RC STRUCTURAL DESIGN REVIEW CHECKLIST

PROJECT LPG TANK DEPOT FOR A.A RANO


LOCATION IJEGUN, SATELLITE TOWN, LAGOS
CLIENT A.A RANO
CONTRACTOR WIZCHINO ENGINEERINGT LIMITED
CONSULTANT CRUSTEAM NIGERIA LIMITED

SECTION
ELEMENTS TO BE CHECKED REMARKS
DATA
1.0 GEOTECHNICAL DATA
1.1 SOIL INVESTIGATION RESULT Provided, under review
1.2 PROPOSED TYPE OF FOUNDATION Pile
1.3 BUILDING LOCATION Swampy, water logged
1.4 WATER TABLE To be verified from soil report
1.5 SOIL BEARING CAPACITY / PILE CAPACITIES To be verified from soil report
1.6 WIND TUNNEL TEST IF ANY Not Applicable
1.7 THIRD PARTY REPORT IF ANY
1.8 ARCHITECTURE DRAWINGS Provided, Under Review
1.9 WIND PARAMETERS Expert verification Required
1.10 SEISMIC PARAMETERS
1.11 GRADE OF CONCRETE OK
1.12 GRADE OF STEEL 360N/mm specified, 460N/mm2
2

recommended
LOADING
DEAD LOAD, DL Concrete desnsity of 26kN/m3
specified. OK
LIVE LOAD, LL OK
WIND LOAD, W Wind Pressure of 0.58kN/m2
specified .Expert verification
required
SEISMIC LOAD, E Not Available
UPLIFT LOAD Not Available
TEMPERATURE T Not applicable
LOAD COMBINATIONS
ULTIMATE LIMIT STATE No calculation sheet provided,
could not be verified
SERVICEABILITY LIMIT STATE No calculation sheet provided,
could not be verified
SPECIAL COMBINATIONS
ANALYSIS / DESIGN
APPROPRIATE CODES AND STANDARDS HAVE BEEN
EMPLOYED

DESIGN LOADING COMPLY WITH BRIEF

DESIGN METHODS ARE APPROPRIATE

DESIGN CALCULATIONS ARE CORRECT

COMPUTER INPUT DATA CORRECTLY ENTERED

INTERPRETATION OF RESULTS IS CORRECT


DESIGN COMPLY WITH ALL STATUTORY
REQUIREMENTS

DESIGN MATERIALS ARE COMPATIBLE AND


SUITABLE FOR ENVIRONMENTS
DESIGN COMPONENTS
BEAM, MINIMUM 10% MANUAL CALCULATION Detailed drawing of beam
elements not provided
SLAB, MINIMUM 10% MANUAL CALCULATION Detailed drawing of slab not
provided
COLUMN, MINIMUM 10% MANUAL CALCULATION Detailed drawing of columns not
provided
SHEAR WALLS, MINIMUM 10% MANUAL Not applicable
CALCULATION
STAIRCASE / RAMP SLABS
ROOF TRUSS IF ANY,
PARAPET
STEEL STRUCTURAL MEMBERS IF ANY
PILE CAP
RAFT
RETAINING WALL
WATER TANK SUPPORT
RC SWIMMING POOL
CHECK UPLIFT PRESSURE DONE
DESIGN CRITERIA
ADEQUATE COVER IS PROVIDED FOR EXPOSURE OK
AND FIRE RATINGS
MINIMUM STEEL PROVIDED OK for all elements
MAXIMUM STEEL NOT EXCEEDED
DEFLECTION TO BE IN COMPLIANCE WITH
REQUIREMENTS
CRACK WIDTHS WITHIN LIMIT Not applicable
TOTAL AND STORY DRIFT WITHIN LIMITS Not applicable
EXPANSION AND MOVEMENT JOINTS PROVIDED,
WHEREVER NECESSARY
SUFFICIENT TIES PROVIDED Not shown in detail
REINFORCEMENT (BENDING MOMENT, SHEAR AND No Calculation sheet Provided
TORSION) PROVIDED COMPLIES WITH CALCULATION
DETAILING
ARRANGEMENT OF BAR PERMITS PLACEMENT OF Yes
CONCRETE
AVOID CONGESTION OF BARS ESPECIALLY AT Detailed structural members not
JOINTS given to ascertain this
SECTIONS, BAR TYPE AND NUMBERS CLEARLY Not Okay
INDICATED
CURTAILMENT, ANCHORAGE LENGTH AND LAPPING Not Indicated in details
ARE ADEQUATE
SEISMIC DETAILING COMPLIED
ADEQUATE NOTES PROVIDED Yes
DRAWINGS
DRAWINGS DIMENSIONALLY CORRECT Yes
DRAWINGS IN COMPLIANCE WITH OTHER
DISCIPLINES
DRAWINGS IN COMPLIANCE WITH CALCULATIONS No Calculation sheet Provided
SPECIFICATIONS CORRECT, COMPLETE AND Further verification required
CONSISTENT WITH DRAWINGS
OPENINGS, DROPS ETC CLEARLY SHOWN
LOADING PLANS, VERTICAL LOADS LAYOUT Not Provided
SPECIFICATIONS OF STRUCTURAL MATERIAL Not Provided
SHOWN ON DRAWINGS
DOCUMENTS FOR CHECKER
ARCHITECTURAL DRAWINGS Provided, under review
STRUCTURAL DRAWINGS Provided
M&E REQUIREMENTS Not Provided
CALCULATIONS AND MATHEMATICAL MODELS Not Provided