF SS4 X2/7
SS1 X2/8
X1/4 BS2
SS2 +
SS3
Combined over- The settings of the combined overcurrent and In transformer protection the setting of the
current and earth- earth-fault relay module are dependent on the overcurrent stages should be at least 1.5 x In,
fault relay module object to be protected and the use of the to be able to utilize the overload capacity of
SPCJ 4D28 protec- tion stages. The low-set stages (I> and the transformer. The setting value of the
I0>) can have a definite time or an inverse time high-set stage I>> can be set to
operation characteristic. Four international automatically double when the transformer is
standardized time/current characteristics and energized. The opera- tion of the overcurrent
two special- type time/current characteristics stages I> and I>> and the earth-fault stages I0>
are available for the inverse time operation and I0>> can be blocked by the control
(IDMT). The switch SGF1 is used for signals BS1, BS2 and BS3. The switches
selecting the operation mode and the SGB1/1...4, SGB2/1...4 and SGB3/1...4 are
time/current characteristic. The operation of used for configuring the blocking signals.
the high-set stages I>>, I>>> and I0>> is based
on the definite time characteristic only. The When required, the blocking signal BS1 can
operation of the individual stages can be be used to block the operation of the phase
blocked by means of the concerned configu- discon- tinuity protection I> of the relay
ration switches. module SPCJ
4D28. The switch SGB1/6 is used for confi-
guring the blocking. The phase
discontinuity protection supervision can be
set out of opera- tion (SGF3/1).
Commissioning The differential relay module SPCD 3D53 is of the phase currents
capable of reliably measuring the amplitudes and the differential
currents, the phase
angles between the phase currents and the the HV side current transformers are included
phase differences of the HV and LV side in the circuit. By making a three-phase short-
phase currents when the current supplied to circuit on the LV side of the transformer so
the relay is above 1% of the rated current. that the LV side current transformers are
Even at lower currents it is possible to measure included in the circuit a three-phase current of
the phase differences. The amplitudes and some mAs is injected into the relay.
phase angles measured are presented on the
display of the module. The amplitudes are
During the test the HV and LV side current
expressed as rela- tive values (x In and % In).
amplitudes and phase angles measured by the
The values displayed take into account the relay module are shown for the individual
vector group matching and the phases on the display of the differential relay
transformation ratio correction set for the module (or over the serial bus). If the
relay. connection, vector group matching and the
transformation ratio corrections of the relay
After mounting the following low-voltage test are correct the following applies to each
can be made on the relay to verify the phase:
connec- tion, phase sequence, vector group
matching and transformation ratio correction - the phase currents are equally
of the dif- ferential relay: Connect three-phase
high
low-voltage to the primary poles of the current
- the differential currents are 0%
transformers on the HV side of the power
- the phase differences of the HV and LV side
transformer so that
phase currents are 0
- the phase differences between the phase cur-
rents on the same side are 120 .
Testing The relay should be subject to regular tests in As the settings of the relay modules vary in
accordance with national regulations and in- different applications, these instructions
structions. The manufacturer recommends an present the test procedure in general.
interval of five years between the tests. Ordinary current supply units and
instruments for measuring current and time
The test is recommended to be carried out as can be used for the tests.
a secondary test. Then the relay has to be
discon- nected during the test procedure. During the test procedure the relay records
However, it is recommended to check the currents and relay operations. The registers
condition of the signal and trip circuits as should be read before the test is started and
well. during the test.
Note!
When testing the three-phase differential
relay module the effect of the vector group
matching, elimination of the zero-sequence
At single-phase currents are IL1m = 0.58 A, IL2m = 0 A and 2/3 of the current applied to the relay at
testing the HV IL3m = 0.58 A. single- phase testing.
side currents
injected are IL1 = 1 If the zero-sequence component has been Example 2. On the HV side of the YNyn-
A, IL2 = 0 A and se- lected to be numerically reduced from the con- nected transformer zero-sequence current
IL3 = 0 A. After phase currents on the HV side or the LV is set to be eliminated as follows (SGF1/2 =
vector group side, i.e. SGF1/1 = 1 or SGF1/2 = 1, the 1):
matching the current meas- ured by the relay module on
amplitudes of the that side will be
operation of the stabilized differential current - - -
- -
stage and the instantaneous differential IL1m = IL1 – 1 x (IL1 + IL2 + IL3)
current stage have to be taken into account. 3
If - - - -
- Yd vector group matching has been selected 1
IL2m = IL2 – x (IL1 + IL2 + IL3)
for the HV or LV side, the current measured 3
by the relay module for the concerned side –
will,
after matching of the vector group, be 3 of
1/ - - - - -
the current applied to the relay at single-phase IL3m = IL3 – 1 x (IL1 + IL2 + IL3)
3
testing.
At single-phase testing the HV side currents
Example 1. Vector group matching of a injected are IL1 = 1 A, IL2 = 0 A and IL3 = 0
YNd11- connected power transformer on the A. After the zero-sequence current elimination
HV side. CT connection according type II. the
-and - currents are IL1m = 0.67 A, IL2m = 0.33 A
- IL1 – IL2 IL3m = 0.33 A.
IL1m = –
3
- - The table below shows how the HV side
settings
- IL2 – IL3 of the relay module affect the values measured
IL2m = –
3 at single-phase testing. I is the one-phase
current
- - (A) applied to the relay, In is the rated current
(1
- IL3 – IL1 A or 5 A) of the matching transformer and I1/In
IL3m = –
3 is the setting of the HV side transformation
ratio
correction (the corresponding HV side setting
is
I2/In).
Instantaneous differ- The testing of the module should be started The operation of the instantaneous differential
ential current stage with the differential current stage 3 I>>. To current stage is not stabilized. The instantane-
3 I>> prevent operation of the stabilized differential
stage dur- ing the testing of the differential
current stage its operate signal should be
disconnected at the output relays, that is, the
switches of switch- group SGR1 should be
set in the position 0. Alternatively, the
operation of the stage can be inhibited by
applying an external blocking sig- nal to the
stage.
ous stage can be it should be noted that the setting value 30% of the differential current ( the difference
tested by applying required for the operation of the between the HV and LV side currents).
one or two instantaneous stage will be reduced by 50%,
currents to the if the stabilizing current (average of the HV When the instantaneous differential current
relay. When two and LV side cur- rents) calculated by the stage has been tested the original settings
currents are used, relay module falls below should be restored.
Stabilized differential The stabilized differential current stage can be the stabilizing current is the average of the
current stage 3 I> tested by applying one or two currents to the currents applied. Then increase the differential
relay. If one current is used the phase current current by raising one current and decreasing
inputs of the HV and LV side are tested one the other current so that the stabilizing
by one until all of six inputs have been tested. current remains constant. Increase the
differential cur- rent until the module operates
Two currents have to be used to verify the when the differ- ential current exceeds the
operation characteristic of the stabilized value of the operation characteristic. Repeat
differ- ential current stage of the module. At the test on all three phases. The test can also be
least one stabilizing current value has to be made by raising one current and keeping the
selected from each of the three parts of the other at a constant value.
operation charac- teristic. Apply the current
to the HV side and the LV side on one The table below shows the differential current
phase so that the currents calculated by the required for operation in the different parts
relay module initially are the same. First the of the operation characteristic.
differential current is zero, and
Part of operating
characteristic
Note! The effect of the transformation ratio mental frequency component of the differential
correction, vector group matching and zero- current. The weighting factors, 4, 1 and 1, to
sequence component elimination on the cur- be used between the different phases have to
rents to be applied to the relay should be be taken into account when testing the
consid- ered when using the table. second harmonic blocking. During the
testing of the blocking based on the second
Special equipment is required for testing the harmonic of the differential current the
blockings based on the ratio between the blocking inhibit algo- rithm based on the
second harmonic and the fundamental waveform of the differential current should be
frequency com- ponent or the fifth harmonic set out of use, that is, the switch SGF2/2 is
and the funda- set to 0.
Operate times Apply current to the relay by closing the differential current stage plus the selected
current switch so that the differential current is oper- ate time of the circuit breaker failure
about 2 times the differential current required protection can be separately tested. The
for opera- tion. Then measure the operate operate time of the instantaneous differential
time, i.e. the time from closing the switch current stage can be tested at various
until the relay operates. The operate times differential current levels, say,
of the instantane- ous differential current 1.5 x Id/In>> and 4 x
stage and the stabilized Id/In>>.
Testing of the earth- Test the following values and functions of the Note!
fault relay module protection stages I01 and I02: The earth-fault protection for the HV side and
SPCD 2D55 the LV side is identical and, therefore, tested in
- start value the same way. The test procedure depends on
- operate time the protection principle employed. The
- operation indication and operation of switches SGF1/1...8 are used to select the
output relays protection principle for the HV and LV side.
The effect of the transformation ratio
correction settings on the currents calculated
by the relay module have to be considered
when the module is tested.
Testing of the The stabilized differential current principle is amplitudes of the three phase currents) will be
stabilized tested by applying one or two currents to the 1/3 of the phase current applied to the relay.
differential relay. When one current is used, inject the Repeat the test on each phase current input.
current principle current into the neutral current input I01 or
I02. The neutral current does not affect the The phase difference of the currents applied to
stabiliz- ing current. Increase the current until the relay should be considered in the test (see
the mod- ule starts. The start value of the the functions of switches SGF2/1 and SGF2/2
module is the same as the basic setting of the in the manual for the earth-fault relay module
concerned side. and the specification of the sign of the cos
term).
When testing the differential current
principle using two currents, inject one
current into the phase current input and the
other into the neutral current input of the
same side. Then the residual current calculated
by the relay module will be the same as the
current injected into the phase current input.
At single-phase testing the stabilizing current
calculated by the relay mod- ule (average of the
The module I1 on the HV side or the setting I02/ I2 on The directional criterion cos = 1, if the
starts, if the the LV side residual current or the neutral current of that
following - the directional differential current exceeds side is less than 4% of the rated current.
conditions are the value of the operation characteristic
fulfilled at the - the blocking based on the second Verify the operation characteristic of the stabi-
same time: harmonic and external blocking do not lized differential current principle by selecting a
- the ratio of the prevent starting point on either part of the characteristic.
neutral Keep the stabilizing current at a constant
current and Not value and increase the differential current until
the residual e! the mod- ule starts.
current of the When the setting I01/ I1 or the setting I02/
phase I2 is greater than 0%, the minimum value of Special equipment is required for testing the
currents is the neutral current required for tripping on blockings based on the ratio of the second
above the that side is 2% of the rated current. harmonic and the fundamental frequency
setting I01/ com- ponent of the neutral current.
Testing of high- Test the high-impedance principle by relay. The start value of the module is equal
impedance principle injecting current into the neutral current to the basic setting of the concerned side.
input of the
Testing of residual starts. The start value of the module is equal
overcurrent principle Test the residual overcurrent principle by in- to the basic setting of the concerned side.
jecting current into the phase current inputs
one by one. Increase the current until the
module
Testing of neutral ule starts. The start value of the module is
current principle equal to the basic setting of the concerned
Test the neutral current principle by side.
injecting current into the neutral current
input of the concerned side. Raise the current
Operate times until the mod-
relay module operates. The operate times must
be within the specified tolerances. The
Apply a current of 1.5...2 times the current operate time of the circuit breaker failure
required for starting to the module by protection is to be separately tested.
closing the current switch. Measure the
Operation indicators,
operate time, i.e. the time from closing the
alarm and operate
switch until the
signals
Testing of the When the relay module SPCJ 4D28 is tested, it Start value:
combined over- should be noted that the module measures the Check the start value by raising the current,
current and earth- transformer HV side or the generator star starting from zero, until the relay starts. The
fault relay module point side phase currents, i.e. the phase start value should be within the permitted
SPCJ 4D28 currents con- nected to the terminals X0/1...9, toler- ances.
and the trans- former LV side neutral
current, i.e. neutral current connected to the To measure the resetting value, raise the
terminals X0/37...39. current enough to make the relay start. Then
decrease the current until the relay resets.
The tests should include the following values
and functions of the protection stages (I>, When multi-stage protection relays are tested,
I>>, I>>>, I0>, I0>>, I>) used: the operation of the low-set stages may
disturb the testing of the high-set stages. In
- start value (for the high-set stages to be conse- quence, the operation of the lower
meas- ured for all three phases) current level stages, generally, has to be
- resetting value (when desired/required) inhibited or delayed by changing their setting
- start time (for one values, to enable test- ing of the high-set
phase) stages. In such a case it is recommended to
- operate time (for one start the testing from the stage with the
phase) highest current setting and then move on to
- resetting times (when desired/required) the lower current stages. Thus the original
- operation indication, circuit breaker settings of the stages are restored during the
opening and signalling test.
Start and operate Apply a current of about 1.5...2 times the ured the measurements can be made with
times setting of the protection stage by closing the sev- eral current values (for example 2 x and
current switch. Measure the operate time, i.e. 10 x the setting value).
the time from closing the switch until the relay
operates. The operate times should be within The reset time is the time from opening the
the permit- ted tolerances. When inverse current switch until the relay resets.
times are meas-
Spare parts Th
Ea
Co
Po
-U
-U
I/O
Co
Ca
Bu
Delivery Eq
alternatives
Ba
Ve
ear
Ver
Ve
rela
Ordering SPAD 346 C without test adapter RS 621 002-
numbers AA RS 621
002-CA RS 621
002-DA RS
621 002-FA
202-AA RS
P 18: 621 202-CA RS
R 621 202-DA
S RS 621 202-FA
6
2 The letter combinations of the order number denote the rated frequency fn
1 and auxiliary voltage Uaux of the protection relay:
Designation
AA
CA
DA
FA
Order data
1. Qu
2. Ord
3. Rat
4. Aux
5. Acc
6. Spe
Dimension The basic model of the protection relay case SPA-ZX 301 reduces the depth by 40 mm,
drawings and is designed for flush-mounting. When type SPA-ZX 302 by 80 mm and type SPA-
mounting required, the mounting depth of the case can ZX 303 by 120 mm.
be reduced. Three types of raising frames are
available: type
293
226
259 34
30 229
162
136
214 ±1 a b
139 ±1
Raising frame
SPA-ZX 301
SPA-ZX 302
SPA-ZX 303
Fig. 10. Dimension and mounting drawings for differential relay SPAD 346 C.
The relay case is made of grey anodized by enclo- sure
profile aluminium. between the relay
case and the
The rubber gasket fitted to the mounting mounting base.
collar provides an IP 54 degree of protection
The hinged cover of the case is made of The terminal blocks X1 and X2 contain dis-
transpar- ent, UV-stabilized polycarbonate connectable multi-pole screw terminals. The
polymer and provided with two sealable male part of the disconnectable terminal
locking screws. The rubber gasket of the blocks is attached to the I/O module. The
cover provides an IP 54 degree of protection female parts, which are included in the
between the case and the cover. delivery, can be locked to the male part with
fixing accessories and screws.
The required input and output connections
are made to the screw terminals on the rear The external control inputs of the modules
panel. The energizing currents are linked to are connected to the terminal block X1. The
the termi- nal block X0 which consists of trip signals are obtained from the the terminal
fixed screw terminals. Each terminal screw is blocks X1 and X2. The alarm signals are
dimensioned for one wire of maximum 6 mm2 obtained from X2. Each terminal of X1 and X2
or two wires of maximum 2.5 mm2. is dimensioned for one wire of max 1.5 mm2
or two wires of max. 0.75 mm2.
3 I>
I1 Id I2
L1 L2 L3 IRF
RESET
P / I n [ %] STEP
S [% ]
I 2tp / I n
I d / I n >>
SGF
SGB
SGR
TRIP
0021A
SPCD 3D53
1MRS 750097-MUM EN
SPCD 3D53
Issued 1996-10-16
Modified 2004-04-27
Version F (replaces 34 SPCD 2 EN1)
Differential
Checked PS
Approved MÖ
Relay Module
Data subject to change without notice
37 3
Stabilized Blocking based on the ratio between the Integrated circuit breaker failure protection
against fifth harmonic and the fundamental
connection frequency com- ponent of the differential Integrated disturbance recorder capable of re-
inrush current prevents un- necessary operation in cording six phase currents, the internal
currents harmless situations of transformer operate and blocking signals, and the
and faults overexcitation. This blocking func- tion can control signals linked to the relay
outside the be prevented if the ratio between the fifth
protected harmonic and the fundamental frequency High immunity to electrical and electromag-
area component increases at high overvoltages netic interference allows the relay to be used
in severe environments
Blocking Measured, set and recorded values are
based on indicated on the display of the relay module. Dynamic measuring
the ratio functions
between the Sensitive phase current and phase angle
second displays facilitate the checking of connection High availability - the integrated self-supervi-
harmonic and vector group matching sion system monitors the operation of the
and the elec- tronics and the software and gives an
fundamental Writing and reading of setting values alarm signal in the event of a fault.
frequency through local display and front panel push-
com- buttons, a PC with configuration software, or
ponent of from higher system levels over the serial
the port and optical fibres.
differential
current Five programmable external control
prevents inputs
op- eration
at Output relay matrix allowing the operate
transformer and control signals to be linked to the desired
connection output relay
inrush cur-
rents
Description of The differential relay module SPCD 3D53 neous differential stage is based on the funda-
function pro- vides differential current protection for mental frequency components I1 and I2 of
three phases. The settings are the same for the phase currents. The fundamental frequency
each phase. The differential relay module com- ponent Id1f (i.e. Id) of the differential
measures the phase currents on the HV and current , the fundamental frequency
LV side of the trans- former to be protected component Ib1f (i.e. Ib) of the stabilizing
or the phase currents on the stator star-point current, the second har- monic Id2f of the
side and the network side of the generator to differential current, and the fifth harmonic
be protected. The operation of the stabilized Idf5 are digitally filtered.
differential stage and the instanta-
Rated frequency
The differential relay module can be used at 16.667 Hz up to 60 Hz. The setting is
frequencies between 16 2/3 and 60 Hz. The made either via the push-buttons on the front
rated frequency setting is accurate to within 1 panel, the subregisters 5 and 6 of register A,
mHz. The rated frequency has two settings, i.e. or the serial bus, in which case the control
Hz and mHz, which are separately set from parameters V180 and V181 are used.
Transformer vector The phase difference of the HV side and LV sired vector group. The matching of the
group matching side currents that is caused by the vector group phase difference in vector group matching
of the power transformer to be protected is can be set for the HV and LV side at intervals
numeri- cally compensated. The matching of of 30 . The switches SGF1/3...5 are used for
the phase difference is based on phase the LV side vector group matching, whereas
shifting and nu- merical delta connection SGF1/6...8 are used for the vector group
inside the relay. The switches SGF1/3...8 are matching on the HV side.
used to select the de-
38 3
Transforming ratio In vector group matching the zero-sequence can, when required, be separately calculated
correction of phase component of the phase currents is and reduced for each phase current.
current transformers eliminated before the differential and Elimination of the zero-sequence component
stabilizing current are calculated. Unless the on the HV and/ or the LV side is selected
vector group matching is made on the side of with the switches SGF1/1 and SGF1/2.
the earthed winding, the zero-sequence
component of the phase currents
Id
In
3.0
2.5 Id3
In
2.0
In Ib3
1.0 In
Id1 I d2
0.5 In In
39 3
Fig. 1. Operating characteristic of the stabilized differential current stage of the differential
relay module SPCD 3D53
The operation of the relay is affected by The starting ratio S is determined
the stabilization as shown graphically by the correspond- ingly
operat- ing characteristic illustrated in Fig. 1.
S = Id2/Ib2
The basic setting P/In of the stabilized stage (4)
of the differential relay module is determined
ac- cording to Fig. 1: The second turning point I2tp/In can be set
at the desired point in the range 1.0...3.0. The
P/In = Id1/In first turning point is always fixed at Ib/In =
(3) 0.5.
The slope of operating characteristic of the Part 2, i.e. 0.5 Ib/In < I2tp/In, is called
differential relay module varies in the different the influence area of starting ratio S. In this
parts of the range. In part 1 (0.0 Ib/In < 0.5) part variations in the starting ratio affect the
the differential current required for tripping is slope of the characteristic, that is, how big the
con- stant. The value of the differential change in the differential current, in
current is the same as the basic setting P/In comparison with the change in the load
selected for the relay module. The basic current, is required for trip- ping. The
setting basically allows for the no-load starting ratio should consider CT errors and
current of the power trans- former, but it can variations in the power transformer tap
also be used to influence the overall level of changer position. Too high a starting ratio
the the operation characteristic. At rated should be avoided, because the sensitivity of
current the no-load losses of the power the differential relay for detecting
transformer are about 0.2 per cent at rated transformer interturn faults depends basically
voltage. Should the supply voltage of the on the starting ratio.
trans- former suddenly increase due to
operational disturbances the magnetizing At high stabilizing currents I /I I2tp/In
b n
current of the transformer increases as well. the slope of the characteristic is constant (part
In general the magnetic flux density of the 3). The slope is 100%, which means that the
transformer is rather high at rated voltage and in- crease in the differential current is equal to
the rise in voltage by a few per cent will cause the corresponding increase in the stabilizing
the magnetizing current to increase by tens cur- rent.
per cent. This should be considered in the
basic setting.
Id
In
Curve
5.0
4.0
3.0
2
2.0
1.0
0.0 0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 Ib
In
Fig. 2. Setting range for the stabilized differential current stage of the differential relay module
SPCD 3D53.
40 4
Blocking based on The blocking of relay operation at through switch SGF2/1. The switchgroup
the second harmonic transformer inrush currents is based on the SGR3 is used to route the blocking signals
of the differential ratio Id2f/Id1f of the amplitudes of the second to the required output relays, if the differential
current Id2f/Id1f harmonic and the fundamental frequency current of the phase concerned is above the
component of the dif- ferential current. The value of the trip curve and if the operate signal
ratio to be used for block- ing is calculated as of the other phases is not active at the
a weighted average on the basis of the ratios same time. The blocking remains active until
between the second harmonic and the the ratio Id2f/Id1f falls below the blocking
fundamental frequency component cal- limit.
culated from the differential currents of the
three phases. The ratio between the second If the power transformer is connected against a
harmonic and the fundamental frequency fault in the protected area, the blocking based
com- ponent of the differential current of on the second harmonic of the differential
the con- cerned phase is of most weight current is inhibited by a special algorithm.
compared with the ratios of the other two The opera- tion of the relay will not be
phases. Using sepa- rate blocking for the delayed even if the differential current
individual phases and weighted averages contains a great amount of second harmonics
calculated for the separate phases provides a due to the connection inrush current. The
blocking scheme that is stable at connection operation of the blocking inhibit- ing
inrush currents. algorithm is based on the different wave-
form and the different rate of change of
The operation of the stabilized stage on the normal connection inrush current and
concerned phase is blocked if the weighted connection in- rush current containing fault
ratio of the second harmonic and the current. The algo- rithm does not eliminate
fundamental frequency component of the the blocking at con- nection inrush currents,
differential current of the concerned phase is unless there is a fault in the protected area.
above the set blocking limit Id2f/Id1f > and When required, the operation of the algorithm
if blocking is enabled can be disabled (switch SGF2/2).
Blocking based on Blocking of relay operation in situations of the value of the trip curve and no operate
the fifth harmonic overexcitation is based on the ratio Id5f/Id1f signal of the other phases is active at the same
of the differential of the amplitudes of the fifth harmonic and time.
current Id5f/Id1f the fundamental frequency component of the
dif- ferential current. The ratio is calculated The setting value Id5f/Id1f>> is used to
sepa- rately for each phase without weighting eliminate the blocking immediately if the
factors. Should the ratio exceed the setting ratio between the fifth harmonic and the
value of Id5f/ Id1f and blocking is enabled fundamental fre- quency component of the
through switch SGF2/3, the operation of the differential current approaches a dangerous
stabilized stage of the relay in the concerned level because of a high overvoltage. The
phase will be blocked. The blocking signal is blocking is eliminated, if ena- bled by switch
routed to the output relays determined by SGF2/4 (SGF2/4 = 1) and the ratio of the
SGR3, provided the dif- ferential current of fifth harmonic and the fundamental frequency
the phase concerned exceeds component is greater than the setting value of
Id5f/Id1f>>.
Differential current In addition to the stabilized stage the
stage 3 I>> relay includes an instantaneous differential The switchgroups SGR1...SGR8 can be used to
current stage 3 I>> which does not allow link the operate signals of the stabilized
for stabi- lization. This stage provides an differen- tial stage and the instantaneous
operate signal to the output relays selected differential stage, the internal blocking signals
with the switchgroup SGR2, when the and the external control signals BS1...BS5 to
amplitude of the fundamental frequency the desired signal outputs SS1...SS4 or
component of the differential current exceeds TS...TS4.
the set operate value Id/In>> or the
instantaneous value of the differential The switchgroup SGF4 allows a self-holding
current exceeds 2.5 x Id/In>>. The value can feature to be selected for the output signals
be set in the range 5...30 x In. The internal SS1...SS4 and TS1...TS4. When this function
blocking signals of the relay module do not has been selected, the output signal remains
prevent the operate signal of the differential
current stage 3 I>>. When required the
operate signal of the stage
Output signals
41 4
can be blocked by Should the fundamental frequency active though the signal that caused operation
the external component of the stabilizing current fall resets. The means of resetting the output
control signals below 30% of the fundamental frequency relays are shown in the table in paragraph
BS1...BS5 or the component of the dif- ferential current, a "Resetting".
intermodular fault has most certainly oc- curred in the
blocking signals BS area protected by the differential relay The operation of the TRIP operation
INT1...BS INT3. module. Then the operate value set for the indicator on the front panel can be
Blocking is stage 3 I>> will be automatically halved and configured to be initiated by the activation of
enabled via the internal blocking signals of the stabilized any TS signal. The operation indicator
switches stage will be inhibited. remains lit when the signal resets. The
SGB3/1...8. switchgroup SGF5 is used for pro- gramming.
The means of resetting are shown in the table
in paragraph "Resetting".
Circuit-breaker The differential relay module SPCD 3D53 is duty output relay TS1 of the circuit-breaker
failure protection provided with circuit-breaker failure protection failure protection can be used to operate the
(CBFP), which provides an operate signal TS1 circuit breaker in front of the circuit breaker
0.1...1 s after the operate signal TS2, TS3 or of the feeder of the object to be protected.
TS4, unless the fault has disappeared during The switches SGF3/1...3 are used to enable
this time. In the range 100...440 ms the the cir- cuit-breaker failure protection and the
operate time can be adjusted in steps of 20 ms switches SGF3/4...8 are used for setting the
and in the range operate time of the CBFP.
440....1000 ms in steps of 40 ms. The heavy-
Signals between the the logic active state of the external control
relay modules The signals BS INT1, BS INT2 and BS INT3 signals and the intermodular blocking signals.
are intermodular blocking signals which can So, the input can be activated when energized
be used to block the operation of a relay or when non-energized.
module located in another card location of
the same protection relay. An intermodular The signals AR1, AR2 and AR3 can be used
signal is acti- vated when the corresponding to trigger the disturbance recorder SPCR
blocking signal of one relay module is 8C27 fitted in one of the card locations of
activated. The blocking signals BS INT1, BS the relay. These signals cannot be used to
INT2 and BS INT3 are not capable of control the output relays.
controlling the output relays. The switches
SGB1/1...8 are used for the selection of
Second settings Two different setting values are available for the The S parameters allow the main setting
relay: main setting values and second values and second setting values to be read and
setting values. Switching between these two set over the serial bus. The push-buttons on
types of setting value can be done in three the front panel can be used for reading and
ways as follows: setting actual setting values only.
1) Over the serial bus, using command V150 N.B. If external control signals have been
2) By means of an external control signal: used for selecting main or second setting
BS1, BS2 or BS3 values, it is not possible to switch between
3) Via the push-buttons on the front panel of main settings and second settings via the
the relay module and subregister 4 of serial bus or the push-buttons on the front
register A. Selecting the value 0 for the panel.
subregister brings the main settings into
effect, whereas the value 1 activates the
second settings.
Resetting The operation indicators on the front panel with the push-buttons on the front panel, via
of the relay module, the operation codes on an external control signal or a serial
the display, latched output relays, and the communica- tion parameter as shown in the
registers of the relay module can be reset in table below.
three ways:
42 4
Means of resetting recording
RESET
PROGRAM
SGB6/1...3 = 1
SGB7/1...3 = 1
Parameter V101
Parameter V102
Integrated The integrated disturbance recorder records the V242 specifies whether the recording is to be
disturbance recorder waveforms of the currents to be measured, the started by the rising or falling edge of the
digital control inputs of the module and the signal specified by parameter V241.
internal signals. The module has six analog and Parameter V243 defines the control signals to
11 digital channels. The memory has a be used for trigger- ing, and parameter V244
capacity of one record the length of which is specifies whether the rising or falling edge of
38 cycles. The record has to be downloaded the control signal is to start the recording
before a new recording sequence can be sequence.
started. The memory is also emptied by
resetting the values recorded by the module. Parameter V245 is used for setting the length
The sampling frequency of the disturbance of the recording that follows triggering.
recorder is 40 times the rated fre- quency of The number of the recording cycles following
the module, that means that the sampling trig- gering is equal to the value of parameter
frequency at 50 Hz is 2000 Hz. V245. The total recording length is fixed and
always about 38 cycles.
The recording can be triggered by the
internal signals of the relay module or the When the serial communication parameter
control signals linked to the module. Internal V246
signals are the operate signals of the stabilized = 0, the disturbance recorder has not been
stage (3 I>) and the instantaneous stage (3 triggered, i.e. the recording memory is
I>>), plus the block- ing signal . The control empty. When V246 = 1, the disturbance
signals linked to the module are the signals recorder has been triggered and the memory
BS1...5 and BS INT1...3. Recording can be is full. The recording memory is emptied
triggered by the rising or falling edge of by giving the parameter V246 the value 0.
any (one or several) of these signals. The memory has to be empty before the
Triggering at rising edge means that the disturbance recorder is able to start a new
recording sequence starts when the signal is recording sequence. A memorized recording
activated. Correspondingly, triggering by fall- is indicated by the letter "d" to the right of
ing edge means that the recording sequence the display, when no measured, set or
starts when the active signal resets. recorded value is displayed.
The serial communication parameters V241... The recorded data of the built-in
V245 are used for configuring the disturbance recorder are downloaded, for
disturbance recorder. Parameter V241 instance, with the help of a PC program and
specifies the internal signals to be used for the serial communi- cation parameter V247.
triggering and parameter
43 4
Bloc
k
sche
mati
c
diag
ram
Fi SGF1/2=0 1f P/ I n, S, I 2tp / In
g. i 1- i 01
I d1f = I d
3.
Bl I L1
I /I
1 n i 1+ i 2
ib SGR1/1=1
oc i1 2 3I > trip SS1
&
k I L2
I / In >>
d
sc Y 1f SGR1/2=1
he I L3
I
I < 0.3 x I
ma
tic b b d
3I >> trip SGR2/2=1 1 TS1
dia SGF1/1=0 i2- i 02
gra
m I'
i d = i 1- i 2 I d2f / I
d1f SGR2/3=1
I /I > SS2
wi L1 2 n
2f SGF2/1=1 &
th I' L2
i2 +
-
I d2f &
sw Y SGR1/4=1
itc I' L3 SGR2/4=1 1 TS2
Inhibition of &
hg blocking
ro SGF2/2=1
up I /I > SGF6/1=1
def 5f
d5f d1f
1 AR1
SGF6/2=1
aul SGF1/3...8=0 I d5f SGF2/3=1
t &
set SGF7/3=1
tin 1 AR2
gs I d5f / I d1f >> 2nd or 5th
harmonic
blocking
SGF2/4=0 SGF5/1=1
SGF5/2=1 1
RESET TRIP
SPCD 3D53
11
n
SGF1/ 1f P/ I , S, 2tp
I /nI
2 I d1f =
i1 - i 01 Id SGF4/1 RESET +
PROGRA
i +i M
I 3I > trip
L1 i2 b 1 SGR1/x x=1 1 SS1
I1 / I n
I 2 &
L2 i1 1f SGF4/2 RESET +
I d / I n >> PROGRA
Y Ib I b < 0.3 x Id M
I 3I >> trip SGR2/
L3 x=2 1
x 1 TS1
t CBFP
Fi i -i
SGF1/ 2 02 SGF4/3
SGF5/1
g. 1
2f
Id2f / Id1f >
2nd or x=3 1
RESET +
PROGRA
M SGF3/4...8
4. I' L1 I2 / I n
id = i1 - i 2
SGF2/
1 5th SGR3/
SS2
harmonic x
Bl blocking
oc I' L2 &
I d2f
k Y
i2 +
- & SGF3/
1
SGF4/4 RESET +
PROGRA
M
sc I'L3 Inhibition
of blocking SGF2/2
1 TS2
he & x=4
SGF4/5
SGF5/2
ma SGF1/3...8
Id5f / I d1f > RESET +
PROGRA
tic 5f
1 M
dia x=5
for SGB1/2
SGB3/
x
Id5f / Id1f
>> x=6 TS3
dif
fer BS2
1
x=2 SGB4/1... SGF2/ SGF4/ SGF5/3
ent 3 Settings (main / 4 7
RESET +
ial
PROGRA
SGB1/3 SGB5/1... second) Reset trip M
3
rel BS3 1
indicator
Reset trip indicator
x=7 1 SS4
SGB6/1... RESET +
ay x=3
3
and output relays
Reset trip indicator, output
SGF3/
3
PROGRA
M
m SGB1/4 SGB7/1...
relays
SGF4/8
od 3
ule BS4 1
x=4
and registers (complete relay reset)
x=8 1 TS4
SP BS1 SGF5/
4
C SGB1/5
1
SGR4/x
SGR5/x
BS2
BS3
RESET
D BS5 x=5
SGR6/x BS4 TRIP
3 x=6
SGR7/x
3I > trip x=1
D BS INT1
SGB1/6
1
BS5
SGR8/x 3I >> trip x=2
SGF6/
x
AR1
AR2
53 SGF7/
x
2nd or 5th harm. bl. SGF8/
x=3 x AR3
SGB8/1 BS INT1
SGB1/7 BS1 x= 1
1 4
BS INT2
x=8
BS INT2
SGB8/3
1 BS INT3
SPCD 3D53
Symbols and signal IL1, IL
I’L1, I
abbreviations used I1
I2
In
i1
i2
i01
i02
id
ib
Id1f, Id
Ib
Id2f
Id5f
3 I>
3 I>>
SGF1.
SGB1
SGR1
BS1...
SS1...
TS1...
BS IN
AR1..
tCBFP
Note! wired to the terminals are shown in the
All input and output signals of the module are diagram illustrating the flow of signals between
not necessarily wired to the terminals of every the plug- in modules of the relay assembly.
relay assembly using this module. The signals
13 13
Front panel
3 I>
I1 Id I2
L1 L2 L3 IRF
Current measurement indicators
Indicator for setting the second turning point of the operation characteristic
I 2tp / I n
Indicator for setting the ratio of the fifth harmonic and the fundamental I d5f / I d1f > [ % ]
frequency component of the differential current (for setting the blocking and I d5f / I d1f >> [ % ]
deblocking operation)
I 1/ In
Indicator for transforming ratio correction of current transformers
on transformer HV side or generator neutral side
I2/ In
Indicator for transforming ratio correction of current transformers
SGF PROGRAM
on transformer LV side or generator network side
Indicator for checksums of switchgroups SGF1...11
SGB
Indicator for checksums of switchgroups SGB1...8
SGR
Indicator for checksums of switchgroups SGR1...8
TRIP
0021A
SPCD 3D53
3 I> Device symbol
I1 Id I2
L1 L2 L3 IRF
IRF indicator
Display
RESET
P / I n [ %]
STEP
I 2tp / I n
I d / I n >>
I1/ In
I2/ In PROGRAM
SGB
SGR
TRIP
Operation indicator
0021A
Code D
1 St
2 In
3 Bl
Ex
4 C
5 D
6
7
8
A
Yellow d
When the protection stage or the control the relay, an external control signal or over
signal resets, the TRIP indicator and the the serial bus, see the table in paragraph
red operation code remain lit. The "Descrip- tion of operation". Unreset
operation indicators can be reset via the operation indicators do not affect the
push-buttons on the front panel of operation of the relay module.
The self-supervision alarm indicator IRF the red indicator is
indi- cates internal relay faults. Once the lit. At the same
self-supervi- sion system of the relay time the relay
module has detected a permanent fault, module delivers a
signal to the self-supervision system output figure one and a green code number cannot
relay of the relay assembly. In addition, a be removed by resetting. It should be
fault code is lit on the display to show the recorded and stated when service is
type of the fault that has occurred. This ordered.
fault code that consists of a red
The table below shows the priority of the
opera- tion codes representing certain
events. If the priorities of the events to be
indicated are the same, the operation
indicator of the latest event is indicated on
the display.
6.
7.
Settings The setting values are indicated by the The second settings of the differential
three right-most digits on the display. relay module can be activated via
When a LED in front of a setting value subregister 4 of register A. The setting
symbol is lit it shows that the particular ranges are the same as those of the main
setting value is indicated on the display. settings. When the second settings are
The setting value given in parentheses active the LED representing the particular
under the setting range is the default setting value indicated on the display is
setting. flashing.
Setting
P/In(%)
S (%)
I2tp/In
Id/In>>
Id2f/Id1f>(%)
Id5f/Id1f>(%)
Id5f/Id1f>>(%)
I1/In
I2/In
L2
L3 L3
3 6 9 1,4,7 13,16,19 21
18 15 1,4,7 9 6 3 15 18 21 13,16,19
P2 P1 P2 P1 P2
L1 P1
P1 L1
S2 S1 P2 S1 S2
S2 S1
L2
S1 S2
L2
L3 L3
3 6 9 1,4,7 15 18 21
13,16,19 1,4,7 9 6 3 13,16,19 21 18 15
Yy6 Yy0
YNyn8 YNyn2
YNyn10 YNyn4
YNyn6 YNyn0
Yy0 Yy6
YNyn2 YNyn8
YNyn4 YNyn10
YNyn0 YNyn6
Yd1 Yd7
YNd1 YNd7
Yd5 Yd11
YNd5 YNd11
Yd7 Yd1
YNd7 YNd1
Yd11 Yd5
YNd11 YNd5
Dd6 Dd0
Dd0 Dd6
Dy1 Dy7
Dyn1 Dyn7
Dy5 Dy11
Dyn5 Dyn11
Dy7 Dy1
Dyn7 Dyn1
Dy11 Dy5
Dyn11 Dyn5
YNzn1 YNzn7
YNzn5 YNzn11
YNzn7 YNzn1
YNzn11 YNzn5
Dzn0 Dzn6
Dzn2 Dzn8
Dzn4 Dzn10
Dzn6 Dzn0
Dzn8 Dzn2
Dzn10 Dzn4
The switches SGF1/3...8 are used for compen- ential current and the stabilizing current are
sating the phase difference of the HV and LV calculated.
side phase currents that is caused by the
vector group of the power transformer. Vector group matching is not required if there
is no phase difference between the HV and
Vector group matching can be implemented LV side phase currents of the transformer to
both on the HV side and the LV side or only be protected. However, the zero-sequence
on the HV or the LV side. Vector group compo- nent of the phase currents on the star-
matching is almost always made on the star connected side that is earthed at its start
connected side of YNd and Dyn connected point has to be eliminated before the
transformers. Then the zero-sequence differential and stabilizing current are
component of the phase cur- rents at earth calculated. The switches SGF1/1...2 are used
faults occurring out of the protec- tion area is for eliminating the zero-sequence com- ponent
eliminated in the vector group match- ing on from the HV and/or LV side phase
the star connected side before the differ- currents.
If, for instance, there is an earthing transformer on quence component of the phase currents has to be
the delta-connected side of the YNd power separately selected with switch SGF1/1. No
transformer in the area to be protected, the interposing transformers are required for the
vector group matching is normally made on the side elimination of the zero-sequence component.
of the star connection. On the side of the delta The table below shows the function of the
connection elimination of the zero-se- switches SGF1/1 and SGF1/2.
SGF1/1 = 1
SGF1/1 = 0
SGF1/2 = 1
SGF1/2 = 0
The tables below show how the switches SGF1/ column "internal matching" shows the vector
3...8 can be used to set the vector groups for group matching implemented numerically in-
phase currents linked to the relay. The first side the relay module.
Internal matching
Yy0
Yd1
Yd5
Yy6
Yd7
Yd11
Internal matching
Yy0
Yd1
Yd5
Yy6
Yd7
Yd11
When the internal matching is Yy0 the phase quence component of the phase currents is not
angle of the phase currents connected to the relay eliminated. Then the switches SGF1/1 and
does not change. When the internal match- ing is SGF1/2 have to be used to eliminate the zero-
Yy6, the phase currents will be turned sequence component of the phase currents, when
180 in the relay. If the internal matching is required.
Yd1, Yd5, Yd7 or Yd11, a possible zero-seq-
uence component in the phase currents will be By using the tables 2, 3 and 4 it is possible to
eliminated in the numerically implemented delta program vector groups for the differential relay
connection before the differential current and the module other than those presented in table 1
stabilizing current are calculated. With the internal "Matching of the most general power trans-
matching Yy0 and Yy6 the zero-se- former vector groups".
Switchgroup SGF2 Internal blockings
Switch Function
SGF2
20
Switchgroup SGF3 Circuit-breaker failure protection (CBFP)
Switch
SGF3/1
signal TS2
SGF3/2
signal TS3
SGF3/3
SGF3/4...8
SGF3
Table 5. Circuit-breaker failure protection operate times to be selected with switches SGF3/4...8.
tCBFP / ms
100
120
140
160
180
200
220
240
260
280
300
320
340
360
380
400
420
440
480
520
560
600
640
680
720
760
800
840
880
920
960
1000
21 21
Switchgroup SGF4 Self-holding of output signals
Switch Function
SGF4
When a switch is
Switch
SGF5/
1
2
3
4
SGF5
Switchgroups Selection of the signals of the protection The signals of the protection stages and the
SGF6...11 stages and the external control signals control signals are linked with the desired
BS1...5 to be used as intermodular signals intermodular signal lines, for example, by encir-
AR1...3 and BS INT1...3. The signal
configuration is presented in Fig 8 below.
cling the number is marked at each intersection point checksums of the switchgroups are obtained
intersections and the weighting value of the switch is at the bottom of the matrix. The checksums
of the signal given on the right side of the matrix. By of the factory settings are given under the
lines. The adding the weighting values of the switches calculated checksums.
switch selected from each switchgroup the
Function/ Weighting
signal factor
3I> 1 1 1 1 1 1 1
trip
3I>> 2 2 2 2 2 2 2
trip
Harm. 3 3 3 3 3 3 4
block.
4 4 4 4 4 4 8
BS1
5 5 5 5 5 5 16
BS2
6 6 6 6 6 6 32
BS3
7 7 7 7 7 7 64
BS4
8 8 8 8 8 8 128
BS5
Factory
setting = 3 4 0 0 0 0
Switch Function
SGB1/1 Selection of activ
SGB1/2 Selection of activ
SGB1/3 Selection of activ
SGB1/4 Selection of activ
SGB1/5 Selection of activ
SGB1/6 Selection of activ
SGB1/7 Selection of activ
SGB1/8 Selection of activ
SGB1
Switchgroup The switchgroups SGB2...7 are used to selected switches for each switchgroup gives
SGB2...7 configure the functions of the control signals the switchgroup checksums at the bottom of
BS1...5 and BS INT1...3. The matrix below the matrix. Switches not mentioned are not in
can be used for configuring the signals. The use and should be in position 0.
control signals are linked with the desired
function by marking the intersections of the Note!
lines. The switch number is marked at each Before programming it should be checked
intersection point and the corre- sponding whether all control signals of the relay
weighting factor to the right of the matrix. module SPCD 3D53 are used in the relay.
Adding the weighting factors of the
RESET
3I> Indicators,
trip
Control
s ignals
BS1
BS2
BS3
BS4
BS5
BS
6
INT1
BS
7
INT2
BS 128
8 8
INT3
Factory
setting = 0 0 0 0 0 0
SGB2
SGB3
SGB4/1...3
SGB5/1...3
SGB6/1...3
SGB7/1...3
Switchgroup SGB8 The active logic state of the blocking signals ule in relation to the logic state of the
BS INT1, BS INT2 or BS INT3 of the relay signal linked to the blocking signal.
mod-
Switch Function
SGB8/3
SGB8/4
SGB8/5
SGB8/6
SGB8/7
SGB8/8
SGB8
Switchgroups The switches SGR1...8 are used to configure TS1...TS4 by encir- cling the intersections of
SGR1...SGR8 the operate signals of the protection stages the signal lines. The switch number is marked
and the control signals to operate as at each intersection point and the weighting
desired output signals SS1...SS4 or value of the switch is
TS1...TS4.
Output signal
Switch- Function/ Checksum
group control signal (factory setting)
3I>
SGR1 trip 1
3I>>
SGR2 trip
1
SGR3 1
block.
SGR4 BS1
SGR5 BS2
SGR6 BS3
SGR7 BS4
SGR8 BS5
Weighting factor
Fig. 10. Output relay matrix for differential relay module SPCD 3D53.
Switchgroup SGX
Switch
Measured data Measured values are indicated by the three Note! The measured data displayed consider
green right-most digits on the display. Data the effect of the transforming ratio corrections
LED
that isSGX/1
currently being measured is indicated by Red
indicator I1/In and I2/In. The phase difference displayed
symbol
a LED above the display and by a red digit or is the phase difference of the currents after
letter to the left on the display. vector group matching.
L1
L2
Measured data of SGX/2..8
main menu L3
L1
L2
L3
L1
L2
L3
Measured data of The measured data of the submenu are de- register in the subregister of which the con-
submenu scribed in the table below. The red symbol cerned measured data is available.
displayed on main menu level shows the main
L1
L2
L3
L1
L1, L2
L2, L3
LED Main menu
indicator
L1, L3
L2
L1
L2
L3
L3
L1, L2
L2, L3
L1, L3
L1
L2
L3
29
Recorded The information recorded is stored in a Note!
information pushdown storage either at the moment of Minimum value of the ratio of the second
(modified 2004-04) the relay operation, registers 1…6, or during harmonic and the fundamental frequency
trans- former connection inrush, registers 7… com- ponent of the differential current is
9. The pushdown storage contains the five recorded in each phase without using any
latest values recorded (n)...(n-4). Each new weighting coeffi- cients.
value is stored in the first location (n) in the
storage and pushes all the previous items one Note!
step forward (n-1). When a sixth item is stored Recorded information can be stored to non-
the oldest item (n-4) of the memory is lost. volatile memory by setting SGX/1 in position 1.
By factory settings, SGX/1 is in position 0, re-
The most recently stored values (n) are corded information is cleared after a loss of
available in the main registers. Maximum aux- iliary power supply.
four of the previous values are in the
subregisters. The left- most digit indicates the
address of the storage location and the other
three digits the numerical value of the
parameter recorded.
Register Recorded va
number
1 Differential c
Differential c
2 Differential c
Stabilizing cu
3 Stabilizing cu
Stabilizing cu
4 Minimum va
Minimum va
5 Minimum va
30 30
Register Record
number
0 Status
Con
From
A detai
The ad
A cont
1. Sett
2. Bus
3. Pass
4. Sele
Def
5. Hz
A 6. mH
So,
7. Che
When the display is dark, access to the begin- tion parameter, see section "Resetting" in para-
ning of the main menu is gained by pressing graph "Description of function". In case
the STEP push-button on the front panel for storing of the recorded value into non-volatile
more than 0.5 s. Pressing the push-button memory function is not use (SGX/1 = 0), the
for less than 0.5 s gives direct access to the registers are also cleared by an auxiliary power
end of the main menu of the relay module supply failure. The setting values, the address
(Serial commu- nication address). code, the data transfer rate and the password of
the relay module are not affected by voltage
The information recorded in registers 1...9 can failures. Instructions for setting the address code
be reset using the push-buttons on the front and data transfer rate are given in the
panel, an external control signal, or a serial document "General characteris- tics of D-type
communica- relay modules".
Main menus MAIN MENU SUBMENU
and submenus
of
settings STEP 0.5
s
PROGRAM 1
s
REV. STEP 0.5 s FWD. STEP 1 s
Normal status, display
and off 0
registers
1
H.V. side
H.V. side
1 current on
current
phase L1
[x In] on phase
L1 [% In]
H.V. side
1 current on H.V. side
phase L2 0 current
[x In] on phase
L2 [% In]
H.V. side
1 current on H.V. side
phase L3 0 current
[x In] on phase
L3 [% In]
0
Diff. current on
phase L1 [x In] Diff. current on phase L1 Phase angle
d
diff. 11 between
phases L1-L2
Diff. current on [% In]
d phase L2 [x In]
Phase angle
Diff. current on phase L2 diff. 12 on phase
0 L1
1
[% In]
Diff. current on
d phase L3 [x In] Diff. current on phase L3 Phase angle
1 diff. 22 between
phases L1-L2
[% In]
0
0
L.V. side
L.V. side
2 current
current
on phase
L1 [x In] on phase
L1 [% In]
L.V. side
0
current
2 L.V. side
current on phase
on phase L3 [% In]
L3 [x In]
B
a
si
c
s
et
ti
n
g
P
/I
n[
%
]
S
t
a
r
t
i
n
g
r
a
t
i
o
S
[
%
]
2
n
d
t
u
r
n
p
o
i
n
t
o
f
t
h
e
t
r
i
p
p
i
n
g
c
u
r
v
e
I
2
t
p
/
I
n
R E
High set stage
V. starting value
Id/In>>
STE
P
2nd harmonic
0.5 blocking threshold
Id2f/Id1f> [%]
s
5th harmonic
blocking threshold
Id5f/Id1f> [%]
CT ratio
correction
I1/In
5th harmonic
1 unblocking
threshold
Id5f/Id1f>>
[%]
M
CT ratio
A correction
I I2/In
Functional Functional Functional
2 switchgroup 3 switchgroup 4 switchgroup
SGF2 SGF3 SGF4
Functional
N switchgroup
1 SGF1 Blocking Blocking Blocking
M 2 switchgroup 3 switchgroup 4 switchgroup
E SGB2 SGB3 SGB4
N Blocking
U 1 switchgroup
SGB1 Relay matrix Relay matrix Relay matrix
F 2 switchgroup 3 switchgroup 4 switchgroup
SGR2 SGR3 SGR4
Relay matrix
switchgroup 1
SGR1 Diff. current on phase Diff. current on phase L1
W 2 L1 Diff. current on phase L1 3 at n-3 trip
D. 1
Diff. current on phase at n-1 trip at n-2 trip
S
L1 at latest (n:th) trip
T
E 1
P
Diff. current on phase L2 Diff. current on phase L2 Diff. current on phase L2
3 at n-3 trip
1 Diff. current on
phase L2 2 at
s 1 2
latest (n:th) trip at n-1 trip at n-2 trip
Diff. current on phase L3
3 at n-3 trip
Diff. current on phase L3 Diff. current on phase L3
Diff. current on 1 2
3 phase L3 at
at n-1 trip at n-2 trip
Bias current on phase L1
latest (n:th) trip
Min. 2nd harmonic content Min. 2nd harmonic content Min. 2nd harmonic content
1 2
of n-1 inrush on phase L1
Min. 2nd
7 harmonic content 3
of latest inrush on of n-3 inrush on phase L1
phase L1 of n-2 inrush on phase L1
Min. 2nd harmonic content
1 of n-1 inrush on phase L2
Min. 2nd harmonic content
Min. 2nd 2 Min. 2nd harmonic content 3 of n-3 inrush on phase L2
8 harmonic content Min. 2nd harmonic content of n-2 inrush on phase L2
of latest inrush on 1 of n-1 inrush on phase L3
phase L2
Min. 2nd harmonic content
2 Min. 2nd harmonic content 3 of n-3 inrush on phase L3
of n-2 inrush on phase L3
Min. 2nd
9 harmonic content
of latest inrush on
phase L3
Status of
0 external relay
blocking / 0 IRF Id > Id >> Id2f> BS1 BS2 BS3 BS4 BS5
control signals 000
Fig. 11. Main menus and submenus for settings and registers of differential relay
module
SPCD 3D53.
The procedure for entering a "General characteristics of D-
submenu or a setting mode and type SPC relay modules.
for configuring the module is Below a simplified instruction.
described in detail in the manual
34 SPC 3 ENG
Functional
5 switchgroup Functional Functional
SGF5 6 switchgroup 7 switchgroup 8 Function
SGF6 SGF7 al
switchg
roup
SGF8
Functional
9 switchgrou Functional
p SGF9 0 switchgroup II Functiona
SGF10 l
switchgr
oup
SGF11
Blocking
5 switchgroup Blocking Blocking Blocking
SGB5 6 switchgroup 7 switchgroup 8 switchgr
SGB6 SGB7 oup
SGB8
Relay matrix
5 Relay matrix Relay matrix Relay
6 switchgroup 7 switchgroup 8 matrix
switchgroup SGR5 SGR7 switchg
SGR6 roup
SGR8
Diff. current on
4 phase L1 at n-4
trip
4 Diff
.
cur
ren
t
on
ph
as
e
L2
at
n-4
trip
4 Diff
.
cur
ren
t
on
ph
as
e
L3
at
n-4
trip
Bia
4
s
curr
ent
on
pha
se
L1
at
n-4
trip
Bia
4
s
curr
ent
on
pha
se
L2
at
n-4
trip
Bia
4
s
curr
ent
on
pha
se
L3
at
n-4
trip
Min.
2nd
harm
onic
conte
4 nt
of n-
4 inrush
on phase
L1
Min.
4 2nd
har
moni
c
cont
ent
of n-
4
inrus
h on
phas
e L2
Min.
4 2nd
har
moni
c
cont
ent
of n-
4
inrus
h on
phas
e L3
Selection of main vs
4 second settings 5 Nominal frequency Nominal frequency
Switchgroup SGX
6 7
setting, Hz -part setting, mHz -part
Testing of In the test mode, entered from the supervision output is tested. The LEDs in
output relays submenu of register 0, it is possible to front of the settings show the output
activate the output signals of the relay one signals to be activated at the moment.
by one. The desired output signal is selected by
pressing PROGRAM for about one
When the PROGRAM push-button is second.
pressed for about five seconds the three
digits to the right start flashing as an The setting LEDs on the front panel and
indication of the relay module being in their respective output signals are as
the test mode. Initially, the self- follows:
Pressing the push-buttons STEP and When the push-button STEP is being
PRO- GRAM simultaneously activates pressed in the test mode, the self-
the selected output signal, which supervision output relay operates in about
remains active as long as the push- 1 second and remains oper- ated until the
buttons are being pressed. The effect on push-button is reset. Return
the functions of the output relays to the main menu is possible at any stage
depends on the settings of the of the test sequence by pressing the
switchgroups SGR1...SGR8. PROGRAM push- button for about five
seconds.
STEP
STEP & STEP & STEP
PROGRA PROGRA &
S M M PROG
RAM
T
E
P
&
P
R
O
G
R
A
M
Fig. 12. Sequence for selecting output signals during testing of the output relay control
functions.
Technical data
Note!
Operate times are valid at rated frequency 50 Hz and 60 Hz.
Serial Special codes have been specified to represent In channel 0 operation or signal activation of
communication different events such as operation and blocking one phase alone is enough to cause an event. A
parameters of protection stages, activation of control and condition for resetting, on the other hand, is
output signals, etc. These event codes can be that the operations or signal activations of all
Event codes transferred to higher-level systems over the se- phases have reset.
rial bus.
An event to be included in event reporting is
The event mask V155 is available on the chan- marked with 1. The event mask is obtained
nels 0, 1, 2 and 3 so that the event mask by adding the weighting factors of the events
0V155 is shared by all phases and the in- cluded, see the tables below.
event masks
1V155, 2V155 and 3V155 represent events on
the respective phases L1, L2 and L3.
Event mask
0V155
1V155
2V155
3V155
V156
V157
V158
Channel Code
0 E1
0 E2
0 E3
0 E4
0 E5
0 E6
0 E7
0 E8
0 E9
0 E10
1...3 E1
1...3 E2
1...3 E3
1...3 E4
1...3 E5
1...3 E6
1...3 E7
1...3 E8
Channel Code
0 E11
0 E12
0 E13
0 E14
0 E15
0 E16
0 E17
0 E18
0 E19
0 E20
0 E21
0 E22
0 E23
0 E24
0 E25
0 E26
0 E27
0 E28
0 E29
0 E30
0 E31
0 E32
0 E33
0 E34
0 E35
0 E36
E50
E51
E52
E53
E54
The event codes E50...E54 and the events rep- The event codes E52...E54 are generated by the
resented by these cannot be excluded from control data communicator (e.g. SRIO
re- porting. The capacity of the event register 1000M).
is 60 events.
Data to be In addition to event codes input data (I range 1...999. The default setting of the
transferred data), output data O data), setting password is 1.
over the serial values (S data) memorized data (V data),
bus and some other data can be read from the The password is opened by giving the
module over the serial bus. The setting of serial communication parameter V160 the
parameters marked with the letter W can desired numerical value. Parameter V161
be changed over the SPA bus. is used for
Measured data
39
Output data The actual status data provide after the latest reset of the registers. When the
information about the current status of the value is 0, the signal is not activated and when
signals at the moment. The operations stored the value is 1, the signal is activated.
in the memory indicate those signal
activations which has taken place
Protection stage/
signal
Signal activations
Output signal
The parameters V11...V59 can be used to read (R) n-1 = the value before that, and so on. The
the latest five values stored in the registers. Event n registers are described in detail in the paragraph
= the most recent value recorded, event "Recorded information".
42 42
Value measured
43 43
Setting values
Setting
Checksum, SGF1
Checksum, SGF2
Checksum, SGF3
Checksum, SGF4
Checksum, SGF5
Checksum, SGF6
Checksum, SGF7
Checksum, SGF8
Checksum, SGF9
Checksum, SGF10
Checksum, SGF11
Checksum, SGB1
Checksum, SGB2
Checksum, SGB3
Checksum, SGB4
Checksum, SGB5
Checksum, SGB6
Checksum, SGB7
Checksum, SGB8
Checksum, SGR1
Checksum, SGR2
Checksum, SGR3
Checksum, SGR4
Checksum, SGR5
Checksum, SGR6
Checksum, SGR7
Checksum, SGR8
42
Control parameters
Data
Resetting of front panel operation indicators and latched output relay Resetting of front panel operati
Switchgroup SGX
EEPROM formatting
Error code
Rated frequency, Hz setting Rated frequency, mHz setting Address of relay module
43 43
Data
Internal signal
3 I>
3 I>>
Id2f/Id1f blocking
Id5f/Id1f blocking
Internal signal
3 I>
3 I>>
Id2f/Id1f blocking
Id5f/Id1f blocking
Control signal
BS1
BS2
BS3
BS4
BS5
BS INT1
BS INT2
BS INT3
Internal signal
BS1
BS2
BS3
BS4
BS5
BS INT1
BS INT2
BS INT3
The event register can be read by the L com- 1000M reads the event data and forwards the
mand only once. Should a fault occur, say, in information to an output device. Under
the data transfer, the B command can be used normal conditions the event register of the relay
to re- read the contents of the register. module is empty. The control data
When re- quired, the B command can be communicator also resets abnormal status
repeated. In general, the control data data, so this data is nor- mally zero.
communicator SRIO
Fault codes
1 Auxiliary voltage interrupted
4 Faulty trip relay path, TS1, or missing output relay card
5 Faulty trip relay path, TS2, or missing output relay card
6 Faulty trip relay path, TS3, or missing output relay card
7 Faulty trip relay path, TS4, or missing output relay card
20 The module has restarted, although no fault was detected by the self-
supervision system.
21 The module has restarted more than 10 times, although no fault was detected by
the self-supervision system.
23 Error during start-up of DSP
24 DSP halted due to unknown error
29 DSP code memory area checksum
30 Faulty program memory (EPROM)
49 DSP internal RAM faulty
50 MCU internal RAM faulty
51 Parameter memory (EEPROM) block 1 faulty
52 Parameter memory (EEPROM) block 2 faulty
53 Parameter memory (EEPROM) block 1 and block 2 faulty
54 Parameter memory (EEPROM) block 1 and block 2 faulty, different checksums
55 Faulty parameter area in RAM
56 Parameter memory (EEPROM) key fault. Parameter memory not formatted.
57 Gain/channel correction value checksum
58 Active setting bank checksum
59 DSP external RAM faulty
60 MCU external RAM faulty
100 DSP overloaded
195 The analog supply voltage measured is too low (rated voltage -12 V)
196 The analog supply voltage measured is too low (rated voltage +12 V)
203 The analog supply voltage measured is too high (rated voltage -12 V)
204 The analog supply voltage measured is too high (rated voltage +12 V)
252 Input filter faulty
253 A/D converter faulty
254 DSP does not interrupt
SPCD 2D55
Earth-fault relay module
User´s manual and Technical description
I 01 >
I 02 >
I1 I2
I 01 I d1 I d2 I 02 IRF
P 1 /I n [ % ]
RESET
t 01 > [ s ]
STEP
P 2 /I n [ % ]
t 02 > [ s ]
I 01 / I n
I 01 / I 1 [%]
I 02 / I n
I 02 / I 2 [ % ]
I 2f / I 1f (I 01 ) >
[ %]
I 2f / I 1f (I 02 ) >
[ %]
I 1 /I n
I 2 /I n PROGRAM
SGF
SGB
SGR
TRIP
0029A
SPCD 2D55
1MRS 750098-MUM EN
SPCD 2D55
Issued 1996-10-14
Modified 2004-04-27
Version B (replaces 34 SPCD 3 EN1)
Earth-fault relay module
Checked PS
Approved MÖ
Contents Features
...................................................................................................................... .... 3
Description of function
.................................................................................................. 3
Rated frequency
.....................................................................................................
.... 4
Stabilized differential current principle
...................................................................... 4
Residual overcurrent principle and neutral current principle
..................................... 5
High-impedance principle
......................................................................................... 5
Blocking based on the second harmonic of the neutral
current .................................. 6
Protection stages
.....................................................................................................
... 6
External control
signals ............................................................................................
.. 7
Intermodular signals
.................................................................................................. 7
Output signals
.....................................................................................................
...... 7
Circuit-breaker failure protection
.............................................................................. 7
Second settings
.....................................................................................................
..... 7
Resetting .......................................................................................
............................ 8
Integrated disturbance recorder
................................................................................. 8
Block schematic diagram
................................................................................................ 9
Symbols and signal abbreviations used
.......................................................................... 11
Front panel
........................................................................................................
........... 12
Operation indicators
.....................................................................................................
13
Settings ............................................................................................
............................. 15
Configuration switches (modified 2004-04)
.................................................................. 16
Measured data
.........................................................................................................
..... 25
4 4
Recorded values
.........................................................................................................
... 26
Main menus and submenus for settings and
registers .................................................... 28
Testing of output relays
................................................................................................ 30
Technical data
.........................................................................................................
..... 31
Serial communication parameters
................................................................................. 33
Event codes
.....................................................................................................
........ 33
Remote transfer
data ...............................................................................................
. 35
Fault codes of self-supervision system
........................................................................... 42
Features Earth-fault relay module for the earth-fault pro- Display of measured, set and recorded
tection of two-winding power transformers values
Provides protection for both HV and LV Writing and reading of setting values via
side windings local display and front panel push-buttons,
a PC with configuration software, or from
The earth-fault protection can be higher system levels over the serial port and
implemented by four principles: the high- optical fibres.
impedance princi- ple, the numerical stabilized
differential current principle, the residual Five programmable external control inputs
overcurrent principle, or the neutral
overcurrent principle Output relay matrix allowing the operate and
control signals to be linked to the desired
The earth-fault protection principles to be output relay
used on the HV side and the LV side are
independent of each other Integrated circuit breaker failure protection
The relay module is entirely numerical - the Integrated disturbance recorder capable of re-
fundamental component of the currents are cording six phase currents, two neutral
used for calculating the residual current of the currents, the internal start and blocking
phase currents, the neutral current and the signals, and the control signals linked to the
differential and stabilizing currents. The DC relay
component and the harmonics of the currents
are digitally filtered. High immunity to electrical and electromag-
netic interference allows the relay to be used
Separately adjustable basic setting and in severe environments
operate time for HV and LV side
Dynamic measuring
High immunity to electrical and electromag- functions
netic interference allows the relay to be used
in severe environments High availability - the integrated self-supervi-
sion system monitors the operation of the
Stabilized against transformer inrush electronics and the software and gives an
currents and faults outside the protected area alarm signal in the event of a fault.
Description of function
4 4
The earth-fault (low-impedance type protection) The stabilized differential current principle, the
relay measures the - the residual overcurrent residual overcurrent principle and the
HV and LV side principle neutral overcurrent principle are based on
phase currents - the neutral overcurrent the funda- mental frequency components of
and neutral principle the currents measured. The fundamental
currents of the - the high-impedance principle frequency compo- nents are digitally filtered
transformer. Four in the relay module. The high-impedance
alternative The protection principle to be used depends principle is based on the instantaneous peak
principles can be on the connection of the windings of the values of the measured cur- rent.
used for power transformer and on the requirements
implementing the for the earth-fault protection. The switches SGF1/1...8 are used to select
HV side and LV the desired protection principle. The
side earth-fault protection stages of the HV side and the LV
protection of the side operate quite independently of each
transformer to be other, so the pro- tection principle used on the
protected: HV side can be the same as that used on the
LV side, or another. At the same time,
- the stabilized however, one protection princi- ple only can
differential be used on one or the other side of the
current principle transformer.
Rated frequency The earth-fault relay module can be used in The frequency is selected with the push-
the frequency range 16 2/3....60 Hz. The rated buttons on the front panel, via subregister 5
fre- quency setting is accurate to within 1 and 6 in register A, or over the serial bus, in
mHz. Two settings are available, i.e. Hz and which case the parameters V180 and V181
mHz, which are separately set from 16.667 are used.
Hz up to 60 Hz.
Stabilized The numerical stabilized differential current The stabilizing current Ib used with the
differential principle is selected for the earth-fault stabiliz- ing differential current principle is
current protec- tion on the HV side and on the LV calculated as an average of the phase currents
principle side with the settings SGF1/1 = 1 and on the side of the winding to be protected:
SGF1/5 = 1, respec- tively. No external
stabilizing resistor or non- linear resistor is IL1 + IL2 + IL3
required. Ib =
(2)
Operation according to the differential current 3
principle is based on comparing the amplitude The basic settings P1/In and P2/In are used
and phase difference between the sum of the for setting the characteristic of the stabilized
fundamental frequency zero-sequence currents differ- ential current principle. The
of the phase currents ( I) and the differential current value P1/In or P2/In
fundamental frequency component of the required for tripping is constant at the
neutral current (I0) flowing in the conductor stabilizing current values Ib/In =
between the trans- former neutral point and 0...1. When the stabilizing current is higher
earth. The differential current Id is calculated than the rated current, the slope of the
as the absolute value of the difference between operation characteristic is constantly 50% as
the residual current (i.e. the sum of the zero- shown in Fig.
sequence currents in the phases) and the 1. That means that the relationship between
neutral current. the change in the directional differential
current Idcos and the change in the
Id = I - I0 (1) stabilizing cur- rent Ib is constant.
An earth fault occurring in the protected
area (that is, between the phase CTs and the Id cos
neutral connection CT) will cause differential In
current. In addition, the direction of the
residual current and the neutral current and 1.5
Ib
also the ratio of the neutral current and the 1.0 In
residual current (I0/ I) on the side to be P / In
protected have to be considered in order to 0.5
maintain selectivity. Ib
0.0
5 5
In
During an earth fault in the protected area the 0.0 1.0 2.0 3.0
current is In
180 , that is, when the currents are in
opposite direction at earth faults within the 1.5
be- tween the residual current and the neutral 0.0 1.0 2.0 3.0 In
Residual overcurrent Should the transformer have no star point, the earth- fault. The sum of the zero-sequence
principle and neutral star point be unearthed or no neutral current currents in the phases is calculated inside the
current principle be available, the residual overcurrent principle relay module on the basis of the phase currents
can be employed for the protection against linked to the relay. The overcurrent principle is
5 5
used on the HV side, The residual current of the phase currents the neutral current can be used in
when SGF1/2 = 1, and can also be formed via an external combination with these types of protection.
on the LV side, when connection by connecting the neutral
SGF1/6 = 1. The terminals of the windings of the relay’s phase
protection stage current matching transform- ers to the 5 A
starts when the or 1 A terminal of the neutral current
amplitude of the matching transformer I01 or I02. Natu- rally,
fundamental fre- it is also possible to connect the neutral
quency component of current of the neutral connection current
the residual current trans- former to the terminals, and use the
ex- ceeds the basic neutral overcurrent principle. When external
setting P1/In or P2/In. summing of the phase currents or the
When the residual neutral current principle is used on the HV
current I1 or I2 is side, the switch SGF1/3 has to be in
calculated from the position 1.When external summing of the
phase currents inside phase currents or the neutral current
the relay module the principle is used on the LV side, the switch
blocking based on the SGF1/7 has to be in position 1. The
second harmonic of blocking based on the second harmonic of
the neutral current
cannot be used.
5 5
LV side protection principle I02>
No protection Stab. diff. current principle
Residual overcurrent principle
Neutral current principle
High-impedance principle
Protection stages Switchgroup SGR1 is used to link the start eration is not inhibited by an external control
signals of the HV side protection stage I01> signal or an intermodular blocking signal.
to the specified output relays, provided starting
is not inhibited by a blocking function based In the same way the LV side protection stage
on the ratio of the second harmonic and the I02> delivers an operate signal to the output
funda- mental frequency component of the relays specified by switchgroup SGR5,
neutral current. Correspondingly, provided
switchgroup SGR4 is used to link the start operation is not
signals of the LV side protection stage I02> inhibited.
to the specified relays.
The blocking of the HV side protection
The operate time can be separately set for the stage, I2f/I1f (I01)>, is routed to the output
HV and LV side in the setting ranges t01> relays specified by switchgroup SGR3,
= provided the HV side start conditions are
0.03...100 s and t02> = 0.03...100 s, respec- fulfilled. In the same way the blocking of the
tively. When the operate time t01> of the HV LV side protection stage, I2f/I1f (I02)>, is
side protection stage I01> has elapsed, the routed to the output relays specified by
stage switchgroup SGR6, provided the LV side
delivers an operate signal to the output relays start conditions are fulfilled.
specified by switchgroup SGR2, provided
op-
External control Five external control signals BS1...BS5 are
signals avail- able to the earth-fault relay module The switchgroup SGF4 allows a latching
SPCD 2D55. The control signals can be used feature to be selected for the output signals
to control the output signals or block the SS1...SS4 and TS1...TS4. When this function
operation of the module (protection stages). has been selected, the output signal remains
In addition the con- trol signals BS1, BS2 and active, even though the signal that caused
BS3 can be used for the operation
Intermodular signals
The signals BS INT1, BS INT2 and BS INT3
are intermodular blocking signals which can
be used to block the operation of a relay
module fitted in another card location of
the same protection relay. An intermodular
blocking sig- nal is activated when the
corresponding block- ing signal of one relay
module is activated. The blocking signals BS
INT1, BS INT2 and BS INT3 are not
capable of controlling the output relays.
Switchgroup SGB1 is used for selecting
Output signals
Circuit-breaker The relay module is provided with circuit- TS1 of the circuit-breaker failure protection
failure protection breaker failure protection (CBFP), which can be used to operate the circuit breaker in
provides an operate signal TS1 0.1...1 s front of the circuit breaker of the feeder of
after the operate signal TS2, TS3 or TS4, the object to be protected. The switches
unless the fault has disappeared during this SGF3/1...3 are used to enable the circuit-
time. In the range breaker failure protection and the switches
100...440 ms the operate time can be adjusted SGF3/4...8 are used for setting the operate
in steps of 20 ms and in the range 440....1000 time of the CBFP.
ms in steps of 40 ms. The heavy-duty output
relay
Second settings Two different setting values are available for the The S parameters allow the main setting
relay: main setting values and second values and second setting values to be read and
setting values. Switching between these two set over the serial bus. The push-buttons on
types of setting value can be done in three the front panel can be used for reading and
ways as follows: setting actual setting values only.
1) Over the serial bus, using command N.B. If external control signals have been
V150 used for selecting the main or second settings,
2) By means of an external control signal: it is not possible to switch between main
BS1, BS2 or BS3 settings and second settings via the serial bus
3) Via the push-buttons on the front panel of or the push- buttons on the front panel.
the relay module and subregister 4 of
register A. Selecting the value 0 for the
subregister brings the main settings into
effect, whereas the value 1 activates the
second settings.
Resetting The operation indicators on the front panel can be reset in three ways: with the push-
of the relay module, the operation codes on buttons on the front panel, via an external
the display, latched output relays, and the control signal or a serial communication
registers and the recording memory of the parameter as shown in the table below.
relay module
Means of resetting
RESET
PROGRAM
RESET & PROGRAM
External control signal
BS1, BS2 or BS3, when
SGB5/1...3 = 1
SGB6/1...3 = 1
5 5
SGB7/1...3 = 1
Parameter V101
Parameter V102
Integrated The integrated disturbance recorder records the recorder. Parameter V241 specifies the internal
disturbance waveforms of the currents to be measured, the signals to be used for triggering and
recorder digital control inputs of the module and the parameter V242 specifies whether the
internal signals. The module has eight recording is to be started by the rising or
analog and 12 digital channels. The falling edge of the signal specified by
memory has a capacity of one record the parameter V241. Parameter V243 defines the
length of which is 30 cycles. The recording control signals to be used for trigger- ing, and
has to be downloaded before a new recording parameter V244 specifies whether the rising
sequence can be started. The memory is also or falling edge of the control signal is to start
emptied when the values recorded by the the recording sequence.
module are reset. The sampling frequency of
the disturbance recorder is 40 times the Parameter V245 is used for setting the length
rated frequency of the module, which means of the recording. The number of the
that the sampling frequency at 50 Hz is recording cycles following triggering is equal
2000 Hz. to the value of parameter V245. The total
recording length is fixed and always about 30
The recording can be triggered by the internal cycles.
signals of the relay module or the control
signals linked to the module. Internal When the serial communication parameter
signals to be recorded and available for V246 = 0, the disturbance recorder has not
triggering are the start signals of the HV side been triggered, i.e. the recording memory is
and LV side earth-fault protection, and the empty. When V246 = 1, the disturbance
HV and LV side blocking signals. The recorder has been triggered and the memory
control signals linked to the module are the is full. The recording memory is emptied by
signals BS1...5 and BS INT1...3. Re- giving param- eter V246 the value 0. The
cording can be triggered by the rising or memory has to be empty before the
falling edge of any (one or several) of these disturbance recorder is able to start a new
signals. Triggering at rising edge means that recording sequence. A memorized recording
the record- ing sequence starts when the signal is indicated by the letter "d" to the right of
is activated. Correspondingly, triggering by the display, when no measured, set or
falling edge means that the recording recorded value is displayed.
sequence starts when the active signal resets.
The recorded data of the integrated
The serial communication parameters V241... disturbance recorder are downloaded, for
V245 are used for configuring the instance, with the help of a PC program and
disturbance the serial communi- cation parameter V247.
5 5
Bloc
k
sche
mati
c
diag
ram
Fig.
3. I1 / I n
I b1 SGF1/1
I 01 > start t
Block I L1 I d1 = I 1 - I 01
P1 / I n
01 >
sche 1f
+
I 01 > trip
SGR2/2=1
matic I
L2 I1
- * & 1 &
1
SGR5/2=1 TS1
diagra I L3 I 01/ I 1
cos
m for
earth-
fault I 01/ I n SGF2/1 +180 1f
SGF1/2
SGR2/4=1
relay I 01
SGR5/4=1 1 TS2
modu
le SGF1/3
SPC
D SGF1/4
2D55 2f I 2f / I 1f > (I 01) I
02
> start SGR1/5=1 SS3
with SGF2/3 SGR4/5=1 1
switc 1f
I b2 SGF1/5
hgrou I2 / I n
p I'L1 1f
P2 / I t 02 >
SGR2/7=1
defau n
lt Id2 = I 2 - I 02
I'L2 & I 02 > trip SS4
setti I2
+
* 1 &
SGR5/7=1
1
I'L3
ngs - I02 / I 2
cos
SGF2/2 SGF1/6
SGF8/1=1
I 02/ I n +180
1f SGF8/2=1
I 02 1 AR3
SGF8/4=1
SGF1/7
SGF8/5=1
SGF1/8 SGF5/1=1
2f I 2f / I 1f > SGF5/2=1 1
SGF2/4 (I 02)
RESET TRIP
SPCD 2D55
9
I1 / I n 1f I 01 > start SGR1/
I b1 x
SGF1/1
P1 / I t 01 > RESET +
Id1 = I 1 - I 01 SGF4/
I 1
PROGRAM
L1 n
I L2 1f
I1
I 01 > trip
I L3 + & SGR2/ x=1
Fi * 1 &
- x 1 SS1
RESET +
PROGRAM
g.
I 01/ I 1
cos
SGF4/2
I01 / I n SGF2/1 +180 1f SGF1/2
t CBFP 1
4. I
01
x=2
1
SGF5/
1 TS1
Bl SGF1/
3 SGF4/3
RESET +
PROGRAM SGF3/4...8
sc & SGF4/4
x SGF5/
I 2 / In I b2 2
ma I'L1 n x
SGF4/5
tic I'L2 I2
I d2 = I 2 - I 02
* I 02 > trip
x = 5SGF3/ 1 SS3
dia + SGR5/ 2
& 1 &
I' - x RESET +
L3 I 02 / I 2 PROGRAM
SGF4/6
gra SGF1/6 cos
TS3
m I02 / I n
SGF2/2
+180
x=6 1 SGF5/
3
for I
02
1f
SGF1/
7
SGF4/7 RESET +
PROGRAM
ear x=7
SGF3/
1 SS4
th- SGF1/8
3
SGF4/8 RESET +
PROGRAM
fau SGF2/4
I 2f / I 1f >
(I 02 ) 2nd harmonic
blocking (LV
lt SGB1/ 1
x=1
2f
&
side) SGR6/
x
x=8 1
SGF5/
TS4
rel BS1
1 4
RESE
ay SGB1/
1
x=2
SGB2/x T
TRIP
m BS2
2 SGB3/x
od SGB4/x (x =
1...3)
Settings (main /
second)
ule SGB1/3
SGB5/x (x =
I 01 > start x=1 SGF6/ AR1
SP x
1...3)
Reset trip I 01 > trip SGF7/
C BS3 1 indicator x=2 x AR2
x=3
SGB6/x (x = 1...3) SGF8/
Reset trip indicator and 2nd harm. bl. (HV) x= x AR3
D output relays
3
2
SGB1/4 I 02 > start SGB8/1
SGB7/x (x = 1...3) x=4
Reset trip indicator, output 1
relays
D BS4 1
x=4 and registers (complete relay
reset)
5
I 02 > trip x= SGF9/
x BS INT1
55 SGB1/5
BS1 SGR7/x
2nd harm. bl. x=6 SGB8/2
1
BS2 SGR8/x (LV) BS4 x=7
1 x=8 SGF10/
x
BS5 SGB1/ x=5 BS5 SGB8/3 BS INT2
BS3 SGR9/x
6 1
BS4 SGR10/x
BS5 SGR11/x
1 SGF11/
BS INT1 x=6 BS INT3
x
SGB1/ 1
x=7
7
BS INT2
10
SGB1/ 1
x=8
8
Front panel
I 01 >
I 02 >
I1 I2
I 01 I d1 I d2 I 02 IRF
Current measurement indicators
59 59
TRIP
0029A
SPCD 2D55
I 01 > Device symbol
I 02 >
I1 I2
I 01 I d1 I d2 I 02 IRF IRF indicator
Display
P 1 /I n [ % ]
t > [s ] RESET
01
STEP
P 2 /I n [ % ] Display step/reset push-button
t 02 > [ s ]
I 01 / I n
I 01 / I 1 [ % ]
I 02 / I n
I 02 / I 2 [ % ]
I 2f / I 1f (I 01 ) > [ %]
I 2f / I 1f (I 02 ) > [ %]
I 1 /I n
I 2 /I n PROGRAM
SGR
Operation indicator
TRIP
Type designation of relay module
0029A
SPCD 2D55
60 60
output signals can be linked to operate as trip or signal of the control signal has been set to
relays, alarm signals by routing the concerned light the indicator (switchgroup SGF5).
registers or signal to the desired output relay
recording (switchgroups SGR7...SGR11). Operation Activation of the blocking based on the ratio
memory, ini- tiated by an external control signal is between the amplitudes of the second
the indicated on the display by the operation harmonic and the fundamental frequency
activation code of the respective control signal. The component of the HV side neutral current,
of the operation codes remain lit until reset. I2f/I1f (I01)>, is indicated by the operation
control code 3, whereas the activation of the LV side
signal is not When relay operation is initiated by an blocking I2f/I1f(I02)> is indicated by the
indi- cated external control signal, the TRIP indicator is operation code 6.
on the automati- cally lit, if the output relay selected
display. is one of the heavy-duty output relays The table below describes the red operation
TS1...TS4 configured to be controlled by codes shown on the display to indicate start,
The stage I01> or stage I02>. Otherwise the operation, blocking, an activated control
external TRIP indicator will be lit only if the output signal or operation of the circuit-breaker
control failure pro- tection.
Code
1
2
3
4
5
6
7
8
9
0
II A
Yellow d
When a protection stage or a control signal same time the relay module delivers a control
resets, the TRIP indicator and the red signal to the self-supervision system output re-
operation code remain lit. The operation lay of the relay assembly. In addition, a
indicators can be reset via the push-buttons on fault code is lit on the display to show the type
the front panel of the relay, an external of the fault that has occurred. This fault
control signal or over the serial bus, see the code that consists of a red figure one and a
table in paragraph "Reset- ting". Unreset green code number cannot be removed by
operation indicators do not affect the resetting. It should be recorded and stated
operation of the relay module. If the output when service is ordered.
relay has a latching feature, the operation
indi- cators remain lit until the latching is The table below shows the priority of the
reset. opera- tion codes representing certain
events. If the priorities of the events to be
The self-supervision alarm indicator IRF indi- indicated are the same, the operation indicator
cates internal relay faults. Once the self- of the latest event is indicated on the display.
supervi- sion system of the relay module has
detected a permanent fault, the red indicator
is lit. At the
1. Self-supervision fault c
2. Circuit-breaker failure
3. Stage I01> or stage
Stage I01> or stage
4. Activation of external c
5. the external control sig
61 61
Activation of external c
6. Activation of blocking
7.
Settings The setting values are indicated by the three The second settings can be activated via
right-most green digits on the display. When subregister 4 in register A. The setting ranges
a LED in front of a setting value symbol is lit are the same as those of the main settings. A
it shows that the particular setting value is flashing light of the setting indicators
indi- cated on the display. If the same LED shows that the second settings are active.
represents several settings, a red digit is used to
indicate the setting displayed. The default
setting is given in parentheses under the
setting range.
Setting
P1/In(%)
t01> (s)
P2/In(%)
t02> (s)
I01/In
I01/ I1
I02/In
I02/ I2
I2f/I1f(I01)>(%)
I2f/I1f(I02)>(%)
I1/In
I2/In
Switchgroup SGF1 The switchgroup SGF1 is used to select the It should be noted that one protection
protection principle to be used on the HV principle at a time can be used on the HV
side and LV side. When the switch is in side or the LV side.
position 1 the protection principle is used.
Switch Function
SGF1/1 Stabilize
SGF1/2 Calculate
SGF1/3 Measure
principle on HV side
SGF1/4 High-impedanc
SGF1/5 Stabilize
SGF1/6 Calculate
SGF1/7 Measure
principle on LV side
Switchgroup SGF2 SGF1/8
The switches of switchgroup SGF2 are used High-impedanc
blockings based on the second harmonic of
to define the influence of the directions of the neutral current.
SGF1
the connected currents and to configure
the
P2 P1 P2 P1
L1 L1
S2 S1 S2 S1
L2 L2
L3 L3
S1 P1 S2 P2
3 6 9
3 6 9 1,4,7 1,4,7
S2 S1
P2 P1
25 27 27 25
a) b)
63 63
current exceeds the setting value.
Switch Function
When
The switc
SGF2/4 When
SGF2/5 Not i
SGF2/6 Not i
SGF2/7 Not i
SGF2/8 Not i
SGF2
64 64
Switchgroup SGF3 Circuit-breaker failure protection (CBFP)
Switch
SGF3/1
SGF3/2
SGF3/3
SGF3/4...8
SGF3
Circuit-breaker failure protection operate times tCBFP to be selected with switches SGF3/4...8.
tCBFP / ms
100
120
140
160
180
200
220
240
260
280
300
320
340
360
380
400
420
440
480
520
560
600
640
680
720
760
800
840
880
920
960
1000
Switchgroup SGF4 Self-holding of output signals
Switch Function
SGF4/1 Selection of
SGF4/2 Selection of
SGF4/3 Selection of
SGF4/4 Selection of
SGF4/5 Selection of
SGF4/6 Selection of
SGF4/7 Selection of
SGF4/8 Selection of
SGF4
When a swi
When the se
Switch
SGF5/
1
2
3
4
SGF5
I 01> 1 1 1 1 1 1 1
start
I 01> 2 2 2 2 2 2 2
trip
I 2f/I
1f 3 3 3 3 3 3 4
(I 01)>
block.
4 4 4 4 4 4 8
I 02>
start
I 02> 5 5 5 5 5 5 16
trip
I 2f/I 6 6 6 6 6 6 32
1f (I02
)>
block.
7 7 7 7 7 7 64
BS4
8 8 8 8 8 8 128
BS5
Factory
setting = 0 0 27 0 0 0
Switch Function
SGB1/1 Selection of
SGB1/2 Selection of
SGB1/3 Selection of
SGB1/4 Selection of
SGB1/5 Selection of
SGB1/6 Selection of
SGB1/7 Selection of
SGB1/8 Selection of
SGB1
Switchgroup
SGB2...7
RESET
Control
signals Weighting
BS1
BS2
BS3
BS4
BS5
BS INT1
BS INT2
BS INT3
Check-
sum =
Factory default =
SGB2/1...8
SGB3/1...8
SGB4/1...3
SGB5/1...3
SGB6/1...3
SGB7/1...3
Switchgroup SGB8 The logic active state of the blocking signals ule in relation to the logic state of the
BS INT1, BS INT2 or BS INT3 of the relay signal linked to the blocking signal.
mod-
Switch Function
SGB8/4
SGB8/5
SGB8/6
SGB8/7
SGB8/8
SGB8
Switchgroups The switchgroups SGR1...11 are used to with the desired output signal SS1...SS4 or
SGR1...SGR11 config- ure the start and operate signals of TS1...TS4 by cir- cling the intersections of the
the protec- tion stages and various control signal lines. The switch number is marked at
signals to operate as desired output signals each intersection and the weighting value of
SS1...SS4 or TS...TS4. the switch is given
Output signal SS1 TS1 SS2 TS2 SS3 TS3 SS4 TS4
I 02> 1 2 3 4 5 6 7 SGR4 =
SGR4 start 8 (=16)
I 02> SGR5 =
SGR5 trip 1 2 3 4 5 6 7 (=74)
8
I 2f/I 1f SGR6 =
SGR6 (I 02) > (=0)
block. 1 2 3 4 5 6 7
8
1 2 3 4 5 6 7
SGR11 BS5 SGR11 =
8
(=0)
1 2 3 4 5 6 7
8
Fig. 9. Output relay matrix for differential relay module SPCD 2D55
Measured data Measured data of main menu Measured values are indicated by the three
green right-most digits on the display. Data
that is being measured at the moment is
indicated by a LED above the display and a red
digit or letter to the left on the display.
Note! The the transformation ratio corrections. When differential current Idcos is zero. Then the
measured data the phase difference between the residual measured data displayed is zero too.
displayed allow current of the phase currents and neutral
for the effect of cur- rent is less than 90 , the directional
I1, I01
I1, I01
Id1
I1, I01
I1, I01
I1, I01
Id1
Id2
I2, I02
I2, I02
I2, I02
Recorded The values recorded are stored in a The pushdown storage contains the five
information pushdown storage at the moment of relay start, latest values recorded (n)...(n-4). Each new
relay opera- tion, and during transformer value is stored in the first location (n) in the
connection inrush currents. Both the HV storage and pushes all the previous items one
side and the LV side values are recorded at step forward (n-1). When a sixth item is
relay start or relay opera- tion, irrespective of stored the oldest item (n-4) of the storage
whether the relay start or operation took will be lost.
place on the HV side or the LV side. The
values are also recorded when the operate The most recently stored values (n) are
signal is obtained via an external control output available in the main registers. At a maximum
BS1...5 four of the previous values are in the
subregisters. The left- most digit indicates the
address of the storage location and the other
three digits the numerical value of the
parameter stored.
Register Record
number
1 Directi
The su
Stabiliz
The su
2
Directi
The su
Stabiliz
3 The su
Neutra
The su
4 Durati
The su
Neutra
The su
5
Durati
The su
6
8
Register Record
number
9 Minimu
Subregi
(n-1)...
Status o
0 Contr
BS
BS
BS
BS
BS
BS
BS
BS
From th
The tes
Address
contain
1. Setti
Defa
2. Bus t
3. Passw
4. Selec
Defa
5. Hz s
6. mHz
So, t
A
When the display is dark, access to the begin- communication parameter, see section
ning of the main menu is gained by pressing "Reset- ting" in paragraph "Description of
the STEP push-button on the front panel for function". The registers are also cleared by
more than 0.5 s. Pressing the push-button an auxiliary power supply failure. The
for less than 0.5 s gives direct access to the setting values, the address code, the data
end of the main menu of the relay module. transfer rate and the password of the relay
module are not affected by voltage failures.
The information recorded in registers 1...9 can Instructions for setting the ad- dress code and
be reset with the push-buttons on the front data transfer rate are given in the document
panel, via an external control signal or a serial "General characteristics of D-type relay
modules".
Main menus
and submenus
of settings and MAIN MENU SUBMENU
registers
STEP 0.5 s PROGRAM 1 s
Normal status, display off
REV. STEP 0.5 s FWD. STEP 1 s
Sum current I 1 of phase Phase current Phase current IL2 on Phase current IL3
S currents on H.V. side [% In] IL1 3
1 H.V. side [x In]
H.V. side [x In]
2 H.V. side [x In]
Neutral current Io1 on
0 H.V. side [% In]
S T 2nd harmonic
blocking threshold
EP
I2f/I1f(Io1)> [%]
0.5
s 2nd harmonic
blocking threshold
I2f/I1f(Io2)> [%]
CT ratio correction
I1/In
M
CT ratio correction
I2/In
A Functional Functional Functional
I 2 3 4
switchgroup switchgroup switchgroup
N SGF2 SGF3 SGF4
Functional
M 1 switchgroup SGF1
E 2 Blocking Blocking 4 Blocking
switchgroup 3 switchgroup switchgroup
N SGB2 SGB3 SGB4
U Blocking
1 switchgroup SGB1
Neutral current Neutral current Io2 on L.V. Neutral current Io2 on L.V.
Io2 on L.V. side
at latest (n:th) Neutral current Io2 on L.V. side at
event 1 2 3 side at n-3 event
side at n-1 event
Duration of latest event (n) Duration of event n-1 Duration of event n-3
1 2
starting on L.V. side 3
starting on L.V. side
Duration of event n-2 starting on L.V.
starting on L.V. side Min. 2nd harmonic content
Min. 2nd harmonic content 2 3 of n-3 inrush on H.V. side
of latest inrush on H. V. side
Min. 2nd harmonic content
Status of
external relay 0 IRF Id1>&to Id2 Id2>&to BS1 BS2 BS4 BS5
blocking / 000 Id1> 1> > 2> BS3
control
signals
Relay unit Communication rate Loss of bus traffic time Password for altering
identification
address for
communication 1 3
setting (kBd) counter 0...255 s settings
2
Fig. 10. Main menus and submenus for settings and registers of earth-fault relay
module
SPCD 2D55.
The procedure for entering a submenu "General characteristics of D-type SPC
or a setting mode and configuring the relay modules. Below a simplified
module is described in detail in the manual instruction.
34 SPC 3 EN1
Functional
6 Functional
7
switchgroup SGF7
switchgroup SGF6
9 0 II
5 Functional
switchgroup Functional Functional
SGF5 switchgroup switchgroup
6 SGF9 SGF10 8
Function
al
switchgr
oup
SGF11
Relay matrix
5 switchgroup Relay matrix Relay matrix Relay
6 switchgroup 7 switchgroup 8 matrix
SGR5 SGR6 SGR7 switchgr
oup
SGR8
Diff.
4 current
Id2cos2
on L.V.
side at
n-4
event
Selection of main vs
second settings Nominal 6 Nominal frequency
4 5 setting, mHz -part
frequency
setting, Hz
-part
Testing of In the test mode, entered from the supervision output is tested. The LEDs in
output relays submenu of register 0, it is possible to front of the settings show the output
activate the output signals of the relay one signals to be activated at the moment.
by one. The desired output signal is selected by
pressing PROGRAM for about one
When the PROGRAM push-button is second.
pressed for about five seconds the three
digits to the right start flashing as an The setting LEDs on the front panel and
indication of the relay module being in their respective output signals are as
the test mode. Initially, the self- follows:
Pressing the push-buttons STEP and When the push-button STEP is being
PRO- GRAM simultaneously activates pressed in the IRF test mode, the self-
the selected output signal, which supervision output relay operates in about
remains active as long as the push- 1 second. Return to the main menu is
buttons are being pressed. The effect on possible at any stage of the test sequence
the functions of the output relays by pressing the PROGRAM push-
depends on the configuration of the button for about five seconds.
switchgroups SGR1... SGR11.
The signals are selected in the sequence
illus- trated in the Fig. 11.
IRF I 01 > start I 01 > trip I2f / I1f (I 01 I 02 > start I 02 > trip
)>
STEP
Fig. 11. Sequence for selecting the output signals in output relay testing.
Technical data
CT ratio I01/In
Correction range of LV side neutral connection
CT ratio I02/In
Harmonics blocking ratio I2f/I1f of HV side
neutral current I01
Harmonics blocking ratio I2f/I1f of LV side
neutral current I02
Operate time accuracy
Operation accuracy
Restricted earth-fault principle
(high-impedance type earth-fault protection)
Basic setting on HV side P1/In 5...50%
Operate time setting on HV side t01> 0.03...100 s
Basic setting on LV side P2/In 5...50%
Operate time setting on LV side t02> 0.03...100 s
Correction range of HV side neutral connection
CT ratio I01/In 0.40...1.50
Correction range of LV side neutral connection
CT ratio I02/In 0.40...1.50
Operate time accuracy 2% of set value or 25 ms
Operation accuracy 4% of set value or 2% x In
Note!
Operate times are valid at rated frequency 50 Hz and 60 Hz.
Serial Special codes have been specified to An event to be included in event reporting
communicatio represent different events such as starting is marked with 1. The event mask is
n parameters and operation of protection stages, obtained by adding the weighting values of
blocking, and activation of control and the events in- cluded, see the tables below.
Event codes output signals. These event codes can be
transferred to higher-level systems over the
serial bus.
Event mask
V155
V156
V157
V158
V159
Channel Code
0 E1
0 E2
0 E3
0 E4
0 E5
0 E6
0 E7
0 E8
0 E9
0 E10
0 E11
0 E12
0 E13
0 E14
0 E15
0 E16
0 E17
0 E18
0 E19
0 E20
0 E21
0 E22
0 E23
0 E24
Channel Code
0 E25
0 E26
0 E27
0 E28
0 E29
0 E30
0 E31
0 E32
0 E33
0 E34
0 E35
0 E36
0 E37
0 E38
0 E39
0 E40
E50
E51
E52
E53
E54
The event codes E50...E54 and the events rep- 60 events. The event codes E52... E54 are
resented by these are always reported and gen- erated by the control data
cannot be excluded. The capacity of the event communicator (e.g. SRIO 1000M).
register is
Remote In addition to the event codes input data (I The push-buttons of the relay module or a
transfer data data), output data (O data), setting values (S command over the serial bus can be used to
data) memorized data (V data), and some change the password. To be able to change the
other data can be read from the module over password over the serial bus, the password first
the serial bus. The values of parameters marked has to be opened. The new password is entered
with the letter W can be changed over the by means of parameter V161. When using
SPA bus. the push-buttons, the new password is
written in the place of the old one in
When Measured
a setting value
data is to be changed, either subregister 3 of register A.
via the push-buttons on the front panel or
over the serial on
Current bus,HVthe siderelay
phasemodule
L1 checks Should the wrong password be given 7 succes-
whether the given parameter
Current on HV side phase L2 value is legal. A sive times, it turns into a zero and can no
value outside the permitted
Current on HV side phase L3 setting range will longer be opened over the serial bus. Then
not beResidual
memo- current
rized, butI the previous setting the pass- word can be given a new numerical
1calculated from HV side phase currents
will beHV
retained.
side neutral current I01 value via the push-buttons only.
Directional differential current Id1cos 1 on HV side
Changing a setting
Current on LVparameter
side phaseover
L1 the serial
bus requires a password
Current on LV side phase L2 in the range 1..999. R = data to be read from the
The default setting is 1.
Current on LV side phase L3 module
Residual current I2 calculated from LV side W phase
= data to be written to the
currents
The password is opened
LV side neutral current I02 by giving the module
serial Directional
communication parameter
differential currentV160
Id2costhe2 on(P)
LV=side
writing allowed through a password
desiredPhase
numerical value. Parameter V161
difference between residual current and is
used for closing
neutral the password.
current on HV side The password is
also closed by failures in the voltage
Phase difference between residual supply.
current and neutral current on LV side
Input data Status data of control signals BS1...5 and
Output data TheBSactual status INT3
INT1...BS data provide information latest resetting of the register. When the
about the present status of the signals. The value is 0, the signal is not activated and
events stored in the memory indicate those when the value is 1, the signal is activated.
signal activations which have taken place
after the
Status data of protection stages and control signals
Protection stage/
signal
Signal activations
Output signal
The parameters V11...V59 can be used to read (R) n-1 = the value before that, and so on. The
the latest five values stored in the registers. Event n registers are described in detail in the paragraph
= the most recent value recorded, event "Recorded information".
Value measured
Checksum, SGF1
Checksum, SGF2
Checksum, SGF3
Checksum, SGF4
Checksum, SGF5
Checksum, SGF6
Checksum, SGF7
Checksum, SGF8
Checksum, SGF9
Checksum, SGF10
Checksum, SGF11
Checksum, SGB1
Checksum, SGB2
Checksum, SGB3
Checksum, SGB4
Checksum, SGB5
Checksum, SGB6
Checksum, SGB7
Checksum, SGB8
Checksum, SGR1
Checksum, SGR2
Checksum, SGR3
Checksum, SGR4
Checksum, SGR5
Checksum, SGR6
Checksum, SGR7
Checksum, SGR8
Checksum, SGR9
Checksum, SGR10
Checksum, SGR11
38
Control parameters
Data
EEPROM formatting
Error code
39 39
Data
Internal signal
I01> start
I02> start
Blocking I2f/I1f(I01)>
Blocking I2f/I1f(I02)>
Control signal
I01> start
I02> start
Blocking I2f/I1f(I01)>
Blocking I2f/I1f(I02)>
Control signal
BS1
BS2
BS3
BS4
BS5
BS INT1
BS INT2
BS INT3
Internal signal
BS1
BS2
BS3
BS4
BS5
BS INT1
BS INT2
BS INT3
automatic reset
The
mandevent
only register can bearead
once. Should faultbyoccur,
the Lsay,
com-in forwards the information to an output device.
the data communication, the B command Under normal conditions the event register
can be used to re-read the contents of the of the relay module is empty. The control
register. When required, the B command can data communicator also resets abnormal status
be re- peated. In general, the control data data, so this data is normally zero.
communica-
Fault codes
SPCJ 4D28
Overcurrent and earth-fault relay
module
User´s manual and Technical description
3I>
I
I L1 I L2 I L3 I o IRF
I >/ In RESET
STEP
t > [s ]
k
I >> / I n
t >> [ s ]
I >>> /I n
t >>> [ s ]
I0 >/ I n
t 0 > [s ]
k0
I 0 >> / I n
t 0 >> [s ]
I > [%]
t > [s ] PROGRAM
SGF
SGB
SGR
TRIP
0023A
SPCJ 4D28
1MRS 750093-MUM EN
SPCJ 4D28
Issued 1995-05-04
Modified 2002-05-15
Version E (replaces 34 SPCJ 18 EN1)
Overcurrent and earth-fault
Checked MK
Approved OL
relay module
Data subject to change without notice
Characteristics Low-set overcurrent stage I> with definite Output relay matrix allowing any start or trip
time or inverse definite time characteristic, the signal from the protection stages to be routed
latter with six selectable inverse-time curves. to the desired output relay.
High-set overcurrent stage I>> with definite Flexible configuration of auto-reclose start ini-
time characteristic. The high-set stage can be tiation signals.
set out of operation.
Local display of measured and set values
Superhigh-set overcurrent stage I>>> with and data recorded at the moment of a fault.
defi- nite time characteristic. The superhigh- Reading and writing of setting values either
set stage can be set out of operation. via local display and front panel push-
buttons or from higher-level systems over the
Low-set neutral overcurrent stage I0> with serial interface and the fibre-optic bus.
defi- nite time or inverse definite time
characteristic, the latter with six selectable Self-supervision system continuously monitor-
inverse-time curves. ing the operation of the electronics and the
microprocessor. When a permanent fault is
High-set neutral current stage I0>> with de- tected the alarm output relay operates and
defi- nite time characteristic. The high-set the other relay outputs are blocked.
stage can be set out of operation.
-20
-30
-40
0 1 2 3 4 5 6 7
f/fn
Phase discontinuity The overcurrent and earth-fault relay issuing an operate signal, which can be routed
protection unit module SPCJ 4D28 is provided with a phase to the desired output relay. At the same time a
disconti- nuity protection unit which red operation indicator code is lit on the
monitors the mini- mum and maximum phase display.
currents. The differ- ence between these
currents is calculated from the expression I = The phase discontinuity protection stage can be
(Imax-Imin)/Imax x 100%. The phase set out of operation completely, if not
discontinuity protection is not in use when needed. When the stage is set out of
the measured currents fall below 0.1 x In. operation the set start current is displayed with
three dashes "- - -".
The phase discontinuity protection stage
starts, if the current difference exceeds the The operation of the phase discontinuity pro-
set start current I of the stage. Should the tection stage can be inhibited by an
duration of the phase discontinuity situation external control signal BS1 applied to the
exceed the set operate time t > of the stage relay module. The external blocking signal is
the stage operates configured with switch SGB1/6.
Circuit breaker The overcurrent and earth-fault relay in question. The CBFP can also be used to
failure protection module SPCJ 4D28 is provided with a establish a redundant trip system by using two
unit circuit breaker failure protection unit (CBFP) trip coils in the circuit breaker and
which provides a trip signal TS1 within controlling one of the coils with TS2, TS3 or
0.1...1 s after the trip signal TS2, TS3 or TS4 and the other with TS1. The switches
TS4 has been delivered, provided the fault SGF4/5...7 are used for activating the circuit
still persists after the time has elapsed. The breaker failure protection. The operate time is
CBFP normally controls the cir- cuit breaker set in submenu
which precedes the circuit breaker 5 of register A.
Output signals Switchgroups SGR1...11 are used for routing active, although the signal that caused the op-
the start or trip signals of any protection eration resets. The resetting functions are
stage to the desired start outputs SS1...SS4 ex- plained in paragraph "Resetting". The
or trip outputs TS...TS4. TRIP indicator on the front panel can be set
to be lit on activation of any of the output
The output signals TS1…TS4 can be assigned signals. The operation indicator remains lit
a self-holding function with switches SGF4/
1…4. In this case the output signal remains
46 46
after the output signal has disappeared. The functions are se- lected
with switchgroup SGF5.
Auto-reclose start The start signals AR1, AR2 and AR3 can be to be activated by the desired start and
initiation signals used as start initiation signals for the desired operate signals of the earth-fault module and
autoreclose shots. The initiation signal AR2 the initia- tion signal AR1 by the start and
can be programmed to be activated by the operate signals of both the overcurrent
desired start and operate signals of the module and the earth- fault module.
overcurrent module. The start signal AR3 can
be programmed
Second settings Either the main settings or the second The main and second settings can be read and
settings can be selected as currently used set via the serial bus using the S parameters.
settings. Switch- ing between the main Those settings only, which currently are
settings and the second settings can be done used, can be read and set with the push-
in three different ways: buttons and the display on the front panel.
When the second settings are used the
1) By command V150 over the serial indicators of the settings are flashing.
communi- cation bus
2) By an external control signal BS1, BS2 Note!
or If external control signals have been used for
RRES (BS3) selecting the main or second settings, it is not
3) Via the push-buttons of the relay module, possible to switch between the settings over the
see submenu 4 of register A. When the serial bus or using the push-buttons on the
value of submenu 4 is 0 the main settings are front panel.
used and when the value of submenu 4 is 1
the second settings are used.
Resettings The LED operation indicators, the operation reset with the push-buttons on the front
code numbers of the display, the latched panel, with an external control signal or by a
output relays and the registers of the module command via the serial bus, see table below.
can be
Way of resetting
RESET
SGB_7/ = 1
SGB_8/ = 1
Parameter V101
Parameter V102
Block diagram
I L1 I> t>
I L2 Imax - Imin SGF 5/1
Imax SGR 11 / x 1 SS1
I L3 RESET +
PROGRAM
SGF 4/1
I> 2 1 TS1
t>, k 1
SGR 2 / x
SGB 1/1 SGB SGF1/1… 30 ms
3/1 3
SGB 1/6 SGB 2/1 t>>
I>>
47 47
3 0.1..1s SGF 5/3 SS2
1
SGR 3 / x 4
S RESET +
G PROGRAM
F
4/ SGF 5/4
SGR 4 / x
2
TS2
60 ms SGF 5/6
SGF 5/8
SGB 1/3 TS4
SGB 2/3 SGR 7 / x 8 1
50 ms
SGB 3/3
SGF 1/6…8
SGR 9 / x
RESET
Io>>
I> start
1
30 ms SGF 6 / x AR1
SGB 1/4
SGB 2/4
SGB 3/4
Fig. 2. Block diagram for overcurrent and earth-fault relay module SPCJ 4D28
Indicato I 0 >> / I
r for the n
t 0 >> [ s ]
I > [%]
t > [ s ] PROGRAM
the operate time t >
Indicator for the checksums of switchgroups SGF1...8 SGF
TRIP
0023A
SPCJ 4D28
3I> Device symbol
I
Display window
I >/ In RESET
STEP
t > [s ] Reset and display step push-button
k
I >> / I n
t >> [ s ]
I >>> /I n
t >>> [ s ]
I0>/ In
t 0 > [s ]
k0
I 0 >> / I n
t 0 >> [s ]
I > [%]
t > [ s ] PROGRAM
SGF
Setting push-button
SGB
49 49
Fig. 3. Front panel of the combined overcurrent and earth-fault relay module SPCJ 4D28
Operation Each protection stage has its own red start started also operates the code number
indicators and trip code shown as a number on the indicating starting turns into a code number
display. The TRIP indicator at the bottom indicating operation. When desired, the
right corner is shared by the different code numbers indicating starting can be set
protection stages. Switch- group SGF5 is to remain lit, by giving switches SGF2/1...5
used for defining the mode of function of proper settings.
the TRIP indicator.
Operation indicators that remain lit are
The code numbers indicating tripping and the reset either by pressing the RESET push-
red TRIP indicator remain lit, when the button on the front panel or by command
protec- tion relay has issued a trip signal. Thus V101 over the SPA bus. Unreset operation
it is easy to identify the tripping stage. The indicators do not affect the operation of the
indicators remain lit even though the stage relay module.
that caused the indication resets, and they have
to be separately reset. On the other hand, The table below shows the code numbers of
the code numbers indication starting the display or the corresponding code numbers
automatically turned off when the protection read- able with parameter V9 indicating
stage resets. If the stage that starting or operation of the relay module.
Indication P
1
2
3
4
5
6
7
8
9
0
11
When one of the protection stages of the The self-supervision alarm indicator IRF indi-
mod- ule operates, the yellow LEDs on the cates that the self-supervision system of the
upper part of the front panel show on which relay module has detected a permanent fault.
phase the current exceeded the set start Once a fault has been detected the red indicator
current of the stage, named phase fault is lit. At the same time the relay module
indication. If, for in- stance, code number 2 delivers a con- trol signal to the self-
and indicators IL1 and IL2 are lit, operation supervision system output relay of the
was caused by overcurrent on the phases L1 protection relay. In addition, in most fault
and L2. The phase fault indication is reset cases, a fault code appears on the display to
with the RESET push-but- ton. indicate the type of fault. This fault code,
which consists of a red figure one (1) and a
green 1…3 digit code number cannot be
removed by resetting. The code number
should be recorded after a fault situation
and stated when service is ordered.
Settings The setting values are indicated by the three to be set indicates the quantity currently
rightmost digits on the display.The LED indi- being displayed.
Numerical cators adjacent to the symbols of the
settings quantities
(modified 99-10)
50 50
Setting Explanation
*) At inverse time characteristic the relay al- lows setting above 2.5 x
CBFP Note! Operate tim
In, but regards any setting >2.5 x In as being equal to 2.5 x In. The continuous current carrying capacityprotection
of the
** ) The stage can be set out of operation with SGF switches. This energizing inputs is 4.0 x In.
state is indicated as "- - -" on the display.
51 51
Switch settings
Switch Function
SGF1/1 SGF1/2 S
0 0
1 0
0 1
1 1
0 0
1 0
0 1
1 1
When SGF1/5 = 0, th
When SGF1/5 = 1, th
SGF1/6 SGF1/7 S
0 0
1 0
0 1
1 1
0 0
1 0
0 1
1 1
SGF1
Switch Function
Switch S
SGF2/1
SGF2/2
SGF2/3
SGF2/4
SGF2/5
Switch S
SGF2/6
SGF2/7
SGF2/8
SGF2
SGF3/2
SGF3/3
SGF3/4
SGF3/5
SGF3
Switch Function
At self-holding the ou
SGF4
SGF5/1 Selection o
SGF5/2 When the
SGF5/3 position 1
SGF5/4
SGF5/5 Switch
SGF5/6
SGF5/7
SGF5/8
SGF5/1
SGF5/2
SGF5/3
SGF5/4
SGF5/5
SGF5/6
SGF5/7
SGF5/8
SGF5 170
Switchgroups Using the different start and operation signals point. The numbers of the different switches
SGF6…8 as autoreclose start initiation signals AR1, and their weight factors are marked near the
AR2 or AR3. The signal selection possibilities crossing points. The checksums for the
(modified 96-02) are shown in Fig. 4 below. different switch groups are obtained by adding
the weight factors of the selected switches.
In the figure the start and operate signals of
the different protection stages are connected to Switches SGF6/7…8 and SGF7/7…8 are not
the desired autoreclose start line AR1, AR2 or in use.
AR3, for instance, by encircling the signal
crossing
Autoreclose AR1 AR3
initiating
AR2 signal
t>> SGF6 = (
4 (8) 4 (8) = 0)
SGF7 = (
I>>> 5 (16) 5 (16) = 0)
SGF8 = (
t>>> = 0)
6 (32) 6 (32)
SGF8
SGF8
1 (1) 5 (16)
I0 >
Indicators Indicators,
t 0 >> Main I> self-hold.
Indicators,
t> t>> t 0> self-hold.,
Second registers
Checksum
(factory setting)
2 3 4 5 6 7 8 SGB1=
BS1 1 ( = 0)
BS2 1 2 3 4 5 6 7 8 SGB2=
( = 0)
RRES 8 SGB3=
(BS3) 1 2 3 4 5 6 7
( = 0)
Weighting 2 4 8 16 32 32 64 128
factor 1
Fig. 5. Control signal matrix of the combined overcurrent and earth-fault relay module SPCJ 4D28.
Switch
SGB_/1...4
SGB_/5
SGB1/6
SGB2…3/6
SGB_/7
SGB_/8
Switchgroups The start and operate signals of the point is marked with a switch number and
SGR1…11 protection stages are combined with the the corresponding weight factor of the
outputs SS1… SS4 and TS1…TS4 with switch is shown at the bottom row of the
(modified 96-02) the switches of switchgroups SGR1…11. matrix. By horizontally adding the weight
factors of all the selected switches of a
The matrix shown below can be used as an switchgroup the switch- group checksums is
aid for making theI>desired selections. The start obtained.
and operate signals of the different protection
stages can be combined with the output Note!
signals SS1…SS4 and TS1…TS4 by Check if all the start and operate signals of
encircling the desired intersection points. the relay module SPCJ 4D28 are available in
Each intersection the protection relay in question.
Output signal
SGR1 I>
SGR2
SGR3 I>>
SGR4
I>>>
SGR5
I0>>
SGR6
SGR7 I0>
SGR8
SGR9
SGR10
SGR11
Weighting factor
Fig. 6. Output signal matrix of the combined overcurrent and earth-fault relay module SPCJ 4D28.
Manual checksum
calculation Switch Weight factor Position Value
SGF1/1
SGF1/2
SGF1/3
SGF1/4
SGF1/5
SGF1/6
SGF1/7
SGF1/8
Measured data The measured values are indicated by the value currently presented is indicated by a
three right-most digits on the display. The yel- low LED above the display.
measured
Indicator Measured da
I0 Residual cur
I0 In the subme
between the
phase curren
Recorded The left-most digit of the display shows the isters is presented in the section "Main menus
information register address and the other three digits the and submenus of settings and registers".
recorded information. The structure of the
reg-
1 Current mea
When the st
Register 2 re
Register 3 re
Duration of
Subregister 5
2 Duration of
Subregister 5
3
Residual cur
When the st
4
6
Register/ Recorded i
STEP
7 Duration o
Subregister
Duration o
Subregister
Unbalance
Continuou
8 last relay re
Display of
The right-m
9 Displaye
figure
0
1
2
3
11 4
5
6
7
0 The functi
18
Register/ Record
STEP
From re
Indicat
I>
t>
I>>
t0>
I0>>
I>
For fur
Address
1. Selec
2. Bus
3. Passw
A 4. Selec
Defa
5. Selec
0.1...
When the display is dark, press the STEP external control signal BS1, BS2 or RRES.
push- button for 1 second to go to the The registers are cleared by failures in the
beginning of the display menu. To go to the auxiliary power supply to the module. The
end of the display menu, press the STEP setting values, the address code, the data
push-button for a short moment only (<0.5 transfer rate and the password of the relay
s). module are not affected by supply voltage
failures. Instructions for specify- ing the
The values stored in registers 1...11 are cleared address code and the data transfer rate of the
by pressing the push-buttons RESET and relay module are given in the description
PRO- GRAM simultaneously, by a command "General characteristics of D-type SPC relay
V102 over the serial communication system modules".
or by an
Menu MAIN MENU SUBMENU
chart
Normal
status,
display
off
C
ur
re
nt
in
ph
19 19
as
e
L2
SUBMEN
REV. STEP 0.5 U FWD STEP 1 s
Current in phase L3
s
Neutral current Io
1 Differential current I
S
t
a
r
t
v
a
l
u
e
I
>
O
p
e
r
a
t
e
t
i
m
e
t
>
o
r
m
u
l
t
i
p
l
i
e
r
k
Start value I>>
1 Operate time t>>
S
T Start value Io>>
1 Operate time t>
E
Setting of
P Setting of switchgroup
3 SGF3
Start value I
switchgroup
. 2 SGF2
5 Setting of switchgroup
8 SGF8
Setting of
s 7
Setting of switchgroup switchgroup Setting of switchgroup
SGF1 SGF7 3 SGB3
Setting of switchgroup
A Setting of 8 SGR8
2
switchgroup
I Setting of switchgroup
SGR2
N SGB1
Setting of
M Setting of switchgroup switchgroup
7
E SGR1 SGR7
N
F E
1
3 Value of current
P Value of cur
W I L1, latest I L3, latest
memorized memorized
event n n
D
1s
Value of current I L2, latest Duration of I> starting, latest
2 S memorized event n 4 memorized event n
T
20 20
Value of current IL1,
1 event n-1
Duration of
1
I>> starting,
latest
memorized Value of current IL2,
1 event n-1
event n
2
Value of
current Io, Value of current IL3,
1 event n-1
latest
memorized 3
Desired step event n
Duration of I> starting,
1 event n-1
Io>> starting,
Storing a setting value in setting mode latest
memorized
event n
Fig. 7. Main and submenus of the combined overcurrent and earth-fault relay module
SPCJ 4D28.
The procedure for entering a submenu 1MRS 750066-MUM EN: "General
or a setting mode, setting a value and charac- teristics of D-type SPC relay
entering the TEST mode is described in modules". A short guide follows:
detail in the manual
21 21
Setting of
switchgroup Setting of Setting of switchgroup
4 switchgroup 6
SGF4 5 SGF5
SGF6
Setting of switchgroup
Setting of Setting of 6
switchgroup SGR6
4 5
switchgroup
SGR4
SGR5
Setting of switchgroup
11 SGR11
Setting of
switchgroup Setting of
9 SGR9 10
switchgroup
SGR10
Value of current
I L1, Value of current I L1,
3 4 event n-4
1 event n-3
Value of current
I L2, Value of current I L2,
3 4 event n-4
2 event n-3
Value of current
3 Value
I L3 4 of
curre
3 event n-3 nt
IL3,
event
n-4
Duration of I>
starting, Duration of I> Number of I>
3 event n-3 4 starting, starts since
4 event n-4 5 latest reset
Duration of I>>
3 starting, event n-3 Duration of I>>
5 4 starting, event n-4 Number of I>>
5 starts since
latest reset
Value of current
3 Io, event n-3 Value of current
6 4 Io, event n-4
Duration of Io>
7 3 starting, event n-3 Duration of Io>
4 starting, event n-4 Number of Io>
5 starts since
latest reset
Duration of Io>>
8 3 starting, event n-3 Duration of Io>>
4 starting, event n-4
Number of Io>>
5 starts since latest
reset
Value of current
Value of current
5 Number of I>
I,
3 event n-3 4 I, starts since
9 event n-4 latest reset
Password for
altering Selection of main Operate
3 settings 4 vs. time for
A the
second settings 5 CB-failure
protection
Time/current The overcurrent stage I> and the low- At the IDMT characteristic, the operate
characteristics set re- sidual current stage I0> can be time of the stage will be a function of the
(modified 2002- given definite time or an inverse definite current: the higher the current, the
05) time operation char- acteristic. The shorter is the operate time. Six
settings of the switches SGF1/ time/current curve groups are avail- able.
1...3 determine the mode of operation of Four of these comply with the BS 142 and
stage I> and the switches SGF1/6…8 that IEC 255 standards and two curve groups,
of the stage I0>. See section "Setting the RI and the RXIDG curve groups are
switches". special type curve groups according to
ABB praxis.
Characteristic
s according to The relay module incorporates four The values of the constants and
IEC 60255 internation- ally standardized time/current determine the slope as follows:
and BS 142 curve groups named "extremely inverse",
"very inverse", "normal in- verse" Time/current
and
"long-time inverse". The relationship curve group
between time and current is in accordance
with the standards BS 142 and IEC 60255-
Normal inverse
3, and can be expressed as follows: Very inverse
Extremely inverse
Long-time inverse
kx
t [s] =
22 22
I The standard BS 142.1966 defines the
( ) I
-1
normal current range to be 2...20 times
> the setting value. In addition, the relay
where t = operate time has to start at the latest when the current
k = time exceeds the setting value by 1.3 times, if
multiplier the time/current characteristic is normal
I = phase current inverse, very inverse or extremely in-
value verse. For the long-time inverse
I> = set current characteristic the normal current range is
value specified to be 2...7 times the setting and
the relay is to start when the current
exceeds the setting value by 1.1 times.
I/I>
2
5
7
10
20
In the normal current ranges specified N
above the inverse time stages of the ot
overcurrent and earth- fault relay e.
module SPCJ 4D28 fulfil the toler- The actual operate time of the relay,
ance requirements of class 5 at all presented in the graphs in Fig. 8…11,
degrees of inversity. includes an addi- tional filter and
detection time plus the operate time of the
The time/current characteristics trip output relay. When the operate time
according to the IEC and BS standards of the relay is calculated using the math-
are illustrated in Fig. ematical expression above, these additional
8 times of about 30 ms in total have to be
… added to the time received.
11
.
RI-type The RI-type characteristic is a special where t = operate time in
characteristi character- istic that is principally used seconds k = time
c to obtain time grading with mechanical multiplier
relays. The character- istic can be I = phase current
expressed by the mathematical ex- I> = set start
pression current
RXIDG-
The RXIDG-type characteristic is a special
type Mathematically, the time/current
char- acteristic that is principally used in
characteristi characteristic can be expressed as follows:
earth-fault protection, in which a high
c k x I>
degree of selectivity
24 24
t/s
70
60
50
40
30
20
10
9
8
7
6
5
1
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0.09
0.08
0.06
0.04
0.03
0.02 2 3 4 5 6 7 8 9 10 20 I/I>
1
Fig. 8. Inverse-time characteristics of overcurrent and earth-fault relay module SPCJ 4D28
Extremely inverse
t/s
70
60
50
40
30
20
10
9
8
7
6
5
0.8
0.7
0.6
0.5
0.3
0.2
0.1
0.09
0.08
0.07
5
0.05
0.04
0.03
0.02 1 2 3 4 5 6 7 8 9 10 20 I/I>
Fig. 9. Inverse-time characteristics of overcurrent and earth-fault relay module SPCJ 4D28
Very inverse
t/s
70
60
50
40
30
20
10
9
8
7
6
5
0.9
0.8
0.7
0.6
0.4
0.3
0.2
0.1
0.09
0.08
0.07
0.06
0.05
0.04
0.03
0.021 2 3 4 5 6 7 8 9 10 20 I/I>
Fig. 10. Inverse-time characteristics of overcurrent and earth-fault relay module SPCJ 4D28
Normal inverse
t/s
700
600
500
400
300
200
100
90
80
70
60
50
Fig. 11. Inverse-time characteristics of overcurrent and earth-fault relay module SPCJ 4D28
Long-time inverse
t/s
70
60
50
40
30
20
10
9
8
7
6
5
4 k
3 1.0
0.9
0.8
2 0.7
0.6
0.5
0.4
0.3
1
0.9
0.8
0.2
0.7
0.6
0.5
0.4
0.3 0.1
0.2 0.05
0.1
0.09
0.08
0.07
0.06
0.05
0.04
0.03
0.02 1 2 3 4 5 6 7 8 9 10 20 I/I>
Fig. 12. Inverse-time characteristic of overcurrent and earth-fault relay module SPCJ 4D28
RI-type inverse
t/s
70
60
50
40
30
20
10
9
8
7
6
5
k
1
0.9
0.8 1.0
0.7
0.9
0.6
0.5 0.8
0.4 0.7
0.3
0.2
0.6
0.1
0.09
0.08
0.07
0.06
0.05
0.04
0.03
0.02 1 2 3 4 5 6 7 8 9 10 20 30 40 I/I>
Fig. 13. Inverse-time characteristic of overcurrent and earth-fault relay module SPCJ 4D28
RXIDG-type inverse
Technical data Feature Stage I> Stage I>> Stage I>>>
Start current
- at definite time 0.5…5.0 x In 0.5…40.0 x In and 0.5…40.0 x In and
- at inverse time 0.5…2.5 x In
Start time, typ. 70 ms 40 ms 40 ms
Operate time at definite 0.05…300 s 0.04…300 s 0.04…30 s
time characteristic
Time/current characteristic Extremely inv.
at inverse mode Very inv.
Normal inv.
Long-time inv.
RI type inv.
RXIDG type inv.
Time multiplier k 0.05…1.0
Reset time, typ. 40 ms 40 ms 40 ms
Retardation time <30 ms <30 ms <30
ms Reset ratio, typ. 0.96 0.96
0.96
Operate time accuracy 2% of set 2% of set 2% of set
at definite time mode value or 25 ms value or 25 ms value or 25 ms
Accuracy class index E 5
at inverse time mode
Operation accuracy 3% of set value 3% of set value 3% of set value
Feature
Start current
Start time, typ.
Operate time at definite
time characteristic
Time/current characteristic
at inverse mode
Time multiplier k
Reset time, typ.
Retardation time
Reset ratio, typ.
Operate time accuracy
at definite time mode
Accuracy class index E
at inverse time mode
Operation accuracy
set value
Serial The start and operate situations of the to be communicated, is marked with a multi-
communication protec- tion stages and the states of the plier 1. The event mask is formed by the sum
parameters output signals are defined as events and of the weight factors of all those events, that
provided with event codes, which can be are to be communicated.
Event codes transmitted to higher sys- tem levels via the
serial bus. An event, which is
Event mask
V155
V156
V157
V158
Event codes of the combined overcurrent and earth-fault relay module SPCJ 4D28
Code Event
E1 Starting of stage I> Starting of stage I>
E2 Tripping of stage I>>> reset
E3
E4
E5
E6
E7
E8
E9
E10
E11
E12
Explanations:
0 not included in event reporting
1 included in event reporting
* no code number
- cannot be programmed
Note.
The event represented by the codes E52...E54
are generated by a higher-level control data
communicator, for example type SRIO
1000M.
Remote transfer data In addition to the event data all input data 999. The default
(I data), setting values (S values), recorded password is 1.
infor- mation (V data) and certain other data
of the overcurrent module can be read via the The password is
SPA bus. Parameters marked with a W opened by writing the
letter can be altered via the SPA bus. password number to
parameter V160 and
When setting values are altered via the MMI closed by writ- ing
on the front panel or via the serial bus, the the password number
module checks that the entered parameter to parameter V161.
values are within the permitted setting
range. The relay module refuses to accept a
too high or a too low setting value, but
keeps the old setting value unchanged.
Input The measured currents and the status of the When the value of parameters I6…I8 is 1, the
s external control signals can be read (R) with corresponding control inputs are energized.
parameters I1…I8.
Information
Outputs The state information indicates the state of a module. When the value = 0, the signal has
signal at a certain moment. The recorded not been activated and when the value = 1, the
func- tions indicate such activations of signal has been activated.
signals, that happen after the last reset of the
registers of the
Output stages
Output signals
Checksum, SGF 1
Checksum, SGF 2
Checksum, SGF 3
Checksum, SGF 4
Checksum, SGF 5
Checksum, SGF 6
Checksum, SGF 7
Checksum, SGF 8
Checksum, SGB 1
Checksum, SGB 2
Checksum, SGB 3
Checksum, SGR 1
Checksum, SGR 2
Checksum, SGR 3
Checksum, SGR 4
Checksum, SGR 5
Checksum, SGR 6
Checksum, SGR 7
Checksum, SGR 8
Checksum, SGR 9
Checksum, SGR 10
Checksum, SGR 11
*) If the protection stage has been set out of function, the display shows 999 for the currently used value.
Measured and
Measured value
recorded parameter
values
Last 15 min maximum demand current
Number of starts of stage I>
Number of starts of stage I>>
Number of starts of stage I0>
Number of starts of stage I0>>
Number of starts of stage I>
Stage/phase that caused operation
Registered value
Overcurrent even mask Residual/unbalance current event mask Output signal event mask
Opening of password for remote setting Changing and closing of password for remote setting
Activation of self-supervision system
Program version
Reading of event register
The maximum capacity of the event register is general, the control data communicator reads
65 events. The content of the register can be read by the L command, the event data and forwards the information to
5 events at a time, only once. Should a fault occur, say, in the data an output device. Under normal conditions
communication, the B command can be used to re-read the contents of the event register of the relay module is empty.
the register. When required, the B command can be repeated. In The control data communicator also resets
abnor- mal status data, so this data is
normally zero.
Fault codes Once the self-supervision system has detected number one (1) and a green code number that
an internal relay fault, the IRF indicator on identifies the fault type. The fault codes
the front panel of the relay module is lit. At the should be recorded and stated when service is
same time the self-supervision alarm relay ordered.
that is normally picked up, drops off. In
most situa- tions a fault code appears on the The table below lists some of the fault codes
display of the relay module. This fault code of the combined overcurrent and earth-fault
consists of a red relay module SPCJ 4D28.
Fault code
4
30
50
51
52
53
54
56
195
131
67
203
139
75
252
253
General characteristics of
D-type relay modules
User´s manual and Technical description
Display, 1 + 3 digits
I > /I RESET
n STEP
t > [s]
k Reset / Step push-button
I >> / I
n
Indicators for setting t >> [s]
parameters
I o >/ I
n
t o > [s]
ko
I o >> /I
PROGRAM
n to Programming push-button
Indicators for switchgroups
SGF, SGB and SGR >> [s]
SGF
SGR
879B
Display The measured and set values and the recorded When the auxiliary voltage of a protection
data are shown on the display of the relay module is switched on the module
protection relay module. The display consists initially tests the display by stepping through
of four digits. The three green digits to the all the segments of the display for about 15
right show the measured, set or recorded value seconds. At first the corresponding segments
and the leftmost red digit shows the code of all digits are lit one by one clockwise,
number of the register. The measured or set including the decimal points. Then the center
value displayed is indicated by the adjacent segment of each digit is lit one by one. The
yellow LED indicator on the front panel. complete sequence is carried out twice. When
When a recorded fault value is being displayed the test is finished the display turns dark. The
the red digit shows the number of the testing can be interrupted by pressing the
corresponding register. When the display STEP push button. The protection func-
func- tions as an operation indicator the red tions of the relay module are alerted
digit alone is shown. throughout the testing.
Display main menu Any data required during normal operation When the push
are accessible in the main menu i.e. present button is pressed for
meas- ured values, present setting values and about 0.5 seconds,
recorded parameter values. the display moves
backward in the
The data to be shown in the main menu are display sequence.
sequentially called up for display by means of
the STEP push button. When the STEP push
button is pressed for about one second, the
display moves forward in the display sequence.
41 41
From a dark display only forward movement is possible. When the Unless the display is switched off by stepping
STEP push button is pushed constantly, the display continuously to the dark point, it remains lit for about 5
moves for- ward stopping for a while in the dark position. minutes from the moment the STEP push
button was last pushed. After the 5 minutes'
time-out the dispaly is switched off.
Display submenus Less important values and values not very the display moves forward when the STEP
often set are displayed in the submenus. The push button is pushed for one second and
number of submenus varies with different backward when it is pushed for 0.5 seconds.
relay module types. The submenus are The main menu has been re-entered when the
presented in the de- scription of the red display turns dark.
concerned protection relay module.
When a submenu is entered from a main
A submenu is entered from the main menu menu of a measured or set value indicated by
by pressing the PROGRAM push button for a LED indicator, the indicator remains lit and
about one second. When the push button is the ad- dress window of the display starts
released, the red digit of the display starts flashing. A submenu position is indicated by a
flashing, indi- cating that a submenu has been flashing red address number alone on the
entered. Going from one submenu to dispaly without any lit set value LED
another or back to the main menu follows indicator on the front panel.
the same principle as when moving from the
main menu display to another;
Selector switch- Part of the settings and the selections of the
groups SGF, SGB operation characteristic of the relay modules Switch No Pos. Weigth Value
and SGR in various applications are made with the
selector
switchgroups SG_ . The switchgroups are 1 1 x 1 = 1
soft- 2 0 x 2 = 0
ware based and thus not physically to be found 3 1 x 4 = 4
in the hardware of the relay module. The 4 1 x 8 = 8
indi- cator of the switchgroup is lit when the 5 1 x 16 = 16
checksum of the switchgroup is shown on 6 0 x 32 = 0
the display. Starting from the displayed 7 1 x 64 = 64
checksum and by entering the setting mode, 8 0 x 128 = 0
the switches can be set one by one as if they
were real physical switches. At the end of the Checksum = 93
setting procedure, a checksum for the whole
switchgroup is shown. The checksum can be
used for verifying that the switches have been Fig. 2. Example of calculating the checksum of
properly set. Fig. 2 shows an example of a a selector switchgroup SG_.
manual checksum calculation.
The functions of the selector switches of the
When the checksum calculated according to different protection relay modules are described
the example equals the checksum indicated in detail in the manuals of the different
on the display of the relay module, the relay modules.
switches in the concerned switchgroup are
properly set.
Settings Most of the start values and operate times are and the second settings can be done in three
set by means of the display and the push different ways:
buttons on the front panel of the relay
modules. Each setting has its related indicator 1) By command V150 over the serial
which is lit when the concerned setting value communi- cation bus
is shown on the display. 2) By an external control signal BS1, BS2 or
RRES (BS3)
In addition to the main stack of setting values 3) Via the push-buttons of the relay module,
most D type relay modules allow a second see submenu 4 of register A.
stack of settings. Switching between the main
settings
43 43
NOTE! IN MOST MENU CHARTS THE SUBMENUS HAVE BEEN DRAWN IN A HORIZONTAL DIRECTION IN ORDER TO GET ALL
MAIN AND SUBMENU POSITIONS SHOWN IN THE SAME CHART.
Fig.3. Basic principles of entering the main menus and submenus of a relay module.
44 44
MAIN MENU SUBMENUS
Current on phase L1
Current on phase L2
Current on phase L3
REV. STEP 0.5 SUBMENU FWD. STEP 1 s
Neutral current Io S
s
2 Second
Actual start value I> setting value
1 Main
setting for I>
value for I>
2 Second
t>> 1 Main setting value
setting for t>>
R
of stage I>> value for
E t>>
V.
2 Second
Actual start value Io> setting value
S 1 Main for Io>
T setting
E value for
P Actual operate time to> Io> Second setting
or multiplier ko 2 value for to> or
.5
Main setting ko
s 1
value for to> or
M Actual start value Io>> ko
A 2 Second
setting value
I for Io>>
N 1 Main setting
Actual operate time value for
to>> Io>>
Second
2 setting value
M Main setting for to>>
Actual setting of 1 value for
functional
E to>> Main setting of
switchgroup SGF1 2
N SGF2 checksum
U
1 Main setting of
SGF1 checksum
Actual setting of blocking 1 Main setting of 2 Second setting of
switchgroup SGB SGB checksum SGB
F
W
checksum
D.
Actual setting of relay 1 Main setting of
2 Main setting of
S switchgroup SGR1 SGR1 SGR2 checksum
T checksum
E
P
1
Latest memorized, event
1 Event (n-1) 2 Event (n-2)
(n) value of phase value of phase L1
1
value of phase L1 L1
s 2 Event (n-2)
Latest memorized, event value of phase L2
2 1 Event (n-1)
(n) value of phase
L2 Event (n-2)
value of phase L2 2
value of phase L3
Latest memorized, event 1 Event (n-1)
3 value of phase
(n) L3
value of phase L3
1 Highest maximum
Maximum demand demand value
current found
4
value for 15 minutes
Fig. 4.Example of part of the main and submenus for the settings of the overcurrent and earth-
fault relay module SPCJ 4D29. The settings currently in use are in the main manu and they are
displayed by pressing the STEP push button. The main menu also includes the measured
current values, the registers 1...9, 0 and A. The main and second setting values are located in
the submenus and are called up on the display with the PROGRAM push button.
Example 1 Operation in the setting mode. Manual for the main setting is 0.80 x I and for the
n
setting of the main setting of the start current second setting 1.00 x I . The desired main
n
value I> of an overcurrent relay module. The start value is 1.05 x I .
n
initial value
a)
Press push button STEP repeatedly until the RESE
T 5x1s
LED close to the I> symbol is lit and the STEP
b) PROGRAM
Enter the submenu to get the main setting 1s
value by pressing the PROGRAM push
button more than one second and then 1 0. 8 0
releasing it. The red display digit now shows
a flashing number 1, indicating the first
submenu position and the green digits show
the set value.
PROGRAM
c)
Enter the setting mode by pressing the PRO-
5s
1 0. 8 0
GRAM push button for five seconds until the
display starts flashing.
1 0. 8 0
PROGRAM
d) 1s
Press the PROGRAM push button once again
for one second to get the rightmost digit
flash- ing.
RESE
T
1 0. 8 5
STEP
e) 5x
Now the flashing digit can be altered. Use the
STEP push button to set the digit to the
desired value.
PROGRAM
1s
f)
Press the PROGRAM push button to make 1 0. 8 5
the middle one of the green digits flash.
RESE
T
STEP
g) 2x
Set the middle digit with of the STEP push
button. 1 0. 0 5
PROGRAM
h) 1s
Press the PROGRAM push button to make
the leftmost green digit flash. 1 0. 0 5
i) l)
Set the digit with the STEP push P
button. re
If ss
move th
decima e
point P
the R
j) STE O
Press the PROGRAM push button to make button. G
the decimal point flash. R
A
M
RESE
push button to make the whole display flash. T
STEP
In this position, corre- sponding to position
c) above, one can see the new value before it
is recorded. If the value needs changing, use
0x 1 1. 0 5
the PROGRAM push but- ton to alter the
value.
PROGRAM
m) 1s
When the new value has been corrected,
record it in the memory of the relay module by
1 1. 0 5
pressing the PROGRAM and STEP push
buttons simul- taneously. At the moment the
information en- ters the memory, the green
dashes flash once in the display, i.e. 1 - - -. RESE
T
STEP
0x 1 1. 0 5
PROGRAM
1s
1 1. 0 5
RESE
T
STEP
1 - - -
PROGRAM
n)
1
PROGRAM
Recording of the new value automatically 5s
initi- ates a return from the setting mode to
the normal submenu. Without recording one
can leave the setting mode any time by
pressing the PROGRAM push button for
about five sec- onds, until the green display
digits stop flashing.
RESE
o) T
STEP
If the second setting is to be altered, enter 1s
submenu position 2 of the setting I> by
pressing the STEP push button for approx.
one second. The flashing position indicator 1
will then be replaced by a flashing number 2
which indicates that the setting shown on
the display is the second setting for I>.
until the first digit is switched off. The LED
Enter the setting mode as in step c) and still shows that one is in the I> position and
proceed in the same way. After recording the display shows the new setting value
of the re- quested values return to the currently in use by the relay module.
main menu is obtained by pressing the
STEP push button
Example 2 Operation in the setting mode. Manual The initial value for the checksum is 000 and
setting of the main setting of the checksum the switches
for the switchgroup SGF1 of a relay module.
SGF1/1an are to be set in position 1. This means that a
d SGF1/3 checksum of 005 should be the final result.
a) RESE
T nx1s
Press push button STEP until the LED close STEP
d) PROGRA
M
f) PROGRA
1
When switch number 1 is in the requested M
h) Usin b
The switch position is altered to the desired procedur
position 1 by pressing the STEP push button switche
once. 4... In
and settin
th position
in correspond-
in
i) th
RESE
ased on the set switch positions is shown. 1x
1 3 1
T
STEP
PROGRAM 5x1s
1 0 0 5
k) RESE
If the correct checksum has been obtained, it T
STEP
is recorded in the memory by pressing the
push buttons PROGRAM and STEP 1 - - -
simultaneously. At the moment the
information enters the memory, the green
dashes flash in the display, i.e.1 - - -. If the PROGRAM
l)
Recording the new value automatically PROGRAM
5s
initiates a return from the setting mode to
the normal menu. Without recording one 1 0 0 5
can leave the setting mode any time by
pressing the PRO- GRAM push button for
about five seconds, until the green display
digits stop flashing.
m) RESE
T
After recording the desired values return to the STEP
nx1s
main menu is obtained by pressing the STEP
push button until the first digit is turned off.
The LED indicator SGF still shows that one is
in the SGF position and that the display
shows the new checksum for SGF1 currently
in use by the relay module.
Recorded The parameter values measured at the moment regis- ters are illustrated in the descriptions
information when a fault occurs or at the trip instant are of the different relay modules. Additionally,
recorded in the registers. The recorded data, the sys- tem front panel of the relay contains a
except for some parameters, are set to zero simplified list of the data recorded by the
by pressing the push buttons STEP and various relay modules of the protection relay.
PRO- GRAM simultaneously. The data in
normal registers are erased if the auxiliary All D type relay modules are provided with two
voltage supply to the relay is interrupted, only general registers: register 0 and register A.
the set values and certain other essential
parameters are maintained in non-volatile Register 0 contains, in coded form, the
registers during a voltage failure. informa- tion about e.g. external blocking
signals, status information and other signals.
The number of registers varies with different The codes are explained in the manuals of the
relay module types. The functions of the different relay modules.
Submenu 2 of register A contains a bus The default value is 001 for the address code,
Register A commu- nication monitor for the SPAbus. If 9.6 kilobaud for the data transfer rate and
contains the the protec- tion relay, which contains the 001 for the password.
address code of relay module, is linked to a system
the relay including a contol data communicatoe, for In order to secure the setting values, all
modul which is instance SRIO 1000M and the data settings are recorded in two separate
reqiured by the communication system is operating, the memory banks within the non-volatile
serial counter reading of the monitor will be zero. memory. Each bank is complete with its
communi- Otherwise the digits 1...255 are own checksum test to verify the condition of
cation system. continuously scrolling in the monitor. the memory contents. If, for some reason,
the contents of one bank is disturbed, all
Submenu 1 of Submenu 3 contains the password required settings are taken from the other bank and
register A for changing the remote settings. The address the contents from here is transferred to the
contains the code, the data transfer rate of the serial faulty memory region, all while the relay is in
data trans- fer communica- tion and the password can be set full operation condition. If both memory
rate value, manually or via the serial communication banks are simultaneously damaged the relay
expressed in bus. For manual set- ting see example 1. will be be set out of operation, and an alarm
kilobaud, of signal will be given over the serial port and
the serial the IRF output relay
communicatio
n.
Trip test function Register 0 also provides access to a trip test The selected starting or tripping is activated
function, which allows the output signals of by simultaneous pressing of the push
the relay module to be activated one by one. buttons STEP and PROGRAM. The signal
If the auxiliary relay module of the protection remains activated as long as the two push
assem- bly is in place, the auxiliary relays butttons are pressed. The effect on the output
then will operate one by one during the relays depends on the configuration of the
testing. output relay matrix switches.
When pressing the PROGRAM push button The self-supervision output is activated by
for about five seconds, the green digits to press- ing the STEP push button 1 second
the right start flashing indicating that the when no setting indicator is flashing. The IRF
relay module is in the test position. The output is activated in about 1 second after
indicators of the settings indicate by flashing pressing of the STEP push button.
which output signal can be activated. The
required output function is selected by pressing
the PROGRAM push button for about one The signals are selected in the order illustrated
second. in
Fig. 4.
The indicators of the setting quantities refer to
the following output signals:
IRF I> TRIP I» START I» TRIP Io> START Io> TRIP Io»START Io» TRIP
I> START
REGISTER 0
PROGRAM PROGRAM PROGRAM PROGRAM
I> PROGRAM PROGRAM PROGRAM PROGRAM PROGRAM PROGRAM
5s 1s 1s t> 1s 1s
I» 1s 1s 1s 1s 1s
t»
Io» to»
Io> to>
Fig. 5.Sequence order for the selection of output signals in the Trip test mode
If, for instance, the indicator of the setting t> scheme, by pressing
is flashing, and the push buttons STEP and the PROGRAM push
PRO- GRAM are being pressed, the trip button for about
signal from the low-set overcurrent stage is five sec- onds.
activated. Re- turn to the main menu is
possible at any stage of the trip test sequence
Note! The effect on the output relays then depends
on the configuration of the output relay
matrix switchgroups SGR 1...3.
Example 3 Trip test function. Forced activation of the
outputs.
a)
Step forward on the display to register 0.
RESE
T
STEP nx1s
0
b) 3I>
Press the PROGRAM push button for about I
right.
PROGRAM
RESET
0 0 0 0
5s I > /I n STEP
t > [ s]
k
I >> / I n
t >>[s]
I o >/ I n
t o > [s]
ko
I o >> /I n
PROGRAM
t o >>[s]
SGF
SGB
SGR
c) TRIP
SPCJ 4D29
Hold down the STEP push button. After one
879B
d) 3I>
I
Press the PROGRAM push button for one
second and the indicator of the topmost setting I I I IL1 IRF
L2 L3 o
start flashing.
0 0 0 0
e) RESET
t > [ s]
press k
I >> / I n
t o >>[s]
the relay output switchgroups SGR. SGF
PROGRAM
SGB
RESE SGR
T
STEP
879B
TRIP
SPCJ 4D29
PROGRAM
f)
To proceed to the next position press the PRO- 3I>
I
GRAM push button for about 1 second until
0 0 0 0
I L1 I L2 I L3 I o IRF
1s I >> / I n
t >>[s]
I o >/ I n
t o > [s]
ko
I o >> /I n
PROGRAM
t o >>[s]
SGF
SGB
SGR
TRIP
SPCJ 4D29
879B
g) 3I>
Press the push buttons PROGRAM and STEP I
0 0 0 0
IRF
I o >/ I n
RESE t o > [s]
T ko
STEP
I o >> /I n
t o >>[s]
PROGRAM
SGF
SGB
SGR
TRIP
PROGRAM
SPCJ 4D29
879B