Académique Documents
Professionnel Documents
Culture Documents
24/10/2018
GENOMICA
GENOMICA 24/10/2018
GENOMICA / Índice
Índice
GENOMICA
GENOMICA
LEDVANCE GmbH - PanelLED Value 600 40W/ 4000K (1xLED 4000K / CRI >= 80).....................................................................................3
Terreno 1
Edificación 3
Planta (nivel) 1
Local 2
Sinopsis de locales..................................................................................................................................................................................6
Plano de situación de luminarias.............................................................................................................................................................7
Lista de luminarias.................................................................................................................................................................................. 8
Plano útil 2 / Intensidad lumínica perpendicular (Adaptativamente)....................................................................................................... 9
Página 2
GENOMICA 24/10/2018
Terreno 1 / Edificación 3 / Planta (nivel) 1 / LEDVANCE GmbH 4058075066601 PanelLED Value 600 40W/ 4000K 1xLED 4000K /
CRI >= 80 / LEDVANCE GmbH - PanelLED Value 600 40W/ 4000K (1xLED 4000K / CRI >= 80)
Indicaciones colorimétricas
1xLED 4000K / CRI >= 80: CCT 4000 K, CRI 100
90° 90°
75° 75°
60° 60°
200
45° 45°
300
400
cd/klm η = 100%
C0 - C180 C90 - C270
Página 3
GENOMICA 24/10/2018
Terreno 1 / Edificación 3 / Planta (nivel) 1 / LEDVANCE GmbH 4058075066601 PanelLED Value 600 40W/ 4000K 1xLED 4000K /
CRI >= 80 / LEDVANCE GmbH - PanelLED Value 600 40W/ 4000K (1xLED 4000K / CRI >= 80)
320
240
160
80
E(0°) 5734
1.5 E(C90) 55.6° 517
0.50 1.3 E(C0) 53.2° 616
E(0°) 1434
2.9 E(C90) 55.6° 129
1.0 2.7 E(C0) 53.2° 154
E(0°) 637
4.4 E(C90) 55.6° 57
1.5 4.0 E(C0) 53.2° 68
E(0°) 358
5.8 E(C90) 55.6° 32
2.0 5.3 E(C0) 53.2° 39
E(0°) 229
7.3 E(C90) 55.6° 21
2.5 6.7 E(C0) 53.2° 25
E(0°) 159
8.8 E(C90) 55.6° 14
3.0 8.0 E(C0) 53.2° 17
Separación [m] Diámetro cónico [m] Intensidad lumínica [lx]
C0 - C180 (Semiángulo de dispersión: 106.4°)
C90 - C270 (Semiángulo de dispersión: 111.2°)
Página 4
GENOMICA 24/10/2018
Terreno 1 / Edificación 3 / Planta (nivel) 1 / LEDVANCE GmbH 4058075066601 PanelLED Value 600 40W/ 4000K 1xLED 4000K /
CRI >= 80 / LEDVANCE GmbH - PanelLED Value 600 40W/ 4000K (1xLED 4000K / CRI >= 80)
C270 C90
2000
3000
C315 C0 C45
cd/m²
g = 65.0° g = 75.0° g = 85.0°
2H 2H 17.3 18.6 17.6 18.9 19.1 17.5 18.8 17.8 19.1 19.3
3H 19.0 20.2 19.3 20.5 20.8 19.1 20.3 19.4 20.5 20.8
4H 19.8 20.9 20.1 21.2 21.5 19.7 20.8 20.0 21.1 21.4
6H 20.5 21.5 20.8 21.8 22.1 20.2 21.2 20.5 21.5 21.8
8H 20.7 21.7 21.1 22.0 22.4 20.3 21.3 20.7 21.6 22.0
12H 20.9 21.9 21.3 22.2 22.6 20.4 21.3 20.7 21.7 22.0
4H 2H 18.0 19.1 18.3 19.4 19.7 18.1 19.3 18.5 19.6 19.9
3H 19.9 20.9 20.3 21.2 21.6 19.9 20.9 20.3 21.2 21.5
4H 20.9 21.7 21.3 22.1 22.4 20.7 21.5 21.1 21.9 22.3
6H 21.7 22.4 22.1 22.8 23.2 21.3 22.0 21.7 22.4 22.8
8H 22.0 22.7 22.4 23.1 23.5 21.4 22.1 21.9 22.5 23.0
12H 22.3 22.9 22.7 23.3 23.7 21.6 22.2 22.0 22.6 23.0
8H 4H 21.2 21.9 21.6 22.3 22.7 21.0 21.7 21.5 22.1 22.5
6H 22.2 22.8 22.7 23.2 23.7 21.8 22.4 22.2 22.8 23.2
8H 22.6 23.1 23.1 23.6 24.1 22.1 22.6 22.6 23.0 23.5
12H 23.0 23.4 23.5 23.9 24.4 22.3 22.7 22.8 23.2 23.7
12H 4H 21.2 21.9 21.7 22.3 22.7 21.1 21.7 21.5 22.1 22.6
6H 22.3 22.8 22.8 23.2 23.7 21.9 22.4 22.4 22.9 23.3
8H 22.8 23.2 23.3 23.7 24.2 22.2 22.7 22.7 23.1 23.6
Variación de la posición del espectador para separaciones S entre luminarias
S = 1.0H +0.1 / -0.1 +0.1 / -0.1
S = 1.5H +0.2 / -0.3 +0.2 / -0.3
S = 2.0H +0.3 / -0.6 +0.4 / -0.6
Página 5
GENOMICA 24/10/2018
Local 2
Altura interior del local: 3.000 m, Grado de reflexión: Techo 70.0%, Paredes 50.0%, Suelo 20.0%, Factor de degradación: 0.80
Plano útil
Superficie Resultado Media (Nominal) Min Max Mín./medio Mín./máx.
1 Plano útil 2 Intensidad lumínica perpendicular (Adaptativamente) [lx] 507 (≥ 500) 281 650 0.55 0.43
Altura: 0.800 m, Zona marginal: 0.000 m
12 LEDVANCE GmbH - 4058075066601 PanelLED Value 600 40W/ 4000 40.0 100.0
4000K
Potencia específica de conexión: 7.97 W/m² = 1.57 W/m²/100 lx (Superficie de planta de la estancia 60.25 m²)
Las magnitudes de consumo de energía se refieren a las luminarias planificadas para en la estancia sin tener en cuenta escenas de luz ni sus estados
de atenuación.
Consumo: 1300 kWh/a de un máximo de 2150 kWh/a
Página 6
GENOMICA 24/10/2018
Local 2
Página 7
GENOMICA 24/10/2018
Local 2
Número de Luminaria (Emisión de luz)
unidades
12 LEDVANCE GmbH - 4058075066601 PanelLED Value
600 40W/ 4000K
Emisión de luz 1
Lámpara: 1xLED 4000K / CRI >= 80
Grado de eficacia de funcionamiento: 100%
Flujo luminoso de lámparas: 4000 lm Dispone de una imagen de la
Flujo luminoso de las luminarias: 4000 lm luminaria en nuestro catálogo
Potencia: 40.0 W de luminarias.
Rendimiento lumínico: 100.0 lm/W
Indicaciones colorimétricas
1xLED 4000K / CRI >= 80: CCT 4000 K, CRI 100
Flujo luminoso total de lámparas: 48000 lm, Flujo luminoso total de luminarias: 48000 lm, Potencia total: 480.0 W, Rendimiento lumínico: 100.0 lm/W
Página 8
GENOMICA 24/10/2018
Terreno 1 / Edificación 3 / Planta (nivel) 1 / Local 2 / Plano útil 2 / Intensidad lumínica perpendicular (Adaptativamente)
Página 9
GENOMICA 24/10/2018
Terreno 1 / Edificación 3 / Planta (nivel) 1 / Local 2 / Plano útil 2 / Intensidad lumínica perpendicular (Adaptativamente)
Isolíneas [lx]
Escala: 1 : 75
Página 10
GENOMICA 24/10/2018
Terreno 1 / Edificación 3 / Planta (nivel) 1 / Local 2 / Plano útil 2 / Intensidad lumínica perpendicular (Adaptativamente)
Escala: 1 : 75
Página 11
GENOMICA 24/10/2018
Terreno 1 / Edificación 3 / Planta (nivel) 1 / Local 2 / Plano útil 2 / Intensidad lumínica perpendicular (Adaptativamente)
Escala: 1 : 75
Página 12