Académique Documents
Professionnel Documents
Culture Documents
MI 4100
MI 4101
User’s manual
Version 1.0, Code no. 20 750 191
Distributor:
Mark on your equipment certifies that this equipment meets the requirements of the EU
(European Union) concerning safety and electromagnetic compatibility regulations.
Manufacturer:
METREL d.d.
Ljubljanska cesta 77
1354 Horjul
Slovenia
© 2005 METREL
No part of this publication may be reproduced or utilized in any form or by any means
without permission in writing from METREL.
Table of contents
Table of contents
3
Table of contents
4
MI4100/MI4101 – Power monitor
In addition to its durable body, easy installation and simple operation Power monitor also
boasts the following features:
Direct connection of current inputs to standard CTs with 5 A output reduces
problems related to wiring positioning and burden resistor selection,
Single instrument can be used in wide voltage range from 0 V to 500 V, this range
can be further extended with potential transformers,
LCD with 4x20 characters offers simultaneous display of different measured
values,
up to 42 days of active and reactive energy monitoring (integration period of 15
minutes),
RS 485 communication port compatible with industry-standard MODBUS protocol,
enables use of standard off-the-shelf software packages and connection to
standard controllers (RS 232 communication adapter for connection to a PC is
also available),
4 optically insulated digital inputs configurable as 40-bit counters (increments of
0.01 inc/imp ÷ 327.67 inc/imp), integration period synchronisation or tariff selectors
(2 or 4 tariffs),
2 digital outputs configurable as various alarms (voltage, current, active or reactive
power, frequency out of range), power demand control outputs or energy pulse
output.
Standard 96mm x 96mm panel case
5
MI4100/MI4101 – Power monitor
Immediately disconnect from the power line and discontinue use if:
the unit is dropped or subjected to an impact in which the interior is exposed,
the unit emits a strange smell, excessive heat, or smoke.
Caution:
It is recommended to short any unused measurement input using insulated jumper
wire (especially CT inputs), otherwise external noise may influence readings
(especially total power and energy).
6
MI4100/MI4101 – Power monitor
Safety (LVD)
Safety requirements for electrical equipment for measurement, control,
EN 61010 - 1
and laboratory use – Part 1: General requirements
7
MI4100/MI4101 – Power monitor
2 3
Legend:
1...........LCD with 4x20 characters. The backlight is automatically turned on whenever a
key is pressed.
2...........Confirmation key (ENTER). Use it to confirm option, to show information screen
(press and hold for 1 s) or to enter configuration menu (press and hold for 5 s).
3...........Arrow keys. Use ↑ and ↓ keys to select appropriate option. Use ← and → keys to
change parameters.
8
MI4100/MI4101 – Power monitor
NC – Not connected
9
MI4100/MI4101 – Power monitor
1 7
3 6
4 5
Legend:
1...........3-phase 5 A current inputs.
Burden resistors are built into Power monitor.
2...........Information label with connection diagrams for various Power monitor ports.
3...........RS 485 communication port.
4...........2 relay outputs. Relay contacts are normally open (N.O.).
Maximum switching current is 1 A. Maximum switching voltage is 25 V.
5...........Configurable digital inputs.
Intended for use in SELV environment only (max. voltage 25 V)!
Not TTL compatible.
6...........Power supply input.
7...........3-phase voltage inputs (max. line-to-line voltage 500 V).
Warning:
Power monitor must be connected to voltage lines which are protected by
fuses or circuit breakers. See section 4.3 for information about protecting Power
monitor measurement inputs.
10
MI4100/MI4101 – Power monitor
3.4 Cleaning
No special maintenance is required for the housing. To clean the surface of the
instrument use a soft cloth slightly moistened with soapy water or alcohol. Then leave the
instrument to dry totally before use.
Warnings:
Do not use liquids based on petrol or hydrocarbons!
Do not spill cleaning liquid over the instrument!
3.6 Service
Service intervention or adjustment procedure is allowed to be carried out only by a
competent authorized person. Unauthorised person is not allowed to open the Power
monitor unit. There are no user replaceable components inside the instrument.
For repairs under warranty, or at any other time, please contact your distributor.
11
MI4100/MI4101 – Power monitor
Step Action
Make sure that the
instrument installation
position is away from
high current wires or bus
bars.
1 Insert screw adapter into
the holes in the side
cover of the instrument.
2 Tighten the adapter.
3 Screw the adapter into
step 3 position (e.g. into the
step 2 rack ...).
4 Repeat the above steps
step 1 with the second screw
adapter (opposite side of
the instrument).
Step Action
1 Mount the Power monitor.
2 Turn power off before connecting the instrument to current
transformers or making voltage connections.
Insert appropriate fuses into measurement and power supply cables (see
section 4.3)
3 Connect current lines to built-in current transformers (CTs).
Take care to orient the CTs correctly.
4 Jumper any unused CT inputs with an insulated shorting wire to minimise
noise influence on measurements.
5 Connect the voltage wires to the voltage measurement inputs.
Always start with the N wire.
6 Double check that the current measurement phases match voltage
measurement phases.
7 Jumper any unused voltage inputs with an insulated shorting wire to
minimise noise influence on measurements.
8 Connect relay output terminals to the monitoring equipment (if applicable).
9 Connect digital input/output port to the monitoring equipment (if
applicable).
10 Connect RS 485 port to the communication network (if applicable).
Verify polarisation voltage present on communication network before
connecting Power monitor. Make sure that it doesn’t exceed allowed limit.
11 Power on the instrument and start using it.
12
MI4100/MI4101 – Power monitor
Figure 4.2: Basic connection of Power monitor to the star (WYE, 4-wire) power system
(left) and delta (3-wire) power system (right)
Any unused instrument CT or voltage input must be shorted with insulated jumper wire.
Pay special attention to the polarity of current phases – they need to match the polarity of
voltage phases. Power monitor will report incorrect power polarity otherwise.
If you need to extend Power monitor voltage measuring range, use appropriate voltage
transformers. The following figure presents typical voltage extension circuits.
Figure 4.3: Extending Power monitor voltage measuring range with voltage transformers;
star (WYE, 4-wire) connection (left), delta (3-wire) connection (right)
13
MI4100/MI4101 – Power monitor
Use similar measures when connecting Power monitor using Aaron connection, see
figure below.
N L1
x A/5 A L2
L1
x A/5 A L3
L2
x A/5 A
L3
L1 N L3
Figure 4.4: Connecting Power monitor using Aaron connection (left), extending voltage
and current measuring range of Aaron connection (right)
Remember to set correct voltage and current transformation factors (see section 5.3).
Power monitor will report incorrect measurement results otherwise.
Warnings:
Output of external current transformer will produce dangerous voltages if left open
while current is flowing through primary winding. Do not disconnect external CT
output while it’s connected to the live circuit to prevent damage to the CT or
the operator!
Due to the high voltages involved, it is suggested that only licensed electrician
install and configure high voltage transformers. Voltage transformers have to be
rated to handle line voltages.
For connecting current inputs to the measured system use wire which insulation
withstands at least 85 °C.
4.3 External fuses for voltage inputs and mains power supply
It is necessary to protect Power monitor voltage inputs with external fuses or circuit
breakers. Several fuse connection diagrams are shown in Figure 4.2 and Figure 4.3.
Never insert a fuse into neutral (N) measuring wire.
It is also necessary to protect instrument power supply input with appropriate fuse. We
recommend using a fuse with nominal current rating of around 100 mA.
14
MI4100/MI4101 – Power monitor
15
MI4100/MI4101 – Power monitor
16
MI4100/MI4101 – Power monitor
Meter Communication
Instrument information information
information IP information
Calibration Counter
and RTC info* information
Output 1
Recorder Output status Output 2 information
information information information
*
RTC info is valid only for MI 4101
Figure 5.1: Circling through Power monitor information screens
17
MI4100/MI4101 – Power monitor
Notes:
When adjusting settings press and hold ← or → key for fast rewind.
Select Exit in main configuration menu and confirm with ENTER to return to
measurement screens. Power monitor automatically returns from configuration
menu after 1 minute of inactivity.
18
MI4100/MI4101 – Power monitor
19
MI4100/MI4101 – Power monitor
Notes:
Each device on MODBUS network must be assigned different network address.
Otherwise data on the network will be corrupted and communication will fail. Refer
to section 6 for more information.
Input 3 is available as an IP synchronisation source only if 2-tariff system is
selected (it is used as a tariff selector in 4-tariff system).
Integration period can be set to match specific standards or as a convenient filter
for short term fluctuations in input power, as required.
It is possible to select from 1 to 4 different energy types for recording. Energy is
recorded in circular buffer (see section 7 for register addresses and programming
considerations). Number of possible records ranges from 1614 (all 4 energy types
selected) to 4035 (only one energy type selected for recording). If integration
period of 15 minutes is selected, this corresponds to 42 days (1 energy type), 28
days (2 energy types), 21 days (3 energy types) and 16 days (all 4 energy types
selected).
Because energy recording buffers are circular they hold accumulated results for
the last 16 to 42 days, depending on number of selected energy types for
recording.
MI4100 is not equipped with real time clock (RTC). After power-up date and tme
are set to 01. 01. 2005 00:00:00. Optionally its clock can be set via MODBUS
interface. Refer to section 7.3 for details. Once clock is set, instrument preserves
set time/date until power supply is switched off.
Each input can only be used for one operation at a time. For instance, if you select 4-tariff
system, you can’t use input 3 as a source for IP synchronization as it is used as tariff
selector (together with input 4).
Tariff selection
Input 3 Input 4 2-tariff system 4-tariff system
0 0 1st tariff 1st tariff
0 1 2nd tariff 2nd tariff
1 0 1st tariff 3rd tariff
1 1 2nd tariff 4th tariff
Please note that only input 4 is used for tariff selection in 2-tariff system. Continuous
voltage has to be present for each selected input, otherwise Power monitor sets the 1st
tariff (both input states are treated as 0). 0 means that the voltage between any input (+)
and COMM (-) is 0 V. 1 means there is a voltage in the range between 6 V to 25 V
between any input (+) and COMM (-).
20
MI4100/MI4101 – Power monitor
Caution:
Power monitor digital inputs are not TTL compatible!
Maximum input voltage is 25 V.
Maximum cable length is up to 100 m. The length is limited by induced voltage on
the line. Functioning of each digital input will be impaired if induced voltage
exceeds voltage threshold level. Digital input may be damaged if induced voltage
exceeds 25 V!
Keep cables away from high voltage lines and measure induced voltages before
connecting cables to Power monitor!
Caution:
Connection power is set for each output independently. Power monitor checks
power on each input every minute. Power monitor will disconnect only one load if
calculation shows this is adequate (output 1 has priority). The same is true when
the possibility to reconnect any of the loads is evaluated.
Power monitor relays can’t switch loads connected to mains power supply
directly – use appropriate interface circuit if such operation is needed.
Consider maximum switching current and voltage ratings.
Pay special attention when switching inductive loads to prevent damage caused by
disconnected-state energy accumulated in the load.
Cable length is limited only by the induced voltage. Relay output may be damaged
if induced voltage exceeds 25 V!
Keep cables away from high voltage lines and measure induced voltages before
connecting cables to Power monitor!
21
MI4100/MI4101 – Power monitor
22
MI4100/MI4101 – Power monitor
23
MI4100/MI4101 – Power monitor
U1 U2 U3 U, I, f
screen
I1 I2 I3 LX - LY
Press and hold ↑ Press and hold ↑
or ↓ key for 1 s or ↓ key for 2 s
Use ↑ and ↓ keys to select menu items, ENTER key confirms settings and
Use ← and → keys confirm selection with ENTER key returns to Configuration screen
*
Instrument info Calibration & RTC Meter Output 2
*
Real time clock info – valid only for MI 4101
24
MI4100/MI4101 – Power monitor
6 MODBUS communication
6.1 Introduction to MODBUS protocol
MODBUS communication protocol was designed by Modicon at the end of 1970s. It is
widely accepted communication protocol in industry, allowing commonly available means
of connecting almost many industrial electronic devices. Beside measurements reading,
protocol allows administration of devices across the network. Standard is published by
Modbus-IDA group and it is available at www.modbus.org. It is also widely supported by
many SCADA (Supervisory Control And Data Acquisition) systems and other software,
including Labview, PLC control software, etc.
The MODBUS serial line protocol is a master-slaves protocol. Only one master (at the
same time) is connected to the bus, and one or several (max. 247) slaves nodes are also
connected to the same serial bus. The master always initiates a MODBUS
communication. The slave nodes will never transmit data without receiving a request from
the master node. The slave nodes will never communicate with each other. The master
node initiates only one MODBUS transaction at the same time.
Notes:
MODBUS application protocol corresponds to OSI model level 7, providing
client/server communication between devices connected on buses or networks.
On MODBUS serial line the client role is provided by the master of the serial bus
and the slave nodes act as servers.
The master always addresses one or all slaves (the master doesn’t have an address).
The master can address each slave individually (unicast mode). Such conversation
consists of request from the master and reply from the slave. The master can also
address all slaves at the same time (broadcast mode). Slaves don’t reply to such
messages. An address of ‘0’ is used in such case.
Power monitor use RTU serial transmission mode with CRC (cyclic redundancy check)
error detection.
25
MI4100/MI4101 – Power monitor
Power monitor sends and receives data in fixed format over the network. Data byte is
binary coded and transmitted with least-significant bit first. User can select transmission
with even or no parity bit added, and with 1 or 2 stop bits (the later is available only if
none parity is selected).
The baud rate is programmable as 4800 bps, 9600 bps, 19200 bps (default), 38400 bps
or 57600 bps (refer to section 5.3 for more information).
Notes:
Each device on MODBUS network must be assigned a unique address between 1
and 247. If two or more devices on the same network have the same addresses,
the communication will fail.
It is a good practice to maintain a database of MODBUS devices, their connections
and addresses.
All devices connected MODBUS network must have the same communication
speed selected, otherwise data will be corrupted and communication not possible.
Maximum data transfer rate depends on network distance and electrical noise
present in the network. Try to decrease communication speed if you encounter
communication problems.
Warning:
4-pairs crossed CAT 5/6 cable may cause system damage in 2-wire MODBUS
system (see MODBUS specification).
26
MI4100/MI4101 – Power monitor
Notes:
Power monitor connector pins are described in Figure 3.2.
Often it is necessary to install repeaters in MODBUS network where more than 32
devices are installed (up to 247 maximum) or where total connection distance
exceeds 1000 m.
Derivates must be short, never more than 20 m – never connect line termination
resistor to derivate.
It is possible to interconnect 2-wire and 4-wire devices, see MODBUS specification
for more information.
RS-485 requires line termination with two 150 Ω/0.5 W resistors to reduce line reflections,
see figure below. 100 Ω resistors can be used instead of 150 Ω (resistor value should be
equal to characteristic cable impedance). Install one resistor at the controller input/output
buffer and the other at the buffer of the most remote device (at each extremity of the trunk
cable).
D1
150 Ω 150 Ω
D0
Common*
Controller
A better solution for line termination is to use a serial capacitor of 1 nF (10 V min.) with
120 Ω/0.25 W resistor. This solution is preferred when communication line has to be
polarised.
RS485 uses half duplex mode for communication. Electrical operation in receive mode:
D0 line is pulled up by weak “1” (+5 V and 10 kΩ resistor).
D1 line is pulled down by weak “0” (0 V and 10 kΩ resistor).
It is assumed that lines are driven by other sources. Pull-up resistors are built-
in only to prevent random signals at input (false detections due to high induced
voltage on connected cables may still occur).
27
MI4100/MI4101 – Power monitor
+5V
10k
Iout D0
D1
10k
RS-485
Iout max=60mA@5V
Handling half duplex communication with a PC usually requires software control of data
direction. This can prove to be a problem under some operating systems like Windows
(high speed communication is required). Contact your software vendor for additional
information if you encounter communication problems.
RS-232 or USB to RS-485 converters are available for standard PCs. They handle data
direction control automatically. Power monitor is tested with Nudam converters models:
ND-6520 (RS-232 to RS-485) and ND-6530 (USB to RS-485).
28
MI4100/MI4101 – Power monitor
29
MI4100/MI4101 – Power monitor
30
MI4100/MI4101 – Power monitor
Meter output registers, start address 0100h, all values are in binary format.
Register address Mode Data format Multiplication Unit Register name
dec hex factor
00256 0100 R lo word
0.1 W Total active power
00257 0101 R hi word
00258 0102 R lo word
0.1 VA Total apparent power
00259 0103 R hi word
00260 0104 R lo word
0.1 VAr Total reactive power
00261 0105 R hi word
00262 0106 R word 0.01 / Total power factor (see 7.2)
00263 0107 R word 0.01 Hz Frequency
31
MI4100/MI4101 – Power monitor
32
MI4100/MI4101 – Power monitor
33
MI4100/MI4101 – Power monitor
34
MI4100/MI4101 – Power monitor
Harmonics output registers, start address 0200h, all values are in binary format.
Register address Mode Data format Multiplication Unit Register name
dec hex factor
00512 0200 R word 0.1 % L1 voltage THD
st
00513 0201 R word 0.1 % L1 voltage, 1 harmonic
nd
00514 0202 R word 0.1 % L1 voltage, 2 harmonic
rd
00515 0203 R word 0.1 % L1 voltage, 3 harmonic
th
R n harmonic address:
513 + (n – 1)
st
00543 021F R word 0.1 % L1 voltage, 31 harmonic
35
MI4100/MI4101 – Power monitor
36
MI4100/MI4101 – Power monitor
Clear IP max.
Clear energy
Clear energy
Clear input
Remote IP
Command
counters
counters
recorder
records
status
sync.
To execute any command first set appropriate bit(s) to “1” using MODBUS command 06. Command(s) are
executed after bit 7 (command status) is set to “1”. After the completion of requested action(s), Power
monitor sets appropriate bit(s) to “0”.
Communication
Voltage range
Password
Connect.
status
type
Communication status
Bit 3 Description
0 Disabled
1 Enabled
IP synchronization
source
37
MI4100/MI4101 – Power monitor
Output 1
Input 1
Input 3
Input 4
Input 2
38
MI4100/MI4101 – Power monitor
capacitive energy
Active consumed
Active generated
inductive energy
Reactive
Reactive
energy
energy
Energy (active, reactive)
Bit 7, Bit 6, Bit 5, Bit 4 Description
0 Disabled
1 Enabled
parameters error
AD converter
RTC present
RTC error
Settings/
error
error
Every bit is set to “1” whenever Power monitor encounters error during operation, except RTC present bit
which is set to “1” for MI 4101:
Settings/parameters error bit is set if default parameters are loaded into the instrument (see
section 5.6) – check set parameters and measured values, send the instrument for calibration if
necessary.
When ADC converter error bit is set, the instrument AD converter failed – send it for repair. The
instrument operation is stopped.
RTC error bit is set when real-time clock time is invalid – set real-time clock time and date (this bit
has meaning only for MI 4101).
Please contact manufacturer or your distributor if recorder memory error bit is set.
39
MI4100/MI4101 – Power monitor
Total reactive
Total power
Total active
power sign
power sign
factor type
Value Total PF = 1? Total power = 0? Total active Total reactive Total power
power sign power sign factor type
0 Total PF value is Total power value is Negative Negative Inductive
valid valid
1 Total PF = 1.00 Total power = 0.0 Positive Positive Capacitive
If Total PF = 1? bit is set to “1”, total power factor value is 1.00 – other bits have no meaning. If Total
power = 0? bit is set to “1”, total measured power is 0 – other power values have no meaning and are
undefined. Total power factor value is represented as unsigned byte with values between 0 and 100.
Divide by 100 to get actual total power factor value. This value is meaningful only if Total PF = 1? and
Total power = 0? bits are both set to “0”.
Phase reactive
Phase power
Phase active
power sign
power sign
factor type
Value Phase PF = 1? Phase power = 0? Phase active Phase reactive Phase power
power sign power sign factor type
0 Phase PF value Phase power value Negative Negative Inductive
is valid is valid
1 Phase PF = 1.00 Phase power = 0.0 Positive Positive Capacitive
If Phase PF = 1? bit is set to “1”, phase power factor value is 1.00 – other bits have no meaning. If Phase
power = 0? bit is set to “1”, total measured power is 0 – other power values have no meaning and are
undefined. Phase power factor value is represented as unsigned byte with values between 0 and 100.
Divide by 100 to get actual phase power factor value. This value is meaningful only if Phase PF = 1? and
Phase power = 0? bits are both set to “0”.
40
MI4100/MI4101 – Power monitor
One word-long value corresponds to unsigned integer data type (ANSI C). Two-word long
value corresponds to unsigned long integer data type (ANSI C). It is the responsibility of
controller (or a PC communication program) to interpret larger data structures, including
3-word records (consisting of low, middle and high words).
The register represents a pointer relative to the energy recording memory address where
the first energy record for reading is positioned. It is 0-based (the first record has address
of 0000h). If the register value is FFFFh, there are no energy records available for
reading.
Power monitor always sends 48 words to controller (24 energy register values). The 1st
register address is defined in “Number of 1st selected record” at address 00025/0019h.
Controller always has to start reading at address 00768/0300h.
Maximum number of energy record depends on number of selected energy types for
recording. Refer to section 5.3 about recorder configuration (FreeLapRec parameter).
Value is available in “Maximum possible number of records” register at address
00024/0018h.
Each energy record is started with time/date stamp (see below for ANSI C programming
example on how to interpret time stamp value). This stamp represents elapsed time from
1. 1. 2005 00:00:00. Note that MI 4100 instrument time/date values are set to 0 each time
it’s powered on, while in MI 4101 which is equipped with real-time clock (RTC), has valid
time/date stamp. It is possible to set time/date by sending new values to “Power monitor
real time and date” register (addresses from 00026/001Ah to 00028/001Ch, data format
is described below). The instrument preserves set time/date until power supply is
switched off (unless RTC is incorporated in the instrument).
Each record consists of time/date, active consumed energy (eP+), reactive consumed
energy (eQ+), active generated energy (eP-) and reactive generated energy (eQ-).
Please note that only energy types, selected for recording, are sent.
41
MI4100/MI4101 – Power monitor
Example 1:
Recording of active consumed energy (eP+) is set.
In such case each record consists of 4 registers.
th
00812 032C lo word 12 selected record for read – time/date
00813 032D hi word Time/date
00814 032E lo word eP+
00815 032F hi word eP+
Example 2:
Recording of active consumed (eP+) and reactive consumed energy (eQ+) is set.
In such case each record consists of 6 registers.
th
00810 032A lo word 12 selected record for read – time/date
00811 032B hi word Time/date
00812 032C lo word energy eP+
00813 032D hi word energy eP+
00814 032E lo word energy eQ+
00815 032F hi word energy eQ+
42
MI4100/MI4101 – Power monitor
Each 32-bits time stamp consists of two parts. The lowest 26 bits represent elapsed
minutes from 1.1.2005 00:00:00. The highest 6 bits represent IP length in minutes
multiplied by 4. Therefore 15 sec IP length is represented by value 1, 30 sec IP is
represented by value 2 and so on. ANSI C example for time stamp conversion into real
time value is presented below:
rectime = localtime
// IP length in minutes
iplenght = (temp & 0xfc000000) / 4;
43
MI4100/MI4101 – Power monitor
Power monitor uses special sequence to set calibration date and time (available only to
manufacturer, distributors and authorized calibration labs). Please contact manufacturer
for additional information.
Remote IP synchronization
Remote synchronization is preformed by writing “1” into the 6 bit of register 0000h using
MODBUS command 06. Instrument then synchronize IP, and set bit 7 to “1” (command
status). Finally bit 6 is automatically reset back to “0”.
Exception function codes are sent to a controller by slave device in case of an error
during execution of request.
Error correction
Power monitor implements CRC error correction.
44
MI4100/MI4101 – Power monitor
There is internal timeout sequence, which resets communication devices and enables
communication again.
Example 1:
Setting voltage transformation factor (UTF, register 0002h) to 40 (28h).
Example 2:
Setting slave network address (register 0016h) to 10 (0Ah), incorrect register
address will result in communication error (trying to write a word into one-byte
register).
Example 3:
If tariff 2 is active enable output 1, otherwise disable it. Preserve alarm settings for
output 1.
45
MI4100/MI4101 – Power monitor
8 Technical specifications
8.1 General
Power supply voltage ........................ 180 V a.c. ÷ 260 V a.c., 50 Hz/60 Hz
Protection classification .................... double insulation
Pollution degree ................................ 3
Protection degree.............................. IP 40
Over voltage category....................... CAT II 600 V / CAT III 300 V
Load ............................................ 5 VA max.
Reference conditions
Reference temperature range........... 0 °C ÷ +40 °C
Reference humidity range................. 30 %RH ÷ 75 %RH, non-condensing
Operation conditions
Working temperature range .............. -10 °C ÷ +50 °C
Maximum relative humidity ............... 95 %RH (0 °C ÷ +40 °C), non-condensing
Storage conditions
Temperature range ........................... -10 OC ÷ +70 OC
Maximum relative humidity ............... 90 %RH (-10 OC ÷ +40 OC)
70 %RH (+40 OC ÷ +70 OC)
Caution:
Error of voltage and current transducers is not considered in this specification.
Accuracies apply for 1 year in reference conditions. Temperature coefficient
outside these limits is at most the error in reference conditions + 0.01 % of
measured value per °C.
In case the unit gets moistened the results and/or safety could be impaired. In
such case it is recommended to dry the unit for at least 12 hours.
46
MI4100/MI4101 – Power monitor
8.3 Voltage
TRMS phase to neutral voltage LX – N, AC
Nominal input range (V) Phase to neutral Resolution (V)
Accuracy
voltage range (V)
140
280 0.00 UFS ÷ 0.14 UFS 0.1 ±(1.3 V * UTF)
500
140
±(0.2 %FS +
280 0.15 UFS ÷ 1.10 UFS 0.1
0.3 % of reading)
500
Voltage crest factor is 1.5 × UN (measuring range). Accuracies are given according to full scale value
(UFS = UN * UTF). Over-range indication with ↑↑↑ mark. Over-range indicator appears when line voltage is
out-of-range. Accuracies apply for frequency range 45.00 Hz ÷ 65.00 Hz. Line-to-neutral input impedance is
approx. 550 kΩ. Line-to-line input impedance is approx. 1100 kΩ.
8.4 Current
TRMS current
Current range (A) Resolution (A) Accuracy
0.00 IFS ÷ 0.10 IFS TBD*
0.001 ±(0.1 %FS +
0.11 IFS ÷ 1.25 IFS
0.4 % of reading)
Nominal current input range is 0 A ÷ 5 A (IN). Current crest factor is 2.0 × IN. Accuracies are given according
to full scale value (IFS = IN * ITF). Over-range indication with ↑↑↑ mark. Accuracies apply for frequency range
45.00 Hz ÷ 65.00 Hz.
*
To be defined
47
MI4100/MI4101 – Power monitor
8.5 Frequency
Frequency range (Hz) Resolution (Hz) Accuracy
45.00 ÷ 65.00 0.01 ±0.04 Hz
Out-of-range indication with SYNC? mark. Phase used for synchronisation is displayed. Accuracy applies
for voltage range 0.15 UN ÷ 1.20 UN.
8.8 Energy
IP max/IP last energy
Product of voltage range, voltage TF, current range Resolution
and current TF (MWh, MVAh, MVArh) (Wh, VAh, Accuracy
VArh)
0 ÷ 1.000.000 10 TBD*
48
MI4100/MI4101 – Power monitor
Total energy
Product of voltage range, voltage TF, current range Resolution
and current TF (Wh, VAh, VArh) (Wh, VAh, Accuracy
VArh)
0 ÷ 1.000.000 10 TBD*
*
To be defined
Voltage harmonics
Measuring range (V) Resolution (%) Accuracy (V)
UM < 0.03 UN ±5 % UM
0.1
UM > 0.03 UN ±0.15 % UN
Voltage THD
Nominal input range (V) Resolution (%) Accuracy (V)
140
280 0.1 ±1 % UN
500
U N: nominal input voltage range (TRMS)
st st
U M: measured harmonic voltage (TRMS), M = 1 ... 31
Current harmonics
Measuring range (A) Resolution (%) Accuracy (A)
IM < 0.03 IN ±5 % IM
0.1
IM > 0.03 IN ±0.15 % IN
Current THD
Nominal input range (A) Resolution (%) Accuracy (V)
5 0.1 ±1 % IN
IN: nominal input current range (TRMS)
st st
IM: measured harmonic current (TRMS), M = 1 ... 31
49
MI4100/MI4101 – Power monitor
50