Vous êtes sur la page 1sur 178

SPAD 346 C

Stabilized Differential Relay


User´s manual and Technical description

I n = 1A 5A ( I 2 ) 2
f n = 50Hz I n = 1A 5A ( I 01 )
5

n STEP
80...265 V – 1 /n RESET

~
18...80 V –

2tp I n 02 / n
t >> [ s ]

2f / 1f 02

In
2 3 I >> Trip 2 I 01 > Trip 2 I > Trip 1 1 / n
>[ ]
In
2 2 / n
0029A
0021A

0023A
0199A

RS 621 Ser.No.
1MRS 750096-MUM EN
SPAD 346 C
Issued 1996-08-08
Modified 2002-04-12 Stabilized
Version F (replaces 34 SPAD 5 EN1)
Checked MK
Approved OL
Differential Relay
Data subject to change without notice

Contents Features
...................................................................................................................... .... 3
Application ........................................................................................
............................. 4
Description of function
.................................................................................................. 4
Three-phase stabilized differential relay module SPCD 3D53
................................... 4
Earth-fault relay module SPCD
2D55 ....................................................................... 6
Combined overcurrent and earth-fault relay module SPCJ
4D28 .............................. 8
Connection diagram
.......................................................................................................
9
Connections .......................................................................................
.......................... 10
Control input and output relay module
........................................................................ 11
Intermodular signals (modified 1997-10)
...................................................................... 12
Power supply module
................................................................................................... 13
Operation indicators
.....................................................................................................
14
Technical data (modified 2002-04)
............................................................................... 15
Recommendations for current transformers
.................................................................. 18
Circuit-breaker control
................................................................................................. 20
Application examples
.................................................................................................... 21
Setting instructions
.......................................................................................................
25
Commissioning ..................................................................................
.......................... 28
Testing .............................................................................................
............................ 28
Maintenance and service
............................................................................................... 33
Spare parts
........................................................................................................
............ 33
Delivery alternatives
.....................................................................................................
33

2 2
Order numbers
.........................................................................................................
.... 34
Information required with order
................................................................................... 34
Dimensioned drawings and mounting
.......................................................................... 35

In addition to this general part the complete manual of the stabilized


differential relay includes the following individual documents:

Stabilized differential relay module SPCD 3D53


Earth-fault relay module SPCD 2D55
Combined overcurrent and earth-fault relay module SPCJ 4D28
General characteristics of D-type SPC relay modules

Features Integrated three-phase differential relay, over- No interposing transformers are needed for the
current relay and earth-fault relay protection of two-winding transformers - nu-
merical vector group matching on HV and LV
Stabilized three-phase differential relay provid- side
ing winding short-circuit and interturn fault
protection for two-winding transformers and Wide CT ratio correction range - accurate cor-
generator-transformer units and winding rection allowed by digital setting
short- circuit protection for generators.
Sensitive phase current and phase angle
Earth-fault protection for transformer HV and displays facilitate the checking of
LV side windings according to the desired measurement circuit connection and vector
prin- ciple: the stabilized differential current group matching
princi- ple, the high-impedance principle,
the calcu- lated or measured residual current Four trip and four signal relay outputs
principle or the neutral current principle available to the protection design engineer

Three-stage overcurrent protection for trans- Five programmable external control inputs in-
formers and generators and two-stage back-up tended for the indication and retransmission
protection for earth-fault protection of alarm and trip signals of gas relays, oil
tempera- ture sensors and other sensors of
The operation characteristic of the differential transformer auxiliary devices
relay easily adapted for different applications
Adjustable CBFP operate time to improve
Short operate times, even with partially reli- ability of operation
satu- rated current transformers
Integrated disturbance recorder capable of re-
Stabilization prevents unwanted operations at cording currents and digital signals - signals to
faults outside the protected area and trans- be used for triggering selectable
former inrush currents
High immunity to electrical and electromag-
Blocking based on the ratio of the second har- netic interference allows the relay to be used
monic and the fundamental component of in severe environments
the differential current prevents unwanted
opera- tions at transformer inrush currents High availability and system reliability due to
continuous supervision of hardware and soft-
Blocking based on the ratio of the fifth har- ware
monic and the basic frequency component of
the differential current prevents operation in
harmless situations of transformer overexcitation
- can be eliminated if the ratio of the fifth
harmonic and the basic frequency component
increases at high overvoltages
Application The stabilized differential relay SPAD 346 C is against winding
designed to be used to protect two-winding short-circuit,
transformers and generator-transformer units
3 3
interturn fault, earth fault and short circuit generators against winding short-circuit and
and to protect short circuit. The relay can also be used for
the protection of a three-winding transformer
pro- vided 75% of the short circuit power is fed
from the same direction.

Description of The integrated differential relay SPAD 346 C LV side may use the same or different rated
operation includes three independent relay modules: a currents.
three-phase stabilized differential relay module
SPCD 3D53, an earth-fault relay module Below a short description of the features of
SPCD the protection relay modules. The manuals for
2D55 and a combined overcurrent and earth- the separate relay modules describe the
fault relay module SPCJ 4D28. The rated modules more in detail.
cur- rents of the relay are 1 A and 5 A. The
HV and

Three-phase The differential relay module SPCD 3D53 formers to obtain vector group matching and to
stabilized pro- vides protection for winding short- match the secondary currents of the main
differential circuit and interturn faults. The differential trans- formers. Interposing CTs have also been
relay module relay compares the phase currents on both used to eliminate the zero-sequence
SPCD 3D53 sides of the object to be protected. Should the components of the phase currents at earth
differential current of the phase currents in faults occurring outside the protected area. The
one of the phases exceed the setting of the differential current relay SPAD 346 C
stabilized operation character- istic or the eliminates the use of interposing transformers
instantaneous protection stage of the module, for the protection of two-winding
the module provides an operate signal. transformers as the differential relay module
Different amplitudes or phase difference of the allows the transformer vector group matching,
currents may be the reason for the differential the CT ratio correction and the elimination of
current. the zero-sequence component of the phase
cur- rents to be digitally implemented on the
Interposing current transformers have HV and/or the LV side.
normally been used in the differential
protection of trans-
Stabilized
differential or transformer inrush situations. Due to these
current stage In power transformer protection differential circumstances the operation of the differential
current is caused by CT errors, varying tap relay has been stabilized in respect of the load
changer positions, transformer no-load current, current. In a stabilized differential relay the
transformer inrush currents, transformer differential current required for relay
overexcitation in overvoltage and underfre- operation is higher, the higher the load
quency situations, and CT saturation at high current is. The stabilized operation
currents passing through the transformer. Dif- characteristic of the differ- ential relay module
ferential current caused by CT errors and tap- and the setting range of the characteristic is
changer position grows at the same per cent presented in the description of the differential
ratio as the load current increases. In the relay module SPCD 3D53.
protection of generators the differential
current is caused by CT errors and saturation The operation of the differential relay module
of the CTs in situa- tions where high SPCD 3D53 is based on the fundamental fre-
currents pass through the transformer. quency components. Operation based on fun-
damental frequency components is accurate
High currents passing through the object to be and stable: the DC component and harmonics
protected may be caused by short circuits out- of the current do not cause unwanted operation
side the protected area, large currents fed by of the protection stage.
the transformer or the generator in motor
start-up
Blocking based Transformer magnetizing inrush currents occur ferential current, which would cause the relay to
on the second har- when energizing the transformer after a period operate almost always when the transformer is
monic of the differen- of deenergization. The inrush current may be connected to the network. Typically, the inrush
tial current many times the rated current and the halving current contains a large amount of second har-
time may be up to several seconds. To the monics. Blocking of the operation of the stabi-
differential relay inrush current represents dif- lized stage of the relay at magnetizing inrush
4 4
current is based on the The blocking also prevents unwanted the protected transformer already connected to
ratio of the operation at recovery and sympathetic the network, being energized.
amplitudes of the magnetizing in- rush. At recovery inrush the
second harmonic magnetizing cur- rent of the transformer to The connection of the power transformer
digitally filtered from be protected increases momentarily when the against a fault inside the protected area does
the differential voltage returns to nor- mal after clearance of not delay the operation of the relay module,
current and the a fault outside the pro- tected area. because in such a situation the blocking
fundamental fre- Sympathetic inrush is caused by a based on the second harmonic of the
quency Id2f/Id1f. transformer, which runs in parallel with differential current is prevented by a separate
algorithm based on the waveform and the rate
of change of the differen- tial current.

Blocking based on Inhibition of relay operation in situations of matically eliminated by a separate blocking in-
the fifth harmonic of overexcitation is based on the ratio of the hibiting setting Id5f/Id1f>>. When required,
the differential fifth harmonic and the fundamental the blocking based on the second and fifth
current component of the differential current har- monic of the differential current can be
Id5f/Id1f. At dangerous levels of overvoltage disa- bled.
which may cause damage to the transformer,
the blocking can be auto-

setting range of the instantaneous stage


Instantaneous In addition to the stabilized stage the Id/In>>
differential differential relay module SPCD 3D53 has a is 5...30.
current stage separate adjust- able instantaneous stage the
operation of which is not stabilized. The Should the stabilizing current be less than
instantaneous differential current stage 30% of the differential current, there is most
operates when the fundamental component certainly a fault in the protected area. In such
calculated from the differential cur- rent a situation the set operate value Id/In>> will
exceeds the set operate limit Id/In>> or when be halved and the blockings of the stabilized
the instantaneous value of the differential stage are auto- matically prevented.
current exceeds the level 2.5 x Id/In>>. The

Disturbance recorder is 38 cycles. The recording memory has the


The differential relay module SPCD 3D53 is capacity of storing one recording at a time.
provided with an integrated disturbance re- Sampling frequency is 40 samples/cycle. The
corder that is capable of recording six recording is downloaded by using a PC pro-
phase currents, the internal trip and blocking gram. The recording memory has to be reset
signals of the module and the control input before a new recording is possible.
signals. Recording can be triggered by the
rising or falling edge of these signal. The
recording length
Earth-fault When single-phase or two-phase earth faults winding transformer. The earth-fault protec-
relay module occur in the area to be protected the sensitivity tion can be implemented by four principles:
SPCD 2D55 of the differential protection measuring phase the high-impedance principle, the numerical
currents may not be sufficient, in particular, stabi- lized differential current principle, the
if the star point of the transformer is residual overcurrent principle, or the neutral
resistance- earthed. overcur- rent principle. The HV and LV side
earth-fault protection are quite independent
The earth-fault relay module SPCD 2D55 pro- of each other, so the protection principle on
tects the HV and LV side windings of a two- the HV side does not have to be the same as
that of the LV side.

Numerical stabilized The numerical differential current stage oper- The relay measures a differen- tial current as
differential current ates exclusively on earth faults occurring in the the difference between the re- sidual current
principle protected area, i.e. in the area between the of the phase currents and neutral current. An
phase CTs and the CT of the neutral external stabilizing resistor is not required.
connection. An earth fault in this area (See application example 1)
appears as a differential current between the
residual current of the phase currents and At an earth fault in the protected area the phase
the neutral current of the conductor between difference between the residual current of the
the star point of the trans- former and earth. phase currents and the neutral current is greater
5 5
than 90 , i.e. the protected so that the higher the average of the ate limit, an earth-fault has occurred in the
directions of the phase currents on the concerned side the protected area and the relay operates when the
residual current and higher is the differential current required for preset operate time has elapsed. Such a
the neutral current starting. situation may arise when the transformer is
are towards the connected to the network on the HV side
protected area. In the Should the residual current of the phase against an internal earth fault on the LV side.
calculation of the currents be zero the neutral current exceeding So, in this situation the LV side protection
differen- tial current the oper- will operate.
the directions of the
residual current and When the numerical stabilized differential cur-
the neutral current rent principle is used the ratio of the neutral
are so weighted that current and the residual current of the phase
operation is possible currents must be greater than the setting I01/
only if the phase I1 on the HV side and greater than the setting
difference between I02/ I2 on the LV side to allow starting of the
the residual current earth-fault protection on the respective side.
of the phase cur- The settings secure the selectivity of the
rent and neutral protec- tion taking into account the
current exceeds 90 . distribution of the earth-fault current
The smaller the between the transformer neutral and the
phase difference, i.e. network. The distribution of the earth-fault
the closer it is to current depends on the ratio of the zero-
90 , the higher the sequence impedances of the transformer and
differential current the supplying network and also on the
required for position of the earth fault in the winding. In
operation. addition, the number and the location of the
other star-points of the network influence the
The operation distribution of the earth
characteristic for the fault.
differential principle
is presented in the The transformation ratio correction settings
document describ- I01/In and I1/In allow correction of the
ing the earth-fault neutral connection CT and phase CT ratios on
relay module SPCD the HV side, whereas the settings I02/In and
2D55. The setting I2/In are used for the corresponding ratio
range of the basic corrections on the LV side.
settings P1/In and
P2/In is 5...50%. When the stabilized differential current princi-
The operation of the ple is used, the saturation of the current
numeri- cal trans- formers in asymmetrical inrush
differential current situations does not cause any problems, if the
principle is stabilized operation of the earth-fault relay is set to be
in respect of the blocked in inrush situations. This blocking is
phase currents (load based on the ratio of the second harmonic and
current) on the side the fundamental fre- quency component of
of the winding to be the neutral current I01 or I02.
High-impedance type Restricted earth-fault protection (REF protec- decreases when the current transformer is
protection tion) is often implemented by the high- saturated. The reactance of the magnetizing
imped- ance principle. When this principle is circuit of a fully saturated transformer is zero
employed the relay operates exclusively on and the impedance is formed of the winding
faults occurring within the protected area. resistance. Due to the resistor fitted in the
At external faults relay operation is inhibited differential current circuit the sec- ondary
by a stabilizing resis- tor mounted in the current of an unsaturated transformer
differential current circuit in series with the
matching transformer of the relay (see
application examples 2 and 3).

The operation of high-impedance type


protec- tion, when a fault occurs in the
protected area, is based on the fact that the
impedance of the current transformer rapidly
6 6
flows through the due to differential current circuit currents
secondary circuit of caused by faults outside the protected area. At faults occurring within the protected area the
the un- saturated The basic settings P1/In and P2/In are used current transformers try to feed current into
transformer. The for setting the start values on the HV side the differential current circuit, in which case
start value of the and the LV side, when the high-impedance the relay operates. To keep the resistance of
earth-fault principle is used. The relay starts when the secondary circuit as low as possible, the
protection is set the differential current flowing to the relay sum- ming point of the currents should be
high enough to exceeds the setting. The operation is not located as close to the current transformers as
prevent operation stabilized in the relay. possible.

Residual overcurrent The residual overcurrent method can be used Earth-fault protection based on these
principle and for the earth-fault protection of delta- principles starts when the residual current or
neutral overcurrent connected windings connected to the neutral cur- rent exceeds the set start limit
principle network which in- cludes earthed neutral P1/In or P2/In. The operation has a definite-
points. Three phase cur- rent transformers are time characteristic.
used. The sum of the phase currents, i.e. the
sum of the zero-sequence cur- rents in the A blocking function based on the second har-
phases, is calculated in the relay module on monic of the neutral current I01 or I02 can
the basis of the phase currents linked to the be used in combination with the neutral
relay. The three phase currents will not sum current principle. This blocking can also be
to zero for internal earth faults. Special used if the the residual current of the phase
attention has to be paid to the operate time currents is formed via an external connection
settings in order to avoid unwanted by connect- ing the neutral terminals of the
operations, when the phase CTs saturate at windings of the relay’s phase current
external faults or in inrush situations. matching transformers to the 5 A or 1 A
terminal of the neutral current matching
Earth-fault protection based on neutral transformer I01 or I02. Should the residual
current can be used as back-up protection for current be numerically formed inside the
the earth- fault protection. relay module, this blocking function cannot be
used.

Operate time The definite operate time t01> and t02> can
be separately set for the the HV side and the
LV side in the range 0.03...100 s.

Disturbance recorder The earth-fault relay module SPCD 2D55 is recording is about 30 cycles and the capacity
provided with an integrated disturbance re- of the recording memory is one recording at
corder capable of recording six phase a time. The sampling frequency of the
currents, two neutral currents, the internal distur- bance recorder is 40 samples/cycle. A
start and block- ing signals of the module and PC pro- gram can be used for downloading
the control input signals. Recording can be the recording from the memory. The
triggered by the rising or falling edge of these recording memory has to be reset before a
signals. The length of the new recording is possible.
Combined over- The overcurrent unit of the combined directional earth- fault protection and it is well
current and earth- overcur- rent and earth-fault relay module suited for earth- fault back-up protection for
fault relay module SPCJ 4D28 is designed to be used for single- power transform- ers. The earth-fault unit is
SPCJ 4D28 phase, two-phase and three-phase short-circuit provided with two protection stages: a low-set
protection of power transformers and stage I0> and a high- set stage I0>>. The starting
generators. The overcurrent protection of the stage provides a start signal which can be
includes three overcurrent protec- tion linked to the desired output signal. If the
stages: stage I>, stage I>> and stage I>>>. An earth fault still persists, when the set operate
overcurrent stage starts once the current on time elapses, the concerned stage provides an
one of the phases exceeds the setting value operate signal.
of the stage. If the overcurrent situation
lasts long enough to exceed the operate time
set for the module, the stage that started
provides a trip signal to the circuit breaker.

The earth-fault unit of the combined


overcur- rent and earth-fault relay module
SPCD 4D28 is intended to be used for non-
7 7
The low-set stages different stages can be totally inhibited by network. In the protection of Yy-connected
(I> and I0>) may selecting the appropriate setting for the power transformers the phase discontinuity
have either a configuration switches. pro- tection can have a signalling function at
definite time or least. In certain cases the phase discontinuity
an inverse time In addition, the combined overcurrent and protection can be used for unbalance
operating earth- fault relay module SPCJ 4D28 provides protection of small generators.
characteristic, protec- tion against phase discontinuity I>.
whereas the high- The phase discontinuity protection The combined overcurrent and earth-fault

SPA-ZC_
set stages only monitors the mini- mum and maximum relay module SPCJ 4D28 measures currents
have a definite phase current and calcu- lates the applied to the HV side phase current inputs
time mode of differential current I between the phases. IL1, IL2 and IL3 and the LV side neutral
operation. The The phase discontinuity protection unit can current input I02 of the relay.
operation of the be used for monitoring the condition of the

Circuit-breaker The relay modules SPCD 3D53, SPCD 2D55 lowing a secured circuit breaker trip system to
failure protection and SPCJ 4D28 are provided with be implemented.
integrated circuit-breaker failure protection
(CBFP), al-
Connection P2 P1 P1 P2
diagram L1

L2

L3 S1
S2 S1 S2
Rx Tx
S1 P1 P1 S1

S2 S2
P2 P2

+ (~) Uaux
- (~)
X0/1

X2/1
X0/38X0/37
A X0/25
X0/2
N

5X0/26
N
5A

U5
N
N

5A
5A

+ -
SERIAL
PORT
I/O
X2/16 IRF
X2/17
X2/18
IRF +
U6

X2/14
X2/15
Y/ U1 IRF SS1 +
SPAD 346 C SS1
SS2 X2/11
Y/ SS3 X2/12

BS1 3I> SS4 X2/13


SS2
BS2 TS1 +
U4 3I>> TS2
BS3
X1/1 BS4 TS3 X2/9
TS4 X2/10
X1/2 BS1 BS5 SS3
I/O +

X1/3 U2 IRF X2/7


SS1
X1/4 BS2 SS4 X2/8
SS2 +
SS3 X2/5
X1/5 BS3 BS1 I 01 > TS1 TRIP
SS4 X2/6
X1/6 BS2 I 02 > TS1 +
BS3 TS2
X1/7 TS3 X2/3
BS4 TS4

X1/8 BS4 BS5 U3 I/O TRIP


X2/4
TS2
IRF +
X1/9 SS1
3I> SS2 X1/15
X1/10 BS5
I SS3 X1/16
BS1 SS4 TRIP
I> X1/17
BS2 TS1 X1/18
BS3 TS2 TS3 +
TS3
TS4
X1/11
I/O
X1/12
TRIP
X1/13
X1/14
TS4 +

8 8
Fig. 1. Connection diagram for the stabilized differential relay SPAD 346 C.

Uaux Auxiliary voltage


TS1...TS4 Output relay (heavy-duty types)
SS1...SS4 Output relay
IRF Self-supervision output relay
BS1...BS5 External control inputs
U1 Three-phase stabilized differential relay module SPCD 3D53
U2 Earth-fault relay module SPCD 2D55
U3 Combined overcurrent and earth-fault relay module SPCJ 4D28
U4 I/O relay module SPTR 9B31
U5 Power supply module SPGU 240A1 or SPGU 48B2
U6 Energizing input module SPTE 8B18
TS1...TS4 Output signals (for heavy-duty output relays)
SS1...SS4 Output signals
SERIAL PORT Serial communication port
SPA-ZC_ Bus connection module
Rx/Tx Receiver (Rx) and transmitter (Tx) for the connection of optical fibres

9 9
Terminals The terminals of the differential relay SPAD
346 C are as follows:

Terminal Contact
group interval

X0 1-2
X0 1-3
X0 4-5
X0 4-6
X0 7-8
X0 7-9
X0 13-14
X0 13-15
X0 16-17
X0 16-18
X0 19-20
X0 19-21
X0 25-26
X0 25-27
X0 37-38
X0 37-39

X1 1-2
X1 3-4
X1 5-6
X1 7-8
X1 9-10
X1 11-12-13-14
(heavy-duty two-pole relay, see "Circuit breaker control")
X1 15-16-17-18

X2 1-2

X2 3-4
X2 5-6
X2 7-8
X2 9-10
X2 11-12-13
X2 14-15
X2 16-17-18

The protection relay is connected to the optical fibres are connected to the counter
fibre- optic bus via a bus-connection con- tacts Rx and Tx of the module through
module, type SPA-ZC 17 or SPA ZC 21, snap-on connectors. The selector switches are
fitted to the D connector on the rear panel set in the position "SPA".
of the relay. The
1 13
X2 I L1 I'L1
2 14

TS2 Uaux 3 15
IRF SS1 SS2 SS3 SS4 TS1

4 16

IL2 5 17 IL' 2
Made in Finland Serial Port
6 18

7 19

SPA I L3 8 20 I'L3

9 21

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
18

BS1 BS2 BS3 BS4 BS5 TS4 TS3 25 37

I 01 26 38
02 I
X1 27 39
Fig. 2. Rear view of the stabilized differential relay SPAD 346 C

Control input and The control input and output relay module Five external inputs BS1, BS2, BS3, BS4
output relay of the differential relay SPAD 346 C is fitted to and
module the rear panel of the relay in the same BS5 are available to the differential relay
direction as the mother board. To remove the SPAD
module, the fixing screws have to be undone 346 C. For example, the alarm and trip signals
and the protec- tive earth cable of the module from the power transformer gas relay and the
plus the flat cable connecting the mother winding temperature sensor can be linked to
board to the module have to be the external control inputs. The external
disconnected. control inputs can be used for:
- blocking one or several protection stages of
The control input and output relay module the relay modules
contains the output relays (8 pcs + IRF), the - direct output relay
control circuits of the relays, the control
electronic circuits of the external control - the indication of the primary protection
inputs (5 pcs) and the D connector required relay signals or operations
for serial communica- tion. A flat cable links - resetting the operation indicators, latched
the output and input signals of the module to output relays, registers and recording memory
the mother board. The relay module - changing the actual setting values of the
locations U1, U2 and U3 are identical. relay modules. i.e.switching from main
setting val- ues to second setting values and
The output signals SS1...SS4 and TS1...TS4 vice versa.
of the mother board control an output relay
with the same designation. The operation The switchgroups of the relay modules are
of the protection stages of the relay module is used to specify the influence of the external
not fixed to any specific output relays, but the control inputs BS1...BS5 on the operation of
stages can be linked to the desired output the relay and the active state of the control
signals. In con- trast, the output relays TS1, inputs.
TS2, TS3 and TS4 are the only output
relays capable of circuit breaker control (see The activation of a protection stage, a
"Circuit-breaker control"). The configuration blocking function and an external control
of the output relay matrix switchgroups of input is indi- cated on the display of the relay
the relay modules is described in the manuals module by the red code representing the
of the relay modules. event. The codes are explained in the manuals
of the relay modules. Event information is also
received over the serial bus, when a protection
stage, a blocking func- tion, an external
control input or an output signal is
activated.
Intermodular The signals BS INT1, BS INT2 and BS INT3 for blocking the relay module SPCJ 4D28.
signals are blocking signals for the relay modules The figure below shows how the the external
(modified 97-10) SPCD control inputs, the start, operate and blocking
3D53 and SPCD 2D55. These blocking signals of the relay modules can be configured
signals allow one relay module to prevent the to obtain the desired functions of the relay
operation of another relay module fitted in modules. The switches to be used for selecting
another relay module location. An the active state of the signals and for
intermodular blocking sig- nal is activated configuring the latching feature of the output
when the corresponding block- ing signal of relays and the operation of the circuit-breaker
one relay module is activated. The blocking failure protection have been omitted.
signals BS INT1...3 are not capable of
controlling output relays, nor can they be
used
I>

SGR11
t>

SGR10
4

2
t >>
0
II 0>>

SGR9
3

2
>

SGR8
t 0>

2
0

SGR7
1

SGB3
6 SGF8
1 1

t>>>

SGR6
SGB2
I>>>

65

11

22

SGB1 SGR5
5
I>>
1

SGR4
4

2
t>>
I>
SPAD 346 C
SGR3

2
SGR2

12

12

11

22
t>
SGR1 X1/11

SGF6
SGF7

SS1
TS1
X1/12
X1/13
SPCJ 4D28 (U3)

AR2

AR1
X1/14

+
TS4
AR1
X2/7

8
X2/8
SGR11

AR2 7

+
SGR10

5 6 7

1 1 1

2 2 2

SS4
SGR9

8
SGR8

7
SGR7

2 3 4

2
X1/15

side) blocking (LV side)


SGR6
X1/16

2
X1/17

SGB2 1
X1/18

+
SGR5

TS3
t02 >
I 02 >

2
SGR4

(HV harm.

2
SGR3
X2/9

2
3

3
2nd harm. blocking 2nd
X2/10

+
SS3
t01>
SGR2

2
I01>
SGR1

2
X2/3

SS1
SGF10 SGF9

TS3

TS4
SGF6

SGF7
SGF8
X2/4
SPCD 2D55 (U2)

+
TS4

TS2
SS4
TS3
AR1

AR3

SS3
TS2
SS2
TS1
SS1
X2/11

6 7 8BS INT1 AR3


X2/12

BS INT3
7 8

SS1
AR1
X2/13

TS3

TS4
6

+
4 5

SS2
6 7 8 SGR8

6 7 8

1 1 1

2 2 2
SGR7
3

SGR6
X2/5
1 2

SGR5
4 5

4 5

4 5

1 1

2 2
SGR4
X2/6
SGB2

+
TS1
SGR3
2nd or 5th harmonic blocking

2
SGR2 X2/14
3 I> 3 I>>

2 X2/15

+
SGR1

SS1
1

SGF10 1

2
IL1 , I L2, IL3
I'L1, I'L2 , I'L3

SGF6

SGF8

Fig. 3. The energizing inputs, external control inputs, intermodular signals, output signals and
output relays of the differential relay SPAD 346 C.
Power supply The power supply module forms the voltages The power supply module type SPGU 240
module required by the relay modules. The power A1 can be used for both ac voltage and dc
sup- ply module, which is a separate unit, is voltage, whereas type SPGU 48 B2 is
located behind the system front panel. The designed for dc voltage only. The voltage
module can be withdrawn after the system range of the power supply module of the
panel has been removed. relay is marked on the system panel of the
relay.
The power supply module is available in two
versions, SPGU 240A1 and SPGU 48B2 , The power supply module is a transformer con-
which have different input voltages: nected, i.e. galvanically isolated primary and
secondary side, flyback-type dc/dc
SPGU 240A1 converter. The primary side of the power
- rated voltage supply module is protected with a fuse, F1,
Un = 110/120/230/240 V ac located on the PVC board of the module.
Un = 110/125/220 V dc The fuse size of SPGU
- operation 240A1 is 1 A (slow) and that of SPGU 48B2
range is
U = 80...265 V ac/dc 4 A (slow).
SPGU 48B2
- rated voltage
Un = 24/48/60 V dc
- operation
range
U = 18...80 V dc

Uaux
80...265
18...80
+8V U ilized logics
n voltage
+12V s
t Operation amplifier
a voltage
-12V
b
Output relay coil
+24V
voltage

Fig. 4. Voltage levels of the power supply module


A green LED indicator Uaux is lit when the more than 25% a self-supervision alarm will
power supply module is operating. The be obtained. An alarm signal will also be
supervi- sion of the voltages supplying the received if the power supply module has been
electronics is integrated into the relay removed or the power supply to the module is
modules. Should a secondary voltage deviate interrupted.
from its rated value by
Operation
indicators

I n = 1A 5A ( I 2 ) 2
f n = 50Hz I n = 1A 5A ( I 01 )
5

n STEP
80...265 V –~ 1 / n RESET

18...80 V –
2tp In 02 / n
t >> [ s ]

2f / 1f 02

In
1 1/ n

2 3 I >> Trip 2 I 01 > Trip 2 I > Trip

0029A
0021A

0023A
0199A

RS 621 Ser.No.

Fig. 5. Front panel of stabilized differential relay SPAD 346 C


1. The green LED Uaux on the system panel is sented on the display is recognized by yellow
lit when the power supply module is LED indicators on the front panel and red
operating. codes on the display. The measured values
and setting values are explained in the
2. The displays of the relay modules indicate manu- als for the relay modules.
measured data, setting values and
recorded information. The operation 4. A permanent fault detected by the self-super-
indicators of the relay modules consist of a vision system is indicated by the IRF
red digit or code on the display and LED indica- tors on the separate relay modules.
indicator "TRIP". The operation indicators, The fault code appearing on the display of
their internal priorities and means of the module when a fault occurs should be
resetting are explained in the manuals for stated when service is ordered. The fault
the relay modules. codes are ex- plained in the manuals of the
relay modules.
3. A measured value or setting value being pre-
Technical data Measuring inputs
(modified 2002-04) Rated current In
Terminal numbers

Thermal current withstand


- continuously
- for 10 s
- for 1 s
Dynamic current withstand
- half-vawe value
Input impedance
Rated frequency fn

Output relays
Heavy-duty output relays
Terminal numbers X1/11-12-13-14, 15-16-17-18
X2/3-4, 5-6
Rated voltage 250 V ac/dc
Continuous current carrying capacity 5A
Make and carry for 0.5 s 30 A
Make and carry for 3 s 15 A
Breaking capacity for dc when the control circuit
time constant L/R 40 ms at the control levels
48/110/220 V dc 5 A/3 A/1 A

Signal relays
Terminal numbers X2/7-8, 9-10, 11-12-13, 14-15
16-17-18
Rated voltage 250 V ac/dc
Continuous current carrying capacity 5A
Make and carry for 0.5 s 10 A
Make and carry for 3 s 8A
Breaking capacity for dc when the control circuit
time constant L/R 40 ms at the control levels
48/110/220 V dc 1 A/0.25 A/0.15 A

Control inputs
Terminal numbers X1/1-2, 3-4, 5-6, 7-8, 9-10
Control voltage
- rated voltages Un = 24/48/60/110/220 V dc
Un = 110/220 V ac
- operation range 18...265 V dc and 80...265 V ac
Current drain 2...20 mA
Selectable mode of activation in the relay modules
- input activated when Energized
- input activated when Non-energized
Time between activation of control input and
relay operation (control input active when energized,
to be programmed in the relay module) <30 ms
Time between activation of control input and
relay operation (control input active when
non-
energized, to be programmed in the relay module) <50 ms
Power supply module
Terminal numbers X2/1-2
Type SPGU 240A1
- rated voltages Un = 110/120/230/240 V ac
Un = 110/125/220 V dc
- operation range 80...265 V ac/dc
Type SPGU 48B2
- rated voltage Un = 24/48/60 V dc
- operation range 18...80 V dc
Current consumption under quiescent/operation
conditions about 10 W/15 W

Stabilized three-phase differential relay module SPCD 3D53


- see "Technical data" of the manual 1MRS 750097-MUM EN.

Earth-fault relay module SPCD 2D55


- see "Technical data" of the manual 1MRS 750098-MUM EN.

Combined overcurrent and earth-fault relay module SPCJ 4D28


- see "Technical data" of the manual 1MRS 750093-MUM EN.

Data communications
Transmission mode Fibre-optic serial bus
Coding ASCII
Data transfer rate 4800 or 9600 Bd
Optical bus connection module
- for plastic core cables SPA-ZC 21 BB
- for glass fibre cables SPA-ZC 21 MM
Optical bus connection module power from an
internal power source
- for plastic core cables SPA-ZC 17 BB
- for glass fibre cables SPA-ZC 17 MM

Software support for SPAD 346 C


Substation monitoring program SMS 010
Disturbance recorder PC program DR-COM

Insulation Tests *)
Dielectric test IEC 60255-5 2 kV, 50 Hz, 1 min
Impulse voltage test IEC 60255-5 5 kV, 1.2/50 s, 0.5
J Insulation resistance measurement IEC 60255-5 >100 M , 500 Vdc
Electromagnetic Compatibility Tests *)
High-frequency (1 MHz) burst disturbance test
IEC 60255-22-1
- common mode 2.5 kV
- differential mode 1.0 kV
Electrostatic discharge test IEC 60255-22-2 and
IEC 61000-4-2
- contact discharge 6 kV
- air discharge 8 kV
Fast transient disturbance test IEC 60255-22-4
and IEC 61000-4-4
- power supply 4 kV
- I/O ports
2 kV

Environmental Conditions
Specified service temperature range -10...+55 C
Transport and storage temperature range -40...+70 C
Temperature influence on the operating values
of the relay over the specified service
temperature range <0.2%/ C
Damp heat test, cyclic IEC 60068-2-30 +25...55 C, r.h. > 93%, 6 cycles
Degree of protection by enclosure
of the relay case when panel mounted IP
54
Weight of fully equipped relay 6 kg

*) The tests do not apply to the serial port, which is used exclusively for the bus connection
module.
Recommenda- The more important the object to be the current transformers are partially
tions for protected, the more attention should be saturated. The purpose of the following
current paid to the current transformers. current trans- former recommendations is
transformers Normally, it is not possible to to secure the stabil- ity of the relay at
dimension the current transformers so that high through-currents, and quick and
they repeat currents with high DC sensitive operation of the relay at faults
components with- out saturating, when occurring in the protected area, where the
the residual flux of the current fault currents may be high.
transformer is high. The differential
relay SPAD 346 C operates reliably, even
though

Differenti The accuracy class recommended for Sin +


Fa = Fn x
al current transformers (IEC 60044-1) to be Sn
protection used with the differential relay SPAD 346 Sin + Sa
C is 5P, in which the limit of the current
error at rated primary current is 1% and
the limit of the phase displace- ment is 60 In the example the rated burden Sn of the
minutes. The limit of the composite error LV side CTs 5P20 is 10 VA, the secondary
at rated accuracy limit primary current is rated current 5 A, the internal resistance Rin
5 = 0.07 and the accuracy limit factor Fn
% (ALF) corre- sponding to the rated burden
. is 20 (5P20). Thus the internal burden of
the current transformer is Sin = (5 A)2 x
The approximate value of the accuracy 0.07 = 1.75 VA. The input impedance
limit factor Fa corresponding to the actual of the relay at a rated current of 5 A is <20
CT burden can be calculated on the m . If the measurement conductors have a
basis of the rated accuracy limit factor resistance of 0.113 the actual burden of
Fn (ALF) at the rated burden, the rated the current transformer is Sa =(5 A)2 x
burden Sn, the internal bur- den Sin and (0.113 +
the actual burden Sa of the current 0.020) = 3.33 VA. Thus the accuracy
transformer as follows: limit
factor Fa corresponding to the actual
burden will be about 46.
The CT ule it is enough that the current
burden may transformers are capable of repeating, In generator protection it is important that
grow during the first cycle, the current the repeatability of the phase current
considerabl required for instantaneous tripping. transformers on the neutral side and on
y at rated the network side of the generator
current of Thus the current transformers should be correspond, that means that the burdens
5 A. At 1 able to reproduce the asymmetric fault of the current transformers on both sides
A rated current without saturating within the are as equal as possible. Should, in connec-
current the next 10 ms after the occur- rence of the tion situations following synchronization,
actual fault, to secure that the operate times high inrush or start currents containing
burden of of the relay comply with the times stated high DC components pass through the
the current in the manuals of the modules protected genera- tor, special attention
transformer should be paid to the performance and
decreases, The accuracy limit factors corresponding the burdens of the current transformers
at the same to the actual burden of phase current and to the settings of the relay.
time as transformer to be used in differential
repeatability protection shall fulfil the following
improves. requirements:

At faults Fa >
occurring 40
in the
and
protected Fa > 4 x
area on the Imax1
HV side of
the
The setting Id/In>> of the instantaneous
transforme
differ- ential current stage is used as the
r, the fault
factor Imax1.
currents
may be very
The use of auto-reclosing to clarify a
high
fault occur- ring outside the protected
compared
area may produce a substantial residual
to the rated
flux in the CT core. To guarantee that
currents of
the differential protection re- mains
the current
stable in an auto-reclose situation also at
transformer
large currents when the residual flux is
s. Thanks
great, the accuracy limit factors
to the in-
corresponding to the ac- tual burden of
stantaneous
the HV and LV side CTs should fulfill
stage of the
the requirements mentioned above and
differential
be of the same order, if possible.
relay mod-
The technical features of class X (BS where
3938) current transformers are n is the transformation ratio of the
determined by the knee- point voltage current transformer
and the resistance of the secondary Rin is the secondary resistance of the
winding. The knee-point voltage is the current transformer
value of the CT secondary voltage at RL is the total resistance of the longest
which a further loop measured (outgoing and return
10% increase in the secondary voltage lead)
would cause a 50% increase in the Imax2 is the setting of the instantaneous
excitation current. The knee-point differ- ential current stage Id/In>>
voltages Uk of current trans- formers multiplied by the rated current of
used in differential protection should the protected object.
fulfil the following requirement:
4 x Imax2 x (Rin + RL)
Uk>
n

Earth- The recommendations for current of the neutral current transformer should
fault transformers used in earth-fault be as close as possible to the accuracy
protectio protection based on the stabilized limit factor corresponding to the actual
n differential current principle are the same burden of the phase current transformers.
as for differential protection. The accuracy
limit factor corresponding to the actual
burden
Earth-fault The sensitivity and reliability of The sensitivity requirements for the
protection based on differential current protection stabilized protection are jeopardized if the
the high- through a resistor are strongly related to magnetizing current of the current
impedance type the current transformers used. The transformers is allowed to rise too much
protection number of turns of the current trans- compared to the knee-point voltage. The
formers that are part of the same Iprim value of the primary current at
differential current circuit should be the which the relay operates at certain settings
same. The current transformers should can be calculated as follows:
have the same transforma- tion ratio.
Iprim = n x (Ir + Iu + m
To be able to feed the differential current x Im )
circuit with the current required for
starting, when a fault occurs in the w
protected area, the current transformers he
need a knee-point voltage that is about re
twice the stabilizing voltage required from n = the transformation ratio of the
the relay at faults outside the protected current transformer
area. The stabilizing voltage Us of the relay Ir = the current value representing the
and the knee- point voltage Uk of the relay setting
current transformer is calculated as Iu = is the current flowing through the
follows: protec- tion varistor
m = the number of current transformers
Ifmax x (Rin + RL) in- cluded in the protection
Im = the magnetizing current of one
current
Us = transformer
n A protection varistor connected in parallel
Uk = 2 with the differential current prevents the
voltage gen- erated in the differential
x Us
circuit at faults occur- ring in the protected
area from rising too high. The resistance
where Ifmax is the maximum through-
of the varistor depends on the voltage
going fault current at which the
applied to it: the higher the voltage the
protection is not allowed to operate. The
smaller the resistance.
factor two is used when no operation
delay whatsoever is permitted for the
protection. To prevent the knee-point
volt- age of the current transformers to
grow too high, it is recommended to use
current transformers whose secondary
winding resistance is of the same level
as the resistance of the measurement
circuit.

Overcurre The recommendations for current those used in differential current protection,
nt transformers used in overcurrent i.e. there are no special requirements.
protection protection are the same as
Circuit- The opening of the circuit-breaker can be and X1/17 are connected to the open coil
breaker im- plemented as double-pole control or of the circuit breaker. If the heavy-duty
control single-pole control. The stabilized output relay TS4 is used for
differential relay SPAD
346 C is provided with two heavy-duty
one-pole relays (TS1 and TS2) and two
heavy-duty dou- ble-pole relays (TS3 and
TS4).

When double-pole circuit-breaker


control is used, the control voltage is
linked to both sides of the tripping coils
of the transformer. If the heavy-duty
output relay TS3 is used for double- pole
control, for example, terminal X1/15 is
connected to negative control voltage and
ter- minal X1/18 is connected to positive
control voltage. The terminals X1/16
two-pole positive con- trol voltage. Terminals terminal X1/18 to the positive control
control, the X1/12 and X1/13 are connected to the voltage. Should output relay TS4 be used
terminal X1/11 open coil of the circuit breaker. for single-pole control, terminals X1/12 and
can be X1/13 should be connected together.
connected to If the output relay TS3 is used for Terminal X1/11 is connected to the open
negative control single-pole control, the terminals X1/16 coil and terminal X1/
voltage and ter- and X1/17 should be connected together, 14 to the positive control
minal X1/14 that is, the relays should be connected voltage.
can be in series. Terminal X1/15 is connected
connected to to the open coil of the circuit breaker and

OPEN

SS1 SS2 SS3 SS4 TS1 TS3 TS4


-
TS2
+

X2 14 15
X2 11 12 13 X2 9 10

+ +

Double-pole circuit-breaker control

0
-

OPEN

SS1 SS2 SS3 SS4 TS1 TS2 TS4


TS3 +

X2 14 15
X2 11 12 13 X2 9 10

+ +

Single-pole circuit-breaker control

Fig. 6. Double-pole and single-pole circuit-breaker control


Applicatio The following application examples show All the three relay modules have been
n the differential relay SPAD 346 C used used in solutions presented.
examples for the protection of power transformers.

Example Differential relay SPAD 346 C used for the protection of a YNyn0-connected power
1. transformer.

P2 P1
L P1 P2
1

L
2

L S1
3 S2
S2 S1
S1 P1 P1 S1
Rx Tx

SPA-ZC_
2
S
2
P
2

P
2

X0/2X0/1
Uaux
- (~)

X0/25
X0/26

5 A NX0/37

X2/1
X0/38
U5

5AN
+ -
SERI
AL
I/O POR
T
5A N

5AN
5A
X2/16 IRF

X2/17
U6
IRF
X2/18

Y/ U1 SS X2/14
SPAD 346 C 1
Y/ IR
F
S
S X2/15
1 +
S
S2 X2/11
S
S3
X2/12

B 3I> SS X2/13
S1 SS
4 +
2
U4 B 3I>> TS
S2 1 X2/9
X1/1
B TS
S3 2
TS
B X2/10
3
S4 TS
BS 4 SS
X1/2 BS I/ 3 +
1 5
O
X1/3 X2/7
U2
SS
BS X2/8
X1/4 4
2 IR +
F
S
S
1
S
S2
S
S3 X2/5
X1/5 BS BS I 01 > SS TRIP X2/6
3 1 4
I 02 > TS +
BS TS 1
X1/6 2 1 X2/3
TS
BS
2
3 TS
X1/7 BS 3
4 TS
4

X1/8 BS BS U3 I/ TS TRIP
4 5 X2/
O 2 4
IR +
3I F
X1/9
B >I SS X1/15
S5 1 TRIP
BS SS
X1/10 1 I> 2 TS X1/16
BS SS
3 3
2 SS X1/17
BS 4
TS TRIP
3
1 X1/18
TS
2 TS
TS 4 +
3
TS X1/11
4
I/
O X1/12

X1/13

X1/14

+
Fig. 7. Application of example 1.
The stabilized stage and the poles of the LV side and serves as back-
instantaneous stage of the three-phase up at short circuits in the LV side busbar
differential relay module SPCD 3D53 system. A facility of automatic doubling
are used to protect the power of the setting value of the I>> stage at
transformer against winding short magnetizing inrush currents is available.
circuit and interturn faults. In an inrush The overcurrent stage I> of the module
situation the trip- ping of the stabilized can be employed as inverse time earth-
stage is inhibited by a blocking fault back-up protection for the LV side
function based on the second har- feeders.
monic of the differential current. In cases
where the transformer is not allowed Blocking based on the second harmonic of
to be discon- nected from the network the differential current of the relay module
in a situation of over- excitation, a SPCD
blocking arrangement based on the fifth 3D53 can be used for blocking the
harmonic of the differential current is overcurrent stages I> and I>> of the
used. relay module SPCJ
4D28 at transformer magnetizing inrush
The stabilized differential current cur- rents. The blocking is programmed in
principle or the high-impedance the relay module SPCD 3D53 for the
principle of the relay mod- ule SPCD desired output relay, from which it is
2D55 is employed for protecting the HV linked to the external control input BS1,
and LV side winding against earth BS2 or BS3. The concerned control input
fault. When the stabilized differential is programmed to block the opera- tion of
current princi- ple is used, the inverse the overcurrent stage I> and/or I>> of the
time stage I0> of the relay module SPCJ relay module SPCJ 4D28. The operation of
4D28 can be used as back-up the overcurrent stage I>>> will not be
protection on the LV side. The blocking blocked.
based on the ratio between the second
harmonic and the fundamental In combination with protection of YNyn-
frequency component of the neutral con- nected power transformers the phase
current is permitted both on the HV disconti- nuity protection I> of the relay
side and on the LV side. If the high- module SPCJ
impedance principle is used on the LV 4D28 can be used for network
side, no back-up protection can be supervision, at least as alarming
arranged for the earth-fault protection. protection. Then it should be noticed that
the phase discontinuity protection can
The relay module SPCJ 4D28 provides provide an alarm signal at earth fault as well.
three- phase, three-stage overcurrent
protection and earth-fault back-up The operate signals of the integrated
protection. The module measures the circuit- breaker failure protection of the
phase currents on the HV side and relay modules are linked to a heavy-duty
neutral current on the LV side. The output relay that is capable of operating
definite time overcurrent stage I>>> is the circuit breaker preced- ing the HV
set to operate on short circuits occurring side circuit breaker in the supply
on the HV side of the transformer. direction.
The overcurrent stage I>> is
configured to operate on short circuits
in the

Example Differential relay SPAD 346 C used for the protection of a YNd11-connected power
2. transformer.
The principle of the winding and the 4D28 serves as
interturn fault protection and the back-up for the
overcurrent protection is the same as in earth-fault
example 1. The high-imped- ance protection. Then
protection principle of the module the neutral
SPCD current from the
2D55 is used for protecting the HV side second neutral
windings against earth fault. connection
transformer on the
The stage I0>, operating with inverse time HV side is con-
char- acteristic, of the relay module SPCJ nected to the
terminals XO/37-38 or X0/37-39, as The neutral current principle is
illustrated in the figure. When the HV programmed to be used on the LV side
side star point is directly earthed the in the relay module SPCD 2D55. Then
definite time stage I0>> can also be used the blocking function based on the second
as earth-fault back- up protection. harmonic of the neutral current can be
used. The blocking function can be used
for blocking the stages I0> and I0>> of the
relay module SPCJ 4D28 in transformer
inrush situ- ations. In the relay module
SPCD 2D55 the blocking is programmed
to the desired output relay, from which it
is externally linked to the control input
BS1, BS2 or BS3. The concerned control
input is programmed to block the opera-
tion of the desired earth-fault stage of the
mod- ule SPCJ 4D28.
P2 P1
P2 P1 YNd11
L1

L2

L3 S1
S1 S2
S2

S1 P1 Rx Tx

SPA-ZC_
S2
P2
S1 P1
S2
P2
Uaux

- (~)
X0/25

X0/37
X0/1

X2/1
5 A NX0/26

5 A NX0/38
X0/2
5A N

U5
5AN

+ -
SERIAL
PORT
I/O
X2/16 IRF
X2/17
X2/18
+
IRF
U6

X2/14
X2/15
Y/ U1 IRF SS1 +
SPAD 346 C SS1
SS2 X2/11
Y/ SS3 X2/12

BS1 3I> SS4 SS2 X2/13


BS2 +
U4 TS1
BS3 3I>> TS2

TS4 X2/10
X1/2 SS3

X1/3
BS2 SS1 SS4
X2/8
X1/4 SS2
BS1 I 01 > +
SS3
X1/5 BS2 I 02 > SS4
BS3 X2/5
BS3 TS1 TS1 X2/6
X1/6 TS2
BS4 +
TS3
X1/7 BS5 TS4 TRIP
BS4 X2/3
X1/8 I/O TS2 X2/4
U3
IRF +
X1/9 SS1
BS5 SS2
X1/10 3I> X1/15 TRIP
BS1 SS3 X1/16
I SS4
BS2 X1/17
I> TS1
BS3 TS3 X1/18
TS2
TS3 +
TS4
I/O X1/11 TRIP
X1/12
X1/13
TS4 X1/14
+

Fig. 8. Application of example 2


Example 3. Differential relay SPAD 346 C used for the protection of a YNd11-connected power
transformer and a zigzag-connected earthing transformer.
The winding and interturn fault protection rent principle can be used for the earth-fault
and the overcurrent protection are arranged protection. The figure below shows the
in the same manner as in example 1. The high- connec- tion when the high-impedance
imped- ance principle or the stabilized principle is used.
differential cur-

P1 P2
P2 P1 YNd1
L1 1

L2

L3 S1
S1 S2
S2

Rx Tx

S1 P1 S1 P1

SPA-ZC_
S2
P2 S2
P2

+ (~) U aux
- (~)

X0/13
X0/25
X0/1

X2/1
5AN

5AN

5 AN

U5
5 AN

N
5A

+ -
SERIA
L
I/O PORT
X2/16 IRF
X2/17
X2/18
+
IRF
U6

X2/14
Y/ IRF SS1 X2/15
U1
SPAD 346 C SS1 +
SS2 X2/11
Y/ SS3 X2/12
BS1 3 I> SS4 X2/13
SS2
BS2 +
U4 TS1
BS3 3 I>> TS2
X2/9
X1/1 BS4 TS3 X2/10
TS4 SS3
X1/2 BS1 BS5 +
I/O
X1/3 U2 IRF SS4 X2/7
SS1 X2/8
X1/4 BS2
SS2 +
SS3

X1/5 BS1 I 01 > TS1 TRIP


SS4 X2/5
BS2 I 02 > TS1 X2/6
X1/6

X1/7 BS4 TS3 TS2


BS4 TRIP
BS5 I/O X2/4
X1/8

X1/9 BS5 SS1 X1/15


X1/10 SS2 TRIP
3I> X1/16
SS3 TS3
BS1 I X1/17
SS4 X1/18
BS2
I> TS1 +
BS3 TS2
TS3 X1/11
TS4 TRIP
TS4 X1/12
I/O
X1/13
X1/14
+

Fig. 9. Application of example 3.


Setting A table in the manual of the differential relay to use the table you must know the vector
instructions module presents the vector group matching group of the power trans- former to be
settings corresponding to the most general protected and the connection type of the
Three-phase power transformer vector groups. The current transformers, which also has to be
differential vector group matching shown in the table is considered in the protection of generators.
relay module programmed into the relay module via the
SPCD 3D53 switches of switch- group SGF1. To be able
In the matched in the differential relay module on On the LV side the zero-sequence component
application the LV side (SGF1/3=1, SGF 1/4=1 and has to be set to be calculated and eliminated
example 1 (Fig. SGF1/ from the phase currents separately
7) the phase (SGF1/1=1). The checksum of switchgroup
current SGF1 will be 65.
transformers
are connected If the rated primary current of the HV and
according to LV side current transformers is not equal to
connection the rated current of the power transformer on
type I, in the concerned side, the settings I1/In and I2/In
which case the are used for correcting the transformation
phase ratios. In the example the rated power of the
difference of power trans- former is 40 MVA and the rated
HV and LV voltage is 110 kV/
side phase 10.5 kV. The transformation ratio of the HV
currents side current transformers is 300 A/1 A and
applied to the that of the LV side current transformers is 2500
relay is 180 . A/5A.
The phase
difference is The rated HV side current I1n of the power
transformer is
5...8=0). The star points of the transformer I1n = Sn – = 40 MVA – = 210 A
HV side and LV side windings are earthed, 3 U1n 3 x 110 kV
so the zero-sequence component occurring
in earth
faults outside the protection area is set to be Correspondingly, the rated LV side current I2n
eliminated from the HV and LV side phase is
currents (SGF1/1=1, SGF 1/2=1). The
check-
sum of swichgroup SGF1 will be 15. I2n = Sn = 40 MVA = 2199 A
– –
3 U2n 3 x 10.5 kV
In the application example 2 (Fig. 8) the con-
nection of the current transformers is in The settings for the transformation ratio
accord- correc-
ance with connection type II, so the tion are calculated on the basis of these rated
connection currents and the rated primary currents of
of the current transformers does not cause the
phase HV and LV side current transformers:
difference between the currents linked to the
relay. On the HV side the zero-sequence com- I1/In = 210 A / 300 A = 0.70
ponent of the phase currents is eliminated in and
the matching of the phase difference in the I2/In = 2199 A / 2500 A =
numeri- 0.88
cally implemented delta connection (SGF1/6=1,
SGF1/7=0 and SGF1/8=1). The checksum of The basic setting P/In is used to set the
switchgroup SGF1 will be 160. maxi- mum sensitivity of the differential
relay. This setting takes into account the
Should the required vector group matching not differential cur- rents caused by a no-load
appear from the table, the vector group situation and a small overexcitation of the
match- ing is set by means of the additional transformer. The basic setting can also be
tables. All the vector groups of two-winding used to influence the level of the whole
transformers can be matched in the relay operation characteristic. The basic setting
module irrespective of the earthing method of P/In for transformer protection is typi- cally
the transformer and the network. 20...40%. In generator protection the ba- sic
setting is typically 5...20%.
The setting of the vector group matching
shown in the application example 3 (Fig. 9) When setting the starting ratio S the accuracy
takes into account not only the vector group class of the current transformers to be used,
of the main transformer but also the earthing the accuracy limit factors corresponding to the
transformer in the protected area on the LV ac- tual burden of the current transformers,
side. The connec- tion of the phase current the regulation range of the tap changer of the
transformers is in accordance with power transformer and the location of the
connection type I. In the pro- tected area second turn- ing point I2tp/In of the operation
there is an earthed neutral point both on the characteristic
HV side and on the LV side and thus the zero- have to be considered. The bigger the errors of
sequence component of the phase currents has the current transformers used, the greater the
to be considered in the vector group match- value of S. Should, for instance, the accuracy
ing. On the HV side the zero-sequence class of the HV and LV side current
compo- nent is eliminated in the phase transform- ers be 5P, the composite error at
difference match- ing (SGF1/6=0, SGF1/7=1 rated accuracy
and SGF1/8=0).
limit primary current would be maximum 5% on both sides.
The transformation ratios of the current rent the DC component is great. The
trans- formers on the HV and LV side of the amplitude of the fundamental frequency
power transformer are normally matched to component is typically only half of the peak
corre- spond to the middle position of the tap value of the inrush current. Thus the
changer. The maximum error will be caused instantaneous tripping value Id/In>> of the
by the tap changer position, when the tap relay can be set below the peak value of the
changer is in the extreme position. One asymmetric inrush. In power trans- former
setting factor for the starting ratio is the protection the setting value of the in-
regulation range of the tap changer, which stantaneous differential current stage is
may be for example 9 x 1.67% typically
= 15%. Another factor to be considered in 6...10. In generator protection the
the starting ratio setting is the error caused appropriate setting value for instantaneous
by the matching transformers of the relay tripping is 5...8.
and the inaccuracy of the A/D converters.
This error is about 2% at a maximum. Blocking of the stabilized stage based on the
ratio between the second harmonic and the
The starting ratio is set by means of above fundamental frequency component of the dif-
setting factors. In the case of the example the ferential current is enabled when the switch
appropriate setting of the starting ratio is SGF2/1 = 1. In power transformer protection
25... the blocking should always be enabled. The
35%. Should the accuracy limit factors corre- appropriate setting of the blocking ratio Id2f/
sponding to the actual burden of the current Id1f> in power transformer protection is usually
transformers to be used on the HV side and 15%. When SGF2/2 = 1, the operate time of
LV side clearly deviate from each other, the the relay is not getting longer in a situation
starting ratio S must be given a greater value when the transformer is connected against a
than in the case where the concerned accuracy fault in the protected area.
limit factors are nearly the same.
Blocking based on the second harmonic of the
The setting I2tp/In of the second turning point differential current should be allowed in the
of the operation characteristic influences on differential relay of a generator in such situa-
the tripping sensitivity at values above the tions where a relatively large block
rated current. If the short circuit power is transformer or power transformer is energized
mainly fed from one direction at a fault through the generator after synchronization.
occurring in the protected area, the The inrush current passing through the
appropriate setting of I2tp/In is 2.0...2.5. generator may satu- rate the current
Should the short-circuit power be fed both transformers, thus causing dif- ferential
from the HV side and the LV side when a current that typically contains a high amount
fault accurs in the protected area, the second of second harmonic. In this situation the
turning point can be given a smaller value main and second settings of the relay can be
with- out the sensitivity being reduced. In the used. In a connection situation the actual
protec- tion of the block transformer of the set- tings of the differential relay module
generator the short circuit power is normally are re- placed by the second settings, in
fed from two directions and then, when a fault which the blocking is enabled. After
occurs in the protection area, the phase damping of the inrush current the main
difference of the currents increases and the settings, which do not allow the blocking
stabilizing current decreases. In the case of function, are used.
the block transformer the recommended
setting of I2tp/In is 1.5...2.0. When setting the blocking of the fifth
harmonic it has to be specified whether
The instantaneous tripping limit Id/In>> is set blocking is to be allowed at all (SGF2/3=0
so that the differential relay module does not and SGF2/4=0), whether only the
trip when the transformer is energized. The blocking ratio Id5f/Id1f> (SGF2/3=1 and
instantaneous stage trips, when the SGF2/4=0) is to be set for the differential
fundamen- tal frequency component of the relay module or whether both the blocking
differential cur- rent exceeds the set tripping ratio Id5f/Id1f> and the deblocking ratio
limit Id/In>> or when the instantaneous value Id5f/Id1f>> (SGF2/3=1 and SGF2/4=1) are to
of the differential current exceeds the limit 2.5 be set. In the last case mentioned the opera-
x Id/In>>. When the differential current is tion of the stabilized stage will be blocked, if
below 2.5 x Id/In>> the DC component and the ratio between the fifth harmonic and the
the harmonics of the cur- rent do not affect funda- mental frequency component of the
the operation of the relay. Normally, the differential current is between the setting
peak value of the asymmetric inrush current values Id5f/Id1f> and Id5f/Id1f>>. Should only
of the power transformer is con- siderably the blocking facil- ity be used the blocking
greater than the peak value of the ratio is set high enough to prevent the module
symmetric inrush. At asymmetric inrush cur-
from blocking its opera- tion at high overvoltages, which might
cause damage to the transformer.
Earth-fault The type of earth-fault protection to be used current principle is used the phase difference
relay module on the HV and LV side of the transformer is has to be matched in the relay module
SPCD 2D55 selected with the configuration switches SGF1/ (switches SGF2/1 and SGF2/2).
1...8. The switch positions corresponding to
the different protection principles are When the differential current principle is used
presented in the manual of the module. the transformation ratio corrections I01/In,
I02/In, I1/In and I2/In are set in the same
The basic settings P1/In and P2/In are used way as the transformation ratio correction of
for selecting the start value of the earth-fault the differen- tial relay module. The settings
protec- tion. When the numerical stabilized can also be used for scaling the start values
differential current principle is used the basic when other protec- tion principles are used.
setting influ- ences the level of the whole
operation character- istic. The settings I01/ I1 and I02/ I2 are deter-
mined on the basis of the zero-sequence
When the stabilized differential current princi- imped- ances of the transformer and the
ple is used the setting of the operate time t01> supplying network. If the star point of the
or t02> should be longer than the DC time transformer is directly earthed, the earth-fault
con- stant of the network. The smaller the current and the ratio between the neutral
basic setting, the longer the operate time current and the re- sidual current of the phase
setting should be. If the high-impedance currents are typically greater than in a situation
type protection is used, the operate time of where the concerned star point is earthed
the earth-fault relay module should be set at through a resistor or a choke. When the star
the minimum value, i.e. point of the power trans- former is directly
0.03 s. earthed the recommended setting is 5...15%.
The position of the earth fault in the
When the protection principle is based on the winding and also the number and position of
residual current of the phase currents the the other star points of the network, too,
oper- ate time has to be long enough (up to affect the distribution of the earth-fault
several seconds) to prevent unwanted tripping current.
due to the very asymmetric inrush or start-up
current passing through the protected object. Blocking based on the ratio between the
second harmonic and the fundamental
The connection of the phase CTs and neutral frequency com- ponent of the neutral current
connection CT can cause a 180 phase should be used in combination with the
displace- ment between the residual current of stabilized differential cur- rent principle and
the phase currents and the neutral current at the neutral current principle. The blocking is
external earth faults (see Fig. 6 in the manual enabled by the switch settings SGF2/3=1 and
of the module SPCD 2D55). When the SGF2/4=1. The blocking limits are typically
stabilized differential 20...30%.

Combined over- The settings of the combined overcurrent and In transformer protection the setting of the
current and earth- earth-fault relay module are dependent on the overcurrent stages should be at least 1.5 x In,
fault relay module object to be protected and the use of the to be able to utilize the overload capacity of
SPCJ 4D28 protec- tion stages. The low-set stages (I> and the transformer. The setting value of the
I0>) can have a definite time or an inverse time high-set stage I>> can be set to
operation characteristic. Four international automatically double when the transformer is
standardized time/current characteristics and energized. The opera- tion of the overcurrent
two special- type time/current characteristics stages I> and I>> and the earth-fault stages I0>
are available for the inverse time operation and I0>> can be blocked by the control
(IDMT). The switch SGF1 is used for signals BS1, BS2 and BS3. The switches
selecting the operation mode and the SGB1/1...4, SGB2/1...4 and SGB3/1...4 are
time/current characteristic. The operation of used for configuring the blocking signals.
the high-set stages I>>, I>>> and I0>> is based
on the definite time characteristic only. The When required, the blocking signal BS1 can
operation of the individual stages can be be used to block the operation of the phase
blocked by means of the concerned configu- discon- tinuity protection I> of the relay
ration switches. module SPCJ
4D28. The switch SGB1/6 is used for confi-
guring the blocking. The phase
discontinuity protection supervision can be
set out of opera- tion (SGF3/1).
Commissioning The differential relay module SPCD 3D53 is of the phase currents
capable of reliably measuring the amplitudes and the differential
currents, the phase
angles between the phase currents and the the HV side current transformers are included
phase differences of the HV and LV side in the circuit. By making a three-phase short-
phase currents when the current supplied to circuit on the LV side of the transformer so
the relay is above 1% of the rated current. that the LV side current transformers are
Even at lower currents it is possible to measure included in the circuit a three-phase current of
the phase differences. The amplitudes and some mAs is injected into the relay.
phase angles measured are presented on the
display of the module. The amplitudes are
During the test the HV and LV side current
expressed as rela- tive values (x In and % In).
amplitudes and phase angles measured by the
The values displayed take into account the relay module are shown for the individual
vector group matching and the phases on the display of the differential relay
transformation ratio correction set for the module (or over the serial bus). If the
relay. connection, vector group matching and the
transformation ratio corrections of the relay
After mounting the following low-voltage test are correct the following applies to each
can be made on the relay to verify the phase:
connec- tion, phase sequence, vector group
matching and transformation ratio correction - the phase currents are equally
of the dif- ferential relay: Connect three-phase
high
low-voltage to the primary poles of the current
- the differential currents are 0%
transformers on the HV side of the power
- the phase differences of the HV and LV side
transformer so that
phase currents are 0
- the phase differences between the phase cur-
rents on the same side are 120 .

Testing The relay should be subject to regular tests in As the settings of the relay modules vary in
accordance with national regulations and in- different applications, these instructions
structions. The manufacturer recommends an present the test procedure in general.
interval of five years between the tests. Ordinary current supply units and
instruments for measuring current and time
The test is recommended to be carried out as can be used for the tests.
a secondary test. Then the relay has to be
discon- nected during the test procedure. During the test procedure the relay records
However, it is recommended to check the currents and relay operations. The registers
condition of the signal and trip circuits as should be read before the test is started and
well. during the test.

WARNING! The relay settings may have to be changed


Do not open the secondary circuits of the cur- during testing. A PC program is
rent transformers when disconnecting and recommended to be used to read the relay
test- ing the relay, because the high voltage settings before starting the test, to make sure
produced may be lethal and could damage that the original settings are being restored
insulation. when the test has been completed.

The test should be carried out using the


normal setting values of the relay and the
energizing inputs used. When required, the
test can be extended to include more setting
values.
Testing of differen- The following values and functions of the component and transformation ratio
tial relay module stabi- lized differential current stage 3 I> corrections on the
SPCD 3D53 and the instantaneous differential current
stage 3 I>> should be tested:

- operate value (to be measured on all three


phases)
- operate time (to be measured on one phase
at least)
- operation indication and operation of
output relays

Note!
When testing the three-phase differential
relay module the effect of the vector group
matching, elimination of the zero-sequence
At single-phase currents are IL1m = 0.58 A, IL2m = 0 A and 2/3 of the current applied to the relay at
testing the HV IL3m = 0.58 A. single- phase testing.
side currents
injected are IL1 = 1 If the zero-sequence component has been Example 2. On the HV side of the YNyn-
A, IL2 = 0 A and se- lected to be numerically reduced from the con- nected transformer zero-sequence current
IL3 = 0 A. After phase currents on the HV side or the LV is set to be eliminated as follows (SGF1/2 =
vector group side, i.e. SGF1/1 = 1 or SGF1/2 = 1, the 1):
matching the current meas- ured by the relay module on
amplitudes of the that side will be
operation of the stabilized differential current - - -
- -
stage and the instantaneous differential IL1m = IL1 – 1 x (IL1 + IL2 + IL3)
current stage have to be taken into account. 3

If - - - -
- Yd vector group matching has been selected 1
IL2m = IL2 – x (IL1 + IL2 + IL3)
for the HV or LV side, the current measured 3
by the relay module for the concerned side –
will,
after matching of the vector group, be 3 of
1/ - - - - -
the current applied to the relay at single-phase IL3m = IL3 – 1 x (IL1 + IL2 + IL3)
3
testing.
At single-phase testing the HV side currents
Example 1. Vector group matching of a injected are IL1 = 1 A, IL2 = 0 A and IL3 = 0
YNd11- connected power transformer on the A. After the zero-sequence current elimination
HV side. CT connection according type II. the
-and - currents are IL1m = 0.67 A, IL2m = 0.33 A
- IL1 – IL2 IL3m = 0.33 A.
IL1m = –
3
- - The table below shows how the HV side
settings
- IL2 – IL3 of the relay module affect the values measured
IL2m = –
3 at single-phase testing. I is the one-phase
current
- - (A) applied to the relay, In is the rated current
(1
- IL3 – IL1 A or 5 A) of the matching transformer and I1/In
IL3m = –
3 is the setting of the HV side transformation
ratio
correction (the corresponding HV side setting
is
I2/In).

HV side vector group


matching

Instantaneous differ- The testing of the module should be started The operation of the instantaneous differential
ential current stage with the differential current stage 3 I>>. To current stage is not stabilized. The instantane-
3 I>> prevent operation of the stabilized differential
stage dur- ing the testing of the differential
current stage its operate signal should be
disconnected at the output relays, that is, the
switches of switch- group SGR1 should be
set in the position 0. Alternatively, the
operation of the stage can be inhibited by
applying an external blocking sig- nal to the
stage.
ous stage can be it should be noted that the setting value 30% of the differential current ( the difference
tested by applying required for the operation of the between the HV and LV side currents).
one or two instantaneous stage will be reduced by 50%,
currents to the if the stabilizing current (average of the HV When the instantaneous differential current
relay. When two and LV side cur- rents) calculated by the stage has been tested the original settings
currents are used, relay module falls below should be restored.

Stabilized differential The stabilized differential current stage can be the stabilizing current is the average of the
current stage 3 I> tested by applying one or two currents to the currents applied. Then increase the differential
relay. If one current is used the phase current current by raising one current and decreasing
inputs of the HV and LV side are tested one the other current so that the stabilizing
by one until all of six inputs have been tested. current remains constant. Increase the
differential cur- rent until the module operates
Two currents have to be used to verify the when the differ- ential current exceeds the
operation characteristic of the stabilized value of the operation characteristic. Repeat
differ- ential current stage of the module. At the test on all three phases. The test can also be
least one stabilizing current value has to be made by raising one current and keeping the
selected from each of the three parts of the other at a constant value.
operation charac- teristic. Apply the current
to the HV side and the LV side on one The table below shows the differential current
phase so that the currents calculated by the required for operation in the different parts
relay module initially are the same. First the of the operation characteristic.
differential current is zero, and
Part of operating
characteristic

Note! The effect of the transformation ratio mental frequency component of the differential
correction, vector group matching and zero- current. The weighting factors, 4, 1 and 1, to
sequence component elimination on the cur- be used between the different phases have to
rents to be applied to the relay should be be taken into account when testing the
consid- ered when using the table. second harmonic blocking. During the
testing of the blocking based on the second
Special equipment is required for testing the harmonic of the differential current the
blockings based on the ratio between the blocking inhibit algo- rithm based on the
second harmonic and the fundamental waveform of the differential current should be
frequency com- ponent or the fifth harmonic set out of use, that is, the switch SGF2/2 is
and the funda- set to 0.
Operate times Apply current to the relay by closing the differential current stage plus the selected
current switch so that the differential current is oper- ate time of the circuit breaker failure
about 2 times the differential current required protection can be separately tested. The
for opera- tion. Then measure the operate operate time of the instantaneous differential
time, i.e. the time from closing the switch current stage can be tested at various
until the relay operates. The operate times differential current levels, say,
of the instantane- ous differential current 1.5 x Id/In>> and 4 x
stage and the stabilized Id/In>>.

Operation indicators, Check that the operation indicators and the


alarm and trip output relays (alarm and heavy-duty) operate
signals properly during the testing of the relay
module.

Testing of the earth- Test the following values and functions of the Note!
fault relay module protection stages I01 and I02: The earth-fault protection for the HV side and
SPCD 2D55 the LV side is identical and, therefore, tested in
- start value the same way. The test procedure depends on
- operate time the protection principle employed. The
- operation indication and operation of switches SGF1/1...8 are used to select the
output relays protection principle for the HV and LV side.
The effect of the transformation ratio
correction settings on the currents calculated
by the relay module have to be considered
when the module is tested.

Testing of the The stabilized differential current principle is amplitudes of the three phase currents) will be
stabilized tested by applying one or two currents to the 1/3 of the phase current applied to the relay.
differential relay. When one current is used, inject the Repeat the test on each phase current input.
current principle current into the neutral current input I01 or
I02. The neutral current does not affect the The phase difference of the currents applied to
stabiliz- ing current. Increase the current until the relay should be considered in the test (see
the mod- ule starts. The start value of the the functions of switches SGF2/1 and SGF2/2
module is the same as the basic setting of the in the manual for the earth-fault relay module
concerned side. and the specification of the sign of the cos
term).
When testing the differential current
principle using two currents, inject one
current into the phase current input and the
other into the neutral current input of the
same side. Then the residual current calculated
by the relay module will be the same as the
current injected into the phase current input.
At single-phase testing the stabilizing current
calculated by the relay mod- ule (average of the
The module I1 on the HV side or the setting I02/ I2 on The directional criterion cos = 1, if the
starts, if the the LV side residual current or the neutral current of that
following - the directional differential current exceeds side is less than 4% of the rated current.
conditions are the value of the operation characteristic
fulfilled at the - the blocking based on the second Verify the operation characteristic of the stabi-
same time: harmonic and external blocking do not lized differential current principle by selecting a
- the ratio of the prevent starting point on either part of the characteristic.
neutral Keep the stabilizing current at a constant
current and Not value and increase the differential current until
the residual e! the mod- ule starts.
current of the When the setting I01/ I1 or the setting I02/
phase I2 is greater than 0%, the minimum value of Special equipment is required for testing the
currents is the neutral current required for tripping on blockings based on the ratio of the second
above the that side is 2% of the rated current. harmonic and the fundamental frequency
setting I01/ com- ponent of the neutral current.
Testing of high- Test the high-impedance principle by relay. The start value of the module is equal
impedance principle injecting current into the neutral current to the basic setting of the concerned side.
input of the
Testing of residual starts. The start value of the module is equal
overcurrent principle Test the residual overcurrent principle by in- to the basic setting of the concerned side.
jecting current into the phase current inputs
one by one. Increase the current until the
module
Testing of neutral ule starts. The start value of the module is
current principle equal to the basic setting of the concerned
Test the neutral current principle by side.
injecting current into the neutral current
input of the concerned side. Raise the current
Operate times until the mod-
relay module operates. The operate times must
be within the specified tolerances. The
Apply a current of 1.5...2 times the current operate time of the circuit breaker failure
required for starting to the module by protection is to be separately tested.
closing the current switch. Measure the
Operation indicators,
operate time, i.e. the time from closing the
alarm and operate
switch until the
signals

Check that the operation indicators and the


output relays operate properly during the test-
ing of the relay module.

Testing of the When the relay module SPCJ 4D28 is tested, it Start value:
combined over- should be noted that the module measures the Check the start value by raising the current,
current and earth- transformer HV side or the generator star starting from zero, until the relay starts. The
fault relay module point side phase currents, i.e. the phase start value should be within the permitted
SPCJ 4D28 currents con- nected to the terminals X0/1...9, toler- ances.
and the trans- former LV side neutral
current, i.e. neutral current connected to the To measure the resetting value, raise the
terminals X0/37...39. current enough to make the relay start. Then
decrease the current until the relay resets.
The tests should include the following values
and functions of the protection stages (I>, When multi-stage protection relays are tested,
I>>, I>>>, I0>, I0>>, I>) used: the operation of the low-set stages may
disturb the testing of the high-set stages. In
- start value (for the high-set stages to be conse- quence, the operation of the lower
meas- ured for all three phases) current level stages, generally, has to be
- resetting value (when desired/required) inhibited or delayed by changing their setting
- start time (for one values, to enable test- ing of the high-set
phase) stages. In such a case it is recommended to
- operate time (for one start the testing from the stage with the
phase) highest current setting and then move on to
- resetting times (when desired/required) the lower current stages. Thus the original
- operation indication, circuit breaker settings of the stages are restored during the
opening and signalling test.
Start and operate Apply a current of about 1.5...2 times the ured the measurements can be made with
times setting of the protection stage by closing the sev- eral current values (for example 2 x and
current switch. Measure the operate time, i.e. 10 x the setting value).
the time from closing the switch until the relay
operates. The operate times should be within The reset time is the time from opening the
the permit- ted tolerances. When inverse current switch until the relay resets.
times are meas-

Operation indicators, Check that the operation indicators and the


alarm and operate output relays (signalling and tripping) operate
signals properly during the testing of the relay
module.
Maintenance When the protection relay is used under the If the relay malfunctions or the operating
and repairs conditions specified in "Technical data", it re- values differ from those specified, the relay
quires practically no maintenance. The relay should be overhauled. Minor measures can
includes no parts or components that are be taken by the customer but any major repair
sensi- tive to physical or electrical wear under involving the electronics has to be carried out
normal operating conditions. by the manufac- turer. Please contact the
manufacturer or his nearest representative
Should the temperature and humidity at the for further information about checking,
site differ from the values specified, or the overhaul and recalibration of the relay.
atmos- phere contain chemically active gases
or dust, the relay should be visually inspected The protection relay contains circuits that
during the secondary testing of the relay. are sensitive to electrostatic discharge. If you
This visual in- spection should focus on: have to withdraw a relay module, ensure that
you are at the same potential as the module,
- Signs of mechanical damage to relay case and for instance, by touching the case. Detached
terminals modules should always be transported and
- Collection of dust inside the relay case; to be stored in antistatic plastic bags.
removed with compressed air
- Signs of corrosion on terminals, case or Note!
inside the relay Static protective relays are measuring
instru- ments and should be handled with
care and protected against moisture and
mechanical stress, especially during transport.

Spare parts Th
Ea
Co
Po
-U
-U
I/O
Co
Ca
Bu

Delivery Eq
alternatives
Ba
Ve
ear
Ver
Ve
rela
Ordering SPAD 346 C without test adapter RS 621 002-
numbers AA RS 621
002-CA RS 621
002-DA RS
621 002-FA
202-AA RS
P 18: 621 202-CA RS
R 621 202-DA
S RS 621 202-FA

6
2 The letter combinations of the order number denote the rated frequency fn
1 and auxiliary voltage Uaux of the protection relay:

Designation

AA
CA
DA
FA

Order data
1. Qu
2. Ord
3. Rat
4. Aux
5. Acc
6. Spe
Dimension The basic model of the protection relay case SPA-ZX 301 reduces the depth by 40 mm,
drawings and is designed for flush-mounting. When type SPA-ZX 302 by 80 mm and type SPA-
mounting required, the mounting depth of the case can ZX 303 by 120 mm.
be reduced. Three types of raising frames are
available: type

293
226
259 34
30 229
162

136

214 ±1 a b
139 ±1

Raising frame
SPA-ZX 301
SPA-ZX 302
SPA-ZX 303

Fig. 10. Dimension and mounting drawings for differential relay SPAD 346 C.
The relay case is made of grey anodized by enclo- sure
profile aluminium. between the relay
case and the
The rubber gasket fitted to the mounting mounting base.
collar provides an IP 54 degree of protection
The hinged cover of the case is made of The terminal blocks X1 and X2 contain dis-
transpar- ent, UV-stabilized polycarbonate connectable multi-pole screw terminals. The
polymer and provided with two sealable male part of the disconnectable terminal
locking screws. The rubber gasket of the blocks is attached to the I/O module. The
cover provides an IP 54 degree of protection female parts, which are included in the
between the case and the cover. delivery, can be locked to the male part with
fixing accessories and screws.
The required input and output connections
are made to the screw terminals on the rear The external control inputs of the modules
panel. The energizing currents are linked to are connected to the terminal block X1. The
the termi- nal block X0 which consists of trip signals are obtained from the the terminal
fixed screw terminals. Each terminal screw is blocks X1 and X2. The alarm signals are
dimensioned for one wire of maximum 6 mm2 obtained from X2. Each terminal of X1 and X2
or two wires of maximum 2.5 mm2. is dimensioned for one wire of max 1.5 mm2
or two wires of max. 0.75 mm2.

The 9-pole D-type connector is intended for


serial communication.
SPCD 3D53
Differential Relay Module
User´s manual and Technical description

3 I>
I1 Id I2
L1 L2 L3 IRF

RESET
P / I n [ %] STEP

S [% ]

I 2tp / I n

I d / I n >>

I d2f / I d1f > [ % ]

I d5f / I d1f > [ % ]


I d5f / I d1f >> [ % ]
I 1 / In
I2/ In PROGRAM

SGF

SGB

SGR

TRIP
0021A

SPCD 3D53
1MRS 750097-MUM EN
SPCD 3D53
Issued 1996-10-16
Modified 2004-04-27
Version F (replaces 34 SPCD 2 EN1)
Differential
Checked PS
Approved MÖ
Relay Module
Data subject to change without notice

Contents Features .......................................................................................................................... 3


Description of function .................................................................................................. 4
Rated frequency ......................................................................................................... 4
Transformer vector group matching .......................................................................... 4
Elimination of the zero-sequence component of the phase currents ........................... 4
Transforming ratio correction of phase current transformers ..................................... 4
Stabilized differential current stage 3 I> ................................................................... 5
Blocking based on the second harmonic of the differential current Id2f/Id1f .............. 7
Blocking based on the fifth harmonic of the differential current Id5f/Id1f .................. 7
Differential current stage 3 I>> ................................................................................ 8
Output signals ........................................................................................................... 8
Circuit-breaker failure protection .............................................................................. 8
Signals between the relay modules ............................................................................. 8
Second settings .......................................................................................................... 9
Resetting ................................................................................................................... 9
Integrated disturbance recorder ............................................................................... 10
Block schematic diagram .............................................................................................. 11
Symbols and signal abbreviations used .......................................................................... 13
Front panel ................................................................................................................... 14
Operation indicators ..................................................................................................... 15
Settings ......................................................................................................................... 16
Configuration switches (modified 2004-04) .................................................................. 17
Measured data .............................................................................................................. 28
Recorded information (modified 2004-04) ................................................................... 30
Main menus and submenus for settings and registers (modified 2004-04) .................... 32
Testing of output relays ................................................................................................ 34
Technical data .............................................................................................................. 35
Serial communication parameters ................................................................................. 36
Event codes ............................................................................................................. 36
Remote transfer data (modified 2004-04) ................................................................ 38
Fault codes of self-supervision system ........................................................................... 46
Features Stabilized three-phase differential relay module No interposing current transformers are needed
providing winding short circuit, interturn for the protection of two-winding transformers;
fault and short circuit protection for two- the vector group of the transformer is numeri-
winding transformers and for generator- cally matched on the HV and LV side. When
transformer units and winding short circuit required, the zero-sequence component of the
and short circuit pro- tection for generators phase currents can be reduced without vector
group matching.
Can also be used for the protection of three-
winding transformers, provided over 75% of Digital front panel settings for the correction of
the short circuit power is fed from the same CT transforming ratios
direction
Adjustable operating characteristic of the relay
The relay module is completely numerical; module
the differential current and the stabilizing
current are calculated on the basis of the Separate adjustable instantaneous differential
currents’ fun- damental frequency component. current stage
The DC com- ponent and the harmonics of
the phase currents are digitally filtered. Short operate time for faults occurring in the
zone to be protected, also at partially saturated
current transformers.

37 3
Stabilized Blocking based on the ratio between the Integrated circuit breaker failure protection
against fifth harmonic and the fundamental
connection frequency com- ponent of the differential Integrated disturbance recorder capable of re-
inrush current prevents un- necessary operation in cording six phase currents, the internal
currents harmless situations of transformer operate and blocking signals, and the
and faults overexcitation. This blocking func- tion can control signals linked to the relay
outside the be prevented if the ratio between the fifth
protected harmonic and the fundamental frequency High immunity to electrical and electromag-
area component increases at high overvoltages netic interference allows the relay to be used
in severe environments
Blocking Measured, set and recorded values are
based on indicated on the display of the relay module. Dynamic measuring
the ratio functions
between the Sensitive phase current and phase angle
second displays facilitate the checking of connection High availability - the integrated self-supervi-
harmonic and vector group matching sion system monitors the operation of the
and the elec- tronics and the software and gives an
fundamental Writing and reading of setting values alarm signal in the event of a fault.
frequency through local display and front panel push-
com- buttons, a PC with configuration software, or
ponent of from higher system levels over the serial
the port and optical fibres.
differential
current Five programmable external control
prevents inputs
op- eration
at Output relay matrix allowing the operate
transformer and control signals to be linked to the desired
connection output relay
inrush cur-
rents
Description of The differential relay module SPCD 3D53 neous differential stage is based on the funda-
function pro- vides differential current protection for mental frequency components I1 and I2 of
three phases. The settings are the same for the phase currents. The fundamental frequency
each phase. The differential relay module com- ponent Id1f (i.e. Id) of the differential
measures the phase currents on the HV and current , the fundamental frequency
LV side of the trans- former to be protected component Ib1f (i.e. Ib) of the stabilizing
or the phase currents on the stator star-point current, the second har- monic Id2f of the
side and the network side of the generator to differential current, and the fifth harmonic
be protected. The operation of the stabilized Idf5 are digitally filtered.
differential stage and the instanta-
Rated frequency
The differential relay module can be used at 16.667 Hz up to 60 Hz. The setting is
frequencies between 16 2/3 and 60 Hz. The made either via the push-buttons on the front
rated frequency setting is accurate to within 1 panel, the subregisters 5 and 6 of register A,
mHz. The rated frequency has two settings, i.e. or the serial bus, in which case the control
Hz and mHz, which are separately set from parameters V180 and V181 are used.

Transformer vector The phase difference of the HV side and LV sired vector group. The matching of the
group matching side currents that is caused by the vector group phase difference in vector group matching
of the power transformer to be protected is can be set for the HV and LV side at intervals
numeri- cally compensated. The matching of of 30 . The switches SGF1/3...5 are used for
the phase difference is based on phase the LV side vector group matching, whereas
shifting and nu- merical delta connection SGF1/6...8 are used for the vector group
inside the relay. The switches SGF1/3...8 are matching on the HV side.
used to select the de-

Elimination of the zero-sequence


component of the phase currents

38 3
Transforming ratio In vector group matching the zero-sequence can, when required, be separately calculated
correction of phase component of the phase currents is and reduced for each phase current.
current transformers eliminated before the differential and Elimination of the zero-sequence component
stabilizing current are calculated. Unless the on the HV and/ or the LV side is selected
vector group matching is made on the side of with the switches SGF1/1 and SGF1/2.
the earthed winding, the zero-sequence
component of the phase currents

sides of the protected object by adjusting the


Should the CT secondary currents deviate setting of the ratios I1/In and I2/In on the
from the rated current at the rated load of the front panel of the relay module in the
trans- former or generator to be protected, range of
the CT transforming ratios can be corrected 0.40...1.50 x In.
on both
Stabilized The operating characteristic of the stabilized In a normal situation there is no fault in the
differential stage 3 I> is determined by the basic area protected- by th- e differential relay.
current setting P/In, the setting of the starting ratio
stage 3 I> Then the
S, and the setting I2tp/In of the second turning currents I1 and I2 are equal and the differential
point of the characteristic. When the current Id = 0. In practice, however, the
differential current exceeds the setting value differ-
of the operating char- acteristic, the relay ential current deviates from zero in normal
provides an operate signal unless the relay situations. In power transformer protection
module internally blocks the trip function dif- ferential current is caused by CT
and it is not blocked by an external blocking inaccuracies, variations in tap changer
signal BS1, BS2, BS3, BS4 or BS5, or an position, transformer no-load current and
intermodular blocking signal BS INT1, BS instantaneous transformer inrush currents.
INT2 or BS INT3. The switches SGB2/1...8 Increases in the load current cause the
are used for configuring the blocking signals differential current caused by the CT
inaccuracies and the tap changer position to
grow at the same percentage rate.
- -
Designate the phasors I1 and I2 of the funda- In a stabilized differential relay the differential
mental frequency currents of the CT current required for tripping is higher the
secondary higher
currents on the input and output side of the the load current is. The stabilizing current Ib
protected object. The amplitude of the of the relay is obtained as follows:
differen- tial current Id is obtained as
follows:
- -
- - I 1 + I2
Id = I1 – I2 (1) Ib = (2)
2

Id
In
3.0
2.5 Id3
In
2.0

In Ib3
1.0 In
Id1 I d2
0.5 In In

0.0 0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 Ib


In
1 2 3

39 3
Fig. 1. Operating characteristic of the stabilized differential current stage of the differential
relay module SPCD 3D53
The operation of the relay is affected by The starting ratio S is determined
the stabilization as shown graphically by the correspond- ingly
operat- ing characteristic illustrated in Fig. 1.
S = Id2/Ib2
The basic setting P/In of the stabilized stage (4)
of the differential relay module is determined
ac- cording to Fig. 1: The second turning point I2tp/In can be set
at the desired point in the range 1.0...3.0. The
P/In = Id1/In first turning point is always fixed at Ib/In =
(3) 0.5.
The slope of operating characteristic of the Part 2, i.e. 0.5 Ib/In < I2tp/In, is called
differential relay module varies in the different the influence area of starting ratio S. In this
parts of the range. In part 1 (0.0 Ib/In < 0.5) part variations in the starting ratio affect the
the differential current required for tripping is slope of the characteristic, that is, how big the
con- stant. The value of the differential change in the differential current, in
current is the same as the basic setting P/In comparison with the change in the load
selected for the relay module. The basic current, is required for trip- ping. The
setting basically allows for the no-load starting ratio should consider CT errors and
current of the power trans- former, but it can variations in the power transformer tap
also be used to influence the overall level of changer position. Too high a starting ratio
the the operation characteristic. At rated should be avoided, because the sensitivity of
current the no-load losses of the power the differential relay for detecting
transformer are about 0.2 per cent at rated transformer interturn faults depends basically
voltage. Should the supply voltage of the on the starting ratio.
trans- former suddenly increase due to
operational disturbances the magnetizing At high stabilizing currents I /I I2tp/In
b n
current of the transformer increases as well. the slope of the characteristic is constant (part
In general the magnetic flux density of the 3). The slope is 100%, which means that the
transformer is rather high at rated voltage and in- crease in the differential current is equal to
the rise in voltage by a few per cent will cause the corresponding increase in the stabilizing
the magnetizing current to increase by tens cur- rent.
per cent. This should be considered in the
basic setting.

Id
In
Curve
5.0

4.0

3.0

2
2.0

1.0

0.0 0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 Ib
In

Fig. 2. Setting range for the stabilized differential current stage of the differential relay module
SPCD 3D53.

40 4
Blocking based on The blocking of relay operation at through switch SGF2/1. The switchgroup
the second harmonic transformer inrush currents is based on the SGR3 is used to route the blocking signals
of the differential ratio Id2f/Id1f of the amplitudes of the second to the required output relays, if the differential
current Id2f/Id1f harmonic and the fundamental frequency current of the phase concerned is above the
component of the dif- ferential current. The value of the trip curve and if the operate signal
ratio to be used for block- ing is calculated as of the other phases is not active at the
a weighted average on the basis of the ratios same time. The blocking remains active until
between the second harmonic and the the ratio Id2f/Id1f falls below the blocking
fundamental frequency component cal- limit.
culated from the differential currents of the
three phases. The ratio between the second If the power transformer is connected against a
harmonic and the fundamental frequency fault in the protected area, the blocking based
com- ponent of the differential current of on the second harmonic of the differential
the con- cerned phase is of most weight current is inhibited by a special algorithm.
compared with the ratios of the other two The opera- tion of the relay will not be
phases. Using sepa- rate blocking for the delayed even if the differential current
individual phases and weighted averages contains a great amount of second harmonics
calculated for the separate phases provides a due to the connection inrush current. The
blocking scheme that is stable at connection operation of the blocking inhibit- ing
inrush currents. algorithm is based on the different wave-
form and the different rate of change of
The operation of the stabilized stage on the normal connection inrush current and
concerned phase is blocked if the weighted connection in- rush current containing fault
ratio of the second harmonic and the current. The algo- rithm does not eliminate
fundamental frequency component of the the blocking at con- nection inrush currents,
differential current of the concerned phase is unless there is a fault in the protected area.
above the set blocking limit Id2f/Id1f > and When required, the operation of the algorithm
if blocking is enabled can be disabled (switch SGF2/2).

Blocking based on Blocking of relay operation in situations of the value of the trip curve and no operate
the fifth harmonic overexcitation is based on the ratio Id5f/Id1f signal of the other phases is active at the same
of the differential of the amplitudes of the fifth harmonic and time.
current Id5f/Id1f the fundamental frequency component of the
dif- ferential current. The ratio is calculated The setting value Id5f/Id1f>> is used to
sepa- rately for each phase without weighting eliminate the blocking immediately if the
factors. Should the ratio exceed the setting ratio between the fifth harmonic and the
value of Id5f/ Id1f and blocking is enabled fundamental fre- quency component of the
through switch SGF2/3, the operation of the differential current approaches a dangerous
stabilized stage of the relay in the concerned level because of a high overvoltage. The
phase will be blocked. The blocking signal is blocking is eliminated, if ena- bled by switch
routed to the output relays determined by SGF2/4 (SGF2/4 = 1) and the ratio of the
SGR3, provided the dif- ferential current of fifth harmonic and the fundamental frequency
the phase concerned exceeds component is greater than the setting value of
Id5f/Id1f>>.
Differential current In addition to the stabilized stage the
stage 3 I>> relay includes an instantaneous differential The switchgroups SGR1...SGR8 can be used to
current stage 3 I>> which does not allow link the operate signals of the stabilized
for stabi- lization. This stage provides an differen- tial stage and the instantaneous
operate signal to the output relays selected differential stage, the internal blocking signals
with the switchgroup SGR2, when the and the external control signals BS1...BS5 to
amplitude of the fundamental frequency the desired signal outputs SS1...SS4 or
component of the differential current exceeds TS...TS4.
the set operate value Id/In>> or the
instantaneous value of the differential The switchgroup SGF4 allows a self-holding
current exceeds 2.5 x Id/In>>. The value can feature to be selected for the output signals
be set in the range 5...30 x In. The internal SS1...SS4 and TS1...TS4. When this function
blocking signals of the relay module do not has been selected, the output signal remains
prevent the operate signal of the differential
current stage 3 I>>. When required the
operate signal of the stage
Output signals
41 4
can be blocked by Should the fundamental frequency active though the signal that caused operation
the external component of the stabilizing current fall resets. The means of resetting the output
control signals below 30% of the fundamental frequency relays are shown in the table in paragraph
BS1...BS5 or the component of the dif- ferential current, a "Resetting".
intermodular fault has most certainly oc- curred in the
blocking signals BS area protected by the differential relay The operation of the TRIP operation
INT1...BS INT3. module. Then the operate value set for the indicator on the front panel can be
Blocking is stage 3 I>> will be automatically halved and configured to be initiated by the activation of
enabled via the internal blocking signals of the stabilized any TS signal. The operation indicator
switches stage will be inhibited. remains lit when the signal resets. The
SGB3/1...8. switchgroup SGF5 is used for pro- gramming.
The means of resetting are shown in the table
in paragraph "Resetting".

Circuit-breaker The differential relay module SPCD 3D53 is duty output relay TS1 of the circuit-breaker
failure protection provided with circuit-breaker failure protection failure protection can be used to operate the
(CBFP), which provides an operate signal TS1 circuit breaker in front of the circuit breaker
0.1...1 s after the operate signal TS2, TS3 or of the feeder of the object to be protected.
TS4, unless the fault has disappeared during The switches SGF3/1...3 are used to enable
this time. In the range 100...440 ms the the cir- cuit-breaker failure protection and the
operate time can be adjusted in steps of 20 ms switches SGF3/4...8 are used for setting the
and in the range operate time of the CBFP.
440....1000 ms in steps of 40 ms. The heavy-

Signals between the the logic active state of the external control
relay modules The signals BS INT1, BS INT2 and BS INT3 signals and the intermodular blocking signals.
are intermodular blocking signals which can So, the input can be activated when energized
be used to block the operation of a relay or when non-energized.
module located in another card location of
the same protection relay. An intermodular The signals AR1, AR2 and AR3 can be used
signal is acti- vated when the corresponding to trigger the disturbance recorder SPCR
blocking signal of one relay module is 8C27 fitted in one of the card locations of
activated. The blocking signals BS INT1, BS the relay. These signals cannot be used to
INT2 and BS INT3 are not capable of control the output relays.
controlling the output relays. The switches
SGB1/1...8 are used for the selection of
Second settings Two different setting values are available for the The S parameters allow the main setting
relay: main setting values and second values and second setting values to be read and
setting values. Switching between these two set over the serial bus. The push-buttons on
types of setting value can be done in three the front panel can be used for reading and
ways as follows: setting actual setting values only.
1) Over the serial bus, using command V150 N.B. If external control signals have been
2) By means of an external control signal: used for selecting main or second setting
BS1, BS2 or BS3 values, it is not possible to switch between
3) Via the push-buttons on the front panel of main settings and second settings via the
the relay module and subregister 4 of serial bus or the push-buttons on the front
register A. Selecting the value 0 for the panel.
subregister brings the main settings into
effect, whereas the value 1 activates the
second settings.

Resetting The operation indicators on the front panel with the push-buttons on the front panel, via
of the relay module, the operation codes on an external control signal or a serial
the display, latched output relays, and the communica- tion parameter as shown in the
registers of the relay module can be reset in table below.
three ways:

42 4
Means of resetting recording

RESET

PROGRAM

RESET & PROGRAM

External control signal BS1, BS2 or BS3, when SGB5/1...3 = 1

SGB6/1...3 = 1
SGB7/1...3 = 1

Parameter V101

Parameter V102

Integrated The integrated disturbance recorder records the V242 specifies whether the recording is to be
disturbance recorder waveforms of the currents to be measured, the started by the rising or falling edge of the
digital control inputs of the module and the signal specified by parameter V241.
internal signals. The module has six analog and Parameter V243 defines the control signals to
11 digital channels. The memory has a be used for trigger- ing, and parameter V244
capacity of one record the length of which is specifies whether the rising or falling edge of
38 cycles. The record has to be downloaded the control signal is to start the recording
before a new recording sequence can be sequence.
started. The memory is also emptied by
resetting the values recorded by the module. Parameter V245 is used for setting the length
The sampling frequency of the disturbance of the recording that follows triggering.
recorder is 40 times the rated fre- quency of The number of the recording cycles following
the module, that means that the sampling trig- gering is equal to the value of parameter
frequency at 50 Hz is 2000 Hz. V245. The total recording length is fixed and
always about 38 cycles.
The recording can be triggered by the
internal signals of the relay module or the When the serial communication parameter
control signals linked to the module. Internal V246
signals are the operate signals of the stabilized = 0, the disturbance recorder has not been
stage (3 I>) and the instantaneous stage (3 triggered, i.e. the recording memory is
I>>), plus the block- ing signal . The control empty. When V246 = 1, the disturbance
signals linked to the module are the signals recorder has been triggered and the memory
BS1...5 and BS INT1...3. Recording can be is full. The recording memory is emptied
triggered by the rising or falling edge of by giving the parameter V246 the value 0.
any (one or several) of these signals. The memory has to be empty before the
Triggering at rising edge means that the disturbance recorder is able to start a new
recording sequence starts when the signal is recording sequence. A memorized recording
activated. Correspondingly, triggering by fall- is indicated by the letter "d" to the right of
ing edge means that the recording sequence the display, when no measured, set or
starts when the active signal resets. recorded value is displayed.

The serial communication parameters V241... The recorded data of the built-in
V245 are used for configuring the disturbance recorder are downloaded, for
disturbance recorder. Parameter V241 instance, with the help of a PC program and
specifies the internal signals to be used for the serial communi- cation parameter V247.
triggering and parameter

43 4
Bloc
k
sche
mati
c
diag
ram

Fi SGF1/2=0 1f P/ I n, S, I 2tp / In
g. i 1- i 01
I d1f = I d
3.
Bl I L1
I /I
1 n i 1+ i 2
ib SGR1/1=1
oc i1 2 3I > trip SS1
&
k I L2
I / In >>
d
sc Y 1f SGR1/2=1
he I L3
I
I < 0.3 x I
ma
tic b b d
3I >> trip SGR2/2=1 1 TS1
dia SGF1/1=0 i2- i 02
gra
m I'
i d = i 1- i 2 I d2f / I
d1f SGR2/3=1
I /I > SS2
wi L1 2 n
2f SGF2/1=1 &
th I' L2
i2 +
-
I d2f &
sw Y SGR1/4=1
itc I' L3 SGR2/4=1 1 TS2
Inhibition of &
hg blocking
ro SGF2/2=1
up I /I > SGF6/1=1
def 5f
d5f d1f
1 AR1
SGF6/2=1
aul SGF1/3...8=0 I d5f SGF2/3=1
t &
set SGF7/3=1
tin 1 AR2
gs I d5f / I d1f >> 2nd or 5th
harmonic
blocking
SGF2/4=0 SGF5/1=1
SGF5/2=1 1

RESET TRIP
SPCD 3D53

11
n
SGF1/ 1f P/ I , S, 2tp
I /nI
2 I d1f =
i1 - i 01 Id SGF4/1 RESET +
PROGRA
i +i M
I 3I > trip
L1 i2 b 1 SGR1/x x=1 1 SS1
I1 / I n

I 2 &
L2 i1 1f SGF4/2 RESET +
I d / I n >> PROGRA
Y Ib I b < 0.3 x Id M
I 3I >> trip SGR2/
L3 x=2 1
x 1 TS1
t CBFP
Fi i -i
SGF1/ 2 02 SGF4/3
SGF5/1

g. 1
2f
Id2f / Id1f >
2nd or x=3 1
RESET +
PROGRA
M SGF3/4...8
4. I' L1 I2 / I n
id = i1 - i 2
SGF2/
1 5th SGR3/
SS2

harmonic x
Bl blocking
oc I' L2 &
I d2f
k Y
i2 +
- & SGF3/
1
SGF4/4 RESET +
PROGRA
M
sc I'L3 Inhibition
of blocking SGF2/2
1 TS2

he & x=4
SGF4/5
SGF5/2

ma SGF1/3...8
Id5f / I d1f > RESET +
PROGRA

tic 5f
1 M

dia x=5

gra SGB1/1 x=1 SGB2/


x
I d5f SGF2/3 SGF3/
2
SGF4/6 RESET +
PROGRA
SS3
&
m BS1 1
1
M

for SGB1/2
SGB3/
x
Id5f / Id1f
>> x=6 TS3
dif
fer BS2
1
x=2 SGB4/1... SGF2/ SGF4/ SGF5/3
ent 3 Settings (main / 4 7
RESET +

ial
PROGRA
SGB1/3 SGB5/1... second) Reset trip M
3
rel BS3 1
indicator
Reset trip indicator
x=7 1 SS4
SGB6/1... RESET +
ay x=3
3
and output relays
Reset trip indicator, output
SGF3/
3
PROGRA
M
m SGB1/4 SGB7/1...
relays
SGF4/8

od 3

ule BS4 1
x=4
and registers (complete relay reset)
x=8 1 TS4
SP BS1 SGF5/
4
C SGB1/5
1
SGR4/x
SGR5/x
BS2
BS3
RESET

D BS5 x=5
SGR6/x BS4 TRIP

3 x=6
SGR7/x
3I > trip x=1
D BS INT1
SGB1/6
1
BS5
SGR8/x 3I >> trip x=2
SGF6/
x
AR1
AR2
53 SGF7/
x
2nd or 5th harm. bl. SGF8/
x=3 x AR3
SGB8/1 BS INT1
SGB1/7 BS1 x= 1
1 4
BS INT2

BS INT3 SGB1/8 SGB8/2


1
1
12 x=7

x=8
BS INT2
SGB8/3
1 BS INT3

SPCD 3D53
Symbols and signal IL1, IL
I’L1, I
abbreviations used I1
I2
In
i1
i2
i01

i02

id
ib
Id1f, Id

Ib

Id2f
Id5f
3 I>
3 I>>
SGF1.
SGB1
SGR1
BS1...
SS1...
TS1...
BS IN
AR1..
tCBFP
Note! wired to the terminals are shown in the
All input and output signals of the module are diagram illustrating the flow of signals between
not necessarily wired to the terminals of every the plug- in modules of the relay assembly.
relay assembly using this module. The signals

13 13
Front panel
3 I>
I1 Id I2
L1 L2 L3 IRF
Current measurement indicators

Basic setting indicator RESET


P / I n [ %] STEP

Starting ratio setting indicator S [% ]

Indicator for setting the second turning point of the operation characteristic
I 2tp / I n

Indicator for setting the instantaneous differential current stage


I d / I n >>
Indicator for setting the blocking ratio of the second harmonic and
the fundamental frequency of the differential current I d2f / I d1f > [ % ]

Indicator for setting the ratio of the fifth harmonic and the fundamental I d5f / I d1f > [ % ]
frequency component of the differential current (for setting the blocking and I d5f / I d1f >> [ % ]
deblocking operation)
I 1/ In
Indicator for transforming ratio correction of current transformers
on transformer HV side or generator neutral side
I2/ In
Indicator for transforming ratio correction of current transformers
SGF PROGRAM
on transformer LV side or generator network side
Indicator for checksums of switchgroups SGF1...11
SGB
Indicator for checksums of switchgroups SGB1...8
SGR
Indicator for checksums of switchgroups SGR1...8

TRIP

0021A
SPCD 3D53
3 I> Device symbol
I1 Id I2
L1 L2 L3 IRF
IRF indicator

Display

RESET
P / I n [ %]
STEP

S [% ] Display step/reset push-button

I 2tp / I n

I d / I n >>

I d2f / I d1f > [ % ]

I d5f / I d1f > [ % ]


I d5f / I d1f >> [ % ]

I1/ In

I2/ In PROGRAM

SGF Setting switch

SGB

SGR
TRIP
Operation indicator
0021A

SPCD 3D53 Type designation of relay module

Fig. 5. Front panel for differential relay module SPCD 3D53


Operatio The operation indicators of the differential An operate signal issued by the stabilizing
n relay module are the red operation code of stage of the differential relay module is
indicator the display and the red TRIP indicator that indicated by a red operation code 1 on the
s indicates opera- tion. display, whereas an operate signal by the
instantaneous stage is indicated by the
operation code 2. When an operate signal is
issued by the dark, the operate signal was not linked to a cerned signal to the desired output relay via
stabilizing heavy-duty output relay. Indica- tors the switchgroups SGR4...SGR8.
stage or the indicating operation remain lit until reset. Operation ini- titated by an external
instantaneo control signal is indicated on the display by
us stage the Activation of the external control the respective operation code. The
TRIP signals BS1...BS5 is indicated on the operation codes remain lit until reset.
indicator is display by the respective red operation
lit, code 4, 5, 6, 7 and 8. The operation code When relay operation is initiated by an
provided remains lit as long as the control signal is external control signal, the TRIP indicator
the operate active. If the control signal was is automati- cally lit, if the output relay
signal of programmed (switchgroups SGB4...7) to selected is one of the heavy-duty output
the be used to switch the main settings to relays TS1...TS4 configured to be
concerned second settings or vice versa, or to reset the controlled by stage 3 I> or stage 3 I>>.
stage is operation indicators, latched output Otherwise the TRIP indicator is lit only if
linked to a relays, registers or recording memory, the the output signal of the control signal has
heavy-duty activation of the control signal is not been set to light the indicator (switchgroup
output relay indicated on the display. SGF5). If latch- ing feature is selected for
TS1, TS2, the output signal, the operation indicators
TS3 or TS4 The external control signals can be used remain lit until reset.
via a switch as operate or alarm signals by routing the
of con- Blocking based on the ratio between the
switchgroup second harmonic and the fundamental
SGR1 or frequency com- ponent of the differential
SGR2. The current and on the ratio between the fifth
phase that harmonic and the funda- mental frequency
initiated component of the differential current is
relay indicated by the red operation code 3 on the
operation is display. The code is displayed as long as the
indicated by blocking signal is active. If the output relays
the yellow controlled by the blocking has a latching
LED indi- fea- ture, the operation code is displayed
cators above until the relays are reset. If the circuit-
the display. breaker failure protection has operated, the
Should the operation code A is indicated on the
operation display until the operation indicators are
code 1 or 2 reset.
be indicated
on the The table below describes the red
display the operation codes shown on the display to
TRIP indicate operate signals, blocking, an
indicator activated control input or operation of the
still being circuit-breaker failure protec- tion.

Code D

1 St
2 In
3 Bl
Ex
4 C
5 D
6
7
8
A
Yellow d
When the protection stage or the control the relay, an external control signal or over
signal resets, the TRIP indicator and the the serial bus, see the table in paragraph
red operation code remain lit. The "Descrip- tion of operation". Unreset
operation indicators can be reset via the operation indicators do not affect the
push-buttons on the front panel of operation of the relay module.
The self-supervision alarm indicator IRF the red indicator is
indi- cates internal relay faults. Once the lit. At the same
self-supervi- sion system of the relay time the relay
module has detected a permanent fault, module delivers a
signal to the self-supervision system output figure one and a green code number cannot
relay of the relay assembly. In addition, a be removed by resetting. It should be
fault code is lit on the display to show the recorded and stated when service is
type of the fault that has occurred. This ordered.
fault code that consists of a red
The table below shows the priority of the
opera- tion codes representing certain
events. If the priorities of the events to be
indicated are the same, the operation
indicator of the latest event is indicated on
the display.

Priority Event to be indicated

1. Self-supervision fault code C


2. Stabilized stage 3 I> operate
3. External control signal activ
4. Internal blocking Id2f/Id1> o
5.

6.
7.

Settings The setting values are indicated by the The second settings of the differential
three right-most digits on the display. relay module can be activated via
When a LED in front of a setting value subregister 4 of register A. The setting
symbol is lit it shows that the particular ranges are the same as those of the main
setting value is indicated on the display. settings. When the second settings are
The setting value given in parentheses active the LED representing the particular
under the setting range is the default setting value indicated on the display is
setting. flashing.

Setting

P/In(%)

S (%)

I2tp/In

Id/In>>

Id2f/Id1f>(%)

Id5f/Id1f>(%)

Id5f/Id1f>>(%)

I1/In

I2/In

The setting of the switchgroups


SGF1...11, SGB1...8 and SGR1...8 are
described in the following paragraph
"Configuration switches".
Configuratio The switches of switchgroups tion, 0 or 1, are displayed during
n switches SGF1...11, SGB1...8 and the setting procedure. In normal
(modified 2004- SGR1…8 can be used to select service conditions the checksums
04) additional functions required for of the switchgroups are
different ap- plications. The displayed. These are found in the
switch number, 1...8, and posi- main menu of the relay module,
see chapter menus of settings and contains an extra switchgroup
"Main menus registers". The default settings SGX, which is located in
and sub- and their checksums are also submenu 7 of register A on the
mentioned in the tables. The frontpanel (effective from software
calculation of the checksum is version
described in the end of this 187 A
paragraph. Further, the module onwards).

Switchgroup Vector group matching and elimination of the zero-sequence


SGF1 component

The Table 1. below includes the The connection of the main


switch posi- tions representing current transform- ers in the
the most general power trans- vector groups of column "II" is of
former vector groups. In the type II. In this case the normal
vector groups given in column directions of the HV and LV side
"I" the connection of the main relay currents are equal, see Fig.
cur- rent transformers are of type 7.
I. Then the normal directions of
the HV and LV side relay
currents are opposite, i.e. when
there is no fault in the
protected zone, see Fig. 6.
P2 P1 P1 P2 P1
L1 P1
P2 L1
S2 S1 P2 S2 S1
S1 S1
L2
S2 S2

L2

L3 L3

3 6 9 1,4,7 13,16,19 21
18 15 1,4,7 9 6 3 15 18 21 13,16,19

Fig. 6. Connections of current transformers of type I. The relay


currents on HV and LV side have opposite directions. The CT wires
are numbered according to the 1 A nominal current input
terminals of the relay.

P2 P1 P2 P1 P2
L1 P1
P1 L1
S2 S1 P2 S1 S2
S2 S1
L2
S1 S2

L2

L3 L3

3 6 9 1,4,7 15 18 21
13,16,19 1,4,7 9 6 3 13,16,19 21 18 15

Fig. 7. Connections of current transformers of type II. The relay


currents on HV and LV side have equal directions. The CT wires are
numbered according to the 1 A nominal current input terminals of
the relay.
Table 1. Matching of the most general power transformer vector groups

Power transformer vector group

Yy6 Yy0
YNyn8 YNyn2
YNyn10 YNyn4
YNyn6 YNyn0
Yy0 Yy6
YNyn2 YNyn8
YNyn4 YNyn10
YNyn0 YNyn6
Yd1 Yd7
YNd1 YNd7
Yd5 Yd11
YNd5 YNd11
Yd7 Yd1
YNd7 YNd1
Yd11 Yd5
YNd11 YNd5
Dd6 Dd0
Dd0 Dd6
Dy1 Dy7
Dyn1 Dyn7
Dy5 Dy11
Dyn5 Dyn11
Dy7 Dy1
Dyn7 Dyn1
Dy11 Dy5
Dyn11 Dyn5
YNzn1 YNzn7
YNzn5 YNzn11
YNzn7 YNzn1
YNzn11 YNzn5
Dzn0 Dzn6
Dzn2 Dzn8
Dzn4 Dzn10
Dzn6 Dzn0
Dzn8 Dzn2
Dzn10 Dzn4

The switches SGF1/3...8 are used for compen- ential current and the stabilizing current are
sating the phase difference of the HV and LV calculated.
side phase currents that is caused by the
vector group of the power transformer. Vector group matching is not required if there
is no phase difference between the HV and
Vector group matching can be implemented LV side phase currents of the transformer to
both on the HV side and the LV side or only be protected. However, the zero-sequence
on the HV or the LV side. Vector group compo- nent of the phase currents on the star-
matching is almost always made on the star connected side that is earthed at its start
connected side of YNd and Dyn connected point has to be eliminated before the
transformers. Then the zero-sequence differential and stabilizing current are
component of the phase cur- rents at earth calculated. The switches SGF1/1...2 are used
faults occurring out of the protec- tion area is for eliminating the zero-sequence com- ponent
eliminated in the vector group match- ing on from the HV and/or LV side phase
the star connected side before the differ- currents.
If, for instance, there is an earthing transformer on quence component of the phase currents has to be
the delta-connected side of the YNd power separately selected with switch SGF1/1. No
transformer in the area to be protected, the interposing transformers are required for the
vector group matching is normally made on the side elimination of the zero-sequence component.
of the star connection. On the side of the delta The table below shows the function of the
connection elimination of the zero-se- switches SGF1/1 and SGF1/2.

Table 2. Calculated zero-sequence component elimination


Switch

SGF1/1 = 1

SGF1/1 = 0
SGF1/2 = 1

SGF1/2 = 0

The tables below show how the switches SGF1/ column "internal matching" shows the vector
3...8 can be used to set the vector groups for group matching implemented numerically in-
phase currents linked to the relay. The first side the relay module.

Table 3. Vector group matching on LV side.

Internal matching

Yy0
Yd1
Yd5
Yy6
Yd7
Yd11

Table 4. Switchgroup matching on HV side

Internal matching

Yy0
Yd1
Yd5
Yy6
Yd7
Yd11
When the internal matching is Yy0 the phase quence component of the phase currents is not
angle of the phase currents connected to the relay eliminated. Then the switches SGF1/1 and
does not change. When the internal match- ing is SGF1/2 have to be used to eliminate the zero-
Yy6, the phase currents will be turned sequence component of the phase currents, when
180 in the relay. If the internal matching is required.
Yd1, Yd5, Yd7 or Yd11, a possible zero-seq-
uence component in the phase currents will be By using the tables 2, 3 and 4 it is possible to
eliminated in the numerically implemented delta program vector groups for the differential relay
connection before the differential current and the module other than those presented in table 1
stabilizing current are calculated. With the internal "Matching of the most general power trans-
matching Yy0 and Yy6 the zero-se- former vector groups".
Switchgroup SGF2 Internal blockings

Switch Function

SGF2/1 The switch is used


When SGF2/1 = 1

SGF2/2 The switch is used


When SGF2/2 = 1

SGF2/3 The switch is used


When SGF2/3 = 1

SGF2/4 The switch is used


When SGF2/4 = 1

SGF2/5 Not in use. Has to


SGF2/6 Not in use. Has to
SGF2/7 Not in use. Has to
SGF2/8 Not in use. Has to

SGF2

20
Switchgroup SGF3 Circuit-breaker failure protection (CBFP)

Switch

SGF3/1
signal TS2
SGF3/2
signal TS3
SGF3/3

SGF3/4...8

SGF3

Table 5. Circuit-breaker failure protection operate times to be selected with switches SGF3/4...8.

tCBFP / ms

100
120
140
160
180
200
220
240
260
280
300
320
340
360
380
400
420
440
480
520
560
600
640
680
720
760
800
840
880
920
960
1000

21 21
Switchgroup SGF4 Self-holding of output signals

Switch Function

SGF4/1 Selection of self-h


SGF4/2 Selection of self-h
SGF4/3 Selection of self-h
SGF4/4 Selection of self-h
SGF4/5 Selection of self-h
SGF4/6 Selection of self-h
SGF4/7 Selection of self-h
SGF4/8 Selection of self-h

SGF4

When a switch is

When the self-ho

Switchgroup SGF5 Activation of TRIP operation


indicator
output is in position 1, the TRIP operation
indicator is lit by the activation of the signal.
Selection of the output signal to control the The switches SGF5/5...8 are not in use.
TRIP operation indicator on the front panel.
When the switch linked to a certain signal

Switch
SGF5/

1
2
3
4

SGF5

Note! Special attention should be paid to the setting


The operate signal of the stabilizing and the of switchgroup SGF5 when the operate signal
instantaneous stage of the differential relay can be initiated by an external control signal
module lights the TRIP indicator irrespective BS1, BS2, BS3, BS4 or BS5.
of the setting of switchgroup SGF5, provided
the operate signal is linked to a heavy-duty
output relay via an output signal TS1, TS2,
TS3 or TS4.

Switchgroups Selection of the signals of the protection The signals of the protection stages and the
SGF6...11 stages and the external control signals control signals are linked with the desired
BS1...5 to be used as intermodular signals intermodular signal lines, for example, by encir-
AR1...3 and BS INT1...3. The signal
configuration is presented in Fig 8 below.
cling the number is marked at each intersection point checksums of the switchgroups are obtained
intersections and the weighting value of the switch is at the bottom of the matrix. The checksums
of the signal given on the right side of the matrix. By of the factory settings are given under the
lines. The adding the weighting values of the switches calculated checksums.
switch selected from each switchgroup the

Intermodula AR1 AR2 AR3 BS BS BS


r signal INT1 INT2 INT3

Function/ Weighting
signal factor

3I> 1 1 1 1 1 1 1
trip

3I>> 2 2 2 2 2 2 2
trip

Harm. 3 3 3 3 3 3 4
block.

4 4 4 4 4 4 8
BS1

5 5 5 5 5 5 16
BS2

6 6 6 6 6 6 32
BS3

7 7 7 7 7 7 64
BS4

8 8 8 8 8 8 128
BS5

SGF6 SGF7 SGF8 SGF9 SGF10 SGF11


Check-
sum =

Factory
setting = 3 4 0 0 0 0

Fig. 8. Programming matrix for intermodular signals


Switchgroup SGB1 Selection of the logic active state of the active (state 1), when voltage, either DC voltage
external control signals BS1...5 and the 18...265 V or AC voltage 80...265 V, is
intermodular blocking signals BS INT1...3. applied to the control input. When the
switch is in position 1, the signal is active
When the switch is in position 0, the signal is when no voltage is applied to the control
input.

Switch Function
SGB1/1 Selection of activ
SGB1/2 Selection of activ
SGB1/3 Selection of activ
SGB1/4 Selection of activ
SGB1/5 Selection of activ
SGB1/6 Selection of activ
SGB1/7 Selection of activ
SGB1/8 Selection of activ

SGB1

Switchgroup The switchgroups SGB2...7 are used to selected switches for each switchgroup gives
SGB2...7 configure the functions of the control signals the switchgroup checksums at the bottom of
BS1...5 and BS INT1...3. The matrix below the matrix. Switches not mentioned are not in
can be used for configuring the signals. The use and should be in position 0.
control signals are linked with the desired
function by marking the intersections of the Note!
lines. The switch number is marked at each Before programming it should be checked
intersection point and the corre- sponding whether all control signals of the relay
weighting factor to the right of the matrix. module SPCD 3D53 are used in the relay.
Adding the weighting factors of the

RESET

3I> Indicators,

trip

Control
s ignals

BS1

BS2

BS3

BS4

BS5

BS
6
INT1

BS
7
INT2
BS 128
8 8
INT3

SGB2 SGB3 SGB4 SGB5 SGB6 SGB7


Check-
sum =

Factory
setting = 0 0 0 0 0 0

Fig. 9. Matrix for programming external control signals


Switches

SGB2

SGB3

SGB4/1...3

SGB5/1...3

SGB6/1...3

SGB7/1...3

Switchgroup SGB8 The active logic state of the blocking signals ule in relation to the logic state of the
BS INT1, BS INT2 or BS INT3 of the relay signal linked to the blocking signal.
mod-

Switch Function

SGB8/1 When SGB8/1 =


Not in used. Has
SGB8/2

SGB8/3

SGB8/4
SGB8/5
SGB8/6
SGB8/7
SGB8/8

SGB8

Switchgroups The switches SGR1...8 are used to configure TS1...TS4 by encir- cling the intersections of
SGR1...SGR8 the operate signals of the protection stages the signal lines. The switch number is marked
and the control signals to operate as at each intersection point and the weighting
desired output signals SS1...SS4 or value of the switch is
TS1...TS4.

The matrix below can be used for


programming. The signals are connected
with the desired output signal SS1...SS4 or
given at the factors of the switches selected from each Note!
bottom of the switchgroup the checksums of the Check that all output signals of the relay
matrix. By switchgroups are obtained to the right of mod- ule SPCD 3D53 are in use in the
adding the the matrix. (The checksums of the factory concerned protection relay before
weighting setting are given in paranthesis). programming.

Output signal
Switch- Function/ Checksum
group control signal (factory setting)
3I>
SGR1 trip 1

3I>>
SGR2 trip
1

SGR3 1
block.

SGR4 BS1

SGR5 BS2

SGR6 BS3

SGR7 BS4

SGR8 BS5

Weighting factor

Fig. 10. Output relay matrix for differential relay module SPCD 3D53.

Switchgroup SGX
Switch
Measured data Measured values are indicated by the three Note! The measured data displayed consider
green right-most digits on the display. Data the effect of the transforming ratio corrections
LED
that isSGX/1
currently being measured is indicated by Red
indicator I1/In and I2/In. The phase difference displayed
symbol
a LED above the display and by a red digit or is the phase difference of the currents after
letter to the left on the display. vector group matching.
L1

L2
Measured data of SGX/2..8
main menu L3

L1

L2

L3

L1

L2

L3
Measured data of The measured data of the submenu are de- register in the subregister of which the con-
submenu scribed in the table below. The red symbol cerned measured data is available.
displayed on main menu level shows the main

LED Main menu


indicator red symbol

L1

L2

L3

L1

L1, L2

L2, L3
LED Main menu
indicator

L1, L3

L2

L1

L2

L3

L3

L1, L2

L2, L3

L1, L3

L1

L2

L3

29
Recorded The information recorded is stored in a Note!
information pushdown storage either at the moment of Minimum value of the ratio of the second
(modified 2004-04) the relay operation, registers 1…6, or during harmonic and the fundamental frequency
trans- former connection inrush, registers 7… com- ponent of the differential current is
9. The pushdown storage contains the five recorded in each phase without using any
latest values recorded (n)...(n-4). Each new weighting coeffi- cients.
value is stored in the first location (n) in the
storage and pushes all the previous items one Note!
step forward (n-1). When a sixth item is stored Recorded information can be stored to non-
the oldest item (n-4) of the memory is lost. volatile memory by setting SGX/1 in position 1.
By factory settings, SGX/1 is in position 0, re-
The most recently stored values (n) are corded information is cleared after a loss of
available in the main registers. Maximum aux- iliary power supply.
four of the previous values are in the
subregisters. The left- most digit indicates the
address of the storage location and the other
three digits the numerical value of the
parameter recorded.

Register Recorded va
number

1 Differential c

Differential c

2 Differential c

Stabilizing cu

3 Stabilizing cu

Stabilizing cu

4 Minimum va

Minimum va

5 Minimum va

30 30
Register Record
number

0 Status

Con

From

A detai

The ad
A cont

1. Sett
2. Bus
3. Pass
4. Sele
Def
5. Hz
A 6. mH
So,
7. Che

When the display is dark, access to the begin- tion parameter, see section "Resetting" in para-
ning of the main menu is gained by pressing graph "Description of function". In case
the STEP push-button on the front panel for storing of the recorded value into non-volatile
more than 0.5 s. Pressing the push-button memory function is not use (SGX/1 = 0), the
for less than 0.5 s gives direct access to the registers are also cleared by an auxiliary power
end of the main menu of the relay module supply failure. The setting values, the address
(Serial commu- nication address). code, the data transfer rate and the password of
the relay module are not affected by voltage
The information recorded in registers 1...9 can failures. Instructions for setting the address code
be reset using the push-buttons on the front and data transfer rate are given in the
panel, an external control signal, or a serial document "General characteris- tics of D-type
communica- relay modules".
Main menus MAIN MENU SUBMENU
and submenus
of
settings STEP 0.5
s
PROGRAM 1
s
REV. STEP 0.5 s FWD. STEP 1 s
Normal status, display
and off 0

registers

1
H.V. side
H.V. side
1 current on
current
phase L1
[x In] on phase
L1 [% In]

H.V. side
1 current on H.V. side
phase L2 0 current
[x In] on phase
L2 [% In]

H.V. side
1 current on H.V. side
phase L3 0 current
[x In] on phase
L3 [% In]

0
Diff. current on
phase L1 [x In] Diff. current on phase L1 Phase angle
d
diff. 11 between
phases L1-L2
Diff. current on [% In]
d phase L2 [x In]
Phase angle
Diff. current on phase L2 diff. 12 on phase
0 L1
1
[% In]

Diff. current on
d phase L3 [x In] Diff. current on phase L3 Phase angle
1 diff. 22 between
phases L1-L2
[% In]
0
0
L.V. side
L.V. side
2 current
current
on phase
L1 [x In] on phase
L1 [% In]

2 L.V. side L.V. side current on


current 0 phase L2 [% In]
on phase
L2 [x In]

L.V. side
0
current
2 L.V. side
current on phase
on phase L3 [% In]
L3 [x In]

B
a
si
c
s
et
ti
n
g
P
/I
n[
%
]

S
t
a
r
t
i
n
g

r
a
t
i
o

S
[
%
]

2
n
d

t
u
r
n

p
o
i
n
t

o
f

t
h
e

t
r
i
p
p
i
n
g

c
u
r
v
e

I
2
t
p
/
I
n

R E
High set stage
V. starting value
Id/In>>
STE
P
2nd harmonic
0.5 blocking threshold
Id2f/Id1f> [%]
s

5th harmonic
blocking threshold
Id5f/Id1f> [%]

CT ratio
correction
I1/In
5th harmonic
1 unblocking
threshold
Id5f/Id1f>>
[%]

M
CT ratio
A correction
I I2/In
Functional Functional Functional
2 switchgroup 3 switchgroup 4 switchgroup
SGF2 SGF3 SGF4
Functional
N switchgroup
1 SGF1 Blocking Blocking Blocking
M 2 switchgroup 3 switchgroup 4 switchgroup
E SGB2 SGB3 SGB4
N Blocking
U 1 switchgroup
SGB1 Relay matrix Relay matrix Relay matrix
F 2 switchgroup 3 switchgroup 4 switchgroup
SGR2 SGR3 SGR4

Relay matrix
switchgroup 1
SGR1 Diff. current on phase Diff. current on phase L1
W 2 L1 Diff. current on phase L1 3 at n-3 trip
D. 1
Diff. current on phase at n-1 trip at n-2 trip
S
L1 at latest (n:th) trip

T
E 1
P
Diff. current on phase L2 Diff. current on phase L2 Diff. current on phase L2
3 at n-3 trip
1 Diff. current on
phase L2 2 at
s 1 2
latest (n:th) trip at n-1 trip at n-2 trip
Diff. current on phase L3
3 at n-3 trip
Diff. current on phase L3 Diff. current on phase L3
Diff. current on 1 2
3 phase L3 at
at n-1 trip at n-2 trip
Bias current on phase L1
latest (n:th) trip

Bias current on phase


2 L1 Bias current on phase 3
L1
1 at n-3 trip
at n-1 trip
Bias current on
4 phase L1 at
latest (n:th) trip
at n-2 trip
Bias current on phase L2 Bias current on phase L2
1 at n-1 trip
Bias current on Bias current on phase L2
5 phase L2 at 2 3 at n-3 trip
latest (n:th) trip at n-2 trip
1 Bias current on phase L3

Bias current on phase L3 Bias current on phase L3


6 Bias current on at n-1 trip 2 3 at n-3 trip
phase L3 at at n-2 trip
latest (n:th) trip

Min. 2nd harmonic content Min. 2nd harmonic content Min. 2nd harmonic content
1 2
of n-1 inrush on phase L1
Min. 2nd
7 harmonic content 3
of latest inrush on of n-3 inrush on phase L1
phase L1 of n-2 inrush on phase L1
Min. 2nd harmonic content
1 of n-1 inrush on phase L2
Min. 2nd harmonic content
Min. 2nd 2 Min. 2nd harmonic content 3 of n-3 inrush on phase L2
8 harmonic content Min. 2nd harmonic content of n-2 inrush on phase L2
of latest inrush on 1 of n-1 inrush on phase L3
phase L2
Min. 2nd harmonic content
2 Min. 2nd harmonic content 3 of n-3 inrush on phase L3
of n-2 inrush on phase L3
Min. 2nd
9 harmonic content
of latest inrush on
phase L3

Status of
0 external relay
blocking / 0 IRF Id > Id >> Id2f> BS1 BS2 BS3 BS4 BS5
control signals 000

Relay unit Communication rate Loss of bus traffic time


A identification 1 Password for altering
address for counter 0...255 s settings
communication 2 3
setting (kBd)

Fig. 11. Main menus and submenus for settings and registers of differential relay
module
SPCD 3D53.
The procedure for entering a "General characteristics of D-
submenu or a setting mode and type SPC relay modules.
for configuring the module is Below a simplified instruction.
described in detail in the manual
34 SPC 3 ENG

Desirde step or function

One step forward in main or submenu


Rapid browse forward in main menu
One step backwards in main or submenu
Entering a submenu from the main menu

Entering or quitting a setting mode


Increasing a value in the setting mode
Moving the cursor in the setting mode
Storing a setting value in the setting mode

Resetting of memorized values

Resetting of latched output relays

Phase angle diff. 11


2 between phases L2-L3
angle
3 diff.
P 11
h betwe
a en
s phase
e s L3-
L1

Phase angle diff. 12


2 Phase
3 on phase L2 angle
diff.
12 on
phase
L3

Phase angle diff. 22


2 Phase
3 angle
diff.
between phases L2-L3 22
betwe
en
phase
s L3-
L1

Functional
5 switchgroup Functional Functional
SGF5 6 switchgroup 7 switchgroup 8 Function
SGF6 SGF7 al
switchg
roup
SGF8

Functional
9 switchgrou Functional
p SGF9 0 switchgroup II Functiona
SGF10 l
switchgr
oup
SGF11

Blocking
5 switchgroup Blocking Blocking Blocking
SGB5 6 switchgroup 7 switchgroup 8 switchgr
SGB6 SGB7 oup
SGB8

Relay matrix
5 Relay matrix Relay matrix Relay
6 switchgroup 7 switchgroup 8 matrix
switchgroup SGR5 SGR7 switchg
SGR6 roup
SGR8

Diff. current on
4 phase L1 at n-4
trip

4 Diff
.
cur
ren
t
on
ph
as
e
L2
at
n-4
trip

4 Diff
.
cur
ren
t
on
ph
as
e
L3
at
n-4
trip

Bia
4
s
curr
ent
on
pha
se
L1
at
n-4
trip

Bia
4
s
curr
ent
on
pha
se
L2
at
n-4
trip

Bia
4
s
curr
ent
on
pha
se
L3
at
n-4
trip

Min.
2nd
harm
onic
conte
4 nt
of n-
4 inrush
on phase
L1

Min.
4 2nd
har
moni
c
cont
ent
of n-
4
inrus
h on
phas
e L2
Min.
4 2nd
har
moni
c
cont
ent
of n-
4
inrus
h on
phas
e L3

Selection of main vs
4 second settings 5 Nominal frequency Nominal frequency
Switchgroup SGX
6 7
setting, Hz -part setting, mHz -part

Testing of In the test mode, entered from the supervision output is tested. The LEDs in
output relays submenu of register 0, it is possible to front of the settings show the output
activate the output signals of the relay one signals to be activated at the moment.
by one. The desired output signal is selected by
pressing PROGRAM for about one
When the PROGRAM push-button is second.
pressed for about five seconds the three
digits to the right start flashing as an The setting LEDs on the front panel and
indication of the relay module being in their respective output signals are as
the test mode. Initially, the self- follows:

No LED Self-supervision IRF


Setting P/In (%) Operation of stabilized stage 3
I> Setting S (%) Operation of instantaneous
stage 3 I>> Setting I2tp/In Internal blocking
Idf2/Id1f> or Id5f/Id1f> Setting Id/In>>
External control signal BS1
Setting Id2f/Id1f> (%) External control signal BS2
Setting Id5f/Id1f> (%) External control signal BS3
Setting I1/In External control signal BS4
Setting I2/In External control signal BS5

Pressing the push-buttons STEP and When the push-button STEP is being
PRO- GRAM simultaneously activates pressed in the test mode, the self-
the selected output signal, which supervision output relay operates in about
remains active as long as the push- 1 second and remains oper- ated until the
buttons are being pressed. The effect on push-button is reset. Return
the functions of the output relays to the main menu is possible at any stage
depends on the settings of the of the test sequence by pressing the
switchgroups SGR1...SGR8. PROGRAM push- button for about five
seconds.

The signals are selected in the sequence


illus- trated in the Fig. 12.

IRF 3I > 3I >> Id2f / Id1f BS1


>

Register 0 PROGRA PROGRA P / In PROGRA S I2tp / PROGRAM Id / In PROGRA


M M M PROGRAM In 1s >> M
5 1 1 1s 1
s s s s

STEP
STEP & STEP & STEP
PROGRA PROGRA &
S M M PROG
RAM
T
E
P
&
P
R
O
G
R
A
M

BS2 BS3 BS5


BS4
Id2f /I d1f>

S STEP & STEP & STEP


T PROGRA PROGRA &
E M M PROG
P
RAM
&
P
R
O
G
R
A
M

Fig. 12. Sequence for selecting output signals during testing of the output relay control
functions.
Technical data

Stabilized differential current stage 3 I>


Basic setting P/In 5...50%
Starting ratio setting S 10...50%
Second turning point I2tp/In of characteristic curve 1.0...3.0
Harmonics blocking ratio Id2f/Id1f> 7...20%
Harmonics blocking ratio Id5f/Id1f>
10...50% Harmonics deblocking ratio Id5f/Id1f>>
10...50% Operate time (including heavy-duty output relays)
- at currents 1.5…4 x operate value < 50 ms
- at currents above 4 x operate value < 45 ms
Operation accuracy 4% of set value or 2% x In

Instantaneous differential current stage 3 I>>


Setting range Id/In>> 5...30
Operate time (including heavy-duty output relays)
- at currents in the range 1.1...2.6 x Id/In>> < 35 ms
- at currents above 2.6 x Id/In>> < 30 ms

Operation accuracy 4% of set value or 2% x In

Circuit breaker failure protection


Operate time 0.1...1.0 s

Integrated disturbance recorder


Recording length 38 cycles
Recording memory capacity 1 recording = 38 cycles
Sampling frequency 40 samples/cycle
Signals to be recorded 6 analog signals
11 digital signals
Triggering
- when the selected digital signal is activated
- when the selected digital signal resets
Length of recording preceding triggering 0...38 cycles

Note!
Operate times are valid at rated frequency 50 Hz and 60 Hz.
Serial Special codes have been specified to represent In channel 0 operation or signal activation of
communication different events such as operation and blocking one phase alone is enough to cause an event. A
parameters of protection stages, activation of control and condition for resetting, on the other hand, is
output signals, etc. These event codes can be that the operations or signal activations of all
Event codes transferred to higher-level systems over the se- phases have reset.
rial bus.
An event to be included in event reporting is
The event mask V155 is available on the chan- marked with 1. The event mask is obtained
nels 0, 1, 2 and 3 so that the event mask by adding the weighting factors of the events
0V155 is shared by all phases and the in- cluded, see the tables below.
event masks
1V155, 2V155 and 3V155 represent events on
the respective phases L1, L2 and L3.

Event mask

0V155
1V155
2V155
3V155
V156
V157
V158

Channel Code

0 E1
0 E2
0 E3
0 E4
0 E5
0 E6
0 E7
0 E8
0 E9
0 E10

1...3 E1
1...3 E2
1...3 E3
1...3 E4
1...3 E5
1...3 E6
1...3 E7
1...3 E8
Channel Code

0 E11
0 E12
0 E13
0 E14
0 E15
0 E16
0 E17
0 E18
0 E19
0 E20

0 E21
0 E22
0 E23
0 E24
0 E25
0 E26
0 E27
0 E28

0 E29
0 E30
0 E31
0 E32
0 E33
0 E34
0 E35
0 E36

E50
E51
E52
E53
E54
The event codes E50...E54 and the events rep- The event codes E52...E54 are generated by the
resented by these cannot be excluded from control data communicator (e.g. SRIO
re- porting. The capacity of the event register 1000M).
is 60 events.
Data to be In addition to event codes input data (I range 1...999. The default setting of the
transferred data), output data O data), setting password is 1.
over the serial values (S data) memorized data (V data),
bus and some other data can be read from the The password is opened by giving the
module over the serial bus. The setting of serial communication parameter V160 the
parameters marked with the letter W can desired numerical value. Parameter V161
be changed over the SPA bus. is used for

When a setting value is to be changed,


either via the push-buttons on the front
panel or over the serial bus, the relay
module checks whether the given
parameter value is legal. Values outside
the permitted setting range are not
memorized by the relay module, but the
previous setting remains in memory.

Changing a setting parameter over the


serial bus requires a password in the
closing the command over the serial bus can be after that it is no longer possible to open it
password. The used to change the password. To be able over the serial bus. Then the password can
password is to change the password over the serial be given a new numeri- cal value via the
also closed by bus, it first has to be opened. The new push-buttons.
failures in the password is entered by means of
voltage parameter V161. When the push-buttons
supply. are used, the new password is written in R = data to be read from the
the place of the old one in subregister 3 module
The push- of register A. W = data to be written to the
buttons of module
the relay Should the wrong password be given 7 (P) = writing allowed through a
module or a succes- sive times, it turns into a zero, and password
Input data The parameters I1...I28 are readable parameters (R).

Measured data

Current on HV side phase L1


Current on HV side phase L2
Current on HV side phase L3
Differential current of phase L1
Differential current of phase L2
Differential current of phase L3
Current on LV side phase L1
Current on LV side phase L2
Current on LV side phase L3
Current on HV side phase L1 as a percentage of the rated current
Current on HV side phase L2 as a percentage of the rated current
Current on HV side phase L3 as a percentage of the rated current
Differential current of phase L1 as a percentage of the rated current
Differential current of phase L2 as a percentage of the rated current
Differential current of phase L3 as a percentage of the rated current
Current on LV side phase L1 as a percentage of the rated current
Current on LV side phase L2 as a percentage of the rated current
Current on LV side phase L3 as a percentage of the rated current
Status data of control signals BS1...5 and BS INT1...3

Phase difference of the currents on HV side phases


L1 and L2
Phase difference of the currents on HV side phases
L2 and L3
Phase difference of the currents on HV side phases
L3 and L1
Phase difference of HV and LV side phase currents on phase L1
Phase difference of HV and LV side phase currents on phase L2
Phase difference of HV and LV side phase currents on phase L3
Phase difference of the currents on LV side phases
L1 and L2
Phase difference of the currents on LV side phases
L2 and L3
Phase difference of the currents on LV side phases
L3 and L1

39
Output data The actual status data provide after the latest reset of the registers. When the
information about the current status of the value is 0, the signal is not activated and when
signals at the moment. The operations stored the value is 1, the signal is activated.
in the memory indicate those signal
activations which has taken place

Status data of protection stages and control signals

Protection stage/
signal

3 I>, operate signal


3 I>>, operate signal
Internal blocking signal
Id2f/Id1f> or Id5f/Id1f>
Output relay controlled
by control signal BS1
by control signal BS2
by control signal BS3
by control signal BS4
by control signal BS5
Trip signal of CBFP

Signal activations

Output signal

Output signal SS1


Output signal TS1
Output signal SS2
Output signal TS2
Output signal SS3
Output signal TS3
Output signal SS4
Output signal TS4

Enable signal for remote control of output signals

The parameters V11...V59 can be used to read (R) n-1 = the value before that, and so on. The
the latest five values stored in the registers. Event n registers are described in detail in the paragraph
= the most recent value recorded, event "Recorded information".

42 42
Value measured

Differential current on phase L1


Differential current on phase L2
Differential current on phase L3
Stabilizing current on phase L1
Stabilizing current on phase L2
Stabilizing current on phase L3
Smallest ratio Id2f/Id1f during the
latest connection inrush current
on phase L1
Smallest ratio Id2f/Id1f during the
latest connection inrush current
on phase L2
Smallest ratio Id2f/Id1f during the
latest connection inrush current
on phase L3

Stage/phase that initiated tripping

43 43
Setting values
Setting

Basic setting P/In


Starting ratio S
Second turning point of characteristic curve I2tp/In
Operate range Id/In>> of instantaneous differential current stage 3 I>> Harmonics blocking rati
CT transforming ratio correction range on power transformer LV side
Reserved

Checksum, SGF1
Checksum, SGF2
Checksum, SGF3
Checksum, SGF4
Checksum, SGF5
Checksum, SGF6
Checksum, SGF7
Checksum, SGF8
Checksum, SGF9
Checksum, SGF10
Checksum, SGF11
Checksum, SGB1
Checksum, SGB2
Checksum, SGB3
Checksum, SGB4
Checksum, SGB5
Checksum, SGB6
Checksum, SGB7
Checksum, SGB8
Checksum, SGR1
Checksum, SGR2
Checksum, SGR3
Checksum, SGR4
Checksum, SGR5
Checksum, SGR6
Checksum, SGR7
Checksum, SGR8

42
Control parameters
Data

Resetting of front panel operation indicators and latched output relay Resetting of front panel operati

Remote control of settings

Switchgroup SGX

Event masks for differential protection

Event masks for differential protection on phase L1


Event masks for differential protection on phase L2
Event masks for differential protection on phase L3

Event mask for external control signals


Event mask for output signals
Event mask for output signals

Opening of password for remote setting


Changing and closing the password for remote setting

Activation of self-supervision input


is activated and IRF LED
is lit

EEPROM formatting

Error code

Rated frequency, Hz setting Rated frequency, mHz setting Address of relay module

Data transfer rate

Programme version symbol

43 43
Data

Selection of internal signals to be used for triggering the disturbance recorder

Internal signal

3 I>

3 I>>

Id2f/Id1f blocking

Id5f/Id1f blocking

Factory setting V241

Selection of method for triggering V242 R,W 0...255


the disturbance recorder

Internal signal

3 I>

3 I>>

Id2f/Id1f blocking

Id5f/Id1f blocking

Factory setting V242

Selection of control signals to be used V243 R,W 0...255


for triggering the disturbance recorder

Control signal

BS1

BS2

BS3

BS4

BS5

BS INT1

BS INT2

BS INT3

Factory setting V243


Data

Selection of method for triggering the disturbance recorder

Internal signal

BS1

BS2

BS3

BS4

BS5

BS INT1

BS INT2

BS INT3

Factory setting V244

Length of recording following


disturbance recorder triggering, in cycles
Status/command register of recording
i.e. the memory is empty
1 = recording triggered and
recording memory is full

Reading of event register

Re-reading of event register

Type designation of relay module


Reading of module status data

Resetting of module status data


Time reading or setting
Date and time reading and setting

The event register can be read by the L com- 1000M reads the event data and forwards the
mand only once. Should a fault occur, say, in information to an output device. Under
the data transfer, the B command can be used normal conditions the event register of the relay
to re- read the contents of the register. module is empty. The control data
When re- quired, the B command can be communicator also resets abnormal status
repeated. In general, the control data data, so this data is nor- mally zero.
communicator SRIO
Fault codes
1 Auxiliary voltage interrupted
4 Faulty trip relay path, TS1, or missing output relay card
5 Faulty trip relay path, TS2, or missing output relay card
6 Faulty trip relay path, TS3, or missing output relay card
7 Faulty trip relay path, TS4, or missing output relay card
20 The module has restarted, although no fault was detected by the self-
supervision system.
21 The module has restarted more than 10 times, although no fault was detected by
the self-supervision system.
23 Error during start-up of DSP
24 DSP halted due to unknown error
29 DSP code memory area checksum
30 Faulty program memory (EPROM)
49 DSP internal RAM faulty
50 MCU internal RAM faulty
51 Parameter memory (EEPROM) block 1 faulty
52 Parameter memory (EEPROM) block 2 faulty
53 Parameter memory (EEPROM) block 1 and block 2 faulty
54 Parameter memory (EEPROM) block 1 and block 2 faulty, different checksums
55 Faulty parameter area in RAM
56 Parameter memory (EEPROM) key fault. Parameter memory not formatted.
57 Gain/channel correction value checksum
58 Active setting bank checksum
59 DSP external RAM faulty
60 MCU external RAM faulty
100 DSP overloaded
195 The analog supply voltage measured is too low (rated voltage -12 V)
196 The analog supply voltage measured is too low (rated voltage +12 V)
203 The analog supply voltage measured is too high (rated voltage -12 V)
204 The analog supply voltage measured is too high (rated voltage +12 V)
252 Input filter faulty
253 A/D converter faulty
254 DSP does not interrupt
SPCD 2D55
Earth-fault relay module
User´s manual and Technical description

I 01 >
I 02 >
I1 I2
I 01 I d1 I d2 I 02 IRF

P 1 /I n [ % ]
RESET
t 01 > [ s ]
STEP
P 2 /I n [ % ]
t 02 > [ s ]
I 01 / I n
I 01 / I 1 [%]
I 02 / I n
I 02 / I 2 [ % ]

I 2f / I 1f (I 01 ) >
[ %]

I 2f / I 1f (I 02 ) >
[ %]

I 1 /I n
I 2 /I n PROGRAM

SGF

SGB

SGR

TRIP
0029A

SPCD 2D55
1MRS 750098-MUM EN
SPCD 2D55
Issued 1996-10-14
Modified 2004-04-27
Version B (replaces 34 SPCD 3 EN1)
Earth-fault relay module
Checked PS
Approved MÖ

Data subject to change without notice

Contents Features
...................................................................................................................... .... 3
Description of function
.................................................................................................. 3
Rated frequency
.....................................................................................................
.... 4
Stabilized differential current principle
...................................................................... 4
Residual overcurrent principle and neutral current principle
..................................... 5
High-impedance principle
......................................................................................... 5
Blocking based on the second harmonic of the neutral
current .................................. 6
Protection stages
.....................................................................................................
... 6
External control
signals ............................................................................................
.. 7
Intermodular signals
.................................................................................................. 7
Output signals
.....................................................................................................
...... 7
Circuit-breaker failure protection
.............................................................................. 7
Second settings
.....................................................................................................
..... 7
Resetting .......................................................................................
............................ 8
Integrated disturbance recorder
................................................................................. 8
Block schematic diagram
................................................................................................ 9
Symbols and signal abbreviations used
.......................................................................... 11
Front panel
........................................................................................................
........... 12
Operation indicators
.....................................................................................................
13
Settings ............................................................................................
............................. 15
Configuration switches (modified 2004-04)
.................................................................. 16
Measured data
.........................................................................................................
..... 25
4 4
Recorded values
.........................................................................................................
... 26
Main menus and submenus for settings and
registers .................................................... 28
Testing of output relays
................................................................................................ 30
Technical data
.........................................................................................................
..... 31
Serial communication parameters
................................................................................. 33
Event codes
.....................................................................................................
........ 33
Remote transfer
data ...............................................................................................
. 35
Fault codes of self-supervision system
........................................................................... 42
Features Earth-fault relay module for the earth-fault pro- Display of measured, set and recorded
tection of two-winding power transformers values

Provides protection for both HV and LV Writing and reading of setting values via
side windings local display and front panel push-buttons,
a PC with configuration software, or from
The earth-fault protection can be higher system levels over the serial port and
implemented by four principles: the high- optical fibres.
impedance princi- ple, the numerical stabilized
differential current principle, the residual Five programmable external control inputs
overcurrent principle, or the neutral
overcurrent principle Output relay matrix allowing the operate and
control signals to be linked to the desired
The earth-fault protection principles to be output relay
used on the HV side and the LV side are
independent of each other Integrated circuit breaker failure protection

The relay module is entirely numerical - the Integrated disturbance recorder capable of re-
fundamental component of the currents are cording six phase currents, two neutral
used for calculating the residual current of the currents, the internal start and blocking
phase currents, the neutral current and the signals, and the control signals linked to the
differential and stabilizing currents. The DC relay
component and the harmonics of the currents
are digitally filtered. High immunity to electrical and electromag-
netic interference allows the relay to be used
Separately adjustable basic setting and in severe environments
operate time for HV and LV side
Dynamic measuring
High immunity to electrical and electromag- functions
netic interference allows the relay to be used
in severe environments High availability - the integrated self-supervi-
sion system monitors the operation of the
Stabilized against transformer inrush electronics and the software and gives an
currents and faults outside the protected area alarm signal in the event of a fault.

Blocking based on the ratio between the


second harmonic and the fundamental
frequency com- ponent of the neutral current
prevents opera- tion at transformer
connection inrush currents

Description of function
4 4
The earth-fault (low-impedance type protection) The stabilized differential current principle, the
relay measures the - the residual overcurrent residual overcurrent principle and the
HV and LV side principle neutral overcurrent principle are based on
phase currents - the neutral overcurrent the funda- mental frequency components of
and neutral principle the currents measured. The fundamental
currents of the - the high-impedance principle frequency compo- nents are digitally filtered
transformer. Four in the relay module. The high-impedance
alternative The protection principle to be used depends principle is based on the instantaneous peak
principles can be on the connection of the windings of the values of the measured cur- rent.
used for power transformer and on the requirements
implementing the for the earth-fault protection. The switches SGF1/1...8 are used to select
HV side and LV the desired protection principle. The
side earth-fault protection stages of the HV side and the LV
protection of the side operate quite independently of each
transformer to be other, so the pro- tection principle used on the
protected: HV side can be the same as that used on the
LV side, or another. At the same time,
- the stabilized however, one protection princi- ple only can
differential be used on one or the other side of the
current principle transformer.
Rated frequency The earth-fault relay module can be used in The frequency is selected with the push-
the frequency range 16 2/3....60 Hz. The rated buttons on the front panel, via subregister 5
fre- quency setting is accurate to within 1 and 6 in register A, or over the serial bus, in
mHz. Two settings are available, i.e. Hz and which case the parameters V180 and V181
mHz, which are separately set from 16.667 are used.
Hz up to 60 Hz.

Stabilized The numerical stabilized differential current The stabilizing current Ib used with the
differential principle is selected for the earth-fault stabiliz- ing differential current principle is
current protec- tion on the HV side and on the LV calculated as an average of the phase currents
principle side with the settings SGF1/1 = 1 and on the side of the winding to be protected:
SGF1/5 = 1, respec- tively. No external
stabilizing resistor or non- linear resistor is IL1 + IL2 + IL3
required. Ib =
(2)
Operation according to the differential current 3
principle is based on comparing the amplitude The basic settings P1/In and P2/In are used
and phase difference between the sum of the for setting the characteristic of the stabilized
fundamental frequency zero-sequence currents differ- ential current principle. The
of the phase currents ( I) and the differential current value P1/In or P2/In
fundamental frequency component of the required for tripping is constant at the
neutral current (I0) flowing in the conductor stabilizing current values Ib/In =
between the trans- former neutral point and 0...1. When the stabilizing current is higher
earth. The differential current Id is calculated than the rated current, the slope of the
as the absolute value of the difference between operation characteristic is constantly 50% as
the residual current (i.e. the sum of the zero- shown in Fig.
sequence currents in the phases) and the 1. That means that the relationship between
neutral current. the change in the directional differential
current Idcos and the change in the
Id = I - I0 (1) stabilizing cur- rent Ib is constant.
An earth fault occurring in the protected
area (that is, between the phase CTs and the Id cos
neutral connection CT) will cause differential In
current. In addition, the direction of the
residual current and the neutral current and 1.5
Ib
also the ratio of the neutral current and the 1.0 In
residual current (I0/ I) on the side to be P / In
protected have to be considered in order to 0.5
maintain selectivity. Ib
0.0

5 5
In
During an earth fault in the protected area the 0.0 1.0 2.0 3.0

currents 1 and I0 are directed towards the


protected area. The calculation of the direc- Fig. 1. Operation characteristic for the stabi-
tional differential current Idcos is based on the lized differential current principle of the
differential current Id and the angle between the earth- fault relay module SPCD 2D55
residual current and the neutral current. cos
is specified to be 1, when the phase difference
Curve
of the residual current and the neutral Id cos

current is In
180 , that is, when the currents are in
opposite direction at earth faults within the 1.5

protected area. cos is specified to be 0, 1.0 1


when the phase difference between the
residual current and the neutral current is less
than 90 in situations with
no earth fault in the protected area. Thus trip- 0.5 2

ping is possible when the phase difference 0.0


Ib

be- tween the residual current and the neutral 0.0 1.0 2.0 3.0 In

cur- rent is above 90 .

Fig. 2. Setting range of the operation


character- istic for the stabilized differential
current prin- ciple of the earth-fault relay
module SPCD
2D55
To be able to calculate the directional ting I01/ I1 on the HV side and the
differen- tial current Idcos the amplitude of
setting
the funda- mental frequency component of I02/ I2 on the LV side
both the re- sidual current of the phase - the directional differential current exceeds
currents and the neutral current has to be the
above 4% of the rated current. Should one value of the operation characteristic (the
condition only be fulfilled, cos = 1. phase difference between the residual
current of the phase currents and the
The relay module has a separate setting that neutral current has to be greater than 90 )
takes into account the distribution of the - the blocking based on the second harmonic
earth- fault current between the star-point of of the neutral current I01 or I02 of the
the trans- former and the network on the side concerned side does not prevent starting.
to be pro- tected. The ratio of the neutral
current and the residual current of the phase Should the CT secondary currents deviate
currents must be greater than the setting I01/ from the rated current of the protected
I1 on the HV side and the setting I02/ I2 on transformer at rated load, the relay module
the LV side to allow the protection stage on allows the transfor- mation ratios of the
the concerned side to start. The setting range neutral connection CTs and the phase CTs to
of the ratio is 0...20%. When the setting I01/ be corrected. The transforma- tion ratio
I1 (or I02/ I2) is more than 0%, the corrections can be made both on the HV and
minimum value of the neutral current of LV side by selecting a value for the front
that side required for tripping is panel settings I01/In and I02/In, and I1/In and
2% x In. I2/In in the range 0.40...1.50 x In. The
default setting is 1.00.
So, the protection stage starts provided the
following conditions are fulfilled at the The influence of the connection of the
same time on the side to be protected: phase current transformers and the neutral
- the ratio of the neutral current and the connec- tion CT on the operation of the
residual current of the phase currents stabilized differential current principle is
exceeds the set- determined by the setting of the switches
SGF2/1...2.

Residual overcurrent Should the transformer have no star point, the earth- fault. The sum of the zero-sequence
principle and neutral star point be unearthed or no neutral current currents in the phases is calculated inside the
current principle be available, the residual overcurrent principle relay module on the basis of the phase currents
can be employed for the protection against linked to the relay. The overcurrent principle is
5 5
used on the HV side, The residual current of the phase currents the neutral current can be used in
when SGF1/2 = 1, and can also be formed via an external combination with these types of protection.
on the LV side, when connection by connecting the neutral
SGF1/6 = 1. The terminals of the windings of the relay’s phase
protection stage current matching transform- ers to the 5 A
starts when the or 1 A terminal of the neutral current
amplitude of the matching transformer I01 or I02. Natu- rally,
fundamental fre- it is also possible to connect the neutral
quency component of current of the neutral connection current
the residual current trans- former to the terminals, and use the
ex- ceeds the basic neutral overcurrent principle. When external
setting P1/In or P2/In. summing of the phase currents or the
When the residual neutral current principle is used on the HV
current I1 or I2 is side, the switch SGF1/3 has to be in
calculated from the position 1.When external summing of the
phase currents inside phase currents or the neutral current
the relay module the principle is used on the LV side, the switch
blocking based on the SGF1/7 has to be in position 1. The
second harmonic of blocking based on the second harmonic of
the neutral current
cannot be used.

High-impedance High-impedance type protection can be SGF1/8 = 1. When the high-impedance


principle applied to a star-connected winding. This princi- ple is used the protection stage start
type of pro- tection employs four CTs, i.e. when the instantaneous peak value of the
three phase CTs and one neutral connection neutral current exceeds the basic setting P1/In
CT. To be able to use the high-impedance on the HV side or the basic setting P2/In on
principle an external stabilizing resistor and the LV side. The blocking based on the
often also a non-linear voltage limiting second harmonic of the neutral current
resistor are required. The high- impedance cannot be used in combination with the high-
principle can be used on the HV side, if impedance principle.
SGF1/4 = 1, and on the LV side, if
Blocking based Blocking of the starting at power Start inhibition based on the second
on the second transformer connection inrush currents is harmonic can be used in combination with
harmonic of the based on the ratio between the second the switch settings SGF1/1 = 1, SGF1/3 = 1,
neutral current harmonic and the funda- mental frequency SGF1/5 = 1, SGF1/7 = 1. The blocking is
component calculated from the neutral enabled by SGF2/3 on the HV side and switch
current I01 or I02. The start of the protection SGF2/4 on the LV side. The HV side
stage is blocked, if blocking is ena- bled and blocking does not affect the LV side
if the ratio of the second harmonic and the protection stage and the LV side blocking
fundamental frequency component exceeds the does not affect the LV side protection stage.
set blocking limit I2f/I1f (I01)> or I2f/I1f
(I02)>. The HV and LV side earth-fault protection
principles and blocking arrangement are se-
lected in accordance with the following tables:

HV side protection principle I01>

No protection Stab. diff. current principle


Residual overcurrent principle
Neutral current principle
High-impedance principle

5 5
LV side protection principle I02>
No protection Stab. diff. current principle
Residual overcurrent principle
Neutral current principle
High-impedance principle

Protection stages Switchgroup SGR1 is used to link the start eration is not inhibited by an external control
signals of the HV side protection stage I01> signal or an intermodular blocking signal.
to the specified output relays, provided starting
is not inhibited by a blocking function based In the same way the LV side protection stage
on the ratio of the second harmonic and the I02> delivers an operate signal to the output
funda- mental frequency component of the relays specified by switchgroup SGR5,
neutral current. Correspondingly, provided
switchgroup SGR4 is used to link the start operation is not
signals of the LV side protection stage I02> inhibited.
to the specified relays.
The blocking of the HV side protection
The operate time can be separately set for the stage, I2f/I1f (I01)>, is routed to the output
HV and LV side in the setting ranges t01> relays specified by switchgroup SGR3,
= provided the HV side start conditions are
0.03...100 s and t02> = 0.03...100 s, respec- fulfilled. In the same way the blocking of the
tively. When the operate time t01> of the HV LV side protection stage, I2f/I1f (I02)>, is
side protection stage I01> has elapsed, the routed to the output relays specified by
stage switchgroup SGR6, provided the LV side
delivers an operate signal to the output relays start conditions are fulfilled.
specified by switchgroup SGR2, provided
op-
External control Five external control signals BS1...BS5 are
signals avail- able to the earth-fault relay module The switchgroup SGF4 allows a latching
SPCD 2D55. The control signals can be used feature to be selected for the output signals
to control the output signals or block the SS1...SS4 and TS1...TS4. When this function
operation of the module (protection stages). has been selected, the output signal remains
In addition the con- trol signals BS1, BS2 and active, even though the signal that caused
BS3 can be used for the operation

Intermodular signals
The signals BS INT1, BS INT2 and BS INT3
are intermodular blocking signals which can
be used to block the operation of a relay
module fitted in another card location of
the same protection relay. An intermodular
blocking sig- nal is activated when the
corresponding block- ing signal of one relay
module is activated. The blocking signals BS
INT1, BS INT2 and BS INT3 are not
capable of controlling the output relays.
Switchgroup SGB1 is used for selecting
Output signals

The switchgroups SGR1...SGR11 can be


used to link the start and operate signals
of the protection stages, the internal blocking
signals and the external control signals
BS1...BS5 to the desired output relays
SS1...SS4 or TS...TS4.
5 5
switching between
main and second
settings and for resets. The means of resetting the output
resetting the the logic active state of the external relays are shown in the table in paragraph
operation indicator, control signals and the intermodular "Resetting".
output relays, blocking signals. So, the input can be
registers and activated when energized or when non- The operation of the TRIP operation
recording memory. energized. indicator on the front panel can be
The switches of the configured to be initiated by the activation of
SGB switchgroups The signals AR1, AR2 and AR3 can be used any TS signal. The operation indicator
are used for to trigger the disturbance recorder SPCR remains lit when the signal resets. The
configuring the 8C27 fitted in one of the card locations of switchgroup SGF5 is used for the
external control the relay. These signals cannot be used to programming. The means of resetting are
signals. control the output relays. shown in the table in paragraph "Resetting".

Circuit-breaker The relay module is provided with circuit- TS1 of the circuit-breaker failure protection
failure protection breaker failure protection (CBFP), which can be used to operate the circuit breaker in
provides an operate signal TS1 0.1...1 s front of the circuit breaker of the feeder of
after the operate signal TS2, TS3 or TS4, the object to be protected. The switches
unless the fault has disappeared during this SGF3/1...3 are used to enable the circuit-
time. In the range breaker failure protection and the switches
100...440 ms the operate time can be adjusted SGF3/4...8 are used for setting the operate
in steps of 20 ms and in the range 440....1000 time of the CBFP.
ms in steps of 40 ms. The heavy-duty output
relay

Second settings Two different setting values are available for the The S parameters allow the main setting
relay: main setting values and second values and second setting values to be read and
setting values. Switching between these two set over the serial bus. The push-buttons on
types of setting value can be done in three the front panel can be used for reading and
ways as follows: setting actual setting values only.

1) Over the serial bus, using command N.B. If external control signals have been
V150 used for selecting the main or second settings,
2) By means of an external control signal: it is not possible to switch between main
BS1, BS2 or BS3 settings and second settings via the serial bus
3) Via the push-buttons on the front panel of or the push- buttons on the front panel.
the relay module and subregister 4 of
register A. Selecting the value 0 for the
subregister brings the main settings into
effect, whereas the value 1 activates the
second settings.
Resetting The operation indicators on the front panel can be reset in three ways: with the push-
of the relay module, the operation codes on buttons on the front panel, via an external
the display, latched output relays, and the control signal or a serial communication
registers and the recording memory of the parameter as shown in the table below.
relay module

Means of resetting

RESET
PROGRAM
RESET & PROGRAM
External control signal
BS1, BS2 or BS3, when
SGB5/1...3 = 1
SGB6/1...3 = 1

5 5
SGB7/1...3 = 1
Parameter V101
Parameter V102

Integrated The integrated disturbance recorder records the recorder. Parameter V241 specifies the internal
disturbance waveforms of the currents to be measured, the signals to be used for triggering and
recorder digital control inputs of the module and the parameter V242 specifies whether the
internal signals. The module has eight recording is to be started by the rising or
analog and 12 digital channels. The falling edge of the signal specified by
memory has a capacity of one record the parameter V241. Parameter V243 defines the
length of which is 30 cycles. The recording control signals to be used for trigger- ing, and
has to be downloaded before a new recording parameter V244 specifies whether the rising
sequence can be started. The memory is also or falling edge of the control signal is to start
emptied when the values recorded by the the recording sequence.
module are reset. The sampling frequency of
the disturbance recorder is 40 times the Parameter V245 is used for setting the length
rated frequency of the module, which means of the recording. The number of the
that the sampling frequency at 50 Hz is recording cycles following triggering is equal
2000 Hz. to the value of parameter V245. The total
recording length is fixed and always about 30
The recording can be triggered by the internal cycles.
signals of the relay module or the control
signals linked to the module. Internal When the serial communication parameter
signals to be recorded and available for V246 = 0, the disturbance recorder has not
triggering are the start signals of the HV side been triggered, i.e. the recording memory is
and LV side earth-fault protection, and the empty. When V246 = 1, the disturbance
HV and LV side blocking signals. The recorder has been triggered and the memory
control signals linked to the module are the is full. The recording memory is emptied by
signals BS1...5 and BS INT1...3. Re- giving param- eter V246 the value 0. The
cording can be triggered by the rising or memory has to be empty before the
falling edge of any (one or several) of these disturbance recorder is able to start a new
signals. Triggering at rising edge means that recording sequence. A memorized recording
the record- ing sequence starts when the signal is indicated by the letter "d" to the right of
is activated. Correspondingly, triggering by the display, when no measured, set or
falling edge means that the recording recorded value is displayed.
sequence starts when the active signal resets.
The recorded data of the integrated
The serial communication parameters V241... disturbance recorder are downloaded, for
V245 are used for configuring the instance, with the help of a PC program and
disturbance the serial communi- cation parameter V247.

5 5
Bloc
k
sche
mati
c
diag
ram

Fig.
3. I1 / I n
I b1 SGF1/1
I 01 > start t

Block I L1 I d1 = I 1 - I 01
P1 / I n
01 >

sche 1f
+
I 01 > trip
SGR2/2=1
matic I
L2 I1
- * & 1 &
1
SGR5/2=1 TS1
diagra I L3 I 01/ I 1
cos
m for
earth-
fault I 01/ I n SGF2/1 +180 1f
SGF1/2
SGR2/4=1

relay I 01
SGR5/4=1 1 TS2
modu
le SGF1/3

SPC
D SGF1/4
2D55 2f I 2f / I 1f > (I 01) I
02
> start SGR1/5=1 SS3
with SGF2/3 SGR4/5=1 1
switc 1f
I b2 SGF1/5
hgrou I2 / I n

p I'L1 1f
P2 / I t 02 >
SGR2/7=1
defau n

lt Id2 = I 2 - I 02
I'L2 & I 02 > trip SS4
setti I2
+
* 1 &
SGR5/7=1
1
I'L3
ngs - I02 / I 2

cos
SGF2/2 SGF1/6
SGF8/1=1
I 02/ I n +180
1f SGF8/2=1
I 02 1 AR3
SGF8/4=1
SGF1/7
SGF8/5=1

SGF1/8 SGF5/1=1

2f I 2f / I 1f > SGF5/2=1 1
SGF2/4 (I 02)

RESET TRIP

SPCD 2D55
9
I1 / I n 1f I 01 > start SGR1/
I b1 x
SGF1/1
P1 / I t 01 > RESET +
Id1 = I 1 - I 01 SGF4/
I 1
PROGRAM
L1 n
I L2 1f
I1

I 01 > trip
I L3 + & SGR2/ x=1

Fi * 1 &
- x 1 SS1
RESET +
PROGRAM

g.
I 01/ I 1
cos
SGF4/2
I01 / I n SGF2/1 +180 1f SGF1/2
t CBFP 1
4. I
01
x=2
1
SGF5/
1 TS1

Bl SGF1/
3 SGF4/3
RESET +
PROGRAM SGF3/4...8

oc SGF2/3 I 2f / I 1f > 2nd harmonic x = 3SGF3/ 1 RESET + SS2


k
SGF1/4 PROGRAM
2f (I 01) blocking (HV 1
side) SGR3/

sc & SGF4/4
x SGF5/
I 2 / In I b2 2

he 1f I 02 > start x=4 1 TS2


SGF1/5
P2 / I SGR4/ RESET +
t 02 > PROGRAM

ma I'L1 n x
SGF4/5

tic I'L2 I2
I d2 = I 2 - I 02
* I 02 > trip
x = 5SGF3/ 1 SS3
dia + SGR5/ 2
& 1 &
I' - x RESET +
L3 I 02 / I 2 PROGRAM
SGF4/6
gra SGF1/6 cos
TS3
m I02 / I n
SGF2/2
+180
x=6 1 SGF5/
3

for I
02
1f
SGF1/
7
SGF4/7 RESET +
PROGRAM

ear x=7
SGF3/
1 SS4

th- SGF1/8
3
SGF4/8 RESET +
PROGRAM

fau SGF2/4
I 2f / I 1f >
(I 02 ) 2nd harmonic
blocking (LV
lt SGB1/ 1
x=1
2f
&
side) SGR6/
x
x=8 1
SGF5/
TS4

rel BS1
1 4
RESE

ay SGB1/
1
x=2
SGB2/x T
TRIP

m BS2
2 SGB3/x

od SGB4/x (x =
1...3)
Settings (main /
second)

ule SGB1/3
SGB5/x (x =
I 01 > start x=1 SGF6/ AR1
SP x
1...3)
Reset trip I 01 > trip SGF7/
C BS3 1 indicator x=2 x AR2
x=3
SGB6/x (x = 1...3) SGF8/
Reset trip indicator and 2nd harm. bl. (HV) x= x AR3

D output relays
3

2
SGB1/4 I 02 > start SGB8/1
SGB7/x (x = 1...3) x=4
Reset trip indicator, output 1
relays
D BS4 1
x=4 and registers (complete relay
reset)
5
I 02 > trip x= SGF9/
x BS INT1

55 SGB1/5
BS1 SGR7/x
2nd harm. bl. x=6 SGB8/2
1
BS2 SGR8/x (LV) BS4 x=7
1 x=8 SGF10/
x
BS5 SGB1/ x=5 BS5 SGB8/3 BS INT2
BS3 SGR9/x
6 1
BS4 SGR10/x
BS5 SGR11/x
1 SGF11/
BS INT1 x=6 BS INT3
x

SGB1/ 1
x=7
7

BS INT2
10

SGB1/ 1
x=8
8

BS INT3 SPCD 2D55


Symbols and IL1, IL2, IL3 Phase currents measured on HV
signal side I'L1, I'L2, I'L3 Phase currents measured on LV
abbreviations side I01 HV side neutral current
used I02 LV side neutral current
In Rated current
Summing of phase currents
1f Digital filtering of fundamental frequency component
I1 Residual current of HV side phase currents
I2 Residual current of LV side phase currents
Id1 Differential current calculated as SI1 - I01
Id2 Differential current calculated as SI2 - I02
cos Cosine of the phase angle between the residual current of the phase
currents and neutral current
Ib Stabilizing current used with the numerical differential current principle
2f Digital filtering of the second harmonic component
I2f Amplitude of the second harmonic of the neutral current
I1f Amplitude of the fundamental frequency component of the neutral current
I01> HV side protection stage
I02> LV side protection stage
SGF1...SGF11 Switchgroups for configuring the functions
SGB1...SGB8 Switchgroups for configuring external control and blocking signals
SGR1...SGR11 Output relay matrix switchgroups
BS1...BS5 External control inputs
SS1...SS4 Output signals
TS1...TS4 Output signals to heavy-duty output relays
BS INT1...BS INT3 Intermodular blocking and control signals
AR1...AR3 Intermodular control signals
tCBFP Adjustable operate time for circuit-breaker failure protection

Note! wired to the terminals are shown in the


All input and output signals of the module are diagram illustrating the flow of signals between
not necessarily wired to the terminals of every the plug- in modules of the relay assembly.
relay assembly using this module. The signals

Front panel
I 01 >
I 02 >
I1 I2

I 01 I d1 I d2 I 02 IRF
Current measurement indicators

Indicator for HV side basic setting and operate time P 1 /I n [ % ] RESET


t 01 > [ s ] STEP
Indicator for LV side basic setting and operate time P 2 /I n [ % ]
t 02 > [ s ]
Indicator for setting the ratio correction of transformer HV side neutral connection
I 01 / I n
CT and the minimum ratio between neutral current and the residual current of the
phase currents I 01 / I 1 [ %]
Indicator for setting the ratio correction of transformer LV side neutral connection I 02 / I n
CT and the minimum ratio between neutral current and the residual current of the I 02 / I 2 [ %]
phase currents
I 2f / I 1f (I 01 ) > [ %]
Indicator for setting the ratio of the second harmonic and the fundamental
frequency component of the HV side neutral current
I 2f / I 1f (I 02 ) > [ %]
Indicator for setting the ratio of the second harmonic and the fundamental
frequency component of the LV side neutral current
I 1 /I n
Indicator for transformation ratio correction of transformer HV side phase CTs
Indicator for transformation ratio correction of transformer LV side phase CTs I 2 /I n
SGF PROGRAM
Indicator for checksums of switchgroups SGF1...11
SGB
Indicator for checksums of switchgroups SGB1...8
SGR
Indicator for checksums of switchgroups SGR1...11

59 59
TRIP

0029A
SPCD 2D55
I 01 > Device symbol
I 02 >
I1 I2
I 01 I d1 I d2 I 02 IRF IRF indicator

Display
P 1 /I n [ % ]
t > [s ] RESET
01
STEP
P 2 /I n [ % ] Display step/reset push-button
t 02 > [ s ]
I 01 / I n
I 01 / I 1 [ % ]
I 02 / I n
I 02 / I 2 [ % ]

I 2f / I 1f (I 01 ) > [ %]

I 2f / I 1f (I 02 ) > [ %]

I 1 /I n

I 2 /I n PROGRAM

SGF Setting switch


SGB

SGR
Operation indicator
TRIP
Type designation of relay module
0029A

SPCD 2D55

Fig. 5. Front panel for earth-fault relay module SPCD 2D55


Operation The operation indicators of the earth-fault Activation of the external control signals BS1...
indicators relay module are the red operation code of the BS5 is indicated on the display by the respective
display and the TRIP indicator that red operation code 7, 8, 9, 0 or II. The
indicates opera- tion. operation code remains lit as long as the
control signal is active. If the control signal
When the HV side protection stage I01> was programmed (switchgroups SGB4...7) to
starts, the red operation code 1 is lit on the be used for switch- ing main settings into
display. Operation of the stage is indicated by second settings or vice versa, or to reset the
the code number 2. Start and operation of operation indicators, latched
the LV side protection stage I02> are
indicated by the red operation codes 4 and 5
respectively. The codes indicating start and
operation remain lit until reset. Should the
circuit-breaker failure protec- tion have
operated, the operation indicator A remains
lit until the operation indicators are reset.

When an operate signal is issued by a HV or


LV side protection stage of the earth-fault
relay module the TRIP indicator is lit,
provided the concerned operate signal is
linked to a heavy- duty output relay TS1,
TS2, TS3 or TS4 via a switch of switchgroup
SGR2 or SGR5. Should the red operation
code 2 or 5 be indicated on the display the
TRIP indicator still being dark, the operate
signal is not linked to one of the heavy- duty
output relays.

60 60
output signals can be linked to operate as trip or signal of the control signal has been set to
relays, alarm signals by routing the concerned light the indicator (switchgroup SGF5).
registers or signal to the desired output relay
recording (switchgroups SGR7...SGR11). Operation Activation of the blocking based on the ratio
memory, ini- tiated by an external control signal is between the amplitudes of the second
the indicated on the display by the operation harmonic and the fundamental frequency
activation code of the respective control signal. The component of the HV side neutral current,
of the operation codes remain lit until reset. I2f/I1f (I01)>, is indicated by the operation
control code 3, whereas the activation of the LV side
signal is not When relay operation is initiated by an blocking I2f/I1f(I02)> is indicated by the
indi- cated external control signal, the TRIP indicator is operation code 6.
on the automati- cally lit, if the output relay selected
display. is one of the heavy-duty output relays The table below describes the red operation
TS1...TS4 configured to be controlled by codes shown on the display to indicate start,
The stage I01> or stage I02>. Otherwise the operation, blocking, an activated control
external TRIP indicator will be lit only if the output signal or operation of the circuit-breaker
control failure pro- tection.

Code

1
2
3
4
5
6
7
8
9
0
II A
Yellow d

When a protection stage or a control signal same time the relay module delivers a control
resets, the TRIP indicator and the red signal to the self-supervision system output re-
operation code remain lit. The operation lay of the relay assembly. In addition, a
indicators can be reset via the push-buttons on fault code is lit on the display to show the type
the front panel of the relay, an external of the fault that has occurred. This fault
control signal or over the serial bus, see the code that consists of a red figure one and a
table in paragraph "Reset- ting". Unreset green code number cannot be removed by
operation indicators do not affect the resetting. It should be recorded and stated
operation of the relay module. If the output when service is ordered.
relay has a latching feature, the operation
indi- cators remain lit until the latching is The table below shows the priority of the
reset. opera- tion codes representing certain
events. If the priorities of the events to be
The self-supervision alarm indicator IRF indi- indicated are the same, the operation indicator
cates internal relay faults. Once the self- of the latest event is indicated on the display.
supervi- sion system of the relay module has
detected a permanent fault, the red indicator
is lit. At the

Priority Event to be indicated

1. Self-supervision fault c
2. Circuit-breaker failure
3. Stage I01> or stage
Stage I01> or stage
4. Activation of external c
5. the external control sig
61 61
Activation of external c
6. Activation of blocking
7.
Settings The setting values are indicated by the three The second settings can be activated via
right-most green digits on the display. When subregister 4 in register A. The setting ranges
a LED in front of a setting value symbol is lit are the same as those of the main settings. A
it shows that the particular setting value is flashing light of the setting indicators
indi- cated on the display. If the same LED shows that the second settings are active.
represents several settings, a red digit is used to
indicate the setting displayed. The default
setting is given in parentheses under the
setting range.

Setting

P1/In(%)

t01> (s)

P2/In(%)

t02> (s)

I01/In

I01/ I1

I02/In

I02/ I2

I2f/I1f(I01)>(%)

I2f/I1f(I02)>(%)

I1/In

I2/In

The setting of the switchgroups SGF1...11,


SGB1...8 and SGR1...11 are described in the
following paragraph "Configuration
switches"
62 62
Configuration The switches of switchgroups SGF1...11, These are found in the main menu of the
switches SGB1...8 and SGR1...11 can be used to relay module, see chapter "Main menus and
select additional functions required for submenus of settings and registers". The
different ap- plications. The switch number, default settings with checksums are also
1...8, and posi- tion, 0 or 1, are displayed mentioned in the tables. The calculation of
during the setting procedure. In normal the checksum is described in the end of
service conditions the checksums of the this paragraph.
switchgroups are displayed.

Switchgroup SGF1 The switchgroup SGF1 is used to select the It should be noted that one protection
protection principle to be used on the HV principle at a time can be used on the HV
side and LV side. When the switch is in side or the LV side.
position 1 the protection principle is used.

Switch Function

SGF1/1 Stabilize
SGF1/2 Calculate
SGF1/3 Measure
principle on HV side
SGF1/4 High-impedanc

SGF1/5 Stabilize
SGF1/6 Calculate
SGF1/7 Measure
principle on LV side
Switchgroup SGF2 SGF1/8
The switches of switchgroup SGF2 are used High-impedanc
blockings based on the second harmonic of
to define the influence of the directions of the neutral current.
SGF1
the connected currents and to configure
the

P2 P1 P2 P1
L1 L1
S2 S1 S2 S1
L2 L2

L3 L3

S1 P1 S2 P2
3 6 9
3 6 9 1,4,7 1,4,7
S2 S1
P2 P1

25 27 27 25

a) b)

Fig. 6. The connected phase currents and neutral current


have a) opposite directions
b) equal directions
at an external earth fault situation. The CT wires are numbered according to the 1 A nominal
current input terminals of the relay.

63 63
current exceeds the setting value.

Switch Function

SGF2/1 The switc


When
When

SGF2/2 The switc


When
When

SGF2/3 The switc

When
The switc
SGF2/4 When

SGF2/5 Not i
SGF2/6 Not i
SGF2/7 Not i
SGF2/8 Not i

SGF2

64 64
Switchgroup SGF3 Circuit-breaker failure protection (CBFP)

Switch

SGF3/1

SGF3/2

SGF3/3

SGF3/4...8

SGF3

Circuit-breaker failure protection operate times tCBFP to be selected with switches SGF3/4...8.

tCBFP / ms

100
120
140
160
180
200
220
240
260
280
300
320
340
360
380
400
420
440
480
520
560
600
640
680
720
760
800
840
880
920
960
1000
Switchgroup SGF4 Self-holding of output signals

Switch Function

SGF4/1 Selection of
SGF4/2 Selection of
SGF4/3 Selection of
SGF4/4 Selection of
SGF4/5 Selection of
SGF4/6 Selection of
SGF4/7 Selection of
SGF4/8 Selection of

SGF4

When a swi

When the se

Switchgroup SGF5 Activation of TRIP indicator LED


position 1, the TRIP operation indicator is lit
Selection of the output signal to control the
by the activation of the signal. The switches
TRIP indicator LED on the front panel.
SGF5/
When the switch linked to a certain output
5...8 are not in use.
signal is in

Switch
SGF5/

1
2
3
4

SGF5

Note! Special attention should be paid to the setting


The HV and LV side operate signals of the of switchgroup SGF5 when the operate signal
earth-fault relay module light the TRIP indica- can be initiated by an external control signal
tor irrespective of the setting of switchgroup BS1, BS2, BS3, BS4 or BS5.
SGF5, provided the operate signal is linked to
a heavy-duty output relay via an output The operation indicators of the earth-fault
signal TS1, TS2, TS3 or TS4. relay module are described in detail in the
paragraph "Operation indicators".
Switchgroups Selection of the start and operate signals of example, by circling the intersection of the
SGF6...11 the protection stages, the blocking signals and signal lines. The switch number is marked at
the external control signals BS4 and BS5 to be each intersection point and the weighting
used as intermodular signals AR1...3 and value of the switch is given to the right of the
BS1 matrix. Adding the weighting values of the
INT1...3. The signal configuration is switches selected from each switchgroup gives
presented in Fig 7 below. the switch- group checksums at the bottom of
the matrix. The checksums of the factory
The signals of the protection stages, the settings are given under the calculated
block- ing signals and the control signals are checksums.
linked with the desired intermodular signal
lines, for
Intermodular AR1 AR2 AR3 BS BS BS
signal
INT1 INT2 INT3
Function / Weighting
signal factor

I 01> 1 1 1 1 1 1 1
start

I 01> 2 2 2 2 2 2 2
trip

I 2f/I
1f 3 3 3 3 3 3 4
(I 01)>
block.

4 4 4 4 4 4 8
I 02>
start

I 02> 5 5 5 5 5 5 16
trip

I 2f/I 6 6 6 6 6 6 32
1f (I02
)>
block.
7 7 7 7 7 7 64
BS4

8 8 8 8 8 8 128
BS5

SGF6 SGF7 SGF8 SGF9 SGF10 SGF11


Check-
sum =

Factory
setting = 0 0 27 0 0 0

Fig. 7. Programming matrix for intermodular signals


Switchgroup SGB1 Selection of the logic active state of the When the switch is in position 0, the signal is
external control signals BS1...5 and the active (state 1), when voltage, either DC voltage
intermodular blocking signals BS INT1...3. 18...265 V or AC voltage 80...265 V, is
applied to the control input. When the
switch is in position 1, the signal is active
when no voltage is applied to the control
input.

Switch Function

SGB1/1 Selection of
SGB1/2 Selection of
SGB1/3 Selection of
SGB1/4 Selection of
SGB1/5 Selection of
SGB1/6 Selection of
SGB1/7 Selection of
SGB1/8 Selection of
SGB1
Switchgroup
SGB2...7

RESET

I 01> Main Indicators, Indicators


self-hold. , self-
trip Second hold.,

Control
signals Weighting

BS1

BS2

BS3

BS4

BS5

BS INT1

BS INT2

BS INT3

Check-
sum =

Factory default =

Fig. 8. Matrix for programming external control signals


Switches

SGB2/1...8

SGB3/1...8

SGB4/1...3

SGB5/1...3

SGB6/1...3

SGB7/1...3

Switchgroup SGB8 The logic active state of the blocking signals ule in relation to the logic state of the
BS INT1, BS INT2 or BS INT3 of the relay signal linked to the blocking signal.
mod-

Switch Function

SGB8/1 When SGB


When SGB
SGB8/2 When SGB
Not in used
SGB8/3

SGB8/4
SGB8/5
SGB8/6
SGB8/7
SGB8/8

SGB8

Switchgroups The switchgroups SGR1...11 are used to with the desired output signal SS1...SS4 or
SGR1...SGR11 config- ure the start and operate signals of TS1...TS4 by cir- cling the intersections of the
the protec- tion stages and various control signal lines. The switch number is marked at
signals to operate as desired output signals each intersection and the weighting value of
SS1...SS4 or TS...TS4. the switch is given

The matrix below can be used for


programming. The signals are connected
below the switches selected from each switch- group the Note!
matrix. By checksums of the switchgroups are obtained Before starting the programming check that all
adding the to the right of the matrix. (The output signals of the relay module SPCD
weighting checksums of the factory setting are given 2D55 are in use in the concerned protection
values of the in parenthesis). relay.

Output signal SS1 TS1 SS2 TS2 SS3 TS3 SS4 TS4

Switch Function / Checksum


- group control (factory setting)
signal 1 2 3 4 5 6 7
SGR1 8 SGR1 =
I 01>
start (=16)

SGR2 I 01> 1 2 3 4 5 6 7 SGR2 =


trip 8 (=74)

SGR3 I 2f/I 1f SGR3 =


(I 01) > 1 2 3 4 5 6 7 (=0)
block. 8

I 02> 1 2 3 4 5 6 7 SGR4 =
SGR4 start 8 (=16)

I 02> SGR5 =
SGR5 trip 1 2 3 4 5 6 7 (=74)
8
I 2f/I 1f SGR6 =
SGR6 (I 02) > (=0)
block. 1 2 3 4 5 6 7
8

SGR7 BS1 1 2 3 4 5 6 7 SGR7 =


8 (=0)

SGR8 BS2 SGR8 =


1 2 3 4 5 6 7 (=0)
8
SGR9 BS3 SGR9 =
(=0)
1 2 3 4 5 6 7
8
SGR10 BS4 SGR10 =
(=0)

1 2 3 4 5 6 7
SGR11 BS5 SGR11 =
8
(=0)

1 2 3 4 5 6 7
8

Weighting factor 1 2 4 8 16 32 64 128

Fig. 9. Output relay matrix for differential relay module SPCD 2D55
Measured data Measured data of main menu Measured values are indicated by the three
green right-most digits on the display. Data
that is being measured at the moment is
indicated by a LED above the display and a red
digit or letter to the left on the display.
Note! The the transformation ratio corrections. When differential current Idcos is zero. Then the
measured data the phase difference between the residual measured data displayed is zero too.
displayed allow current of the phase currents and neutral
for the effect of cur- rent is less than 90 , the directional

of the rated current


LED Red
percentage
indicatorof the rated current symbol

I1, I01

I1, I01

Id1

Measured data of Id2


The measured data available in submenus are contains the subregister with the measured
submenu described
I2, I02 in the table below. The red symbol data concerned.
on main menu level shows the main register
which
I2, I02
LED Main regis
indicator red symbo

I1, I01

I1, I01

I1, I01

Id1

Id2

I2, I02

I2, I02

I2, I02

Recorded The values recorded are stored in a The pushdown storage contains the five
information pushdown storage at the moment of relay start, latest values recorded (n)...(n-4). Each new
relay opera- tion, and during transformer value is stored in the first location (n) in the
connection inrush currents. Both the HV storage and pushes all the previous items one
side and the LV side values are recorded at step forward (n-1). When a sixth item is
relay start or relay opera- tion, irrespective of stored the oldest item (n-4) of the storage
whether the relay start or operation took will be lost.
place on the HV side or the LV side. The
values are also recorded when the operate The most recently stored values (n) are
signal is obtained via an external control output available in the main registers. At a maximum
BS1...5 four of the previous values are in the
subregisters. The left- most digit indicates the
address of the storage location and the other
three digits the numerical value of the
parameter stored.

Register Record
number

1 Directi
The su

Stabiliz
The su
2
Directi
The su

Stabiliz
3 The su

Neutra
The su

4 Durati
The su

Neutra
The su
5
Durati
The su
6

8
Register Record
number

9 Minimu
Subregi
(n-1)...

Status o

0 Contr

BS
BS
BS
BS
BS
BS
BS
BS

From th
The tes

Address
contain
1. Setti
Defa
2. Bus t
3. Passw
4. Selec
Defa
5. Hz s
6. mHz
So, t
A

When the display is dark, access to the begin- communication parameter, see section
ning of the main menu is gained by pressing "Reset- ting" in paragraph "Description of
the STEP push-button on the front panel for function". The registers are also cleared by
more than 0.5 s. Pressing the push-button an auxiliary power supply failure. The
for less than 0.5 s gives direct access to the setting values, the address code, the data
end of the main menu of the relay module. transfer rate and the password of the relay
module are not affected by voltage failures.
The information recorded in registers 1...9 can Instructions for setting the ad- dress code and
be reset with the push-buttons on the front data transfer rate are given in the document
panel, via an external control signal or a serial "General characteristics of D-type relay
modules".
Main menus
and submenus
of settings and MAIN MENU SUBMENU

registers
STEP 0.5 s PROGRAM 1 s
Normal status, display off
REV. STEP 0.5 s FWD. STEP 1 s

Sum current I 1 of phase Phase current Phase current IL2 on Phase current IL3
S currents on H.V. side [% In] IL1 3
1 H.V. side [x In]
H.V. side [x In]
2 H.V. side [x In]
Neutral current Io1 on
0 H.V. side [% In]

Diff. current on H.V. side


d [% In]
Phase angle diff.
1
1 on H.V. side

d Diff. current on L.V. side


[% In] Phase angle diff. 2
1 on L.V. side

S Sum current I2 of phase Phase current


currents on L.V. side [% In] I'L1 on Phase current Phase current
1 on L.V. side [x
2 I'L2 on on L.V. 3 I'L3 on on L.V.
side [x In] side [x In]
In]
Neutral current Io2 on
0 L.V. side [% In]

Starting value P1/In [ %] 1 Operating time to1> [s]

Starting value P2/In [%] 1 Operating time to2> [s]

CT ratio correction Io1/In


1 Minimum I01 / I1 [%]

CT ratio correction 1 Minimum I / I [%]


02 2
R E Io2/In
V.

S T 2nd harmonic
blocking threshold
EP
I2f/I1f(Io1)> [%]

0.5
s 2nd harmonic
blocking threshold
I2f/I1f(Io2)> [%]

CT ratio correction
I1/In

M
CT ratio correction
I2/In
A Functional Functional Functional
I 2 3 4
switchgroup switchgroup switchgroup
N SGF2 SGF3 SGF4
Functional
M 1 switchgroup SGF1
E 2 Blocking Blocking 4 Blocking
switchgroup 3 switchgroup switchgroup
N SGB2 SGB3 SGB4
U Blocking
1 switchgroup SGB1

Relay matrix Relay matrix Relay matrix


F 3 switchgroup 4
2 switchgroup SGR3 switchgroup
Relay SGR2
1 W SGR4
matrix
switchgr
oup
SGR1 Diff. current Id1cos1 on H.V.
D Diff. current Id1cos1 on H.V. 3
. 1 2 Diff. current Id1cos1 on H.V.

S side at n-1 event side at n-2 event


T side at n-3 event
Diff. current Id1cos1 on
1
H.V. side Bias current Ib1on H.V.
E at latest (n:th) event Bias current Ib1on H.V.
Bias current Ib1on H.V.
P 3 side at n-3 event
1 1 2 side at n-2 event
side at n-1
Bias. current event
1 2 Ib1on H.V. side Diff. current Id2cos2 on L.V.
at latest (n:th)
event Diff. current Id2cos2 on L.V.
s 2 3
Diff. current Id2cos2 on L.V.
side at n-3 event
Diff. current Id2cos2 side at n-2 event
3 on L.V. side at latest
(n:th) event side at n-1 event Bias current Ib2 on L.V.
3 side at n-3 event
Bias current Ib2 on L.V.
2
Bias current Ib2 on L.V.
Bias current Ib2 on L.V. side at latest (n:th) event 1
Neutral current Io1 on H.V.
side at n-2 event
side at n-1 event
Neutral current 3 side at n-3 event
Io1 on H.V. side Neutral current Io1 on H.V.
2
at latest (n:th) Neutral current Io1 on H.V.
event Duration of event n-3
side at n-2 event 3 starting on H.V. side
1 side at n-1
Duration of latest event (n) event
starting on H.V. side Duration of event n-2

Duration of event n-1


1 2
starting on H.V. side

starting on H.V. side

Neutral current Neutral current Io2 on L.V. Neutral current Io2 on L.V.
Io2 on L.V. side
at latest (n:th) Neutral current Io2 on L.V. side at
event 1 2 3 side at n-3 event
side at n-1 event

Duration of latest event (n) Duration of event n-1 Duration of event n-3
1 2
starting on L.V. side 3
starting on L.V. side
Duration of event n-2 starting on L.V.
starting on L.V. side Min. 2nd harmonic content
Min. 2nd harmonic content 2 3 of n-3 inrush on H.V. side
of latest inrush on H. V. side
Min. 2nd harmonic content

1 of n-1 inrush on H.V. side

Status of
external relay 0 IRF Id1>&to Id2 Id2>&to BS1 BS2 BS4 BS5
blocking / 000 Id1> 1> > 2> BS3
control
signals

Relay unit Communication rate Loss of bus traffic time Password for altering
identification
address for
communication 1 3
setting (kBd) counter 0...255 s settings
2
Fig. 10. Main menus and submenus for settings and registers of earth-fault relay
module
SPCD 2D55.
The procedure for entering a submenu "General characteristics of D-type SPC
or a setting mode and configuring the relay modules. Below a simplified
module is described in detail in the manual instruction.
34 SPC 3 EN1

Desired step or function

One step forward in main menu or submenu


Rapid browse forwards in main menu
One step backwards in main menu or submenu

Entering a submenu from the main menu

Entering or quitting a setting mode


Increasing a value in the setting mode
Moving the cursor in the setting mode
Storing a setting value in the setting mode

Resetting of memorized values

Resetting of latched output relays

Functional
6 Functional
7
switchgroup SGF7
switchgroup SGF6

9 0 II
5 Functional
switchgroup Functional Functional
SGF5 switchgroup switchgroup
6 SGF9 SGF10 8
Function
al
switchgr
oup
SGF11

Blocking Blocking Blocking Blocking


5 switchgroup switchgroup SGB6
7 switchgroup switchgr
SGB5
SGB7 oup
SGB8

Relay matrix
5 switchgroup Relay matrix Relay matrix Relay
6 switchgroup 7 switchgroup 8 matrix
SGR5 SGR6 SGR7 switchgr
oup
SGR8

4 Diff. current Id1cos1 on H.V.


side at n-4 event

Bias current Ib1on H.V.


4 side at n-4 event

Diff.
4 current
Id2cos2
on L.V.
side at
n-4
event

4 Bias current Ib2 on L.V.


side at n-4 event

Neutral current Io1 on H.V.


4 side at n-4 event

Duration of event n-4


4 starting on H.V. side

Neutral current Io2 on L.V.


4 side at n-4 event

Duration of event n-4


4 starting on L.V. side

Min. 2nd harmonic content


4 of n-4 inrush on H.V. side

Selection of main vs
second settings Nominal 6 Nominal frequency
4 5 setting, mHz -part
frequency
setting, Hz
-part
Testing of In the test mode, entered from the supervision output is tested. The LEDs in
output relays submenu of register 0, it is possible to front of the settings show the output
activate the output signals of the relay one signals to be activated at the moment.
by one. The desired output signal is selected by
pressing PROGRAM for about one
When the PROGRAM push-button is second.
pressed for about five seconds the three
digits to the right start flashing as an The setting LEDs on the front panel and
indication of the relay module being in their respective output signals are as
the test mode. Initially, the self- follows:

No LED Self-supervision IRF


P1/In (%) Start of HV side stage
I01> P2/In(%) Operation of HV
side stage I01>
I01/In HV side neutral current If2/I1f(I01)> blocking
I02/In Start of LV side stage I02>
I2f/I1f(I01)> Operation of LV side stage I02>
I2f/I1f(I02)> LV side neutral current I2f/I1f(I02)> blocking
I1/In External control signal BS1
I2/In External control signal BS2
SGF External control signal BS3
SGB External control signal BS4
SGR External control signal BS5

Pressing the push-buttons STEP and When the push-button STEP is being
PRO- GRAM simultaneously activates pressed in the IRF test mode, the self-
the selected output signal, which supervision output relay operates in about
remains active as long as the push- 1 second. Return to the main menu is
buttons are being pressed. The effect on possible at any stage of the test sequence
the functions of the output relays by pressing the PROGRAM push-
depends on the configuration of the button for about five seconds.
switchgroups SGR1... SGR11.
The signals are selected in the sequence
illus- trated in the Fig. 11.

IRF I 01 > start I 01 > trip I2f / I1f (I 01 I 02 > start I 02 > trip
)>

Register 0 PROGRA PROGRA P1 / PROGRA P 2/ I PROGRA I01 / PROGRA I02 / PROGRA I 2f /I


M M In M n M In M In M 1f
5 1 1 1 1 1s >
s s
s s s (I0
1)

STEP

I2f / I 1f (I 02 )> BS BS BS3 BS5


1 2 BS4

I2f /I1f > PROGRAM


(I 02)
1s

Fig. 11. Sequence for selecting the output signals in output relay testing.
Technical data

Principle based on calculated residual current


Basic setting on HV side P1/In
Operate time setting on HV side t01>
Basic setting on LV side P2/In
Operate time setting on LV side t02>
Correction range of HV side phase CTs I1/In
Correction range of LV side phase CTs I2/In
Operate time accuracy
Operation accuracy

Principle based on measured residual current or on neutral current


Basic setting on HV side P1/In Operate time setting on HV side t01> Basic setting on LV sid
Operate time setting on LV side t02>
Correction range of HV side neutral connection

CT ratio I01/In
Correction range of LV side neutral connection
CT ratio I02/In
Harmonics blocking ratio I2f/I1f of HV side
neutral current I01
Harmonics blocking ratio I2f/I1f of LV side
neutral current I02
Operate time accuracy
Operation accuracy
Restricted earth-fault principle
(high-impedance type earth-fault protection)
Basic setting on HV side P1/In 5...50%
Operate time setting on HV side t01> 0.03...100 s
Basic setting on LV side P2/In 5...50%
Operate time setting on LV side t02> 0.03...100 s
Correction range of HV side neutral connection
CT ratio I01/In 0.40...1.50
Correction range of LV side neutral connection
CT ratio I02/In 0.40...1.50
Operate time accuracy 2% of set value or 25 ms
Operation accuracy 4% of set value or 2% x In

Circuit-breaker failure protection


Operate time 0.1...1.0 s

Integrated disturbance recorder


Recording length 30 cycles
Recording memory capacity 1 recording = 30 cycles
Sampling frequency 40 samples/cycle
Signals to be recorded 8 analog signals
12 digital signals
Triggering
- when the selected digital signal is activated
- when the selected digital signal resets
Length of recording preceding triggering 0...30 cycles

Note!
Operate times are valid at rated frequency 50 Hz and 60 Hz.
Serial Special codes have been specified to An event to be included in event reporting
communicatio represent different events such as starting is marked with 1. The event mask is
n parameters and operation of protection stages, obtained by adding the weighting values of
blocking, and activation of control and the events in- cluded, see the tables below.
Event codes output signals. These event codes can be
transferred to higher-level systems over the
serial bus.

Event mask

V155
V156
V157
V158
V159

Channel Code

0 E1
0 E2
0 E3
0 E4
0 E5
0 E6

0 E7
0 E8
0 E9
0 E10
0 E11
0 E12
0 E13
0 E14

0 E15
0 E16
0 E17
0 E18
0 E19
0 E20
0 E21
0 E22
0 E23
0 E24
Channel Code

0 E25
0 E26
0 E27
0 E28
0 E29
0 E30
0 E31
0 E32

0 E33
0 E34
0 E35
0 E36
0 E37
0 E38
0 E39
0 E40

E50
E51
E52
E53
E54

The event codes E50...E54 and the events rep- 60 events. The event codes E52... E54 are
resented by these are always reported and gen- erated by the control data
cannot be excluded. The capacity of the event communicator (e.g. SRIO 1000M).
register is
Remote In addition to the event codes input data (I The push-buttons of the relay module or a
transfer data data), output data (O data), setting values (S command over the serial bus can be used to
data) memorized data (V data), and some change the password. To be able to change the
other data can be read from the module over password over the serial bus, the password first
the serial bus. The values of parameters marked has to be opened. The new password is entered
with the letter W can be changed over the by means of parameter V161. When using
SPA bus. the push-buttons, the new password is
written in the place of the old one in
When Measured
a setting value
data is to be changed, either subregister 3 of register A.
via the push-buttons on the front panel or
over the serial on
Current bus,HVthe siderelay
phasemodule
L1 checks Should the wrong password be given 7 succes-
whether the given parameter
Current on HV side phase L2 value is legal. A sive times, it turns into a zero and can no
value outside the permitted
Current on HV side phase L3 setting range will longer be opened over the serial bus. Then
not beResidual
memo- current
rized, butI the previous setting the pass- word can be given a new numerical
1calculated from HV side phase currents
will beHV
retained.
side neutral current I01 value via the push-buttons only.
Directional differential current Id1cos 1 on HV side
Changing a setting
Current on LVparameter
side phaseover
L1 the serial
bus requires a password
Current on LV side phase L2 in the range 1..999. R = data to be read from the
The default setting is 1.
Current on LV side phase L3 module
Residual current I2 calculated from LV side W phase
= data to be written to the
currents
The password is opened
LV side neutral current I02 by giving the module
serial Directional
communication parameter
differential currentV160
Id2costhe2 on(P)
LV=side
writing allowed through a password
desiredPhase
numerical value. Parameter V161
difference between residual current and is
used for closing
neutral the password.
current on HV side The password is
also closed by failures in the voltage
Phase difference between residual supply.
current and neutral current on LV side
Input data Status data of control signals BS1...5 and
Output data TheBSactual status INT3
INT1...BS data provide information latest resetting of the register. When the
about the present status of the signals. The value is 0, the signal is not activated and
events stored in the memory indicate those when the value is 1, the signal is activated.
signal activations which have taken place
after the
Status data of protection stages and control signals

Protection stage/
signal

Stage I01>, start signal


Stage I01>, operate signal
I2f/I1f(I01)> blocking
Stage I02>, start signal
Stage I02>, operate signal
I2f/I1f(I02)> blocking
Output relay control
by control signal BS1
by control signal BS2
by control signal BS3
by control signal BS4
by control signal BS5
Trip signal of CBFP

Signal activations

Output signal

Output signal SS1


Output signal TS1
Output signal SS2
Output signal TS2
Output signal SS3
Output signal TS3
Output signal SS4
Output signal TS4

Remote control of output signals

The parameters V11...V59 can be used to read (R) n-1 = the value before that, and so on. The
the latest five values stored in the registers. Event n registers are described in detail in the paragraph
= the most recent value recorded, event "Recorded information".
Value measured

Directional differential current


Id1cos 1
Stabilizing current Ib1
Directional differential current
Id2cos 2
Stabilizing current Ib2
Neutral current I01
Duration of start situation,
stage I01>
Neutral current I02
Duration of start situation,
stage I02>
Min. ratio I2f/I1f, of HV side neutral
current, during the latest
connection inrush current

Stage that initiated tripping


Setting values
Setting

Basic setting P1/In


Basic setting P2/In
Operate time t01>
Operate time t02>
Harmonics blocking ratio I2f/I1f(I01)>
Harmonics blocking ratio I2f/I1f(I02)>
Transformation ratio correction I01/In
Transformation ratio correction I02/In
Transformation ratio correction I1/In
Transformation ratio correction I2/In

Checksum, SGF1
Checksum, SGF2
Checksum, SGF3
Checksum, SGF4
Checksum, SGF5
Checksum, SGF6
Checksum, SGF7
Checksum, SGF8
Checksum, SGF9
Checksum, SGF10
Checksum, SGF11
Checksum, SGB1
Checksum, SGB2
Checksum, SGB3
Checksum, SGB4
Checksum, SGB5
Checksum, SGB6
Checksum, SGB7
Checksum, SGB8
Checksum, SGR1
Checksum, SGR2
Checksum, SGR3
Checksum, SGR4
Checksum, SGR5
Checksum, SGR6
Checksum, SGR7
Checksum, SGR8
Checksum, SGR9
Checksum, SGR10
Checksum, SGR11

Min. ratio I01/ I1 of neutral current


and residual current
Min. ratio I02/ I2 of neutral current and residual current

38
Control parameters
Data

Resetting of front panel operation


indicators and latched output relay
Resetting of front panel operation
indicators, output relays, registers and
recording memory

Remote control of settings

Event mask for I01> stage


Event mask for I02> stage
Event mask for external control signals
Event mask for output signals
Event mask for output signals

Opening of password for remote setting


Changing or closing password
for remote setting

Activation of self-supervision input

EEPROM formatting

Error code

Rated frequency, Hz setting


Rated frequency, mHz setting

Data communication address


of relay module
Data transfer rate

Program version symbol

39 39
Data

Selection of internal signals to be used for triggering the disturbance recorder

Internal signal

I01> start

I02> start

Blocking I2f/I1f(I01)>

Blocking I2f/I1f(I02)>

Factory setting V241

Selection of method for triggering


the disturbance recorder V242 R,W 0...15

Control signal

I01> start

I02> start

Blocking I2f/I1f(I01)>

Blocking I2f/I1f(I02)>

Factory setting V242

Selection of control signals to be used for


triggering the disturbance recorder V243 R,W 0...255

Control signal

BS1

BS2

BS3

BS4

BS5

BS INT1

BS INT2

BS INT3

Factory setting V243


Data

Selection of method for triggering the disturbance recorder

Internal signal

BS1

BS2

BS3

BS4

BS5

BS INT1

BS INT2

BS INT3

Factory setting V244

Length of recording following disturbance recorder triggering, in cycles Status/command registe

Reading of event register

Re-reading of event register

Type designation of relay module


Reading of module status data

automatic reset

Resetting of module status data


Time reading or setting
Date and time reading and setting

The
mandevent
only register can bearead
once. Should faultbyoccur,
the Lsay,
com-in forwards the information to an output device.
the data communication, the B command Under normal conditions the event register
can be used to re-read the contents of the of the relay module is empty. The control
register. When required, the B command can data communicator also resets abnormal status
be re- peated. In general, the control data data, so this data is normally zero.
communica-
Fault codes
SPCJ 4D28
Overcurrent and earth-fault relay
module
User´s manual and Technical description

3I>
I
I L1 I L2 I L3 I o IRF

I >/ In RESET
STEP
t > [s ]
k

I >> / I n
t >> [ s ]
I >>> /I n
t >>> [ s ]

I0 >/ I n

t 0 > [s ]
k0
I 0 >> / I n
t 0 >> [s ]
I > [%]
t > [s ] PROGRAM

SGF

SGB

SGR

TRIP
0023A

SPCJ 4D28
1MRS 750093-MUM EN
SPCJ 4D28
Issued 1995-05-04
Modified 2002-05-15
Version E (replaces 34 SPCJ 18 EN1)
Overcurrent and earth-fault
Checked MK
Approved OL
relay module
Data subject to change without notice

Contents Characteristics ................................................................................................................ 2


Description of function .................................................................................................. 3
Overcurrent unit ....................................................................................................... 3
Earth-fault unit.......................................................................................................... 3
Filter characteristics of the measuring inputa ............................................................. 4
Phase discontinuity unit ............................................................................................ 4
Circuit breaker failure protection unit ....................................................................... 4
Output signals ........................................................................................................... 4
Auto-reclose start initiation signals ............................................................................ 5
Second settings .......................................................................................................... 5
Resetting ................................................................................................................... 5
Block diagram ................................................................................................................. 6
Front panel ..................................................................................................................... 7
Operation indicators ....................................................................................................... 8
Settings (modified 1999-10) ............................................................................................ 9
Measured data .............................................................................................................. 16
Recorded information ................................................................................................... 17
Menu chart ................................................................................................................... 20
Time/current characteristic curves (modified 2002-05) ................................................. 22
Technical data .............................................................................................................. 30
Serial communication parameters ................................................................................. 31
Event codes ............................................................................................................. 31
Remote transfer data................................................................................................ 33
Fault codes.................................................................................................................... 38

Characteristics Low-set overcurrent stage I> with definite Output relay matrix allowing any start or trip
time or inverse definite time characteristic, the signal from the protection stages to be routed
latter with six selectable inverse-time curves. to the desired output relay.

High-set overcurrent stage I>> with definite Flexible configuration of auto-reclose start ini-
time characteristic. The high-set stage can be tiation signals.
set out of operation.
Local display of measured and set values
Superhigh-set overcurrent stage I>>> with and data recorded at the moment of a fault.
defi- nite time characteristic. The superhigh- Reading and writing of setting values either
set stage can be set out of operation. via local display and front panel push-
buttons or from higher-level systems over the
Low-set neutral overcurrent stage I0> with serial interface and the fibre-optic bus.
defi- nite time or inverse definite time
characteristic, the latter with six selectable Self-supervision system continuously monitor-
inverse-time curves. ing the operation of the electronics and the
microprocessor. When a permanent fault is
High-set neutral current stage I0>> with de- tected the alarm output relay operates and
defi- nite time characteristic. The high-set the other relay outputs are blocked.
stage can be set out of operation.

Phase discontinuity stage with definite time


characteristic. The phase discontinuity
stage can be set out of operation.
Description of The overcurrent unit of the combined overcur-
operation Overcurrent unit rent and earth-fault relay module SPCJ 4D28 is
44 44
designed to be inverse time operation of stage I>, a time Note! At inverse time characteristic the
used for single- depending on the level of the measured effective setting range of the low-set
phase, two-phase current, the stage operates issuing an operate overcurrent stage is
and three-phase signal, which can be routed to the desired 0.5…2.5 x In, although start current settings
overcurrent output relay. within the range 2.5…5.0 x In can be set on
protection. The the relay. At inverse time characteristic any
overcurrent unit The operation of the overcurrent stages I> start current setting above 2.5 x In of the low-
includes three and I>> can be inhibited by an external set stage will be regarded as being equal to 2.5 x
overcurrent control signal BS1, BS2 or RRES(BS3) In .
stages: a low-set applied to the relay module. The external
stage I>, a high-set blocking signals are configured with If the high-set stage I>> is given a setting
stage I>> and a switchgroups SGB1...3. from the lower part of the the setting range,
superhigh-set stage the relay module will contain two nearly
I>>>. The operation of the overcurrent stage I> can identical opera- tion stages. In this case the
be based on definite time or inverse time relay module SPCJ
An overcurrent character- istic. When inverse time 4D28 can be used in two-stage load shedding
stage starts if the characteristic is se- lected four internationally applications.
current on one or standardized and two special type
more of the phases time/current curves are available. Both the The set start current value I>>/In of stage I>>
exceeds the set mode of operation and the desired can be automatically doubled in a start situa-
start value of the time/current curve is selected with tion, i.e. when the object to be protected is
concerned stage. switchgroup SGF1. connected to the network. Thus a set start
On starting the current value below the connection inrush
stage provides a cur- rent level may be selected for the
start signal which overcurrent stage I>>. A start situation is
can be routed to defined as a situa- tion where the phase
the desired output currents rise from a value below 0.12 x I> to
relay. At the same a value above 1.5 x I> in less than 60 ms. The
time a numeri- cal start situation ends when the currents fall
code indicating below 1.25 x I>.
starting appears on
the dis- play. The I>> stage or the I>>> stage can be set out
Should the of operation completely, if not needed. When
duration of the an overcurrent stage is set out of operation
overcurrent the set start current of the stage is displayed
situation exceed with three dashes "- - -".
the set operate
time of the stage The inverse time function of stage I> can be
at definite time inhibited, when stage I>> or stage I>>> is
operation or, at start- ing, in which case the operate time is
deter- mined by these stages.

Earth-fault unit The earth-fault unit of the combined


overcur- rent and earth-fault relay module The operation of the
SPCJ 4D28 is provided with two protection overcurrent stages I0>
stages: a low-set neutral overcurrent stage and
I0> and a high-set neutral overcurrent stage I0>> can be
I0>>. inhibited by an
external control
The low-set stage or the high-set stage starts, if
the neutral or residual current measured exceeds
the set start current of the concerned stage.
On starting the stage provides a start signal,
which can be routed to the desired output
relay. At the same time a numerical code
indicating starting appears on the display.
Should the duration of the neutral
overcurrent situation exceed the set operate
time of the stage at definite time opera- tion
or, at inverse time operation of stage I0>, a
time depending on the level of the measured
current, the stage operates issuing an
operate signal, which can be routed to the
desired out- put relay.
45 45
signal BS1, BS2 or RRES(BS3) applied to the relay module. The The I0>> stage can be set out of operation
external blocking signals are configured with switchgroups SGB1...3. completely, if not needed. When a neutral
over- current stage is set out of operation the
The operation of the low-set stage I0> can be based on definite time or set start current of the stage is displayed
inverse time character- istic. When inverse time characteristic is se- with three dashes "- - -".
lected four internationally standardized and two special type
time/current curves are available. Both the mode of operation and the The inverse time function of stage I0> can be
desired time/current curve is selected with switchgroup SGF1. inhibited, when stage I0>> is starting, in
which case the operate time is determined
by stage I0>>.
Filter characteristics A low-pass filter suppresses the harmonics of the
of the measuring dB 10
phase currents and the earth-fault current
inputs meas- ured by the module. Figure 1 shows 0
the signal suppression as a function of the
frequency. -10

-20

-30

-40
0 1 2 3 4 5 6 7
f/fn

Fig. 1. Filter characteristics of the measuring


inputs of the module SPCJ 4D28

Phase discontinuity The overcurrent and earth-fault relay issuing an operate signal, which can be routed
protection unit module SPCJ 4D28 is provided with a phase to the desired output relay. At the same time a
disconti- nuity protection unit which red operation indicator code is lit on the
monitors the mini- mum and maximum phase display.
currents. The differ- ence between these
currents is calculated from the expression I = The phase discontinuity protection stage can be
(Imax-Imin)/Imax x 100%. The phase set out of operation completely, if not
discontinuity protection is not in use when needed. When the stage is set out of
the measured currents fall below 0.1 x In. operation the set start current is displayed with
three dashes "- - -".
The phase discontinuity protection stage
starts, if the current difference exceeds the The operation of the phase discontinuity pro-
set start current I of the stage. Should the tection stage can be inhibited by an
duration of the phase discontinuity situation external control signal BS1 applied to the
exceed the set operate time t > of the stage relay module. The external blocking signal is
the stage operates configured with switch SGB1/6.

Circuit breaker The overcurrent and earth-fault relay in question. The CBFP can also be used to
failure protection module SPCJ 4D28 is provided with a establish a redundant trip system by using two
unit circuit breaker failure protection unit (CBFP) trip coils in the circuit breaker and
which provides a trip signal TS1 within controlling one of the coils with TS2, TS3 or
0.1...1 s after the trip signal TS2, TS3 or TS4 and the other with TS1. The switches
TS4 has been delivered, provided the fault SGF4/5...7 are used for activating the circuit
still persists after the time has elapsed. The breaker failure protection. The operate time is
CBFP normally controls the cir- cuit breaker set in submenu
which precedes the circuit breaker 5 of register A.

Output signals Switchgroups SGR1...11 are used for routing active, although the signal that caused the op-
the start or trip signals of any protection eration resets. The resetting functions are
stage to the desired start outputs SS1...SS4 ex- plained in paragraph "Resetting". The
or trip outputs TS...TS4. TRIP indicator on the front panel can be set
to be lit on activation of any of the output
The output signals TS1…TS4 can be assigned signals. The operation indicator remains lit
a self-holding function with switches SGF4/
1…4. In this case the output signal remains
46 46
after the output signal has disappeared. The functions are se- lected
with switchgroup SGF5.
Auto-reclose start The start signals AR1, AR2 and AR3 can be to be activated by the desired start and
initiation signals used as start initiation signals for the desired operate signals of the earth-fault module and
autoreclose shots. The initiation signal AR2 the initia- tion signal AR1 by the start and
can be programmed to be activated by the operate signals of both the overcurrent
desired start and operate signals of the module and the earth- fault module.
overcurrent module. The start signal AR3 can
be programmed

Second settings Either the main settings or the second The main and second settings can be read and
settings can be selected as currently used set via the serial bus using the S parameters.
settings. Switch- ing between the main Those settings only, which currently are
settings and the second settings can be done used, can be read and set with the push-
in three different ways: buttons and the display on the front panel.
When the second settings are used the
1) By command V150 over the serial indicators of the settings are flashing.
communi- cation bus
2) By an external control signal BS1, BS2 Note!
or If external control signals have been used for
RRES (BS3) selecting the main or second settings, it is not
3) Via the push-buttons of the relay module, possible to switch between the settings over the
see submenu 4 of register A. When the serial bus or using the push-buttons on the
value of submenu 4 is 0 the main settings are front panel.
used and when the value of submenu 4 is 1
the second settings are used.

Resettings The LED operation indicators, the operation reset with the push-buttons on the front
code numbers of the display, the latched panel, with an external control signal or by a
output relays and the registers of the module command via the serial bus, see table below.
can be

Way of resetting

RESET

PROGRAM (dark display)

RESET & PROGRAM

External control signal BS1, BS2 or RRES (BS3), when


SGB2…3/6 = 1

SGB_7/ = 1
SGB_8/ = 1

Parameter V101

Parameter V102

Block diagram
I L1 I> t>
I L2 Imax - Imin SGF 5/1
Imax SGR 11 / x 1 SS1
I L3 RESET +
PROGRAM
SGF 4/1

SGR 1 / x SGF 5/2


50 ms

I> 2 1 TS1
t>, k 1
SGR 2 / x
SGB 1/1 SGB SGF1/1… 30 ms
3/1 3
SGB 1/6 SGB 2/1 t>>
I>>
47 47
3 0.1..1s SGF 5/3 SS2
1
SGR 3 / x 4
S RESET +
G PROGRAM
F
4/ SGF 5/4
SGR 4 / x
2
TS2

SGB 1/2 SGF 4/5

SGB 2/2 SGF1/5


5
SGF 5/5
2 x I>>
SS3
SGB 3/2

SGF 4/3 RESET +


0.12 x I> PROGRAM

60 ms SGF 5/6

BS1 & 6 1 TS3


1.5 x I>
BS2 SGR 5 / x
30 ms
RRES 1.25 x I>

(BS3) 7 SGF 4/6 SGF 5/7


I>>>
SGR 6 / x SS4
t>>>

SGF 4/4 RESET +


PROGRAM

SGF 5/8
SGB 1/3 TS4
SGB 2/3 SGR 7 / x 8 1
50 ms
SGB 3/3

SGR 8 / x SGF 4/7


Io> to>, ko
I0 TRIP

SGF 1/6…8
SGR 9 / x
RESET
Io>>
I> start
1
30 ms SGF 6 / x AR1
SGB 1/4
SGB 2/4
SGB 3/4

SGB 1…3/5 Settings (main / 2nd)


Reset trip indicators
SGB 2…3/6
Reset trip indicators and output relays
SGB 1…3/7
Reset trip indicators, output relays and
SGB 1…3/8 registers
SPCJ 4D28

Fig. 2. Block diagram for overcurrent and earth-fault relay module SPCJ 4D28

IL1, IL2, IL3 Phase currents


I0 Neutral current
BS1, BS2, RRES (BS3) External signals for blocking or resetting
SGF1..8 Selector switchgroups for relay functions SGB1...3
Selector switchgroups for external control signals SGR1...11
Selector switchgroups for configuration of output relays SS1...SS4, TS1...TS4
Output signals
AR1, AR2, AR3 AR start initiation signal
TRIP Red operation indicator
Note! module. The signals wired to the terminals are
All input and output signals of the relay shown in the signal diagram of the concerned
module are not necessarily wired to the protection relay.
terminals of each protection relay containing
the SPCJ 4D28

Front panel Indicator tor


for the for
operate the
time t> or start
Phase current and residual current indicators during time curre
current measurement and phase fault indicators multiplier nt of
at relay operation k stage
I I>>
n and
d the
i operat
Indicator for the start current of stage I>
c e
a
48 48
tim start current of stage I0>> and the operate time
e t0>> 3I>
t>> Indicator for the start current of stage I> and I
Indicator
for the I L1 I L2 I L3 I IRF
o
start
current
of stage
I>>> and
the
operate RESET
I >/ In
time STEP
t>>> t > [s ]
Indicator for the k

start current of I >> / I n


t >> [ s ]
stage I0>
I >>> /I n
t >>> [ s ]
Indicator for the
operate time t0> I0 >/ In

and the time t 0 > [s ]


multiplier k0 k0

Indicato I 0 >> / I

r for the n
t 0 >> [ s ]
I > [%]

t > [ s ] PROGRAM
the operate time t >
Indicator for the checksums of switchgroups SGF1...8 SGF

Indicator for the checksums of switchgroups SGB1...3 SGB

Indicator for the checksums of switchgroups SGR1...11 SGR

TRIP

0023A
SPCJ 4D28
3I> Device symbol
I

I L1 I L2 I L3 I IRF Indicator for self-supervision alarm


o

Display window

I >/ In RESET
STEP
t > [s ] Reset and display step push-button
k
I >> / I n
t >> [ s ]
I >>> /I n
t >>> [ s ]

I0>/ In

t 0 > [s ]
k0

I 0 >> / I n
t 0 >> [s ]
I > [%]
t > [ s ] PROGRAM

SGF
Setting push-button
SGB

SGR Operation indicator


TRIP
0023A

SPCJ 4D28 Type designation of relay module

49 49
Fig. 3. Front panel of the combined overcurrent and earth-fault relay module SPCJ 4D28
Operation Each protection stage has its own red start started also operates the code number
indicators and trip code shown as a number on the indicating starting turns into a code number
display. The TRIP indicator at the bottom indicating operation. When desired, the
right corner is shared by the different code numbers indicating starting can be set
protection stages. Switch- group SGF5 is to remain lit, by giving switches SGF2/1...5
used for defining the mode of function of proper settings.
the TRIP indicator.
Operation indicators that remain lit are
The code numbers indicating tripping and the reset either by pressing the RESET push-
red TRIP indicator remain lit, when the button on the front panel or by command
protec- tion relay has issued a trip signal. Thus V101 over the SPA bus. Unreset operation
it is easy to identify the tripping stage. The indicators do not affect the operation of the
indicators remain lit even though the stage relay module.
that caused the indication resets, and they have
to be separately reset. On the other hand, The table below shows the code numbers of
the code numbers indication starting the display or the corresponding code numbers
automatically turned off when the protection read- able with parameter V9 indicating
stage resets. If the stage that starting or operation of the relay module.

Indication P

1
2
3
4
5
6
7
8
9
0
11

When one of the protection stages of the The self-supervision alarm indicator IRF indi-
mod- ule operates, the yellow LEDs on the cates that the self-supervision system of the
upper part of the front panel show on which relay module has detected a permanent fault.
phase the current exceeded the set start Once a fault has been detected the red indicator
current of the stage, named phase fault is lit. At the same time the relay module
indication. If, for in- stance, code number 2 delivers a con- trol signal to the self-
and indicators IL1 and IL2 are lit, operation supervision system output relay of the
was caused by overcurrent on the phases L1 protection relay. In addition, in most fault
and L2. The phase fault indication is reset cases, a fault code appears on the display to
with the RESET push-but- ton. indicate the type of fault. This fault code,
which consists of a red figure one (1) and a
green 1…3 digit code number cannot be
removed by resetting. The code number
should be recorded after a fault situation
and stated when service is ordered.
Settings The setting values are indicated by the three to be set indicates the quantity currently
rightmost digits on the display.The LED indi- being displayed.
Numerical cators adjacent to the symbols of the
settings quantities
(modified 99-10)

50 50
Setting Explanation

I>/In Start curren


input used.
t> Operate tim
characteristic.
k Time multiplie
characteristic.
I>>/In Start curren
energizing inpu
t>> Operate tim

I>>>/In Start curren


energizing inpu
t>>> Operate tim

I0/In Start curren


energizing inpu
t0> Operate tim
characteristic.
k0 Time multiplie
characteristic.
I0>>/In Start curren
energizing inpu
t0>> Operate tim

I> [%] Start curren


the minimu
expressed as

t > Operate tim

*) At inverse time characteristic the relay al- lows setting above 2.5 x
CBFP Note! Operate tim
In, but regards any setting >2.5 x In as being equal to 2.5 x In. The continuous current carrying capacityprotection
of the
** ) The stage can be set out of operation with SGF switches. This energizing inputs is 4.0 x In.
state is indicated as "- - -" on the display.

51 51
Switch settings

Switch Function

SGF1/1 Definite time or inver


SGF1/2 When the inverse time
SGF1/3 current/time character

SGF1/1 SGF1/2 S

0 0
1 0
0 1
1 1
0 0
1 0
0 1
1 1

SGF1/4 Not in use

SGF1/5 Automatic doubling o

When SGF1/5 = 0, th
When SGF1/5 = 1, th

SGF1/6 Definite time or inver


SGF1/7 When the inverse time
SGF1/8 current/time character

SGF1/6 SGF1/7 S

0 0
1 0
0 1
1 1
0 0
1 0
0 1
1 1

SGF1
Switch Function

SGF2/1 Mode of operatio


SGF2/2 ent stages. When
SGF2/3 code number auto
SGF2/4 the switch is in p
SGF2/5 fault disappears.

Switch S

SGF2/1
SGF2/2
SGF2/3
SGF2/4
SGF2/5

SGF2/6 Inhibition of the


SGF2/7 When the operat
SGF2/8 set value is displ

Switch S

SGF2/6
SGF2/7
SGF2/8

SGF2

SGF3/1 Phase discontinuity protection stage I> to be set out of use. 1


When SGF3/1 = 1, the phase discontinuity protection stage is out of use. The out of use state
is indicated as "- - -" on the display.

SGF3/2 Resetting times of stage I> and I0>. 0


SGF3/3 0
SGF3/4 Switch 0
SGF3/5 0

SGF3/2
SGF3/3
SGF3/4
SGF3/5

SGF3/6 Inverse time


When SGF

SGF3/7 Inverse time


stage I>>>.
When SGF
SGF3/8 Inverse time
When SGF

SGF3
Switch Function

SGF4/1 Selection of self-holdin


SGF4/2 Selection of self-holdin
SGF4/3 Selection of self-holdin
SGF4/4 Selection of self-holdin

When the switch is in


When the switch is in

At self-holding the ou

SGF4/5 Starting of the circuit


SGF4/6 Starting of the circuit
SGF4/7 Starting of the circuit

When the switch is in


When the switch is in

SGF4/8 Not in use

SGF4

SGF5/1 Selection o
SGF5/2 When the
SGF5/3 position 1
SGF5/4
SGF5/5 Switch
SGF5/6
SGF5/7
SGF5/8
SGF5/1
SGF5/2
SGF5/3
SGF5/4
SGF5/5
SGF5/6
SGF5/7
SGF5/8

SGF5 170
Switchgroups Using the different start and operation signals point. The numbers of the different switches
SGF6…8 as autoreclose start initiation signals AR1, and their weight factors are marked near the
AR2 or AR3. The signal selection possibilities crossing points. The checksums for the
(modified 96-02) are shown in Fig. 4 below. different switch groups are obtained by adding
the weight factors of the selected switches.
In the figure the start and operate signals of
the different protection stages are connected to Switches SGF6/7…8 and SGF7/7…8 are not
the desired autoreclose start line AR1, AR2 or in use.
AR3, for instance, by encircling the signal
crossing
Autoreclose AR1 AR3
initiating
AR2 signal

Operation stage SGF7 SGF6 SGF6


1 (1) 1 (1) 1 (1)
I>
SGF6 = switchgroup
1 = switchnumber
2 (2) 2 (2) (1) = weighting factor
t>

3 (4) 3 (4) Checksum


I>> (factory setting)

t>> SGF6 = (
4 (8) 4 (8) = 0)

SGF7 = (
I>>> 5 (16) 5 (16) = 0)

SGF8 = (
t>>> = 0)
6 (32) 6 (32)
SGF8
SGF8

1 (1) 5 (16)
I0 >

t0 > 2 (2) 6 (32)

I0 >> 3 (4) 7 (64)

t0 >> 4 (8) 8 (128)

Fig. 4. Selection matrix for the autoreclose initiation signals


Switchgroups The functions of the control signals BS1, the switch is shown at the bottom row of the
SGB1…3 BS2 and RRES (BS3) are defined with matrix. By horizontally adding the weight
switchgroups SGB1…3. The matrix shown fac- tors of all the selected switches of a
below can be used as an aid for making the switchgroup the switchgroup checksums is
desired selections. The control signals at the obtained.
left side in the matrix can be combined with
the functions at the upper side by encircling Note!
the desired intersection points. Each Check if all the control signals of the
intersection point is marked with a switch relay module SPCJ 4D28 are available in the
number and the corresponding weight factor protec- tion relay in question.
of

Indicators Indicators,
t 0 >> Main I> self-hold.
Indicators,
t> t>> t 0> self-hold.,
Second registers

Checksum
(factory setting)
2 3 4 5 6 7 8 SGB1=
BS1 1 ( = 0)

BS2 1 2 3 4 5 6 7 8 SGB2=
( = 0)
RRES 8 SGB3=
(BS3) 1 2 3 4 5 6 7
( = 0)
Weighting 2 4 8 16 32 32 64 128
factor 1
Fig. 5. Control signal matrix of the combined overcurrent and earth-fault relay module SPCJ 4D28.

Switch

SGB_/1...4

SGB_/5

SGB1/6

SGB2…3/6

SGB_/7

SGB_/8

Switchgroups The start and operate signals of the point is marked with a switch number and
SGR1…11 protection stages are combined with the the corresponding weight factor of the
outputs SS1… SS4 and TS1…TS4 with switch is shown at the bottom row of the
(modified 96-02) the switches of switchgroups SGR1…11. matrix. By horizontally adding the weight
factors of all the selected switches of a
The matrix shown below can be used as an switchgroup the switch- group checksums is
aid for making theI>desired selections. The start obtained.
and operate signals of the different protection
stages can be combined with the output Note!
signals SS1…SS4 and TS1…TS4 by Check if all the start and operate signals of
encircling the desired intersection points. the relay module SPCJ 4D28 are available in
Each intersection the protection relay in question.

Output signal

Switch- Operation stage


group

SGR1 I>

SGR2

SGR3 I>>

SGR4
I>>>
SGR5
I0>>
SGR6
SGR7 I0>

SGR8

SGR9

SGR10

SGR11

Weighting factor

Fig. 6. Output signal matrix of the combined overcurrent and earth-fault relay module SPCJ 4D28.
Manual checksum
calculation Switch Weight factor Position Value

SGF1/1
SGF1/2
SGF1/3
SGF1/4
SGF1/5
SGF1/6
SGF1/7
SGF1/8

Checksum of switchgroup SGF1 = 69

Measured data The measured values are indicated by the value currently presented is indicated by a
three right-most digits on the display. The yel- low LED above the display.
measured

Indicator Measured da

IL1 Measured lin

IL2 Measured lin

IL3 Measured lin

I0 Residual cur

I0 In the subme
between the
phase curren

Recorded The left-most digit of the display shows the isters is presented in the section "Main menus
information register address and the other three digits the and submenus of settings and registers".
recorded information. The structure of the
reg-

Register/ Recorded inf


STEP

1 Current mea
When the st

Register 2 re

Register 3 re

Duration of

Subregister 5

2 Duration of

Subregister 5
3
Residual cur
When the st
4

6
Register/ Recorded i
STEP

7 Duration o

Subregister

Duration o

Subregister

Unbalance

Continuou
8 last relay re

Display of

The right-m

9 Displaye
figure

0
1
2
3
11 4
5
6
7

0 The functi

18
Register/ Record
STEP

From re

Indicat
I>
t>
I>>
t0>
I0>>
I>

For fur

Address

1. Selec
2. Bus
3. Passw
A 4. Selec
Defa
5. Selec
0.1...

When the display is dark, press the STEP external control signal BS1, BS2 or RRES.
push- button for 1 second to go to the The registers are cleared by failures in the
beginning of the display menu. To go to the auxiliary power supply to the module. The
end of the display menu, press the STEP setting values, the address code, the data
push-button for a short moment only (<0.5 transfer rate and the password of the relay
s). module are not affected by supply voltage
failures. Instructions for specify- ing the
The values stored in registers 1...11 are cleared address code and the data transfer rate of the
by pressing the push-buttons RESET and relay module are given in the description
PRO- GRAM simultaneously, by a command "General characteristics of D-type SPC relay
V102 over the serial communication system modules".
or by an
Menu MAIN MENU SUBMENU
chart

STEP 0.5 s PROGRAM 1s

Normal
status,
display
off

Value, that can be set


Current in phase L1 = in the setting mode

C
ur
re
nt
in
ph

19 19
as
e
L2
SUBMEN
REV. STEP 0.5 U FWD STEP 1 s
Current in phase L3
s

Neutral current Io
1 Differential current I

S
t
a
r
t

v
a
l
u
e

I
>

O
p
e
r
a
t
e

t
i
m
e

t
>

o
r

m
u
l
t
i
p
l
i
e
r

k
Start value I>>
1 Operate time t>>

Start value I>>>


1 Operate time t>>>

Start value Io>


R

E Operate time to> or


V
multiplier ko 1 Operate time to>>

S
T Start value Io>>
1 Operate time t>
E

Setting of
P Setting of switchgroup
3 SGF3
Start value I
switchgroup
. 2 SGF2
5 Setting of switchgroup
8 SGF8
Setting of
s 7
Setting of switchgroup switchgroup Setting of switchgroup
SGF1 SGF7 3 SGB3

Setting of Setting of switchgroup


switchgroup 3 SGR3
M 2 SGB2

Setting of switchgroup
A Setting of 8 SGR8
2
switchgroup
I Setting of switchgroup
SGR2
N SGB1

Setting of
M Setting of switchgroup switchgroup
7
E SGR1 SGR7
N

F E
1
3 Value of current
P Value of cur
W I L1, latest I L3, latest
memorized memorized
event n n
D
1s
Value of current I L2, latest Duration of I> starting, latest
2 S memorized event n 4 memorized event n
T

20 20
Value of current IL1,
1 event n-1
Duration of
1
I>> starting,
latest
memorized Value of current IL2,
1 event n-1
event n
2

Value of
current Io, Value of current IL3,
1 event n-1
latest
memorized 3
Desired step event n
Duration of I> starting,
1 event n-1

Forward step in main menu or submenu 4

Rapid scan forward in main menu 1 Duration of I>> starting,


event n-1

Backward step in main or submenu 5

Value of current Io,


Entering a submenu from the main menu 1 event n-1
6
Duration of Io> Duration of Io> starting,
starting, 2
Duration of 1 event n-1
event n-2
Entering or leaving a setting mode Io> starting,
latest
7

Incrementation of value in setting mode memorized


event n 1
Duration of Io>>
starting, event n-1 2
Duration of Io>> starting,
event n-2

Moving cursor in setting mode Duration of


8

Io>> starting,
Storing a setting value in setting mode latest
memorized
event n

Erasing of memorized values and re- Value of current


I, 2 Value of current I,
event n-2
1
setting of latched output relays Value of
current I,
event n-1
9
latest
Resetting of latched output relays memorized
event n

Highest maximum demand


1 value found
Maximum
demand
current value
for 15 minutes

0 000 I> t> I>> I>>> Io> to> Io>> I>


IRF
Status of external control
0 signals

Relay module identification


A Communication
2
Loss of bus traffic time
address for communication 1 rate setting [kBd] counter 0…255
A

Fig. 7. Main and submenus of the combined overcurrent and earth-fault relay module
SPCJ 4D28.
The procedure for entering a submenu 1MRS 750066-MUM EN: "General
or a setting mode, setting a value and charac- teristics of D-type SPC relay
entering the TEST mode is described in modules". A short guide follows:
detail in the manual

(activated when released)

21 21
Setting of
switchgroup Setting of Setting of switchgroup
4 switchgroup 6
SGF4 5 SGF5
SGF6

Setting of switchgroup
Setting of Setting of 6
switchgroup SGR6
4 5
switchgroup
SGR4
SGR5
Setting of switchgroup
11 SGR11
Setting of
switchgroup Setting of
9 SGR9 10
switchgroup
SGR10

Value of current
I L1, Value of current I L1,
3 4 event n-4
1 event n-3

Value of current
I L2, Value of current I L2,
3 4 event n-4
2 event n-3

Value of current
3 Value
I L3 4 of
curre
3 event n-3 nt
IL3,
event
n-4

Duration of I>
starting, Duration of I> Number of I>
3 event n-3 4 starting, starts since
4 event n-4 5 latest reset

Duration of I>>
3 starting, event n-3 Duration of I>>
5 4 starting, event n-4 Number of I>>
5 starts since
latest reset

Value of current
3 Io, event n-3 Value of current
6 4 Io, event n-4

Duration of Io>
7 3 starting, event n-3 Duration of Io>
4 starting, event n-4 Number of Io>
5 starts since
latest reset
Duration of Io>>
8 3 starting, event n-3 Duration of Io>>
4 starting, event n-4
Number of Io>>
5 starts since latest
reset

Value of current
Value of current
5 Number of I>
I,
3 event n-3 4 I, starts since
9 event n-4 latest reset

Password for
altering Selection of main Operate
3 settings 4 vs. time for
A the
second settings 5 CB-failure
protection

Time/current The overcurrent stage I> and the low- At the IDMT characteristic, the operate
characteristics set re- sidual current stage I0> can be time of the stage will be a function of the
(modified 2002- given definite time or an inverse definite current: the higher the current, the
05) time operation char- acteristic. The shorter is the operate time. Six
settings of the switches SGF1/ time/current curve groups are avail- able.
1...3 determine the mode of operation of Four of these comply with the BS 142 and
stage I> and the switches SGF1/6…8 that IEC 255 standards and two curve groups,
of the stage I0>. See section "Setting the RI and the RXIDG curve groups are
switches". special type curve groups according to
ABB praxis.
Characteristic
s according to The relay module incorporates four The values of the constants and
IEC 60255 internation- ally standardized time/current determine the slope as follows:
and BS 142 curve groups named "extremely inverse",
"very inverse", "normal in- verse" Time/current
and
"long-time inverse". The relationship curve group
between time and current is in accordance
with the standards BS 142 and IEC 60255-
Normal inverse
3, and can be expressed as follows: Very inverse
Extremely inverse
Long-time inverse
kx
t [s] =

22 22
I The standard BS 142.1966 defines the
( ) I
-1
normal current range to be 2...20 times
> the setting value. In addition, the relay
where t = operate time has to start at the latest when the current
k = time exceeds the setting value by 1.3 times, if
multiplier the time/current characteristic is normal
I = phase current inverse, very inverse or extremely in-
value verse. For the long-time inverse
I> = set current characteristic the normal current range is
value specified to be 2...7 times the setting and
the relay is to start when the current
exceeds the setting value by 1.1 times.

The operate time tolerances specified by


the standard are as follows (E denotes
accuracy in per cent, - = not specified):

I/I>

2
5
7
10
20
In the normal current ranges specified N
above the inverse time stages of the ot
overcurrent and earth- fault relay e.
module SPCJ 4D28 fulfil the toler- The actual operate time of the relay,
ance requirements of class 5 at all presented in the graphs in Fig. 8…11,
degrees of inversity. includes an addi- tional filter and
detection time plus the operate time of the
The time/current characteristics trip output relay. When the operate time
according to the IEC and BS standards of the relay is calculated using the math-
are illustrated in Fig. ematical expression above, these additional
8 times of about 30 ms in total have to be
… added to the time received.
11
.
RI-type The RI-type characteristic is a special where t = operate time in
characteristi character- istic that is principally used seconds k = time
c to obtain time grading with mechanical multiplier
relays. The character- istic can be I = phase current
expressed by the mathematical ex- I> = set start
pression current

t [s] = k The characteristic is illustrated in Fig. 12.

0.339 - 0.236 x I> I

RXIDG-
The RXIDG-type characteristic is a special
type Mathematically, the time/current
char- acteristic that is principally used in
characteristi characteristic can be expressed as follows:
earth-fault protection, in which a high
c k x I>
degree of selectivity

case the protection can operate in a


( )
selective
is required also at high-resistance faults. way, even if they
In this are not
directional.
23 23
t [s] = 5.8-1.35 x loge I I = phase current
I> = set start
current
where t = operate time in seconds k = time
The characteristic is illustrated in Fig. 13.
multiplier

24 24
t/s
70
60
50

40

30

20

10
9
8
7
6
5

1
0.9
0.8
0.7
0.6

0.5

0.4

0.3

0.2

0.1
0.09
0.08

0.06

0.04

0.03

0.02 2 3 4 5 6 7 8 9 10 20 I/I>
1

Fig. 8. Inverse-time characteristics of overcurrent and earth-fault relay module SPCJ 4D28

Extremely inverse
t/s
70
60
50

40

30

20

10
9
8
7
6
5

0.8
0.7
0.6
0.5

0.3

0.2

0.1
0.09
0.08
0.07

5
0.05

0.04

0.03

0.02 1 2 3 4 5 6 7 8 9 10 20 I/I>

Fig. 9. Inverse-time characteristics of overcurrent and earth-fault relay module SPCJ 4D28

Very inverse
t/s
70
60
50

40

30

20

10
9
8
7
6
5

0.9
0.8
0.7
0.6

0.4

0.3

0.2

0.1
0.09
0.08
0.07
0.06
0.05

0.04

0.03

0.021 2 3 4 5 6 7 8 9 10 20 I/I>

Fig. 10. Inverse-time characteristics of overcurrent and earth-fault relay module SPCJ 4D28

Normal inverse
t/s
700
600
500

400

300

200

100
90
80
70
60
50

Fig. 11. Inverse-time characteristics of overcurrent and earth-fault relay module SPCJ 4D28

Long-time inverse
t/s

70
60
50

40

30

20

10
9
8
7
6
5

4 k

3 1.0
0.9
0.8
2 0.7
0.6
0.5
0.4
0.3
1
0.9
0.8
0.2
0.7
0.6
0.5

0.4
0.3 0.1

0.2 0.05

0.1
0.09
0.08
0.07
0.06
0.05

0.04

0.03

0.02 1 2 3 4 5 6 7 8 9 10 20 I/I>

Fig. 12. Inverse-time characteristic of overcurrent and earth-fault relay module SPCJ 4D28

RI-type inverse
t/s

70
60
50

40

30

20

10
9
8
7
6
5

k
1
0.9
0.8 1.0
0.7
0.9
0.6
0.5 0.8

0.4 0.7

0.3

0.2

0.6

0.1
0.09
0.08
0.07
0.06
0.05

0.04

0.03

0.02 1 2 3 4 5 6 7 8 9 10 20 30 40 I/I>

Fig. 13. Inverse-time characteristic of overcurrent and earth-fault relay module SPCJ 4D28

RXIDG-type inverse
Technical data Feature Stage I> Stage I>> Stage I>>>

Start current
- at definite time 0.5…5.0 x In 0.5…40.0 x In and 0.5…40.0 x In and
- at inverse time 0.5…2.5 x In
Start time, typ. 70 ms 40 ms 40 ms
Operate time at definite 0.05…300 s 0.04…300 s 0.04…30 s
time characteristic
Time/current characteristic Extremely inv.
at inverse mode Very inv.
Normal inv.
Long-time inv.
RI type inv.
RXIDG type inv.
Time multiplier k 0.05…1.0
Reset time, typ. 40 ms 40 ms 40 ms
Retardation time <30 ms <30 ms <30
ms Reset ratio, typ. 0.96 0.96
0.96
Operate time accuracy 2% of set 2% of set 2% of set
at definite time mode value or 25 ms value or 25 ms value or 25 ms
Accuracy class index E 5
at inverse time mode
Operation accuracy 3% of set value 3% of set value 3% of set value

Feature

Start current
Start time, typ.
Operate time at definite
time characteristic
Time/current characteristic
at inverse mode

Time multiplier k
Reset time, typ.
Retardation time
Reset ratio, typ.
Operate time accuracy
at definite time mode
Accuracy class index E
at inverse time mode
Operation accuracy
set value
Serial The start and operate situations of the to be communicated, is marked with a multi-
communication protec- tion stages and the states of the plier 1. The event mask is formed by the sum
parameters output signals are defined as events and of the weight factors of all those events, that
provided with event codes, which can be are to be communicated.
Event codes transmitted to higher sys- tem levels via the
serial bus. An event, which is

Event mask

V155
V156
V157
V158

Event codes of the combined overcurrent and earth-fault relay module SPCJ 4D28

Code Event
E1 Starting of stage I> Starting of stage I>
E2 Tripping of stage I>>> reset
E3
E4
E5
E6
E7
E8
E9
E10
E11
E12

Default value of event mask V155

E13 Starting of stage I0>


E14 Starting of stage I0> reset
E15 Tripping of stage I0>
E16 Tripping of stage I0> reset
E17 Starting of stage I0>>
E18 Starting of stage I0>> reset
E19 Tripping of stage I0>>
E20 Tripping of stage I0>> reset
E21 Starting of stage I>
E22 Starting of stage I> reset
E23 Tripping of stage I>
E24 Tripping of stage I> reset

Default value of event mask V156


Code Event

E25 Output signal SS1 activated Output s


E26
E27
E28
E29
E30
E31
E32

Default value of event mask V157

E33 Output signal SS3 activated Output s


E34 Circuit breaker failure protection oper
E35 Circuit breaker failure protection rese
E36
E37
E38
E39
E40
E41
E42

Default value of event mask V158

E50 Restart of microprocessor


E51 Overflow of event register
E52 Temporary interruption in data comm
E53 No response from the module over the
communication
E54 The module responds again over the d

Explanations:
0 not included in event reporting
1 included in event reporting
* no code number
- cannot be programmed

Note.
The event represented by the codes E52...E54
are generated by a higher-level control data
communicator, for example type SRIO
1000M.
Remote transfer data In addition to the event data all input data 999. The default
(I data), setting values (S values), recorded password is 1.
infor- mation (V data) and certain other data
of the overcurrent module can be read via the The password is
SPA bus. Parameters marked with a W opened by writing the
letter can be altered via the SPA bus. password number to
parameter V160 and
When setting values are altered via the MMI closed by writ- ing
on the front panel or via the serial bus, the the password number
module checks that the entered parameter to parameter V161.
values are within the permitted setting
range. The relay module refuses to accept a
too high or a too low setting value, but
keeps the old setting value unchanged.

Altering parameter values via the serial bus


usually requires the use of a password. The
password is a number within the range 1…
The password is also closed on loss of auxiliary supply to the relay If an incorrect password is given seven times in
module. a row via the serial bus, the password is auto-
matically set to zero and after this it cannot
The password can be changed via the serial bus or via the MMI of be opened via the serial bus. Now the password
the module. When the password is to be changed via the serial bus, can be opened only via the MMI of the
the password must be opened first. The new pass- word is written to module.
parameter V161. The change of the password via the MMI of the
module is carried out in register A, subregister 3, in which case the R = readable data
new password is written over the old one. W = writable data
(P) = writing enabled with password

Input The measured currents and the status of the When the value of parameters I6…I8 is 1, the
s external control signals can be read (R) with corresponding control inputs are energized.
parameters I1…I8.
Information

Current measured on phase L1


Current measured on phase L2
Current measured on phase L3
Residual current measured
Maximum phase current difference
Control signal BS1
Control signal BS2
Control signal RRES (BS3)

Outputs The state information indicates the state of a module. When the value = 0, the signal has
signal at a certain moment. The recorded not been activated and when the value = 1, the
func- tions indicate such activations of signal has been activated.
signals, that happen after the last reset of the
registers of the

Output stages

States of the protection stages

Starting of stage I>


Tripping of stage I>
Starting of stage I>>
Tripping of stage I>>
Starting of stage I>>>
Tripping of stage I>>>
Starting of stage I0>
Tripping of stage I0>
Starting of stage I0>>
Tripping of stage I0>>
Tripping of stage I>

Output signals

Operation of output signals

Output signal SS1


Output signal TS1
Output signal SS2
Output signal TS2
Output signal SS3
Output signal TS3
Output signal SS4
Output signal TS4

Enable of output signals SS1…TS4


Setting values
Variable

Start current of stage I>


Operate time or
time multiplier k of stage I>
Start current of stage I>>
Operate time of stage I>>
Start current of stage I>>>
Operate time of stage I>>>
Start current of stage I0>
Operate time or
time multiplier k of stage I0>
Start current of stage I0>>
Operate time of stage I0>>
Start value of stage I>
Operate time of stage I>

Checksum, SGF 1
Checksum, SGF 2
Checksum, SGF 3
Checksum, SGF 4
Checksum, SGF 5
Checksum, SGF 6
Checksum, SGF 7
Checksum, SGF 8

Checksum, SGB 1
Checksum, SGB 2
Checksum, SGB 3

Checksum, SGR 1
Checksum, SGR 2
Checksum, SGR 3
Checksum, SGR 4
Checksum, SGR 5
Checksum, SGR 6
Checksum, SGR 7
Checksum, SGR 8
Checksum, SGR 9
Checksum, SGR 10
Checksum, SGR 11

Operate time of the circuit breaker failure protection

*) If the protection stage has been set out of function, the display shows 999 for the currently used value.
Measured and
Measured value
recorded parameter
values
Last 15 min maximum demand current
Number of starts of stage I>
Number of starts of stage I>>
Number of starts of stage I0>
Number of starts of stage I0>>
Number of starts of stage I>
Stage/phase that caused operation

Stage/phase that caused operation

Operation indication code on the display


Maximum 15 min demand current
The last five recorded values can be read (R) the youngest recorded value and n-1 the
with parameters V11…V59. Event n denotes next youngest and so forth.

Registered value

Phase current IL1


(register 1)
Phase current IL2
(register 2)
Phase current IL3
(register 3)
Earth-fault current I0
(register 6)
Difference current I (register 9)
Start duration, stage I> (register 4)
Start duration, stage I>> (register 5)
Start duration, stage I0> (register 7)
Start duration, stage I0>> (register 8)
Control parameters Information

Resetting of operation indicators and latched output relay


Resetting of indicators and latched output relay and clearing of registers Remote control of setting

Overcurrent even mask Residual/unbalance current event mask Output signal event mask

Output signal event mask

Opening of password for remote setting Changing and closing of password for remote setting
Activation of self-supervision system

Formatting of EEPROM Fault code


Data communication address of relay module
Data transfer rate

Program version
Reading of event register

Rereading of event register

Type designation of relay module


Reading of module state data

Resetting of module state data


Time reading and setting

The maximum capacity of the event register is general, the control data communicator reads
65 events. The content of the register can be read by the L command, the event data and forwards the information to
5 events at a time, only once. Should a fault occur, say, in the data an output device. Under normal conditions
communication, the B command can be used to re-read the contents of the event register of the relay module is empty.
the register. When required, the B command can be repeated. In The control data communicator also resets
abnor- mal status data, so this data is
normally zero.
Fault codes Once the self-supervision system has detected number one (1) and a green code number that
an internal relay fault, the IRF indicator on identifies the fault type. The fault codes
the front panel of the relay module is lit. At the should be recorded and stated when service is
same time the self-supervision alarm relay ordered.
that is normally picked up, drops off. In
most situa- tions a fault code appears on the The table below lists some of the fault codes
display of the relay module. This fault code of the combined overcurrent and earth-fault
consists of a red relay module SPCJ 4D28.

Fault code

4
30
50
51
52
53
54
56
195
131
67
203
139
75
252
253
General characteristics of
D-type relay modules
User´s manual and Technical description

3I> Relay symbol


Fastening screw I
I L1 I L2 I L3
I o IRF Self-supervision alarm indicator
Indicators for measured
quantities (Internal Relay Fault)

Display, 1 + 3 digits

I > /I RESET
n STEP

t > [s]
k Reset / Step push-button
I >> / I
n
Indicators for setting t >> [s]
parameters
I o >/ I
n
t o > [s]
ko

I o >> /I
PROGRAM

n to Programming push-button
Indicators for switchgroups
SGF, SGB and SGR >> [s]

SGF

SGB TRIP Trip indicator

SGR
879B

SPCJ 4D29 Module type designation


Fastening screw
1MRS 750066-MUM EN
General characteristics
Issued 95-04-12
Version A (replaces 34 SPC 3 EN1) of D type relay modules
Checked JH
Approved TK

Data subject to change without notice

Contents Front panel lay-out ......................................................................................................... 1


Control push buttons ..................................................................................................... 3
Display ........................................................................................................................... 3
Display main menu ................................................................................................... 3
Display submenus ..................................................................................................... 3
Selector switchgroups SGF, SGB, SGR .......................................................................... 4
Settings ........................................................................................................................... 4
Setting mode ............................................................................................................. 4
Example 1: Setting of relay operation values .............................................................. 7
Example 2: Setting of relay switchgroups ................................................................... 9
Recorded information ................................................................................................... 11
Trip test function ......................................................................................................... 12
Example 3: Forced activation of outputs ................................................................. 13
Operation indicators ..................................................................................................... 15
Fault codes.................................................................................................................... 15
Control The front panel of the relay module certain position in the main menu to the
push-buttons contains two push buttons. The RESET / corre- sponding submenu, for entering the
STEP push button is used for resetting setting mode of a certain parameter and
operation indicators and for stepping together with the STEP push button for
forward or backward in the display main storing the set values. The different
menu or submenus. The PRO- GRAM push operations are described in the subsequent
button is used for moving from a paragraphs in this manual.

Display The measured and set values and the recorded When the auxiliary voltage of a protection
data are shown on the display of the relay module is switched on the module
protection relay module. The display consists initially tests the display by stepping through
of four digits. The three green digits to the all the segments of the display for about 15
right show the measured, set or recorded value seconds. At first the corresponding segments
and the leftmost red digit shows the code of all digits are lit one by one clockwise,
number of the register. The measured or set including the decimal points. Then the center
value displayed is indicated by the adjacent segment of each digit is lit one by one. The
yellow LED indicator on the front panel. complete sequence is carried out twice. When
When a recorded fault value is being displayed the test is finished the display turns dark. The
the red digit shows the number of the testing can be interrupted by pressing the
corresponding register. When the display STEP push button. The protection func-
func- tions as an operation indicator the red tions of the relay module are alerted
digit alone is shown. throughout the testing.

Display main menu Any data required during normal operation When the push
are accessible in the main menu i.e. present button is pressed for
meas- ured values, present setting values and about 0.5 seconds,
recorded parameter values. the display moves
backward in the
The data to be shown in the main menu are display sequence.
sequentially called up for display by means of
the STEP push button. When the STEP push
button is pressed for about one second, the
display moves forward in the display sequence.

41 41
From a dark display only forward movement is possible. When the Unless the display is switched off by stepping
STEP push button is pushed constantly, the display continuously to the dark point, it remains lit for about 5
moves for- ward stopping for a while in the dark position. minutes from the moment the STEP push
button was last pushed. After the 5 minutes'
time-out the dispaly is switched off.

Display submenus Less important values and values not very the display moves forward when the STEP
often set are displayed in the submenus. The push button is pushed for one second and
number of submenus varies with different backward when it is pushed for 0.5 seconds.
relay module types. The submenus are The main menu has been re-entered when the
presented in the de- scription of the red display turns dark.
concerned protection relay module.
When a submenu is entered from a main
A submenu is entered from the main menu menu of a measured or set value indicated by
by pressing the PROGRAM push button for a LED indicator, the indicator remains lit and
about one second. When the push button is the ad- dress window of the display starts
released, the red digit of the display starts flashing. A submenu position is indicated by a
flashing, indi- cating that a submenu has been flashing red address number alone on the
entered. Going from one submenu to dispaly without any lit set value LED
another or back to the main menu follows indicator on the front panel.
the same principle as when moving from the
main menu display to another;
Selector switch- Part of the settings and the selections of the
groups SGF, SGB operation characteristic of the relay modules Switch No Pos. Weigth Value
and SGR in various applications are made with the
selector
switchgroups SG_ . The switchgroups are 1 1 x 1 = 1
soft- 2 0 x 2 = 0
ware based and thus not physically to be found 3 1 x 4 = 4
in the hardware of the relay module. The 4 1 x 8 = 8
indi- cator of the switchgroup is lit when the 5 1 x 16 = 16
checksum of the switchgroup is shown on 6 0 x 32 = 0
the display. Starting from the displayed 7 1 x 64 = 64
checksum and by entering the setting mode, 8 0 x 128 = 0
the switches can be set one by one as if they
were real physical switches. At the end of the Checksum = 93
setting procedure, a checksum for the whole
switchgroup is shown. The checksum can be
used for verifying that the switches have been Fig. 2. Example of calculating the checksum of
properly set. Fig. 2 shows an example of a a selector switchgroup SG_.
manual checksum calculation.
The functions of the selector switches of the
When the checksum calculated according to different protection relay modules are described
the example equals the checksum indicated in detail in the manuals of the different
on the display of the relay module, the relay modules.
switches in the concerned switchgroup are
properly set.

Settings Most of the start values and operate times are and the second settings can be done in three
set by means of the display and the push different ways:
buttons on the front panel of the relay
modules. Each setting has its related indicator 1) By command V150 over the serial
which is lit when the concerned setting value communi- cation bus
is shown on the display. 2) By an external control signal BS1, BS2 or
RRES (BS3)
In addition to the main stack of setting values 3) Via the push-buttons of the relay module,
most D type relay modules allow a second see submenu 4 of register A.
stack of settings. Switching between the main
settings

Setting mode Generally, when a large number of settings is relay systems, it is


to be altered, e.g. during commissioning of recommended that
42 42
the relay set- tings are entered with the cursor is moved on from digit to digit by
keyboard of a personal computer provided press- ing the PROGRAM push button and
with the necessary software. When no in each stop the setting is performed with
computer nor software is available or when the STEP push button. After the parameter
only a few setting values need to be altered values have been set, the decimal point is put
the procedure described below is used. in place. At the end the position with the
whole display flashing is reached again and
The registers of the main menu and the the data is ready to be stored.
submenus contain all parameters that can
be set. The settings are made in the so called A set value is recorded in the memory by
setting mode, which is accessible from the press- ing the push buttons STEP and
main menu or a submenu by pressing the PROGRAM simultaneously. Until the new
PROGRAM push button, until the whole value has been recorded a return from the
display starts flashing. This position indicates setting mode will have no effect on the
the value of the param- eter before it has been setting and the former value will still be
altered. By pressing the PROGRAM push valid. Furthermore any attempt to make a
button the programming se- quence moves setting outside the permitted limits for a
forward one step. First the rightmost digit particular parameter will cause the new value to
starts flashing while the rest of the display is be disqualified and the former value will be
steady. The flashing digit is set by means of main- tained. Return from the setting mode
the STEP push button. The flashing to the main menu or a submenu is possible by
pressing the PROGRAM push button until
the green digits on the display stop flashing.
NOTE! During any local man-machine com- any doubt about the settings of the module to be
munication over the push buttons and the dis- play inserted, the setting values should be read using a
on the front panel a five minute time-out function spare relay unit or with the relay trip circuits
is active. Thus, if no push button has been pressed disconnected. If this cannot be done the relay
during the last five minutes, the relay returns to can be sett into a non-tripping mode by pressing
its normal state automatically. This means that the the PROGRAM push button and powering up
display turns dark, the relay escapes from a display the relay module simultaneously. The display
mode, a programming routine or any routine will show three dashes "- - -" to indicate the non-
going on, when the relay is left untouched. This is tripping mode. The serial communication is
a convenient way out of any situation when the operative and all main and submenues are acces-
user does not know what to do. sible. In the non-tripping mode unnecessary
trippings are avoided and the settings can be
Before a relay module is inserted into the relay checked. The normal protection relay mode is
case, one must assure that the module has been entered automatically after a timeout of five
given the correct settings. If there however is minutes or ten seconds after the dark display
position of the main menu has been entered.

MAIN MENU SUBMENU SETTING MODE


REV. STEP 0,5 s
STEP 0,5 s PROGRAM 1 s PROGRAM 5 s PROGRAM 5 s
FWD.STEP 1 s

Normal status, display off

First measuring value

REV. STEP 0,5 s


STEP 0,5 s

Last measuring value FWD.STEP 1 s

Main setting value 1


1 for stage 1
Actual setting value 1

Actual setting value 2


MOVE FIGURE OR DECIMAL POINT
CURSOR WITH BUTTON PROGRAM 1 s

STEP AND PROGRAM SIMULTANEOUSLY WHEN


THE VALUE IS READY AND THE WHOLE DISPLAY IS
BLINKING

43 43
NOTE! IN MOST MENU CHARTS THE SUBMENUS HAVE BEEN DRAWN IN A HORIZONTAL DIRECTION IN ORDER TO GET ALL
MAIN AND SUBMENU POSITIONS SHOWN IN THE SAME CHART.

Fig.3. Basic principles of entering the main menus and submenus of a relay module.

44 44
MAIN MENU SUBMENUS

STEP 0.5 s PROGRAM 1


s

Normal status, display off

Current on phase L1

Current on phase L2

Current on phase L3
REV. STEP 0.5 SUBMENU FWD. STEP 1 s
Neutral current Io S
s

2 Second
Actual start value I> setting value
1 Main
setting for I>
value for I>

Actual operate time t>


or multiplier k for 1 Main setting 2 Second setting
stage I> value for t> or value for t> or
k k

Actual start value I>> Main Second


1 setting 2 setting value
value for for I>>
Actual operate time I>>

2 Second
t>> 1 Main setting value
setting for t>>
R
of stage I>> value for
E t>>
V.
2 Second
Actual start value Io> setting value
S 1 Main for Io>
T setting
E value for
P Actual operate time to> Io> Second setting
or multiplier ko 2 value for to> or
.5
Main setting ko
s 1
value for to> or
M Actual start value Io>> ko
A 2 Second
setting value
I for Io>>
N 1 Main setting
Actual operate time value for
to>> Io>>
Second
2 setting value
M Main setting for to>>
Actual setting of 1 value for
functional
E to>> Main setting of
switchgroup SGF1 2
N SGF2 checksum
U
1 Main setting of
SGF1 checksum
Actual setting of blocking 1 Main setting of 2 Second setting of
switchgroup SGB SGB checksum SGB
F
W
checksum
D.
Actual setting of relay 1 Main setting of
2 Main setting of
S switchgroup SGR1 SGR1 SGR2 checksum
T checksum
E
P
1
Latest memorized, event
1 Event (n-1) 2 Event (n-2)
(n) value of phase value of phase L1
1
value of phase L1 L1
s 2 Event (n-2)
Latest memorized, event value of phase L2
2 1 Event (n-1)
(n) value of phase
L2 Event (n-2)
value of phase L2 2
value of phase L3
Latest memorized, event 1 Event (n-1)
3 value of phase
(n) L3
value of phase L3
1 Highest maximum
Maximum demand demand value
current found
4
value for 15 minutes

Fig. 4.Example of part of the main and submenus for the settings of the overcurrent and earth-
fault relay module SPCJ 4D29. The settings currently in use are in the main manu and they are
displayed by pressing the STEP push button. The main menu also includes the measured
current values, the registers 1...9, 0 and A. The main and second setting values are located in
the submenus and are called up on the display with the PROGRAM push button.
Example 1 Operation in the setting mode. Manual for the main setting is 0.80 x I and for the
n
setting of the main setting of the start current second setting 1.00 x I . The desired main
n
value I> of an overcurrent relay module. The start value is 1.05 x I .
n
initial value
a)
Press push button STEP repeatedly until the RESE
T 5x1s
LED close to the I> symbol is lit and the STEP

current start value appears on the display.

b) PROGRAM
Enter the submenu to get the main setting 1s
value by pressing the PROGRAM push
button more than one second and then 1 0. 8 0
releasing it. The red display digit now shows
a flashing number 1, indicating the first
submenu position and the green digits show
the set value.
PROGRAM

c)
Enter the setting mode by pressing the PRO-
5s
1 0. 8 0
GRAM push button for five seconds until the
display starts flashing.

1 0. 8 0
PROGRAM

d) 1s
Press the PROGRAM push button once again
for one second to get the rightmost digit
flash- ing.

RESE
T

1 0. 8 5
STEP
e) 5x
Now the flashing digit can be altered. Use the
STEP push button to set the digit to the
desired value.

PROGRAM

1s
f)
Press the PROGRAM push button to make 1 0. 8 5
the middle one of the green digits flash.

RESE
T
STEP
g) 2x
Set the middle digit with of the STEP push
button. 1 0. 0 5

PROGRAM
h) 1s
Press the PROGRAM push button to make
the leftmost green digit flash. 1 0. 0 5
i) l)
Set the digit with the STEP push P
button. re
If ss
move th
decima e
point P
the R
j) STE O
Press the PROGRAM push button to make button. G
the decimal point flash. R
A
M
RESE
push button to make the whole display flash. T
STEP
In this position, corre- sponding to position
c) above, one can see the new value before it
is recorded. If the value needs changing, use
0x 1 1. 0 5
the PROGRAM push but- ton to alter the
value.

PROGRAM
m) 1s
When the new value has been corrected,
record it in the memory of the relay module by
1 1. 0 5
pressing the PROGRAM and STEP push
buttons simul- taneously. At the moment the
information en- ters the memory, the green
dashes flash once in the display, i.e. 1 - - -. RESE
T
STEP

0x 1 1. 0 5

PROGRAM

1s
1 1. 0 5

RESE
T
STEP

1 - - -
PROGRAM

n)
1
PROGRAM
Recording of the new value automatically 5s
initi- ates a return from the setting mode to
the normal submenu. Without recording one
can leave the setting mode any time by
pressing the PROGRAM push button for
about five sec- onds, until the green display
digits stop flashing.
RESE
o) T
STEP
If the second setting is to be altered, enter 1s
submenu position 2 of the setting I> by
pressing the STEP push button for approx.
one second. The flashing position indicator 1
will then be replaced by a flashing number 2
which indicates that the setting shown on
the display is the second setting for I>.
until the first digit is switched off. The LED
Enter the setting mode as in step c) and still shows that one is in the I> position and
proceed in the same way. After recording the display shows the new setting value
of the re- quested values return to the currently in use by the relay module.
main menu is obtained by pressing the
STEP push button
Example 2 Operation in the setting mode. Manual The initial value for the checksum is 000 and
setting of the main setting of the checksum the switches
for the switchgroup SGF1 of a relay module.
SGF1/1an are to be set in position 1. This means that a
d SGF1/3 checksum of 005 should be the final result.

a) RESE
T nx1s
Press push button STEP until the LED close STEP

to the SGF symbol is lit and the checksum


appears on the display.
PROGRA
b) M

Enter the submenu to get the main checksum 1s


of SGF1 by pressing the PROGRAM push
button for more than one second and then 1 0 0 0
releasing it. The red display now shows a
flashing number 1 indicating the first
submenu position and the green digits show
the checksum.
PROGRA
M
c) 5s
Enter the setting mode by pressing the PRO-
GRAM push button for five seconds until the 1 0 0 0
display starts flashing.

d) PROGRA
M

Press the PROGRAM push button once 1x


again to get the first switch position. The first
digit of the display now shows the switch
number. The position of the switch is shown
by the rightmost digit.
1
e) RESE
T
The switch position can now be toggled STEP

be- tween 1 and 0 by means of the STEP 1x


push button and it is left in the requested
position 1.

f) PROGRA
1
When switch number 1 is in the requested M

position, switch number 2 is called up by 1s


press- ing the PROGRAM push button for
one sec- ond. As in step e), the switch
position can be altered by using the STEP
push button. As the desired setting for
SGF1/2 is 0 the switch is left in the 0 1
position. PROGRA
M
1s
g
)
Switch SGF1/3 is called up as in step f) by
pressing the PROGRAM push button for
about one second.

h) Usin b
The switch position is altered to the desired procedur
position 1 by pressing the STEP push button switche
once. 4... In
and settin
th position
in correspond-
in
i) th
RESE
ased on the set switch positions is shown. 1x
1 3 1
T
STEP

PROGRAM 5x1s

1 0 0 5
k) RESE
If the correct checksum has been obtained, it T
STEP
is recorded in the memory by pressing the
push buttons PROGRAM and STEP 1 - - -
simultaneously. At the moment the
information enters the memory, the green
dashes flash in the display, i.e.1 - - -. If the PROGRAM

checksum is incorrect, the setting of the


separate switches is repeated using the
PROGRAM and STEP push buttons start-
ing from step d).

l)
Recording the new value automatically PROGRAM
5s
initiates a return from the setting mode to
the normal menu. Without recording one 1 0 0 5
can leave the setting mode any time by
pressing the PRO- GRAM push button for
about five seconds, until the green display
digits stop flashing.

m) RESE
T
After recording the desired values return to the STEP
nx1s
main menu is obtained by pressing the STEP
push button until the first digit is turned off.
The LED indicator SGF still shows that one is
in the SGF position and that the display
shows the new checksum for SGF1 currently
in use by the relay module.

Recorded The parameter values measured at the moment regis- ters are illustrated in the descriptions
information when a fault occurs or at the trip instant are of the different relay modules. Additionally,
recorded in the registers. The recorded data, the sys- tem front panel of the relay contains a
except for some parameters, are set to zero simplified list of the data recorded by the
by pressing the push buttons STEP and various relay modules of the protection relay.
PRO- GRAM simultaneously. The data in
normal registers are erased if the auxiliary All D type relay modules are provided with two
voltage supply to the relay is interrupted, only general registers: register 0 and register A.
the set values and certain other essential
parameters are maintained in non-volatile Register 0 contains, in coded form, the
registers during a voltage failure. informa- tion about e.g. external blocking
signals, status information and other signals.
The number of registers varies with different The codes are explained in the manuals of the
relay module types. The functions of the different relay modules.
Submenu 2 of register A contains a bus The default value is 001 for the address code,
Register A commu- nication monitor for the SPAbus. If 9.6 kilobaud for the data transfer rate and
contains the the protec- tion relay, which contains the 001 for the password.
address code of relay module, is linked to a system
the relay including a contol data communicatoe, for In order to secure the setting values, all
modul which is instance SRIO 1000M and the data settings are recorded in two separate
reqiured by the communication system is operating, the memory banks within the non-volatile
serial counter reading of the monitor will be zero. memory. Each bank is complete with its
communi- Otherwise the digits 1...255 are own checksum test to verify the condition of
cation system. continuously scrolling in the monitor. the memory contents. If, for some reason,
the contents of one bank is disturbed, all
Submenu 1 of Submenu 3 contains the password required settings are taken from the other bank and
register A for changing the remote settings. The address the contents from here is transferred to the
contains the code, the data transfer rate of the serial faulty memory region, all while the relay is in
data trans- fer communica- tion and the password can be set full operation condition. If both memory
rate value, manually or via the serial communication banks are simultaneously damaged the relay
expressed in bus. For manual set- ting see example 1. will be be set out of operation, and an alarm
kilobaud, of signal will be given over the serial port and
the serial the IRF output relay
communicatio
n.
Trip test function Register 0 also provides access to a trip test The selected starting or tripping is activated
function, which allows the output signals of by simultaneous pressing of the push
the relay module to be activated one by one. buttons STEP and PROGRAM. The signal
If the auxiliary relay module of the protection remains activated as long as the two push
assem- bly is in place, the auxiliary relays butttons are pressed. The effect on the output
then will operate one by one during the relays depends on the configuration of the
testing. output relay matrix switches.
When pressing the PROGRAM push button The self-supervision output is activated by
for about five seconds, the green digits to press- ing the STEP push button 1 second
the right start flashing indicating that the when no setting indicator is flashing. The IRF
relay module is in the test position. The output is activated in about 1 second after
indicators of the settings indicate by flashing pressing of the STEP push button.
which output signal can be activated. The
required output function is selected by pressing
the PROGRAM push button for about one The signals are selected in the order illustrated
second. in
Fig. 4.
The indicators of the setting quantities refer to
the following output signals:

Setting I> Starting of stage I>


Setting t> Tripping of stage I>
Setting I>> Starting of stage I>>
Setting t>> Tripping of stage I>>
etc.
No indication Self-supervision IRF

IRF I> TRIP I» START I» TRIP Io> START Io> TRIP Io»START Io» TRIP
I> START
REGISTER 0
PROGRAM PROGRAM PROGRAM PROGRAM
I> PROGRAM PROGRAM PROGRAM PROGRAM PROGRAM PROGRAM
5s 1s 1s t> 1s 1s
I» 1s 1s 1s 1s 1s

Io» to»
Io> to>

Fig. 5.Sequence order for the selection of output signals in the Trip test mode
If, for instance, the indicator of the setting t> scheme, by pressing
is flashing, and the push buttons STEP and the PROGRAM push
PRO- GRAM are being pressed, the trip button for about
signal from the low-set overcurrent stage is five sec- onds.
activated. Re- turn to the main menu is
possible at any stage of the trip test sequence
Note! The effect on the output relays then depends
on the configuration of the output relay
matrix switchgroups SGR 1...3.
Example 3 Trip test function. Forced activation of the
outputs.

a)
Step forward on the display to register 0.
RESE
T
STEP nx1s

0
b) 3I>
Press the PROGRAM push button for about I

five seconds until the three green digits to the I L1 I L2 I L3 I o IRF

right.

PROGRAM
RESET
0 0 0 0
5s I > /I n STEP

t > [ s]
k

I >> / I n

t >>[s]

I o >/ I n
t o > [s]
ko

I o >> /I n
PROGRAM
t o >>[s]

SGF

SGB

SGR

c) TRIP

SPCJ 4D29
Hold down the STEP push button. After one
879B

second the red IRF indicator is lit and the


IRF output is activated. When the step push
button is released the IRF indicator is switched
off and the IRF output resets.

d) 3I>
I
Press the PROGRAM push button for one
second and the indicator of the topmost setting I I I IL1 IRF
L2 L3 o

start flashing.
0 0 0 0
e) RESET

If a start of the first stage is required, now


I > /I n
STEP

t > [ s]
press k

I >> / I n

the push-buttons PROGRAM and STEP t >> [s]

simul- taneously. The stage output will be I o >/ I n

activated and the output relays will operate t o > [s]


ko

according to the actual programming of I o >> /I n

t o >>[s]
the relay output switchgroups SGR. SGF
PROGRAM

SGB
RESE SGR
T
STEP
879B

TRIP

SPCJ 4D29

PROGRAM
f)
To proceed to the next position press the PRO- 3I>
I
GRAM push button for about 1 second until
0 0 0 0
I L1 I L2 I L3 I o IRF

the indicator of the second setting starts flash-


ing. I > /I n RESET
STEP
t > [ s]
PROGRAM k

1s I >> / I n

t >>[s]

I o >/ I n
t o > [s]
ko

I o >> /I n
PROGRAM
t o >>[s]

SGF

SGB

SGR

TRIP

SPCJ 4D29

879B
g) 3I>
Press the push buttons PROGRAM and STEP I

simultaneously to activate tripping of stage 1 L1 I L2 IL3 Io I

0 0 0 0
IRF

(e.g. the I> stage of the overcurrent module


SPCJ 4D29). The output relays will operate
according to the actual programming of the
RESET
I > /I n
relay switchgroups SGR. If the main trip relay k
t > [ s]
STEP

is operated the trip indicator of the I >> / I n

measuring module is lit. t >> [s]

I o >/ I n
RESE t o > [s]
T ko
STEP
I o >> /I n

t o >>[s]
PROGRAM
SGF

SGB

SGR

TRIP
PROGRAM
SPCJ 4D29
879B

h) It is possible to leave the trip test mode at any


The starting and tripping of the remaining step of the sequence scheme by pressing the
stages are activated in the same way as the PROGRAM push button for about five seconds
first stage above. The indicator of the until the three digits to the right stop
corresponding setting starts flashing to flashing.
indicate that the con- cerned stage can be
activated by pressing the STEP and
PROGRAM buttons simultaneously. For any
forced stage operation, the output relays will
respond according to the setting of the relay
output switchgroups SGR. Any time a
certain stage is selected that is not wanted to
operate, pressing the PROGRAM button once
more will pass by this position and move to
the next one without carrying out any
operation of the selected stage.

Operation A relay module is provided with a multiple of


indication separate operation stages, each with its own
operation indicator shown on the display and a
common trip indicator on the lower part of the
Fault codes front plate of the relay module.

The starting of a relay stage is indicated with


one number which changes to another number
when the stage supervision system detects a permanent fault indicator is reset by means of the RESET
operates. The in the relay module, the red IRF indicator on push button of the relay module. An unreset
indicator the front panel is lit . At the same time the opera- tion indicator does not affect the
remains glow- module puts forward a control signal to the function of the protection relay module.
ing although output relay of the self-supervision system of
the operation the protection relay. In certain cases the function of the operation
stage resets. indicators may deviate from the above princi-
The In most fault situations a fault code, ples. This is described in detail in the
indicating the nature of the fault, appears on descrip- tions of the separate modules.
the display of
In addition to
the protection
functions the the module. The fault code, which consists of
relay module a red figure "1" and a three digit green
is provided code number, cannot be removed from the
with a self- display by resetting. When a fault occurs, the
supervision fault code should be recorded and stated
sys- tem which when service is ordered. When in a fault
continuously mode, the normal relay menus are operative,
supervises the i.e. all setting values and measured values can
function of the be accessed although the relay operation is
microprocessor inhibited. The serial com- munication is also
, its program operative making it possible to access the
execution and relay information also from a remote site.
the electronics. The internal relay fault code shown on the
display remains active until the internal fault
Shortly after possibly disappears and can also be re-
the self- motely read out as variable V 169.
1MRS 750096-MUM

ABB Oy, Distribution Automation ABB Limited, Distribution Automation


P.O. Box 699 Maneja, Vadodara - 390013, India
FIN-65101 VAASA, Finland Tel. +91 265 260 4386
Tel. +358 10 22 11 Fax. +91 265 263 8922
Fax. +358 10 22 41094 www.abb.com/substationautomation
www.abb.com/substationautomation

Vous aimerez peut-être aussi