Vous êtes sur la page 1sur 22

ANSI/ASHRAE Standard 130-2008

(Supersedes ANSI/ASHRAE Standard 130-1996 [RA 06])

ASHRAE STANDARD
Methods of Testing
Air Terminal Units

Approved by the ASHRAE Standards Committee on January 19, 2008; by the ASHRAE Board of Directors on
January 23, 2008; and by the American National Standards Institute on February 27, 2008.

ASHRAE Standards are scheduled to be updated on a five-year cycle; the date following the standard number is
the year of ASHRAE Board of Directors approval. The latest copies may be purchased from ASHRAE Customer
Service, 1791 Tullie Circle, NE, Atlanta, GA 30329-2305. E-mail: orders@ashrae.org. Fax: 404-321-5478. Tele-
phone: 404-636-8400 (worldwide) or toll free 1-800-527-4723 (for orders in US and Canada).

© Copyright 2008 ASHRAE, Inc.


ISSN 1041-2336

www.ansi.org

American Society of Heating, Refrigerating


and Air-Conditioning Engineers, Inc.
1791 Tullie Circle NE, Atlanta, GA 30329
www.ashrae.org
ASHRAE Standard Project Committee 130
Cognizant TCs: TC 5.3, Room Air Distribution, and TC 9.1, Large Building Air-Conditioning Systems
SPLS Liaison: Carol E. Marriott

Jerry M. Sipes, Chair* Frederick A. Lorch*


James Dale Aswegan* Gregory L. Meeuwsen*
Jason P. Bobruk Roger Gaylon Richardson*
Ted N. Carnes* Julian Rochester
Alfred T. Dyck Jeffery R. Stein*
Eugene W. Faris* Jack L. Stegall
Charles D. Kieffer* Ronald E. Woodbury*
Marvin L. Kloostra Michael W. Woodford*
David James Lingrey

*Denotes members of voting status when the document was approved for publication.

ASHRAE STANDARDS COMMITTEE 2007–2008


Stephen D. Kennedy, Chair Nadar R. Jayaraman
Hugh F. Crowther, Vice-Chair Byron W. Jones
Robert G. Baker Jay A. Kohler
Michael F. Beda James D. Lutz
Donald L. Brandt Carol E. Marriott
Steven T. Bushby R. Michael Martin
Paul W. Cabot Merle F. McBride
Kenneth W. Cooper Frank Myers
Samuel D. Cummings, Jr. H. Michael Newman
K. William Dean Lawrence J. Schoen
Robert G. Doerr Bodh R. Subherwal
Roger L. Hedrick Jerry W. White, Jr.
Eli P. Howard, III Bjarne W. Olesen, BOD ExO
Frank E. Jakob Lynn G. Bellenger, CO
Claire B. Ramspeck, Assistant Director of Technology for Standards and Special Projects

SPECIAL NOTE
This American National Standard (ANS) is a national voluntary consensus standard developed under the auspices of the American Society of
Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE). Consensus is defined by the American National Standards Institute (ANSI), of which
ASHRAE is a member and which has approved this standard as an ANS, as “substantial agreement reached by directly and materially affected interest
categories. This signifies the concurrence of more than a simple majority, but not necessarily unanimity. Consensus requires that all views and objections
be considered, and that an effort be made toward their resolution.” Compliance with this standard is voluntary until and unless a legal jurisdiction makes
compliance mandatory through legislation.
ASHRAE obtains consensus through participation of its national and international members, associated societies, and public review.
ASHRAE Standards are prepared by a Project Committee appointed specifically for the purpose of writing the Standard. The Project Committee
Chair and Vice-Chair must be members of ASHRAE; while other committee members may or may not be ASHRAE members, all must be technically
qualified in the subject area of the Standard. Every effort is made to balance the concerned interests on all Project Committees.
The Assistant Director of Technology for Standards and Special Projects of ASHRAE should be contacted for:
a. interpretation of the contents of this Standard,
b. participation in the next review of the Standard,
c. offering constructive criticism for improving the Standard, or
d. permission to reprint portions of the Standard.

DISCLAIMER
ASHRAE uses its best efforts to promulgate Standards and Guidelines for the benefit of the public in light of available information and
accepted industry practices. However, ASHRAE does not guarantee, certify, or assure the safety or performance of any products, components,
or systems tested, installed, or operated in accordance with ASHRAE’s Standards or Guidelines or that any tests conducted under its
Standards or Guidelines will be nonhazardous or free from risk.

ASHRAE INDUSTRIAL ADVERTISING POLICY ON STANDARDS


ASHRAE Standards and Guidelines are established to assist industry and the public by offering a uniform method of testing for rating
purposes, by suggesting safe practices in designing and installing equipment, by providing proper definitions of this equipment, and by providing
other information that may serve to guide the industry. The creation of ASHRAE Standards and Guidelines is determined by the need for them,
and conformance to them is completely voluntary.
In referring to this Standard or Guideline and in marking of equipment and in advertising, no claim shall be made, either stated or implied,
that the product has been approved by ASHRAE.
CONTENTS

ANSI/ASHRAE Standard 130-2008


Methods of Testing Air Terminal Units
SECTION PAGE
Foreword ................................................................................................................................................................... 2
1 Purpose .......................................................................................................................................................... 2
2 Scope ............................................................................................................................................................. 2
3 Definitions and Symbols ................................................................................................................................. 2
4 Instrumentation and Facilities ......................................................................................................................... 4
5 Test Methods .................................................................................................................................................. 6
6 Modulating Diffuser Terminal Testing............................................................................................................ 13
7 References ................................................................................................................................................... 13
Informative Appendix A: Means of Airflow Rate Measurement ........................................................................ 13
Informative Appendix B: Example for Measurement of Pressure-Control Performance .................................. 16
Informative Appendix C: Examples for Measurement of Mixing Efficiency ...................................................... 17
Informative Appendix D: Illustrations of Acoustically Isolated Ducts ................................................................ 18

NOTE

When addenda, interpretations, or errata to this standard have been approved, they can be downloaded free of
charge from the ASHRAE Web site at http://www.ashrae.org.

© Copyright 2008 American Society of Heating,


Refrigerating and Air-Conditioning Engineers, Inc.
1791 Tullie Circle NE
Atlanta, GA 30329
www.ashrae.org
All rights reserved.
(This foreword is not part of this standard. It is merely d. Air leakage
informative and does not contain requirements necessary e. Induced airflow
for conformance to the standard. It has not been f. Fan airflow
processed according to the ANSI requirements for a g. Fan motor electrical power
standard and may contain material that has not been h. Condensation
subject to public review or a consensus process. i. Airflow sensor performance
Unresolved objectors on informative material are not
offered the right to appeal at ASHRAE or ANSI.) 2.3 This standard does not cover individual control compo-
nents or products addressed in other ASHRAE standards or
FOREWORD
methods of testing, including but not limited to, the standards
First published in 1996 and reaffirmed in 2006, Standard listed in the reference section of this standard.
130 specifies instrumentation and facilities, test installation
methods, and procedures for determining the capacity and 3. DEFINITIONS
related performance of constant-volume and variable-volume
air terminal units. The standard is classified as an ASHRAE 3.1 This section provides definitions of key terms used in
standard method of measurement. this standard. For terms not defined below, refer to the defini-
This revision of the standard includes updates and revi- tions listed in ASHRAE Terminology of Heating, Ventilation,
sions to all parts of the standard, including its title, purpose, Air Conditioning, and Refrigeration.1
and scope. It updates definitions, adds modulating diffusers, airflow: for the purpose of this test method, airflow is the unit
redefines airflow sensor performance testing, and adds a volume displacement of standard air per unit of time. It is
method to determine the power factor. New appendices con- normally measured in cubic feet per minute (cfm) or liters per
tain some material that was formerly in the body of the stan- second (L/s).
dard and some new reference material.
This standard is required for compliance with ARI Stan- air terminal: a device that automatically modulates the
dard 880. volume of air delivered to or removed from a defined space in
The project committee wishes to acknowledge Dan Int- response to an external demand.
Hout, Kerstin Kenty, Patrick Schoof, and Jim Kline for the
amplification factor (F): the ratio of sensor output to true
assistance they provided in revising this standard.
velocity pressure. For example, a pressure sensor with a read-
ing of 1.0 in. of pressure at a velocity pressure of 0.43 in. would
1. PURPOSE
have an amplification factor of 1.0/0.43 = 2.3. F may be calcu-
This standard specifies instrumentation and facilities, test lated from K with the following formula, where A is the nomi-
installation methods, and procedures for measuring the capac- nal duct area in ft2. The nominal duct area is calculated based
ity and related performance of constant-volume, variable- on the geometry of the duct, not on the actual free area.
volume, and modulating integral diffuser air terminals.
4005 × A 2
F = ⎛⎝ ---------------------⎞⎠
K
2. SCOPE
2.1 The methods of test in this standard apply to air control average mixing temperature: the average of the discharge
devices used in air distribution systems. These devices pro- temperatures at a particular operating condition for a given
vide control of air volume with or without temperature control terminal.
by one or more of the following means, and may or may not
booster fan-powered terminal: a terminal that is similar to a
include a fan:
series terminal unit but without a primary valve. It may have
a. Fixed or adjustable directional vanes (i.e., bypass terminals) supplemental heat or reheat, depending upon its application.
b. Pressure-dependent volume dampers or valves (including bypass terminal: a terminal, typically having more than one
air induction nozzles and dampers) outlet, that uses a method of volume modulation whereby
c. Pressure-compensated volume dampers or valves (includ- airflow is varied by distributing the volume required to meet
ing air induction nozzles and dampers) the space requirements, the balance of primary air being
d. Integral heat exchange diverted away from the space.
e. ON/OFF fan control
f. Variable-speed fan control discharge sound power level: sound power that is transmitted
g. Modulating integral diffuser terminals from the terminal outlet.
dual-duct terminal: a terminal that may mix, for individual zones,
2.2 This standard covers test methods for use in determining varying portions of two independent sources of primary air.
the following performance characteristics:
equivalent diameter: the diameter of a circular-duct equiva-
a. Sound power lent that will have a cross-sectional area that is equal to that of
b. Temperature mixing and stratification a particular rectangular duct. The equivalent diameter is calcu-
c. Minimum operating pressure lated by the following equation:

2 ANSI/ASHRAE Standard 130-2008


D e = ( 4 × A ⁄ π ) 0.5 power factor: the ratio of real power to apparent power. Power
factor is a way to describe how much of the current contributes
where A is the cross-sectional area. to power in the load. A power factor of one indicates that 100%
of the current is contributing to power in the load.
exhaust terminal: an air terminal for regulating exhaust or
return airflow. primary air: the treated supply air being transported to a
terminal.
fan-powered terminal unit efficiency: the ratio of the total
power consumed per delivered fan air volume. pressure: for the purpose of this test method, static, total, and
velocity pressure shall be based upon standard air.
flow coefficient (K): the actual flow (in ft3/min) correspond-
ing to a pressure sensor output of 1 in. w.g. K may be calcu- pressure-compensated control system: control system in
lated from the amplification factor, F , with the following which the airflow through the air terminal is independent of
formula, where A is the nominal duct area in ft2. system pressure.
4005 × A
K = ⎛ ---------------------⎞ pressure-dependent control system: a control system in
⎝ F ⎠ which the airflow through the air terminal varies with system
pressure.
K is often used in terminal unit controls to calculate actual
airflow using the following equation, where cfm is airflow in quiet air supply: an air supply in which the sound power level
ft3/min and ΔP is flow sensor output in in. w.g.: introduced in the frequency band of interest by the supply
alone is at least 10 dB lower than the measured sound power
cfm = K × ΔP level generated by the air supply and the terminal under test.
induced airflow: the flow of secondary air into an air terminal radiated sound power level: sound power that radiates from
resulting from a pressure differential within the terminal. the terminal casing (plus the induction port if present).
induction terminal: a terminal, typically having more than reheat: the application of sensible heat to supply air that has
one inlet, that supplies varying proportions of primary and been previously cooled below the temperature desired for
induced air to meet the room load. This type of terminal maintaining the temperature of the conditioned space.
excludes fan-powered terminals.
reheat terminal: a terminal that heats a single source of
minimum operating pressure: the static or total pressure drop primary air from a cooling and/or dehumidification source.
through a terminal at a given airflow rate with the damper/
valve placed in its full open position by its actuator in its secondary air: air that is drawn into a terminal by means of
normal operating mode while the terminal is operating under induction and discharged through the terminal outlet.
steady-state control.
series flow fan-powered terminal: a terminal where the
modulating integral diffuser terminal: a diffuser with the primary valve is in series with the fan, and where all air typi-
features of an air terminal and with an integral airflow control cally flows through the fan. The unit may have supplemental
device. heat or cooling.

octave band: a frequency band with an upper limit that is twice shall: where shall or shall not is used for a provision specified,
the frequency of the lower limit. The center frequency of an that provision is mandatory if compliance with this test
octave band is the geometric mean of its upper and lower method is claimed.
limits. The following table shows octave bands 1 through 8:
should: used to indicate provisions that are not mandatory but
are desirable as good practice.
Octave Band Center Frequency (Hz)
1 63 single-duct terminal: a terminal supplied with one source of
primary air. This type of terminal excludes fan-powered
2 125 terminals.
3 250
sound power level ( L w ): a level of sound power that is ten
4 500 times the logarithm to the base 10 of the ratio of the sound
5 1000 power generated by the source to a reference sound power. The
6 2000 reference sound power shall be 10–12 watts.

7 4000 supplemental cooling: cooling provided by heat that is


8 8000 removed from the air source of the unit.
supplemental heat: heat that is added to an air source consist-
parallel flow fan-powered terminal: a terminal in which the ing primarily of return/plenum air.
primary valve is in parallel to the fan, thus allowing the primary
air to bypass the fan. It may have supplemental heat or cooling. standard air: air that meets the following criteria:

ANSI/ASHRAE Standard 130-2008 3


I-P units: Dry air at 70°F and 14.696 psia. Under these 700 fpm (3.5 m/s) over the wet bulb and only after sufficient
conditions, dry air has a mass density of 0.075 lb/ft3. time has been allowed for evaporative equilibrium to be
attained. The wick on the wet-bulb thermometer shall be clean,
Note: This not the same as SI standard air. fit the thermometer tightly, and be moistened by distilled
water. Wet-bulb thermometers shall always be downstream
SI units: Dry air at 20°C and 101.325 kPa. Under these from dry-bulb thermometers, or, if these thermometers are
conditions, dry air has a mass density of 1.204 kg/m3. positioned side by side, they shall be shielded from each other.
Note: This not the same as I-P standard air. Alternatively, a direct reading electronic relative-humidity
or dew-point meter may be employed if it has been shown to
terminal: an air terminal. provide relative humidity readings to within ±5% or dew-point
readings to within ±1.0°F (0.5°C) of the readings determined by
terminal casing leakage: the amount of the air in ft3/min
the above procedure over a sufficient period of time to ensure
(L/s) at standard conditions escaping from the terminal at
reliability.
a given inlet pressure with the outlet(s) and inlet(s) blocked
and with the damper/valve fully opened. 4.1.3 Temperature-measuring instruments shall be cali-
brated by comparison with a certified standard in the range of
terminal damper leakage: the amount of air in ft3/min (L/s) at use, or shall be certified as to accuracy on an annual basis.
standard conditions passing through a fully closed damper/
valve at a given inlet pressure. 4.1.4 Temperature-measuring instruments shall be placed
so as to measure accurately both the dry-bulb and wet-bulb
3.2 The following nomenclature is used throughout this test temperatures of the air entering the flow-measuring device and
method: the dry-bulb temperature of the air entering the test unit. The
measurements shall be used in determining the air density at
Symbol Quantity I-P Units SI Units
the airflow measuring device and at the intake of the test unit.
A Internal cross section of duct ft2 m2
De Equivalent diameter ft m 4.2 Pressure Measurement
P Absolute static pressure in. H2O Pa 4.2.1 Pressure-measuring instruments shall meet the
Pa Atmospheric pressure in. Hg kPa requirements of ASHRAE Standard 41.3-19893 and the
requirements of Sections 4.2.2 and 4.2.3.
Pv Velocity pressure in. H2O kPa
Ps Static pressure in. H2O kPa
4.2.2 The maximum scale intervals shall not be greater
than the characteristics listed below for the accompanying
Pt Total pressure in. H2O kPa range of manometer.
ΔP Differential pressure in. H2O kPa
ΔP t Total differential pressure in. H2O kPa Range Maximum Scale Interval
3/min (cfm)
Qa Airflow at actual test conditions ft m3/s 1.001 to 0.005 in. 0.0005 in.
Qs Airflow at standard conditions ft3/min (cfm) m3/s (0.2 to 1.0 Pa) (0.1 Pa)
V Air velocity ft/min (fpm) m/s
ρ Air density at standard air lbm/ft3 kg/m3
0.005 to 0.10 in. 0.001 in.
Lw Sound power level dB dB
(1.0 to 25 Pa) (0.25 Pa)

4. INSTRUMENTATION AND FACILITIES


0.10 to 1.00 in. 0.010 in.
4.1 Temperature Measurement. Temperature-measuring
instruments shall meet the requirements of ASHRAE Stan- (25 to 250 Pa) (2.5 Pa)
dard 41.1-1986 (RA 2006)2 and the following.
4.1.1 Accuracy of the temperature-measuring instruments 1.00 to 2.00 in. 0.020 in.
shall be within the following limits:
(250 to 500 Pa) (5.0 Pa)
• Air temperature at the air-measuring section: ±1.0°F
(0.5°C)
>2.00 in. 0.100 in.
• Inlet supply air temperature: ±1.0°F (0.5°C)
• Air temperature mixing and stratification: ±1.0°F (0.5°C) (>500 Pa) (25 Pa)
• All other temperatures: ±1.0°F (0.5°C)
In no case shall the smallest-scale division of the temper- 4.2.3 Calibration standards shall be as follows:
ature-measuring device exceed twice the specified accuracy.
4.1.2 Wet-bulb temperatures shall be read only under con- a. For instruments with the range 0.001 to 0.005 in. of water
ditions that ensure an air velocity of approximately 1000 fpm (0.2 to 1.0 Pa): a micromanometer or other instrument
(5 m/s) but not more than 2000 fpm (10 m/s) or less than calibrated to ±0.0001 in. of water (0.025 Pa).

4 ANSI/ASHRAE Standard 130-2008


b. For instruments with the range 0.005 to 0.100 in. of water 4.2.9 Static Pressure Differential ( ΔP S ).
(1.25 to 25 Pa): a micromanometer or other instrument
calibrated to ±0.0005 in. of water (0.125 Pa). ΔP S = P S out – PS in
c. For instruments with the range 0.1 to 2.0 in. of water (25
4.2.10 Velocity Pressure Differential ( ΔP V ).
to 500 Pa): a micromanometer or other instrument cali-
brated to ±0.01 in. of water (2.5 Pa). ΔP V = P V out – PV in
d. For instruments with a range greater than 2.0 in. of water
(500 Pa): a manometer or other instrument calibrated to 4.2.11 Total Pressure Differential ( ΔP T ).
±0.1 in. of water (25 Pa).
ΔP T = ΔP S + ΔP V
4.2.4 Barometric Pressure. The barometric pressure
shall be obtained by means of a barometer located in the 4.2.12 Temperatures shall be maintained to within ±2.0°F
general test area. (±1.0°C) during pressure measurements.
4.2.5 Supply Air Static Pressure. The static pressure of 4.3 Airflow Measurement
the air entering the test unit shall be measured by means of a 4.3.1 Airflow meters in the ranges shown shall have at
static pressure tap. A static pressure traverse, using the same least the following accuracies:
method for a velocity pressure traverse, as described in
ASHRAE Standard 111,4 should be taken at the place of pres-
Range Accuracy
sure measurement to establish that the static pressure, P s , is
uniform to within ±10% of measurement. The static pressure 5 to 99 cfm ±5.0 cfm
tap shall be located a minimum of 1.5 De upstream of the unit 100 or greater cfm ±5.0% of reading
in a test duct not less than 3.0 D e in length.
4.2.6 Discharge Air Static Pressure. The static pres- 4.3.2 Airflow meters for leakage measurement in the
sure of the air discharging from the test unit shall be mea- ranges shown shall have at least the following accuracies:
sured by means of a static pressure tap. A static pressure
traverse, using the same method for velocity pressure tra- Range Accuracy
verse as described in ASHRAE 111, should be taken at the
5 to 49.9 cfm ±5.0 cfm
place of pressure measurement to establish that P s is uni-
form to within ±10% of measurement. The static pressure 50 or greater cfm 1% of reading
tap shall be located a minimum of 2.5 De downstream of the
terminal outlet in a test duct not less than 3.5 D e in length. 4.3.3 The device for airflow measurement shall be cali-
If no discharge duct is used, the discharge static pressure brated to provide the accuracies listed in Sections 4.3.1 and
shall be that of the surroundings. 4.3.2.
4.2.7 Supply Air Velocity Pressure ( P V in ). The sup- 4.3.4 Airflow meters shall be checked at appropriate inter-
ply air velocity pressure is calculated from the following vals that do not exceed 36 months. This check may take the
equations: form of one of the following:

cfm 2
PV = ρ × ( V ⁄ 1096 ) 2 = ⎛ --------------------------⎞ (I-P) a. A calibration check over the full range using the original
in ⎝ 4005 × Ain ⎠
method employed for the original calibration of flowme-
ters calibrated in situ.
L/s 2
PV in = ρ × ( V 2 ⁄ 2 ) = ⎛⎝ --------------------------⎞⎠ (SI) b. An in situ check by the means described in ASHRAE
4005 × Ain
Standard 41.25 or 41.76 or in Appendix A of this standard.
where cfm is the airflow in ft3/min, measured according to
4.3.5 Temperature shall be maintained to within ±2.0°F
Section 4.3, and A in is the inlet duct area in ft2 (m2).
(±1.0°C) during airflow measurements.
4.2.8 Discharge Air Velocity Pressure (PV out). The dis-
charge air velocity pressure is calculated by the following 4.3.6 Ductwork between the reference airflow-measuring
equations: device and the terminal unit shall be sealed to meet the
requirements of SMACNA 3 inch water pressure class
cfm 2
= ρ × ( V ⁄ 1096 ) 2 = ⎛ ----------------------------⎞ (I-P)
(according to the latest edition of SMACNA HVAC Duct
PV out ⎝ 4005 × Aout ⎠ Construction Standards7).

L/s 2 4.4 Electrical Measurement. Electrical measurements


PV out = ρ × ( V 2 ⁄ 2 ) = ⎛⎝ ----------------------------⎞⎠ (SI) shall be made with the following instruments:
4005 × Aout

where cfm is the airflow in ft3/min, measured according to a. Voltmeters shall be true RMS, high-impedance meters
Section 4.3, and Aout is the discharge duct area (ft2) at the with an accuracy within ±2% of reading.
point where discharge static pressure is measured. If discharge b. Ammeters shall have an accuracy of ±2% of reading.
static pressure is measured without discharge ductwork, then c. Wattmeters shall be true RMS, high-impedance meters
Aout is effectively infinite and P V out = 0 . with an accuracy within ±2% of reading.

ANSI/ASHRAE Standard 130-2008 5


d. Power-factor-measurement devices shall be true RMS, a given airflow, with the primary damper/valve placed in its
high-impedance devices with an accuracy within ±2% of fully open position. Parallel flow fan-powered and non-fan-
the reading. A way to measure the power factor is with a powered terminals shall be installed as shown in Figure 3.
Fluke 40 or 43B meter or an equivalent device. Power Diffuser terminals shall be installed as shown in Figure 3
factor can be read directly from the meter during testing. without downstream ductwork. For any terminal with more
The power factor must be measured as the true ratio than one inlet or outlet, the conditions of those inlets and out-
between VA and the power output, including all harmon- lets shall be stated.
ics. Instruments that measure displacement power factor
only, Cos(Phi), or do not define what type of power factor Series flow fan-powered terminals shall be installed as
is measured in the instrument’s documentation are not shown in Figure 4. This test method may be used to determine
sufficient.

4.5 Temperature-, pressure-, and electrical-measuring


instruments shall have been calibrated within the past year by
comparison with a certified standard in the range of use or
shall itself have been certified as to accuracy.

5. TEST METHODS
5.1 Total or Fan Volume Airflow Measurement
5.1.1 This test is intended to measure the volume of air Figure 1 Test installation for total or fan volume airflow
delivered at various static pressure resistances. The terminal measurement.
to be tested shall be installed as shown in Figure 1.
5.1.2 An airflow-measuring means, in accordance with
Section 4.3, shall be connected to a straight section of dis-
charge ductwork that is connected to the terminal outlet so as
to provide aerodynamic conditions representative of actual
installation. The static pressure resistance shall be measured
in accordance with Section 4.2. Airflow and pressure mea-
surements shall be taken with the terminal under normal oper-
ating conditions after a condition of equilibrium has been
established. Figure 2 Test installation for primary air damper/valve
leakage, backdraft damper and casing leakage,
5.2 Primary Air Damper/Valve Leakage pressure-compensating control performance, and
5.2.1 This test is intended to measure control valve leak- condensation determination.
age or leakage past a primary air damper in the shutoff posi-
tion. The equipment to be tested shall be installed as shown in
Figure 2. This test method may be used to determine the pri-
mary damper/valve leakage with installations that are set up
other than as shown in Figure 2. These installation conditions
shall be described in the test report.
5.2.2 An air supply duct shall be connected to the inlet of
the closed damper/valve. All other apertures in the terminal
shall be open. The supply air duct shall be connected to a suit-
able air supply. The supply air pressure shall be increased to
the desired inlet static pressure; then, without any additional Figure 3 Test installation for primary air damper/valve
adjustment of the supply airflow rate, the terminal air inlet minimum operating pressure.
control valve/damper shall be modulated to the open position
and returned to the closed position by means of the damper/
valve actuator. After the damper/valve has closed, the supply
air pressure shall be adjusted so as to maintain the inlet static
pressure to within ±5% of the desired value after equilibrium
has been established. The airflow rate shall be recorded as the
primary air damper/valve leakage expressed as x cfm (L/s) at
y in. (Pa) inlet static pressure.
5.3 Primary Air Damper/Valve Minimum Operating Figure 4 Test installation for temperature mixing and
Pressure temperature stratification, and primary air damper/valve
5.3.1 This test is intended to measure the inlet static pres- minimum operating pressure for series slow fan-
sure or pressure differential ( ΔP s ) through an air terminal at powered terminals.

6 ANSI/ASHRAE Standard 130-2008


the minimum operating pressure with installations other than 5.5 Dynamic Leakage
those shown in Figures 3 and 4. These installation conditions 5.5.1 This test is intended to measure the leakage during
shall be described in the test report. operation of the terminal unit. The terminal to be tested shall
5.3.2 Series flow fan-powered terminals shall have an be installed as shown in Figure 6. This test method may be
airflow-measuring means, in accordance with Section 4.3, used to determine the dynamic leakage with installations that
connected to a straight section of ductwork that is connected are set up other than as shown in Figure 6. These installation
to the primary air inlet of the terminal, as shown in Figure 4. conditions shall be described in the test report.
The inlet static pressure shall be measured in accordance 5.5.2 An airflow-measuring means in accordance with
with Section 4.2 and referenced to atmospheric pressure. An Section 4.3 shall be connected to a straight section of duct-
airflow-measuring means in accordance with Section 4.3 work that is connected to the primary air inlet of the termi-
shall be connected to a straight section of discharge duct- nal. An airflow-measuring means in accordance with
work that is connected to the terminal outlet. The static pres- Section 4.3 shall be connected to a straight section of duct-
sure resistance shall be measured in accordance with work with a pressure-regulating device that is connected to
Section 4.2 and referenced to atmospheric pressure. Airflow the discharge of the terminal. The primary damper/valve
and pressure measurements shall be recorded with the pri- shall be set to achieve the desired inlet static pressure at the
mary air damper/valve in the fully open position and with desired primary airflow, and the conditions of all other out-
the fan delivering the desired airflow against the desired lets and inlets shall be stated. The desired discharge pressure
static pressure resistance. Readings shall be taken after equi- shall be set. The inlet and discharge static pressure shall be
librium has been established. measured in accordance with Section 4.2. Airflow and static
pressure measurements shall be taken after equilibrium has
5.3.3 Parallel flow fan-powered and non-fan-powered ter-
been established. The dynamic leakage is the difference
minals shall have an airflow-measuring means, in accordance
between the inlet airflow and the outlet airflow and shall be
with Section 4.3, connected to a straight section of ductwork reported as x cfm (L/s) at y in. (Pa) static pressure.
that is connected to the primary air inlet of the terminal, as
shown in Figure 6. A straight section of ductwork shall be con- 5.5.3 This test is intended to be run on a parallel flow ter-
minal with the fan turned off.
nected to the discharge of the terminal. The inlet static pressure
(PS1) and discharge static pressure ( P S2 ) shall be measured in 5.6 Airflow Sensor Performance–Straight Duct Conditions
accordance with Section 4.2. Inlet and discharge velocity pres- 5.6.1 This test is intended to measure terminal unit air
sures shall be calculated using nominal areas. Airflow and dif- flow sensor output at various airflows (or velocities) for a
ferential pressure ( ΔP s and ΔP t ) shall be recorded with the specified duct static pressure. Its purpose is to determine the
primary damper/valve in the fully open position. The operating effects of the throttling device on flow sensor performance.
condition of the fan in variable-volume fan-powered terminals
5.6.2 The terminal to be tested shall be installed as shown
shall be stated. Readings shall be taken after equilibrium has
in Figure 2. An airflow measuring means in accordance with
been established.
Section 4.3 shall be connected to all primary inlets. Static
5.4 Casing Leakage pressure shall be measured in accordance with Section 4.2.
5.4.1 This test is intended to measure the leakage from the
inside to the outside of the terminal unit. The terminal to be
tested shall be installed as shown in Figure 5. This test method
may be used to determine the casing leakage with installations
that are set up other than as shown in Figure 5. These instal-
lation conditions shall be described in the test report.
5.4.2 An airflow-measuring means, in accordance with
Section 4.3, shall be connected to a straight section of duct-
work that is connected to the primary air inlet of the terminal.
The primary damper/valve shall be fully opened, and all other Figure 5 Test configuration for case leaking testing.
outlets and inlets shall be sealed. The inlet static pressure shall
be measured in accordance with Section 4.2. The primary air
supply shall be increased until the desired static pressure is
obtained. Airflow and static pressure measurements shall be
taken after equilibrium has been established. The casing leak-
age shall be reported as x cfm (L/s) at y in. (Pa) static pres-
sure. For parallel flow terminal units, the backdraft damper
leakage may be considered to be part of the casing leakage
and, as such, the induction port should not be sealed during
the test. The leakage across the damper can be determined by
sealing the induction port and calculating the difference in Figure 6 Test configuration for dynamic leakage
leakage during the two tests. testing.

ANSI/ASHRAE Standard 130-2008 7


Airflow shall be measured in accordance with Section 4.3. condition. The change in airflow volume shall be reported as
The test report shall fully describe test conditions, including the percent difference between the straight duct condition and
nominal duct diameter. the desired duct condition, as shown in the following equation:
5.6.3 The airflow to the terminal shall be varied across the
non-straight flow
desired airflow range at the desired duct static pressure. Record % change = ----------------------------------------- – 1 × 100
straight flow
airflow, static pressure, and airflow sensor output (e.g., pres-
sure, voltage, amperage) at each point. For sensors that output 5.8 Temperature Mixing
in pressure, calculate the velocity pressure from the measured 5.8.1 This test is intended to measure the efficiency of the
airflow and calculate the amplification factor from the sensor mixing of the induced plenum air with the supplied primary
output divided by the velocity pressure at each point. air of fan-powered and non-fan-powered induction units and
5.7 Airflow Sensor Performance—Inlet and Outlet Duct of the two supplied primary air inlets of dual-duct units. The
Variations equipment to be tested shall be installed as shown in Figure 4.
This test method may be used to determine the efficiency of
5.7.1 This test is intended to measure the change in air-
temperature mixing with installations other than as shown in
flow caused by variations in the inlet or outlet duct configu-
Figure 4. These installation conditions shall be described in
rations.
the test report.
5.7.2 Sensor performance shall first be measured under 5.8.2 Temperature measurements shall be recorded in a
straight conditions according to Section 5.6. test duct attached to the outlet of the unit. The dimensions
5.7.3 The duct condition shall then be changed to that (length, height, and width) of the test duct shall be reported.
desired (e.g., 90 degree, 0.75 in. radius hard duct elbow from The plane of measurement shall be located so that the test duct
the right at the inlet, 45° elbow up at the discharge, etc.). The extends at least 0.5 D e beyond the plane of measurement. The
same test instruments and devices (airflow-measuring device, distance from the measurement plane to the terminal outlet
terminal unit pressure sensor, etc.) shall be used for the shall be reported. The end points for each row and column
straight duct test and non-straight test. Non-straight condi- shall be 1.0 in. (25 mm) from their respective test duct wall
tions shall be fully described in the report. The report shall surface. The remaining temperature-measuring points shall
include scale drawings in plan view and section view of the be uniformly located throughout the remaining area in the
terminal unit and duct conditions. (see Figure 7). measurement plane. The minimum number of temperature-
5.7.4 Adjust the airflow (e.g., adjust the supply fan speed), measuring points shall be as specified in the following table:
and terminal unit throttling device to obtain the same airflow
sensor output and duct static pressure recorded with the Test Duct Minimum Number of
straight duct conditions. Record airflow for the desired duct Cross-Sectional Area Temperature-Measuring Points
0.25 ft2 (0.025 m2) 4
0.50 ft2 (0.05 m2) 6
1.00 ft2 (0.1 m2) 9
1.50 ft2 (0.15 m2) 12
2.00 ft2 (0.2 m2) 15
3.00 ft2 (0.3 m2) 20
>3.00 ft2 (>0.3 m2) 25

Primary air supply temperature(s) shall be recorded at a


single measurement point located at the centerline of the
primary air supply duct(s) immediately adjacent to the unit
inlet. The induced plenum air temperature shall be recorded
with a single measuring point located immediately adjacent to
the induced air inlet.
5.8.3 An airflow-measuring means in accordance with Sec-
tion 4.3 shall be connected to a straight section of ductwork that
is connected to the primary air inlet of the terminal (only one is
required for dual-duct terminals). The inlet static pressure shall
be measured in accordance with Section 4. An airflow-measur-
ing means, in accordance with Section 4.3, shall be connected
to the outlet duct containing the temperature-measuring point.
Figure 7 Test installation for inlet airflow sensor The discharge static resistance shall be measured in accordance
performance. with Section 4.2.

8 ANSI/ASHRAE Standard 130-2008


The test shall be conducted as follows: y = the maximum difference between end point
discharge temperatures recorded in any vertical
a. The temperature-measuring devices used for this test plane at the temperature-measuring station
shall be normalized to read within 0.2°F (0.1°C) of the downstream, and
average just prior to the test by running isothermal air at
z = the difference between the arithmetic average of
room temperature through the duct. The isothermal room the discharge air temperatures recorded at the
temperature shall be reported. Each entering air tempera- temperature-measuring station downstream and
ture shall be reported along with the resultant discharge the induced air plenum temperature or inlet
temperature. primary air temperature(s).
b. Adjust the supply air temperatures and the terminal air-
flow control devices until the desired airflows, inlet and 5.9.4 For terminals without means of heat exchange, the
outlet static pressures, and supply air temperatures are amount of temperature stratification shall be reported as x
obtained. degree horizontal and y degree vertical for z degree tempera-
ture difference for (L/s) discharge airflow at b inches w.c.
c. Monitor the supply air temperature(s), any induced ple-
(Pa) discharge static pressure with d cfm (L/s) primary air-
num air temperature, and the individual discharge air tem-
flow(s) at e inches w.c. (Pa) inlet static pressure(s), where
peratures at each temperature-measuring point until
thermal equilibrium has been obtained. Thermal equilib-
x = the maximum difference between end point
rium is defined as less than 1.0°F (0.5°C) change over a
discharge temperatures recorded in any
5.0-min period at each temperature-measuring point.
horizontal plane at the temperature-measuring
d. After thermal equilibrium has been obtained, record the
station downstream,
supply airflow(s) and any induced plenum air tempera-
ture. Also record the inlet static pressure(s), the supply air y = the maximum difference between end point
temperature(s), the discharge airflow, the discharge static discharge temperatures recorded in any vertical
pressure, and the discharge air temperatures at each tem- plane at the temperature-measuring station
perature-measuring point. downstream, and
z = the difference between the arithmetic average of
5.8.4 The efficiency of temperature mixing shall be the discharge air temperatures recorded at the
reported as x degrees in y degrees for a cfm (L/s) discharge temperature-measuring station downstream and
airflow at b inches w.c. (Pa) discharge static pressure with d the induced air plenum temperature or inlet
cfm (L/s) primary airflow(s) at e inches w.c. (Pa) inlet static primary air temperature(s).
pressure(s), where
5.10 Sound
x = the difference between the highest and lowest
temperatures recorded at the temperature- 5.10.1 Sound power shall be determined in accordance
measuring point downstream, and with the ANSI Standard S12.51,8 which specifies in general
y = the difference between the highest inlet air the instrumentation, acoustic test facilities, and the uncer-
temperature and the lowest inlet air temperature. tainty of the measurements. The sound test shall be performed
to at least engineering grade 2 as defined in Table 1 of ANSI
5.9 Temperature Stratification Standard S12.51 with the exception that the test room must be
5.9.1 This test is intended to measure the amount of tem- qualified as Precision Grade 1, as defined in its Section 5,
perature stratification in terminals with or without heat Acoustic Environment Subsections 5.2 and 5.3, and qualified
exchange means. The terminal to be tested shall be installed according to Annex E to meet the requirements in Table 1.
as shown in Figure 6. This test method may be used to deter- Sound data shall be measured for the terminal only and shall
mine the amount of temperature stratification in installations not contain a reduction in values obtained by the use of lined
other than the one shown in Figure 6. These installation con- ductwork or silencers unless these items are shown to be an
ditions shall be described in the test report. integral part of the terminal being tested.
5.9.2 Testing shall be conducted in accordance with 5.10.2 Discharge sound power level determination
Section 5.7. requires only that the discharge air be exposed to the reverber-
5.9.3 For terminals with means of heat exchange, the ant room. The terminal casing shall be acoustically isolated
amount of temperature stratification shall be reported as x from the reverberant room. The terminal shall be installed in
degree horizontal and y degree vertical for z degree temper- accordance with Figures 8–11. This test method can be used
ature rise for a cfm (L/s) discharge airflow at b inches w.c. to determine the discharge sound power level with installa-
(Pa) discharge static pressure with d cfm (L/s) primary air- tions other than as shown in Figures 8–11. These installation
conditions shall be described in the test report.
flow(s) at e inches w.c. (Pa) inlet static pressure(s), where
5.10.2.1 Terminal performance is a function of primary
x = the maximum difference between end point air volume, inlet static pressure, fan air volume, and down-
discharge temperatures recorded in any stream static resistance. These variables shall be measured in
horizontal plane at the temperature-measuring accordance with Section 4 and reported with the terminal end
station downstream, discharge sound power levels.

ANSI/ASHRAE Standard 130-2008 9


Figure 8 Test installation for discharge sound test for central terminals with discharge duct.

Figure 9 Test installation for discharge sound test for fan-powered and induction terminals.

5.10.2.2 The reverberant room shall be adjusted to the Figure 12 or 13. These installation conditions shall be
specified static pressure and not changed during the test. The described in the test report.
terminal shall then be adjusted to maintain the specified air-
flow and static pressure. 5.10.4 The terminal shall be located away from any posi-
5.10.3 To determine the sound radiating from the terminal tions of room air entry. Terminal performance is a function of
induction port(s) and/or casing, the terminal shall be installed primary air volume, inlet static pressure, fan air volume, and
in accordance with Figure 12 or 13. This test method may be downstream static resistance. These variables shall be mea-
used to determine the induction port(s) and/or casing radiated sured in accordance with Section 4 and reported with the ter-
sound power level with installations other than those shown in minal radiated sound power levels.

10 ANSI/ASHRAE Standard 130-2008


Figure 10 Test installation for discharge sound test for integral diffuser air terminal.

Figure 11 Test installation for discharge casing-radiated sound test for integral diffuser terminal.

5.11 Electrical Power Measurements ing of measured electrical power. Terminal performance is a
5.11.1 This test is intended to determine the electrical function of primary air volume, inlet static pressure, fan air
power requirements of ducted terminals. volume, and downstream static resistance. These variables
5.11.2 Electrical measurements shall be made with instru- shall be measured in accordance with Section 4 and reported
ments conforming to Section 4.4. Readings shall be taken with the electrical measurements. Controls, heaters, and other
after test condition(s) have reached thermal equilibrium. Any appurtenances shall not be included in this calculation. Equi-
and all electrical control devices shall be included in the list- librium air temperatures shall be reported.

ANSI/ASHRAE Standard 130-2008 11


Figure 12 Test installation for casing-radiated sound test for terminals.

Figure 13 Test installation for inlet and radiated sound test for fan-powered and induction terminals.

5.12 Condensation Determination work that is connected to the primary air inlet of the terminal.
5.12.1 This test is intended to determine the condensation The inlet static pressure shall be measured in accordance with
potential of terminals. The terminal to be tested shall be Section 4.2. Fan-powered and non-fan-powered induction ter-
installed as shown in Figure 4. This test method may be used minals shall have an airflow-measuring means, in accordance
to determine condensation potential with installations other with Section 4.4, connected to a straight section of ductwork
than as shown in Figure 4. These installation conditions shall that is connected to the terminal outlet so as to provide aero-
be described in the test report. dynamic conditions representative of actual installation. The
5.12.2 An airflow-measuring means, in accordance with static pressure resistance shall be measured in accordance
Section 4.4, shall be connected to a straight section of duct- with Section 4.2.

12 ANSI/ASHRAE Standard 130-2008


5.12.3 The terminal shall be operated at the desired test 3. ASHRAE Standard 41.3-1989, Standard Method for Pres-
conditions for a period of not less than one hour at steady-state sure Measurement. Atlanta: American Society of Heat-
conditions. After this period, the terminal shall be inspected ing, Refrigerating and Air Conditioning Engineers Inc.
for condensation. The following test variables shall be 4. ASHRAE Standard 111-1988, Practices for Measurement,
recorded and reported: Testing, Adjusting, and Balancing of Building Heating,
Ventilation, Air-Conditioning, and Refrigeration Sys-
a. Primary airflow rate(s), temperature(s), relative humidity
tems. Atlanta: American Society of Heating, Refrigerat-
(or humidities), and inlet static pressure(s)
ing and Air Conditioning Engineers Inc.
b. Temperature and relative humidity of environment imme-
diately surrounding the terminal under test 5. ASHRAE Standard 41.2-1987 (RA 92), Standard Methods
c. Discharge airflow rate, temperature, relative humidity, for Laboratory Airflow Measurement. Atlanta: Ameri-
and static resistance can Society of Heating, Refrigerating and Air Condi-
d. Any surfaces exhibiting condensation tioning Engineers Inc.
6. ANSI/ASHRAE Standard 41.7-1984 (RA 2006), Method of
6. MODULATING DIFFUSER TERMINAL TESTING Test for Measurement of Flow of Gas. Atlanta: Ameri-
can Society of Heating, Refrigerating and Air Condi-
During all tests of modulating diffuser terminals (e.g., tioning Engineers Inc.
variable geometry diffusers), the unit shall be mounted in its
normal orientation (usually ceiling mounted). This mounting 7. SMACNA/ANSI HVAC Duct Construction Manu-
will allow for proper operation of all gravity-sensitive moving als—Metal and Flexible, 3rd edition (2005), Sheet
parts. If modulating diffuser terminals terminate at the air Metal and Air Conditioning Contractors’ National
outlet where air is distributed into the room, no discharge duct Association, Chantilly, VA 20151-1209.
is required for the test installation. 8. ANSI S12.51-2002, Acoustics—Determination of sound
power levels of noise sources using sound pres-
6.1 For primary air damper leakage test, refer to Section 5.2
sure—Precision method for reverberation rooms. New
of this standard.
York: American National Standards Institute.
6.2 For primary air damper/valve minimum operating pres- 9. ANSI/ASHRAE Standard 70-2006, Method of Testing the
sure test, refer to Section 5.3 of this standard. Performance of Air Outlets and Inlets. Atlanta: Ameri-
6.3 For pressure compensating control performance test can Society of Heating, Refrigerating and Air Condi-
(when required), refer to Appendix B of this standard. tioning Engineers Inc.

6.4 For inlet airflow sensor performance test (when the air-
(This appendix is not part of this standard. It is merely
flow sensor is an integral part of the test unit), refer to Section
informative and does not contain requirements necessary
5.7 of this standard.
for conformance to the standard. It has not been
6.5 For discharge sound test, refer to Section 5.10 of this processed according to the ANSI requirements for a
standard. standard and may contain material that has not been
subject to public review or a consensus process.
6.6 For electrical power measurement test (when appropri- Unresolved objectors on informative material are not
ate), refer to Section 5.11 of this standard. offered the right to appeal at ASHRAE or ANSI.)
6.7 For condensation determination test, refer to Section
5.12 of this standard. INFORMATIVE APPENDIX A
MEANS OF AIRFLOW RATE MEASUREMENT
6.8 For throw test, refer to ASHRAE Standard 70.9 The
throw test should be conducted with the damper in a full open
position and any other damper position required. All damper A1. GENERAL
positions should be noted in the test report.
Airflow rate shall be measured in accordance with
ASHRAE Standard 41.2-1987.A-1 Alternative airflow rate
7. REFERENCES
measurement methods may be used if calibrated by compari-
1. ASHRAE Terminology of Heating, Ventilation, Air Condi- son with a certified standard to the required accuracy.
tioning, and Refrigeration. Atlanta: American Society
of Heating, Refrigerating and Air Conditioning Engi- A2. ORIFICE METERS
neers Inc.
2. ANSI/ASHRAE Standard 41.1-1986 (RA 2006), Standard A2.1 Orifice meters shall be constructed in accordance with
Method for Temperature Measurement. Atlanta: Ameri- ASME Performance Test Code 19.5A-2 and shall be sized for a
can Society of Heating, Refrigerating and Air Condi- throat velocity not less than 3000 fpm (15 m/s) or more than
tioning Engineers Inc. 7000 fpm (35 m/s).

ANSI/ASHRAE Standard 130-2008 13


A3. MULTIPLE NOZZLE CHAMBER METER A4.3.2 Depending on the purpose of the propeller flow
station, several flow ranges will be needed to fully calibrate
A3.1 Multiple nozzle chamber meters shall be constructed
the unit.
in accordance with ANSI/ASHRAE Standard 51-1999
(ANSI/AMCA 210-99).A-3 A4.3.3 The anemometer flow station must be constructed
solidly to minimize the potential for leakage at high static
pressures. Verify that the flowmeter and calibrating venturi
A4. VANE ANEMOMETER
are concentric, straight and level. (This is important because
FLOW MEASURING SYSTEM
misalignment will result in lower than anticipated accuracy.)
A4.1 One method of accurately measuring airflow rates A4.3.4 When constructing the anemometer flowmeter,
with low pressure drop is to use a vane anemometer that has take care to locate the anemometer within 0.16 equivalent
been calibrated in-situ against a certified standard to the diameters of the center of the duct.
required accuracy.
A4.3.5 The target of the calibration is to create an empir-
A4.2 The vane anemometer flow-measuring system con- ical mathematic equation that relates frequency output from
sists of a straight length of duct with a propeller anemometer, the anemometer to flow rate (cfm). The finished anemometer
humidity measuring instruments and a temperature probe will have an extremely wide flow range, 8 cfm to 3400 cfm for
inside (see Figure A-1). The duct has five diameters of inlet a 12-in. Ø duct. Several venturis will be needed to cover the
length, a flow straightener and three diameters of discharge entire range. Larger ducts will have a higher minimum and
length. Optionally, a backpressure regulating device can be higher maximum, and similarly smaller ducts will have a
installed in the discharge of the precision flow station. A prop- lower minimum and lower maximum.
erly calibrated vane anemometer flowmeter can be accurate to
±2% over an extremely wide flow range. Following is a num- a. Start with the smallest venturi first and calibrate through
bered list of components for a vane anemometer flow measur- its range. Gradually increase and then decrease the flow
ing system (see Figure A-1): rate from the lowest practical value for that size venturi to
the highest practical value in small steps recording the
1. Item 1 is a section of straight duct to allow the airflow to flow rate and frequency every few seconds.
stabilize in the duct. b. Repeat with the next size larger venturi until the required
2. Item 2 is the propeller anemometer. flow range is covered. Make sure that the range of each
3. Item 3 is the center section of duct where all of the instru- venturi overlaps the range of adjacent sizes.
ments are mounted. c. Use standard statistical analysis to determine the relation-
4. Item 4 is the humidity sensor. ship between flow and frequency.
5. Item 5 is the temperature probe.
A4.3.6 Venturi flowmeters automatically correct for
6. Item 6 is the discharge duct. atmospheric density, but anemometer flowmeters will not.
7. Item 7 is the discharge transition. The solution to this is to use the barometric pressure trans-
8. Item 8 is the optional backpressure damper. ducer and the static pressure transducer along with the humid-
9. Item 9 is a flow straightener consisting of least a grid of ity and temperature probes to correct for atmospheric density
0.5 in. squares deeper than two times the grid size. changes. The anemometer flowmeter will then give readings
10. Item 10 is an in-duct static pressure probe, mounted 1 diam- in standard cubic feet per minute (scfm).
eter behind the front of the propeller.
Note: The anemometer flowmeter can be inside any size
Not shown is an atmospheric pressure transducer.
or shape duct and still be very accurate over an extremely wide
A4.3 Vane Anemometer Flowmeter Calibration Procedure flow range because of the calibrate-in-place procedure.

A4.3.1 Since the propeller anemometer is most com-


A5. APPENDIX A REFERENCES
monly used for outdoor wind speed measurement and since in
this measurement approach, the anemometer is mounted in a A-1. ASHRAE Standard 41.2-1987 (RA 92), Standard Meth-
duct, the factory calibration will not be valid. The most con- ods for Laboratory Airflow Measurement. Atlanta:
venient and accurate method to calibrate it is to calibrate it in American Society of Heating, Refrigerating and Air
place using a flow standard such as a NIST-traceable venturi Conditioning Engineers Inc.
flowmeter. Following is a partial numbered list of components A-2. SME Performance Test Code 19.5-72, Application, Part
for a vane anemometer flowmeter calibration procedure (see II of Fluid Meters: Interim Supplement 19.5 on Instru-
Figure A-2). ments and Apparatus. New York.
A-3. ANSI/ASHRAE Standard 51-1999/ANSI/AMCA 210-99,
1. Item 1 is the NIST traceable venturi flowmeter. Laboratory Methods of Testing Fans for Aerodynamic
2. Item 2 is the temperature probe (must be upstream of the Performance Rating. Atlanta: American Society of
venturi). Heating, Refrigerating and Air Conditioning Engineers
3. Item 3 is the inlet transition. Inc.

14 ANSI/ASHRAE Standard 130-2008


Figure A-1 Vane anemometer flow-measuring system.

Figure A-2 Vane anemometer flowmeter calibration procedure.

Figure A-3 Correct positioning of the vane in Figures A-1 and A-2.

ANSI/ASHRAE Standard 130-2008 15


(This appendix is not part of this standard. It is merely tion 4.2. The terminal shall be adjusted to deliver the desired
informative and does not contain requirements necessary airflow at an inlet static pressure of 0.75 in. w.c. (187 Pa)
for conformance to the standard. It has not been above the minimum static pressure required to achieve this
processed according to the ANSI requirements for a airflow. The inlet static pressure shall then be increased in
standard and may contain material that has not been increments to the desired maximum inlet static pressure. Air-
subject to public review or a consensus process. flow and static pressure shall be recorded at each increment.
Unresolved objectors on informative material are not
offered the right to appeal at ASHRAE or ANSI.) B2. STEPS FOR FIGURE B-1

INFORMATIVE APPENDIX B a. With initial inlet static pressure at 0.75 in. water w.c.
EXAMPLE FOR MEASUREMENT OF (0.19 kPa) above minimum, adjust airflow to rated (point 1)
PRESSURE-COMPENSATION b. Measure airflow at 1.5in. water w.c. (0.37 kPa) above
CONTROL PERFORMANCE minimum (point 2)
c. Minimum inlet static pressure differential at minimum of
B1. PRESSURE-COMPENSATING 95% of rated air flow (point 3)
(PRESSURE INDEPENDENT) d. Volume variation at rated airflow =
CONTROL PERFORMANCE
( P2 – P3 ) × 100 ( 110 – 95 ) × 100 1500
± ---------------------------------------- = ----------------------------------------- = ------------ = ± 7.5%
B1.1 This test is intended to measure the change in airflow 2 × P1 2 × 100 200
caused by variations in the inlet duct static pressure of termi-
nals with re-setable or preset volume controllers. The terminal e. With initial inlet status pressure at 0.75 in. water w.c.
(0.19 kPa) above minimum, adjust air flow to 50% rated
to be tested shall be installed as shown in Figure 4. This test
(point 4)
method may be used to determine the pressure-compensating
control performance with installations other than as shown in f. Measure air flow at 1.5 in. water w.c. (0.37 kpa) above
minimum (point 5)
Figure 4. These installation conditions shall be described in
the test report. g. Measure flow at the same pressure that was used for
point 3 (point 6)
B1.2 An airflow-measuring means in accordance with Sec- h. Volume variation at 50% rated airflow =
tion 4.3 shall be connected to a straight section of ductwork
that is connected to the primary air inlet of the terminal. The ( P6 – P6 ) × 100 ( 55 – 40 ) × 100 1500
± ---------------------------------------- = -------------------------------------- = ------------ = ± 7.5%
inlet static pressure shall be measured in accordance with Sec- 2 × P1 2 × 100 200

Figure B-1 Graphic depiction of Appendix-B example (using standard air).

16 ANSI/ASHRAE Standard 130-2008


(This appendix is not part of this standard. It is merely (Mixing efficiency = 1°C in 28°C for 188 L/s discharge
informative and does not contain requirements necessary airflow at 75 Pa discharge static
for conformance to the standard. It has not been resistance with 94 L/s 13°C primary
processed according to the ANSI requirements for a air at 250 Pa inlet static pressure and
standard and may contain material that has not been 94 L/s 41°C primary air at 250 Pa
subject to public review or a consensus process. inlet static pressure.)
Unresolved objectors on informative material are not
offered the right to appeal at ASHRAE or ANSI.) C2. FAN-POWERED TERMINAL EXAMPLE

INFORMATIVE APPENDIX C Cold inlet = 200 cfm (94 L/s) at 1.00 in. w.c. (250 Pa)
EXAMPLES FOR MEASUREMENT OF inlet static pressure and 55°F (13°C).
MIXING EFFICIENCY Induced air = 200 cfm (94 L/s) at atmospheric pressure
and 85°F (29°C).
C1. DUAL-DUCT TERMINAL EXAMPLE Discharge = 400 cfm (188 L/s) at 0.30 in. w.c. (75 Pa)
Cold inlet = 200 cfm (94 L/s) at 1.00 in. (250 Pa) inlet static resistance.
static pressure and 55°F (13°C). Maximum discharge air temperature = 71°F (22°C).
Hot inlet = 200 cfm (94 L/s) at 1.00 in. (250 Pa) inlet Minimum discharge air temperature = 69°F (21°C).
static pressure and 105°F (41°C). a = 400 cfm (188 L/s)
Discharge = 400 cfm (188 L/s) at 0.30 in. (75 Pa) static B = 0.30 in. w.c. (75Pa)
resistance. d = 200 cfm (94 L/s)
Maximum discharge air temperature = 81°F (27°C).
F = 1.00 in. w.c. (250Pa)
Minimum discharge air temperature = 79°F (26°C).
e = 200 cfm (94 L/s)
a = 400 cfm (188 L/s)
G = atmospheric pressure
B = 0.30 in. w.c. (75Pa)
x = 71–69 = 2°F (22–21 = 1°C).
d = 200 cfm (94 L/s)
y = 85–55 = 30°F (29–13 = 16°C).
F = 1.00 in. w.c. (250 Pa)
Mixing efficiency = 2°F in. 30°F for 400 cfm discharge
e = 200 cfm (94 L/s)
airflow at 0.30 in. w.c. discharge
G = 1.00 in w.c. (250 Pa) static resistance with 200 cfm 55°F
x = 81–79 = 2°F (27–26 = 1°C) primary air at 1.00 in. w.c. inlet
y = 105–55 = 50°F (41–13 = 28°C) static pressure and 200 cfm 85°F
Mixing efficiency = 2°F in 50°F for 400 cfm discharge induced air at atmospheric pressure.
airflow at 0.30 in. w.c. discharge (Mixing efficiency = 1°C in 16°C for 188 L/s discharge
static resistance with 200 cfm 55°F airflow at 75 Pa discharge static
primary air at 1.00 in. w.c. inlet resistance with 94 L/s 13ºC primary
static pressure and 200 cfm 105°F air at 250 Pa inlet static pressure
primary air at 1.00 in. w.c. inlet and 94 L/s 29°C induced air at
static pressure. atmospheric pressure.)

ANSI/ASHRAE Standard 130-2008 17


(This appendix is not part of this standard. It is merely informative and does not contain requirements necessary for
conformance to the standard. It has not been processed according to the ANSI requirements for a standard and may
contain material that has not been subject to public review or a consensus process. Unresolved objectors on informative
material are not offered the right to appeal at ASHRAE or ANSI.)

INFORMATIVE APPENDIX D
ACOUSTICALLY ISOLATED DUCT

Figure D-1 Acoustically isolated rectangular duct.

Figure D-2 Acoustically isolated round duct.

18 ANSI/ASHRAE Standard 130-2008


POLICY STATEMENT DEFINING ASHRAE’S CONCERN
FOR THE ENVIRONMENTAL IMPACT OF ITS ACTIVITIES
ASHRAE is concerned with the impact of its members’ activities on both the indoor and outdoor environment. ASHRAE’s
members will strive to minimize any possible deleterious effect on the indoor and outdoor environment of the systems and
components in their responsibility while maximizing the beneficial effects these systems provide, consistent with accepted
standards and the practical state of the art.
ASHRAE’s short-range goal is to ensure that the systems and components within its scope do not impact the indoor and
outdoor environment to a greater extent than specified by the standards and guidelines as established by itself and other
responsible bodies.
As an ongoing goal, ASHRAE will, through its Standards Committee and extensive technical committee structure,
continue to generate up-to-date standards and guidelines where appropriate and adopt, recommend, and promote those new
and revised standards developed by other responsible organizations.
Through its Handbook, appropriate chapters will contain up-to-date standards and design considerations as the material is
systematically revised.
ASHRAE will take the lead with respect to dissemination of environmental information of its primary interest and will seek
out and disseminate information from other responsible organizations that is pertinent, as guides to updating standards and
guidelines.
The effects of the design and selection of equipment and systems will be considered within the scope of the system’s
intended use and expected misuse. The disposal of hazardous materials, if any, will also be considered.
ASHRAE’s primary concern for environmental impact will be at the site where equipment within ASHRAE’s scope
operates. However, energy source selection and the possible environmental impact due to the energy source and energy
transportation will be considered where possible. Recommendations concerning energy source selection should be made by
its members.
86427
PC 5/08

Vous aimerez peut-être aussi