S= 125 MVA
V= 15,5 kV
125 𝑀𝑉𝐴
𝐼𝑏𝑎𝑠𝑒 = 4656.05 𝐴
√3 15.5𝑘𝑉
I= 4656.05 A
Datos a considerar
Generador
𝑋´´𝑑 = 𝑋1 = 𝑋2 = 0.2 𝑝. 𝑢.
𝑋0 = 0.03 𝑝. 𝑢.
Transformador
(125 𝑀𝑉𝐴)
𝑋𝑇 = 0,15 ∗
(150 𝑀𝑉𝐴)
𝑋𝑇 = 0,125 𝑝. 𝑢.
(125 𝑀𝑉𝐴)
𝑋𝑒𝑞 = 0,025 ∗
(150 𝑀𝑉𝐴)
𝑋𝑒𝑞 = 0,031 𝑝. 𝑢.
(125 𝑀𝑉𝐴)
𝑋0 = (0,004) ∗
(150 𝑀𝑉𝐴)
𝑋0 = 0,005 𝑝. 𝑢.
1∠0°
𝐼𝑓(0) = = −𝑗4.87 𝑝. 𝑢.
(𝑗0.087 + 𝑗0.087 + 𝑗0.03)
Diagrama de secuencia.
𝐼𝑔2(1) = 𝐼𝑔2(2)
𝑗0,2
𝐼𝑔2(1) = 𝐼𝑔2(2) = (−𝑗4,87) ( )
(𝑗0,2 + 𝑗0,125 + 𝑗0,031)
𝐼𝑔1(1) = 𝐼𝑔2(2)
𝐼𝑔1(0) = 22684.28 𝐴
𝐼𝑓𝐺1𝑎 1 1 1 −𝑗2.736
[ 𝐼𝑓𝐺1𝑏 ] = [1 𝑎2 𝑎 ] ∗ [−𝑗2.135]
𝐼𝑓𝐺1𝑐 1 𝑎 𝑎2 −𝑗2.135
𝐼𝑓𝐺2𝑎 1 1 1 0
[𝐼𝑓𝐺2𝑏 ] = [1 𝑎2 𝑎 ] ∗ [−𝑗2.736 − ( 1∠ − 30°)]
𝐼𝑓𝐺2𝑐 1 𝑎 𝑎2 −𝑗2.736 − ( 1∠30°)
Generador 1
7,006∠ − 90° 𝑆
[0,602∠ − 90°] ∗ ( 𝐼𝐵𝑎𝑠𝑒 ) ∗
0,602∠ − 90° 5000
5 5
𝐼𝑓𝐺1𝑎 ∗ 𝐼𝐵𝑎𝑠𝑒 ∗ = 7.006∠ − 90° ∗ 4656.05 ∗ = 32.62∠ − 90° 𝐴
5000 5000
5 5
𝐼𝑓𝐺1𝑏 ∗ 𝐼𝐵𝑎𝑠𝑒 ∗ = 0,602∠ − 90° ∗ 4656.05 ∗ = 2.803∠ − 90°𝐴
5000 5000
5 5
𝐼𝑓𝐺1𝑐 ∗ 𝐼𝐵𝑎𝑠𝑒 ∗ = 0,602∠ − 90° ∗ 4656.05 ∗ = 2.803∠ − 90° 𝐴
5000 5000
Generador 2
4,7389∠ − 90° 𝑆
[4,73889∠ − 90°] ∗ ( 𝐼𝐵𝑎𝑠𝑒 ) ∗
5000
0
5 5
𝐼𝑓𝐺2𝑎 ∗ 𝐼𝐵𝑎𝑠𝑒 ∗ = 4,7389∠ − 90° ∗ 4656.05 ∗ = 22.065∠ − 90° 𝐴
5000 5000
5 5
𝐼𝑓𝐺2𝑏 ∗ 𝐼𝐵𝑎𝑠𝑒 ∗ = 4,7389∠90° ∗ 4656.05 ∗ = 22.065∠90° 𝐴
5000 5000
5 5
𝐼𝑓𝐺2𝑐 ∗ 𝐼𝐵𝑎𝑠𝑒 ∗ = 0 ∗ 4656.05 ∗ =0
5000 5000
𝑍𝑒𝑞(0) = 0,03 𝑝𝑢
1∠0
𝐼𝑓𝑎𝑙𝑙𝑎(0) = = −𝑗4.87 𝑝𝑢
(2 ∗ (𝑗0.087) + 𝑗0.03)
Sabiendo que:
𝑆𝐵𝑎𝑠𝑒
𝐼𝐵𝑎𝑠𝑒 =
𝑉𝐵𝑎𝑠𝑒
125𝑀𝑉𝐴
𝐼𝐵𝑎𝑠𝑒 =
√3(15,5𝐾𝑉)
𝐼𝐵𝑎𝑠𝑒 = 4656,05 𝐴
Cálculo de la corriente del generador 2
𝑗0,2
𝐼𝑔2(1) = 𝐼𝑔2(1) = (−𝑗4,87) ( )
(𝑗0,2 + 𝑗0,125 + 𝑗0,031)
𝐼𝑔2(0) = 0 𝐴
𝐼𝑔1(0) = 22674,96 𝐴
En esta fase la protección no opera, esto se debe a que la falla se encuentra fuera de la
zona protegida.