Numerical No.

-2

Calculate the voltage regulations at the tail end load at Point X of the following L.T. rural
feeder of A.A.C., ANT conductor [7/3.31]

11/.4 KV Transformer 7.5 HP 5 HP 5 HP


0.3 KM 0.2 KM 0.2 KM
X
O 0.2 KM 0.1 KM 0.25 KM 0.1 KM

5 HP 7.5 HP 7.5 HP 10 HP
(a) Load in H.P.
(b) Distance in KM.
(c) Diversity factor 2.5
(d) Power factor 0.8
(e) Regulation constant is 38.16 for 7/3.31 MM AAC ANT conductor

Solution:
1) 47.5 x 0.3 --------- 14.25
2) 42.5 x 0.2 --------- 8.50
3) 35 x 0.2 --------- 7.00
4) 27.5 x 0.1 --------- 2.75
5) 22.5 x 0.25 --------- 5.625
6) 15 x 0.2 --------- 3.00
7) 10 x 0.1 --------- 1.00

42.125 HP. Km.

% Regulation = Total HP Km x Regulation Constant x Conversion factor for HP to KW


100 x D.F.

% Regulation = 42.125 x 38.16 x 0.746 = 6%


100 x 2.5 x 0.8

(Where regulation constant of 7/3.31 AAC @ 0.8 P.F. is 38.16, Diversity factor of 2.5)

The End