YORK VRF Air-Conditioner


Installation Manual )25012 YDCC IOM (English)(YGF)(0911)



YORK VRF Air-Conditioner IOM
Contents
1 SAFETY CONSIDERATIONS ..................................................................................................................................͘...ϭ
2 BEFORE INSTALLATION........................................................................................................................................... 2
3 SELECTING INSTALLATION SITE ............................................................................................................................... 2
4 BEFORE INSTALLATION........................................................................................................................................... 3
5 INDOOR UNIT INSTALLTION.................................................................................................................................... 4
6 REFRIGERANT PIPING WORK................................................................................................................................ ..4
7 DRAIN PIPING WORK ............................................................................................................................................. 6
8 INSTALLING THE DUCT ........................................................................................................................................... 7
9 SET THE ESP ........................................................................................................................................................... 7
10 ELECTRIC WIRING WORK...................................................................................................................................... 7
YORK VRF Air-Conditioner IOM
z Toxic gas may be produced if the refrigerant comes
 SAFETY CONSIDERATIONS
1 in contact with fire such as a fan heater, stove or
Please read the “SAFETY CONSIDERATIONS” carefully cooking device.
before installing the air-conditioner equipment and be z Power off the unit before touching the electrical
sure to install it correctly. parts.
The below notes include two types, both of which are z Do not touch the switch with wet fingers.
related to safety and extremely important. Please read Touching the switch with wet fingers may cause
it carefully. electric shock.
z Be sure the air-conditioner is well grounded.
Never connect the ground line with the gas pipe,
WARNINGĂĂIndicates a potentially water pipe, lightning conductor or telephone lines.
hazardous situation, which, if not avoided, could result Incomplete ground line may cause electric shock
in death or serious injury. or fire.
z Be sure to install a ground leakage breaker.
Failure to install a ground leakage breaker may
CAUTIONĂĂIndicates a situation that may
result in electric shock or fire.
result in injury or equipment damage. According
z Please follow the instructions in this manual to
different condition, it also may result in the accidents
install drain pipe in order to ensure smooth
of serious injury or other damage.
drainage and insulate the pipe to avoid
accumulating of condensate water.
䄺ਞ
WARNING Improper drain pipe may result in water leakage

and property damage.
z Ask the specially trained personnel to carry out z Install the air-conditioner unit, power supply
the installation work. Do not try to install the wiring and connection wires at least 1m away
machine by yourself. from electrical equipments, such as TVs, radios,
z Please perform the installation work in accordance etc. to avoid electromagnetic waves interference
with the steps in this manual. or noise.
Improper installation may result in water leakage, z Remote controller transmitting distance may be
electric shock or fire. shortened than the expected one in the rooms
z Please install the air-conditioner on a foundation with electronic fluorescent lamps (inverter or
strong enough to withstand the weight of the unit. rapid start types).
An insufficient strength foundation may result in Install the indoor unit as far away from fluorescent
the unit falling and causing injuries. lamps as possible.
z Carry out the specified installation work after z Do not install the air-conditioner in the following
taking into account strong winds, typhoons or locations:
earthquakes. (a) Where a mineral oil mist or an oil spray or
Improper installation work may result in the unit vapor is produced, for example in a kitchen.
falling and causing injuries. Plastic parts may be deteriorated, corroded or
z Make sure that a separate power supply circuit is damaged.
provided for this unit and that all electrical work is (b) Where corrosive gas, such as sulfurous acid
carried out by specially trained personnel gas is produced.
according local laws, regulations and this Corroded copper tubes or soldered parts may
installation manual. result in refrigerant leakage.
An insufficient power supply capacity or improper (c) Where near machinery emitting
electrical construction may lead to electric shock electromagnetic waves.
or fire. Electromagnetic waves may disturb the
z Make sure that the specified wires are used and all operation of the control system and result in a
wiring is secure. No external forces act on the malfunction of the equipment.
terminal connections or wires. (d) Where it may have flammable gas leakage,
Improper wiring connections or installation may carboform or floating flammable dust,
result in electric shock or fire. volatile flammable material such as gasoline
z When connecting the wiring of power supply, or thinner.
wired controller and remote controller, the wiring Using air-conditioner in those places may
should be laid orderly so that the electric parts result in fire.
box lid can be securely fastened. z Do not touch heat exchanger fins
z If it appears refrigerant leakage during the Improper touching the heat exchanger fins may
installation process, open the doors and windows result in machine damage or personnel injury.
immediately to ventilate the room thoroughly. z Be very careful about the product transportation.
1
YORK VRF Air-Conditioner IOM
Do not use any packaging PP bands for a means of
transportation to avoid PP bands rupturing and NO
CAUTION
result in product damaging or personnel injury. TE
z If it has the possibility that the temperature and
 BEFORE INSTALLATION
2 humidity inside the ceiling might exceed 30°C and
RH80%, please reinforce the insulation on the unit.
z Do not unpack the unit before reaching the
Use glass wool or polyethylene foam as insulation
installation site. Where unpacking is unavoidable,
and its thickness is more than 10mm.
countermeasure should be done after unpacking
to avoid damaging or scratching of the unit. 3.1 INSTALLATION SITE REQUIREMENTS
z When moving the unit during or after unpacking,
be sure to avoid putting any pressure or strength z The ceiling is strong enough to bear the indoor
on the refrigerant piping, drain pipe or the other unit weight. If not, please reinforce the ceiling
plastic parts, which may damage the unit. before installation.
z Before installing the unit, be sure to check the z Ensure optimum air distribution and nothing
type of refrigerant to be used is R22 or R410A blocks the air passage.
which should be same as outdoor unit. z Condensate water can be drained out smoothly.
z For the installation of the outdoor unit, please z No risk of flammable gas leakage.
refer to the installation manual attached to the z Ensure sufficient clearance for maintenance and
outdoor unit. service. (Refer to Fig. 1)
z Piping between indoor and outdoor units is within
the allowable limit.
3 SELECTING INSTALLATION SITE

YDCC06-45/YDCC018-115 Indoor Units

Note: the distance between indoor unit top and roof should be more than 5 mm; the bottom of drain pan should
be at least 5mm away from the ceiling.

YDCC50~60 /YDCC140~175 Indoor Units

Fig. 1 Clearance for Maintenance and Service

2
YORK VRF Air-Conditioner IOM
4 PREPARATION BEFORE INSTALLATION connection nuts, temperature sensors, EXV coil,
drain pump (if it has), etc. The inspection
4.1 Confirm the position of suspension bolts opening size should be no smaller than 450h450
z Refer to Fig. 2 to see the diameter of suspension mm2.
hole and confirm the bolt location. z Also inspection opening for repairing should be
z Install an inspection opening on the control box installed in the ceiling right below the unit. The
side for convenient maintenance and inspection size should be no smaller than the unit diameter
of the parts such as electrical parts, refrigerant BhE shown in the Fig. 2.

YDCC06~45 /YDCC018~112 Indoor Units

Models A B C D E
YDCC018/020/ Models A B C D E
605 630 830 609 681
025 YDCC066/078 1205 1235 1450 1213 222
YDCC034 805 830 1030 809 881 YDCC095/115 1505 1535 1780 1513 237
YDCC045/053 910 935 1150 914 986

*Note: indoor unit series type of A, B, C and D is determined by the specific letter in the bar code on the unit. For
example, indoor unit YDCC*****-*C* means C type series unit and YDCC*****-*B* means B type.

YDCC50~60 /YDCC140~175 Indoor Units

᥹ㅵሎᇌ㸼

᥹ㅵ໪ᕘሎᇌ PP
ᴎ㒘ൟো
⎆ㅵ ⇨ㅵ

<'&& $%ᴎൟ Ħ Ħ


<'&& &'ᴎൟ Ħ Ħ

<'&& $%ᴎൟ Ħ Ħ


<'&& &'ᴎൟ Ħ Ħ

Fig. 2 Indoor Unit Diameter

3
YORK VRF Air-Conditioner IOM
4.2 Install the suspension bolts
z Use a hole-in-anchor for existing ceilings, and a
sunken insert, sunken anchor or other part to be
procured in the field to reinforce the ceiling to
bearing the weight of the unit for new ceiling.
(Refer to Fig. 3)
z Note˖
If the internal insulation material is PE, in
installation process, please take some preventive 
measure to avoid brazing sparkle contacting the Fig. 5 Check Unit Level
insulation material, which may result in fire.
5.4 Tighten the upper nuts
z Be sure the below washer and nut are installed
within the hanger bracket for fear of bolt rolling
out, this may result in danger.

6 REFRIGERANT PIPING WORK


z Execute insulation completely on both sides of the
gas piping and the liquid piping. Otherwise, water
Fig. 3 Suspension Bolt Installation leakage can result sometimes.
Please use the insulation materials that can
 INDOOR UNIT INSTALLATION
5 withstand temperature of at least 120°C. Reinforce
5.1 Install the indoor unit temporarily the insulation on the refrigerant piping according
to the installation environment. Otherwise,
z Attach the hanger bracket to the suspension bolt. condensate water may form on the surface of the
Be sure to fix it securely by using a nut and washer insulation.
from the upper and lower sides of the hanger
bracket. (Refer to Fig. 4) NO
CAUTION
TE
Please follow the below items.
z Apply ester oil or ether oil to the flare section
(internal and external surface) when using a flare
connection.
z Only the flare nuts included with the unit can be
used. Using different flare nuts may cause
refrigerant leakage.
z To prevent dust, moisture or other contaminant
from infiltrating the piping, either pinch the end or
cover it with tape.
z Do not allow anything other than the designated
Fig. 4 Indoor Unit Suspension
refrigerant to get mixed into the refrigerant circuit,
5.2 Tighten the nuts and adjust the height of the such as air, etc.
unit to reach the installation site z When brazing the refrigerant piping, perform
nitrogen replacement first, or perform brazing
5.3 Check if the unit is horizontally while feeding nitrogen into the refrigerant piping,
level and finally connect the indoor unit using the flare
NO connections.
CAUTION
TE NO
CAUTION
z Make sure that the unit is installed level using a TE
spirit level or a plastic tube filled with water. (Refer z When brazing a pipe while feeding nitrogen inside
to Fig. 5) the pipe, make sure to set the nitrogen pressure to
(One thing to watch out for in particular is if the 0.02MPa (0.2kgf/cm2) or less using the pressure
unit is installed so that the slope is not in the reducing valve.
direction of the drain pipe, which might cause (This pressure is just like breeze blowing to your
leaking.) cheek.)


4
YORK VRF Air-Conditioner IOM
z Do not use flux when brazing refrigerant piping. 6.2 AIR TIGHT TEST
Therefore, use the phosphor copper brazing filler
metal (BCuP) which does not require flux. z Air tight test should be done after the piping
If chlorine based flux is used, it will cause pipe connection completed.
corrosion and contamination of refrigerant oil z Operation method:
(a) Fill in dry nitrogen into the refrigerant piping
6.1 Connect the piping and let the pressure slowly rise to 4.15MPa.
(b) The specified pressure should be maintained
z Be sure to use both a spanner and torque wrench
for 10 minutes, and then soapy water or other
together, as shown in Fig. 6, when connecting or
foaming agent are applied to the connection
disconnecting pipes to/from the unit.
positions, such as brazing seams, screwed
joints ,etc. for leakage detection.
(c) If it has leakage, then tighten or braze the
leakage point.
(d) After it has been confirmed that the piping
does not leak, the dwelling test should be
performed. Fill in the dry nitrogen again and
let the pressure slowly rise to 4.15MPa.
(e) The pressure needs to be maintained for 6
Fig. 6 Piping Connection hours and then record the pressure value
through the manometer. 24 hours later, record
z Refer to Table 1 for the tightening torque. the pressure again.
(f) No pressure drop after 24 hours means it has
Table 1 no leakage. Otherwise, the leaking point must
Pipe Diameter Tightening Torque be found and mended. Then repeat the above
mm (inch) (Ngm) (d) and (e) steps.
Ħ6.35(1/4") 14̚17
Ħ9.53(3/8") 32.5̚40
Ħ12.7(1/2") 49.5̚60 NO
CAUTION
Ħ15.88(5/8") 62̚75 TE
Ħ19.05(3/4") 80̚95 z Gas pressure is relevant to ambient temperature.
Ħ22.23(7/8") 100̚115 So temperature should be considered when judging
the pressure variation. The relationship of pressure
z If no torque wrench is available, please follow the and temperature is shown below.
below method to do the installation.
§ t  273 ·
Using a wrench to tighten flare nuts causes the 'P P1 u ¨ 2  1¸
tightening torque to suddenly grow much tighter © t1  273 ¹
after a certain point. From that point, tighten the
nut further by the appropriate angle listed in Table Pcorrection P2  'P
2.
Table 2 'P — Pressure correction value (bar)
Pipe Diameter Further tightening Recommended arm length Pcorrection — the correced pressure value (bar)
mm (inch) angle of toll

Ħ6.35(1/4") 60e̚ 90e ̚150mm


P1 — 1st record pressure (bar)
Ħ9.53(3/8") 60e̚ 90e ̚200mm P2 — 2nd record pressure (bar)
Ħ12.7(1/2") 45e̚ 75e ̚250mm
Ħ15.88(5/8") 45e̚ 75e ̚300mm t1 — 1st record temperature (°C)
Ħ19.05(3/4") 30e̚60e ̚400mm
t1 —2nd record temperature (°C)
Ħ22.23(7/8") 30e̚60e ̚400mm

z Do not connect indoor units with outdoor units in


during the air test process. Otherwise, it may result
NO
CAUTION in nitrogen gas emtering into the outdoor unit.
TE
Over tightening may damage the flare and cause 6.3 Insulate the piping
leakage.
z After checking it has no leakage, be sure to insulate
the connection parts of both liquid and and gas
pipe with sufficient thickness heat-resistant

5
YORK VRF Air-Conditioner IOM
polythylene materials. thoroughly insulated to avoid accumulating of
z Be sure to insulate the field piping all the way to condensate water.
the piping connection inside the unit. Any exposed
piping may casue condensate water or being
burned if touched.

 DRAIN PIPING WORK


7
z Drain pipe connection diameter may vary
depending on different models. It can be divided as
free drainage and pump drainage. So please
confirm the model name and use the right method 
for that model.
Fig. 9 Pump Drainage
z Be sure the drain pipe works well and smothly
before making the duct connection. (It is not easy
z To prevent the drain pipe from sagging, install
to check the drain pipe when the duct has been
hanging bracket every 1~1.5 m.
connected.)
z When connecting the drain pipe, effective method
7.1 Install the drain pipe should be carried out to guarantee no leakage on
each connection area.
z Make sure the drain works properly.
z To avoid condensate water accumulating on the
z Diameter of the drain pipe should be larger than or
drain pipe and dropping down, the drain pipe
equal to the one of the connecting pipe. (drain pipe
should be insulated.
connection diameter of indoor unit is 3/4”
(19.05mm)) 7.2 Check the drain pipe
z Make a water trap on the drain pipe outlet from
z After piping work is finished, check if drainage
indoor unit. The water trap should meet below
flows smoothly.
requirements. (A, B ı 50mm)
(a) Free drainage
Gradually insert approximately 1000 ml clean
water into the drain pan to check drainage
status.

Fig. 7 Water Trap

z If central drain pipe has been used, keep the drain


pipe short and sloping downwards at a gradient of
(b) Pump drainage
at least 2/100 to prevent air pockets from forming.
Remove the lid of the control box. Connect
(Refer to Fig. 8)
the relevant power supply and ground lines,
z Select central drain pipe of proper size according to then close the lid.
the total capacity of the connected unit. Gradually insert approximately 1000 ml clean
water from the fin coil side.
Power on the unit and inspect the drain
>100mm Central drain pipe
pump working status.
NO
CAUTION
TE
z The electric wiring works should be performed by
Fig. 8 Central Drain Pipe
specially qualified electricians.
z If no electricians in site, please flow the above
steps to do drainage confirmation after the system
z For the indoor unit with pump drainage test running.
(a) Be sure the drain raising pipe height is within
700mm.
8 INSTALLING THE DUCT
(b) Place the drain raising pipe vertically and make z Materials for duct installation are supplied in the
sure it is no further than 300mm. (Refer to Fig. field.
8) z Refer to Fig. 10 to connect the duct.
(c) The spare drain hole also needs to be

6
YORK VRF Air-Conditioner IOM
YDCC25-45/YDCC066-115 indoor unit models’ ESP
(External Static Pressure) can be divided as 3 types
– 15 Pa, 40 Pa and 100 Pa;
YDCC50~60/YDCC140~175 indoor unit models’ ESP
(External Static Pressure) can be divided as 3 types
– 15 Pa, 50 Pa and 100 Pa;
Out factory state, YDCC indoor unit ESP is 15 Pa
(default value). User can adjust the ESP according
to the actual pressure drop of the air duct.
z Indoor unit ESP can be adjusted by changing the
Fig. 10 Duct Connection connection site of fan wiring in the control board.
For detail setting method of different indoor ESP,
NO please refer to the wiring diagram attached to the
CAUTION control box lid.
TE
z Wrap both the inlet-side and outlet-side flange and 10 ELECTRIC WIRING WORK
the duct connection area with aluminium tape for 10.1 General introduction
something similar to prevent air escaping.
z Please attach an air filter inside the air passage on z Shut off the power before doing any work.
the inlet-side. (Use an air filter which duct z All field supplied parts and materials and electric
collection efficiency (in a gravimetric technique) is works must conform to local laws.
higher than 50%) z All wiring works should be performed by specially
z Be sure to insulate the duct to prevent condensate qualified electricians.
water from forming. (Material: glass wool or z Install a wiring interrupter or ground-fault circuit
polyethylene foam, above 25mm thickness) interrupter for the power supply wiring.
z Be  
    
 
z Be sure the air-conditioner is well grounded. Never
z Duct pressure drop of YDCC06~18/YDCC018~053 connect the ground line with gas pipe, water pipe,
indoor unit models cannot be higher than 30 Pa; lightning conductor or telephone lines.
YDCC25~45/YDCC066~115 indoor unit models z Do not turn on the power sully unless all the work
cannot be higher than 80 Pa; has been done.
YDCC50~60/YDCC140~175 indoor unit models z Wiring of different thickness or diameter cannot be
cannot be higher than 100 Pa. connected to one power supply wiring terminal.
z The air outlet cannot be too high and be positioned z For wiring, please use the designated power supply
at the place where it directly blows the people for a wiring and connect firmly, then secure to prevent
long period. external pressure being exerted on the terminal
z To reduce vibration and noise, it is better to use board.
flexible connection to connect the air inlet and z The terminal screw should not be tightened too
outlet duct with indoor unit. hard or too loose. Too hard may damage the
terminal board and too loose may result in bad
 SET THE ESP
9 connection and danger due to terminal board
z YDCC06~18/YDCC018~053 indoor unit models’ ESP overheating.
(External Static Pressure) can be divided as 3 types
– 0 Pa, 15 Pa and 30 Pa;
10.2 Electrical parameters
Indoor unit power supply and Max operation current
Indoor Unit Model Max Operation Current(A)
Power Supply H0 type
BTU type kW type H2 type H4 type
(or Cooling Only)
YDCC06̚09 YDCC018̚025 0.26 4.76 -
YDCC12̚25 YDCC034̚066 0.85 8.15 9.85
YDCC30̚45 YDCC078̚115 220V̚ 50Hz 1.31 10.31 15.81
YDCC50 YDCC140 2.8 - -
YDCC60 YDCC175 3.18 - -

7
YORK VRF Air-Conditioner IOM
10.3 Power distribution
z Refer to Fig. 11 for power distribution of the system.

Fig. 11 Indoor and Outdoor Units Power Distribution Diagram

z An independent refrigeration system is controlled by a single switch and several systems cannot be controlled
with a switch. Especially forbid some indoors unit in a system sharing a control switch with other system,
while the other indoor units are controlled by another switch.
10.4 Indoor unit field wiring
z For detail indoor unit wiring, see the “Wring Diagram” attached to the control box lid when laying the indoor
unit electrical wiring.
10.5 Setting indoor unit model
z Refer to the “Wring Diagram” attached to the control box lid for indoor unit model setting.
10.5 Communication network

Note: indoor unit communication lines TB2, TB3 (TB2 in, TB3out) cannot be conversely connected, otherwise it will
have communication failure and the unit cannot startup.
Fig. 12 Connection Line Connection

8
YORK VRF Air-Conditioner IOM
10.7 Install the controller determined by the specific letter in the bar code
attached on the unit. For example, indoor unit
z Install the wire controller on the pre-reserved site YDCC*****-*C* means C type series unit and
on the wall. YDCC*****-*B* means B type.
z Carcassing for communication wiring should be z The indoor units in one group should be
ready before installation the controller. The
connected in a same power supply to guarantee
recommended communication line is RVSP2h normal initialization of wire controller when
0.75. Be sure to pull the wires through the PVC power on.
conduit. z Connection of indoor unit and wire controller:
Note: the communication wire and PVC conduit (a) One wire controller connecting only one
are the field supplied parts. indoor unit: (refer to the wiring diagram)
10.8 Connect the wire controller and indoor unit (b) One wire controller connecting multi indoor
units:
z Group control can be realized through the wire For YDCC-B (C, D) series indoor unit, wiring
controller. For YDCC-B (C, D) series indoor unit, diagram of wire controller and the indoor
one wire controller can connect to max 4 indoor units is shown in Fig. 14.
units.
Note: indoor unit series type of A, B, C and D is



Fig. 13 One wire controller connects to multi indoor units (B, C or D type)

9
YDCC IOM(English)(YGF)(0911)
NOTHING