Vous êtes sur la page 1sur 515

INSTRUCTION MANUAL

FOR
CURRENT DIFFERENTIAL SYSTEM

BE1-CDS220

Publication: 9 3139 00 990


Revision: A 09/2000
INTRODUCTION

This instruction manual provides information about the operation and installation of the BE1-CDS Current
Differential System. A summary of the information provided is listed below.
• General information, specifications, and a Quick Start guide.
• Functional description and setting parameters for the input/output functions, protection and control
functions, metering functions, and reporting and alarm functions.
• BESTlogic programmable logic design and programming.
• Documentation of the preprogrammed logic schemes and application tips.
• Description of security and user interface setup including ASCII communication and the Human-
Machine Interface (HMI).
• Installation procedures, dimension drawings, and connection diagrams.
• Description of the front panel HMI and ASCII command interface with write access security
procedures.
• A summary of setting, metering, reporting, control, and miscellaneous commands.
• Testing and maintenance procedures.
• Appendices containing characteristic curves, an ASCII command/HMI cross reference, relay
settings record forms, terminal emulation guidelines, settings calculations assistance, and an index.
A table of contents for the instruction manual is provided in this introduction. A detailed table of contents
for each section is provided in the front of each section. Information about communication protocols such
as Modbus or Distributed Network Protocol (DNP) 3.0 is covered in a separate manual for each optional
protocol.

WARNING
TO AVOID PERSONAL INJURY OR EQUIPMENT DAMAGE, ONLY
QUALIFIED PERSONNEL SHOULD PERFORM THE
PROCEDURES PRESENTED IN THIS MANUAL.

BE1-CDS Introduction i
First Printing: November 1999

Printed in USA

© 1999, 2000 Basler Electric Co., Highland, IL 62249

September 2000

CONFIDENTIAL INFORMATION
OF BASLER ELECTRIC COMPANY, HIGHLAND, IL. IT IS LOANED
FOR CONFIDENTIAL USE, SUBJECT TO RETURN ON REQUEST,
AND WITH THE MUTUAL UNDERSTANDING THAT IT WILL NOT
BE USED IN ANY MANNER DETRIMENTAL TO THE INTEREST
OF BASLER ELECTRIC COMPANY.

It is not the intention of this manual to cover all details and variations in equipment, nor
does this manual provide data for every possible contingency regarding installation or
operation. The availability and design of all features and options are subject to
modification without notice. Should further information be required, contact Basler
Electric Company, Highland, Illinois.

BASLER ELECTRIC
ROUTE 143, BOX 269
HIGHLAND, IL 62249 USA
http://www.basler.com, info@basler.com
PHONE 618-654-2341 FAX 618-654-2351
ii Introduction BE1-CDS
PRODUCT REVISION HISTORY
The following information provides a historical summary of the changes made to the embedded software
(firmware) and hardware of this device. The corresponding revisions made to this instruction manual are
also summarized. This revision history is separated into four categories: Application Program Firmware
Version, BESTCOMS Version, Hardware Version, and Manual Version. All revisions are listed in
chronological order.

Application
Program Firmware Change
Version

1.12.00 - 04/30/99 • Initial Release

1.12.01 – 06/17/99 • Improved current check record diagnostic routine.


• Corrected problem that caused the current magnitude in several
reporting functions to be reported in primary amps squared.
• Changed several setting defaults.

1.13.01 – 11/17/99 • Added option to select Percent of Average Restraint Current operating
characteristic to the 87R, Percentage Restrained Differential element.
• Added Modbus protocol option.
• Improved COMTRADE oscillography recording function.
- Provided user setting to partition the 240 cycles of oscillography
memory to provide control over the length of the records.
- Doubled available oscillography memory to 480 cycles when
enhanced recording option is present.
- Added *.hdr file in addition to the two files required by the
COMTRADE standard (*.cfg and *.dat) to provide additional
information useful in analyzing the data contained in the
oscillographic record.
• Improved target reporting function such that the Trip LED on the relay
front panel only latches when there are targets to be displayed on the
HMI. The pickup condition, indicated by the Trip LED flashing, is now a
higher priority than latching to indicate that targets are being displayed
on the HMI.
• Corrected problem with the 51 inverse overcurrent timing algorithm that
could cause an element to time out too fast when using the V2 curve.

1.14.00 – 03/03/00 • Corrected problem that caused the programmable variable names to be
limited to 10 characters instead of 16 characters. This problem occurred
with version 1.13.01.
• Added Mode 6, Latching Timer to 62 timer functions.
• Added DNP 3.0 Protocol
• Added a feature for the demand recording function to allow the user to
select block average or sliding block average calculation method in
addition to the existing thermal calculation method.

BE1-CDS Introduction iii


Application
Program Firmware Change
Version
1.14.01 – 09/12/00 • Added reporting of the protocol option to the COM2 setting screen on the
LCD HMI.
• Improved the arrangement of information on the current metering
screens on the HMI.
• Added improvements to DNP 3.0 protocol to make it Level 2
compliant.

BESTCOMS Version Change


1.01.01 – 06/99 • Initial release

Hardware Version Change


G – 04/30/99 • Initial Release.
H – 03/08/00 • Changed escutcheon plate from mounting holes to mounting studs.
– 08/04/00 • Added CE qualification, UL recognition and CSA certification.
J – 09/27/00 • Improved the RS-485 operation when driving long lines.
K – 09/2900 • Improved Surge Withstand Capability.

Manual Version
and ECO/ECA Change
Rev None – 11/99 • Initial Release
Rev A – 09/00 – 10886 • Changed the manual organization from two volumes to one volume in a
loose leaf binder with tabs to separate the manual Sections. Added
Revision History to the Introduction, and CE qualification, UL recognition,
CSA certification, and DNP 3.0 certification. Added drawings and made
corrections to all Sections.

iv Introduction BE1-CDS
CONTENTS

SECTION 1 General Information.............................................................................1-1


SECTION 2 Quick Start...........................................................................................2-1
SECTION 3 Input And Output Functions.................................................................3-1
SECTION 4 Protection And Control ........................................................................4-1
SECTION 5 Metering ..............................................................................................5-1
SECTION 6 Reporting And Alarm Functions ..........................................................6-1
SECTION 7 BESTlogic Programmable Logic .........................................................7-1
SECTION 8 Application...........................................................................................8-1
SECTION 9 Security ...............................................................................................9-1
SECTION 10 Human Machine Interface .................................................................10-1
SECTION 11 ASCII Command Interface ................................................................11-1
SECTION 12 Installation .........................................................................................12-1
SECTION 13 Testing And Maintenance..................................................................13-1
APPENDIX A Time-Current Characteristics ............................................................. A-1
APPENDIX B Command Cross Reference............................................................... B-1
APPENDIX C Settings Record.................................................................................. C-1
APPENDIX D Setting Terminal Communications ..................................................... D-1
APPENDIX E Settings Calculations.......................................................................... E-1

BE1-CDS Introduction v
SECTION 1 • GENERAL INFORMATION
TABLE OF CONTENTS

List of Figures ........................................................................................................................................ ii


List of Tables.......................................................................................................................................... ii
SECTION 1 • GENERAL INFORMATION ..................................................................................................1-1
DESCRIPTION .......................................................................................................................................1-1
FEATURES.............................................................................................................................................1-1
I/O Functions (Section 3) ....................................................................................................................1-1
Protection and Control Functions (Section 4).....................................................................................1-2
Metering Functions (Section 5)...........................................................................................................1-3
Reporting and Alarm Functions (Section 6)........................................................................................1-3
BESTlogic Programmable Logic (Section 7) ......................................................................................1-5
Security (Section 9).............................................................................................................................1-5
Human-Machine Interface (Controls and Indicators) (Section 10) .....................................................1-6
ASCII Command Interface (Section 11) .............................................................................................1-6
PRIMARY APPLICATIONS ....................................................................................................................1-6
DIFFERENTIAL PROTECTION APPLICATION CONSIDERATIONS...................................................1-7
Problem 1: False Differential Current Due to Poor CT Performance .................................................1-7
Problem 2: Measured Current Magnitude Mismatch ..........................................................................1-8
Problem 3: Mismatch Caused by Load Tap Changers.......................................................................1-9
Problem 4: Phase Angle Shift .............................................................................................................1-9
Problem 5: Zero Sequence Current Sources Within The Zone Of Protection..................................1-12
Problem 6: Transformer Energization Inrush And Overexcitation ....................................................1-13
Problem 7: Digital Measurement Errors............................................................................................1-14
MODEL AND STYLE NUMBER DESCRIPTION .................................................................................1-14
General .............................................................................................................................................1-14
Sample Style Number .......................................................................................................................1-15
OPERATIONAL SPECIFICATIONS .....................................................................................................1-15
Metered Current Values And Accuracy ............................................................................................1-15
Calculated Values And Accuracy......................................................................................................1-16
Real Time Clock...............................................................................................................................1-16
IRIG...................................................................................................................................................1-16
Recognition Time On Contact Inputs................................................................................................1-16
87 Differential Functions ...................................................................................................................1-16
87ND Neutral Differential Function ...................................................................................................1-17
Time Overcurrent Functions .............................................................................................................1-18
Time-Current Characteristic Curves .................................................................................................1-18
Instantaneous Overcurrent Functions ..............................................................................................1-18
Breaker Fail Timer (BF) ....................................................................................................................1-19
General Purpose Timers (62, 162) ...................................................................................................1-19
Automatic Setting Group Characteristics..........................................................................................1-19
BESTlogic Update Rate ....................................................................................................................1-19
GENERAL SPECIFICATIONS .............................................................................................................1-20
AC Current Inputs With 5 A CT.........................................................................................................1-20
AC Current Inputs with 1 A CT .........................................................................................................1-20
Analog To Digital Converter..............................................................................................................1-20
Power Supply ....................................................................................................................................1-20
Output Contacts ................................................................................................................................1-20
Control Inputs....................................................................................................................................1-20
Communication Ports........................................................................................................................1-21
Display ..............................................................................................................................................1-21
Isolation.............................................................................................................................................1-21

BE1-CDS General Information i


Surge Withstand Capability.............................................................................................................. 1-21
Radio Frequency Interference (RFI) ................................................................................................ 1-21
Electrostatic Discharge (ESD) ......................................................................................................... 1-21
UL Recognized ................................................................................................................................ 1-21
C.S.A. Certified ................................................................................................................................ 1-22
CE Qualified ..................................................................................................................................... 1-22
DNP Certified ................................................................................................................................... 1-22
Environment ..................................................................................................................................... 1-22
Shock ............................................................................................................................................... 1-22
Vibration ........................................................................................................................................... 1-22
Weight .............................................................................................................................................. 1-22
Case Size......................................................................................................................................... 1-22

List of Figures
Figure 1-1. Percentage Restrained Differential Characteristic .................................................................1-7
Figure 1-2. Tap Adjust For Mismatch........................................................................................................1-8
Figure 1-3. Currents On Different Voltage Bases .....................................................................................1-8
Figure 1-4. Delta/Wye Transformer Currents..........................................................................................1-10
Figure 1-5. Three-Phase Connections, Delta-Wye Configuration, CT Compensation ...........................1-11
Figure 1-6. Three-Phase Connections, Delta-Wye Configuration, Internal Phase Compensation ........1-11
Figure 1-7. Traditional Zero-Sequence Trap for Application With Ground Banks ..................................1-13
Figure 1-8. Style Number Identification Chart.........................................................................................1-15
Figure 1-9. 87 Response Characteristic Curves.....................................................................................1-17

List of Tables
Table 1-1. Burden....................................................................................................................................1-21

ii General Information BE1-CDS


SECTION 1 • GENERAL INFORMATION

DESCRIPTION
The BE1-CDS220 Current Differential System is an economical, microprocessor based, multifunction
system that provides two-input, three-phase percentage differential with harmonic restraint, three-phase,
ground, and negative sequence overcurrent protection with control, breaker failure, breaker monitoring,
transformer monitoring, and metering functions in an integrated system with communications. The
BE1-CDS Current Differential System is intended for use in any low impedance current differential
protection application including transformer, generator, motor, and bus protection. Four setting groups
are provided for adaptive relaying with automatic selection logic for cold load pickup and/or dynamic
setting group changes.
BE1-CDS relays have eight programmable contact sensing inputs, six programmable outputs, and one
alarm output. Outputs can be assigned various functions by logical programming to perform either
protection, control, or indicator operations. For example, protection functions could cause a protective
trip operation. Control functions could cause a manual trip, manual close, or automatic reclose operation.
Indicators could be relay fail, setting group one enable, setting group two enable, and others.
Protection scheme designers may select from a number of pre-programmed logic schemes that perform
the most common protection and control requirements or create a custom scheme using BESTlogic.
A Quick Start, Section 2, provides BE1-CDS Current Differential System users with a simplified How To
Get Started procedure.

FEATURES
The BE1-CDS220 relay includes many features for the protection, monitoring, and control of power
system equipment such as transformers, breakers, buses, generators, and motors. These features
include protection and control functions, metering functions, and reporting and alarm functions. A highly
flexible programmable logic system called BESTlogic allows the user to apply the available functions with
complete flexibility and customize the system to meet the requirements of the protected power system.
Programmable I/O, extensive communications features, and an optional advanced HMI (Human Machine
Interface) provide easy access to the features provided. BE1-CDS220 relay users with personal
computers (PC) have another easy access means to communicate, program, control, and monitor
relay/system performance. That means is BESTCOMS for BE1-CDS220. BESTCOMS is a Windows
based software application that enhances communication between the PC user and the BE1-CDS220
relay. This software is provided free with every BE1-CDS220 relay. Another software application tool is
BESTWAVE. BESTWAVE is a utility program to view standard COMTRADE (Common Format for
Transient Data Exchange) files and Basler UMOS (Utilities Management Operating System) files
captured by the Basler Electric multifunction relays. This software is available free of charge through the
web site at http://www.basler.com or Customer Service at the Highland, Illinois manufacturing facility.
The following information summarizes the features included in this multifunction device. The organization
of this information outlines organization of the rest of the manual. Each feature, along with how to set it
up and how to use the outputs, is described in complete detail in the later sections of this manual.

I/O Functions (Section 3)

Power System Measurement Functions


• Two sets of three-phase currents are digitally sampled and digitally filtered. The fundamental,
second, and fifth harmonics are extracted using a Discrete Fourier Transform (DFT) algorithm for
use by all of the current based functions.
• Neutral (residual) and negative sequence current magnitudes are derived from each set of three-
phase currents.

BE1-CDS General Information 1-1


• Each set of three-phase currents can be phase-shift and tap compensated for use in transformer
differential applications.
• The digital sampling rate tracks the measured frequency to provide high accuracy at frequencies
other than nominal frequency to make this relay ideally suited for applications such as generator,
motor, and generator step-up transformer differential protection.
• An optional independent ground current input is available for directly measuring the current in a
transformer neutral, tertiary winding, or a flux balancing CT and for providing ground differential
protection.
• Each of the seven current sensing circuits are low burden and isolated to allow improving zones
of protection with fewer costly CTs.

Contact Sensing Inputs


• Eight programmable contact sensing inputs with programmable signal conditioning provide binary
logic interface to the protection and control system: IN1, IN2, IN3, IN4, IN5, IN6, IN7, IN8.
• The function of each input is programmable using BESTlogic and can be given a user meaningful
name for the variable and for each state (open and closed) for use in reporting functions.

Contact Outputs
• Six programmable general purpose contact outputs provide binary logic interface to the
protection and control system: OUT1, OUT2, OUT3, OUT4, OUT5, OUT6.
• One programmable, fail-safe, alarm output: OUTA
• All outputs are trip rated and output 1 and 6 are high speed (quarter-cycle nominal speed).
Output 6 is Form C.
• Each output is programmable using BESTlogic and can be given a user meaningful name for the
variable and for each state (open and closed) for use in reporting functions.
• Output logic can be overridden to open, close, or pulse each output contact for testing or control
purposes.

Protection and Control Functions (Section 4)

Setting Groups
• Four settings groups allow adaptive relaying to be implemented to optimize the relay settings for
various operating conditions.
• Automatic and external logic can be employed to select the active setting group.

Differential Protection
• Three-phase percentage restrained differential protection with harmonic restraint: 87.
• Restricted earth fault ground differential protection with optional independent ground input: 87ND.
• Tap compensation for the differential protection can be automatically calculated by the relay
based upon user settings of CT ratio, MVA and kV base values.

Overcurrent Protection
• Nine instantaneous overcurrent functions with settable time delay. Three each for Phase,
Neutral, and Negative Sequence. Each function is individually assignable to any of the current
input circuits. Functions are: 50TP, 150TP, 250TP, 50TN, 150TN, 250TN, 50TQ, 150TQ, 250TQ.
• Nine inverse time overcurrent functions with integrating or instantaneous reset. Three each for
Phase, Neutral, and Negative Sequence. Each function is individually assignable to any of the
current input circuits. Functions are: 51TP, 151TP, 251TP, 51TN, 151TN, 251TN, 51TQ, 151TQ,
251TQ.
1-2 General Information BE1-CDS
• Time overcurrent functions employ a dynamic integrating timing algorithm covering a range from
pickup to 40 times pickup with selectable instantaneous or integrated reset characteristics.
• Time overcurrent curves conform to the IEEE PC37.112 document and include seven curves
similar to Westinghouse/ABB CO curves, five curves similar to GE IAC curves, four IEC curves, a
fixed time curve, and a user programmable curve.
• Digital signal processing filters out unwanted harmonic components while providing fast
overcurrent response with limited transient overreach and overtravel.

Breaker Failure Protection


• One breaker failure protection function block is assignable to any of the current input circuits.
• The current circuit assigned to the breaker failure function block also determines which current
circuit is used by the breaker monitoring functions described later.

General Purpose Logic Timers


• Two general purpose logic timers with six modes of operation: 62, 162.

Virtual Control Switches


• One virtual breaker control switch, accessible locally from the optional HMI or remotely from the
communications ports, can be used to provide trip and close control of a selected breaker: 101.
• The breaker label provided for the breaker monitoring function is used to label the virtual breaker
control switch. This makes it easily discernible which breaker is being controlled since there is
often more than one breaker associated with the differential zone of protection.
• Eight virtual switches with three modes of operation, accessible locally from the optional HMI or
remotely from the communications ports, can be used to provide additional control; for example,
to trip and close additional switches or breakers, or to enable and disable certain functions such
as 43, 143, 243, 343, 443, 543, 643, 743.

Metering Functions (Section 5)


• Metering is provided for all measured phase and neutral currents and all derived neutral and
negative sequence currents.
• Metering is also provided for the phase and tap compensated restraint, 2nd and 5th harmonic,
and differential currents.

Reporting and Alarm Functions (Section 6)

Relay Identification
• The relay includes four 30-character, free-form fields for the user to enter information to identify
the relay. Examples would be station name, circuit number, relay system, purchase order, etc.
These fields are used by many of the reporting functions to identify which relay created the
report.

Clock
• A real-time clock is included with a capacitor backup that will keep time upon loss of power for 8
to 24 hours depending upon conditions.
• A standard IRIG input (Format B002 from IRIG Standard 200-98) is provided for receiving time
synch signals from a master clock.
• The time reporting format is settable for 12 or 24 hour format and for mm/dd/yy or dd/mm/yy
format.
• Automatic daylight savings time adjustment can be enabled.

BE1-CDS General Information 1-3


General Status Reporting
• The relay has extensive capability to report its general status for monitoring, commissioning, and
trouble shooting.
• Status reports are available from the optional HMI or the communications ports.

Demand Reporting
• Ampere demand registers are provided for monitoring A, B, C, N, and Q. These registers are
assignable to any of the current input circuits.
• The demand interval and demand calculation method is separately settable for phase, neutral,
and negative sequence measurements.
• The demand reporting function records today’s peak, yesterday’s peak, and peak since reset with
time stamps for each register.
• An optional 4000 point data array can record over 40 days of 15 minute demand data.

Differential Current Monitoring


• A detailed current check record can be requested from the relay to aid in initial in-service
readings to verify correct phase and tap compensation of the differential currents. This report
can be stored with commissioning records to save time during initial check out.
• Once in service, the mismatch in the differential function is continuously monitored and can
provide an alarm if the mismatch is approaching a trip condition due to loading current. A current
check record is generated when this occurs and the diagnostic function will indicated the possible
source of the mismatch: for example, incorrect or missing phase compensation.

Transformer Monitoring
• Transformer through-fault duty statistics are recorded including number of through faults,
accumulated through-fault (It or I2t), and maximum through-fault (It or I2t). The
through-fault current measurement is assignable to any of the current input circuits.
• Each of these conditions can be set to alarm.

Breaker Monitoring
• Breaker statistics are recorded for a single breaker. They include the number of operations,
accumulated interrupted I or I2, and breaker time to trip. This function is associated with the
current input circuit assigned to the breaker failure function block.
• Each of these conditions can be set to alarm.

Trip Circuit Monitoring


• A trip circuit monitor function is provided to monitor the trip circuit of a breaker or lockout relay for
loss of voltage (fuse blown) or loss of continuity (trip coil open).
• Additional trip or close circuit monitors can be implemented in BESTlogic using additional inputs,
logic timers and programmable logic alarms.

Fault Reporting
• Fault reports consist of simple target information, fault summary reports, and detailed
oscillography records to enable the user to retrieve information about disturbances in as much
detail as is desired.
• Oscillography memory can be partitioned into 6 to 16 records (6 to 32 records with enhanced
recording option, Load Profile option Y).
• The relay records and reports oscillography data in industry standard IEEE, COMTRADE format
to allow using any fault analysis software.

1-4 General Information BE1-CDS


Sequence Of Events Recorder
• A 255 event sequence of events recorder (SER) is provided that records and time stamps all
inputs and outputs to the relay as well as all alarm conditions monitored by the relay. Time
stamps are to the nearest quarter cycle resolution.
• I/O and Alarm reports can be extracted from the records as well as reports of events recorded
during the time span associated with a specific fault report.

Alarm Function
• The relay includes extensive self diagnostics. Fatal relay trouble alarms are not programmable
and are dedicated to OUTA and the relay trouble LED on the front of the relay.
• Additional relay trouble alarms and all other alarm functions are programmable for major or minor
priority. Programmed alarms are indicated by major and minor alarm LEDs on the front of the
relay. The major and minor alarm points can also can be programmed to any output contact
including OUTA.
• The optional HMI provides local annunciation of programmed alarm conditions.
• Active alarms can be read and reset from the optional HMI or from the communications ports. A
historical sequence of events report of alarms with time stamps as to when each alarm occurred
and cleared is also available from the communications ports.
• Twenty-eight alarm conditions are available to be monitored including user definable logic
conditions using BESTlogic.

Version Report
• The version of the embedded software (firmware) is available from the optional front panel
interface HMI or the communications ports.
• The unit serial number and style number is also available from the communications ports.

BESTlogic Programmable Logic (Section 7)


• Each of the protection and control functions in the BE1-CDS is implemented in an independent
function that is equivalent to its single function, discrete device counterpart so that it is immed-
iately familiar to the protection engineer. Each independent function block has all of the inputs
and outputs that the discrete component counterpart might have. Programming BESTlogic is
equivalent to choosing the devices required by your protection and control scheme and drawing
schematic diagrams to connect the inputs and outputs to obtain the desired operational logic.
• Several preprogrammed logic schemes are provided and thoroughly documented in this manual
in Section 8, Applications. To use the relay in one of these applications, it is only necessary to
make that scheme active.
• A set of custom logic settings is also available for you to optimize the functionality to the specific
needs of your operations practices and power system requirements.

Security (Section 9)
• Security can be defined for three distinct functional access areas: Settings, Reports, and Control.
Each functional access area can be assigned a password. A global password can provide
access to all three functional areas. Each of these four passwords can be unique or multiple
functional access areas can have the same password.
• A second dimension of security is provided by allowing the user to restrict access to any of the
three functional access areas from only specific communication ports. For example, you could
set security to deny access to control commands from the rear RS-232 port that is connected
through a modem to a telephone line.
• Security settings only affect write access. You have read access from any port to any area.

BE1-CDS General Information 1-5


Human-Machine Interface (Controls and Indicators) (Section 10)
• Each BE1-CDS220 comes with a front panel display with LED indicators for power, relay trouble
alarm, minor alarm, major alarm, and trip. Each BE1-CDS also comes with the software
application program BESTCOMS-CDS220-16. This program is a user friendly, Windows® based
program that makes relay setup and support very easy.
• The optional programmable graphical LCD allows the relay to replace local indication and control
functions such as panel metering, alarm annunciation, and control switches.
• The HMI is set up in a menu tree with four scrolling buttons for navigation. Edit and Reset
pushbuttons provide access to change parameters and reset targets, alarms, and other registers.
The scrolling buttons are used for data entry when in edit mode. Edit mode is indicated by an
Edit LED on the Edit button.
• The LCD has automatic priority logic to govern what is being displayed on the screen so that
when an operator approaches, the information of most interest is automatically displayed without
having to navigate the menu structure. The priorities are targets, then alarms, then the
programmable automatic scrolling list.
• Up to 16 screens can be defined in the programmable automatic scroll list.

ASCII Command Interface (Section 11)


• Three independent, isolated communications ports provide access to all functions in the relay.
Com 0 is a 9 pin RS-232 port located on the front of the case. Com 1 is a nine pin RS-232 port
located on the back of the case. Com 2 is a 3-wire, RS-485 port located on the back of the case.
• Standard communications is an ASCII command interface to allow easy interaction with the relay
using standard, off the shelf, communications software.
• The ASCII command interface is optimized to allow automating the procedure for setting the relay
by allowing settings files to be captured from the relay and edited using any software that
supports *.txt file format. These ASCII *.txt files can then be used to set the relay using the send
text file function of the communications software.
• Modbus and other common protocols are optionally available for the RS 485 communications
port. A separate instruction manual appropriate for the protocol comes with each unit. Consult
the product bulletin or the factory for availability of these options and instruction manuals.

PRIMARY APPLICATIONS
The BE1-CDS Current Differential System provides percentage restrained differential protection along
with multiple overcurrent elements and is intended for use in any low impedance current differential
protection application including transformer, generator, motor, reactor, and bus protection. Its unique
capabilities make it ideally suited for applications with the following requirements.
• Applications that require low burden to extend the linear range of CTs.
• Applications where dedicated CTs for the differential are not available. Unlike traditional
differential relays, dedicated CT circuits are not required because each CT input is isolated from
the others and phase shift compensation can be accomplished internally.
• Applications that require high accuracy across a wide frequency range such as motor, generator,
and generator step-up transformer protection or in cogeneration facilities.
• Applications that require the flexibility provided by wide settings ranges, multiple setting groups,
and multiple coordination curves in one unit.
• Applications that require the economy and space savings provided by a multifunction, multiphase
unit. This one unit can provide all of the protection, as well as, the local and remote indication,
metering, and control required on a typical circuit.
• Applications that require harmonic restraint to aid security for the differential.
• Applications that require communication capability and protocol support.
• Applications where the optional case configurations facilitate modernizing protection and control
systems in existing substations.
1-6 General Information BE1-CDS
• Applications where the capabilities of a digital multifunction relay are required, yet drawout
construction is also desirable.
• Applications where bus protection is provided by a high speed overcurrent blocking scheme on
the transformer bus mains instead of dedicated bus differential circuit.
• Applications where the capabilities of intelligent electronic devices (IEDs) are used to decrease
relay, and equipment maintenance costs.

DIFFERENTIAL PROTECTION APPLICATION CONSIDERATIONS


The principle of current differential relaying is simple in concept. Measure the current flowing into the
protected zone and the current flowing out of the protected zone. These should match exactly (sum to
zero). If they do not, there is a fault within the protected zone. The mismatch in current that results from
the instantaneous summation of the currents into and out of the zone of protection is called the differential
current or the operate current. While the concept is simple, differential protection has several difficulties
which present challenges to the application of this type of protection. The BE1-CDS Current Differential
System provides several features that allow it to easily address these complications and enable it to be
used in all differential applications including transformer protection.

Problem 1: False Differential Current Due to Poor CT Performance

General
The principle of current differential relaying requires accurate measurement of the currents entering and
exiting the zone of protection. During fault conditions where high current is flowing through the zone of
protection, a CT may saturate and not faithfully reproduce the current flowing in the primary system. This
will cause a false differential current to be seen by the differential relay.

BE1-CDS Solution:
The percentage restrained differential characteristic, shown in Figure 1-1, is applied in this application.
The differential current required to cause a trip is a percentage of the restraint current. The restraint
current is a measure of the current flowing into or through the zone of protection. Thus for higher levels
of restraint current, where the CTs may be subject to saturation, higher levels of differential current must
be seen to cause a trip. The percentage restraint is often called the slope characteristic.
3

D2837-11.DWG
OPERATING CURRENT (IN MULTIPLES OF TAP)

01-05-99
2

)
60%
TO
MINIMUM PICKUP = (15
= 0.01 to 1.00
* 100
TIMES TAP IOP
R
= IREST
SL OPE
1

1 2 3 4 5
MAXIMUM RESTRAINT CURRENT (IN MULTIPLES OF TAP)

Figure 1-1. Restrained Differential Characteristic

The BE1-CDS relay has two settable restraint current calculation methods: average and maximum.
Average restraint emulates the operating characteristics of common electromechanical relays. Maximum
BE1-CDS General Information 1-7
restraint is recommended because it uses the current from the best performing CT to determine the
restraint to use during a fault condition. In addition, digital technology provides a transient monitor
function that enables the BE1-CDS relay to detect the onset of CT saturation to ride through the condition
to further enhance security from misoperation caused by poorly performing CTs.
Finally, Basler Electric addresses the source of false differential current at its roots. Active CT technology
used on the current inputs provides low burden to extend the linear range of power system CTs and wide
dynamic range to reduce measurement errors at high current levels. Sixteen bit ADC performance and
digital anti-aliasing filters also contribute to minimizing magnitude and angle measurement errors.

Problem 2: Measured Current Magnitude Mismatch

General
The currents measured by each set of
current inputs can be transformed from their 400A
primary values by different CT ratios. This
600:5
is illustrated in Figure 1-2. When the zone
of protection includes a transformer, there
is another source of magnitude mismatch 1200A 400A
that must be accounted for. The primary
currents that the differential relay must 600:5
monitor will be on different voltage bases in 1200:5
most cases. That is—due to the trans-
former action, the current on each side of 400A
the transformer is transformed by the
600:5
inverse of the voltage transformation ratio.
This is illustrated in Figure 1-3.
CDS

5.0 A 10.0 A
2400/240 Volts Secondary Secondary D2837-18.dwg
12-14-98
40A 400A
H1 X1
Input 1 Tap = 5 So 5A = 1 x Tap
Input 2 Tap = 10 10A = 1 x Tap

H0 X0 Current out balances current in


(in multiples of tap).
D2837-17.vsd
12-14-98
Figure 1-2. Tap Adjust For Mismatch
Figure 1-3. Currents On
Different Voltage Bases

BE1-CDS Solution:
The BE1-CDS relay applies a tap adjustment factor to the measured currents to cancel the effect of
dissimilar CT ratio and voltage bases by converting the currents to per unit quantities on a common base.
The tap adjusted currents are used by the percentage restrained differential protection functions to
determine the restraint and differential currents. Thus the mismatch in magnitudes under normal
balanced conditions is eliminated. The tap adjustment factor can be manually entered or automatically
calculated by the relay using parameters entered for each CT input circuit and for the differential tap
settings.
The setup parameters for each of the current input circuits are described in Section 3, I/O Functions,
Power System Measurement Functions. The CT ratio is included to allow the currents to be metered,
displayed, and reported in primary values. The CT ratio is also used as a parameter for the automatic tap
calculation feature.
The setup parameters for the tap adjustment factor are described in Section 4, Protection and Control
Functions, 87 Differential Protection. The user can enter the mega-volt-ampere (MVA) base for the
application and the kilovolt (kV) base for each current input, and the relay will automatically calculate the

1-8 General Information BE1-CDS


taps using these settings and the settings for each current input circuit. Or, the user can enter the taps
directly for each CT input.

Problem 3: Mismatch Caused by Load Tap Changers


The voltage transformation ratio (and thus the current transformation ratio) of a transformer within the
zone of the differential can be adjusted in service by typically ±10% with the use of load tap changers.
The tap adjustment factors can be used to eliminate the mismatch when the tap changer is at neutral;
but, when the tap changer is off of neutral, differential current will be measured.

BE1-CDS Solution:
The percentage restraint characteristic of the differential function mentioned previously allows the relay to
accommodate a prescribed amount of mismatch. The differential current must exceed a percentage of
the through current as described by the slope characteristic setting of the differential protection function.
Also, the relay has four setting groups to allow the tap settings and other parameters to be changed
dynamically based upon operating conditions.

Problem 4: Phase Angle Shift

General
When differential protection is used in a transformer application, the transformer often introduces a phase
shift between the various current inputs to the zone of protection. An example is a transformer with a
delta connected high side and a wye connected low side as shown in Figure 1-4a. The currents in the
phases connected to the delta side of the transformer are each made up of the combination of the current
flowing in two legs of the delta winding. On the other hand, the currents in the phases connected to the
wye side of the transformer are made up of the current in only one leg of the wye winding. It can be seen
that the primary currents flowing into the zone of protection, when tap is adjusted for magnitude
mismatch, still do not sum to zero as shown in Figures 1-4b and 1-4c.

BE1-CDS Solution:
The input currents must be combined to mimic the way they are combined in the protected power
transformer so that the currents presented to the differential protection are made up of the same
components. Traditionally, this has been done by special connection of the CTs. Figure 1-5 shows the
transformer from Figure 1-4 with the CTs connected. The wye side CTs can be connected in delta such
that the differential protection is summing IA with Ia-Ib. The resulting two currents being seen by the
differential relay are now made up of the same components but exactly 180° out of phase with each
other. They will always sum to zero (after tap adjust for magnitude mismatch) under all conditions of
balance or unbalance except when there is a fault inside the zone of protection.
There are several drawbacks to the traditional solution:
• The delta connection requires a dedicated set of CTs that generally cannot be used for other
purposes.
• The delta connection is more difficult to test.
• The delta connected CTs experience greater burden than wye connected CTs because the lead
burden must be multiplied by a factor of three in the CT performance calculation. See Appendix E for
more information on calculating CT performance.
The BE1-CDS relays support the traditional solution so that they may be used in retrofit/modernization
projects. However, in a numerical relay, it is possible to connect all of the CTs in wye as shown in Figure
1-6 so that the above mentioned drawbacks are not a consideration. The BE1-CDS relay can
numerically combine currents internally to accomplish a numerical delta if required for phase angle
compensation.

BE1-CDS General Information 1-9


The setup parameters for each of the current input circuits are described in Section 3, I/O Functions,
Power System Measurement Functions. The CT connection and the transformer connection is included
to allow the BE1-CDS relay to automatically determine the appropriate combination of currents to present
to the differential protection function.

B H2 X2

X1
X0
H1 H3
A C X3

IC=ICD-IAD ICD Icy Ic=-Icy


H3 X3

IB=IBD-ICD IBD Iby Ib=-Iby


H2 X2

IA=IAD-IBD IAD Iay Ia=-Iay


H1 X1

X0
Figure 1-4a

IA=High side, phase A line current Ia=Low side, phase A line current

IB=High side, phase B line current Ib=Low side, phase B line current
IC=High side, phase C line current Ic=Low side, phase C line current

IAD=Phase A, delta winding current IaY=Phase A, wye winding current


IBD=Phase B, delta winding current IbY=Phase B, wye winding current
ICD=Phase C, delta winding current IcY=Phase C, wye winding current

ICD -IBD
Ib
IA=IAD-IBD
IDifferential
I
Ia IAD Ia

IBD D2837-12.vsd
Ic 02-03-99

Ia lags IA by 180°+30°=210°

Figure 1-4b Figure 1-4c

Figure 1-4. Delta/Wye Transformer Currents

1-10 General Information BE1-CDS


H3 X3
C C

H2 X2
B B

H1 X1
A A

X0
BE1-CDS
*
B14
B13
B12
B11
B10
B9
B6
B5
B4
B3
B2
B1
*An alternative to grounding one corner of the delta connected CTs is D2837-19.vsd
to connect the ground to a lead connected to terminal B10, 12, or 14. 02-03-99

Figure 1-5. Three-Phase Connections, Delta-Wye Configuration, CT Compensation

H3 X3
C C

H2 X2
B B

H1 X1
A A

X0
BE1-CDS

B14
B13
B12
B11
B10
B9
B6
B5
B4
B3
B2
B1
D2837-20.vsd
02-03-99

Figure 1-6. Three-Phase Connections, Delta-Wye Configuration, Internal Phase Compensation

BE1-CDS General Information 1-11


Note
The BE1-CDS relay uses transformer internal connection information to determine the
correct phase compensation to use. It is not possible to reliably determine the phase
compensation settings based simply upon phase angle shift information because the
phase shift from high to low side is dependent upon the phase sequence of the power
system phasors. That is, a power system with ABC phase sequence will produce a
different phase shift from high to low than a power system with ACB phase sequence in
the same transformer connection. By specifying the transformer connections from the
three-line diagram, the correct phase compensation can be determined in all cases.

Problem 5: Zero Sequence Current Sources Within The Zone Of Protection

General
A ground source (grounded transformer winding or zig-zag grounding bank) within the zone of protection
can result in differential current being measured during ground imbalances. The most common example
of this is when the zone of protection is around a delta/grounded, wye transformer. If a ground fault or
neutral imbalance occurs on the power system external to the wye side zone of protection, the zero
sequence components of the current flow through the grounded neutral and are a component of the
current flowing out of the zone of protection. On the delta side, there is no path for the zero sequence
components to flow and they circulate inside the delta winding. The result is that this component of the
current is not seen entering the zone of protection on the delta side resulting in a differential current that
can cause the relay to operate.

BE1-CDS Solution:
There are two traditional solutions to this problem. The first is using delta phase-shift compensation on
the grounded side of the zone of protection to block the zero sequence components from getting to the
differential protection. The second is removing the zero sequence components from the currents using a
zero sequence trap to prevent them from getting to the differential protection. The BE1-CDS provides
both solutions.
In the previous discussion on compensating for the phase shift on the primary system, the solution is to
combine the currents such that the currents seen by the differential are made up of the same components
at all terminals of the zone of protection. This solution has the added benefit of causing the currents to
match (after magnitude mismatch is eliminated by tap adjustment) under all situations of imbalance,
including ground faults. That is, by using delta compensation on the wye side of the power transformer to
mimic the power transformer’s delta connection, the zero sequence currents are blocked from flowing to
the differential protection and circulate in the CT delta just as they circulate in the delta of the power
transformer on the delta side.
The BE1-CDS selects the proper phase shift compensation settings to not only provide the correct phase
shift, but to also block zero sequence currents as appropriate.
The second solution of inserting a zero sequence trap is used in applications where there is a grounding
bank within the zone of protection that is not predicted by the transformer connection information
contained in the CT circuit setup parameters. In the example shown in Figure 1-7, the compensation
logic would require that the delta compensation be applied to the grounded wye winding. The grounding
bank on the delta side will cause the differential protection to operate for external ground faults.
Figure 1-7 shows how this would be done with traditional differential relays.
This application is greatly simplified with the BE1-CDS. The user can connect all CTs in wye and specify
that the delta transformer winding has a ground source. The BE1-CDS will apply delta compensation to
the wye winding to obtain phase shift and zero sequence compensation for that current input. For the
delta winding with ground source, it will numerically remove the zero sequence components from that
current input just as would traditionally be done with a zero sequence trap.

1-12 General Information BE1-CDS


Wye/Delta (DAB)
Transformer with Ground
IC Delta CT Connection Bank on Delta Side Ic Wye CT Connection
IO
C c

IB Ib IO
B b

IC Ia IO
A a

IO IO IO
GROUNDING
3IO
BANK

3IO
87T
IA-IB 1 2
Ia-Io
C
87T
IB-IC 1 2
Ib-Io
C
87T
IC-IA 1 2
Ic-Io
C
IO IO IO

IO IO IO
D2837-16
12-14-98

Figure 1-7. Traditional Zero-Sequence Trap for Application With Ground Banks
The setup parameters for each of the current input circuits are described in Section 3, Input and Output
Functions, Power System Measurement Functions. The parameters specifying CT connection,
transformer connection, and ground source for each current circuit determines the angle and zero
sequence compensation used on each current input.

Note
The BE1-CDS relay does not automatically remove the zero sequence components from
all currents presented to the differential protection functions as that can unnecessarily
reduce the relay’s sensitivity to internal ground faults by 33%. Also, since the zero
sequence components are removed from all phases, it can result in confusion during
single-phase testing by introducing differential current in phases not under test.

Problem 6: Transformer Energization Inrush And Overexcitation

General
When the zone of protection includes a transformer, excitation and energization inrush currents appear
as differential current because they flow into the zone of protection and not back out again. Normally,
transformer excitation losses are small. However, when the transformer is overexcited, or upon initial
energization or sympathetic inrush conditions, they can cause sensitive differential protection to operate.

BE1-CDS Solution:
Overexcitation and inrush are non-linear and the currents have high harmonic content. Inrush is
characterized by high, even harmonics such as the second harmonic. Overexcitation is characterized by
high, fifth harmonics. The BE1-CDS calculates the magnitude of the second and fifth harmonic
components of the differential current. If the differential current is made up of a significant proportion of

BE1-CDS General Information 1-13


either of these two components, the user can select to inhibit the sensitive percentage restrained
protection from operating.
Since CT saturation can also cause the currents seen by the relay to be rich in harmonics, an
unrestrained instantaneous differential element is included to provide dependability for an internal fault
with CT saturation.
During inrush, the second harmonic component may not be equally shared on all three phases. Because
of this, misoperation can occur on a phase with low second harmonic content. Our unique method of
second harmonic sharing improves security by allowing the harmonic restraint elements to respond to the
ratio of operate current to the sum of harmonic current measured on all three phases. This is superior to
other methods of cross blocking since each phase element operates independently in its comparison of
operating current to harmonic current. Thus, security is enhanced without sacrificing dependability
because a faulted phase will not be restrained by inrush on unfaulted phases.
To further enhance security from false tripping on inrush, the operating characteristic responds only to the
fundamental component of this highly distorted current, reducing sensitivity to inrush current yet allowing
improved sensitivity to power system faults.

Problem 7: Digital Measurement Errors

General
Numerical relays sample the current and use digital signal processing algorithms to extract magnitude
and angle information to develop their operating quantities. Most methods used are accurate only when
the sampled power system quantity is operating at nominal frequency. Unless steps are taken to
compensate, accuracy falls off very quickly with deviations in the power system frequency.
Another problem that must be overcome with digital technology is the need to use anti-aliasing filters prior
to the sampling process to prevent harmonic components from affecting the measurement. Analog filters
introduce phase shift errors and are subject to attenuation drift which can introduce magnitude and angle
errors to the measurement.
These problems are more acute for differential protection since the operating quantity (differential current)
is derived from the difference between the measured quantities. Any error in magnitude or angle
measurement can result in large inaccuracies in the differential current measurement.

BE1-CDS Solution:
Digital relay designers must decide on which of three solutions to use for this problem. They can allow
their relays to misoperate at off-nominal frequency operation. Or, disable the protection at off-nominal
frequency. Or, compensate to maintain accuracy at off-nominal frequency. The BE1-CDS uses
frequency tracking to adjust the sampling interval to maintain full accuracy across a wide frequency range
so that it is both secure and dependable in all applications. For example, tripping of important
transformers during a disturbance that causes the system to go unstable can have a catastrophic affect
on an already over-stressed power system. Generator and motor differential protection applications are
another situation where accuracy across a wide frequency range is important.
To eliminate the errors introduced by analog low pass filters, the BE1-CDS uses digital signal processing
technology and 144 sample per cycle over-sampling to provide digital low-pass filtering.

MODEL AND STYLE NUMBER DESCRIPTION

General
The BE1-CDS Relay electrical characteristics and operational features are defined by a combination of
letters and numbers that make up the style number. The model number, together with the style number,
describe the options included in a specific device, and appear in the clear window on the front panel and
on a sticker located inside the case. Upon receipt of a relay, be sure to check the style number against
the requisition and the packing list to ensure that they agree.

1-14 General Information BE1-CDS


Sample Style Number
The style number identification chart (Figure 1-8) defines the electrical characteristics and operational
features included in BE1-CDS Relays. For example, if the style number were BE1-CDS220-
E0EN0YYONOR, the device would have the following:
BE1-CDS220 Three-phase two input
(E) - 5 Amp Nominal System with 5 Amp Independent Ground Input
(0) - No Option
(E) - With 8 inputs, 6 programmable outputs and 1 alarm output
(N) - No Option
(0) - No Option
(Y) - 48/125 Vac/dc Power Supply
(Y) - With six button HMI with graphic LCD
(0) - ASCII Communications
(N) - No load profile recording
(0) - No cover
(R) - Horizontal with 19” Rack Mount Brackets


$ 
02'(/ 12

)URQW /RDG
0RGHO1R 1R2SWLRQ 1R2SWLRQ 0RXQWLQJ
3DQHO 3URILOH

 1 :LWK7DUJHWDQG 1 1RQH + +RUL]RQWDO3DQHO


$ODUP/('V < 3RLQW 0RXQW
< :LWKEXWWRQ 'DWD$UUD\ 5 +RUL]RQWDO 
+0,ZLWK/&' 9 9HUWLFDO3DQHO
'LVSOD\  0RXQW

6HQVLQJ ,QSXW2XWSXW
,QSXW7\SH 563RUW
3RZHU6XSSO\
&RPPXQLFDWLRQ
$PS1RPLQDO6\VWHPV ( ,QSXWV2XWSXWVDQG 6HDODEOH
&RYHU
$ODUP2XWSXW / 9GF  $6&,,
$ :2,QGHSHQGHQW*QG,QSXW < 9DFGF  0RGEXV  1RFRYHU
% $PS,QGHSHQGHQW*QG,QSXW = 9DFGF  713   6HDODEOHFRYHU
 '13
$PS1RPLQDO6\VWHPV
127(6
' :2,QGHSHQGHQW*QG,QSXW
( $PS,QGHSHQGHQW*QG,QSXW  &RQVXOW\RXU%DVOHU5HSUHVHQWDWLYHIRUDYDLODELOLW\
) $PS,QGHSHQGHQW*QG,QSXW 'YVG

 'RXEOH6(5DQGRVFLOORJUDSK\PHPRU\ 

Figure 1-8. Style Number Identification Chart

OPERATIONAL SPECIFICATIONS
BE1-CDS relays have the following features and capabilities.

Metered Current Values And Accuracy


Current range: 0.1 to 1.5 nominal
Accuracy (Phase and Neutral): ±1% of reading ±1 least significant digit at 25°C
Accuracy (Negative Sequence): ±1.5% of reading ±1 least significant digit at
25°C
Temperature dependence: ≤ ±0.02% per °C

BE1-CDS General Information 1-15


Calculated Values And Accuracy
Demand range: 0.1 to 1.5 nominal
Demand type: Thermal, Block, and Sliding Block
Accuracy: ±1% of reading ± 1 digit at 25°C
Temperature dependence: ≤ ±0.02% per °C
Demand interval: 1 to 60 minutes

Real Time Clock


Accuracy: 1 second per day at 25°C(free running) or ±2
milliseconds (with IRIG synchronization)
Resolution: One millisecond
Date and time setting provisions: Front panel, communications port and IRIG.
Leap year correction provided. Daylight savings
time correction available.
Power Supply Holdup: 8 to 24 hours, depending on conditions

IRIG
Standard: 200-98, Format B002
Input Signal: Demodulated (dc level-shifted digital signal)
Logic-High Voltage: 3.5 Vdc, minimum
Logic Low Voltage: 0.5 Vdc, maximum
Input Voltage Range: 20 Vdc, maximum
Burden: Non-linear, approximately 4 k$ at 3.5 Vdc,
approximately 3 k$ at 20 Vdc

Recognition Time On Contact Inputs

Programmable 4 to 255 milliseconds

NOTE
All timing specifications are for the worst case response. This includes output contact
operate times and standard BESTlogic operation timing, but excludes input debounce
timing and non-standard logic configurations. If a non-standard logic scheme involves
feedback, then one or more BESTlogic update rate delays must be included to calculate
the worst case delay. An example of feedback is Virtual Outputs driving Function Block
Inputs or other higher numbered Virtual Outputs or Function Block Outputs driving
Function Block Inputs. For more information, See Section 7, BESTlogic Programmable
Logic.

87 Differential Functions
Restrained Differential, (87RPU,87RT)
Pickup Accuracy:
5 Ampere CT ±4% or ±75 mA whichever is greater
1 Ampere CT ±4% or ±25 mA whichever is greater
Response Time (See Figure 1-9) <2 cycles @ 5 times pickup
<3 cycles @ 1.5 times pickup
Unrestrained Differential, (87UT)
Pickup Accuracy:
5 Ampere CT ±3% or ±75 mA whichever is greater
1 Ampere CT ±3% or ±25 mA whichever is greater
Response Time (See Figure 1-9) <1 cycle @ 5 times pickup
<2 cycles @ 1.5 times pickup

1-16 General Information BE1-CDS


3.50

3.00

Response Time (cycles)


2.50

2.00
Unrestrained

1.50 Restrained

1.00

0.50

0.00
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0 11.0
Multiple of Pickup

Figure 1-9. Typical 87 Response Characteristic Curves

Harmonic Inhibit
Pickup Accuracy:
5 Ampere CT ±2% of setting or 50 mA whichever is greater
1 Ampere CT ±2% of setting or 50 mA whichever is greater
TAP
5 Ampere CT:
Range 2.00 to 20.0 A
Increments 0.01 from 2.00 to 9.99, 0.1 from 10.0 to 20.0
1 Ampere CT:
Range 0.40 to 4.00A
Increments 0.01 A
Minimum Pickup
1 or 5 Ampere CT:
Range 0.10 to 1.00 per unit
Increment 0.01
Restraint Slope
1 or 5 Ampere CT:
Range 15 - 60 %
Increment 1%
2nd and 5th harmonic
1 or 5 Ampere CT:
Range 5.0 - 75.0 %
Increment 0.5%
Unrestrained Pickup
1 or 5 Ampere CT:
Range 1 - 21 times TAP up to 30 times I nominal
symmetrical
Increment 1

87ND Neutral Differential Function


Restrained Differential, (87NDPU,87NDT)
Pickup Accuracy:
5 Ampere CT ±4% or ±75 mA
1 Ampere CT ±4% or ±25 mA

BE1-CDS General Information 1-17


TAP
5 Ampere CT:
Range 2.00 to 20.0 A
Increments 0.01 from 2.00 to 9.99, 0.1 from 10.0 to 20.0
1 Ampere CT:
Range 0.40 to 4.00A
Increments 0.01 A
Minimum Pickup
1 or 5 Ampere CT:
Range 0.10 to 1.00 per unit
Increment 0.01
Restraint Slope
1 or 5 Ampere CT:
Range 15 - 60 %
Increment 1%

Time Overcurrent Functions


Current Pickup, Phase and Neutral (#51P, #51N) Dropout/pickup ratio: 95% ±2%
Pickup Accuracy:
5 Ampere CT ±2% or ±50 mA
1 Ampere CT ±2% or ±10 mA
Current Pickup, Negative Sequence (#51Q) Dropout/pickup ratio: 95% ±2%
Pickup Accuracy:
5 Ampere CT ±3% or ±75 mA
1 Ampere CT ±3% or ±15 mA
Current Input All 51 Functions
5 Ampere CT:
Range 0.50 to 16.0 A
Increments 0.01 from 0.50 to 9.99, 0.1 from 10.0 to 16.0
1 Ampere CT:
Range 0.10 to 3.20A
Increments 0.01 A

Time-Current Characteristic Curves


Timing Accuracy (All 51 Functions) Within ±5% or ±1ó cycles, whichever is greater
for time dial settings greater than 0.1 and
multiples of 2 to 40 times the pickup setting but
not over 150 A for 5 A CT units or 30 A for 1 A CT
units.
See Appendix A for information on available timing curves.

Instantaneous Overcurrent Functions


Current Pickup Accuracy, Phase and Neutral
(#50TP, #50TN): Dropout/pickup ratio: 95% ±2%
5 Ampere CT ±2% or ±50 mA
1 Ampere CT ±2% or ±10 mA
Current Pickup Accuracy, Negative Sequence
(#50TQ): Dropout/pickup ratio: 95% ±2%
5 Ampere CT ±3% or ±75 mA
1 Ampere CT ±3% or ±15 mA
Current Pickup Ranges (#50T):
5 Ampere CT
Range 0.5 to 150.0A
Increments 0.01 from 0.50 to 9.99A, 0.1 from 10.0 to 99.9A,
and 1.0 from 100A to 150A
1 Ampere CT
Range 0.1 to 30.0 A
1-18 General Information BE1-CDS
Increments 0.01 from 0.01 to 9.9A, 0.1 from 10.0 to 30.0A
Settable Time Delay Characteristics
(#50T): Definite time for any current exceeding pickup
Time Range 0.00 to 60.0 seconds
Time Increments One millisecond from 0 to 999 milliseconds, 0.1
second from 1.0 to 9.9 seconds, 1 second from
10 to 60 seconds
Timing accuracy(#50TP, #50TN) ±0.5% or ±¼ cycle whichever is greater plus trip
time for instantaneous response (0.0 setting)
Timing accuracy(#50TQ) ±0.5% or ±1 cycle whichever is greater plus trip
time for instantaneous response (0.0 setting)
Trip Time : For 0.0 delay setting:
(#50TP, #50TN): 1¼cycles maximum for currents ≥ 5 times the
pickup setting. Two cycles maximum for a
current of 1.5 times pickup. Four cycles
maximum for a current of 1.05 times the pickup
setting
Trip Time : For 0.0 delay setting:
(#50TQ): 2¼ cycles maximum for currents ≥ 5 times the
pickup setting. 3 cycles maximum for a current
of 1.5 times pickup. Five cycles maximum for a
current of 1.05 times the pickup setting
Breaker Fail Timer (BF)
Current Detector Pickup: Fixed at 0.5 A for 5 A unit, 0.1 A for 1 A unit
Current Detector Pickup Accuracy: ±10%
Delay Range: 50 to 999 milliseconds
Increments: 1 millisecond
Reset: Less than 1 cycle of the current being removed
Timer Accuracy: ±0.5% or (+1ô,, -ô cycles) whichever is greater

General Purpose Timers (62, 162)


Modes: PU/DO, 1 Shot Non-Retrig., 1 Shot Retrig.,
Oscillator, Integrating, and Latch.
Range: 0 to 9999 seconds.
Increments: 1 millisecond from 0 to 999 milliseconds; 0.1
second from 1.0 to 9.9 seconds; 1 second from
10 to 9999 seconds
Accuracy: ±0.5% or ±¾ cycles whichever is greater

Automatic Setting Group Characteristics


Number Of Setting Groups: Four
Switch Level Range: 0-150% of the setting group 0, #51 phase,
neutral, or negative sequence pickup setting

Switch Level Accuracy: ±2% or ±50 mA (5 A),±2% or ±10 mA (1 A)


Switch Timer range: 0 to 60 minutes with 1 minute increments. (0 =
disabled)
Switch Timer accuracy: ±0.5% or ±2 sec whichever is greater

BESTlogic Update Rate


One-Fourth cycle

BE1-CDS General Information 1-19


GENERAL SPECIFICATIONS

AC Current Inputs With 5 A CT


Continuous: 20 A
One second rating: 400 A
For other current levels, use the following formula
I = (K/t)1/2
where t = time in seconds
K=160,000
Saturation limit: 150 A
Burden: Less than 10 milliohms at 5 A

AC Current Inputs with 1 A CT


Continuous: 4A
One second rating: 80 A
For other current levels, use the following formula
I = (K/t)1/2
where t = time in seconds
K=6,400(S1/H1/F1 case)
Saturation limit: 30 A
Burden: Less than 22 milliohms at 1 A

Analog To Digital Converter


Type: 16 bit
Sampling Rate: 144 samples per cycle into digital filter
Digital Filter Output: 24 samples per cycle
Frequency Tracking: 40 to 63 hertz

Power Supply
Option L:
24 Vdc: Range 17-32 Vdc
Option Y:
48, 110, and 125 Vdc: Range 35-150 Vdc
67, 110, and 120 Vac: Range 55-135 Vac
Option Z:
110, 125, and 250 Vdc: Range 90-300 Vdc
110, 120, and 240 Vac: Range 90-270 Vac
Burden:
Options L: 12 watts continuous, 17 watts maximum with all
outputs energized
Option Y: 11 watts continuous, 15 watts maximum with all
outputs energized
Option Z: 10 watts continuous, 13 watts maximum with all
outputs energized

Output Contacts
Make and carry for tripping duty: 30 A for 0.2 seconds per ANSI C37.90;
Continuous 7 A
Break Resistive Or Inductive: 0.3 A at 125 or 250 Vdc (L/R = 0.04 maximum)

Control Inputs
Voltage Range: Same as control power

1-20 General Information BE1-CDS


Turn-On Voltage:
24 Vdc Power Supply: 13 19 Vdc
48/125 Vac/Vdc Power Supply: 26 to 38 V
125/250 Vac/Vdc Power Supply: 69 to 100 V
Input Burden: Burden per contact for sensing depends on the
power supply model and the input voltage. Table
1-1 provides appropriate burden specifications.
Table 1-1. Burden
Jumper Installed Jumper Not Installed
Power Supply Burden Burden
1 (48/125V) 35 kilo-ohm 90 kilo-ohm
2 (125/250V) 90 kilo-ohm 185 kilo-ohm
3 (24 V) 15 kilo-ohm N/A

Communication Ports
Interface:
Front RS-232: 300 to 19200 baud, 8N1 full duplex
Rear RS-232: 300 to 19200 baud, 8N1 full duplex
Rear RS-485: 300 to 19200 baud, 8N1 half duplex

Display
Type: Graphic LCD (liquid crystal display) with LED
(light emitting diode) back-light
Operating Temperature: -40°C to 70°C (-40°F to 158°F)
Display contrast may be impaired at temperatures
below -20°C (-4°F)

Isolation
2000 Vac at 50/60 Hz in accordance with IEEE
C37.90 and IEC 255-5. (This includes commun-
ication ports.)

Surge Withstand Capability


Oscillatory: Qualified to IEEE C37.90.1-1989 Standard Surge
Withstand Capability (SWC) Tests for Protective
Relays and Relay Systems.
Fast Transient: Qualified to IEEE C37.90.1-1989 Standard Surge
Withstand Capability (SWC) Tests for Protective
Relays and Relay Systems.

Radio Frequency Interference (RFI)


Qualified to IEEE C37.90.2-1995 Standard For
Withstand Capability Of Relay Systems To
Radiated Electromagnetic Interference From
Transceivers.

Electrostatic Discharge (ESD)


Eight kilovolts contact discharges and 15
kilovolts air discharges applied in accordance
with IEC 60255-22

UL Recognized
U.L. recognized per Standard 508, U.L. File
Number E97033. Note: Output contacts are not
U.L. recognized for voltages greater than 250 V.

BE1-CDS General Information 1-21


C.S.A. Certified
C.S.A. certified per Standard CAN/CSA-C22.2
Number 14-M91, C.S.A. File Number LR23131.
Note: Output contacts are not C.S.A. certified for
voltages greater than 250 V.

CE Qualified
This product meets or exceeds the standards
required for distribution in the European
Community.

DNP Certified
DNP 3.0 IED certified, Subset Level 2, 06/20/00,
by SUBNET Solutions, Inc.
Environment
Operating Temperature Range: -40°C to 70°C (-40°F to 158°F)
Storage Temperature Range: -40°C to 70°C (-40°F to 158°F)
Humidity: Qualified to IEC 68-2-38, 1st Edition 1974, Basic
Environmental Test Procedures, Part 2: Test
Z/AD: Composite Temperature Humidity Cyclic
Test.
Shock
Qualified to IEC 255-21-2, Class 1

Vibration
Qualified to IEC 255-21-1, Class 1

Weight
Maximum weight 12 pounds (5.4 kilograms).
Shipping weight approximately 16.5 pounds (7.5
kilograms).

Case Size
19 inch rack mount, 3 rack units high, or MX
case: M1, M2/FT31, and FT32 size. See Section
12, Installation for more information

1-22 General Information BE1-CDS


SECTION 2 • QUICK START
TABLE OF CONTENTS
List Of Figures......................................................................................................................................... i
List Of Tables.......................................................................................................................................... i
SECTION 2 • QUICK START..................................................................................................................... 2-1
GENERAL .............................................................................................................................................. 2-1
BESTlogic ............................................................................................................................................... 2-1
Characteristics of Protection and Control Elements ........................................................................... 2-2
Element Logic Settings ....................................................................................................................... 2-2
Output Logic Settings.......................................................................................................................... 2-3
USER INTERFACES.............................................................................................................................. 2-3
Front Panel HMI.................................................................................................................................. 2-3
ASCII Command Communications ..................................................................................................... 2-4
BESTCOMS For BE1-CDS 220, Graphical User Interface................................................................. 2-6
GETTING STARTED.............................................................................................................................. 2-6
Connections ........................................................................................................................................ 2-6
Entering Test Settings......................................................................................................................... 2-6
Checking The State Of Inputs............................................................................................................. 2-7
Testing ................................................................................................................................................ 2-7
FAQ/TROUBLE SHOOTING .................................................................................................................. 2-7
Frequently Asked Questions............................................................................................................... 2-7

List Of Figures
Figure 2-1. 87 Phase Differential Element ................................................................................................ 2-2

List Of Tables
Table 2-1. Sections For Functional Categories......................................................................................... 2-1
Table 2-2. Trip LED Truth Table ............................................................................................................... 2-9

BE1-CDS Quick Start i


SECTION 2 • QUICK START

GENERAL
This section provides an overview of the BE1-CDS Current Differential System. You should be familiar
with the concepts behind the user interfaces and BESTlogic before you begin reading about the detailed
BE1-CDS functions. Sections 3 through 6 in this manual describe in detail each function of the BE1-CDS.
The following information is intended to provide the reader with a basic understanding of the three user
interfaces (front panel HMI, ASCII serial communications link, and the BESTCOMS for BE1-CDS220
software) and the security features provided in the BE1-CDS relay. Detailed information on the operation
of the HMI (Human-Machine Interface) is in Section 10, and the information on ASCII command
communications is in Section 11. BESTCOMS is a transparent, Windows based software application
that enhances communication between the PC user and the BE1-CDS220 relay. BESTCOMS for the
BE1-CDS is provided free of charge with the BE1-CDS.
Also covered in this section is an overview of BESTlogic. BESTlogic is a highly flexible programmable
logic system that allows the user to apply the available functions with complete flexibility and customize
the system to meet the requirements of the protected power system. Detailed information on using
BESTlogic to design complete protection and control schemes for the protected circuit can be found in
Section 7, BESTlogic Programmable Logic and Section 8, Application.
Sections 3 through 6 describe each function provided in the BE1-CDS relay and include references to the
following items. Note that NOT all items are appropriate for each function.
• HMI screens for setting the operational parameters
• ASCII commands for setting the operational parameters
• ASCII commands for setting up the BESTlogic required to use the function in your protection and
control scheme.
• Outputs from the function such as Alarms, BESTlogic variables, and data reports.
• HMI screens for operation or interrogation of the outputs and/or reports provided by each function.
• ASCII commands for operation or interrogation of the outputs and/or reports provided by each
function.
About This Manual
The various application functions provided by this multifunction relay are divided into four functional
categories: input/output functions, protection and control functions, metering functions, and reporting and
alarm functions. Detailed descriptions of each individual function, setup, and use is covered in the
Sections as shown in Table 2-1. Detailed information on using programmable logic to create your
protection and control scheme is described in Section 7, BESTlogic Programmable Logic.
Table 2-1. Sections For Functional Categories
Functional Category Volume 1, Application
Input/Output Functions Section 3
Protection and Control Section 4
Metering Functions Section 5
Reporting and Alarm Functions Section 6
BESTlogic Programmable Logic Section 7
Application Section 8

BESTlogic
Each of the protection and control elements in the BE1-CDS is implemented as an independent function
that is equivalent to a single function, discrete device counterpart. Each independent element has all of
BE1-CDS Quick Start 2-1
the inputs and outputs that the discrete component counterpart might have. Programming BESTlogic is
equivalent to choosing the devices required by your protection and control scheme and drawing schematic
diagrams to connect the inputs and outputs to obtain the desired operational logic. The concept is the
same but the method is different in that you choose each element by enabling it and use Boolean logic
expressions to connect the inputs and outputs. The result is that you have even greater flexibility in
designing your system than you had using discrete devices. An added benefit is that you are not
constrained by the limitations in flexibility inherent in many multifunction relays.
One user programmable, custom logic scheme created by the user may be programmed and saved in
memory. To save you time, several preprogrammed logic schemes have also been provided. Any of the
preprogrammed schemes can be copied into the programmable logic settings without the user having to
make any BESTlogic programming.
Preprogrammed logic settings can also be modified after being copied. This provides a good starting point
for a custom logic scheme. After copying the preprogrammed scheme, it is necessary to enter a unique
name for the new logic before modifying the settings. Naming the new logic distinguishes the new logic
from the preprogrammed logic scheme.
There are two types of BESTlogic settings: element (function block) logic settings and output logic
settings. These will be described briefly in the following paragraphs. Detailed information on using
BESTlogic to design complete protection and control schemes for the protected circuit can be found in
Section 7, BESTlogic Programmable Logic and Section 8, Application.

Characteristics of Protection and Control Elements


As stated before, each element (function block) is equivalent to a
discrete device counterpart. For example, the transformer 87RPU
differential element in the BE1-CDS relay has all of the 87RT
Mode = PERCENT
characteristics of a version of the BE1-87T transformer
0-disable DIFF
differential relay with similar functionality. Figure 2-1 shows the 1-enabled with 87UT
87 phase differential element inputs and outputs. Harmonic
Restraint
Two inputs: (87)
2NDHAR
• Mode (enable/disable 87 operation) BLK
• BLK (block 87 operation)
5THHAR
Five outputs: D2840-23.vsd


01-28-99
87RPU (87 Restrained Pickup)
• 87RT (87 Restrained Trip)
• 87UT (87 Unrestrained Trip)
Figure 2-1. 87 Phase Differential
• 2NDHAR (2nd Harmonic Inhibit Status)
Element
• 5THHAR (5th Harmonic Inhibit Status)
Five operational settings:
• Minimum pickup
• Slope
• 2nd Harmonic Inhibit
• 5th Harmonic Inhibit
• Unrestrained Pickup
Of the above characteristics, the five operational settings are not included in the logic settings. They are
included in the protection settings. This is an important distinction. Since changing logic settings is similar
to rewiring a panel, the logic settings are separate and distinct from the operational settings such as
pickups and time delays.

Element Logic Settings


To use a protection or control element, there are two items that need to be set: the mode and the input
logic. The mode is equivalent to deciding which devices you want to install in your protection and control
scheme. You then must set the logic variables that will be connected to the inputs.

2-2 Quick Start BE1-CDS


For example, the 51N element has two modes (disabled and enabled), and one input, block (torque
control). To use this element, the logic setting command might be SL-51N=1,/IN2 for Set Logic-51N to be
mode 1 (enabled) with the element blocked when contact sensing INput 2 is not (/) energized. Contact
sensing input 2 would be wired to a ground relay enable switch.
As noted before, the protection settings for this element, pickup, time dial, and curve, must be set
separately in the setting group settings. The setting might be S0-51N=6.5,2.1,S1R for Set in group 0 - the
51N function = to pickup at 6.5 amps with a time dial of 2.1 using curve S1 with an integrating Reset
characteristic.
The 51N element has two logic output variables, 51NT (Trip) and 51NPU (Picked Up). The combination of
the logic settings and the operational settings for the element govern how these variables respond to logic
and current inputs.

Output Logic Settings


BESTlogic, as implemented in the BE1-CDS, supports up to 16 output expressions. The output
expressions are called virtual outputs to distinguish them from the physical output relays. VOA and VO1
through VO6 drive physical outputs Out A (fail safe alarm output), and Out 1 through Out 6 respectively.
The rest of the virtual outputs can be used for intermediate logic expressions.
For example, OUT 1 is wired to the trip bus of the circuit breaker. To set up the logic to trip the breaker,
the BESTlogic setting command might be SL-VO1=VO11+101T+BFPU for Set Logic - Virtual Output 1 =
to Virtual Output 11 (which is the intermediate logic expression for all of the element tripping outputs) or
(+) 101T (the trip output of the virtual breaker control switch) or (+) BFPU (the pickup output of the breaker
failure element that indicates that breaker failure has been initiated).

USER INTERFACES
Three user interfaces are provided for interacting with the BE1-CDS relay: the front panel HMI, ASCII
communications, and the BESTCOMS for BE1-CDS software. The front panel HMI provides access to a
subset of the total functionality of the device. ASCII communications provides access to all settings,
controls, reports, and metering functionality of the system. The BESTCOMS for BE1-CDS software
provides a Windows® based, user friendly environment for editing settings files and uploading and
downloading them from the relay.

Front Panel HMI

The front panel HMI consists of five LEDs for indicating power, relay trouble alarm status, programmable
major and minor alarm status, and a multipurpose trip LED that flashes to indicate that a protective
element is picked up. The trip LED lights solidly when the trip output is energized, and seals-in when a
protective trip has occurred. An optional front panel also has a 64-by-128 pixel graphic liquid crystal
display (LCD) with four scrolling pushbuttons, an edit pushbutton, and a reset pushbutton. The edit
pushbutton includes an LED to indicate when edit mode is active. When the Trip LED lights solidly, it
indicates that target information is being displayed on the LCD. A complete description of the HMI is
included in Section 10, HMI (Controls And Indicators).
The BE1-CDS HMI is organized into a menu tree structure with six branches. The complete menu tree
description with displays is also provided in Section 10. A list of the menu branches and a brief
description for scrolling through the menu is in the following paragraphs.
1. REPORT STATUS. Display and resetting of general status information such as targets, alarms,
recloser status, etc.
2. CONTROL. Operation of manual controls such as virtual switches, selection of active setting group,
etc.
3. METERING. Display of real time metering values.
4. REPORTS. Display and resetting of report information such as time and date, demand registers,
breaker duty statistics, etc.

BE1-CDS Quick Start 2-3


5. PROTECTION. Display and setting of protective function setting parameters such as logic scheme,
pickups, time delays, etc.
6. GENERAL SETTINGS. Display and setting of non protective function setting parameters such as
communications, LCD contrast, and CT ratio.
Each screen in the menu tree displays the path in the upper left hand corner of the screen. Additionally,
each screen is assigned a number in the HMI section. The path indicates the branch and level in the
menu tree structure. This path should help you to keep track of where you are when you leave the menu
tree top level. You scroll through each level of the menu tree by using the right and left scrolling
pushbuttons. To go to a level of greater detail, you use the down scrolling pushbutton. Each time you go
to a lower level in the menu tree, another string is added to the path and separated by a backslash.
For example, to check or change the 51N pickup setting in setting
group 3, you would press the right or left scrolling pushbuttons to get \PROT\SG3\51\51
to Screen \PROT PROTECTION. You would then press the down MODE PU TD CRV
scrolling pushbutton to get to the next level of detail and the right or 51P 1 10.3 9.99 B1R
left scrolling pushbutton to get to Screen \PROT\SG3 -SETTING 51N G 1.0 0.20 B5
GROUP 3. To continue, you would press the down and then the 51Q 0 xx.x x.xx C4R
right or left scrolling pushbuttons to get to Screen \PROT\SG3\51
INVERSE TIME OVERCURRENT and then Screen
<251 >151
\PROT\SG3\51\51 51 Settings. On this screen shown in Figure 2-2,
the pickup, time dial and curve settings for the 51P/N/Q functions Figure 2-2. 51 Screen
can be read and/or edited. To return to the top level from this
location, you would press the up scrolling pushbutton three times.

ASCII Command Communications

The BE1-CDS relay has three independent communications ports for serial communications. A computer
terminal or PC running a terminal emulation program such as Windows Terminal can be connected to
any of the three ports so that the user may send commands to the relay. Communication with the relay
uses a simple ASCII command language. When a command is entered via a serial port, the relay
responds with the appropriate action. The ASCII command communications is designed to be used in
both human-to-machine interactions and in batch download type operations. The following paragraphs
briefly describe the command structure and then discuss human-to-machine interactions and batch
command text file operations for interacting with the relay. The operation of the ASCII commands is
described in detail in Section 11, ASCII Command Interface.

Command Structure
An ASCII command consists of a command string made up of one or two letters followed by a hyphen and
an object name. The first letter specifies the general command function and the second a sub-grouping.
The object name is the specific function for which the command is intended. If the command string is
entered by itself, it is a read command. If the command string is entered followed by an equal sign and
one or more parameters, it is a write command. The general command groupings are organized into six
major groups plus several miscellaneous commands. These commands are as follows:
C CONTROL. Commands to perform select before operate control actions such as tripping and
closing the circuit breaker, changing the active setting group, etc.. Sub-groupings include S for
Select and O for Operate.
G GLOBAL. Perform global operations that do not fall into the other general groupings such as
password security. Sub-groupings include: S for security settings.
M METERING. Read all real time metering values. This general command grouping has no sub-
groupings.
P PROGRAM. Subgroup command to read or program a setting.

2-4 Quick Start BE1-CDS


R REPORTS. Read and reset reporting functions such as time and date, demand registers, breaker
duty statistics, etc. Sub-groupings include: A for Alarm functions, B for Breaker monitoring
functions, D for Demand recording functions, F for Fault summary reporting functions, G for
General information, and S for Sequence of Events recorder functions.
S SETTINGS. Set all setting parameters that govern the functioning of the relay. Sub-groupings
include: 0,1,2,3 for settings in setting groups, A for alarm settings, B for breaker monitoring
settings, G for general settings, L for logic settings.
MISCELLANEOUS. These include Access, Exit, and Help.
Examples of object names would be 51N for the neutral inverse time overcurrent element or PIA for the A
phase, peak current demand register.
For example, to check the 51N pickup setting in setting group 3, you would enter S3-51N for Settings,
Group 3-51N. The relay would respond with the current pickup, time dial, and curve settings for the 51N
element. To edit these settings, the same command would be used with an = followed by the new settings
and the enter pushbutton. The user should note that it is necessary to use the Access and Exit
commands when using the write version of these commands.

Human-To-Machine ASCII Command Operations


The ASCII command scheme allows the user to read and/or write settings and operational items on a
function-by-function basis. However, this also requires a great many commands. The mnemonic format
of the commands is designed to facilitate interactive communications with the relay. It is not necessary to
remember all of the object names. Most commands support a multiple read version where it is not
necessary to specify a complete object name. You can enter the first two letters of a command and the
relay will respond with all applicable objects.
For example, you want the relay to report the breaker operations counter reading. You can enter RB for
Report Breaker and the relay will respond with all of the breaker report objects including the operations
counter. If you had remembered that the object name is OPCNTR, you could have entered RB-OPCNTR
and received only the operations counter report.
Partial object names are also supported. For example, you wish to read the entire peak—since-reset
demand registers. You can enter RD-PI for Report Demand - Peak Current (I) and the relay will respond
with the values and time stamps for A, B, C, N, and Q. To reset all five of the peak since reset demand
registers, enter the command RD-PI=0. To read only the value for the neutral demand, the full object
name would have been entered (RD-PIN).

Batch Command Text File Operations


With a few exceptions, each function of the relay uses one command to set it and each setting command
operates on all of the parameters required by that element. See the example mentioned above in the
paragraph titled Command Structure. This format results in a great many commands to fully set the relay.
Also, the process of setting the relay does not use a prompting mode where the relay prompts you for
each parameter in turn until you exit the setting process. For these reasons, a method for setting the relay
using batch text files is recommended.
In batch upload type operations, the user creates an ASCII text file of commands and sends it to the relay.
To facilitate this process, the response from a multiple read command is output from the BE1-CDS in
command format. So the user need only enter S for Set (with no subgroup) and the relay responds with
all of the setting commands and their associated parameters. If the user enters S2 for Set Group 2, the
relay responds with all of the setting commands for setting group 2. The user may capture this response
to a file, edit it using any ASCII text editor, and then send the file back to the relay. See Section 11, ASCII
Command Interface for a more detailed discussion of how to use ASCII text files for setting the relay.

BE1-CDS Quick Start 2-5


BESTCOMS For BE1-CDS 220, Graphical User Interface
BESTCOMS-CDS220-16, Basler Electric’s graphical user interface (GUI) software is an alternative
method for quickly developing setting files in a friendly, Windows® based environment. Using the GUI,
you may prepare setting files off-line (without being connected to the relay) and then upload the settings to
the relay at your convenience. These settings include protection and control, operational and logic,
breaker and transformer monitoring, metering, and fault recording. Engineering personnel can develop,
test, and replicate the settings before exporting it to a file and transmitting the file to technical personnel in
the field. On the field end, the technician simply imports the file into the BESTCOMS database and
uploads the file to the relay where it is stored in nonvolatile memory.
The GUI also has the same preprogrammed logic schemes that are stored in the relay. This gives the
engineer the option (off-line) of developing his setting file using a preprogrammed logic scheme,
customizing a preprogrammed logic scheme, or building a scheme from scratch. Files may be exported
from the GUI to a text editor where they can be reviewed or modified. The modified text file may then be
uploaded to the relay. After it is uploaded to the relay, it can be brought into the GUI, but it can not be
brought directly into the GUI from the text file. The GUI logic builder uses basic AND/OR gate logic
combined with point and click variables to build the logic expressions. This reduces the design time and
increases dependability.
The GUI also allows for downloading industry standard COMTRADE files for analysis of stored
oscillography data. Detailed analysis of the oscillography files may be accomplished using Basler
Electric’s BESTWAVE software. For more information on Basler Electric’s Windows® based BESTCOMS
(GUI) software or BESTWAVE, contact your local sales representative or Basler Electric Technical
Support Services Department in Highland, Illinois.

GETTING STARTED
Connections
Figure 12-10 in Section 12, shows typical external dc control connections. If your relay has power supply
option Y or Z, it can be supplied by normal 120V ac house power. These two power supply options (Y and
Z) are the midrange and high range ac/dc power supplies. The contact sensing inputs are half-wave
rectified, opto-isolators. The default contact recognition and debounce settings enable their use on ac
signals as well as dc signals.
Figure 12-9 shows typical external ac sensing connections. The relay measures the A phase, B phase,
and C phase current magnitudes directly from the three current sensing inputs on Circuit #1 (this is
dependent on style configuration). Circuit #2 measures the A phase, B phase, and C phase current
magnitudes directly from the three current sensing inputs. The neutral and negative sequence
magnitudes are calculated from the fundamental component of each of the three-phase currents. When
evaluating the negative sequence functions, the relay can be tested using a two-phase current source. To
fully evaluate the operation of the relay in the power system, it is desirable to use a three-phase current
source.
Connect a computer to the front RS-232 port (refer to Section 12, Installation, for connection diagrams).
Apply power and set the clock using the RG-TIME= and RG-DATE= commands (refer to Appendix D,
Setting Terminal Communications, and Section 11, ASCII Command Interface, for additional information).

Entering Test Settings


Enter SG (Set General) to get a listing of the general setting commands with default parameters and put
them in a text file as described previously in Batch Command Text File Operations. Then enter S0
(setting group zero) to get a listing of the group 0 protection setting commands with default parameters
and put them in a text file also. With these two subgroups of settings, you will not see the global security
settings, user programmable BESTlogic settings, settings for protection setting groups 1, 2, and 3, settings
for alarm functions, and the settings for breaker monitoring functions.
Open the SG file in a text editor, change settings as required, and save the changes. For example:
• The ratios for the phase and neutral current transformers (CT2, CTG).
• The demand interval and CT circuit to monitor for the phase, neutral, and negative sequence currents
(DIP, DIN, DIQ).
2-6 Quick Start BE1-CDS
• The nominal system frequency (FREQ).
• The normal phase sequence (ABC or ACB) for the system (PHROT).

Open the S0 file in a text editor, change settings as required, and save the changes. For example:
• The differential taps setting by putting the 87 function in manual and selecting tap values (87).
• The pickup, time dial, and curve for the 51 functions (51P, 51N, 51Q).
While editing this file, it is necessary to set a logic scheme to be active using the SL-N= (Set Protection
LOGIC) command. The default setting is BASIC-87, which means that several protection elements are
enabled and interconnected but are disabled with settings of zero. See Section 8, Application, for
diagrams that describe the BASIC-87 logic scheme.

Enter A= to gain setting access and then send each of these text files to the relay as described above
under Batch Command Text File Operations. Do not forget to add E;Y (Exit; Save Settings? Yes) to the
end of both files.

As you gain knowledge of the relay, you can experiment with the rest of the settings. To set up a file with
all user settings, enter S and the relay will respond with all settings in command format. The acceptance
test procedure in Section 13, Testing And Maintenance, provides a basic procedure for creating a file with
all user settings.

Checking The State Of Inputs


Section 8, Application shows the BASIC-87 logic diagram. Review the basic 87 logic to help understand
the following discussion. In this BASIC-87 scheme, IN1 and IN2 are being used to show the position of
the breakers in the sequence of events record (SER). Input 3 is showing the status of the 86 lockout
relay. Inputs 6 to 8 can be used for alarm annunciation. You can quickly review the state of the inputs in
two different ways: one, through the front panel HMI, and two, using the ASCII command interface.
The front panel HMI displays the input status on screen 1.4.1, \STAT\OPER\INPUT. A diagram showing
all of the menu tree branches is located in Section 10, HMI. To get to this screen, press the up scrolling
pushbutton until you reach the top screen in the current branch. You know when you have reached the
top screen because the screen stops changing when you press the up scrolling pushbutton. From this
position, press the right scrolling pushbutton until you have reached the screen titled, \STATUS BE1-
CDS220 REPORT STATUS. From this position, press the down scrolling pushbutton one time
(\STAT\TARGETS) and press the right scrolling pushbutton three times. At this time, you should see the
OPERATIONAL STATUS screen, \STAT\OPER_STAT. If you press the down scrolling pushbutton from
this screen, you should see the INPUTS screen, \STAT\OPER\INPUT.
Another method would be to use the ASCII command interface. One command that you can use to see
the status of the inputs is RG-STAT. Another command is RG-INPUT. This command will only read the
status of the inputs and nothing else.

Testing
To determine if the relay is responding correctly to each test, the following commands are useful.
• RG-TARG, (report general targets): reports the targets from the last fault.
• RF, (report faults): reports a directory listing of the twelve fault summary reports. The fault summary
reports are numbered from 1 to 255 and then wrap around and start over. RF-### reports the ###
report.
• RS-##, (report sequence of events record), ## events: reports the most recent ## changes of state in
the protection and control logic.

FAQ/TROUBLE SHOOTING

Frequently Asked Questions


1.) Why won’t the trip LED reset when I press the reset key on the front panel?
The Reset key is context sensitive. To reset the trip LED or the targets, the target screen must be
displayed. To reset the alarms, the alarm screen must be displayed.

BE1-CDS Quick Start 2-7


2.) Is the power supply polarity sensitive?
No, the power supply will accept either an ac or dc voltage input. However, the contact sensing for
the programmable inputs is polarity sensitive. See Section 12, Installation, for a typical
interconnection diagram.

3.) What voltage level is used to develop current flow through the contact sensing inputs?
Voltage level is dependent on the power supply option (BE1-CDS style) and the position of the
contact sensing jumper. See Section 12, Installation, for additional information.

4.) How can the BE1-CDS be configured into a simple transformer differential relay?
There are two preprogrammed schemes that perform this function. One is the BASIC-87 and the
other is BASIC-TX. See Section 8, Application, for additional information.

5.) How can the BE1-CDS be configured into a generator differential relay?
The BE1-CDS can be configured into a generator differential relay by loading the preprogrammed
nd th
logic scheme BASIC-87. You may disable the 2 and 5 harmonic functions by setting these
thresholds to zero. See Section 8, Application, for additional information.

6.) Do I have to connect my current transformers in a special way to compensate for the phase shift
between the high side and low side of a transformer?
No, the BE1-CDS can compensate for phase shift. See Section 3, Input And Output Functions for
additional information.

7.) Should I be concerned about zero sequence blocking in my CT connections?


No, the BE1-CDS can compensate for zero sequence blocking. See Section 3, Input And Output
Functions for additional information.

8.) Does the BE1-CDS trip output contact latch after a fault?
The answer to the question is yes and no. In general, once the fault goes away the output contacts
open. The BE1-CDS does offer an option to ensure that the contact will stay closed for at least 200
milliseconds. See Section 3, Input And Output Functions for additional information on that function.
But, BESTlogic can latch the relay outputs. See Section 8, Application, Application Tips, for
additional information.

9.) Why won’t a function work when I put in settings such as the pickup and time delays?
Make sure that the logic function is enabled.

10.) How many overcurrent elements does the BE1-CDS have available?
The BE1-CDS has nine instantaneous overcurrent and nine time overcurrent elements. Just like any
element, each of these elements can be assigned to any output for building logic equations.

11.) Can I make logic settings from the front panel?


No, the front panel cannot program logic settings. Logic settings must be programmed using the
ASCII command interface or BESTCOMS communication software.

12.) Since the BE1-CDS is a programmable device, what are the factory defaults?
The factory default logic is BASIC-87 logic. Default settings are shown with each function in the
instruction manual. For input or output default settings see Section 3, Input And Output Functions.
For protection and control functions, see Section 4, Protection And Control. The default settings are
also embedded in the BE1-CDS spreadsheets that are available from the Basler Electric web site,
http://www.basler.com, in the Download Section under Software Tools.

2-8 Quick Start BE1-CDS


13.) Does the BE1-CDS have a battery installed as the back-up power source for the internal clock on
loss of power?
No, the BE1-CDS does not have a battery. It uses a capacitor installed for a battery back-up power
source for the internal clock on loss of power. This design maintains the clock for at least eight
hours. See Section 1, Specifications, for additional information.

14.) Since the BE1-CDS has overcurrent elements in addition to the differential protection functions, are
the timing curves the same as Basler Electric’s other numeric overcurrent relays?
Yes, the timing curves are the same as other Basler Electric numerical overcurrent relays such as
the BE1-851.

15.) Why do I keep getting access conflict errors when I am communicating with the relay?
If you have tried to gain access to more than one port at a time, an access conflict results. The unit
has three different communication ports. The front HMI and front RS-232 are considered to be the
same port and are the first port (COM 0). The rear RS-232 (COM 1) is the second and the rear RS-
485 (COM 2) is the third port. If you have gained access at the front panel HMI and the 5-minute
timeout has not ended, you cannot gain access at another port. The front RS-232 can still be
accessed because the HMI and front RS-232 are considered to be the same port. Access needs to
be gained only when a write to the BE1-CDS is required (control or setting change or report reset).
Data can be read and reports can be obtained without gaining access. After gaining access though
one of the ports, the session can be ended with the Exit command. If access is gained, but the
session is not ended, a 5-minute timeout will end the session and any changes that were not saved
will be lost. If you are using the BESTCOMS program, the access and exit commands are executed
for you.

16) Why doesn’t the trip LED behave as expected when the relay picks up and trips? Another closely
related question would be why don’t the targets work?
If the logic is setup to the point were the protective element is tripping at the desired current level, but
the targets, trip LED, and fault records are not behaving as expected, then there are two commands
(SG-TRIGGER and SG-TARGET) that need to be checked for proper operation. The SG-TRIGGER
command needs to have the PU trigger and TRIP trigger logic correctly programmed. This should
initiate the fault record. The SG-TARGET command needs the protective element (function) enabled
to log targets. See Section 6, Reporting And Alarm Functions, Fault Reporting, to get more details on
how to correctly program these commands. The trip LED has two different functions in the relay.
When the SG-TRIGGER PU expression is true and the TRIP expression is false, the trip LED
flashes. When both the SG-TRIGGER PU and TRIP expression are true, the trip LED lights solidly.
When neither expression is true, the trip LED lights solidly if there are latched targets. A flashing LED
means one of the protection elements is in a picked-up state and timing towards trip. Once the trip
occurs, the LED turns on solidly. The LED will not change state until the target has been reset. If the
fault has not cleared, the LED turns on again. Table 2-2 is a truth table for the Trip LED, and should
help to interpret the LED indications.
Table 2-2. Trip LED Truth Table
Trip PU Targets LED
0 0 0 OFF
0 0 1 ON
0 1 0 FLASH
0 1 1 FLASH
1 0 0 ON
1 0 1 ON
1 1 0 ON
1 1 1 ON

BE1-CDS Quick Start 2-9


17.) Is the IRIG signal modulated or demodulated?
The IRIG signal is demodulated (dc level-shifted digital signal). See Section 1, Specifications, Section
6, Reporting And Alarm Functions, and Section 12, Installation, for additional information.

18.) Can the IRIG signal be daisy-chained to multiple BE1-CDS units?


Yes, multiple BE1-CDS units can use the same IRIG input signal by daisy-chaining the BE1-CDS
inputs. The burden data is non-linear, approximately 4 kilo-ohms at 3.5 Vdc and 3 kilo-ohms at 20
Vdc. See Section 1, Specifications, Section 6, Reporting And Alarm Functions, and Section 12,
Installation, for additional information.

19.) How can I find out the version number of my CDS?


The application version can be found in three different ways. One, use the HMI, screen 4.6. Two,
use the ASCII command interface with the RG-VER command. Three, use BE1-CDS BESTCOMS
(the version is provided on the general identification screen).

20.) How are reports and other information obtained from the relay saved in files for future use?
Any information reported by the relay can be transferred to a text file and saved for future use. Text
transferred from the relay to your terminal emulation software can be selected and copied to the
clipboard. The clipboard contents are pasted into any word processor such as Microsoft® Notepad,
and then saved with an appropriate file name.
You may also use your terminal emulation software to store reports in files as they are received from
the relay. In BESTVIEW (Basler Electric’s software for terminal emulation), this is accomplished by
using the log/open log file function. In Microsoft® HyperTerminal, this function is available through
the capture text feature. Microsoft® Windows® Terminal provides this function through the received
text file feature.

2-10 Quick Start BE1-CDS


SECTION 3 • INPUT AND OUTPUT FUNCTIONS
TABLE OF CONTENTS

List Of Figures......................................................................................................................................... i
List Of Tables.......................................................................................................................................... i
SECTION 3 • INPUT AND OUTPUT FUNCTIONS.................................................................................... 3-1
GENERAL .............................................................................................................................................. 3-1
INPUT CURRENT .................................................................................................................................. 3-1
Current Measurement Functions..................................................................................................... 3-1
Setting Up The Current Measurement Functions............................................................................ 3-1
CONTACT SENSING INPUTS............................................................................................................... 3-8
Nominal............................................................................................................................................... 3-8
Digital Input Conditioning Function.................................................................................................. 3-8
Setting Up The Digital Input Conditioning Function......................................................................... 3-9
Retrieving Input Status Information From The Relay ...................................................................... 3-9
OUTPUTS .............................................................................................................................................. 3-9
Difference Between Hardware Outputs and Virtual Outputs........................................................... 3-9
Retrieving Output Status ............................................................................................................... 3-10
Relay Trouble Alarm Disable......................................................................................................... 3-10
Programmable Hold Timer................................................................................................................ 3-10
Output Logic Override Control .......................................................................................................... 3-11
Enabling Logic Override Control ................................................................................................... 3-11
Pulsing an Output Contact ............................................................................................................ 3-11
Holding an Output Contact Open or Closed.................................................................................. 3-12
Returning An Output Contact To Logic Control............................................................................. 3-12
Retrieving Output Logic Override Status....................................................................................... 3-13

List Of Figures
Figure 3-1. CT Connections ...................................................................................................................... 3-3
Figure 3-2. DAB/DAC Delta ...................................................................................................................... 3-3
Figure 3-3. Internal Phase and Zero Sequence Compensation................................................................ 3-7
Figure 3-4. Output Logic, General Purpose Output Contacts ................................................................. 3-10
Figure 3-5. Output Logic, Fail-Safe Alarm Output Contact ..................................................................... 3-10

List Of Tables
Table 3-1. Power System Measurement Function Settings ...................................................................... 3-2
Table 3-2. CT Input Circuit Settings .......................................................................................................... 3-4
Table 3-2. CT Input Circuit Settings - Continued ...................................................................................... 3-5
Table 3-3. Internal Compensation Chart .................................................................................................. 3-7
Table 3-4. Contact Sensing Turn-On Voltage ........................................................................................... 3-8
Table 3-5. Digital Input Conditioning Function Settings ............................................................................ 3-9
Table 3-6. Output Hold Function Settings ............................................................................................... 3-11

BE1-CDS Input And Output Functions i


SECTION 3 • INPUT AND OUTPUT FUNCTIONS

GENERAL
BE1-CDS 220 relays have two sets of three-phase current measurement inputs, an optional ground
current measurement input, eight contact sensing (programmable) inputs, six general purpose output
contacts, and one dedicated, fail-safe alarm output contact. Each input and output is isolated and brought
out to separate terminal blocks. This section describes the functioning and setup of these inputs and
outputs.

INPUT CURRENT
Currents from the secondary of CT in power system equipment are applied to internal current transformer
primaries. The internal current transformers provide isolation from the monitored line currents and step the
currents down to internal circuit levels. Secondary current from each internal CT is converted to a voltage
signal, and filtered by an analog, low-pass, anti-aliasing filter.

Current Measurement Functions


The input waveforms are sampled by an analog-to-digital converter (ADC) at 144 samples per cycle and
digitally filtered in a DSP (digital signal processor) using an FIR (finite impulse response) anti-aliasing filter
algorithm. This high sampling rate allows the analog filter to have a high cutoff point which virtually
eliminates errors from the analog filter elements. The output from the digital filter is sample data reduced
to 24 samples per cycle. From the digitally filtered samples, the relay extracts the magnitude and angle of
the fundamental, second harmonic, and fifth harmonic components of each three-phase input and the
fundamental of the optional independent ground current input.
Frequency Compensation. The frequency of the power system is monitored on the C phase input for CT
circuit one. When the current applied to phase C of CT circuit one, is greater than 10% nominal, the BE1-
CDS relay measures the frequency and varies the sampling rate to maintain 144 samples per cycle over a
frequency range of 40 to 63 hertz. If the C phase current on input circuit one is too low for the frequency
to be accurately read, or the measured frequency is outside this range, the relay ADC defaults to 144
samples per cycle of the nominal frequency. Protection is still provided for all functions except for
negative sequence, but accuracy is degraded.
Compensated Restraint And Operate Currents For Differential Protection. As described in Section 1,
General Information, it is necessary to provide phase angle, zero sequence, and tap compensation to the
measured currents prior to their use by the differential protection. The current measurement function
calculates compensated currents for restraint and operate currents and for second and fifth harmonic
operate currents. Tap compensation setup is covered in Section 4, Protection and Control, Phase
Differential Protection.
Neutral and Negative Sequence Current Measurement. The BE1-CDS relay also calculates the neutral
and negative sequence components from the fundamental component of each of the three-phase current
inputs. The relay can be set to accommodate either ABC or ACB phase sequence in calculating the
negative sequence component.
Fast-Dropout Current Detector. The relay includes a separate, fast-dropout current measurement
algorithm for use by the breaker failure function and the breaker trip speed monitoring function. This
measurement algorithm has a sensitivity of 10% nominal rating and detects the interruption of current in
the circuit breaker in less than a cycle.

Setting Up The Current Measurement Functions


Settings for the current measurement functions are provided in Table 3-1.

BE1-CDS Input And Output Functions 3-1


Table 3-1. Power System Measurement Function Settings
Setting Range Increment Unit of Default
Measure
Nominal Frequency 50, 60 NA Hertz 60
Phase Rotation ABC, ACB NA NA ABC
CT Ratio (ct ratio), Input 1 1-50,000 1 Turns 1
CT Connection (ct con), Input 1 WYE, DAB, DAC NA NA WYE
Transf. Connection (tx con), Input 1 NA, WYE, DAB, DAC NA NA NA
Ground Source (gnd src), Input 1 0=No, 1=Yes NA NA 0
(optional)
CT Ratio (ct ratio), Input 2 1-50,000 1 Turns 1
CT Connection (ct con), Input 2 WYE, DAB, DAC NA NA WYE
Transf. Connection (tx con), Input 2 NA, WYE, DAB, DAC NA NA NA
Ground Source (gnd src), Input 2 0=No, 1=Yes NA NA 0
(optional)
CT Ratio, Optional Independent 1-50,000 1 Turns 1
Ground Input

Nominal Frequency. When the current is too low for the frequency to be reliably measured, the ADC
circuit defaults to operation at the nominal frequency setting. This can be set for operation on either 50 or
60 hertz power systems from the optional HMI using screen 6.3.2, SETUP\PWR_S\FREQ and from the
ASCII command interface using the SG-FREQ (settings general-frequency) command.

SG-FREQ Command
Purpose: Reads or changes the nominal power system frequency information used by the relay.
Syntax: SG-FREQ [= <hz>]
Example 1. Change frequency setting
>SG-FREQ=60
Normal Phase Sequence. The normal phase sequence setting can be entered from the optional HMI
using screen 6.3.3, SETUP\PWR_S\P_SEQ and from the ASCII command interface using the SG-PHROT
(settings general-Phase Rotation Sequence) command.

SG-PHROT Command
Purpose: Read/set Phase Rotation setting
Syntax: SG-PHROT[=<phase rotation ABC/ACB>]
Example 1. Set phase rotation sequence to ACB
>SG-PHROT=ACB
Current Input Circuit Settings. The BE1-CDS relay requires information on the CT connections and the
characteristics of the protected zone. For each three-phase CT input circuit, it is necessary to enter the
CT ratio, the CT connection, the transformer connection (if applicable), and optionally whether there is a
ground source that must be taken into consideration.
Each set of three-phase CTs can be connected in wye or one of two delta configurations as shown in
Figure 3-1. As described in Section 1, General Information, Differential Protection Application
Considerations, wye CT connections are recommended for most applications. The CT ratio should always
be entered as the actual ratio and not the effective ratio. When the CTs are connected in delta, the
secondary current under balanced conditions is increased by a factor of the square-root of three, yielding
an effective ratio that is lower than the actual CT ratio. The BE1-CDS automatically takes this factor into
account so it is not necessary for the user to manually compensate when entering the CT ratio.

3-2 Input And Output Functions BE1-CDS


POLARITY
ZONE OF
PROTECTION INTO ZONE

N IA IB IC IA-IB IB-IC IC-IA IA-IC IB-IA IC-IB


D2837-15
12-22-98 WYE DAB DAC
Figure 3-1. CT Connections
As described in Section 1, General Information, Differential Protection Application Considerations, when
the zone of protection includes a transformer, it may be necessary to provide phase angle and zero se-
quence compensation to the currents used by the differential protection elements (see Sidebar 3-1). For
each CT input circuit, a setting is provided to enter the transformer connection associated with that input.
If there is no transformer within the protected zone, this setting should be set to NA (Not Applicable).

Sidebar 3-1. Determining the Transformer Connection Parameters


Wye and Autotransformer Windings. The transformer connection for a CT input circuit that is
connected to either a wye or autotransformer winding should be classified as a wye winding.
Delta Transformer Windings. The transformer connection for a CT input circuit that is connected to a
delta winding can be classified as one of two delta connections: Delta IA-IB (DAB), or Delta IA-IC
(DAC). A delta configuration is defined by the currents that flow in the primary phases connected to
the delta. The wye winding phase connections are used as the point of reference since the current
that flows in the wye winding is the same as the current in the wye side primary phases. Figure 3-2a
shows an example of a transformer with a DAB connection. Figure 3-2b shows an example of the
same transformer with the phases reconnected to provide a DAC connection. If there is no wye
winding to use as reference, as is the case with a delta/delta transformer, the definition of the delta
configuration is not important.
IC=Ic-Ia IA=Ia-Ic
C c A a

IB=Ib-Ic IB=Ib-Ia
b B b
B

IA=Ia-Ib IA=Ic-Ib
a C c
A

D2837-22.vsd
D2837-21.vsd 12-22-98
12-21-98

Figure 3-2a. DAB Delta Figure 3-2b. DAC Delta

BE1-CDS Input And Output Functions 3-3


With the appropriate CT and transformer connection information, the relay can automatically determine the
correct compensation required. Table 3-2 provides a listing of all acceptable combinations of CT and
transformer connection settings and the compensation that the BE1-CDS will apply. The recommended
settings for each configuration are highlighted in Bold. Figure 3-2 provides details on how to choose the
correct CT and transformer connections to describe the application. If a combination of connection
settings is entered that results in an invalid condition, the relay will give an error message when the
settings are validated on Exit/Save Yes.

Table 3-2. CT Input Circuit Settings


Normal Transformer Connection CT Connection Compensation
Phase CT Input CT Input CT Input CT Input CT Input CT Input
Sequence Circuit 1 Circuit 2 Circuit 1 Circuit 2 Circuit 1 Circuit 2
NA NA NA WYE WYE WYE (NONE) WYE (NONE)
WYE DAB DAB WYE (NONE)
WYE DAC DAC WYE (NONE)
DAB WYE WYE (NONE) DAB
DAC WYE WYE (NONE) DAC
DAB DAB WYE (NONE) WYE (NONE)
DAC DAC WYE (NONE) WYE (NONE)
B WYE WYE WYE WYE DAB DAB
WYE DAB DAB WYE (NONE)
WYE DAC DAC WYE (NONE)
DAB WYE WYE (NONE) DAB
A C
0° LAG DAC WYE WYE (NONE) DAC
C DAB DAB WYE (NONE) WYE (NONE)
DAC DAC WYE (NONE) WYE (NONE)

A B 0° LAG
B DAB WYE WYE WYE WYE (NONE) DAB)
WYE DAB WYE (NONE) WYE (NONE)

A C
30° LAG
C

A B 30° LEAD
B DAC WYE WYE WYE WYE (NONE) DAC
WYE DAC WYE (NONE) WYE (NONE)

A C
30° LEAD
C

A B 30° LAG

3-4 Input And Output Functions BE1-CDS


Table 3-2. CT Input Circuit Settings - Continued
Normal Transformer Connection CT Connection Compensation
Phase CT Input CT Input CT Input CT Input CT Input CT Input
Sequence Circuit 1 Circuit 2 Circuit 1 Circuit 2 Circuit 1 Circuit 2
B WYE DAB WYE WYE DAB WYE (NONE
DAB WYE WYE (NONE) WYE (NONE)

A C
30° LEAD
C

A B 30° LAG
B WYE DAC WYE WYE DAC WYE (NONE)
DAC WYE WYE (NONE) WYE (NONE)

A C
30° LAG
C

A B 30° LEAD
B DAB DAB WYE WYE WYE (NONE) WYE (NONE)
WYE DAB DAB WYE (NONE)
WYE DAC DAC WYE (NONE)
DAB WYE WYE (NONE) DAB
A C
0° LAG DAC WYE WYE (NONE) DAC
C DAB DAB WYE (NONE) WYE (NONE)
DAC DAC WYE (NONE) WYE (NONE)

A B 0° LAG
B DAB DAC WYE WYE DAC DAB
WYE DAB DAC WYE (NONE)
DAC WYE WYE (NONE) DAB
DAC DAC WYE (NONE) WYE (NONE)
A C
60° LAG
C

A B 60° LEAD

BE1-CDS Input And Output Functions 3-5


Table 3-2. Continued, CT Input Circuit Settings
Normal Transformer Connection CT Connection Compensation
Phase CT Input CT Input CT Input CT Input CT Input CT Input
Sequence Circuit 1 Circuit 2 Circuit 1 Circuit 2 Circuit 1 Circuit 2
B DAC DAC WYE WYE WYE (NONE) WYE (NONE)
WYE DAB DAB WYE (NONE)
WYE DAC DAC WYE (NONE)
DAB WYE WYE (NONE) DAB
A C
0° LAG DAC WYE WYE (NONE) DAC
C DAB DAB WYE (NONE) WYE (NONE)
DAC DAC WYE (NONE) WYE (NONE)

A B 0° LAG
B DAC DAB WYE WYE DAB DAC
WYE DAC DAB WYE (NONE)
DAB WYE WYE (NONE) DAC
DAB DAC WYE (NONE) WYE (NONE)
A C
60° LEAD
C

A B 60° LAG

NOTE
The CT input circuit settings are used by the auto-tap calculation function to calculate the
correct tap adjustment factor for the differential functions. When entering these settings
via the ASCII command interface, the validation routine and auto-tap calculation is
performed on exit after all parameters have been entered.
When entering these settings using the optional HMI, the validation routine and auto-tap
calculation is performed on exit of each screen. This may cause an out of range error
message from the auto-tap calculation function. The user is advised to enter valid CT
input circuit settings on screen 6.3.1.1, SETUP\PWR_S\CON\CTP prior to entering the
auto-tap calculation settings. If the user has previously set the auto-tap calculation
settings and needs to change the CT input circuit settings, it may be necessary to
temporarily change the auto-tap function setting to manual on screens 5.1.1.3, 5.2.1.3,
5.3.1.3, and 5.4.1.3, \PROT\SG#\87\TAP in order to enter the new CT settings.
See Section 4 Protection and Control, Phase Differential Protection for more information
on the auto-tap calculation function.

Additionally, as described in Section 1, General Information, Differential Protection Application


Considerations, Problem 5, if there is a ground source within the protected zone, the user can apply a
numerical, zero sequence trap to remove the zero sequence components from the current to prevent
misoperation on external ground faults. This setting is optional. It is not required to enter a ground source
setting of 1 to describe a grounded wye transformer connection. Even though not all grounded wye
transformer connections are ground sources, the relay always assumes that a wye transformer connection
is a ground source so that it is secure. Zero sequence current unbalance can occur in three legged core
transformers due to the phantom tertiary effect. In all cases, the relay chooses delta compensation for a
wye transformer connection so that the zero sequence components are blocked.
Figure 3-3 shows how the currents will be calculated for each set of current inputs for use by the phase
differential protection function. The calculation is dependent upon the phase compensation chosen as
shown in Table 3-2 and the ground source setting.

3-6 Input And Output Functions BE1-CDS


Table 3-3. Internal Compensation Chart
Compensation Ground Source A Phase B Phase C Phase
Wye (None) 0 = No IA IB IC
Wye (None) 1 = Yes IA - I0 IB - I0 IC - I0
DAB 0 = No or 1 = Yes (IA - IB) / √3 (IB - IC) / √3 (IC - IA) / √3
DAC 0 = No or 1 = Yes (IA - IC) / √3 (IB - IA) / √3 (IC - IB) / √3

(IC-IB)/√3
IC IC
-IB -IB

(IC-IA)/√3

(IA-IB)/√3
-IA -IA
IA IA
(IB-IA)/√3

(IA-IC)/√3

IB IB
(IB-IC)/√3 -IC -IC

DAB Internal Compensation DAC Internal Compensation

Measured Current Measured Current *(-1) Compensated Current


Figure 3-3. Internal Phase and Zero Sequence Compensation
CT connection settings can be entered from the optional HMI using screen 6.3.1.1,
SETUP\PWR_S\CON\CTP and from the ASCII command interface using the SG-CT (setting general-CT
input circuit) command.

SG-CT Command
Purpose: Enter CT connections and the characteristics of the protected zone
Syntax: SG-CT[n] [ = <ct ratio>, <ct con>,<tx con>,<gnd src>
Comments: n =three-phase current input circuit 1 or 2
The ratio may be entered in a number of different formats, (primary/secondary,
primary:secondary, or turns), but it is always reported in turns.
Example 1. Enter the following parameters for a transformer differential application:
For input 1, CT ratio is 300:5, CT are connected in wye, and transformer winding is delta
with phase currents of A minus B. There is no grounding bank within the delta side of the
zone of protection. For input 2, CT ratio is 800:5, CT are connected in wye, and
th
transformer winding is wye. Notice in this example that the 4 parameter is not entered.
In this case it will be unchanged from its previous setting.
>SG-CT1 = 60,WYE,DAB; SG-CT2 = 800:5,WYE,WYE

Example 2. Enter the following parameters for a bus differential application:


For input 1 and 2, CT ratio of 1200:5, CT are connected in wye.
>SG-CT1 = 1200/5,WYE,NA; SG-CT2 = 1200/5,WYE,NA
Example 3. Read the CT input circuit parameters
>SG-CT
SG-CT1=60,WYE,DAB,0
SG-CT2=160,WYE,WYE,0

BE1-CDS Input And Output Functions 3-7


If the BE1-CDS relay is equipped with the optional independent ground current input, the CT ratio must be
entered for that input. This setting can be entered from the optional HMI using screen 6.3.1.2,
SETUP\PWR_S\CON\CTG and from the ASCII command interface using the SG-CTG (setting general-CT
input circuit ground) command.

SG-CTG Command
Purpose: Reads or changes the ground CT ratio information used by the relay.
Syntax: SG-CTG[=<ratio>]
Comments: The ratio may be entered in a number of different formats, (primary/secondary,
primary:secondary, or turns), but it is always reported in turns.

Example 1. Enter the CT ratio of a neutral 400:5 CT.


>SG-CTG=80
or
>SG-CTG=400/5
or
>SG-CTG=400:5
SG-CTn and SG-CTG affect the primary current metering values, the contact duty log (RB-DUTY)
calculations, the transformer duty log (RT-DUTY), and the COMTRADE fault record current levels. The
CT ratios and connections also affect the automatic phase compensation used by the 87 differential
function as well as the auto-tap calculation.

CONTACT SENSING INPUTS


BE1-CDS relays have eight contact sensing inputs to initiate BE1-CDS relay actions. These inputs are
isolated and require an external wetting voltage. Nominal voltage(s) of the external dc source(s) must fall
within the relay dc power supply input voltage range. To enhance user flexibility, the BE1-CDS relay uses
wide range ac/dc power supplies that cover several common control voltage ratings. To further enhance
flexibility, the input circuits are designed to respond to voltages at the lower end of the control voltage
range while not overheating at the high end of the control voltage range.
Energizing levels for the contact sensing inputs are jumper selectable for a minimum of 13 Vdc for 24 Vdc
nominal sensing voltages, 26 Vdc for 48 Vdc nominal sensing voltages, or 69 Vdc for 125 Vdc nominal
sensing voltages. See Table 3-4 for the control voltage ranges.
Each BE1-CDS is delivered with the contact sensing jumpers installed for operation in the lower end of the
control voltage range (pins 1 and 2 shorted). If the contact sensing inputs are to be operated at the upper
end of the control voltage range, the jumpers must be changed to pins 2 and 3 shorted or completely
removed. See Section 3, Installation for details on how to set the jumper positions in the contact sensing
input circuits.
Table 3-4. Contact Sensing Turn-On Voltage
Nominal Turn-On Range
Control Voltage Pin 1 – Pin 2 Pin 2 – Pin 3
24 Vdc 13-19 Vdc N/A
48/125 Vac/dc 26 to 38 V 69 to 100 V
125/250 Vac/dc 69 to 100 V 138 to 200 V

Digital Input Conditioning Function


The relay scans the inputs for status 24 times per cycle. When operating on a 60 hertz power system, this
results in the input status being sampled every 0.7 milliseconds (0.8 milliseconds on 50 hertz systems).
The relay uses digital contact recognition and debounce timers that are user settable to condition the
signals applied to the inputs. The user can adjust these parameters so that the optimum compromise
between speed and security can be attained for the specific application. The digital input conditioning
function is evaluated every quarter cycle.

3-8 Input And Output Functions BE1-CDS


If the sampled status of the monitored contact is detected to be closed for the recognition time, the logic
variable changes from an open (logic zero or FALSE) state to a closed (logic one or TRUE) state. Once
the contact closure has been recognized, the logic variable will remain in the closed state until the
sampled status of the monitored contact is detected to be open for longer than the debounce time. At this
point, the logic variable will change from a closed (logic one or TRUE) state to an open (logic zero or
FALSE) state.

Setting Up The Digital Input Conditioning Function


The settings for the digital input signal conditioning function are shown in Table 3-5. The digital input
conditioning settings can be entered from the ASCII command interface using the SG-IN (setting general-
input) command.
Table 3-5. Digital Input Conditioning Function Settings
Setting Range Increment Unit of Measure Default
Recognition Time 4 to 255 1* milliseconds 4
Debounce Time 4 to 255 1* milliseconds 16
NOTE: * Since the input conditioning function is evaluated every quarter
cycle, the setting is internally rounded to the nearest multiple of 4.16
milliseconds for 60 hertz systems and 5 milliseconds for 50 hertz
systems.

SG-IN Command
Purpose: Read/Set the logic for the input contact debounce settings.
Syntax: SG-IN[n] [=<recognition time>, <debounce time>]
Comments: n=input number 1-8
Example1. Read the input conditioning settings for input 3.
>SG-IN3
4,16
If the user desires that the relay reject ac voltage that may become coupled into the contact sensing
circuits, the recognition time can be set to greater than one-half of the power system cycle period to take
advantage of the half-wave rectification provided by the input circuitry.
If the user desires to use an ac wetting voltage, the recognition time can be set to less that one-half of the
power system cycle period and the debounce timer can be set to greater than one-half of the power
system cycle period to ride through the negative half cycle. The default settings of 4 milliseconds
recognition and 16 milliseconds debounce time allow the relay to be used with ac wetting voltage.

Retrieving Input Status Information From The Relay


The status of the inputs can be determined from the optional HMI using screen 1.4.1, STAT\OPER\INPUT
and from the ASCII command interface using the RG-STAT (report general-status) command or RG-
INPUT (report general-input status) command. See Section 6, Reporting and Alarm Functions, General
Status Reporting for more information.

OUTPUTS
BE1-CDS relays have six general purpose output contacts (OUT1 through OUT6) and one fail-safe,
normally closed (relay in de-energized state), alarm output contact (OUTA). Each output is isolated and
rated for tripping duty. Relays OUT1 and OUT6 are high speed (one-quarter cycle nominal operating
time). OUT1 through OUT5 are Form A (normally open), OUT6 is Form C (single-pole, double-throw) and
OUTA is Form B (normally closed).

Difference Between Hardware Outputs and Virtual Outputs


Output contacts OUT1 through OUT6 and OUTA are driven by BESTlogic output expressions VO1
through VO6 and VOA (virtual outputs 1 through 6, and A). Since the use of each output contact is

BE1-CDS Input And Output Functions 3-9


completely programmable, the user can assign meaningful labels to each output, as well as, to the zero
and one states. See Section 7, BESTlogic Programmable Logic for more information on programming
output expressions in your programmable logic scheme.
A virtual output (VOn) exists only as a logical state inside the relay. A hardware output (OUTn) is a
physical, output relay contact. The state of the output contact can vary from the state of the output logic
expression for three reasons: one, the relay trouble alarm disables all outputs; two, the programmable
hold timer function; and three, the select before operate logic override control function. Figure 3-4 shows
a diagram of the output contact logic for the general purpose output contacts. Figure 3-5 shows a diagram
of the output contact logic for the fail-safe alarm output contact.
VIRTUAL OUTPUT
CONTROLED BY SL-VO[n]
LOGIC EQUATION
OUTPUT
VO[n] STATUS H A R D W A R E
AND
OUTPUT
OUTPUT CONTROL
(CO-OUT COMMAND) OR 0 Sec OR
Control Override (0/1) AND AND OUT[n]
0.200 Sec
AND
Override State (0/1)
ONE SHOT TIMER

Hold State (0/1) ALMREL


HOLD ENA D2647-18
08-20-98
(SG-HOLD COMMAND)

Figure 3-4. Output Logic, General Purpose Output Contacts


VIRTUAL OUTPUT
CONTROLED BY SL-VO[n]
LOGIC EQUATION OUTPUT
STATUS HARDWARE
VO[A]
AND OUTPUT
OUTPUT CONTROL
(CO-OUT COMMAND) OR 0 Sec
Control Override (0/1) AND OR NOT OUT[A]
0.200 Sec
AND
Override State (0/1)
ONE SHOT TIMER

ALMREL
Hold State (0/1)
HOLD ENA D2647-19
08-20-98
(SG-HOLD COMMAND)

Figure 3-5. Output Logic, Fail-Safe Alarm Output Contact

Retrieving Output Status


The status of the output contacts can be accessed from the HMI using screen 1.4.2, STAT\OPER\OUT
and from the ASCII command interface using the RG-STAT (report general-status) command or RG-
OUTSTAT (report general-output status) command. See Section 6, Reporting and Alarm Functions,
General Status Reporting for more information.

Relay Trouble Alarm Disable


When the relay self diagnostics function detects a problem in the relay, it sets internal alarm condition
ALMREL. See Section 6, Reporting and Alarm Functions, Alarms Function for more details on this
function. This alarm condition disables the outputs and de-energizes the OUTA relay closing the OUTA
contact.

Programmable Hold Timer


Historically, trip contact seal-in circuits have been provided in electromechanical relays. These seal-in
circuits consisted of a dc coil in series with the relay trip contact and a seal-in contact in parallel with the
trip contact. The seal-in feature serves several purposes for the electromechanical relays. One is to
provide mechanical energy to drop the target. Two is to carry the dc tripping current from the induction
disk contact which may not have significant closing torque for a low resistance connection. Three is to
prevent the relay contact from dropping out until the current has been interrupted by the 52a contacts in

3-10 Input And Output Functions BE1-CDS


series with the trip coil. If the tripping contact opens before the dc current is interrupted, the contact may
be damaged. The first two of these items are not an issue for solid-state relays, but the third item is an
issue.
To prevent the output relay contacts from opening prematurely, a hold timer can hold the output contact
closed for a minimum of 200 milliseconds. Alternatively, if the protection engineer desires seal-in logic
with feedback from the breaker position logic, he can provide this logic by modifying the BESTlogic
expression for the tripping output. How to do this is described in Section 7, BESTlogic Programmable
Logic, Application Tips.
The hold timer can be enabled for each input from the ASCII command input using the SG-HOLD (setting
general, hold) command. The settings are shown in Table 3-6.
Table 3-6. Output Hold Function Settings
Setting Range Increment Unit of Measure Default
Output Hold Timer 0=disabled NA NA OUTA=0
1=enabled OUT1=1
OUT2=1
OUT3=1
OUT4=1
OUT5=1
OUT6=0

SG-HOLD Command
Purpose: Read/set output hold operation
Syntax: SG-HOLD[n] [= <hold status(0/1)>]
Comments: n = output number 1 to 6 or A
Example 1. Program all outputs to have a minimum hold time except OUT2
>SG-HOLDA=1; SG-HOLD1=1; SG-HOLD2=0; SG-HOLD3=1; SG-HOLD4=1;
SG-HOLD5=1 ; SG-HOLD6=1.

Output Logic Override Control


The state of each output contact can be controlled directly using the select before operate, output control
function. The virtual output logic expression that normally controls the state of an output contact can be
overridden and the contact pulsed, held open, or held closed. This function is useful for testing purposes.
An alarm point is available in the programmable alarm function for monitoring when the output logic has
been overridden. See Section 6. Reporting and Alarm Functions, Alarm Functions for more information
on programmable alarms. Write access to control functions is required to use the select before operate
control functions from either the optional HMI or the ASCII command interface.

Enabling Logic Override Control


The logic override control must be enabled before the function can be used. The default state is disabled.
Enabling output logic override control cannot be accessed from the HMI. It can only be accessed from the
ASCII command interface using the CS/CO-OUT=ena/dis (control select/control operate-output
override=enable or disable) command. This command only enables or disables logic override control. It
does not enable or disable the outputs themselves.

Pulsing an Output Contact


Outputs can be pulsed to provide the push-to-energize function provided in Basler Electric solid state
relays. This is useful in trip testing the protection and control system. When pulsed, the contact changes
from the current state as determined by the virtual output logic expression to the opposite state for 200
milliseconds. After 200 milliseconds, the output contact is returned automatically to logic control.
Pulse override control can be accessed from the HMI using screen 2.4, \CTRL\OUT and entering a P in
the field for the output contact. Control can be accessed from the ASCII command interface using the
CS/CO-OUTn=P (control select/control operate-output contact n=pulse) command.

BE1-CDS Input And Output Functions 3-11


Holding an Output Contact Open or Closed
An output can be forced to a closed (logic one or TRUE) state or to an open (logic zero or FALSE) state.
This is useful in testing to disable a contact during testing. Open or close logic override control can be
accessed from the HMI using screen 2.4, \CTRL\OUT and entering a one for closed or a zero for open in
the field for the output contact. Control can be accessed from the ASCII command interface using the
CS/CO-OUTn=0/1 (control select/control operate-output contact n=0/1) command.

Returning An Output Contact To Logic Control


When the logic has been overridden and the contact is held in an open or closed state, it is necessary to
return the contact to logic control manually.
Return to logic control can be accessed from the HMI using screen 2.4, \CTRL\OUT and entering an L for
return to logic control in the field for the output contact. Control can be accessed from the ASCII
command interface using the CS/CO-OUTn=L (control select/control operate-output contact n=logic
control) command.

CS/CO-OUT Command
Purpose: Control Output status
Syntax: CS/CO-OUT[n][=<mode>/ENA/DIS]
Comments: n = Output number A/1/2/3/4/5/6.
mode=1/0/P/L
The output control commands require the use of Select Before Operate logic. First the
command must be selected using the CS-OUT command. After the command is
selected, there is a 30 second window during which the CO-OUT control command can
be entered. The control selected and operation selected must exactly match or the
command is blocked. If the command is not entered within the 30 second window, the
command is blocked. If the control command is blocked, an error message is output.
Output control commands, except for ENA and DIS, are acted on immediately. To take
effect, the ENA or DIS output control command changes must be saved with the EXIT
command. The output control status is saved to non-volatile memory, and if power is lost,
it is restored after power returns.

Example 1. Enable output control feature .


>CS-OUT = ENA
OUT=ENA SELECTED
>CO-OUT = ENA
OUT=ENA EXECUTED (NOTE: Not effective until EXIT with SAVE(Y).)

Example 2. Test all outputs by pulsing momentarily.


CS-OUT = P
OUT=P SELECTED
CO-OUT = P
OUT=P EXECUTED

Example 3. Disable the trip output (1) by holding at 0.


CS-OUT1 = 0
OUT1=0 SELECTED
CO-OUT1 = 0
OUT1=0 EXECUTED

Example 4. Return output 1 to logic control.


CS-OUT1 = L
OUT1=L SELECTED
CO-OUT1 = 0
OUT1=L EXECUTED

3-12 Input And Output Functions BE1-CDS


Retrieving Output Logic Override Status
The status of the output contact logic override control can be accessed from the HMI using screen 1.4.2,
\STAT\OPER\OUT. Screen 2.4, \CTRL\OUT is output control but can also display the current status. The
status of the output logic can also be accessed from the ASCII command interface using the RG-STAT
(report general-status) command or RG-OUTCNTRL (report general-output control status) command.
See Section 6, Reporting and Alarm Functions, General Status Reporting for more information.
An L indicates that the state of the output is controlled by logic. A zero or one indicates that the logic has
been overridden and the contact is held in the open (zero) or closed (one) state. A P indicates that the
contact is being pulsed and will return to logic control automatically.

BE1-CDS Input And Output Functions 3-13


SECTION 4 • PROTECTIO N AND CONTROL
TABLE OF CONTENTS

List Of Figures ........................................................................................................................................ii


List Of Tables..........................................................................................................................................ii
SECTION 4 • PROTECTION AND CONTROL.......................................................................................... 4-1
GENERAL .............................................................................................................................................. 4-1
SETTING GROUPS ............................................................................................................................... 4-1
Setting BESTlogic Settings, Setting Group Control Function ......................................................... 4-2
Setting Operational Settings, Setting Group Control Function ....................................................... 4-4
Logic Override, Setting Group Control Function ............................................................................. 4-7
Retrieving Setting Group Status Information From the Relay......................................................... 4-8
DIFFERENTIAL PROTECTION ............................................................................................................. 4-8
87 Phase Differential Function............................................................................................................ 4-8
Setting BESTlogic, 87 Phase Differential Function....................................................................... 4-10
Setting Tap Compensation Settings, 87 Phase Differential Function........................................... 4-11
Setting Operational Settings, 87 Phase Differential Function....................................................... 4-13
Retrieving Logic Output Status Information From the Relay ........................................................ 4-14
87ND Neutral Differential Function................................................................................................... 4-14
Setting BESTlogic,87ND Neutral Differential Function Block ....................................................... 4-16
Auto-Tap Compensation, 87 Neutral Differential Function ........................................................... 4-16
Setting Operational Settings, 87ND Neutral Differential Function ................................................ 4-17
Retrieving Logic Output Status Information From the Relay ........................................................ 4-17
OVERCURRENT PROTECTION ......................................................................................................... 4-17
50T Instantaneous Overcurrent With Settable Delay Functions ...................................................... 4-17
Setting BESTlogic, 50T Overcurrent Functions ............................................................................ 4-18
Setting Operational Settings, 50T Overcurrent Functions ............................................................ 4-19
Retrieving Logic Output Status Information From the Relay ........................................................ 4-20
51 Time Overcurrent Functions ........................................................................................................ 4-20
Setting BESTlogic, 51 Time Overcurrent Function Blocks ........................................................... 4-20
Setting Operational Settings, 51 Time Overcurrent Functions ..................................................... 4-21
Setting Programmable Time Current Characteristic Curve Coefficients ...................................... 4-22
Retrieving Logic Output Status Information From the Relay ........................................................ 4-23
Negative Sequence Overcurrent Protection ..................................................................................... 4-23
Negative Sequence Pickup Settings............................................................................................. 4-23
Negative Sequence Coordination Settings ................................................................................... 4-24
Delta/Wye Transformer Application. ............................................................................................. 4-25
BF BREAKER FAILURE PROTECTION.............................................................................................. 4-25
Setting BESTlogic, Breaker Failure Function................................................................................ 4-26
Setting Operational Settings, Breaker Failure Function................................................................ 4-27
Retrieving Logic Output Status Information From the Relay ........................................................ 4-27
62/162 GENERAL PURPOSE LOGIC TIMER FUNCTIONS............................................................... 4-28
Mode 1, Pickup/Dropout Timer ..................................................................................................... 4-28
Mode 2, One-Shot Nonretriggerable Timer................................................................................... 4-28
Mode 3, One-Shot Retriggerable Timer........................................................................................ 4-28
Mode 4 Oscillator .......................................................................................................................... 4-29
Mode 5, Integrating Timer ............................................................................................................. 4-29
Mode 6, Latch ............................................................................................................................... 4-29
Setting BESTlogic, 62/162 General Purpose Logic Timer Function Blocks ................................. 4-29
Setting Operational Settings, 62/162 General Purpose Logic Timer Functions ........................... 4-30
Retrieving Logic Output Status Information From the Relay ........................................................ 4-31
VIRTUAL SWITCHES .......................................................................................................................... 4-31
43 Virtual Selector Switches ............................................................................................................. 4-31
Setting BESTlogic, 43/143/243/343/443/543/643/743 Virtual Selector Switch Function.............. 4-32
Select Before Operate Control, Virtual Selector Switches............................................................ 4-32
Retrieving Virtual Selector Switch Status Information From the Relay......................................... 4-33
BE1-CDS Protection And Control i
101 Virtual Breaker Control Switch................................................................................................... 4-33
Setting BESTlogic, 101 Virtual Breaker Control Switch Function ................................................. 4-33
Select Before Operate Control, Virtual Breaker Control Switches................................................ 4-34
Retrieving Virtual Selector Switch Status Information From the Relay......................................... 4-34

List Of Figures
Figure 4-1. Setting Group Control Function Block .................................................................................. 4-1
Figure 4-2. Input Control Mode 1 .............................................................................................................. 4-3
Figure 4-3. Input Control Mode 2 .............................................................................................................. 4-3
Figure 4-4. Automatic Operation Based On Load Change ....................................................................... 4-5
Figure 4-5. Automatic Based on Cold Load Pickup .................................................................................. 4-6
Figure 4-6. 87 Phase Differential Function ............................................................................................... 4-8
Figure 4-7. 87 Phase Differential Protection Functional Block Diagram................................................... 4-9
Figure 4-8. Percentage Restrained Differential Characteristic ................................................................. 4-9
Figure 4-9. 87ND Neutral Differential Function Block............................................................................. 4-14
Figure 4-10. 87ND Polarity Configuration ............................................................................................... 4-15
Figure 4-11. 87 Neutral Differential Protection Functional Block Diagram ............................................. 4-15
Figure 4-12. Typical 50T Overcurrent Function ...................................................................................... 4-18
Figure 4-13. Typical 51 Time-Overcurrent Function ............................................................................... 4-20
Figure 4-14. Phase-to-Phase Fault Magnitude....................................................................................... 4-24
Figure 4-15. Sequence Components For An A-B Fault .......................................................................... 4-24
Figure 4-16. Breaker Failure Function ..................................................................................................... 4-25
Figure 4-17. 62/162 General Purpose Logic Timer Function ................................................................. 4-28
Figure 4-18. Mode 1, Pickup/Dropout Timer.......................................................................................... 4-28
Figure 4-19. Mode 2, One-Shot Nonretriggerable Timer ....................................................................... 4-28
Figure 4-20. Mode 3, One-Shot Retriggerable Timer ............................................................................ 4-28
Figure 4-21. Mode 4, Oscillator............................................................................................................... 4-29
Figure 4-22. Mode 5, Integrating Timer ................................................................................................. 4-29
Figure 4-23. Mode 6, Latch..................................................................................................................... 4-29
Figure 4-24. Typical Virtual Selector Switch Function ............................................................................ 4-31
Figure 4-25. Virtual Breaker Control Switch Function............................................................................. 4-33
Figure 4-26. Virtual Breaker Control Switch State Diagram ................................................................... 4-33

List Of Tables

Table 4-1. Setting Group Control Function BESTlogic Settings ............................................................... 4-2
Table 4-2. Setting Group Binary Codes .................................................................................................... 4-3
Table 4-3. Setting Group Control Function Settings ................................................................................. 4-4
Table 4-4. 87 Phase Differential Function BESTlogic Settings .............................................................. 4-10
Table 4-5. MVA And KVA Base Parameters .......................................................................................... 4-11
Table 4-6. 87 Phase Differential Tap Compensation Settings................................................................ 4-11
Table 4-7. 87 Phase Differential Operational Settings............................................................................ 4-13
Table 4-8. 87ND Neutral Differential Function BESTlogic Settings........................................................ 4-16
Table 4-9. 87ND Neutral Differential Operational Settings ..................................................................... 4-17
Table 4-10. 50T Overcurrent Function BESTlogic Settings.................................................................... 4-18
Table 4-11. 50T Overcurrent Function Operational Settings .................................................................. 4-19
Table 4-12. 51 Time Overcurrent Function BESTlogic Settings............................................................. 4-21
Table 4-13. 51 Time Overcurrent Function Operational Settings ........................................................... 4-21
Table 4-14. Definitions for Equations 4-8 and 4-9 .................................................................................. 4-22
Table 4-15. Programmable Time Current Characteristic Curve Coefficients ......................................... 4-23
Table 4-16. BF Breaker Failure Function BESTlogic Settings................................................................ 4-26
Table 4-17. BF Breaker Failure Function Operational Settings .............................................................. 4-27
Table 4-18. 62/162 General Purpose Logic Timer BESTlogic Settings.................................................. 4-30
Table 4-19. 62/162 General Purpose Logic Timer Operational Settings................................................ 4-30
Table 4-20. 43/143/243/343/443/543/643/743 Virtual Selector Switch BESTlogic Settings .................. 4-32
Table 4-21. 101 Virtual Breaker Control Switch BESTlogic Settings...................................................... 4-34

ii Protection And Control BE1-CDS


SECTION 4 • PROTECTION AND CONTROL

GENERAL
BE1-CDS relays provide many functions that can be used for protection and control of power system
equipment in and around the protected zone. Four settings groups are provided for adapting the
coordination under various operating conditions with options for controlling which settings are active by
automatic or programmable logic criteria. Protection and control functions include phase and neutral
differential protection, overcurrent protection, breaker failure protection, general purpose logic timers, and
virtual control switches.
To use a function, three things must occur.
1. The function block must be enabled in the active logic scheme by SL-<function> command.
2. The inputs and outputs of that function must be connected properly in a logic scheme.
3. Operational characteristics or settings for the function must be programmed by the user and
based on the specific application requirements.
Items 1 and 2 may be skipped if a preprogrammed logic scheme is used for a typical application. Most of
the schemes are general in nature and unneeded capabilities may be disabled by programming the
operational characteristics setting to zero.

Example: The second negative sequence instantaneous overcurrent function is enabled in the logic
scheme but is not needed for this application. Set the 150TQ function pickup setting to
zero (S#-150TQ=0).
More information on each individual function for item 1 is provided in this section. More information on
items 2 and 3 is provided in Section 7, BESTlogic Programmable Logic and Section 8, Application.

SETTING GROUPS
BE1-CDS relays provide a normal setting group, SG0, and up to three auxiliary setting groups SG1, SG2,
and SG3. Auxiliary setting groups allow adapting the coordination settings to optimize them for a
predictable situation. Sensitivity and time coordination settings can be adjusted to optimize sensitivity or
clearing time based upon source conditions or to improve security during overload conditions. The
possibilities for improving protection by eliminating compromises in coordination settings with adaptive
setting groups are endless.
The group of settings that are active at any point in time is
controlled by the setting group control function. This function
Mode =
allows for manual (logic) or automatic control. When manual 0-disable SG0
control is enabled by the AUTO logic input not being asserted, 1-discrete select
SETTING
the function monitors logic inputs D0, D1, D2, and D3 and 2-binary select SG1
GROUP
changes the active setting group according to the status of D0 LOGIC
SG2
these inputs. These inputs can be connected to logic D1 SL-GROUP
expressions such as contact sensing inputs. When automatic D2 SG3
D3
control is enabled by the AUTO logic input being asserted, the
AUTO D2840-21.vsd
relay monitors loading or unbalance conditions and changes 05-28-99

the active setting group according to the switch to and return Figure 4-1. Setting Group Control
criteria set. The change criteria for manual and automatic Function Block
control is described in more detail later in this section.
The setting group control function has four logic variable
outputs, SG0, SG1, SG2, and SG3. The appropriate variable is asserted when each setting group is
active. These logic variables can be used in programmable logic to modify the logic based upon which
setting group is active. For example, it may be desired for the 51P to trip the low side breaker through
OUT2 under normal conditions, but to trip the 86T lockout relay through OUT1 when in setting group 3.
The logic for OUT1 would include the term 51PT*SG3 so that 51PT only actuates OUT1 when SG3 is
asserted.

BE1-CDS Protection And Control 4-1


The setting group control function also has an alarm output variable SGC (Setting Group Changed). This
output is asserted whenever the relay switches from one setting group to another. The SGC alarm bit is
asserted for the SGCON time setting. This output can be used in the programmable alarms function if it
is desired to monitor when the relay changes to a new setting group. See Section 6, Reporting and
Alarms Functions, Alarms Function for more information on using alarm outputs.
The SGCON time setting also serves to provide anti-pump protection to prevent excessive changing
between groups. Once a change in active group has been made, another change cannot take place for
two times the SGCON setting.
When the relay switches to a new setting group, all functions are reset and initialized with the new
operating parameters. The settings change occurs instantaneously so at no time is the relay off line. The
active setting group is saved in nonvolatile memory so that the relay will power up using the same setting
group as it was using when it was powered down. To prevent the relay from changing settings while a
fault condition is in process, setting group changes are blocked when the relay is in a picked-up state.
Since the relay is completely programmable, the fault condition is defined by the pickup logic expression
in the fault reporting functions. See Section 6, Reporting and Alarm Functions, Fault Reporting for more
information.
The selection of the active setting group provided by this function block can also be overridden. When
the logic override is used, a setting group is made active and the relay stays in that group regardless of
the state of the automatic or manual logic control conditions.

Setting BESTlogic Settings, Setting Group Control Function


The logic settings for the setting group control function are provided in Table 4-1. These settings will
determine how the function selects the active setting group when manual (logic) selection is enabled.
Table 4-1. Setting Group Control Function BESTlogic Settings
Function Range/Purpose Default
Logic Mode 0=Disabled, 1=Discrete Input Selection, 1
2=Binary Coded Selection
Discrete Input 0 (D0) Logic Input Logic expression. Meaning dependent upon Mode setting 0
Discrete Input 1 (D1) Logic Input Logic expression. Meaning dependent upon Mode setting 0
Discrete Input 2 (D2) Logic Input Logic expression. Meaning dependent upon Mode setting 0
Discrete Input 3 (D3) Logic Input Logic expression. Meaning dependent upon Mode setting 0
Auto/Manual (AUTO) Logic Input Logic expression. When TRUE enables automatic control /0
and when FALSE enables logic control

Manual (logic) control reads the status of the logic inputs to the setting group control function block to
determine what setting group should be active. For the logic inputs to determine which setting group
should be active, the AUTO input must be a logic 0. The function block logic mode setting determines
how it reads these logic inputs. There are three possible logic modes as shown in Table 4-1.
When the setting group control function block is enabled for Mode 1, there is a direct correspondence
between each discrete logic input and the setting group that will be selected. That is, when input D0 is
asserted, SG0 will be selected, and when input D1 is asserted, SG1 will be selected, etc. The active
setting group latches in after the input is read so they can be pulsed. It is not necessary that the input be
maintained. If one or more inputs are asserted at the same time, the numerically higher setting group will
be the one that is active. A pulse must be present for approximately one second for the setting group
change to occur. After a setting group change occurs, no setting group change can occur within two
times the SGC ON time. Any pulses to the inputs will be ignored during that period.
Figure 4-2 shows an example of how the inputs are read when the setting group control function is
enabled for Mode 1. Note that a pulse on the D3 input while D0 was also active does not cause a setting
group change to SG3 because the AUTO input is active.
When the setting group control function block is enabled for Mode 2, the inputs on D0 and D1 are read as
binary encoded as shown in Table 4-2. Inputs D2 and D3 are ignored. A new coded input must be stable
for approximately 1 second for the setting group change to occur. After a setting group change occurs,
no setting group change can occur within two times the SGC ON time.

4-2 Protection And Control BE1-CDS


D3
D2647-20
08-21-98
D2

D1

D0

AUTO

SG3

SG2

SG1

SG0

SGC

Figure 4-2. Input Control Mode 1


Table 4-2. Setting Group Binary Codes
Binary Code
D1 D0 Decimal Equivalent Setting Group
0 0 0 SG0
0 1 1 SG1
1 0 2 SG2
1 1 3 SG3

Input control mode 2 is when the active setting group is controlled by a binary signal applied to the
discrete inputs D0-D1. This requires separate logic equations for only D0 and D1 if all setting groups are
to be used. Figure 4-3 shows how the active setting group follows the binary sum of the D0 and D1
inputs except when blocked by the AUTO input. Note that a pulse on the D1 input while D0 was also
active does not cause a setting group change to SG3 because the AUTO input is active.

D3
D2647-21
08-21-98
D2

D1

D0

AUTO

SG3

SG2

SG1

SG0

SGC

Figure 4-3. Input Control Mode 2


Figure 4-3 shows an example of how the inputs are read when the setting group control function block is
enabled for Mode 2. Note that a pulse on the D1 input while D0 was also active does not cause a setting
group change to SG3 because the AUTO input is active.
The BESTlogic settings can be made from the ASCII command interface using the SL-GROUP (settings
logic-group control) command.

BE1-CDS Protection And Control 4-3


SL-GROUP Command
Purpose: Used to program a logical mode of operation for the setting group control block.
Syntax: SL-GROUP[=<mode>,<D0 Logic>,<D1 Logic>,<D2 Logic>,<D3 Logic>,<AUTO Logic>]
Example Set the setting group control such that automatic selection is overridden and emergency
overload settings (SG3) are in place when Transformer 2 is out of service. Contact
sensing input 2 is TRUE when either the high side or low side breakers for Transformer 2
are open.
>SL-GROUP=1,0,0,0,IN2,/IN2
>
or
>SL-GROUP=2,IN2,IN2,0,0,/IN2
>
Setting Operational Settings, Setting Group Control Function
The operating parameter settings for the setting group control function are provided in Table 4-3. The
group 1, 2, and 3 switch to and return settings will determine how the function selects the active setting
group when automatic selection is enabled.
Table 4-3. Setting Group Control Function Settings
Setting Range Increment Unit of Measure Default
SGC (Setting Group Change) On 0=disabled, 1-10 1 Seconds 5
Time
Group 1 switch to time 0=disabled, 1-60 1 Minutes 0
Group 1 switch to threshold 0-150 1 % of SG0 51* Pickup 0
Group 1 return time 0=disabled, 1-60 1 Minutes 0
Group 1 return threshold 0-150 1 % of SG0 51* Pickup 0
Group 1 monitored element 51* NA NA 51P
Group 2 switch to time 0=disabled, 1-60 1 Minutes 0
Group 2 switch to threshold 0-150 1 % of SG0 51* Pickup 0
Group 2 return time 0=disabled, 1-60 1 Minutes 0
Group 2 return threshold 0-150 1 % 0
Group 2 monitored element 51* NA NA 51P
Group 3 switch to time 0=disabled,1-60 1 Minutes 0
Group 3 switch to threshold 0-150 1 % 0
Group 3 return time 0=disabled,1-60 1 Minutes 0
Group 3 return threshold 0-150 1 % 0
Group 3 monitored element 51* NA NA 51P
Note: 51* is any 51 element: 51P, 51N, 51Q, 151P, 151N, 151Q, 251P, 251N, or 251Q,
The SGC ACTIVE output is typically used to provide an external acknowledgment that a setting group
change occurred. If SCADA was used to change the active group, then this signal could be monitored to
verify that the operation occurred. The SGC ACTIVE output ON time is user programmable and should
be set greater than the SCADA scan rate. This can be set from the optional HMI using screen 6.7,
SETUP\AUX_STGS and from the ASCII command interface using the SG-SGCON (settings general-SGC
ON time) command.

SG-SGCON Command
Purpose: Read/Program the SGC output ON time.
Syntax: SG-SGCON[=<time>]
Example Set the SGC output to pulse ON (TRUE) for one second after the setting group is
changed.
>SG-SGCON=1
>
Automatic control of the active setting group allows the relay to automatically change configuration for
optimum protection based on the current system conditions. For example, in locations where seasonal
variations can cause large variations in loading, the overcurrent protection can be set with sensitive

4-4 Protection And Control BE1-CDS


settings during the majority of the time and switch to a setting group with lower sensitivity (higher pickups)
during the few days of the year when the loading is at peak.
There are five settings for each group that are used for automatic control. Each group has a switch to
threshold and time delay, a return threshold and time delay, and a monitored element. The switch to and
return thresholds are a percentage of the SG0 pickup setting for the monitored element. The monitored
element can be any of the 51 protective functions. Thus, if you wish to switch settings based upon
loading, you could set it to monitor 51P. If you wish to switch settings based upon unbalance, you could
set it to monitor 51N or 51Q. When the monitored element is 51P, any one phase must be above the
switch to threshold for the switch to time delay for the criteria to be met. All phases must be below the
return threshold for the return time delay for the return criteria to be met.
Figure 4-4 shows an example of using the automatic setting group selection settings to change settings
groups based upon loading. Note that the AUTO input must be at a TRUE logic state in order to allow the
automatic logic to operate. At time = 0, current begins to increase. When current reaches 75 percent of
pickup, setting group two begins timing (30 minutes). When current reaches 90 percent of pickup, setting
group three begins timing (5 minutes). After 5 minutes, at time = 37, with the current still above setting
group three threshold, setting group three becomes active and the setting group change output pulses.
At time = 55, setting group two timer times out but no setting group change occurs because a higher
setting group takes precedence. The faint dashed line for SG2, between time = 55 and 75 shows that
setting group two would be active except for setting group three. Current decreases to 75 percent at time
= 70, and setting group three return timer begins timing. Current varies but stays below 75 percent for 5
minutes and at time = 75, setting group two becomes active and the setting change output pulses. After
20 minutes, setting group zero becomes active and the setting change output pulses.

Load Current
as % of S0-51 <pickup>
150

140
SP-GROUP2=30,75,20,70,51P
130
SP-GROUP3=5,90,5,75,51P
120

110

100

90

80

70

60 30
5 5
50
20
40

30

20

10
TIME
(MINUTES)
0 10 20 30 40 50 60 70 80 90 100

SG3

SG2

SG1

SG0
D2837-23.vsd
01-07-99
SGC

Figure 4-4. Automatic Operation Based On Load Change

BE1-CDS Protection And Control 4-5


This function can also be used to automatically change the active setting group for cold load pickup
conditions. If the switch to threshold for a group is set to 0%, the function will switch to that group when
there is no current flow for the time delay period indicating that the breaker is open or the circuit source is
out of service. The threshold for this is 10% nominal rating of the relay current input.
Figure 4-5 shows how the active setting group follows the load current and time delay settings for setting
group 1. Note that the AUTO input must be at a TRUE (1) logic state in order to allow the automatic logic
to operate. When the breaker opens, the load current falls to zero at time = 15 minutes. After 10
minutes, setting group one becomes active and the setting group change output pulses TRUE. When the
breaker is closed at time = 40 minutes, load current increases to approximately 90 percent of pickup. As
the load current decreases to 50 percent of pickup, the setting group one return timer begins timing. After
ten minutes, setting group one output goes FALSE, the setting group returns to setting group zero, and
the setting group change output pulses TRUE.
When the switch-to criteria is met for more than one setting group at a time, the function will use the
numerically higher of the enabled settings groups. If the switch-to time delay setting is set to 0 for a
setting group, automatic control for that group is disabled. If the return time delay setting is set to 0 for a
setting group, automatic return for that group is disabled and the relay will remain in that settings group
until returned manually of by logic override control.

Load Current
as % of S0-51 <pickup>
150

140

130

120 SP-GROUP1=10, 0, 10, 50, 51P

SP-GROUP2=0,0,0,0,0
110
SP-GROUP3=0,0,0,0,0
100

90

80

70

60

50

40

30

20

10 10 10
0 TIME
(0.5A) (MINUTES)
0 10 20 30 40 50 60 70 80 90 100

SG3

SG2

SG1

SG0
D2840-22.vsd
01-28-99
SGC

Figure 4-5. Automatic Operation Based on Cold Load Pickup


The automatic setting group control parameters can be set from the optional HMI using screen 6.7.1,
6.7.2, 6.7.3, SETUP\AUX\SG# and from the ASCII command interface using the SP-GROUP (settings
protection-group control) command.

4-6 Protection And Control BE1-CDS


SP-GROUP Command
Purpose: Read/change automatic control settings for setting group
Syntax: SP-GROUP[n][=<switch time>,<switch level>,<return time>,<return level>,<prot element>]
Example Read the setting group automatic operation settings.
>SP-GROUP
SP-GROUP1=30,0,15,75,51P; SP-GROUP2=15,75,5,70,151P
SP-GROUP3=5,70,5,50,51N
>
SG1 is set to switch to cold-load pickup settings when the loading in the CT circuit
monitored by the 51P protective function is 0 for 30 minutes. It will return after the
current drops to 75% of SG0, 51P setting for 15 minutes
SG2 is set to switch to overload settings when loading in the CT circuit monitored by the
151P protective function is above 75% of the SG0, 151P pickup setting for 15 minutes. It
will return after the current drops below 70% for 5 minutes.
SG3 is set to switch to unbalance settings when the ground unbalance in the CT circuit
monitored by the 51N protective element is above 70% of the SG0 51N pickup setting for
5 minutes. It will return after the ground unbalance current drops below 50% for 5
minutes.

Logic Override, Setting Group Control Function


Control of the active setting group from the setting group control function can be overridden. This can be
accomplished from the optional HMI from screen 2.3, \CTRL\SG or from the ASCII command interface
using the select before operate CS/CO-GROUP (control select-setting group/control operate-setting
group) command. A setting group change using logic override control is also blocked for two times the
SGCON setting after a setting group change and when the fault reporting pickup expression is TRUE.
The setting group change takes place immediately without having to execute an exit-save settings
command.
A group override alarm bit is set in the programmable alarm function when the logic has been overridden.
This output can be used in the programmable alarms function if it is desired to monitor when the function
has been overridden. See Section 6, Reporting and Alarms Functions, Alarms Function for more
information on using alarm outputs.

CS/CO-GROUP Command
Purpose: Read/change active setting group
Syntax: CS/CO-GROUP[=<n>/L]
Comments: <n> = new setting group number 0-3
L = returns group control to the setting group control function.
The group control commands require the use of Select Before Operate logic. First the
command must be selected using the CS-GROUP command. After the command is
selected there is a 30 second window during which the CO-GROUP control command
can be entered. The control selected and operation selected must exactly match or the
command is blocked. If the command is not entered within the 30 second window, the
command is blocked. If the control command is blocked, an error message is output.
Example 1. Read the current status of setting group override which is overridden and held in SG0.
>CO-GROUP
0
>
Example 2. Override logic control and change the active setting group to SG3.
>CS-GROUP=3
GROUP=3 SELECTED
>CO-GROUP=3
GROUP=3 EXECUTED
>

BE1-CDS Protection And Control 4-7


Example 3. Return control of the active setting group to the setting group control function.
>CS-GROUP=L
GROUP=L SELECTED
>CO-GROUP=L
GROUP=L EXECUTED
>
Example 4. Group override error due to time out of select.
>CS-GROUP=3
GROUP=3 SELECTED
>CO-GROUP=3
ERROR:NO SELECT
?
Retrieving Setting Group Status Information From the Relay
The active setting group can be determined from the optional HMI from screen 1.4.4, \STAT\OPER\
ACTIVEG. The setting group can be determined from the ASCII command interface using the RG-STAT
or RG-GRPACTIVE commands. See Section 6, Reporting and Alarm Functions, General Status
Reporting for more information.
The status of logic override can be determined from the optional HMI from screen 2.3, \CTRL\SG. The
status of logic override can be determined from the ASCII command interface using the RG-STAT or RG-
GRPCNTRL commands. See Section 6, Reporting and Alarm Functions, General Status Reporting for
more information.

DIFFERENTIAL PROTECTION

87 Phase Differential Function


BE1-CDS relays provide three-phase percentage restrained differential 87RPU
protection with high-speed unrestrained instantaneous differential 87RT
Mode = PERCENT
protection. The differential protection includes harmonic restraint to 0-disable DIFF
improve security in transformer applications. The 87 function (see 1-enabled with 87UT
Figure 4-6) has five outputs 87RPU (restrained pickup), 87RT Harmonic
(restrained trip), 87UT (unrestrained trip), 2NDHAR (second harmonic Restraint
restraint picked up), and 5THHAR (fifth harmonic restraint picked up). (87)
BLK 2NDHAR
A Block logic input is provided to block operation of the differential
protection. When this expression is TRUE, the function is disabled. 5THHAR
For example, this may be an input wired to a differential cutoff switch. D2840-23.vsd
01-28-99

Section 1 General Information, Differential Protection Application Con- Figure 4-6. 87 Phase Differential
siderations describes application of percentage restrained differential Function
protection. This section discusses the details of how the function works
and how to set it up. Figure 4-7 shows a detailed functional diagram of one phase of the phase
differential protection function. These functions and comparators are duplicated for each phase.
The measured currents are phase, zero sequence, and tap compensated. Section 3, Input And Output
Functions, Current Measurement Input Functions describes the setup of the relay for phase and zero
sequence compensation. Setup of the tap adjustment compensation is described later in this section.
The restraint current function uses the compensated current to calculate the restraint current magnitude
(in multiples of tap). Depending on the setting (S<g>-87), it calculates the maximum or average restraint
current. The Operating Current Function determines the magnitude of the fundamental, second, and fifth
harmonic differential current as the phasor sum of those components of the compensated currents.
Figure 4-8 shows the characteristic of the Restrained Element function. This comparator has a slope
setting and a minimum pickup setting. The slope setting is the ratio of operate current to restraint current.
The slope setting should be set above the maximum mismatch caused by excitation losses, tap
mismatch, and load tap changers. The minimum pickup setting determines the minimum sensitivity of the
restrained element. If the ratio of operate current to restraint current is above the slope setting and the
operate current is above the minimum pickup setting for any of the three phases, the 87RPU (87
restrained element picked up) logic output is set.

4-8 Protection And Control BE1-CDS


Minimum
Pickup Slope

Restraint
87 Restrained
Current Restrained Pickup
Element

2nd 2 Cycle
harmonic Delay
Fundamental Fund inhibit
per unit Fund Iop
Phasor
87 Restrained
Phase 2nd TM Trip
2nd harmonic
Compensation per unit Operating 2nd Iop
Phasor

5th harmonic
and Tap 5th Current 2nd
5th Iop
Phasor Adjustment per unit
Harmonic

5th
Harmonic 2nd Harmonic
Inhibit Status

Unrestrained 5th Harmonic


setting
5th
Status
TM
Harmonic
Restraint
Current
Transient
F u n d Iop
Monitor

Unrestrained 87 Unrestrained Trip


2X Unrestrained
setting Element
D2840-24.vsd
02-08-99

Figure 4-7. 87 Phase Differential Protection Functional Block Diagram


3

D2837-11.DWG
OPERATING CURRENT (IN MULTIPLES OF TAP)

01-28-99
2

)
60%
TO
( 15
MINIMUM PICKUP =
= 0.01 to 1.00 00
TIMES TAP * 1
IOP
R
E = IREST
SLOP
1

1 2 3 4 5
RESTRAINT CURRENT (IN MULTIPLES OF TAP)

Figure 4-8. Percentage Restrained Differential Characteristic

BE1-CDS Protection And Control 4-9


If the target is enabled for the restrained element, the target reporting function will record an 87R target
for the appropriate phases when the 87RT output is TRUE and the fault recording function trip logic
expression is TRUE. See Section 6 Reporting and Alarm Functions, Fault Reporting Functions for more
details on the target reporting function.
The differential protection function includes a transient monitor to detect the effects of CT saturation
during a through fault. It does this by monitoring the change in restraint current versus the change in
operate current. For an internal fault, the restraint current and operate current will experience a step
increase at the same time. For an external fault, there should be no operate current. If CT saturation
occurs during a through fault, the operate current will increase at some time after the restraint current
increases. In this case, a two-cycle delay is added to the restrained differential output to enhance
security.
The second and fifth Harmonic functions check the ratio of the second and fifth harmonic operate current
to the fundamental operate current. Traditional harmonic restraint units operate on the ratio of harmonic
current to total operate current versus the ratio to only the fundamental operate current used by the BE1-
CDS. For this reason, the relay will provide greater security for inrush and overexcitation with the same
harmonic inhibit ratio settings used with traditional differential relays. When either of these two
comparators is above the threshold, the percentage restrained output is blocked from setting the 87RT
(87 restrained trip) logic output. If the second or fifth harmonic inhibit comparators are picked up for any
of the three phases, the 2NDHAR and 5THHAR logic outputs respectively are also set.
In many cases, the second harmonic content of the inrush current may show up primarily in only one or
two phases which can cause one or two phases to not be inhibited. The BE1-CDS relay allows the
second harmonic currents to be shared between the three phases. When second harmonic sharing is
enabled, the magnitude of the second harmonic operating current is summed from all three phases and
this magnitude is used by the second harmonic comparator for each phase instead of the second
harmonic operate current for only that phase. This is superior to other methods of cross blocking since
each phase element operates independently in its comparison of operating current to harmonic current.
Thus, security is enhanced without sacrificing dependability because a faulted phase will not be
restrained by inrush on unfaulted phases.
The Unrestrained Element function provides high-speed tripping for high grade faults inside the zone of
protection. This comparator has a minimum pickup setting. If the operate current is above the threshold,
for any of the three phases, the 87UT (87 unrestrained element trip) logic output is set. The transient
monitor function also enhances security for this function by doubling the pickup threshold when CT
saturation is detected. The minimum setting for the unrestrained trip threshold should be the maximum
inrush current with a small margin. See Appendix E for more information on setting this element.
If the target is enabled for the unrestrained element, the target reporting function will record an 87U target
for the appropriate phases when the 87UT output is TRUE and the fault recording function trip logic
expression is TRUE. See Section 6, Reporting and Alarm Functions, Fault Reporting Functions for more
details on the target reporting function.
An alarm variable is also provided in the programmable alarms function that can be used to indicate an
alarm condition if the percentage restrained differential protection is nearing a trip condition on load. This
alarm triggers a diagnostic routine that attempts to determine the source of the mismatch that is causing
the differential unbalance. See Section 6, Reporting and Alarm Functions, Alarms Function for more
details on the alarm reporting function.

Setting BESTlogic, 87 Phase Differential Function


The logic settings for the 87 Phase Differential function are provided in Table 4-4. These settings will
enable the function and provide blocking control as determined by the logic expression assigned to the
block input.
Table 4-4. 87 Phase Differential Function BESTlogic Settings
Function Range/Purpose Default

Logic Mode 0=Disabled, 1=Enabled 1


Block Logic Input Logic expression. Disables function when TRUE 0

The BESTlogic settings can be made from the ASCII command interface using the SL-87 (settings logic-
87) command.
4-10 Protection And Control BE1-CDS
SL-87 Command
Purpose: Used to program a logical mode of operation for an 87 protection block.
Syntax: SL-87[= <mode>,[<BLK logic>]]
Example 1. Read 87 Logic Configurations (enabled with no blocking)
>SL-87
1,0
>
Example 2. Set 87 Logic to be enable and blocked if input 1 is closed (TRUE)
>SL-87=1,IN1
>
Setting Tap Compensation Settings, 87 Phase Differential Function
As discussed in Section 1, General Information, Differential Protection Application Considerations, the
measured currents must be tap adjusted to eliminate magnitude mismatch prior to being used by the 87
phase differential protection function. The tap adjust factors can be manually calculated per Equations
4-1 and 4-2. Or, the user can enter the MVA and KV base parameters (Table 4-5) and the relay will
calculate the tap adjust factors using CTR and Compensation Factor parameters from the current
measurement input function settings. See Section 3, Input And Output Functions, Current Measurement
Functions for more details on these settings. For a transformer application, the mismatch will be at a
minimum if the actual transformer voltage ratings are used taking the no-load tap changer into
consideration. If the transformer has a load tap changer, the voltage rating at the middle of the
adjustment range should be used. This is generally at neutral. Table 4-6 lists the tap compensation
settings.
MVA * 1000 * COMP1 MVA * 1000 * COMP2
TAP1= TAP2 =
3 * KV1* CTR1 3 * KV2 * CTR2
Equation 4-1 Equation 4-2
Table 4-5. MVA And KVn Base Parameters
Parameter Description Explanation
MVA MVA Base Full load MVA or top rating of the protected equipment
KVn KV Base for CT input n L-L Voltage in KV for each CT input circuit
CTRn CT Ratio for CT input n Actual ratio not effective ratio
COMPn Phase Compensation √3 if CTs are connected in Delta (ctcon = DAB or DAC).
Adjustment Factor for 1 in all other cases.
CT input n See Section 3, Table 3-2 and Figure 3-3

Table 4-6. 87 Phase Differential Tap Compensation Settings


Setting Range Increment Unit of Default
5A 1A Measure
Auto-tap MVA base Manual = auto- Manual = auto- NA Manual
tap disabled tap disabled
0.5 to 9999 0.5 to 9999 0.1 MVA
Tap CT input 1 or 2.0 to 20.0 or 0.40 to 4.00 or 0.01 for 2.00 to 9.99 Sec. Amps 2
0.1 for 10.0 to 20.0 or or
Auto-tap KV Base 0.01 to 1000.0 0.01 to 1000 0.01 Pri. KV
Tap CT input 2 or 2.0 to 20.0 or 0.40 to 4.00 or 0.01 for 2.00 to 9.99 Sec. Amps 2
0.1 for 10.0 to 20.0 or or
Auto-tap KV Base 0.01 to 1000.0 0.01 to 1000 0.01 Pri. KV

BE1-CDS Protection And Control 4-11


Note To Users Of The BE1-87T Transformer Differential Relay:
Three-phase versions of the BE1-87T also allow internal phase compensation. The
jumper settings for the BE1-87T correspond to the internal compensation for the BE1-
CDS as follows: ∆1 = DAC and ∆2 = DAB.
When calculating the tap adjust settings for the BE1-87T, the √3 COMPn factor has to be
included regardless of whether phase compensation is done by connecting the CTs in
delta or by using internal delta compensation. The BE1-CDS automatically takes the √3
factor into account prior to the tap adjustment when internal phase compensation is
applied to a set of CT input currents. Thus, the tap adjust factors for these two relays will
not be the same in applications using internal phase compensation.

The input currents can be tap adjusted up to a spread ratio of 10:1. If the ratio between TAP1 and TAP2
is greater than ten, it will be necessary to adjust the CT ratios to bring the tap factors closer together.
When the auto-tap calculation feature is used, the relay will give an error message if the spread ratio is
greater than ten.
If one of the calculated taps is outside the acceptable range (2.0 to 20 for 5 ampere units or 0.4 to 4.0 for
1 ampere units), the auto-tap calculation feature will select the nearest acceptable tap and calculate the
other tap so that the correct spread ratio is maintained. If the user is manually calculating the taps, the
same adjustment should be made.
The auto-tap calculation settings can be entered for each setting group from the optional HMI using
screen 5.#.1.2, \PROT\SG#\87\MVA. The manual tap compensation settings can be entered for each
setting group from the optional HMI using screen 5.#.1.3, \PROT\SG#\87\TAP. These two screens are
mutually exclusive. If the user enters settings on the TAP screen, the MVA and KV settings on the MVA
screen will be zeroed out. If the user enters settings on the MVA screen, the automatically calculated
taps are shown on both screens.
The auto-tap calculation settings or the manual tap settings can be entered for each setting group from
the ASCII command interface using the S<g>-TAP87 command.

S<g>-TAP87 Command
Purpose: TAP Settings for 87
Syntax: S<g>-TAP87[ = <mva/MANUAL>,<kv1/tap1>,<kv2/tap2>]
Comments: g = setting group number 0 to 3. Use # as a wild card to refer to all groups.
Example 1. Set the MVA to 20, KV1 to 69 kV, and KV2 to 12.47 kV on all setting groups. The relay
will calculate the taps automatically.
>S#-TAP87=20,69,12.47
>
Example 2. Manually set taps. TAP1 to 2.72 amps and TAP2 to 2.00 amps in setting group 2
>S2-TAP87=MANUAL,2.72,2.00
>
NOTE
The CT input circuit settings are used by the auto-tap calculation function to calculate the
correct tap adjustment factor for the differential functions. When entering these settings
via the ASCII command interface, the validation routine and auto-tap calculation is
performed on exit after all parameters have been entered.
When entering these settings using the optional HMI, the validation routine and auto-tap
calculation is performed on exit of each screen. This may cause an OUT OF RANGE
error message from the auto-tap calculation function. The user is advised to enter valid
CT input circuit settings on screen 6.3.1.1, SETUP\PWR_S\CON\CTP prior to entering
the auto-tap calculation settings. If the user has previously set the auto-tap calculation
settings and needs to change the CT input circuit settings, it may be necessary to
temporarily change the auto-tap function setting to MANUAL on screens 5.1.1.3, 5.2.1.3,
5.3.1.3, and 5.4.1.3 \PROT\SG#\87\TAP in order to enter the new CT settings.
See Section 4, Input and Output Functions, Current Measurement Functions for more
information on CT input circuit settings.

4-12 Protection And Control BE1-CDS


The tap factors calculated by the auto-tap calculation feature can be determined in several ways. They
are displayed on the optional HMI using screen 5.#.1.2, \PROT\SG#\87\MVA. Or, the current check
record provided by the differential alarm function includes a listing of the compensation parameters in the
setting group that was active at the time that the record was triggered. See Section 6 Reporting and
Alarms Function, Differential Alarm for more details on this report.

Setting Operational Settings, 87 Phase Differential Function


The operating parameter settings for the 87 Phase Differential function are provided in Table 4-7.
The settings for restrained minimum pickup and unrestrained trip are set in multiples of tap. If the ideal
taps calculated by Equations 4-1 and 4-2 fell within the acceptable range, the sensitivity settings will be in
Per Unit on the MVA Base used in the equations. For example, a 100 MVA, 115KV transformer has a full
load (1 per unit) current of 500 amperes. A pickup setting of 10 times tap for the unrestrained output
pickup (URO) element is equivalent to 5000 primary amperes of differential current.
If the taps had to be adjusted upwards or downwards to fit within the acceptable range, the sensitivity
settings for these protective elements should be adjusted as well. Equation 4-3 gives the adjustment
factor. The definitions for the variables in Equation 4-3 are the same as those for Equations 4-1 and 4-2.
For example, the ideal taps (TAPnI) were calculated using Equations 4-1 and 4-2 to be 1.6 and 5.0. They
had to be adjusted upwards so that the actual taps (TAPnA) are 2.0 and 6.25. Per Equation 4-3, X is 0.8.
It is desired that the minimum pickup of the restrained element be 0.35 per unit on the circuit base. The
actual setting should be 0.35*0.8=0.28 to achieve the same sensitivity.
The pickup settings in Times Tap can be related to primary amps by Equation 4-4. Minpu is the minimum
pickup setting in Times Tap. The definitions for the remaining variables in Equation 4-4 are the same as
those for Equations 4-1 and 4-2.

TAPnI MVA * 1000 * COMPn Mpu * TAPn * CTRn


X= = Ipri =
TAPnA TAPnA * 3 * KVn * CTRn COMPn
Equation 4-3 Equation 4-4
Table 4-7. 87 Phase Differential Operational Settings
Setting Range Increment Unit of Default
Measure
Minimum Pickup (minpu) 0=disabled 0.01 Times tap 0
0.10 to 1.00
Slope (Maximum Restraint) 15 to 60 1 % I Operate
vs. Maximum 45
Restraint
(Average Restraint) 15A to 60A 1A % I Operate
vs. Average NA
Restraint
nd nd nd
2 Harmonic Inhibit (2 ) 0=disabled 0.5 % of 2 vs. 18
5.0 to 75.0 Fundamental
I Operate
th th
5 Harmonic Inhibit (5 ) 0=disabled 0.5 % of 5th vs. 35
5.0- to.0 Fundamental
I Operate
Unrestrained output pickup) (URO) 0=disabled 1 Times tap 10
0 to 21
nd nd
2 harmonic sharing between phases (2 0=independent NA NA 1
harmonic sharing) 1=shared
Maximum restraint uses the maximum of two compensated currents, and average restraint uses the aver-
age of the two compensated currents. For example: If maximum restraint is used (no A after the slope
percentage), the restraint current for phase A would be IRA = max(IA1COMP, IA2COMP). If average restraint is
used, (an A after the slope percentage), the restraint current for phase A would be given by Equation 4-5.

BE1-CDS Protection And Control 4-13


I +I
IRA = A1COMP A2COMP
2
Equation 4-5
The 87 phase differential operational settings may be entered from the optional front panel HMI from
screens 5.#.1.1 \PROT\SG#\87\87 or from the ASCII command interface using the S<g>-87 (settings
group number-87 phase protection) command.

S<g>-87 Command
Purpose: Protection Settings for 87 (transformer differential) function
nd
Syntax: S<g>-87 [ = <minpu>, <slope>,<2nd>,<5th>,<URO>,[<2 harmonic sharing>] ]
Comments: g = setting group number 0-3. Use # as wildcard to refer to all groups.
Example 1. Read 87 Settings for setting group 0 (0.5 time tap minimum pu, 60% slope using
maximum restraint, 12% second harmonic, 30% fifth harmonic, 18 times tap unrestrained
pickup, second harmonic sharing on)
>S0-87
0.5,60,12,30,18,1
>
Example 2. Set 87 settings group 0 for a minimum pickup of 0.35 per unit, slope of 35% using
average restraint, second harmonic setting of 18%, fifth harmonic setting of 35%,
unrestrained output of 12 times tap, second harmonic sharing off
>S0-87=0.35,35A,18,35,12,0
>
Retrieving Logic Output Status Information From the Relay
The status of each logic variable can be determined from the ASCII command interface using the RG-
STAT (report general-status) or the RL (report logic) commands. See Section 6, Reporting and Alarm
Functions, General Status Reporting for more information.

87ND Neutral Differential Function


When equipped with the optional independent ground input, BE1-CDS relays can provide sensitive
differential protection for ground faults on the grounded side of a delta/wye transformer. On an
impedance grounded system, ground fault levels may be reduced below the sensitivity of the phase
differential protection. The result is that ground faults within the protected zone have to be cleared by
time delayed backup overcurrent protection if sensitive differential protection is not available.
The function block in Figure 4-9 has two outputs: 87NDPU
(pickup) and 87NDT (trip). A Block logic input is provided to Mode =
block operation of the differential protection. When this 0-disable 87NDPU
expression is TRUE, the function is disabled. For example, 1- G vs. N1 PERCENT
this may be an input wired to a differential cutoff switch. 2- G vs. N2 NEUTRAL
DIFF 87NDT
To use this function, the relay must be equipped with the (87ND)
BLK
optional independent ground sensing input. IG is the zero
sequence current entering the zone of protection. Figure 4-10 D2840-25.vsd
02-01-99
shows the configuration of this protective function. The zero
sequence current exiting the zone of protection is the Figure 4-9. 87ND Neutral Differential
calculated neutral for the three-phase CT input circuit Function Block
designated by the BESTlogic mode setting.

NOTE
The CTs for this three-phase input circuit must be connected in wye with zero sequence
compensation for the grounded winding provided by internal delta compensation. If the
CTs are connected in delta to provide external zero sequence compensation, the
calculated 3I0 (neutral) current exiting the zone will always be zero since it is filtered out
by the CTs delta connection.

4-14 Protection And Control BE1-CDS


IO

IO

IO

IO IO IO
IOP
IR IR
3Io -3Io
Z0

3IO D2840-20.vsd
02-08-99

Figure 4-10. 87ND Polarity Configuration

These paragraphs discuss the details of how the function works and how to set it up. Figure 4-11 shows
a detailed functional block diagram of the neutral differential protection function. The measured ground
current and the neutral current are tap adjusted to eliminate magnitude mismatch. The Restraint Current
function determines the magnitude of the restraint current as the maximum of the compensated currents
in multiples of tap. The Operating Current function determines the magnitude of the differential current as
the phasor sum of the compensated currents.

Restraint Settable
Delay
Current Minimum
Pickup Slope 87ND
Restrained
TM Trip

Fundamental
Phasor

Fund
Restrained
Tap per unit Operating Fund Iop Element
Ground
Phasor
Adjustment Current 87ND Restrained Pickup

D2843-01.vsd
02-08-99

Figure 4-11. 87 Neutral Differential Protection Functional Block Diagram


The characteristic of the Restrained Element function is the same as that for the phase differential shown
in Figure 4-8 with the exception that maximum restraint is always used. This comparator has a slope
setting and a minimum pickup setting. The slope setting is the ratio of operate current to restraint current.
The minimum pickup setting determines the minimum sensitivity. If the ratio of operate current to restraint
current is above the slope setting and the operate current is above the minimum pickup setting, the
87NDPU (87 neutral element picked up) logic output is set.
A timer provides security from misoperation on false residual caused by CT saturation during a through
fault. If the transient monitor function from the 87 phase differential function detects CT saturation, the
87NDT trip logic output is routed through the timer. The timer should be set longer than the normal
clearing time for a fault just outside the zone of protection to allow it to ride-through until the external fault
is cleared.

BE1-CDS Protection And Control 4-15


If the target is enabled for this function, the target reporting function will record an 87ND target when the
87NDT logic output is TRUE and the fault recording function trip logic expression is TRUE. See Section 6
Reporting and Alarm Functions, Fault Reporting Functions for more details on the target reporting
function.

Setting BESTlogic, 87ND Neutral Differential Function Block


The logic settings for the 87ND Neutral Differential function are provided in Table 4-8. These settings will
enable the function block and provide blocking control as determined by the logic expression assigned to
the block input.
Table 4-8. 87ND Neutral Differential Function BESTlogic Settings
Function Range/Purpose Default
Logic Mode 0=Disabled, 1=IG vs. CT Input 1 Neutral, 0
2=IG vs. CT Input 2 Neutral *
Block Logic Input Logic expression. Disables function when TRUE 0
NOTE: * If the unit does not have an independent ground input, a NO GROUND CT PRESENT
error message will be returned if you try to set the mode to 1 or 2.

The BESTlogic settings can be made from the ASCII command interface using the SL-87ND (settings
logic-87 neutral differential) command.

SL-87ND Command
Purpose: Used to program a logical mode of operation for an 87ND protection block.
Syntax: SL-87ND[= <mode>,[<BLK logic>]]
Example 1. Read 87ND Logic Configurations (enabled IG vs. IN1, no blocking)
>SL-87ND
1,0
>
Example 2. Change 87 Logic to be blocked if input 1 is closed (TRUE)
>SL-87ND=1,IN1
>
Auto-Tap Compensation, 87 Neutral Differential Function
The tap adjustment factors are automatically calculated such that Equation 4-6 is TRUE. CTRn is the CT
ratio for the three-phase CT input circuit designated by the SL-87ND setting in the active logic. The CTR
settings are entered using the SG-CTn and SG-CTG settings. See Section 3, Input and Output
Functions, Current Measurement Functions for more details on these settings.
TAPN * CTRn = TAPG * CTRG
Equation 4-6
The CT input with the highest CTR is selected as the driving tap and set to the minimum setting (2.0 for 5
ampere units or 0.4 for 1 ampere units). Equation 4-6 is solved for the other tap. The currents can be tap
adjusted up to a spread ratio of 10:1. If the ratio between TAPN and TAPG is greater than 10, it will be
necessary to adjust CT ratios to bring the tap factors closer together. The relay will give an error
message if the spread ratio is greater than 10.

NOTE
Since the calculated neutral used by the 87ND function is designated by BESTlogic, you
may get an auto-tap error when changing the 87ND logic setting in the user program-
mable logic settings.

The tap factors calculated by the auto-tap calculation feature can be determined in several ways. They
are displayed on the optional HMI using screen 5.#.2.1, \PROT\SG#\87ND\87ND. Or, the current check
record provided by the differential alarm function includes a listing of the compensation parameters in the
setting group that was active at the time that the record was triggered. See Section 6, Reporting and
Alarm Function, Differential Alarm for more details on this report.

4-16 Protection And Control BE1-CDS


Setting Operational Settings, 87ND Neutral Differential Function
The operating parameter settings for the 87ND Neutral Differential function are provided in Table 4-9.
The minimum pickup is set in multiples of tap. Equation 4-7 can be used to convert the Minpu setting to
primary current. The 87ND auto-tap calculation routine uses the minimum allowable taps to allow the
minimum pickup to be set to allow maximum sensitivity to ground faults.
Ipri = Minpu * TAPn * CTRn
Equation 4-7
Table 4-9. 87ND Neutral Differential Operational Settings
Setting Range Increment Unit of Measure Default
Minimum 0=disabled 0.01 Times tap 0
Pickup (minpu) 0.10-1.00
Slope 15-60 1 % I Operate vs. 20
Restraint
Time Delay 50-999 ms 1m milliseconds 500
0.05-60 sec 0.1 for 0.1-9.9 sec seconds
1.0 for 10-60 sec seconds
0-3600 (60 Hz) or 0-2500 (50 Hz) * cycles
NOTE * Time delays less than 10 cycles can be entered to the nearest 0.1 cycle from the optional HMI.
All time delays can be entered to the nearest 0.01 cycle from the ASCII command interface.
Time delays entered in cycles are converted to milliseconds or seconds. Increment precision
after conversion is limited to that appropriate for each of those units of measure.
The 87ND neutral differential operational settings may be entered from the optional front panel HMI from
screens 5.#.2.1, \PROT\SG#\8ND7\87ND or from the ASCII command interface using the S<g>-87ND
command.

S<g>-87ND Command
Purpose: Protection Settings for 87ND (neutral differential) function
Syntax: S<g>-87ND [ = <minpu>, <slope>,<time delay[units]>]
Comments: g = setting group number 0-3. Use # as wildcard to refer to all groups.
units = m for milliseconds (default)
s for seconds
c for cycles
Example 1. Read 87ND Settings for setting group 0 (0.35 times tap min pu, 45% slope, 500 ms
delay)
>S0-87ND
0.35,45,500
>
Example 2. Set 87 settings group 0 for a minimum pickup of 0.50 times tap, slope of 35%, delay of
500 mSec.
>S0-87ND=0.50,35,500
>
Retrieving Logic Output Status Information From the Relay
The status of each logic variable can be determined from the ASCII command interface using the RG-
STAT (report general-status) or the RL (report logic) commands. See Section 6, Reporting and Alarm
Functions, General Status Reporting for more information.

OVERCURRENT PROTECTION

50T Instantaneous Overcurrent With Settable Delay Functions


There are three independent function blocks for phase (50TP, 150TP, 250TP), three for neutral (50TN,
150TN, 250TN), and three for negative sequence (50TQ, 150TQ, 250TQ) instantaneous overcurrent
protection. Each function block can be attached to any of the CT input circuits by the BESTlogic mode
setting. The instantaneous overcurrent protective functions in the BE1-CDS relay are labeled 50T

BE1-CDS Protection And Control 4-17


because each has a settable time delay. If the time delay is set to zero, they operate as instantaneous
overcurrent relays.
Figure 4-12 shows the 50TP phase instantaneous over-
current as a typical 50T function. Each of the nine Mode =
0-disable 50TPT
independent functions has two logic outputs: #50TnPU 1-ct ckt 1
(picked up) and #50TnT (trip) where n indicates whether it is 2-ct ckt 2 SL-50TP 50TPPU
a P (phase), N (neutral), or Q (negative sequence) and the LOGIC
#50 differentiates between the three protective functions (50, BLK
D2843-02.vsd
07-24-00
150, or 250).
A Block logic input is provided to each function and can be Figure 4-12. Typical 50T Overcurrent
used to disable the function. When this expression is TRUE, Function
the function is disabled by forcing the outputs to logic zero
and resetting the timers to zero. For example, this could be used similar to a torque control contact on an
electromechanical relay.
Each instantaneous overcurrent function has a pickup and a time delay setting. When the measured
current is above the pickup threshold, the pickup logic output, 50TPPU (for example) = TRUE and the
timer is started. If the current stays above pickup for the time delay, the trip logic output, 50TPT (for
example) = TRUE. If the current falls below the dropout ratio, which is 95%, the timer is reset to zero.
The phase overcurrent protective functions include three independent comparators and timers, one for
each phase. If the current is above the pickup setting for any one phase, the pickup logic output is
asserted and if the trip condition is TRUE for any one phase, the trip logic output is asserted.
If the target is enabled for the function, the target reporting function will record a target for the appropriate
phase when the protective function trip output is TRUE and the fault recording function trip logic
expression is TRUE. See Section 6, Reporting and Alarm Functions, Fault Reporting Functions for more
details on the target reporting function.

Setting BESTlogic, 50T Overcurrent Functions


The logic settings for the 50T Instantaneous overcurrent with settable time delay functions are provided in
Table 4-10. These settings will enable the function by attaching it to one of the CT input circuits and
provide blocking control as determined by the logic expression assigned to the block input.
Table 4-10. 50T Overcurrent Function BESTlogic Settings
Function Range/Purpose Default
Logic Mode 0=Disabled, 1=CT Input Circuit 1, 0
2=CT input Circuit 2,
G=Independent Ground Input (#50TN functions only) *
Block Logic Input Logic expression. Disables function when TRUE 0

The BESTlogic settings can be made from the ASCII command interface using the SL-50T/SL-150T/SL-
250T (settings logic-50T) commands.

SL-50T/150T/250T Command
Purpose: Used to program a logical mode of operation for a 50T protection block.
Syntax: SL-50T[n][= <mode>, <BLK logic>]
SL-150T[n][= <mode>, <BLK logic>]
SL-250T[n][= <mode>, <BLK logic>]
Comments: n = element type P/N/Q. If type is left out then all is assumed.
Example 1. Read Logic for 50T phase element (enabled with no blocking)
>SL-50TP
1,0
>
Example 2. Change 50TN Logic to select a ground CT and to be blocked if input 1 is closed (TRUE).
>SL-50TN = G, IN1
>

4-18 Protection And Control BE1-CDS


NOTE
If the unit has five ampere phase inputs and a one ampere independent ground input, the
valid pickup setting range of the neutral overcurrent functions will be dependent upon the
logic mode setting which designates whether the three-phase residual or the independent
ground input is to be monitored. If changing logic schemes or settings causes a neutral
overcurrent setting to be OUT OF RANGE, the out of range setting will be forced in-range
by multiplying or dividing the current setting by five.

Setting Operational Settings, 50T Overcurrent Functions


The operating parameter settings for the 50T overcurrent functions are provided in Table 4-11.
The time delays can be set in milliseconds, seconds, or cycles. The default is milliseconds if no unit of
measure is specified. The minimum resolution of the timing is to the nearest one-quarter cycle. A time
delay setting of zero makes the element instantaneous with no intentional time delay.
If the time delay settings are made in cycles, they are converted to seconds or milliseconds (per the
nominal frequency setting stored in EEPROM) before being stored. See Section 3, Input and Output
Functions, Current Measurement Functions for more information on this setting. If the user is changing
the nominal frequency setting from the default (60 hertz) and setting the time delays in cycles, the
frequency setting should be entered and saved to EEPROM first by entering E; Y.
See Negative Sequence Overcurrent Protection later in this section for information on setting the negative
sequence overcurrent protection.
Table 4-11. 50T Overcurrent Function Operational Settings
Setting Range Increment Unit of Default
5A 1A Measure
Pickup (pu) 0 = disabled 0 = disabled 0.01 for 0.01 to 9.99 Sec. Amps 0
0.5 to 150 0.1 to 30 0.1 for 10.0 to 99.9
1.0 for 100 to 150
Time Delay (td) 0 to 999 ms 1m milliseconds 0
0.1 to 60 sec. 0.1 for 0.1 to 9.9 sec seconds
1.0 for 10 to 60 sec seconds
0 to 3600 (60 Hz) or 0 to 2500 (50 Hz) * cycles
NOTE; *Time delays less than 10 cycles can be entered to the nearest 0.1 cycle from the
optional HMI. All time delays can be entered to the nearest 0.01 cycle from the ASCII
command interface. Time delays entered in cycles are converted to milliseconds or
seconds. Increment precision after conversion is limited to that appropriate for each of
those units of measure.

The 50T overcurrent operational settings may be entered from the optional front panel HMI from screens
5.#.3.1 to 5.#.3.3, \PROT\SG#\50T\50T, \PROT\SG#\50T\150T, \PROT\SG#\50T\250T, or from the
ASCII command interface using the S<g>-50T/150T/250T (settings group #-50T/150T/250T) command.

NOTE
When changing settings with the relay in service, an error message (PU TOO LOW) will
be generated if the new setting is within approximately 90% of the metered current level.
This is intended to prevent the user from inadvertently causing a trip when changing a
setting.

S<g>-50T/150T/250T Command
Purpose: Protection Settings for first 50T (instantaneous overcurrent) function
Syntax: S<g>-50T[n] [ = <pu>, <td [units] >]
S<g>-150T[n] [ = <pu>, <td [units] >]
S<g>-250T[n] [ = <pu>, <td [units] >]
Comments: g = setting group number 0-3. Use # as wildcard to refer to all groups.
n = element type P/N/Q. If type is left out then all is assumed.
units = m for milliseconds (default)
s for seconds
c for cycles

BE1-CDS Protection And Control 4-19


Example 1. Set phase setting for 50T element for group 0 to 25A, 0 millisecond delay
>S0-50TP=25,0
>
Example 2. Disable 150T P/N/Q functions for setting groups 1, 2 and 3.
>S1-150T=0; S2-150T=0; S3-150T=0
>
Example 3. Set 250TQ function for all setting groups to 2A, 10 seconds
>S#-250TQ=2,10s
>
Retrieving Logic Output Status Information From the Relay
The status of each logic variable can be determined from the ASCII command interface using the RG-
STAT (report general-status) or the RL (report logic) commands. See Section 6, Reporting and Alarm
Functions, General Status Reporting for more information.

51 Time Overcurrent Functions


There are three independent functions for phase (51P, 151P, 251P), three for neutral (51N, 151N, 251N),
and three for negative sequence (51Q, 151Q, 251Q) inverse time overcurrent protection. Each function
can be attached to any of the CT input circuits by the BESTlogic mode setting.
Figure 4-13 shows the 51P (phase time overcurrent) as a typical 51
function. Each of the nine independent functions has two logic Mode =
outputs #51nPU (picked up) and #51nT (trip) where n indicates 0-disable 51PT
1-ct ckt 1
whether it is a P (phase), N (neutral), or Q (negative sequence) and 2-ct ckt 2 SL-51P 51PPU
the # differentiates between the three protective functions (51, 151, LOGIC
or 251). BLK
D2843-03.vsd
07-24-00
A Block logic input is provided to each function that can be used to
disable the function. When this expression is TRUE, the function is Figure 4-13. Typical 51 Time-
disabled by forcing the outputs to logic zero and resetting the timers Overcurrent Function
to zero. For example, this could be used similar to a torque control
contact on an electromechanical relay.
Each inverse time overcurrent function has a pickup, a time dial, and a curve setting. See Appendix A,
Time Current Characteristics for details on each of the curves available. To make the protective element
use integrated reset and emulate an electromechanical induction disk reset characteristic, the user can
append an R to the selected time current characteristic curve. A programmable curve is available that
can be used to create a custom curve by selecting coefficients in the inverse time characteristic equation.
When the measured current is above the pickup threshold, the pickup logic output, 51PPU (for example)
= TRUE and inverse timing is started per the selected characteristic. If the current stays above pickup
until the function times out, the trip logic output, 51PT (for example) = TRUE. If the current falls below the
dropout ratio, which is 95%, the function will either reset instantaneously or begin timing to reset
depending on the user’s setting.
The phase overcurrent protective functions use the highest of the three measured phase currents. If the
current is above the pickup setting for any one phase, the pickup logic output is asserted. If the trip
condition is TRUE, the trip logic output is asserted.
If the target is enabled for the function block, the target reporting function will record a target for all
phases that are above pickup when the protective function trip output is TRUE and the fault recording
function trip logic expression is TRUE. See Section 6, Reporting and Alarm Functions, Fault Reporting
Functions for more details on the target reporting function.

Setting BESTlogic, 51 Time Overcurrent Function Blocks


The logic settings for the 51 inverse time overcurrent functions are provided in Table 4-12. These
settings will enable the function by attaching it to one of the CT input circuits and provide blocking control
as determined by the logic expression assigned to the block input.

4-20 Protection And Control BE1-CDS


Table 4-12. 51 Time Overcurrent Function BESTlogic Settings
Function Range/Purpose Default
Logic Mode 0=Disabled, 1=CT Input Circuit 1, 0
2=CT input Circuit 2,
G=Independent Ground Input (#51N functions only) *
Block Logic Input Logic expression. Disables function when TRUE 0
The BESTlogic settings can be made from the ASCII command interface using the SL-51/SL-151/SL-251
(settings logic-51) commands.

SL-51/151/251 Command
Purpose: Used to program a logical mode of operation for a 51 protection block.
Syntax: SL-51[n][= <mode>, <BLK logic>]
SL-151[n][= <mode>, <BLK logic>]
SL-251[n][= <mode>, <BLK logic>]
Comments: n = element type P/N/Q. If type is left out then all is assumed.
Example 1. Read Logic for all 51 functions <all are enabled on CT circuit 1 with no blocking >
>SL-51
SL-51P=1,0; SL-51N=1,0; SL-51Q=1,0
>
Example 2. Change 51N Logic to select a ground CT and to be blocked if input 1 is closed (TRUE).
>SL-50TN = G, IN1
>
NOTE
If the unit has five ampere phase inputs and a one ampere independent ground input, the
valid pickup setting range of the neutral overcurrent functions will be dependent upon the
logic mode setting which designates whether the three-phase residual or the independent
ground input is to be monitored. If changing logic schemes or settings causes a neutral
overcurrent setting to be OUT OF RANGE, the out of range setting will be forced in-range
by multiplying or dividing the current setting by five.

Setting Operational Settings, 51 Time Overcurrent Functions


The operating parameter settings for the 51 overcurrent functions are provided in Table 4-13.
See Negative Sequence Overcurrent Protection later in this Section for information on setting the
negative sequence overcurrent protection.
Table 4-13. 51 Time Overcurrent Function Operational Settings
Setting Range Increment Unit of Default
5A 1A Measure
Pickup (pu) 0 = disabled 0 = disabled 0.01 for 0.01 to 9.99 Sec. Amps 0
0.5 to 16 0.1 to 3.2 0.1 for 10.0 to 16.0
Time Dial (td) 0.0 to 9.9 0.1 NA 0
Curve (crv) See Appendix A NA NA V2
The 51 overcurrent operational settings may be entered from the optional front panel HMI from screens
5.#.4.1 to 5.#.4.3, \PROT\SG#\51\51, \PROT\SG#\51\151, \PROT\SG#\51\251 or from the ASCII
command interface using the S<g>-51/151/251 (settings group number, 51/151/251) command.

NOTE
When changing settings with the relay in service, an error message (PU TOO LOW) will
be generated if the new setting is within approximately 90% of the metered current level.
This is intended to prevent the user from inadvertently causing a trip when changing a
setting.

BE1-CDS Protection And Control 4-21


S<g>-51/151/251 Command
Purpose: Protection Settings for first 50T (instantaneous overcurrent) function
Syntax: S<g>-51[n] [ = <pu>, <td>, <crv>]
S<g>-151[n] [ = <pu>, <td>, <crv>]
S<g>-251[n] [ = <pu>, <td>, <crv>]
Comments: g = setting group number 0-3. Use # as wildcard to refer to all groups.
n = element type P/N/Q. If type is left out then all is assumed.
Example 1. Read 51 setting data for neutral element in setting group 0. (pickup = 10 amps, Time
Dial = 2.4, Curve is S1 with integrating reset)
>S0-51N
10,2.4,S1R
>
Example 2. Change 51 setting data for neutral element in setting group 0 to make the time dial
setting 3.0
>S0-51N=,3.0
>
Example 3. Disable all negative sequence time overcurrent functions in all settings groups by setting
the pickup to 0
>S#-51Q=0; S#-151Q=0; S#-251Q=0
>
Setting Programmable Time Current Characteristic Curve Coefficients
The time current characteristics for trip and reset are defined by Equation 4-8 and Equation 4-9
respectively. These equations comply with IEEE standard C37.112-1996. The curve specific coefficients
are defined for the standard curves as listed in Appendix A, Time Current Characteristics. When the user
selects time current characteristic curve P, the coefficients used in the equation are those defined by the
user. Definitions for Equations 4-8 and 4-9 are provided in Table 4-14.
AD RD
TT = N
+ BD + K TR =
M −C M2 − 1
Equation 4-8 Equation 4-9

Table 4-14. Definitions for Equations 4-8 and 4-9


Parameter Description Explanation
TT Time to Trip Time that the 51 function will take to time out and trip.
D Time Dial Setting Time dial setting for the 51 function.
M Multiple of pickup Measured current in multiples of pickup. Timing algorithm has a
dynamic range of 0 to 40 time pickup.
A Coefficient specific to Affects the effective range of the time dial.
selected curve
B Coefficient specific to Affects a constant term in the timing equation. Has greatest
selected curve affect on curve shape at high multiples of tap.
C Coefficient specific to Affects the multiple of PU where the curve would approach
selected curve infinity if allowed to continue below pickup. Has greatest affect
on curve shape near pickup.
N Exponent specific to Affects the inverseness of the characteristic. Has greatest
selected curve affect on curve shape at low to medium multiples of tap.
K Constant Characteristic minimum delay term
TR Time to reset Relevant if 51 function is set for integrating reset.
R Coefficient specific to Affect the speed of reset when integrating reset is selected
selected curve

4-22 Protection And Control BE1-CDS


Curve coefficients can be entered from the ASCII command interface using the SP-CURVE (Settings
Protection-programmable curve) command. Table 4-15 shows the programmable curve settings.
Table 4-15. Programmable Time Current Characteristic Curve Coefficients
Setting Range Increment Unit of Default
Measure
A Coefficient 0 to 600 0.0001 NA 0.2663
B Coefficient 0 to 25 0.0001 NA 0.0339
C Coefficient 0.0000 to 1.0000 0.0001 NA 1.0000
N Exponent 0.5 to 2.5 0.0001 NA 1.2969
R Coefficient 0 to 30 0.0001 NA 0.5000

SP-CURVE Command
Purpose: Reads or changes the user programmable 51 curve parameters.
Syntax: SP-CURVE [= <A>, <B>, <C>, <N>, <R>]
Example 1. Read the programmable 51 curve settings :
>SP-CURVE
1,0,0,2,0
>
Retrieving Logic Output Status Information From the Relay
The status of each logic variable can be determined from the ASCII command interface using the RG-
STAT (report general-status) or the RL (report logic) commands. See Section 6, Reporting And Alarm
Functions, General Status Reporting for more information.

Negative Sequence Overcurrent Protection


For years, protection engineers have enjoyed increased sensitivity to phase-to-ground unbalances with
the application of ground relays. Ground relays can be set more sensitively than phase relays because a
balanced load has no ground (3I0) current component. The negative sequence elements can provide
similar increased sensitivity to phase-to-phase faults because a balanced load has no negative sequence
(I2) current component.

Negative Sequence Pickup Settings


A typical setting for the negative sequence elements might be one-half the phase pickup setting in order
to achieve equal sensitivity to phase-to-phase faults as to three-phase faults. This number comes from
the fact that the magnitude of the current for a phase-to-phase fault is √3/2 (87%) of the three-phase fault
at the same location. This is illustrated in Figure 4-14.
The phase-to-phase fault current is made up of both positive and negative sequence components as
shown in Figure 4-15. For a phase-to-phase fault, the magnitude of the negative sequence component is
1/√3 (58%) of the magnitude of the total phase current. When these two factors (√3/2 and 1/√3) are
combined, the √3 factors cancel, which leaves the one-half factor.

BE1-CDS Protection And Control 4-23


Z
I3 P h F A U L T
V
I3 P h F A U L T = V
Z

Z
D2843-04.vsd
02-08-99

Z
IP h - P h F A U L T
V
IP h - P h F A U L T = V* √3 = I3 P h F A U L T* √3
Z *2 2

Figure 4-14. Phase-to-Phase Fault Magnitude

D2843-05.vsd
02-02-99
IC 1
IB 2 IA2 = |I2 | = IA Phase/ √3

IB P h a s e IA P h a s e

IB 1 IA 1
IC 2
IC P h a s e = 0

Pos. Seq. (I1 ) Neg. Seq. (I2 ) Phase Current

Figure 4-15. Sequence Components For An A-B Fault

Negative Sequence Coordination Settings


The 51Q settings should be checked for coordination with phase-only sensing devices such as
downstream fuses and reclosers and/or ground relays. To plot the negative sequence time current
characteristics on the same plot for the phase devices, you need to multiply the negative sequence
element pickup value by the correct multiplier. The multiplier is the ratio of phase current to negative
sequence current for the fault type for which you are interested. To plot the negative sequence time
current characteristics on the same plot for the ground devices, you need to multiply the pickup value by
the multiplier for phase-to-ground faults.
Fault Type Multiplier
Ph-Ph m = 1.732
Ph-Ph-G m > 1.732
Ph-G m=3
3-Phase m = Infinity

4-24 Protection And Control BE1-CDS


For example, a downstream phase 51 element has a pickup of 150 amperes. The upstream 51Q element
has a pickup of 200 amperes. To check the coordination between these two elements for a phase-to-
phase fault, the phase overcurrent element would be plotted normally with pickup at 150 amperes. The
51Q element would be shifted to the right by the appropriate factor m. Thus, the characteristic would be
plotted on the coordination graph with pickup at: (200 amperes)*1.732 = 346 amperes.
Generally, for coordination with downstream phase overcurrent devices, phase-to-phase faults are the
most critical to consider. All other fault types result in an equal or greater shift of the time current
characteristic curve to the right on the plot.

Delta/Wye Transformer Application.


Often, the phase relays on the delta side of a delta/wye transformer must provide backup protection for
faults on the wye side. For faults not involving ground, this is not a problem since the phase relays will
see 1.0 per unit fault current for three-phase faults and 2/√3 (1.15) per unit fault current for phase-to-
phase faults. However, for faults involving ground, the sensitivity is reduced because the zero sequence
components are trapped in the delta and not seen by the delta-side phase relays. The phase relays will
see only 1/√3 (0.577) per unit current for phase-to-ground faults.
Negative sequence overcurrent protection is immune to the effect caused by the zero sequence trap and
30° phase shift provided by the delta/wye transformer. For a phase-to-ground fault, the magnitude of the
negative sequence components is 1/3 the magnitude of the total fault current. On a per unit basis, this is
TRUE for the fault current on the delta side of the transformer as well. (The previous statement specifies
per unit since the actual magnitudes will be adjusted by the inverse of the voltage ratio of the delta/wye
transformer.) Thus, backup protection for phase-to-ground faults on the wye side of the transformer can
be obtained by using negative sequence overcurrent protection on the delta side with the pickup
sensitivity set at 1/3 per unit of the magnitude of the phase-to-ground fault for which you wish to have
backup protection.

BF BREAKER FAILURE PROTECTION


BE1-CDS relays provide one function for breaker BFT
Mode =
failure protection. This function includes a timer and 0-disable
a current detector. The current detector can be 1-ct ckt 1 BFPU
attached to any of the three-phase CT input circuits 2-ct ckt 2 BREAKER
by the BESTlogic mode setting. Figure 4-16 shows FAILURE
INI
the BF function. It is recommended that the CT (BF)
input circuit used by the breaker failure function be
connected to CTs mounted directly on the protected BLK D2843-27.vsd
breaker. The function has two outputs: BFPU 07-24-00

(breaker failure pickup) and BFT (breaker failure Figure 4-16. Breaker Failure Function
trip).
An INI (Initiate) logic input is provided to start the breaker failure timer. When this expression is TRUE
and current is flowing in the assigned input circuit, the breaker failure timer is started. Supervision of the
initiate signal can be designed in BESTlogic. Once the breaker failure timer is started, the initiate signal
does not have to remain TRUE.
A Block logic input is provided to block operation of the breaker failure protection. When this expression
is TRUE, the function is disabled. For example, this may be an input wired to a test switch such that
breaker failure protection is disabled when the primary protective elements are being tested to prevent
inadvertent backup tripping during testing.
The breaker failure timer is stopped by the fast-dropout current detector function. See Section 3, Input
and Output Functions, Current Measurement Functions for more details on this function. The fast-dropout
current detector is designed to directly determine when the current in the poles of the breaker has been
interrupted without having to wait for the fault current samples to clear the one-cycle filter time used by
the normal current measurement function. This function has less than one cycle dropout time. The timer
can also be stopped by the block logic input being asserted.
The current detector sensitivity is fixed at 10% nominal. A traditional breaker failure relay includes a fault
detector function which serves two independent purposes: current detector and fault detector. A current
detector is generally included to determine that the current has been successfully interrupted in all poles

BE1-CDS Protection And Control 4-25


of the breaker to stop breaker failure timing. The secondary function of a traditional fault detector is to
provide an independent confirmation that a fault exists on the system to increase security from
misoperation caused by an inadvertent initiate signal. To do this, a fault detector by definition must be set
above load current—reducing it’s sensitivity as a current detector. Since this breaker failure timer is
included in a multifunction protection system, fault detector supervision is not required.
If you are using external relays to initiate the breaker failure timer, it may be desirable to include fault
detector supervision of the initiate signal using an instantaneous overcurrent function in BESTlogic. For
example, if it is desired that certain initiate signals be supervised by a fault detector, it is possible to AND
them with one of the 50T protective functions using a virtual output expression. In other applications, it
may be desirable to have breaker failure timing with no current detector supervision. In this case, one of
the general purpose logic timers (device 62) can be used as a breaker failure timer. See Section 8,
Application, Application Tips for more details on this application.
When the breaker failure timer is picked up, the BFPU logic output is TRUE. This output would typically
be used as a re-trip signal to the protected breaker. This can provide an independent tripping signal to
the breaker that may also open the breaker to prevent backup tripping.
If the current detector remains picked up for the duration of the breaker failure delay time, the BFT output
is asserted. This output would normally be used to trip an 86F lockout relay which will trip and prevent
closing of adjacent breakers and/or key transfer trip transmitters.
If the target is enabled for the function, the target reporting function will record a target when the
protective function trip output is TRUE and the fault recording function trip logic expression is TRUE. See
Section 6, Reporting and Alarm Functions, Fault Reporting Functions for more details on the target
reporting function.
An alarm variable is also provided in the programmable alarms function that can be used to indicate an
alarm condition when the breaker failure protection trips. See Section 6, Reporting and Alarm Functions,
Alarms Function for more details on the alarm reporting function.

Setting BESTlogic, Breaker Failure Function


The logic settings for the Breaker Failure function are provided in Table 4-16. These settings will enable
the function by attaching it to one of the CT input circuits and provide initiate and blocking control as
determined by the logic expressions assigned to those inputs.
Table 4-16. BF Breaker Failure Function BESTlogic Settings
Function Range/Purpose Default
Logic Mode 0=Disabled, 1=CT Input Circuit 1, 2=CT Input Circuit 2, 0
INI (Initiate) Logic Input Logic expression. Starts the BF timer when TRUE and 0
current is flowing in the assigned input circuit
Block Logic Input Logic expression. Disables function when TRUE 0

The BESTlogic settings can be made from the ASCII command interface using the SL-BF (settings logic-
Breaker Failure) commands.

SL-BF Command
Purpose: Used to program a logical mode of operation for the Breaker Failure protection block.
Syntax: SL-BF[= <mode>, <INI logic>, <BLK logic>]
Example 1. Read 50BF Logic (enabled winding 1, initiate controlled by input 4 and no blocking)
>SL-BF
1,IN4,0
>
Example 2. Change BF Logic to initiate if the TRIP output closes (VO1=1).
>SL-BF=,VO1
>

4-26 Protection And Control BE1-CDS


Setting Operational Settings, Breaker Failure Function
The operating parameter settings for the breaker failure function are provided in Table 4-17. This setting
is not included in the four setting groups.
The time delays can be set in milliseconds, seconds, or cycles. The default is milliseconds if no unit of
measure is specified. The minimum resolution of the timing is to the nearest quarter-cycle. A time delay
setting of 0 makes the element instantaneous with no intentional time delay.
If the time delay settings are made in cycles, they are converted to seconds or milliseconds before being
stored. This conversion is based on the nominal frequency setting stored in EEPROM. See Section 3,
Input and Output Functions, Current Measurement Functions for more information on this setting. If the
user is changing the nominal frequency setting from the default (60 Hz) and setting the time delays in
cycles, the frequency setting should be entered and saved to EEPROM first by entering E; Y.
Table 4-17. BF Breaker Failure Function Operational Settings
Setting Range Increment Unit of Default
Measure
Time Delay (td) 0 = disabled 0
50 to 999 ms 1m milliseconds
0.05 to 0.999 sec. 0.1 sec seconds
0 to 59.96 (60 Hz) or 0 to 49.97 (50 Hz) * cycles
NOTE: * Time delays less than 10 cycles can be entered to the nearest 0.1 cycle from the
optional HMI. All time delays can be entered to the nearest 0.01 cycle from the ASCII
command interface. Time delays entered in cycles are converted to milliseconds or
seconds. Increment precision after conversion is limited to that appropriate for each of
those units of measure.

The BF (breaker failure) setting may be entered from the optional front panel HMI from screen 5.5.1,
\PROT\GLOB\BF, or from the ASCII command interface using the SP-BF (settings protection-breaker
failure) command.

SP-BF Command
Purpose: Read/Set the breaker failure timer setting
Syntax: SP-BF[=<td [units] >]
Comments: units = m for milliseconds (default)
s for seconds
c for cycles
Example 1. Set BF time delay to 10 cycles
>SP-BF=10c
>
Example 2. Read breaker failure time delay setting after setting it in example 1. (Nominal frequency
is set to 60 hertz.)
>SP-BF
167m
>
Retrieving Logic Output Status Information From the Relay
The status of each logic variable can be determined from the ASCII command interface using the RG-
STAT (report general-status) or the RL (report logic) commands. See Section 6, Reporting and Alarm
Functions, General Status Reporting for more information.

BE1-CDS Protection And Control 4-27


62/162 GENERAL PURPOSE LOGIC TIMER FUNCTIONS
BE1-CDS relays provide two general purpose logic timers which are
extremely versatile. Each can be set for one of five modes of Mode =
0-disable
operation to emulate virtually any type of timer. Each function has one 1-pickup/dropout
output, 62 or 162, that is asserted when the timing criteria has been 2-1shot nonretrig
met according to the BESTlogic mode setting. Figure 4-17 shows the 3-1shot retrig
4-oscillator
62 function as an example. Each mode of operation is described in 5-integrating
62
62
TIMER
detail in the following paragraphs. 6-latch

An INI (Initiate) logic input is provided to start the timing sequence. INI

BLK
A Block logic input is provided to block operation of the timer. When D2843-07.vsd
11-01-99

this expression is TRUE, the function is disabled.


Each timer has a t1 time setting and a t2 time setting. The functioning
of these settings is dependent upon the type of timer as specified by Figure 4-17. 62/162 General
the mode setting in BESTlogic. Purpose Logic Timer Function

If the target is enabled for the function, the target reporting function will record a target when the timer
output is TRUE and the fault recording function trip logic expression is TRUE. See Section 6, Reporting
and Alarm Functions, Fault Reporting Functions for more details on the target reporting function.

Mode 1, Pickup/Dropout Timer


The output will change to a logic TRUE if the initiate input expression is TRUE for the duration of PICKUP
time delay setting t1 (see Figure 4-18). If the initiate expression toggles to FALSE before time t1, the t1
timer is reset. Once the output of the timer toggles to TRUE, the initiate input expression must be FALSE
for the duration of DROPOUT time delay setting t2. If the initiate expression toggles to TRUE before time
t2, the output stays TRUE and the t2 timer is reset.
1 D2843-08.vsd 1 D2843-09.vsd
BLK 02-02-99 BLK 02-02-99
0 0

1 1
INI INI
0 0

1 1
x62 X x62
t1 t1 t2 t1 t2
0 0

Figure 4-18. Mode 1, Figure 4-19. Mode 2,


Pickup/Dropout Timer One-Shot Nonretriggerable Timer

Mode 2, One-Shot Nonretriggerable Timer


A one-shot timer starts its timing sequence when the initiate expression changes from FALSE to TRUE.
The timer will time for DELAY time t1 and then the output will toggle to logic TRUE for DURATION time t2
(see Figure 4-19). Additional initiate input expression changes of state will be ignored until the timing
sequence has been completed. If the duration time (t2) is set to 0, this timer will not function.

Mode 3, One-Shot Retriggerable Timer


D2843-10.vsd
1
02-02-99
This mode of operation is similar to Mode 2 except BLK
0
that if a new FALSE-to-TRUE transition occurs on the
initiate input expression, the output is forced to logic 1
INI
FALSE and the timing sequence is restarted (see 0
Figure 4-20). 1 t1 t1 t1
X
x62 X X
t1 t2 t2
0

Figure 4-20. Mode 3,


One-Shot Retriggerable Timer

4-28 Protection And Control BE1-CDS


Mode 4 Oscillator
1 D2843-11.vsd
In this mode, the INI input (Figure 4-21) is ignored. If BLK 02-02-99
0
the BLK input is FALSE, the output, #62, oscillates
with an ON time of t1 and an OFF time of t2. When 1
INI DON'T CARE
the BLK input is held TRUE, the oscillator stops and 0
the output is held OFF. 1
x62 t2
t1
Mode 5, Integrating Timer 0

An integrating timer is similar to a pickup/dropout Figure 4-21. Mode 4, Oscillator


timer except that the PICKUP time t1 defines the rate
that the timer integrates towards timing out and
setting the output to TRUE. Conversely, the RESET 1 D2843-12.vsd
BLK 02-02-99
time t2 defines the rate that the timer integrates 0
towards dropout and resetting the output to FALSE. 1
INI
The PICKUP time t1 defines the time delay for the
0
output to change to TRUE if the initiate input
becomes TRUE and stays TRUE. The RESET time 100%
t1

t2
t2 defines the time delay for the output to change to

t2
Timer t1
FALSE if it is presently TRUE and the initiate input 0%
becomes FALSE and stays FALSE. 1
x62
In the example shown in Figure 4-22, RESET time t2 0
is set to half the time as PICKUP time t1. The initiate Figure 4-22. Mode 5,
input expression becomes TRUE and the timer starts Integrating Timer
integrating towards pickup. Prior to timing out, the
initiate expression toggles to FALSE and the timer
starts resetting at twice the rate as it was integrating towards time out. It stays FALSE long enough for
the integrating timer to reset completely; but, then toggles back to TRUE and stays TRUE for the entire
duration of time t1. At that point, the output of the timer is toggled to TRUE. Then at some time later, the
initiate expression becomes FALSE and stays FALSE for the duration of RESET time t2. At that point,
the output of the timer is toggled to FALSE.
This type of timer is useful in applications where a monitored signal may be hovering at its threshold
between on and off. For example, it is desired to take some action when current is above a certain level
for a certain period of time. A 50T function could be used to monitor the current level. Thus, if the current
level is near the threshold so that the initiate toggles between TRUE and FALSE from time to time, the
function will still time out as long as the time that it is TRUE is longer than the time that it is FALSE. With
a simple PU/DO timer, the timing function would reset to zero and start over each time the initiate
expression became FALSE.

Mode 6, Latch
This type of timer is useful in applications where the 1
BLK
output contacts are to be latched until a reset input is 0
received. A one-shot timer starts the timing sequence
when the initiate expression changes from FALSE to 1
D2843-26.vsd
INI
TRUE. The timer will time for delay time t1 and then 0
07-25-00

the output contacts change to a TRUE state (see


Figure 4-23). Additional initiate input expression 1
t1
x62
changes of state are ignored. Time t2 is also ignored. 0
When the BLK input pulses TRUE, the output latch is
reset and the output changes to FALSE. For an Figure 4-23. Mode 6, Latch
instantaneous latch, set t1 to zero time delay.

Setting BESTlogic, 62/162 General Purpose Logic Timer Function Blocks


The logic settings for the 62/162 general purpose logic timer functions are provided in Table 4-18. These
settings will enable the function block by selecting the mode of operation and providing initiate and
blocking control as determined by the logic expressions assigned to those inputs.

BE1-CDS Protection And Control 4-29


Table 4-18. 62/162 General Purpose Logic Timer BESTlogic Settings
Function Range/Purpose Default
Logic Mode 0=Disabled, 1=PU/DO, 2=One Shot Nonretriggerable, 0
3=One Shot Retriggerable, 4=Oscillator, 5=Integrating
INI (Initiate) Logic Input Logic expression. Initiates timing sequence 0
Block Logic Input Logic expression. Disables function when TRUE 0

The BESTlogic settings can be made from the ASCII command interface using the SL-62 and SL-162
(settings logic-Timer) commands.

SL-62/162 Command
Purpose: Used to program a logical mode of operation for the general purpose logic timer blocks.
Syntax: SL-62/162[= <mode>, <INI logic>, <BLK logic>]
Example 1. Read 62 Logic (enabled for one-shot nonretriggerable operation with timing sequence
initiated by IN2 and blocking disabled)
>SL-62
2,IN2,0
>
Example 2. Change 62 Logic to be controlled by IN3 instead of IN2. (Note that it is not necessary to
enter the mode and the block expression since these are not changed.
>SL-62=,IN3
>
Setting Operational Settings, 62/162 General Purpose Logic Timer Functions
The operating parameter settings for the 62/162 general purpose logic timer functions are provided in
Table 4-19.
The time delays can be set in milliseconds, seconds, or cycles. The default is milliseconds if no unit of
measure is specified. The minimum resolution of the timing is to the nearest four milliseconds. A time
delay setting of zero makes the timer change state immediately with no intentional time delay.
If the time delay settings are made in cycles, they are converted to seconds or milliseconds before being
stored. This conversion is based on the nominal frequency setting stored in EEPROM. See Section 3,
Input And Output Functions, Current Measurement Functions for more information on this setting. If the
user is changing the nominal frequency setting from default (60 hertz) and setting the time delays in
cycles, the frequency setting should be entered and saved to EEPROM first by entering E; Y.
Table 4-19. 62/162 General Purpose Logic Timer Operational Settings
Unit of
Setting Range Increment Measure Default
Time 1 0 to 999 ms 1 ms milliseconds 0
0.1 to 9999 sec. 0.1 for 0.1 to 9.9 sec seconds
1.0 for 10-9999 sec seconds
0 to 599,940 (60 Hz) or 0 to 499,950 (50 Hz) * cycles
Time 2 0 to 999 ms 1 ms milliseconds 0
0.1 to 9999 Sec. 0.1 for 0.1 to 9.9 sec seconds
1.0 for 10 to 9999 sec seconds
0 to 599,940 (60 Hz) or 0 to 499,950 (50 Hz) * cycles
NOTE: * Time delays less than 10 cycles can be entered to the nearest 0.1 cycle from the
optional HMI. All time delays can be entered to the nearest 0.01 cycle from the ASCII
command interface. Time delays entered in cycles are converted to milliseconds or
seconds. Increment precision after conversion is limited to that appropriate for each of
those units of measure.

The 62 general purpose logic timer settings may be entered from the optional front panel HMI from
screens 5.#.5.1, \PROT\SG#\62\SETTINGS, or from the ASCII command interface using the
S<g>-62/162 (settings group #-62/162) command.

4-30 Protection And Control BE1-CDS


S<g>-62/162 Command
Purpose: Read/Set the 62 and 162 time settings.
Syntax: S<g>-62] [= <t1 [units] >, <t2 [units] >]
S<g>-162 [= <t1 [units] >, <t2 [units] >]
Comments: g = setting group number 0-3. Use # as wildcard to refer to all groups.
units = m for milliseconds (default)
s for seconds
c for cycles
Example 1. Set the 62 function for setting group 0 to delay pickup for 100 milliseconds with an
immediate dropout and set the 62 function for setting groups 1, 2, and 3 to delay pickup
for 150 milliseconds with a dropout of 50 milliseconds.
>S0-62=100,0; S1-62=150,50; S2-62=150,50; S3-62=150,50
>
Example 2. Take advantage of the # wildcard character to make the same setting with only two
commands.
>S#-62=150,50; S0-62=100,0
>
Retrieving Logic Output Status Information From the Relay
The status of each logic variable can be determined from the ASCII command interface using the RG-
STAT (report general-status) or the RL (report logic) commands. See Section 6, Reporting and Alarm
Functions, General Status Reporting for more information.

VIRTUAL SWITCHES

43 Virtual Selector Switches


BE1-CDS relays provide eight virtual selector switches which easily allow the user to provide local and
remote manual control without using physical switches and/or interposing relays. Each can be set for one
of three modes of operation to emulate virtually any type of binary (two position) switch. For example,
your application requires a differential cutoff switch. The traditional approach might be to install a switch
on the panel and wire the output to a contact sensing input on the relay or in series with the differential
trip output of the relay. A virtual switch can be used instead to reduce costs with the added benefit that
this switch could be operated both locally from the HMI and remotely from a substation computer or via a
modem connection to a remote operator’s console.
The state of the switches can be controlled from the optional HMI or the ASCII command interface. The
control actions that are allowed can be set by the BESTlogic mode setting. When set for Mode 1, each
switch can be controlled to open (logic 0), close (logic 1), or pulse such that the output toggles from its
current state to the opposite state and then returns. Additional modes allow the switch operation to be
restricted. In Mode 2 (ON/OFF), the switch emulates a two position selector switch and only open and
close commands are accepted. In Mode 3 (OFF/Momentary ON), the switch emulates a momentary
close, spring return switch and only the pulse command is accepted. The status of each switch is saved
to non-volatile memory so that the relay will power up with the switches in the same state as when it was
powered down.
Each function, see Figure 4-24, has one output, 43, 143,
243, 343, 443, 543, 643, and 743. The output state is Mode =
TRUE when the switch is in the closed state and FALSE 0-disable
when the switch is in the open state. Since both the 1-On/Off/Pulse SL-43
2-On/Off 43
output and the inverse of the output of these switches 3-Off/Momen-
LOGIC
can be used as many times as desired in your tary ON
programmable logic, they can emulate a switch with as
many normally open and normally closed decks as CO-43
D2843-13.vsd
desired. 07-25-00

As with a physical switch, these switches can have user Figure 4-24. Typical Virtual Selector
specified labels. In the above differential cutoff switch Switch Function
example, you might enable one of the switches in

BE1-CDS Protection And Control 4-31


BESTlogic as mode 2, ON/OFF and connect the output of that switch, to the blocking input of the 87
phase differential protection function block. This would disable the differential when the switch is closed
(logic 1) and enable it when the switch is open (logic 0). For this application, you might set the switch
label to be 87_CUTOFF. The closed position on the switch might be labeled DISABLD and the open
position might be labeled NORMAL. See Section 7, BESTlogic for more details on setting the user
programmable names for programmable logic variables.

Setting BESTlogic, 43/143/243/343/443/543/643/743 Virtual Selector Switch Function


The logic settings for the virtual selector switch functions are provided in Table 4-20. These settings will
enable the function by selecting the mode of operation. There are no logic inputs.
Table 4-20. 43/143/243/343/443/543/643/743 Virtual Selector Switch BESTlogic Settings
Function Range/Purpose Default
Logic Mode 0=Disabled, 1=On/Off/Pulse, 2=On/Off, 3=Off/Momentary On 0

The BESTlogic settings can be made from the ASCII command interface using the SL-
43/143/243/343/443/543/643/743 (settings logic-43 switch) commands.

SL-43/143/243/343/443/543/643/743 Command
Purpose: Used to program a logical mode of operation for the virtual selector switch blocks.
Syntax: SL-43/143/243/343/443/543/643/743[= <mode>]
Example 1. Read 43 Logic (off/momentary on)
>SL-43
3
>
Select Before Operate Control, Virtual Selector Switches

Control of the state of each virtual selector switch can be accomplished from the optional HMI from
screens 2.1.1, \CTRL\43\43 through 2.1.8, \CTRL\43\743. Or, they can be controlled from the ASCII
command interface using the select before operate CS/CO-#43 (control select-virtual switch/control
operate-virtual switch) commands. The state change takes place immediately without having to execute
an exit save settings command.

CS/CO-43/143/243/343/443/543/643/743 Command
Purpose: Control Virtual Switch Outputs.
Syntax: CS/CO-#43[=<action>]
Comments: #43 = Virtual logic input 43, 143, 243, 343, 443, 543, 643, or 743.
action =1 for close the switch
0 for open the switch
P for pulse the output to the opposite state for 200 milliseconds, and then automatically
return to starting state.
The virtual switch control commands require the use of Select Before Operate logic. First
the command must be selected using the CS-#43 command. After the command is
selected there is a 30 second window during which the CO-x43 control command can be
entered. The control selected and operation selected must exactly match or the
command is blocked. If the command is not entered within the 30 second window, the
command is blocked. If the control command is blocked, an error message is output.
Example 1. Read the current status of virtual switch 43.
>CO-43
0
>
Example 2. Momentarily toggle the state of switch 43 to closed.
>CS-43=P
43=P SELECTED
>CO-43=P
43=P EXECUTED
>
4-32 Protection And Control BE1-CDS
Example 3. Error due to incorrect selection command.
>CS-743=P
743=P SELECTED
>CO-743=1
ERROR:NO SELECT
?
Retrieving Virtual Selector Switch Status Information From the Relay
The state of each virtual selector switch can be determined from the optional HMI from screen 1.4.3,
\STAT\OPER\43. The state of each virtual selector switch can be determined from the ASCII command
interface using the RG-STAT or RG-43STAT commands. See Section 6, Reporting and Alarm Functions,
General Status Reporting for more information.
Screens 2.1.1, \CTRL\43\43 through 2.1.8, \CTRL\43\743 on the optional HMI provide switch control and
can also display the current status of their respective switches. The state of each virtual selector switch
can be determined from the ASCII command interface using the CO-#43 commands in a read only mode.
See example 1 in the previous paragraphs.

101 Virtual Breaker Control Switch


BE1-CDS relays provide one virtual breaker control switch which
Mode =
can easily allow the user to provide local and remote manual control 101T
0-disable
of a circuit breaker or switch without using physical switches and/or 1-enable
interposing relays. A virtual switch can be used instead of a physical 101
101C
BREAKER
switch to reduce costs with the added benefit that this switch can be CONTROL
operated both locally from the HMI and remotely from a substation CO-101 = SWITCH
T-trip 101SC
computer or via a modem connection to a remote operator’s
C-close
console.
D2843-14.vsd
02-02-99
The breaker control switch emulates a typical breaker control switch
with a momentary close, spring return, trip contact (output 101T, Figure 4-25. Virtual Breaker
Figure 4-25), a momentary close, spring return, close contact (output Control Switch Function
101C), and a slip contact (output 101SC). The slip contact output retains the status of the last control
action. That is, it is FALSE (open) in the after-trip state and TRUE (closed) in the after-close state.
Figure 4-26 shows the state of the 101SC logic output with respect to the state of the 101T and 101C
outputs.
When the virtual control switch is controlled to 1
trip, the 101T output pulses TRUE (closed) for 101T 200 ms
0
approximately 200 ms and the 101SC output
goes open (FALSE). When the virtual control 1
switch is controlled to close, the 101C output 101C 200 ms
0
pulses TRUE (closed) for approximately 200
ms and the 101SC output goes TRUE (closed). 1
The status of the slip contact output is saved to 101SC D2843-15.vsd
0 02-02-99
non-volatile memory so that the relay will
power up with the contact in the same state as Figure 4-26. Virtual Breaker Control Switch
when it was powered down. State Diagram
Since a transformer often has multiple breakers
or switches associated with it, it may be necessary to control more than a single breaker. Additional
breaker/switch control can be accomplished using device 43 switches set for mode 3, off/momentary
close. One switch would be used for breaker open, and a second would be used for breaker close. This
type of switch is often used in lieu of a breaker control switch where there is no need for a slip contact in
the control logic.

Setting BESTlogic, 101 Virtual Breaker Control Switch Function


The logic settings for the virtual selector switch functions are provided in Table 4-21. These settings will
enable the function by selecting the mode of operation. There are no logic inputs. The user label for the
101 virtual breaker control switch is entered using the SB-LOGIC command. For more information on the
SB-LOGIC command, see Section 6, Reporting And Alarm Functions, Breaker Monitoring.

BE1-CDS Protection And Control 4-33


Table 4-21. 101 Virtual Breaker Control Switch BESTlogic Settings
Function Range/Purpose Default
Logic Mode 0=Disabled, 1=Enabled 0

The BESTlogic settings can be made from the ASCII command interface using the SL-101 (settings logic-
101 switch) command.

SL-101 Command
Purpose: Used to program a logical mode of operation for the virtual breaker control switch.
Syntax: SL-101[= <mode>]
Example 1. Read 101 Logic (enabled)
>SL-101
1
>
Select Before Operate Control, Virtual Breaker Control Switches
Control of the virtual breaker control switches can be accomplished from the optional HMI from screen
2.2, \CTRL\BKR. Or, they can be controlled from the ASCII command interface using the select before
operate CS/CO-101 (control select-virtual control switch/control operate-virtual control switch) commands.
The state change takes place immediately without having to execute an exit, save settings command.

CS/CO-101 Command
Purpose: Control Virtual Control Switch Outputs.
Syntax: CS/CO-101[=<action>]
Comments: action = T for pulse the 101T output, C for pulse the 101C output
The virtual switch control commands require the use of Select Before Operate logic. First
the command must be selected using the CS-101 command. After the command is
selected there is a 30 second window during which the CO-101 control command can be
entered. The control selected and operation selected must exactly match or the
command is blocked. If the command is not entered within the 30 second window, the
command is blocked. If the control command is blocked, an error message is output.
Example 1. Read the current status of virtual control switch. (It is in the after close state.)
>CO-101
C
>
Example 2. Trip the breaker by closing the trip output of the virtual control switch.
>CS-101=T
101=T SELECTED
>CO-101=T
101=T EXECUTED
>
Retrieving Virtual Selector Switch Status Information From the Relay
The state of the virtual control switch (after-trip or after-close) can be determined from the ASCII
command interface using the RG-STAT command. See Section 6, Reporting and Alarm Functions,
General Status Reporting for more information.

Screen 2.2, \CTRL\BKR on the optional HMI provides switch control and can also display the current
status of the virtual control switches (after-trip or after-close). The state of each virtual control switch can
be determined from the ASCII command interface using the CO-101 command in a read only mode. See
example 1 in the previous paragraphs.

4-34 Protection And Control BE1-CDS


SECTION 5 • METERING
TABLE OF CONTENTS

List Of Figures......................................................................................................................................... i
List Of Tables.......................................................................................................................................... i
METERING ............................................................................................................................................... 5-1
GENERAL .............................................................................................................................................. 5-1
CURRENT METERING .......................................................................................................................... 5-1
Metering Via Serial Commands .......................................................................................................... 5-2
M Command.................................................................................................................................... 5-3
M Command ................................................................................................................................ 5-3
M-FREQ Command ..................................................................................................................... 5-4
M-I Command .............................................................................................................................. 5-4
M1-I And M2-I Commands ........................................................................................................ 5-4
MD Commands............................................................................................................................ 5-5
Metering Via Human Machine Interface (HMI).................................................................................... 5-6

List Of Figures
Figure 5-1. Polar Graph For Phase A Reference...................................................................................... 5-1
Figure 5-2. Screen 3 ................................................................................................................................. 5-6
Figure 5-3. Screen 3.1 .............................................................................................................................. 5-6
Figure 5-4. Screen 3.1.1 ........................................................................................................................... 5-6
Figure 5-5. Screen 3.1.1.1 ........................................................................................................................ 5-6

List Of Tables
Table 5-1. Metering Serial Communication Commands ........................................................................... 5-2

BE1-CDS Metering i
SECTION 5 • METERING
GENERAL
Metering, as it applies to the BE1-CDS relay, is measuring the current inputs, displaying those values in
real time, recording those values every one-quarter second, and calculating other quantities from the
measured inputs. There are two important references. One is that phase angle metering is referenced to
phase A1. (See the following paragraph for more information on phase angle references.) If phase A1 is
not present (zero), all other phase angles will be zero. Two is that the measured frequency is detected by
zero cross-over on phase C1. If phase C1 is not present (zero), all frequency measurements will be NA
(indicates no current flow in the input circuit).
The angles reported by the metering function can be understood by considering the following example. In
response to a request to “Read all metered values when CT circuit is set for a WYE connection”, part of
the report reads “IA1=4.95A,@ 0; and IB1=5.03A,@240;”. Figure 5-1 shows a polar graph with
counterclockwise rotation. Because phase A current magnitude is 4.95 amperes at an angle of 0 degrees
(it is the reference point), the phasor is on 0 degrees and almost reaches the outside of the circle which is
5.0 amperes. Phase B current is at an angle of 240 degrees and is shown on the polar graph at 240
degrees which is lagging phase A by 120 degrees. Phase B current magnitude is 5.03 amperes and the
phasor extends slightly beyond the circle. All reported angles can be laid out on this polar graph to
indicate leading or lagging quantities.

90°
120° 60°

150° 30°

180° IA1=4.95A, @ O°


120° Lagging

24
@
A,

210°
03

330°
5.
1=
IB

240° 300°

270° P0001-19.cdr
07-26-00

Figure 5-1. Polar Graph For Phase Angle Reporting Reference


For information on the current Demand Reporting Functions, see Section 6, Reporting And Alarm
Functions, Demand Functions.

CURRENT METERING
BE1-CDS relays provide metering of phases A, B, C, neutral (N), and negative sequence (Q) for CT circuit
1 and CT circuit 2 as well as the optional independent ground (G). Metering data is available in primary or
secondary current and can be obtained from the HMI screens 3.1 and 3.2, (\METER\CRNT\ and
\METER\DIFF\) and their associated sub-screens. This data can also be obtained through the M or M-I
serial communication commands as shown in the following paragraphs. Any individual metered value may
be obtained using these serial commands. For more information on metering Demand Reporting
Functions see Section 6, Reporting and Alarm Functions, Demand Functions.
BE1-CDS Metering 5-1
Metering Via Serial Commands
A list of all serial commands pertaining to metering is shown in Table 5-1 with a complete description in
the following paragraphs.
Table 5-1. Metering Serial Communication Commands
Serial HMI
Command Description Screen
M Read all metered values NA
M-FREQ Read measured frequency 3.1
M-I Read current (I) magnitude and angles for ckt 1, ckt 2, Gnd, N, and Q NA
M-IG Read ground current (I) 3.1.3.1
M1 Read CT circuit #1 all current magnitudes and angles NA
M1-I Read CT circuit #1 current magnitude and angles 3.1.1.1
M1-IA CT circuit #1, phase A current magnitude and angle 3.1.1.1
M1-IB CT circuit #1, phase B current magnitude and angle 3.1.1.1
M1-IC CT circuit #1, phase C current magnitude and angle 3.1.1.1
M1-IN CT circuit #1, Neutral current magnitude and angle 3.1.1.2
M1-IQ CT circuit #1, Negative sequence magnitude 3.1.1.2
M2 Read CT circuit #2 all current magnitudes and angles NA
M2-I Read CT circuit #2 current magnitude and angle 3.1.2.1
M2-IA CT circuit #2, phase A current magnitude and angle 3.1.2.1
M2-IB CT circuit #2, phase B current magnitude and angle 3.1.2.1
M2-IC CT circuit #2, phase C current magnitude and angle 3.1.2.1
M2-IN CT circuit #2, Neutral current magnitude and angle 3.1.2.2
M2-IQ CT circuit #2, Negative sequence magnitude 3.1.2.2
MD All Differential metering values NA
MD-2ND All 2nd harmonic current values 3.2.2
MD-5TH All 5th harmonic current values 3.2.2
MD-I All differential current metering values NA
MD-IA Differential current, phase A 3.2.1.1
MD-IA1 Differential current, phase A, CT circuit #1 3.2.1.1
MD-IA1COMP Differential current, phase A, CT circuit #1 3.2.1.1
MD-IA2 Differential current, phase A, CT circuit #2 3.2.1.1
MD-IA2COMP Differential current, phase A, CT circuit #2 3.2.1.1
MD-IA2ND 2nd harmonic, phase A current values 3.2.2
MD-IA5TH 5th harmonic, phase A current values 3.2.2
MD-IACOMP All of phase A differential current values NA
MD-IAOP Phase A IOP current value 3.2.1.1
MD-IB Differential current, phase B 3.2.1.2
MD-IB1 Differential current, phase B, CT circuit #1 3.2.1.2
MD-IB1COMP Differential current, phase B, CT circuit #1 3.2.1.2
MD-IB2 Differential current, phase B, CT circuit #2 3.2.1.2
MD-IB2COMP Differential current, phase B, CT circuit #2 3.2.1.2
MD-IB2ND 2nd harmonic, phase B current values 3.2.2
MD-IB5TH 5th harmonic, phase B current values 3.2.2
MD-IBCOMP All of phase B differential current values NA
MD-IBOP Phase B IOP current value 3.2.1.2
MD-IC Differential current, phase C 3.2.1.3
MD-IC1 Differential current, phase C, CT circuit #1 3.2.1.3
MD-IC1COMP Differential current, phase C, CT circuit #1 3.2.1.3
MD-IC2 Differential current, phase C, CT circuit #2 3.2.1.3

5-2 Metering BE1-CDS


Serial HMI
Command Description Screen
MD-IC2COMP Differential current, phase C, CT circuit #2 3.2.1.3
MD-IC2ND 2nd harmonic, phase C current values 3.2.2
MD-IC5TH 5th harmonic, phase C current values 3.2.2
MD-ICCOMP All of phase C differential current values NA
MD-ICOP Phase C Iop current value 3.2.1.3
MD-IGCOMP Ground differential current values 3.1.3.1
MD-IN Differential current, Neutral 3.2.1.4
MD-IN1 Differential current, Neutral, CT circuit #1 3.1.1.2
MD-IN1COMP Differential current, Neutral, CT circuit #1 3.2.1.4
MD-IN2 Differential current, Neutral, CT circuit #2 3.1.2.2
MD-IN2COMP Differential current, Neutral, CT circuit #2 3.2.1.4
MD-INOP Neutral Iop current values 3.2.1.4

M Command
This command returns all measured and calculated metered data. Quantities metered at the terminals are
real time values and are not dependent on the winding configuration. Quantities such as operating current
(IOP ), restraint current (IR), and the second and fifth harmonic values are dependent on the winding
configuration. Operating current and restraint current values are compensated and are metered in
quantity-times-tap. The second and fifth harmonic values are displayed as a percentage of the operating
current for phase A, B, and C. If the winding is set for a WYE configuration, the quantities returned are
IAn, IBn, ICn, INn, and IQn where n is equal to 1 for CT circuit 1 or 2 for CT circuit 2. If the
winding is set for a DAB configuration, then quantities returned are IAn-IBn, 1Bn-ICn, ICn-IAn,
INn, and IQn where n is equal to 1 for CT circuit 1 or 2 for CT circuit 2. If the winding is set for a DAC
configuration, then quantities returned are IAn-ICn, IBn-IAn, ICn-IBn, INn, and IQn where n
is equal to 1 for CT circuit 1 or 2 for CT circuit 2.

M Command
Purpose: Return metering information on all metered parameters
Syntax: M[,y]
Comments: No password access required.
y= P for return values as primary values (default).
S for return values as secondary values.
Example 1. Read all metered values when CT circuit is set for a WYE connection.
>M,S
IA1=4.95A,@ 0; IB1=5.03A,@240; IC1=5.00A,@120
IN1=0.07A,@ 0; IQ1=0.02A
IA2=7.10A,@180; IB2=6.88A,@ 60; IC2=6.95A,@300
IN2=0.19A,@ 0; IQ2=0.06A
IG=1.00A,@ 42
IA1COMP= 2.48XTAP,@ 0; IA2COMP= 2.54XTAP,@180; IAOP= 0.06XTAP
IB1COMP= 2.51XTAP,@240; IB2COMP= 2.46XTAP,@ 60; IBOP= 0.05XTAP
IC1COMP= 2.50XTAP,@120; IC2COMP= 2.48XTAP,@300; ICOP= 0.02XTAP
IGCOMP= 0.50XTAP,@ 0
IN1COMP= 0.10XTAP,@ 0; IN2COMP= 0.03XTAP,@ 0; INOP= 0.13XTAP
IA2ND= 2%IOP; IA5TH= 2%IOP
IB2ND= 1%IOP; IB5TH= 2%IOP
IC2ND= 1%IOP; IC5TH= 3%IOP
FREQ=60.00HZ
>
Example 2. Read all metered values when CT circuit is set for a DELTA (DAB) connection.
>M,S
IA1-IB1=4.95A,@ 0; IB1-IC1=5.03A,@240; IC1-IA1=5.00A,@120
IN1=0.07A,@ 0; IQ1=0.02A
IA2-IB2=7.10A,@180; IB2-IC2=6.88A,@ 60; IC2-IA2=6.95A,@300
IN2=0.19A,@ 0; IQ2=0.06A

BE1-CDS Metering 5-3


IG=1.00A,@ 42
IA1COMP= 2.48XTAP,@ 0; IA2COMP= 2.54XTAP,@180; IAOP= 0.06XTAP
IB1COMP= 2.51XTAP,@240; IB2COMP= 2.46XTAP,@ 60; IBOP= 0.05XTAP
IC1COMP= 2.50XTAP,@120; IC2COMP= 2.48XTAP,@300; ICOP= 0.02XTAP
IGCOMP= 0.50XTAP,@ 0
IN1COMP= 0.10XTAP,@ 0; IN2COMP= 0.03XTAP,@ 0; INOP= 0.13XTAP
IA2ND= 2%IOP; IA5TH= 2%IOP
Example 2. - Continued
IB2ND= 1%IOP; IB5TH= 2%IOP
IC2ND= 1%IOP; IC5TH= 3%IOP
FREQ=60.00HZ
>

M-FREQ Command
Purpose: Read measured frequency.
Syntax: M-FREQ
NOTE
Returned value is frequency measured by zero-crossing detector on phase C1. If there is
current flow in the input circuit indicating that there is a signal and the measured
frequency is out of range (<40 hertz or >63 hertz), a value of 60 hertz (nominal frequency)
is reported. Also, if the current on phase C1 is less than 0.1 times the current nominal
(current nominal = 1 ampere or 5 amperes depending on the sensing input type), 60 hertz
is reported.

M-I Command
Purpose: Read CT circuit #1, #2, Gnd, N, and Q current magnitudes and angles (no angles for Q
measurements).
Syntax: M-I[G,y]
Comments: No password access required.
G= Respond with only the Ground current/angle measurement
y= P for return values as primary values (default).
S for return values as secondary values.
@= angle in degrees

Example 1. Read CT circuit #1, #2, Gnd, N, and Q metered values in secondary units.
>M-I,s
IA1=4.95A,@ 0; IB1=5.03A,@240; IC1=5.00A,@120
IN1=0.07A,@ 0; IQ1=0.02A
IA2=7.10A,@180; IB2=6.88A,@ 60; IC2=6.95A,@300
IN2=0.19A,@ 0; IQ2=0.06A
IG=1.00A,@ 42
>
Example 2. Read the ground metered value.
>M-IG
IG=1.00A,@ 42
>

M1-I And M2-I Commands


Purpose: Read CT circuit current magnitudes and angles.
Syntax: M<x>-I[p][,y]
Comments: No password access required.
x= 1 - CT circuit #1
2 - CT circuit #2
p= A - Phase A magnitude and angle
B - Phase B magnitude and angle
C - Phase C magnitude and angle
N - Neutral magnitude and angle
Q - Negative Sequence magnitude
y= P for return values as primary values (default).
S for return values as secondary values.

5-4 Metering BE1-CDS


@= angle in degrees

The M1 and M2 commands are to retrieve only the current magnitude and angle of the
selected CT circuit.

Example 1. Read phase (A, B, C), N, and Q current magnitude and angle values for CT circuit #1.
(Remember, no phase angles for Q measurements.)
>M1-I,s
IA1=4.95A,@ 0; IB1=5.03A,@240; IC1=5.00A,@120
IN1=0.07A,@ 0; IQ1=0.02A
>
Example 2. Read current value of CT circuit #2 phase B.
>M2-IB,s
5.03A,@240
>
Example 3. Read secondary current values of CT circuit #2.
>M2-I,S
IA2=7.10A,@180; IB2=6.88A,@ 60; IC2=6.95A,@300
IN2=0.19A,@ 0; IQ2=0.06A
>

MD Commands
Purpose: Read differential metered values.
Syntax: MD-[<p>x][,y]
Comments: No password access required.
x= COMP - Compensated currents magnitude and angle
OP - IOP currents magnitude and angle
2ND - Second harmonic current magnitude as a percentage of IOP.
5TH - Fifth harmonic current magnitude as a percentage of IOP.

p= A- Phase A magnitude and angle


B- Phase B magnitude and angle
C- Phase C magnitude and angle

y= P for return values as primary values (default).


S for return values as secondary values.
Example 1. Read IOP, compensated currents, second, and fifth harmonic metered values in
secondary units.
>MD,s
IA1COMP= 2.48XTAP,@ 0; IA2COMP= 2.54XTAP,@180; IAOP= 0.06XTAP
IB1COMP= 2.51XTAP,@240; IB2COMP= 2.46XTAP,@ 60; IBOP= 0.05XTAP
IC1COMP= 2.50XTAP,@120; IC2COMP= 2.48XTAP,@300; ICOP= 0.02XTAP
IGCOMP= 0.50XTAP,@ 0
IN1COMP= 0.10XTAP,@ 0; IN2COMP= 0.03XTAP,@ 0; INOP= 0.13XTAP
IA2ND= 2%IOP; IA5TH= 2%IOP
IB2ND= 1%IOP; IB5TH= 2%IOP
IC2ND= 1%IOP; IC5TH= 3%IOP
>
Example 2. Read IOP and compensated currents in secondary units.
>MD-I,s
IA1COMP= 2.48XTAP,@ 0; IA2COMP= 2.54XTAP,@180; IAOP= 0.06XTAP
IB1COMP= 2.51XTAP,@240; IB2COMP= 2.46XTAP,@ 60; IBOP= 0.05XTAP
IC1COMP= 2.50XTAP,@120; IC2COMP= 2.48XTAP,@300; ICOP= 0.02XTAP
IGCOMP= 0.50XTAP,@ 0
IN1COMP= 0.10XTAP,@ 0; IN2COMP= 0.03XTAP,@ 0; INOP= 0.13XTAP
>

BE1-CDS Metering 5-5


Metering Via Human Machine Interface (HMI)
All metering values can be viewed using the LCD display. For example, to view \METER
the metered values for phase A, B, and C on CT circuit 2, you would press the
right or left scrolling pushbuttons to get to Screen 3 (\METER) METERING METERING
shown in Figure 5-2. PRI/SEC
<CTRL vCRNT >REPRT

Figure 5-2. Screen 3


If the displayed screen is something other than a top level screen, press the up
scrolling pushbutton three times to return to the top level.

After you have the METERING screen displayed, press the down scrolling
\METER\CRNT
pushbutton to get to the next level of detail, Screen 3.1 (\METER\CRNT), Figure
5-3.
CURRENT
MEASURED FREQUENCY
60.00 HZ
<DIFF vCT_1 >DIFF

Figure 5-3. Screen 3.1

To get to Screen 3.1.1 (\METER\CRNT\CT_1) shown in Figure 5-4, press the


down scrolling pushbutton. From this screen you can select whether the \METER\CRNT\CT_1
currents are displayed in primary or secondary values by pushing the EDIT CT CIRCUIT 1
pushbutton, then pressing the up or down pushbuttons until the desired setting is
VIEW PRI CURRENTS
shown. Press the edit button again to make your selection active.
<GND vI_MEA >CT_2

Figure 5-4. Screen 3.1.1

To get to Screen 3.1.1.1 (\METER\CRNT\CT_1\I_MEAS), where phase A, B, and


C currents for CT circuit 1 are displayed, you would press the down scrolling ...\CRNT\CT_1\I_MEAS
pushbutton. Screen 3.1.1.1 is shown in Figure 5-5. IA IB IC S
2.000K 2.300K 2.100K
< 12° <133° <255°
<I_CAL >I_CAL

Figure 5-5. Screen 3.1.1.1

Using the menu map shown in Section 10, Human-Machine Interface, any metered value can be
displayed. Table 5-1 cross references the metered commands to the menu tree.

5-6 Metering BE1-CDS


SECTION 6 • REPORTING AND ALARM
FUNCTIONS
TABLE OF CONTENTS

List Of Figures......................................................................................................................................... i
List Of Tables..........................................................................................................................................ii
SECTION 6 • REPORTING AND ALARM FUNCTIONS ........................................................................... 6-1
GENERAL .............................................................................................................................................. 6-1
RELAY IDENTIFIER INFORMATION..................................................................................................... 6-1
CLOCK ................................................................................................................................................... 6-1
GENERAL STATUS REPORTING......................................................................................................... 6-3
General Status Report ........................................................................................................................ 6-3
Other Report General Commands ...................................................................................................... 6-4
DEMAND FUNCTIONS .......................................................................................................................... 6-5
Demand Calculation And Reporting Function..................................................................................... 6-5
Overload And Unbalance Alarms Function......................................................................................... 6-8
Optional Load Profile Recording ......................................................................................................... 6-8
DIFFERENTIAL CURRENT MONITORING FUNCTION ..................................................................... 6-10
TRANSFORMER MONITORING ......................................................................................................... 6-13
Number Of Through Faults Monitoring Function .............................................................................. 6-14
Transformer Duty Monitoring ............................................................................................................ 6-14
Transformer Alarms .......................................................................................................................... 6-15
BREAKER MONITORING .................................................................................................................... 6-16
Breaker Status Reporting.................................................................................................................. 6-16
Breaker Duty Monitoring ................................................................................................................... 6-17
Breaker Alarms ................................................................................................................................. 6-19
TRIP CIRCUIT MONITOR.................................................................................................................... 6-22
FAULT REPORTING............................................................................................................................ 6-24
Targets.............................................................................................................................................. 6-25
Fault Summary Reports .................................................................................................................... 6-27
Oscillographic Records ..................................................................................................................... 6-30
SEQUENCE OF EVENTS RECORDER FUNCTION........................................................................... 6-32
ALARMS FUNCTION ........................................................................................................................... 6-34
Relay Trouble Alarms ....................................................................................................................... 6-34
Major/Minor/Logic Programmable Alarms......................................................................................... 6-35
Links Between Programmable Alarms Function And BESTlogic Programmable Logic.................... 6-38
HARDWARE AND SOFTWARE VERSION REPORT ......................................................................... 6-38

List Of Figures
Figure 6-1. Differential Alarm Characteristics ......................................................................................... 6-13
Figure 6-2. Protective Fault Analysis ...................................................................................................... 6-21
Figure 6-3. Trip Circuit Monitor Logic...................................................................................................... 6-22
Figure 6-4. Trip Circuit Voltage And Continuity Monitor.......................................................................... 6-23
Figure 6-5. TCM With Other Devices ...................................................................................................... 6-23
Figure 6-6. Target Reset Logic ............................................................................................................... 6-26
Figure 6-7. Programmable Alarm Function ............................................................................................. 6-35

BE1-CDS Reporting And Alarm Functions i


List Of Tables
Table 6-1. SG-ID Settings ......................................................................................................................... 6-1
Table 6-2. Clock Settings .......................................................................................................................... 6-2
Table 6-3. Logic Variable Status Report Format....................................................................................... 6-5
Table 6-4. Demand Interval Settings......................................................................................................... 6-6
Table 6-5. Demand Alarm Threshold Settings .......................................................................................... 6-8
Table 6-6. Load Profile Recording Settings .............................................................................................. 6-9
Table 6-7. Differential Alarm Threshold Setting ...................................................................................... 6-13
Table 6-8. Transformer Duty Monitoring Settings ................................................................................... 6-15
Table 6-9. Transformer Programmable Alarms Settings......................................................................... 6-16
Table 6-10. Breaker Status Reporting Settings....................................................................................... 6-17
Table 6-11. Breaker Duty Monitoring Settings ........................................................................................ 6-18
Table 6-12. Breaker Programmable Alarms Settings.............................................................................. 6-19
Table 6-13. Trip Coil Monitor Function Settings ...................................................................................... 6-24
Table 6-14. Fault Reporting Function Settings........................................................................................ 6-25
Table 6-15. Protective Functions With Targets ....................................................................................... 6-25
Table 6-16. Target Settings..................................................................................................................... 6-26
Table 6-17. Possible Oscillographic Records ......................................................................................... 6-30
Table 6-18. Recording Oscillographic Records Settings.........................................................................6-31
Table 6-19. Relay Trouble Alarms .......................................................................................................... 6-35
Table 6-20. Programmable Alarms ......................................................................................................... 6-35
Table 6-21. Programmable Alarm Priorities Settings .............................................................................. 6-36
Table 6-22. Programming Alarm Reset................................................................................................... 6-38

ii Reporting And Alarm Functions BE1-CDS


SECTION 6 • REPORTING AND ALARM
FUNCTIONS

GENERAL
This Section describes all of the reports that are available from the BE1-CDS relay, how to set the
reporting functions, and how to retrieve these reports. Alarm functions are included in this Section
because they perform a reporting function. This Section also describes all of the alarm functions, how to
set those functions, and how to program (map) the major and minor alarms.

RELAY IDENTIFIER INFORMATION


It is important to attach (label) meaningful names to the relays and the relay reports. To provide this
feature, BE1-CDS relays have four relay identification fields: Relay ID, Station ID, User Label 1, and User
Label 2. These fields are used in the header information lines of the Fault Reports, the Oscillographic
Records, and the Sequence of Events Recorder (SER) Reports. Each of these four ID fields may be up to
30 alpha/numeric characters long. Table 6-1 describes the label settings (identifier names) which can be
programmed via the ASCII command interface using the SG-ID command.
Table 6-1. SG-ID Settings
Setting Identifier For Parameters Default
ID1 BE1-CDS device label 30 characters maximum* BE1-CDS
ID2 Station label 30 characters maximum* SUBSTATION-1
ID3 User label 1 30 characters maximum* USER1-ID
ID4 User label 2 30 characters maximum* USER2-ID
* Each identifier label may consist of a maximum of 30 alphanumeric characters. No spaces are
allowed in the labels. Any spaces used in the labels are stripped when the label change is saved.
Use the character _ (shift underscore) to create a break in alpha characters. For example,
station_name.

SG-ID Command
Purpose: Reads or changes the relay/station name and number for FAULT and SER reports.
Syntax: SG-ID[n][= <relayid\stationid\userlabel1\userlabel2>]
Comments: SG-ID by itself recalls all four labels.
Example 1. Enter the SG-ID information for relay/station where the BE1-CDS220 relay is installed.
>SG-ID1=15 <used for relay id field in COMTRADE files
>SG-ID2=POWERPOINT_SUBSTATION <used for station id field in COMTRADE files
>SG-ID3=PO#123XYZ
>SG-ID4=MAY_1999

Example 2. Display ID labels


>SG-ID
SG-ID1=15
SG-ID2=POWERPOINT_SUBSTATION
SG-ID3=PO#123XYZ
SG-ID4=MAY_1999

CLOCK
BE1-CDS relays use the internal clock to time stamp specific reporting functions and events. The clock
function is used by the demand reporting function, the fault reporting function, the oscillographic recorder
BE1-CDS Reporting And Alarm Functions 6-1
function, and the sequence of events recorder function to time stamp events. The clock function records
the current year in two digit format. You may program the relay to display the date and time in several
formats including automatically adjusting for daylight savings time. See the paragraphs in this Section on
Setting The Clock Function and Reading And Setting The Clock. There are no problems with the year
2000 because the functions that use the clock do not perform any date math calculations or sorting of
information by date. This clock has a capacitor back-up feature which retains the date and time for up to
eight hours after power is removed from the relay.

IRIG Port
An IRIG (demodulated) time code signal port is provided. See Section 12, Installation for information
about connecting an IRIG time code source to the relay. When the BE1-CDS detects a valid time code
signal at the IRIG port, it automatically synchronizes the internal clock to the time code signal. Note that
the IRIG time code signal does not contain the current year information. For this reason, it is necessary to
enter the date even when using IRIG. The current year is stored in nonvolatile memory so that when the
relay powers up after an outage and the clock is re-synchronized, the current year is restored. When the
clock rolls over at a new year, the current year is automatically updated in nonvolatile memory. An alarm
bit is provided in the programmable alarm function for loss of the IRIG signal. This alarm point will monitor
for the loss of an IRIG signal once a valid signal is detected at the IRIG port.
The IRIG input is fully isolated and accepts a demodulated (dc level-shifted) signal. The input signal must
be 3.5 volts or higher to be recognized as a valid signal. Maximum input signal level is +10 volts to -10
volts (20 volt range). Input resistance is nonlinear and rated at 4 kilo-ohms at 3.5 volts. Section 12,
Installation, Communication Connectors and Settings identifies the terminal connections for the IRIG
function.

Setting The Clock Function


The date reporting format may be set to display the date in mm/dd/yy or dd/mm/yy format. The time
reporting format may be set to display in 12 hour or 24 hour format. When set to operate in 12 hour
format, the AM/PM parameter is placed between the minutes and seconds parameters (10:24P23.004
would mean 10:24 in the evening). This setting can be made from the ASCII command interface using the
SG-CLK command. Table 6-2 lists the clock settings.
Table 6-2. Clock Settings
Setting Range Default
Date format D (day first), M (month first) M
Time format 12 (12 hour format), 24 (24 hour format) 24
dst enable 0 (daylight saving time disabled), 0
1 (daylight saving time enabled)

SG-CLK Command
Purpose: Reads/Program the real time clock time/date format.
Syntax: SG-CLK [= <date format>, <time format>, <dst enable>]

Example 1. Read clock format


>SG-CLK
M,12,0
Example 2. Change clock format to display the day first and the 24 hour format with daylight savings
time enabled
>SG-CLK=D,24,1
Reading and Setting the Clock
The clock can be read and set from the ASCII command interface using the RG-TIME (report general,
time) and RG-DATE (report general, date) commands. The time can be read from HMI screen 1.4.6,

6-2 Reporting And Alarm Functions BE1-CDS


\STAT\OPER\TIME_DATE. An alarm point is provided in the programmable alarms to detect that the
relay has powered up and that the clock has not been set.

RG-DATE Command
Purpose: Reads or changes the date programmed in the real time clock.
Syntax: RG-DATE [=<m>/<d>/<y>] or RG-DATE [=<d>-<m>-<y>]
Comments: d=day entered first or second based on SG-CLK setting.
m=month entered first or second based on SG-CLK setting.
y=last two digits of year.
The default on power up is 01/01/yy, where yy is the last value of year utilized by the real-time clock.

Example. Enter new date


>RG-DATE=01/27/94

RG-TIME Command
Purpose: Reads or changes the time setting of the real time clock.
Syntax: RG-TIME [= hr:mn:sc] or RG-TIME [= hr:mn <f><sc>]
Comments: hr = hour in 12 or 24 hour format as defined by the SG-CLK command; mn = minutes;
sc = seconds; f = format ( A = AM, P = PM for 12 hour clock)
: = Military (24 hour clock)
Default on power up is 00:00:00
Example 1. Read the present time from the real time clock (programmed in 12 hour format).
>RG-TIME
12:24P45
Example 2. Set a new time in 12 hour format.
>RG-TIME = 11:24P00

GENERAL STATUS REPORTING


BE1-CDS220 relays have extensive capabilities for reporting relay status. This is important for
determining the health and status of the system for diagnostics and troubleshooting. Throughout this
manual, reference is made to the RG (report general) and RG-STAT (report general, status) reports and
the appropriate HMI screens for determining the status of various functions.

General Status Report


A General Status report is available from the ASCII command interface using the RG-STAT (report
general, status) command. This one report pulls together all of the information required to determine the
status of the relay. The following is an example of a typical general status report. In the discussion of
what each line represents, cross references will be made to the appropriate HMI screens that also contain
that data.
INPUT(12345678) STATUS : 00000000
OUTPUT(A123456) STATUS : 0000001
CO-OUT(A123456) STATUS : LLLL0L1
CO-43 to CO-743 STATUS : 00000000
CO-101(101SC) STATUS : AFTER CLOSE(1)
CO-GROUP STATUS : L
ACTIVE LOGIC STATUS : BASIC-87
LOGIC VAR(00-31) STATUS : 00000000 00000000 00000000 00010000
LOGIC VAR(32-63) STATUS : 00000000 00000000 00000000 00000001
LOGIC VAR(64-95) STATUS : 00000000 00000000 00000000 00000000
ACTIVE GROUP STATUS : 0
BREAKER(52) STATUS : CLOSED
DIAG/ALARM STATUS : 0 RELAY, 0 LOGIC, 0 MAJOR, 0 MINOR

BE1-CDS Reporting And Alarm Functions 6-3


Input (12345678). This line reports the current status of the contact sensing inputs. This information is
available on HMI screen 1.4.1, \STAT\OPER\INPUT, or by using the ASCII command RG-INPUT. See
Section 3, Input and Output Functions for more information about contact sensing input operations.
Output (A123456). This line reports the current status of the output contacts. This information is available
on HMI screen 1.4.2, \STAT\OPER\OUT, or by using the ASCII command RG-OUTSTAT. See Section 3,
Input and Output Functions for more information about output contact operation.
CO-OUT(A123456). This line reports the current status of the logic override of the output contacts. In the
sample report, outputs A, 1, 2, 3, and 5 are not in logic override. Output 4 is in a logic override open state,
and output 6 is in a logic override closed state. This information is available on HMI screen 2.4,
\CTRL\OUT, or by using the RG-OUTCNTRL ASCII commands. Section 3, Input and Output Functions
provides more information about output logic override control of the output contacts.
CO-43/143/243/343/443/543/643/743. This line reports the current status of the virtual switch functions.
This information is available on HMI screen 1.4.3, \STAT\OPER\x43, where x is blank, 1, 2, 3, 4, 5, 6, or 7.
The status of the 43 switches is also available from the RG-43STAT ASCII command. See Section 4,
Protection and Control, Virtual Selector Switches for more information about this function.
CO-101. This line reports the current status of the virtual breaker control switch slip contact output. This
information is available on HMI screen 2.2, \CTRL\BKR, or with ASCII command RG-101STAT. See
Section 4, Protection and Control, Virtual Breaker Control Switch for more information about this function.
CO-GROUP. This line reports the current status of the logic override of the setting group selection
function. In the sample report, CO-GROUP is not in logic override. This information is available on HMI
screen 2.3, \CTRL\SG, or using the RG-GRPCNTRL ASCII command. See Section 4, Protection and
Control, Setting Groups for more information on this function.
ACTIVE LOGIC. This line reports the name of the logic scheme that is currently active. This information
is available on HMI screen 5, \PROT, or the RG-LOGIC ASCII command. See Section 7, BESTlogic
Programmable Logic, Logic Scheme Names for more information about this function.
LOGIC VAR(00-31), LOGIC VAR(32-63), and LOGIC VAR(64-95). These lines report the current status
of each of the BESTlogic logic variables. The output of these lines can be entered into Table 6-3 to
determine the status of each logic variable. See Section 7, BESTlogic Programmable Logic for more
information on the operation this function. This information is not available from the HMI. RL (report logic)
also reports the BESTlogic logic variables.
ACTIVE GROUP. This line reports the current active setting group. This information is available on HMI
screen 1.4.4, \STAT\OPER\ACTIVEG, or using ASCII command RG-GRPACTIVE. See Section 4,
Protection and Control, Settings Groups provides more information about this function.
BREAKER (52). This line reports the state of the breaker as defined by the logic expression SB-LOGIC.
This information is available on HMI screen 1.4.5, \STAT\OPER\BKR, or using ASCII command RG-
BREAKER. See the paragraphs Breaker Monitoring, Programming The Breaker Status Reporting
Function later in this Section for more information about this function.
DIAG/ALARM. This line reports the status of each of the following alarm categories: relay, logic, major,
and minor. Detailed information on individual alarm points is available on HMI screen 1.2,
\STAT\ALARMS, or using ASCII command RA. See Section 4, HMI and the paragraphs on Alarms
Function later in this Section for more information about the diagnostic and alarm functions.

Other Report General Commands


There are several other RG (report general) commands in addition to those discussed in the previous
paragraphs on the RG-STAT command. These include RG-TIME, RG-DATE, RG-TARG, and RG-VER.
These are covered in detail in the respective paragraphs in this Section. As with many other commands,
a combination read command is available to read several items in a group. If the command RG is entered
by itself, the relay reports the time, date, target information, and other reports as shown in the following
example. RG-VER and RG-STAT commands have multiple line outputs and these are not read with the
RG command.

6-4 Reporting And Alarm Functions BE1-CDS


Example. Read the general reports.
RG
RG-DATE=01/01/98 RG-GRPACTIVE=0
RG-TIME=01:47:54 RG-GRPCNTRL=L
RG-TARG=NONE RG-INPUT=00000000
RG-ADDR1= 0 RG-LOGIC=USER
RG-ADDR2= 0 RG-OUTCNTRL=LLLLLLL
RG-43STAT=00000000 RG-OUTSTAT=0000000
RG-101STAT=C

Table 6-3. Logic Variable Status Report Format


1 2 1 2 1 2 2 5 S
5 5 5 5 5 5 5 5 5 1 2 1 2 1 2 8 N T P
0 0 0 0 0 0 0 0 0 5 5 5 5 5 5 5 5 5 7 8 8 D H A
T T T T T T T T T 1 1 1 1 1 1 1 1 1 B N 7 7 H H R 1 S S S S
P P P N N N Q Q Q P P P N N N Q Q Q F D R U A A E 6 6 G G G G
T T T T T T T T T T T T T T T T T T T T T T R R 1 2 2 0 1 2 3 0

00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31

S A A A C
P L L L K 1
V V V V V V A M M M T 1 1 0
V V V V V V V V V V O O O O O O I I I I I I I I R M M L M 0 0 1
O O O O O O O O O O 1 1 1 1 1 1 N N N N N N N N E A I G O 1 1 S
A 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 1 2 3 4 5 6 7 8 2 J N C N T C C

32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63

1 2 1 2 1 2 A T
5 5 5 5 5 5 5 5 5 1 2 1 2 1 2 8 S R R
0 0 0 0 0 0 0 0 0 5 5 5 5 5 5 5 5 5 7 8 P S S
T T T T T T T T T 1 1 1 1 1 1 1 1 1 B N 7 A T T
P P P N N N Q Q Q P P P N N N Q Q Q F D R R K K 1 2 3 4 5 6 7
P P P P P P P P P P P P P P P P P P P P P E E E 4 4 4 4 4 4 4 4
U U U U U U U U U U U U U U U U U U U U U 3 Y Y 3 3 3 3 3 3 3 3

64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95

DEMAND FUNCTIONS
The demand reporting function continuously calculates demand values in primary amperes for the three-
phase currents, neutral current, and negative sequence current for the specified CT input crcuit. This
function provides for recording the demand values with time stamps for Peak Since Reset, Yesterday’s
Peak, and Today’s Peak. It also provides programmable alarm points that can be set to alarm if
thresholds are exceeded for overload and unbalanced loading conditions.

Demand Calculation And Reporting Function


Thermal Demand Calculation Method. The demand reporting function incorporates an algorithm to digitally
simulate a thermal or exponential response. Thermal demand values are computed by an exponential
algorithm with the demand interval or response period defined as the time taken by the meter to reach 90
percent of the final value for a step change in the current being measured. The demand interval and
monitored CT can be set independently for the phase, neutral, and negative sequence demand calculations.
Block Demand Calculation Method. The block demand method calculates the average value of the
measured current for the time interval set by the demand reporting function. This value remains constant and
is stored in registers and reported for the duration of the following time interval. At the end of the time
interval, the calculated average for the previous time interval is again stored in registers and reported for the
duration of the following time interval. If you have set a fifteen minute time interval and block demand

BE1-CDS Reporting And Alarm Functions 6-5


calculation, the reported value for fifteen minutes is the average value of the measured current for the
previous fifteen minutes.
Sliding Block Demand Calculation Method. Sliding block demand method calculates the average value of the
measured current for the time interval set by the demand reporting function. This value is stored in registers
and reported for one minute. After one minute has elapsed, the sliding block demand method again
calculates the average value of the measured current for the set time interval including the most recent
minute. This value is updated each minute.
Each time that the value in the current demand register is updated, it is compared to the values stored in
the Peak Since Reset and the Today’s Peak registers. If the new demand value is greater, the new value
and time stamp is entered into the appropriate registers. In addition, the demand reporting function keeps
an additional set of registers for Yesterday’s Peak. Each day at midnight, the demand reporting function
replaces the values and time stamps stored in yesterday’s peak registers with the values and time stamps
from today’s peak registers. It then starts recording new information in Today’s Peak registers. The
demand registers are stored in volatile memory.
The Today’s Peak and Yesterday’s Peak registers are read only. The values in the Peak Since Reset
registers can be reset to zero or preset to a predetermined value. For example, if you are going to switch
some loads to take a feeder out of service and you do not want the abnormal loading to affect the values
stored in the Peak Since Reset registers. You may read these values prior to doing the switching and
then reset the registers to these values after the abnormal loading condition has passed.

Setting The Demand Reporting Function


For the demand reporting function to calculate demand, it is necessary to specify the demand interval,
calculation method (only one calculation method is currently available), and which CT to monitor. This can
be done from the ASCII command interface using the SG-DI (setting general, demand interval) command
or the HMI using screen 6.4.1, \SETUP\DMD\DETAILS. Table 6-4 lists the settings for demand interval.
Table 6-4. Demand Interval Settings
Setting Range Increment Unit Of Measure Default
Phase Demand Interval 0 to 60 1 Minutes 15
Phase Cal. Method Thermal (T), Block (B), NA NA T
Sliding Block (S)
Phase CT # 1, 2 NA NA 2
Neutral Demand Interval 0 to 60 1 Minutes 1
Neutral Cal. Method Thermal (T), Block (B), NA NA T
Sliding Block (S)
Neutral CT # 1, 2, G NA NA 2
Negative Sequence Demand Interval 0 to 60 1 Minutes 1
Negative Sequence Cal. Method Thermal (T), Block (B), NA NA T
Sliding Block (S)
Negative Sequence CT # 1, 2 NA NA 2

SG-DI Command
Purpose: Read/Program Demand Current Settings
Syntax: SG-DI[p][=<interval>,<calc_method>,<CT#>]

Example 1. Set demand interval for phase, neutral, and negative sequence for 1 minute, sliding block
average, and CT #1.
>SG-DI=1,S,1

Example 2. Set demand interval for phase for 15 minutes, thermal, and CT #1.
>SG-DIP=15,T,1

6-6 Reporting And Alarm Functions BE1-CDS


Retrieving Demand Reporting Information
The values and time stamps in the demand registers are reported in primary amperes. They can be read
from both the HMI and the ASCII command interface.
The values and time stamps can be read from HMI menu screen 4.4, \REPRT\DEMAND. The values in
the Peak Since Reset registers can be reset by pressing the reset key. The value in the register will be
set to zero and then updated on the next processing loop with the currently calculated demand value. No
write access is required to do this from the HMI. It is also possible to preset a value into the Peak Since
Reset demand registers. This can be done by pressing the edit key, changing the preset value using the
scrolling pushbutton keys, exiting and then saving the settings. Write access to the Reports functional
area is required to do this from the HMI.
The values and time stamps in the demand registers can also be read and reset or preset from the ASCII
command interface using the RD (report demands) command.

RD Command
Purpose: Report all Demand Current data in primary units
Syntax: RD
Comments: RD reports the peak demand, today’s demand and yesterday’s demand for all phase,
neutral, and negative sequence currents.
Example. Read all of the demand registers
RD
RD-PIA=4.2KA 12:30 09/02/97
RD-PIB=4.1KA 15:00 08/30/97
RD-PIC=4.2KA 16:45 09/02/97
RD-PIN=0.2KA 15:00 08/30/97
RD-PIQ=0.2KA 15:00 08/30/97
RD-TIA=3.5KA 08:00 09/05/98
RD-TIB=3.4KA 06:30 09/05/98
RD-TIC=3.4KA 07:45 09/05/98
RD-TIN=0.1KA 06:00 09/05/98
RD-TIQ=0.1KA 15:00 09/05/98
RD-YIA=3.5KA 12:30 09/04/98
RD-YIB=3.4KA 15:00 09/04/98
RD-YIC=3.4KA 16:45 09/04/98
RD-YIN=0.1KA 12:15 09/04/98
RD-YIQ=0.1KA 15:00 09/04/98

RD-PI Command
Purpose: Read/Reset the Peak Since Reset (PI), demand registers in primary units.
Syntax: RD-PI[<p>] [=0]]
Comments: <p> phase=A/B/C/N/Q
RD-PI by itself returns the peak ampere demand of all phases.

NOTE
Unlike the metering function, labels are fixed for the RD command. In the above example
for the RD command and in the following examples, the B phase today’s demand current
is simply reported as RD-TIB=<magnitude> <time stamp>. For more detailed information
on metering commands and labels, see Application, Section 5, Metering.

Example 1. Read the peak ampere demand current on phase B.


RD-PIB
4.1KA 15:00 08/30/95
Example 2. Read peak ampere demand on all phases
RD-PI
RD-PIA=4.2KA 12:30 09/02/95

BE1-CDS Reporting And Alarm Functions 6-7


RD-PIB=4.1KA 15:00 08/30/95
RD-PIC=4.2KA 16:45 09/02/95
RD-PIN=0.2KA 15:00 08/30/95
RD-PIQ=0.2KA 15:00 08/30/95
Example 3. Reset peak demand on all phases
RD-PI=0

RD-TI/YI Command
Purpose: Report Today’s Peak or Yesterday’s Peak Demand registers in primary units.
Syntax: RD-TI[<p>] or RD-YI[<p>]
Comments: <p> phase=A/B/C/N/Q
RD-TI or RD-YI by itself returns the appropriate demand registers for all phase, neutral,
and negative sequence currents.
Example 1. Read today’s ampere demand current on phase B.
RD-TIB
RD-TIB=3.4KA 15:00 09/04/95
Example 2. Read yesterday’s ampere demand on all phases.
RD-YI
RD-YIA=3.5KA 12:30 09/04/95
RD-YIB=3.4KA 15:00 09/04/95
RD-YIC=3.4KA 16:45 09/04/95
RD-YIN=0.1KA 12:15 09/04/95
RD-YIQ=0.1KA 15:00 08/30/95

Overload And Unbalance Alarms Function


The programmable alarms function includes alarm points for monitoring phase demand thresholds for
overload alarms, and neutral and negative sequence demand thresholds for unbalanced loading alarms.
Each time that the current demand register is updated, the value is compared to the appropriate demand
alarm threshold. If the threshold is exceeded, the alarm point is set. See Alarm Functions in this Section
for more information on how to use the programmable alarms reporting function.
The demand alarm thresholds can be set from the ASCII command interface using the SA-DI (setting
alarm, demand current) command or the HMI using screen 6.4.2, \SETUP\DMD\ALARMS. Table 6-5
provides the specifications for the Demand Alarm Threshold settings.
Table 6-5. Demand Alarm Threshold Settings
Range
Setting 5A 1A Increment Unit Of Measure Default
Demand Alarm 0 = disabled 0 = disabled 0.01 for 0.1-9.99 Secondary
Threshold 0.5-16.0 0.1-3.2 0.1 for 10.0-16.0 amperes 0

SA-DI Command
Purpose: Read/Program Demand Current Alarm Settings
Syntax: SA-DI[p][=<demand alarm threshold>]
Comments: where p = P/N/Q.
<demand alarm threshold> see above.
Example. Set demand alarm thresholds to 6 amperes for phase and 3 amperes for neutral and
negative sequence.
SA-DIP=6.0; SA-DIN=3.0; SA-DIQ=3.0

Optional Load Profile Recording


Load profile recording is an optional selection when the BE1-220 CDS is ordered. This option (Load
Profile, 4000 Point Data Array or Y as the third character from the right in the style chart) uses a 4,000
point data array for data storage. Refer to Section 1, General Information, Model And Style Number

6-8 Reporting And Alarm Functions BE1-CDS


Description, for more information on optional selections. At the specified (programmed) interval, Load
Profile takes the data from the demand calculation register and places it in a data array. If the
programmed interval is set to 15 minutes, it will take 41 days and 16 hours to generate 4,000 entries.
Load profile data is smoothed by the demand calculation function. If you made a step change in primary
current, with the demand interval set for fifteen minutes, and the load profile recording interval set for one
minute, it would take approximately fifteen minutes for the load (step change) to reach 90 percent of the
final level. See the previous paragraphs in this Section on Demand Reporting for information on
calculation methods.

Setting The Load Profile Recording Function


For the load profile recording function to log data you must set the demand logging interval. This can be
done from the ASCII command interface using the SG-LOG (setting general, logging interval). Table 6-6
lists the settings for the optional load profile recording.
Table 6-6. Load Profile Recording Settings
Function Range Increment Unit Of Measure Default
Demand Log Interval 0 to 60 1 Minutes 15

SG-LOG Command
Purpose: Read/Set load profile interval
Syntax: SG-LOG[={interval}] where interval is between 1 and 60 minutes
Example. Set the demand logging interval to 12 minutes.
SG-LOG=12

Retrieving The Load Profile Recording Function


Load profile recorded data is reported by the ASCII command interface using the RD-LOG command.
You may request the entire log or only a specific number of entries.

RD-LOG Command
Purpose: Report load profile recording data
Syntax: RD-LOG,<n>
Comments: RD-LOG by itself reports all records in the 4,000 point data array. RD-LOG,23 reports the
last (most recent) 23 records.
In the following load profile recording example (RD-LOG), the CT ratio was set to 120, the current demand
interval (SG-DI) was set to 15, and the load profile logging interval was set to 1. A step change (five
amperes input to phases A, B, and C) was made at 15:15 hours (record 38). At record 24, the load profile
data reached approximately 90 percent of the final level shown in record 1.
>rd-log
Record IA IB IC IN IQ Time Date
1 595 599 599 0 0 15:52 05/04/99
2 595 599 599 0 0 15:51 05/04/99
3 595 599 599 0 0 15:50 05/04/99
4 594 598 598 0 0 15:49 05/04/99
5 594 598 598 0 0 15:48 05/04/99
6 593 597 597 0 0 15:47 05/04/99
7 593 597 597 0 0 15:46 05/04/99
8 592 596 596 0 0 15:45 05/04/99
9 591 595 595 0 0 15:44 05/04/99
10 590 594 594 0 0 15:43 05/04/99
11 589 593 593 0 0 15:42 05/04/99
12 588 591 591 0 0 15:41 05/04/99
13 586 590 590 0 0 15:40 05/04/99
14 584 588 588 0 0 15:39 05/04/99
15 582 586 586 0 0 15:38 05/04/99
16 580 583 583 0 0 15:37 05/04/99
17 577 580 580 0 0 15:36 05/04/99
18 573 577 577 0 0 15:35 05/04/99
19 569 573 573 0 0 15:34 05/04/99

BE1-CDS Reporting And Alarm Functions 6-9


20 565 568 568 0 0 15:33 05/04/99
21 559 563 563 0 0 15:32 05/04/99
22 553 557 557 0 0 15:31 05/04/99
23 546 549 549 0 0 15:30 05/04/99
24 537 541 541 0 0 15:29 05/04/99
25 528 531 531 0 0 15:28 05/04/99
26 516 519 519 0 0 15:27 05/04/99
27 503 506 506 0 0 15:26 05/04/99
28 487 490 490 0 0 15:25 05/04/99
29 469 471 471 0 0 15:24 05/04/99
30 447 450 450 0 0 15:23 05/04/99
31 422 425 425 0 0 15:22 05/04/99
32 393 396 396 0 0 15:21 05/04/99
33 359 362 362 0 0 15:20 05/04/99
34 320 322 322 0 0 15:19 05/04/99
35 274 276 276 0 0 15:18 05/04/99
36 220 222 222 0 0 15:17 05/04/99
37 158 159 159 0 0 15:16 05/04/99
38 85 86 86 0 0 15:15 05/04/99
>

DIFFERENTIAL CURRENT MONITORING FUNCTION


Differential current monitoring is a diagnostic function designed to aid in the installation and
commissioning of transformer banks. This function attempts to identify and prevent false trips due to
incorrect polarity, incorrect angle compensation, or mismatch.
During transformer commissioning, it would be particularly useful to analyze the system installation and
create a record of the settings and measured currents. The differential current monitoring function can
create a differential check record like the sample shown in the following paragraphs. These records are
also useful when comparing the present system characteristics to the characteristics at commissioning. A
differential record is generated automatically when the ASCII interface command RA-DIFF=TRIG (report
alarm-differential, trigger) is issued or when a differential alarm is set. When no alarms are active, you
must use the RA-DIFF=TRIG command to obtain a record of the actual operating conditions.
The following differential check record example was developed from a simulated substation and shows
that there are no problems in the installation or settings. The first part of the record is the date and time
the record was captured and the basic relay identification.
The second part is a record of the CT connections and 87 (differential) settings. These settings may be
entered using the S<g>-87 command. (Refer to Section 3, Input And Output Functions, and Section 4,
Protection And Control, Differential Protection for more information on entering settings that develop both
the second and third parts of the record.)
The third part is a record of the compensation factors. It is important to note that the angle compensation
cannot be entered manually. The angle compensation is calculated by the relay based on the CT and
transformer connections (See Section 3, Input And Output Functions, Setting Up The Current
Measurement Functions, for more information on automatically determining compensation.) Additionally,
the tap compensation setting may be entered manually or automatically calculated (See Section 4,
Protection And Control, 87 Phase Differential Function for more information on auto-tap compensation.)
The fourth part of the record attempts to identify polarity and angle compensation errors by looking at the
phase angle differences of compared phases. The differential alarm is set whenever the minimum pickup
or the slope ratio exceeds the differential alarm, percent of trip setting. If the differential alarm is set and
neither the polarity alarm or angle compensation alarm is set, a mismatch error is identified indicating that
the most likely cause of the alarm is incorrect tap settings. The differential check record needs a specific
amount of secondary current to properly measure phase angles. In 5 ampere relays that amount of
current is 150 milliamperes. In one ampere relays it is 30 milliamperes. If there is not enough current
present to run the algorithm, the message I < 150 ma (or 30 ma) appears in the appropriate alarm
column. Since all phase angles are referenced to A1, no current applied to A1 will cause the I < 150
ma (or 30 ma) message to appear for all phases.

6-10 Reporting And Alarm Functions BE1-CDS


The fifth part (MEASUREMENTS) displays the measured and calculated currents at the time of the
differential record trigger. The relay measures secondary current and develops the tap compensated
currents for use by the differential element. Primary current (MEASURED I PRI) is calculated simply as
the secondary current multiplied by the CT turns ratio. Secondary current (MEASURED I SEC) is the
current actually measured by the relay. Angle compensated current (ANGLE COMPENSATED I) is the
measured secondary current with phase compensation applied. Tap compensated current (TAP COMP I)
is the tap and phase compensated current actually used by the differential function. IOP is the operating
current. SLOPE RATIO is the ratio of IOP to the restraint current (maximum TAP COMP I). The slope
ratio is compared against the differential alarm setting. To generate a differential report and set the
differential alarm (alarm point number 3), two requirements must be met. One, IOP must be above
minimum pickup. Two, the slope ratio must exceed the differential alarm. For example, our settings are
minimum pickup = o.20, slope = 40%, and differential alarm setting = 75%. Seventy-five percent of the
minimum pickup is 0.75 times 0.2 = 0.15. Operating current must be above 0.15 to satisfy requirement
one. When a differential alarm setting of 75% and a slope ratio setting of 40, requirement two is satisfied
when the slope ratio exceeds 30% (0.75 times 40 = 30%). See the following paragraphs on Setting
Differential Current Monitoring Alarms and the associated figure in this Section for more information on
slope ratios.
A new differential report will not be generated unless the slope ratio drops below the differential alarm
setting then increases above the setting. Alternatively, a record can be generated using the RA-
DIFF=TRIG command.
Example 1.
CDS 220 DIFFERENTIAL CHECK RECORD
REPORT DATE : 11/10/98
REPORT TIME : 11:10:08.203
STATION ID : SIMULATED SUBST
RELAY ID : BANK-T1
USER1 ID : TEST1
USER2 ID : TEST1
RELAY ADDRESS : 0
ACTIVE GROUP : 0

87T SETTINGS CTR CT CON TX CON GROUNDED


CT CKT1 240 WYE DAC NO
CT CKT2 400 WYE WYE YES
MINPU 0.20 *TAP
SLOPE 25 %
ALARM 50 %
URO 6 *TAP

COMPENSATION Angle Tap


CT CKT1 WYE 3.12
CT CKT2 DAC 4.68

ALARMS PHASE A PHASE B PHASE C


DIFFERENTIAL: OK OK OK
POLARITY: OK OK OK
ANGLE COMP: OK OK OK
MISMATCH: OK OK OK

MEASUREMENTS PHASE A PHASE B PHASE C


MEASURED I PRI
CT CKT1: 209 @ 0 206 @ 240 206 @ 121
CT CKT2: 528 @ 211 516 @ 91 528 @ 332
MEASURED I SEC
CT CKT1: 0.87 @ 0 0.86 @ 240 0.86 @ 121
CT CKT2: 1.32 @ 211 1.29 @ 91 1.32 @ 332
ANGLE COMPENSATED I
CT CKT1: 0.87 @ 0 0.86 @ 240 0.86 @ 121
CT CKT2: 1.32 @ 181 1.29 @ 61 1.32 @ 302
TAP COMP I
CT CKT1: 0.28 @ 0 0.27 @ 240 0.27 @ 121

BE1-CDS Reporting And Alarm Functions 6-11


CT CKT2: 0.28 @ 181 0.28 @ 61 0.27 @ 302
IOP: 0.01 *TAP 0.01 *TAP 0.01 *TAP
SLOPE RATIO 4 % 4 % 4 %
>
The following differential check record example was developed from the same simulated substation but
has differential alarms caused by the angle compensation. This record shows a 60 degree error between
the compared phases (the angle should be 180 degrees). Notice that in the 87 Settings, the transformer
connection for CT circuit 1 is set to DAB. In trying to compensate for a 30 degree shift, the compensation
shifted the angle the wrong direction and created a 60 degree error. The connection should be DAC.
Example 2.
CDS 220 DIFFERENTIAL CHECK RECORD
REPORT DATE : 11/10/98
REPORT TIME : 10:12:42.701
STATION ID : SIMULATED SUBST
RELAY ID : BANK-T1
USER1 ID : TEST1
USER2 ID : TEST1
RELAY ADDRESS : 0
ACTIVE GROUP : 0

87T SETTINGS CTR CT CON TX CON GROUNDED


CT CKT1 240 WYE DAB NO
CT CKT2 400 WYE WYE YES
MINPU 0.20 *TAP
SLOPE 25 %
ALARM 50 %
URO 6 *TAP

COMPENSATION Angle Tap


CT CKT1 WYE 3.12
CT CKT2 DAB 4.68

ALARMS PHASE A PHASE B PHASE C


DIFFERENTIAL: ALARM ALARM ALARM
POLARITY: OK OK OK
ANGLE COMP: ALARM ALARM ALARM
MISMATCH: OK OK OK

MEASUREMENTS PHASE A PHASE B PHASE C


MEASURED I PRI
CT CKT1: 206 @ 0 202 @ 240 204 @ 121
CT CKT2: 516 @ 211 508 @ 91 516 @ 332
MEASURED I SEC
CT CKT1: 0.86 @ 0 0.84 @ 240 0.85 @ 121
CT CKT2: 1.29 @ 211 1.27 @ 91 1.29 @ 332
ANGLE COMPENSATED I
CT CKT1: 0.86 @ 0 0.84 @ 240 0.85 @ 121
CT CKT2: 1.29 @ 241 1.27 @ 122 1.29 @ 2
TAP COMP I
CT CKT1: 0.27 @ 0 0.27 @ 240 0.27 @ 121
CT CKT2: 0.27 @ 241 0.27 @ 122 0.27 @ 2
IOP: 0.28 *TAP 0.28 *TAP 0.28 *TAP
SLOPE RATIO 104 % 104 % 104 %

Setting Differential Current Monitoring Alarms


The differential function continuously monitors the input current in CT circuits 1 and 2. If a mismatch due
to current loading is approaching the trip level, the differential alarm may be activated. This alarm is alarm
point number three in the relay programmable alarms. The alarm point must be mapped to activate an
alarm and/or light an LED. For more information on mapping the alarm functions, see Alarms Function,
Major/Minor/Logic Programmable Alarms later in this Section. The differential alarm is set as a
percentage of the percentage restrained differential characteristic. See Figure 6-1 for a graph showing the
percentage restrained differential and differential alarm characteristics. To set the differential alarm
6-12 Reporting And Alarm Functions BE1-CDS
threshold level, use the ASCII command interface SA-DIFF (setting alarm, differential) command. This
setting is not available via the front panel HMI.
Table 6-7. Differential Alarm Threshold Setting
Setting Range Increment Unit of Measure Default
Differential Alarm Level 50 to 100 1 Percent 67

SA-DIFF command.
Purpose: Read/Set differential alarm setting
Syntax: SA-DIFF[={alarm level}] where alarm level = Percentage (between 50 and 100)
Example. Set the differential alarm threshold to 75.
SA-DIFF=75

Retrieving Differential Current Monitoring Information


To retrieve the differential check record, use the ASCII command interface RA-DIFF command.
Purpose: Retrieve/trigger differential check record
Syntax: RA-DIFF[=TRIG]
Example. Retrieve the differential check record.
RA-DIFF

Example. Trigger a differential check record.


RA-DIFF=TRIG
3

D2850-15.dwg
OPERATING CURRENT (IN MULTIPLES OF TAP)

05-27-99
2

)
60%
5 TO
= (1
MINIMUM PICKUP
= 0.01 to 1.00 00
TIMES TAP * 1
IOP
= I RES T
R
AL
E ENTI
SL OP
DI FFER
1

D
AINE
E R ESTR
TAG
RCEN
THE PE
% OF
FF = 67
I
SA-D

1 2 3 4 5
RESTRAINT CURRENT (IN MULTIPLES OF TAP)

Figure 6-1. Differential Alarm Characteristics

TRANSFORMER MONITORING
The transformer monitoring functions provide monitoring and alarms for the transformer to help manage
equipment inspection and maintenance expenses. Transformer monitoring functions include through-fault
counter reporting and through-fault current duty monitoring. Each of these functions can be set as a
programmable alarm. See the paragraphs on Alarms Function later in this Section for more information on
the use of programmable alarms.

BE1-CDS Reporting And Alarm Functions 6-13


Number Of Through Faults Monitoring Function
This function monitors the SG-TRIGGER pickup logic expression. It increments the count in the
operations counter register each time that the SG-TRIGGER pickup logic expression is true and returns to
false. For more information on this function and the SG-TRIGGER pickup expression see the illustration
and paragraphs later in this Section on Fault Reporting.

Retrieving Through-Fault Operation Counter Information


The current value of the through-fault operations counter register can be read from HMI screen 4.5.1,
\REPRT\XFORM\STATUS. Pressing the edit key allows the user to enter a number into the register to
preset it to a value if desired. Write access to the reports functional area must be gained to edit this value
at the HMI. The current value of the breaker operations counter can also be read or preset from the ASCII
command interface using the RT-TFCNTR (report transformer, through-fault counter) command.

RT-TFCNTR Command
Purpose: Read/Set transformer through-faults counter
Syntax: RT-TFCNTR [= <# through faults>]
Comments: # through faults = number of through faults recorded (0-99999).

Example. Set relay through-faults counter at 65 through faults.


>RT-TFCNTR=65
The through-fault counter can be monitored to give an alarm when the value exceeds a threshold. See
Transformer Alarms in this Section for more information on this feature.

Transformer Duty Monitoring


The Transformer duty monitoring function accumulates the maximum current in each phase of the
transformer when a through fault occurs. A through fault is defined as whenever the pickup expression
set with the SG-TRIGGER command is true.
Every time the pickup expression in the SG-TRIGGER command is true, the transformer duty monitoring
function updates two sets of registers for each phase of the transformer. (Only the CT selected by the
transformer duty monitoring function (ST-DUTY) is monitored.) In the Accumulated I*t Duty registers,
2
the function adds the maximum measured current in primary-ampere seconds. In the Accumulated I *t
Duty registers, the function adds the maximum measured current squared in primary-ampere seconds.
The t is calculated from the time the pickup expression is true. The user selects which of the two sets of
duty registers are reported and monitored by the function when setting up the mode setting in ST-DUTY.
The value in each set of duty registers is calculated and stored in primary ampere seconds or primary-
amperes squared seconds as appropriate. This value is reported, however, as a percent of maximum.
The user sets the value that the relay will use for 100% duty (DMAX). The value set for maximum duty is
2
used directly for reporting the accumulated I*t Duty registers or I *t Duty registers.
When testing the relay by injecting currents into the relay, the values in the duty registers should be read
and recorded prior to the start of testing. Once testing is complete and the relay is returned to service, the
registers should be reset to the original pre-test values. A block accumulation logic input may be used
when testing so that simulated transformer duty is not added to the duty registers. The BLKTXFMR logic
function is an OR logic term (e.g. - IN1 or VO7) which blocks the transformer monitoring logic when TRUE
(1). BLKTXFMR may be set to zero to disable blocking. When transformer monitoring is blocked (logic
expression is equal to 1), transformer through faults are not counted or accumulated. It should be noted
that even though a BESTlogic logic expression is used to make this setting, this setting is not included in
the Section on BESTlogic settings.

Setting The Transformer Duty Monitoring Function


The transformer monitoring function can be set from the ASCII command interface using the ST-DUTY
(setting transformer, duty) command or the HMI using screen 6.6.1, \SETUP\XFRMR\DUTY. This function
selects the transformer CT to be monitored which also affects the transformer alarm function (SA-TX).
Table 6-8 lists the settings for the transformer duty monitoring function.

6-14 Reporting And Alarm Functions BE1-CDS


Table 6-8. Transformer Duty Monitoring Settings
Setting Range/Purpose Default
Calculation Mode 0=Disabled, 1=equals transformer monitoring enabled with duty calculated 0
as ΣI*t, 2=equals transformer monitoring enabled with duty calculated
as ΣI *t. t = fault clearing time
2

DMAX Range=0 to 4.2e+7, Increment=1, Measured in primary amperes 0e+0


CT# 1=CT number 1, 2=CT number 2 1
Block Logic Logic expression. Logic OR blocks transformer duty accumulation when 0
(BLKTXFMR) true. (This parameter can not be set from the HMI screen 6.6.1.)

ST-DUTY Command
Purpose: Read/set Transformer Duty Operation
Syntax: ST-DUTY[=<mode>,[<DMAX>,<CT#>, <BLKTXFMR logic>]
Comments: Password Access Privilege G or Privilege S required to change settings
CT#= 1 or 2
Example 1. Enable transformer monitoring on CT 2 with duty calculated as ΣI*t, DMAX= 300
operations @ 20 kA with a 100 ms fault clearing time. Block accumulation of duty when
INPUT 5 is energized.
ST-DUTY = 1, 600E3, 2, 1N5
Example 2. Read ST-DUTY
ST-DUTY
2,6.000e+04,2,0

Retrieving Transformer Duty Information


The values currently stored in the accumulated transformer duty registers can be read from HMI screen
4.5.1, \REPRT\XFORM\DETAILS. Pressing the edit key allows the user to enter a number into the
register to preset to a previous value. Write access to the reports functional area is required to edit this
value. These values can also be read and set through the ASCII command interface using the RT-DUTY
(report transformer, duty) command. It should be noted that when reading and writing to these registers,
2
only the set of registers that is selected to be monitored by the mode setting (Accumulated I*t or I *t) and
the CT setting (CT 1 or 2) is affected. The other set of registers is ignored.

RT-DUTY Command
Purpose: Reads or changes the selected (ST-DUTY command) transformer duty log settings.
Syntax: RT-DUTY[p][=<d>]
Comments: p = transformer phase A/B/C.
d = accumulated transformer duty as a percent of DMAX from 0.0 to 200.

Example 1. Read current values of transformer duty log


>RT-DUTY
RT-DUTYA=92%; RT-DUTYB=22%; RT-DUTYC=27%;
Example 2. Reset phase A duty to zero after maintenance has been performed.
>RT-DUTYA=0
The transformer duty registers can be monitored to give an alarm when the value exceeds a threshold.
See Transformer Alarms in this Section for more information on this feature.

Transformer Alarms
The programmable alarms function includes three alarm points for checking transformer monitoring
functions. Each of these alarm points can be programmed to monitor either of the two transformer
monitoring functions (through-fault counter or through-fault duty). That is, you may program an alarm
threshold (limit) to monitor each function. Alternately, you may program three different alarm thresholds to
monitor one of the monitored functions. The transformer alarms may be programmed from the ASCII
BE1-CDS Reporting And Alarm Functions 6-15
command interface using the SA-TX command or the HMI using screen 6.6.2, \SETUP\XFORM\ALARMS.
When [n] in SA-TX[n] is equal to 1, alarm point number one is selected. Likewise for alarm points 2 and 3.
When <mode> is set to 0, the transformer alarm function is disabled. When <mode> is set to 1, the
transformer alarm function is set for percent duty and the alarm limit threshold is set for a percentage of
DMAX which is programmed using the ST-DUTY command. The transformer CT to be monitored is also
programmed using the ST-DUTY command.. When <mode> is set to 2, the transformer alarm function is
set for through faults and the alarm limit threshold is set for the through-fault counter value which when
reached would cause an alarm. The transformer CT to be monitored is programmed using the ST-DUTY
command. Table 6-9 lists the settings for the transformer programmable alarms function.
Table 6-9. Transformer Programmable Alarms Settings
Setting Range/Purpose Default
Mode 0=Disabled, 1=equals transformer alarm function enabled and 0
set for percent duty, 2=equals transformer alarm function
enabled and set for through faults
Alarm Limit (in mode 1) 0 to 100%, Increment=1, Measured in % of DMAX 0
Alarm Limit (in mode 2) 0 to 99999, Increment=1, Number of through faults 0

SA-TX Command
Purpose: Reads/Set transformer alarm settings.
Syntax: SA-TX[n][=<mode>,<alarm limit>]
Comments: [n] = 1, 2, or 3; where 1=alarm point number 1, 2=alarm point number 2, 3=alarm point
number 3

Example. Program alarm point 1 to alarm on 20 through faults, alarm point 2 to alarm on 50% duty,
and alarm point 3 to alarm on 80% duty.
>SA-TX1=2,20
>SA-TX2=1,50
>SA-TX3=1,80

BREAKER MONITORING
Depending on the system scheme, one BE1-CDS relay can provide overcurrent protection for more than
one circuit breaker. However, breaker monitoring functions provide extensive monitoring and alarms for
only a single circuit breaker. This extensive monitoring helps to manage equipment inspection and
maintenance expenses. Breaker monitoring functions include breaker status and operations counter
reporting, breaker fault current interruption duty monitoring, and breaker trip speed monitoring. Each of
these functions can be programmed as a programmable alarm. See Alarm Functions in this Section for
more information on the use of programmable alarms.

Breaker Status Reporting


The breaker status monitoring function monitors the position of the breaker for reporting purposes. It also,
counts the opening strokes of the breaker and records them in the breaker operations counter register.
Setting The Breaker Status Reporting Function
Since the relay is completely programmable, it is necessary to program which logic variable is to be
monitored for breaker status. This is done with the ASCII command interface using the SB-LOGIC
(setting breaker, logic) command. It should be noted that even though a BESTlogic logic expression is
used to make this setting, this setting is not included in the Section on BESTlogic settings. We include it
here because it is related to breaker monitoring. See Section 7, BESTlogic Programmable Logic for more
information on the use of BESTlogic for programming the relay. When you program SB-LOGIC, the
breaker name that you set also labels the 101 virtual breaker control switch. For more information on the
this switch, refer to Section 4, Protection And Control, 101 Virtual Breaker Control Switch. Table 6-10 lists
the settings for the breaker status reporting function.

6-16 Reporting And Alarm Functions BE1-CDS


Table 6-10. Breaker Status Reporting Settings
Setting Range/Purpose Default
Breaker Closed Logic Logic expression. Logic OR term that is TRUE when the 0
breaker is closed (e.g. - 52a logic)
Breaker label 16 character alpha/numerical label BREAKER_LABEL

SB-LOGIC Command
Purpose: Read/set breaker status logic.
Syntax: SB-LOGIC [= <breaker closed logic>,<bkr_label>]

Example. Set the relay to monitor input 3 so that when the input is false, the breaker is closed (52b
contact is wired to input 3) and change breaker label to BREAKER_1.

NOTE
(The NOT symbol (/) is applied to the variable immediately following the symbol.)
>SB-LOGIC = /IN3,BREAKER_1

Retrieving Breaker Status And Operation Counter Information


The current breaker status can be read from HMI screen 1.4.5, \STAT\OPER\BKR, and from the ASCII
command interface using the RG-STAT or RG-BREAKER command. The paragraphs on General Status
Reporting in this Section provide more information on this command.
The current value of the breaker operations counter register can be read from HMI screen 4.3.1,
\REPRT\BRPTS\STATUS. Pressing the edit key allows the user to enter a number into the register to
preset it to a value to match an existing mechanical cyclometer on the breaker mechanism. Write access
to the reports functional area must be gained to edit this value at the HMI. The current value of the
breaker operations counter can also be read or preset from the ASCII command interface using the RB-
OPCNTR (report breaker, operations counter) command.

RB-OPCNTR Command
Purpose: Read/Set breaker operations counter
Syntax: RB-OPCNTR [= <#operations>]
Comments: #operations = number of breaker operations recorded (0-99999).

Example 1. Synchronize the relay breaker operations counter with an external counter reading of 65
operations.
>RB-OPCNTR=65
The breaker operations counter can be monitored to give an alarm when the value exceeds a threshold.
See Breaker Alarms in this Section for more information on this feature.

Breaker Duty Monitoring


The breaker duty monitoring function accumulates the current interrupted in each pole of the circuit
breaker when the breaker opens. Breaker opening is defined by the breaker status monitoring function
(SB-LOGIC). Figure 6-2 shows the breaker status (SB-LOGIC) during a fault and protective trip. Current
flow in the circuit breaker is measured when the SB-LOGIC indicates that the breaker is opening (see
Legend I for Figure 6-2).
Every time the breaker trips, the breaker duty monitoring function updates two sets of registers for each
pole of the breaker. In the Accumulated I Duty registers, the function adds the measured current in
2
primary amperes. In the Accumulated I Duty registers, the function adds the measured current-squared
in primary amperes. The user selects which of the two sets of duty registers are reported and monitored
by the function when setting up the function.
The value in each set of duty registers is stored in primary amperes or primary-amperes squared as
appropriate. The value is reported, however, as a percent of maximum. The user sets the value for
BE1-CDS Reporting And Alarm Functions 6-17
maximum duty or 100% duty (DMAX). The value set for maximum duty is used for reporting the
accumulated I Duty registers as a percent of maximum. The square of the value set for maximum duty is
2
used for reporting the accumulated I Duty registers. Changing DMAX affects the value reported as a
percent of maximum but does not change the accumulated data.
Since the true measure of contact wear includes a factor for arcing time (t), the user should include an
assumed arcing time for the breaker when choosing the setting for 100% interruption duty (DMAX).
When testing the relay by injecting currents into the relay, the values in the duty registers should be read
and recorded prior to the start of testing. Once testing is complete and the relay is returned to service, the
registers should be reset to the original pre-test values. A block accumulation logic input may be used
when testing so that simulated breaker duty is not added to the duty registers. The BLKBKR logic function
is an OR logic term (e.g. - IN1 or VO7) which blocks the breaker monitoring logic when TRUE (1).
BLKBKR is set to zero to disable blocking. When breaker monitoring is blocked (logic expression equals
1), breaker duty is not accumulated.

Setting The Breaker Duty Monitoring Function


The breaker monitoring function can be programmed from the ASCII command interface using the
SB-DUTY (setting breaker, duty) command or the HMI using screen 6.5.1, \SETUP\BKR\DUTY.

SB-DUTY Command
Purpose: Read/set breaker Contact Duty Operation
Syntax: SB-DUTY[=<mode>,<DMAX>,<CT CKT#><BLKBKR logic>]
Comments: Password Access Privilege G or Privilege S required to change settings

Table 6-11. Breaker Duty Monitoring Settings


Setting Range/Purpose Default
Mode 0=Breaker monitoring disabled, 1=Breaker monitoring enabled 0
with duty calculated as ΣI, 2=Breaker monitoring enabled with
duty calculated as ΣI
2

DMAX Maximum duty the breaker contacts can withstand before they 0e+0
need service. DMAX is programmed in primary amperes
using exponential floating point format. The maximum DMAX
setting is 4.2e+7
CT CKT # CT number 1 (1), CT number 2 (2) 2
BLKBKR logic Logic expression. Logic OR term which blocks the breaker 0
duty accumulation when TRUE (1).
Enable breaker monitoring on CT 2 with duty calculated as ΣI , DMAX= 3 operations @
2
Example.
20kA = 60kA max. contact duty. Block breaker duty accumulation when INPUT 7 is false.
SB-DUTY = 2, 60E3, 2,/IN7
Retrieving Breaker Duty Information
The values currently stored in the accumulated interruption duty registers can be read from HMI screen
4.3.1, \REPRT\BRPTS\STATUS. Pressing the edit key allows the user to enter a number into the register
to preset to an previous value. Write access to the reports functional area is required to edit this value.
These values can also be read and set through the ASCII command interface using the RB-DUTY (report
breaker, duty) command. It should be noted that when reading and writing to these registers, only the set
2
of registers that is selected to be monitored by the mode setting (Accumulated I or I ) and the CT setting
(CT 1 or 2) is affected. The other set of registers is ignored.

RB-DUTY Command
Purpose: Reads or changes the contact duty log settings.
Syntax: RB-DUTY[p][=<d>]
Comments: p = breaker pole A/B/C. d = accumulated breaker pole duty as a percent of DMAX from
0.0 to 200.

6-18 Reporting And Alarm Functions BE1-CDS


Example 1. Read the current values of contact duty log
>RB-DUTY
RB-DUTYA=92%; RB-DUTYB=22%; RB-DUTYC=27%;
Example 2. Reset phase A duty to zero after maintenance was performed.
>RB-DUTYA=0
The breaker duty registers can be monitored to give an alarm when the value exceeds a threshold. See
the paragraphs on Breaker Alarms in this Section for more information on this feature.

Breaker Clearing Time Monitoring


The breaker clearing time monitoring function monitors the time from when a trip output occurs (as defined
by the TRIP logic expression) to when the fast dropout current detector detects that current is zero in all
three poles of the breaker (see Legend D for Figure 6-2). Which breaker is monitored is determined by
the CT circuit parameters set in the SB-DUTY function. The output of the breaker clearing time function is
reported as a line in the fault summary reports. It is important to note that if the TRIP logic expression
trips an 86 function and the 86 function trips the breaker, the measured clearing time will not be accurate.
To ensure accuracy, the TRIP logic expression must directly trip the monitored breaker. See the
paragraphs on Fault Reporting Function in this Section for more information on the TRIP logic expression
and the Fault Summary reports.
The breaker clearing time can be monitored to give an alarm when the value exceeds a threshold. See
the following paragraphs on Breaker Alarms for more information on this feature.

Breaker Alarms
The programmable alarms function includes three alarm points for checking breaker monitoring functions.
Each of these alarm points can be programmed to monitor any of the three breaker monitoring functions
(operations counter, interruption duty, or clearing time). That is, you may program an alarm threshold
(limit) to monitor each function. Alternately, you may program three different alarm thresholds to monitor
one of the monitored functions. The breaker alarms can be programmed from the ASCII command
interface using the SA-BKR command or the HMI using screen 6.5.2, \SETUP\BKR\ALARM.
Table 6-12. Breaker Programmable Alarms Settings
Setting Range/Purpose Default
Mode 0=Disabled, 1=equals breaker alarm function enabled and set for 0
percent duty, 2=equals breaker alarm function enabled and set
for number of operations, 3=breaker alarm function enabled and
set for breaker operate time
Alarm Limit (in mode 1) 0 to 100%, Increment=0.01, Measured in % of DMAX which is 0
programmed using the SB-DUTY command. The breaker to be
monitored (CT 1 or CT 2) is also programmed using the SB-
DUTY command.
Alarm Limit (in mode 2) 0 to 99999, Increment=1, Number of operations counter value 0
which when reached would cause an alarm
Alarm Limit (in mode 3) Ranges are 20 to 1000 milliseconds, and 2 to 60 cycles). Setting 0
is reported in milliseconds if less than 1 second, but may be
entered in milliseconds (m), or seconds (s), or cycles (c).

SA-BKR Command
Purpose: Reads/Set breaker alarm settings.
Syntax: SA-BKR[n][=<mode>,<alarm limit>]
Comments: [n] = 1, 2, or 3; where 1=alarm point number 1, 2=alarm point number 2, 3=alarm point
number 3

BE1-CDS Reporting And Alarm Functions 6-19


Example. Program breaker alarm point number 1 for 20 operations, alarm point number 2 to 50%
duty, and alarm point number 3 for slow breaker alarm for clearing times greater than 8
cycles.
>SA-BKR1 = 2, 20
>SA-BKR2 = 1, 50
>SA-BKR3 = 3, 8c

6-20 Reporting And Alarm Functions BE1-CDS


Breaker auxiliary Protective
Protective Protective contact changes element
element element state drops out
picks up trips

SG-TRIGGER
-Trip

-Pickup

-Logic

PU + logic Fast
dropout
Fast dropout current
current detector
detector drops out

Breaker (SB-LOGIC setting)


status

Fault summary
report triggered
A (When SG-TRIGGER (PU or Logic) is TRUE)

B
Targets logged

Fault clearing C (When SG-TRIGGER (PU or Logic) is TRUE)


time calculated

Breaker D
operate time
3 cycle
Post-trigger recording
1/4 to 5 cycles
E
Oscillographic pre-trigger (When SG-TRIGGER (PU or Logic) is TRUE) of pre-trigger Post-trigger
Record (Default: 15 cycle record, 3 cycle pre-trigger, 12 cycle post-trigger) When
SG-TRIGGER
Fault currents F (PU or Logic)
goes FALSE
recorded

Red TRIP LED G (When SG-TRIGGER (PU) is TRUE)


flashing

Red TRIP LED H (When SG-TRIGGER (Trip) is TRUE)


solid

Breaker interruption I
duty

Transformer J (When SG-TRIGGER (PU) is TRUE)


fault duty

Setting group K (When SG-TRIGGER (PU) is TRUE)


change blocked
D2843-19.vsd
05-17-99

Figure 6-2. Protective Fault Analysis


BE1-CDS Reporting And Alarm Functions 6-21
Legend For Figure 6-2:
A. A fault summary report and an oscillographic record is triggered when either the SG-TRIGGER
pickup or logic expression becomes true. These reports are also triggered through the HMI
interface by issuing the ASCII command RF-TRIG.
B. During the time that the SG-TRIGGER trip expression is true, targets are logged from each of the
protective functions that reach a trip state. If a protective function is not being used for tripping
purposes, the associated target function can be disable through the SG-TARG setting.
C. Fault clearing time is calculated to be the duration of the time that either the SG-TRIGGER pickup
or logic expression is true.
D. The breaker operate time is calculated to be the time from when the SG-TRIGGER trip expression
becomes true until the fast dropout current detector detects that the breaker has successfully
interrupted the current in all poles of the breaker.
E. A second oscillographic record is triggered to record the end of the fault if the SG-TRIGGER
pickup or logic trigger expression remains in the true state at the time that the first oscillographic
record ends. This second record will have from ¼ to five cycles of pre-trigger data depending
upon when both the SG-TRIGGER pickup and logic expressions become false.
F. The fault currents are recorded in the fault summary report and on the target screen of the
optional HMI for the power system cycle immediately following the SG-TRIGGER trip expression
becoming true. If the SG-TRIGGER trip expression does not become true, as would occur if the
fault were cleared by a down stream device, the fault current recorded in the fault summary report
will be for the power system cycle ending two cycles before the end of the fault record. This is
also the case if the fault record was triggered through the ASCII command interface by the RF-
TRIG command.
G. During the time that the SG-TRIGGER pickup expression is true, the red TRIP LED on the front of
the relay flashes indicating that the relay is picked-up.
H. During the time that the SG-TRIGGER trip expression is true, the red TRIP LED on the front of the
relay turns on and stays on indicating that the relay is in a tripped state. If targets have been
logged for the fault, the TRIP LED is sealed in until the targets have been reset.
I. The breaker operations and interruption duty functions are driven by the breaker status function.
The operations counter is incremented on breaker opening. The magnitude of the currents that
are used for accumulating breaker duty are recorded for the power system cycle ending when the
breaker status changes state. Thus, breaker duty is accumulated every time that the breaker
opens even if it is not opening under fault.
J. The transformer through fault counter is incremented each time that the SG-TRIGGER pickup
expression returns to false. The time used in calculating It or I2t for transformer through fault
duty monitoring is the time that the SG-TRIGGER pickup expression is true.
K. Setting group changes are blocked when the SG-TRIGGER pickup expression is true to prevent
protective functions from being re-initialized with new operating parameters while a fault is
occurring.

TRIP CIRCUIT MONITOR


The trip circuit voltage and continuity monitoring function monitors the trip circuit for voltage and continuity.
If the breaker is closed or the 86 lockout relay is reset and no voltage is detected across the trip contacts,
then either the fuse supplying the circuit is blown or there is a loss of continuity in the trip coil circuit.
The trip circuit monitor function obtains the breaker status from a programmable setting which is set using
the <status> parameter in the SL-CKTMON command. The detector circuit used by the trip circuit
monitoring function is programmable using the <monitor> parameter in the SL-CKTMON command.
Program one of the contact sensing inputs (e.g. – IN6) as the trip circuit monitor input. The input circuit
draws less than two milliamperes of current through the trip coil when the breaker is closed. Figure 6-3
shows the trip circuit monitor logic.

6-22 Reporting And Alarm Functions BE1-CDS


If the relay detects that the breaker is closed and no
voltage is sensed in the trip circuit after the appropriate Mode = CKTMON
coordination time delay (approximately 500 0-disable
1- enable
milliseconds), the relay sets an alarm bit in the CIRCUIT
programmable alarms function and sets the CKTMON MONITOR
BESTlogic logic variable to true. STATUS

Figure 6-4 shows a typical connection diagram for the MONITOR D2850-12.vsd
circuit monitor. Also, see Section 8, Application, 05-18-99

Application Tips for instructions on how to program a close- Figure 6-3. Trip Circuit
circuit monitoring function in BESTlogic. In this example, Monitor Logic
OUT1 is tripping the lockout relay (86T), IN6 is monitoring
the trip circuit voltage, and IN3 is monitoring the lockout relay status.

Trip Circuit Relay Circuit


+ +
Monitor
Other CDS CDS R
Relays IN6 OUT1 86a

Trip
86a Status

CDS
86T IN3
TC
D2850-13.vsd
06-25-99
- -

Figure 6-4. Trip Circuit Voltage And Continuity Monitor

CAUTION
Applications that place other device inputs in parallel with the breaker trip coil may not
perform as desired. The connection of other devices in parallel with the trip coil causes a
voltage divider to occur when the breaker or trip circuit is open. (Figure 6-5 shows a
schematic representation of the equivalent circuit.) This may cause false tripping of the
other devices and prevent the BE1-CDS trip circuit monitor from reliably detecting an
open circuit. Contact Basler Electric for advice on using this application.
The circuit monitor sensing element has the same rating as the power supply voltage. If
the trip circuit voltage is significantly greater than the power supply voltage (for example,
when using a capacitor trip device), the trip circuit monitor function should not be used.

+
Monitor +
Other CDS CDS V TCM
R
Relays IN6 OUT1 -
Trip
Trip
D2850-14.vsd 52a
06-25-99
52a
+
62X 52TC V 62X
-
-

Figure 6-5. TCM With Other Devices


In Figure 6-5, a 62x auxiliary relay is shown. In this case, the impedance of the 62x coil is small compared
to the impedance of the TCM circuit so the TCM is always at logic 1. This prevents the TCM logic from

BE1-CDS Reporting And Alarm Functions 6-23


working, even if the trip coil is open. Normally, when redundant systems are used, each relay system is
on an individual circuit and the sensing input for each relay system is isolated from the tripping circuit.

Setting The Trip Coil Monitor Function


The TCM function can be programmed from the ASCII command interface using the SL-CKTMON (setting
logic, circuit monitor) command.
Table 6-13. Trip Coil Monitor Function Settings
Settings Range/Purpose Default
Mode 0=Disabled, 1=equals enabled 0
Monitor Logic expression for the input circuit monitoring the trip circuit. 0
Status Logic OR expression that is TRUE when the breaker is closed. 0

SL-CKTMON Command
Purpose: Used to program a logical mode of operation for Trip Coil Circuit Monitor logic settings.
Syntax: SL-CKTMON[=<mode>, <monitor>,<status>,]
Example. Set SL-CKTMON alarm settings using IN6 to monitor the trip circuit and IN3 as the status
input contact.
>SL-CKTMON=1,IN6,IN3

FAULT REPORTING
The fault reporting functions provide for recording and reporting information about faults that have been
detected by the relay. The most basic fault reporting function provided by the relay is targets. In addition,
the relay provides many advanced fault reporting features. These include: Fault Summary Reports,
Sequence of Events Recorder Reports, and Oscillographic Records. Fault Summary Reports and
Oscillographic Records are discussed in the following paragraphs. Sequence of Events Recorder Reports
are covered in the paragraphs for Sequence Of Events Recorder Function in this Section.
Since the relay is completely programmable, it is necessary to use logic expressions to define three
conditions for fault reporting. These conditions are: Trip, Pickup, and Logic trigger. Figure 6-2 illustrates
how each of these logic expressions are used by the various functions of the relay. The Legend for Figure
6-2 describes the events associated with each expression illustrated in the figure. It should be noted that
even though BESTlogic logic expressions are used to define these conditions, these expressions are not
included here. See Section 7, BESTlogic Programmable Logic for more information on the use of
BESTlogic for programming the relay.
Trip
The Trip expression is used by the fault reporting function to start logging targets for an event (see Legend
B for Figure 6-2), and to record the fault current magnitudes at the time of trip event (see Legend F for
Figure 6-2). The Trip expression is used by the HMI function to seal-in the trip LED event (see Legend H
for Figure 6-2) and by the breaker monitoring function to start timing breaker operate time event (see
Legend D for Figure 6-2).
Pickup
The Pickup expression is used by the fault reporting function to time stamp the fault summary record, time
the length of the fault from pickup to drop out (fault clearing time) (see Figure 6-2, Legend C), and to
control the recording of oscillographic data (see Figure 6-2, Legend E). The Pickup expression is used by
the HMI function to control the flashing of the Trip LED event (see Legend G for Figure 6-2). In addition,
this expression is used by the setting group selection function to prevent changing setting groups while a
fault is occurring event (see Figure 6-2, Legend K).

Logic
The Logic Trigger expression is provided to allow the user to trigger the fault reporting function even if the
relay is not picked up. It provides an input to the fault reporting function much as the pickup expression
does. This logic expression is not used by the setting group selection or the HMI function.
6-24 Reporting And Alarm Functions BE1-CDS
Fault recording can also be triggered by the ASCII command interface. This is described in detail in the
discussion of the RF (report fault) command in the paragraphs on Fault Summary Reports in this Section.

Setting The Fault Reporting Function


Fault reporting trigger settings are made via the ASCII command interface using the SG-TRIGGER
(settings general, trigger) command.
Table 6-14. Fault Reporting Function Settings
Function Range/Purpose Default
SG-TRIGGER Trip Logic expression. When this expression becomes TRUE (1), it VO11 +
triggers data recording. BFT
SG-TRIGGER Pickup Logic expression. When this expression becomes TRUE (1), it VO12 +
initiates the pickup timing sequence. BFPU
SG-TRIGGER Logic Logic expression. When this expression becomes TRUE (1), it 2NDHAR +
triggers the fault reporting function. 5THHAR

SG-TRIGGER Command
Purpose: Read/Set Fault reporting trigger logic expressions.
Syntax: SG-TRIGGER[=<TRIP trigger logic>, <PU trigger logic>, <LOGIC trigger logic>]
Comments: The BESTlogic rules for input logic apply to the definition of the <trigger logic> which only
allows OR and NOT operators in the Boolean logic equation.
Example. Set SG-TRIGGER so that Pickup occurs when the protective pickup logic expression
(VO12) is true or when breaker failure pickup is true, Trip occurs when the protective trip
logic expression (VO11) is true or when breaker failure trip is true, and a fault report is
created when second or fifth harmonic restraint is picked up.
>SG-TRIGGER=VO11+BFT,VO12+BFPU, 2NDHAR+5THHAR
Targets
Each protective function listed in Table 6-15 can log target information to the fault reporting function when
a trip condition has occurred (as defined by the trip logic expression) and the trip output of the function
block becomes true (refer to Figure 6-2, Legend B). It is possible to program the relay to define which
protective functions log targets. This might be desirable if a protective function is being used for a
supervisory of monitoring function and not for tripping.
Table 6-15. Protective Functions With Targets
Protective Function Name Default
Percentage restrained phase differential 87R Enabled
Unrestrained phase differential 87U Enabled
Percentage restrained neutral differential 87ND Enabled
Phase instantaneous OC with settable time delay 50TP Enabled
Neutral instantaneous OC with settable time delay 50TN Enabled
Negative sequence instantaneous OC with settable time delay 50TQ Enabled
Second Phase instantaneous OC with settable time delay 150TP Enabled
Second Neutral instantaneous OC with settable time delay 150TN Enabled
Second Negative sequence instantaneous OC with settable time delay 150TQ Enabled
Third Phase instantaneous OC with settable time delay 250TP Enabled
Third Neutral instantaneous OC with settable time delay 250TN Enabled
Third Negative sequence instantaneous OC with settable time delay 250TQ Enabled
Phase inverse time OC 51P Enabled
Neutral inverse time OC 51N Enabled
Negative sequence inverse time OC 51Q Enabled

BE1-CDS Reporting And Alarm Functions 6-25


Protective Function Name Default
Second Phase inverse time OC 151P Enabled
Second Neutral inverse time OC 151N Enabled
Second Negative sequence inverse time OC 151Q Enabled
Third Phase inverse time OC 251P Enabled
Third Neutral inverse time OC 251N Enabled
Third Negative sequence inverse time OC 251Q Enabled
Current supervised breaker failure BF Enabled
General purpose logic timer 62 Off
General purpose logic timer 162 Off

Setting The Targets Function


The target functions can be set from the ASCII command interface using the SG-TARG (setting general,
targets) command. Table 6-16 describes the target settings.
Table 6-16. Target Settings
Setting Range/Purpose Default
Protective function blocks List of protective functions from Table 6-15. Each Per Table 6-15
with targeting enabled protective function is separated by a slash (/).*
Target reset logic expression (+ = OR, / = NOT) Logic expression that resets 0
latched targets when true
* Shorthand notations are also accepted. For example, SG-TARG=50/51,0 selects all 50T and 51
protective elements, e.g. – 50TP/50TN/50TQ/51P/51N/51Q.

SG-TARG Command.
Purpose: Defines which protective functions log targets to the fault reporting function.
Syntax: SG-TARG [ = <protective element1/protective element 2/ etc.>, <reset target logic>]
Example. Set the relay to log targets for 87, breaker failure, all 51 functions and only the phase and
neutral 50T functions.
>SG-TARG=87/BF/51/151/251/50P/50N

Retrieving And Resetting Target Information


Target information can be obtained from the front panel HMI screen 1.1.1, \STAT\TARGETS, or through
the ASCII command interface using the RG-TARG (report general, targets) command. The target
information provided by the relay is from the most recent trip event. It is specific to an event and not
cumulative. The two most recent target reports are stored in non-volatile memory. These two reports are
available from the front panel HMI screen 4.1.1, \REPRT\FAULT\M_REC and 4.1.2,
\REPRT\FAULT\PREV. Targets for previous events are recorded in the fault summary reports which are
described in detail later in this Section.
When the relay trips and targets are logged for the event, the trip LED is sealed-in on the front of the relay
and menu tree branch screen 1.1.1, \STAT\TARGETS, is automatically displayed on the LCD. See
Section 4, Human Machine Interface for more information about the automatic display priority logic. The
display scrolls between the targets, and the fault current magnitudes that were recorded during the fault.
See the paragraphs on Fault Summary Reports in this Section for more information on how these fault
current magnitudes are recorded.
Pressing the Reset Key on the HMI while the target screen is displayed will clear these targets and the trip
LED. No password access is required to reset targets from the front panel. After reset, the two most
recent target reports are still available from the HMI menu branch 4, Reports.
The Reset key of the HMI is context sensitive. That is, the functionality depends upon what screen is
currently being displayed. TRSTKEY is a logic variable that is asserted when the HMI Reset key is
pressed while the target screen is displayed. BESTlogic variable TRSTKEY takes advantage of this to

6-26 Reporting And Alarm Functions BE1-CDS


allow the front panel Reset key on the relay to be used in the programmable logic scheme when the target
screens 1.1.1, (\STAT\TARGETS) is active. An example of the use of this logic variable is to break the
seal-in for a logic expression. The logic expression can be programmed so that the seal-in function uses
a virtual output and the virtual output has the TRSTKEY as an input. When the Reset key is pressed on
the front of the relay while the target screen is displayed, the TRSTKEY logic variable is asserted and the
logic expression seal-in is broken. See Section 8, Application, Application Tips, for more information.
Targets are reset from the front panel HMI (Reset TRSTKEY
pushbutton/key) if the target screen 1.1,
\STAT\TARGETS is active, or through the ASCII
command interface using the RG-TARG (report HMI RESET KEY
general, targets) commands. Figure 6-6 illustrates
Target
the target reset logic.
RG-TARG=0 Reset
The RG-TARG (report general, targets) command Logic
can be used to read and reset the targets. Write Logic
access to Reports must be gained to reset the D2850-10.vsd
06-25-99
targets using the ASCII command interface.
Figure 6-6. Target Reset Logic
RG-TARG Command
Purpose: Reads/Resets the target status.
Syntax: RG-TARG[=0]
Comments:
Example. Read the targets from the ASCII command interface when the instantaneous overcurrent
elements (50 and 150), phases A and N logged targets.
>RG-TARG
50AN; 150AN

Fault Summary Reports


The relay records information about a fault and prepares a fault summary report. A maximum of twelve
fault summary reports are stored in the relay with the two most recent fault summary reports stored in
non-volatile memory. When a new fault summary report is generated, the relay discards the twelfth event
and replaces it with the new one. The fault summary reports are numbered sequentially from 1 to 255.
After event number 255 has been assigned, the numbering starts over at 1. If the PICKUP or LOGIC
trigger expressions stay true for longer than 60 seconds, an alarm bit (FAULT RECORD TIMEOUT) in the
programmable alarm function will be set. In this situation, the fault reporting functions (including targets)
will not operate again until the PICKUP and LOGIC trigger expressions return to a false state to enable
another trigger.

Fault Summary Report Example


The fault summary report collects several items of information about the fault that can aid in determining
what happened without having to go through all of the detailed information available. The following
example illustrates a typical fault summary report. The circled letters shown in the fault summary report
are references to the Legend for Figure 6-2.

Example Fault Summary Report.


RF-1
BE1-CDS FAULT SUMMARY REPORT
A
FAULT DATE : 05/11/98
FAULT TIME : 02:09:58.081
STATION ID : SUBSTATION_1
RELAY ID : BE1-CDS
USER1 ID : USER1_ID
USER2 ID : USER2_ID
RELAY ADDRESS : 65
FAULT NUMBER : 1

BE1-CDS Reporting And Alarm Functions 6-27


FAULT TRIGGER : 51NPU, 51QPU
EVENT TYPE : TRIP
ACTIVE GROUP : 1
B
TARGETS : 51N, 51Q C
FAULT CLEARING TIME : 0.164 sec
BREAKER OPERATE TIME : 0.087 sec D
OSCILLOGRAPHIC REPORTS: 1 E
IA1; IA2 : 1.20kA @ 0; 5.43kA @ 180
IB1; IB2 : 0.40kA @ 240; 2.10kA @ 60
F
IC1; IC2 : 0.40kA @ 120; 2.10kA @ 300
IN1; IN2 : 0.80kA @ 0; 3.33kA @ 0
IQ1; IQ2 : 0.27kA; 1.11kA
IG : 0.00A @ 0

Fault Date and Time. These lines report the date and time of the initial trigger of the event. This is based
upon either the PICKUP logic expression or the LOGIC trigger expression becoming true as defined by
the SG-TRIGGER command. Refer to Figure 6-2, Legend A.

Station ID, Relay ID, User1 ID, and User2 ID. These lines report the identifier information defined by the
SG-ID command.

Relay Address. This line reports the communications port address that the report was requested from.
The SG-COM command is used to assign the relay address and is described in Section 11, ASCII
Command Interface.

Fault Number. This line reports the sequential number assigned to the report by the BE1-CDS.

Fault Trigger. This line reports the logic variables in the PICKUP or LOGIC trigger expressions that
became true to trigger the recording of the event.

Event Type. This line reports the classification assigned to the fault event. Fault events are classified into
five categories:
• BKR FAIL: A fault was detected as defined by the pickup expression and the breaker failure trip
became true before the fault was cleared.
• TRIP: A fault was detected as defined by the trip expression and the relay tripped to clear the
fault.
• PICKUP: A fault was detected as defined by the pickup expression but the relay never tripped
indicating that the fault was cleared by some other device.
• LOGIC: A fault report was recorded by the logic trigger expression but no fault was detected as
defined by the pickup expression.
• RF=TRIG: A fault report was recorded by the ASCII command interface.
Active Group. This line reports what setting group was active at the time that the fault occurred.
Targets. This line reports what targets were logged to the fault report between the time that the trip
expression became true until the end of the fault. Refer to Figure 6-2, Legend B.
Fault Clearing Time. This line reports the time from when the relay detected the fault (as defined by either
the PICKUP or LOGIC Trigger expressions becoming true) until the relay detects that the fault has been
cleared (as defined by both the PICKUP and the LOGIC trigger expressions becoming False). If the fault
report was triggered by the RF=TRIG command this line is reported as NO PICKUP. If the PICKUP or
LOGIC trigger expressions stay true for longer than 60 seconds, an alarm bit (FAULT RECORD
TIMEOUT) in the programmable alarm function will be set.

6-28 Reporting And Alarm Functions BE1-CDS


Breaker Operate Time. This line reports the breaker trip time from the breaker monitoring and alarm
function. This is the time from when the breaker is tripped (as defined by when the TRIP expression
becomes true) until the fast dropout current detector function detects that the arc has been extinguished.
This fast dropout current detector function is also used by the breaker failure function block. If there is no
trip, this line is reported as NO OPERATION. Refer to Figure 6-2, Legend D.
Oscillographic Reports. This line reports the number of oscillographic records that are stored in memory
for this fault report. The recording of oscillographic records is described in detail in this Section under
Oscillographic Records. Refer to Figure 6-2, Legend E.
IA1, IA2, IB1, IB2, IC1, IC2, IN1, IN2, IQ1, IQ2, IG. These lines report the current magnitudes measured
for the power system one cycle after the TRIP trigger logic becomes true. If the fault is cleared prior to the
relay tripping, the fault current magnitudes recorded are for the power system two cycles prior to the end
of the fault (as defined by both the PICKUP and the LOGIC trigger expressions becoming false or the 60
second time out). IG is reported as N/A if the optional independent ground input is not available. Refer to
Figure 6-2, Legend F.

Retrieving Fault Report Information


Fault Summary Directory Report. The fault reporting function provides a directory of fault summary
reports that lists the number assigned to the fault summary report along with the date and time of the fault,
the event type, and the number of oscillography records stored in memory for that event. The number
assigned to the event is important because that number is required to retrieve the information from the
relay for that event. This directory report can be accessed from the ASCII command interface using the
RF command. The following example illustrates a typical fault summary directory report.

RF Command
Purpose: Read/Reset Fault Report Data
Syntax: RF[-<id>NEW][=0/TRIG]
Example Fault Summary Directory Report.
>RF
BE1-CDS FAULT DIRECTORY
REPORT DATE : 05/06/99
REPORT TIME : 02:07:52
STATION ID : SUBSTATION_1
RELAY ID : BE1-CDS
USER1 ID : USER1_ID
USER2 ID : USER2_ID
RELAY ADDRESS : 0
NEW FAULTS : 12 (02:07:39 05/06/99-02:07:50 05/06/99)
TOTAL FAULTS : 12 (02:07:39 05/06/99-02:07:50 05/06/99)
-#- --DATE-- --TIME-- --EVENT TYPE-- --OSC--
036 05/06/99 02:07:50 TRIP 2
035 05/06/99 02:07:49 TRIP 2
034 05/06/99 02:07:49 TRIP 2
033 05/06/99 02:07:48 TRIP 2
032 05/06/99 02:07:47 TRIP 2
031 05/06/99 02:07:47 TRIP 2
030 05/06/99 02:07:46 TRIP 2
029 05/06/99 02:07:45 TRIP 2
028 05/06/99 02:07:45 TRIP 0
027 05/06/99 02:07:42 TRIP 0
026 05/06/99 02:07:41 TRIP 0
025 05/06/99 02:07:39 TRIP 0
>
New Faults Counter. A new faults counter is provided to keep track of how many new fault reports have
been recorded since the new faults counter was reset to 0. This feature allows the user to check the fault
information and then reset the new faults counter. Then, the next time that the relay is checked, it is easy

BE1-CDS Reporting And Alarm Functions 6-29


to determine if any additional fault reports have been recorded. The new faults counter is one line in the
fault summary directory report. It can be reset from the ASCII command interface using the RF-NEW=0
command. Write access to Reports must be gained to reset the new faults counter from the ASCII
command interface. The new faults counter can also be read from HMI screen 4.1. It is not possible to
reset the new faults counter from the HMI.
Fault Summary Reports. Individual Fault Summary Reports can be retrieved from the relay through the
ASCII command interface using the RF-# command (where # represents the number assigned to the fault
summary report). To obtain the most recent fault summary report, it is permissible to enter NEW in place
of the fault report number. The following example report was generated by entering RF-NEW immediately
after creating a fault by entering RF=TRIG. Notice that the FAULT TRIGGER and EVENT TYPE both
show the event was an RF-TRIGGER command. Also, NO PICKUP and NO OPERATION are reported
as described in previous paragraphs.
If additional detail is required, Sequence of Events Recorder data and Oscillographic data can be obtained
for the faults as well. This is discussed in greater detail in the following paragraphs in this Section.
Example New Fault Summary Report.
>RF-NEW
BE1-CDS FAULT SUMMARY REPORT
FAULT DATE : 01/01/99
FAULT TIME : 01:06:32.797
STATION ID : SUBSTATION_1
RELAY ID : BE1-CDS
USER1 ID : USER1_ID
USER2 ID : USER2_ID
RELAY ADDRESS : 0
FAULT NUMBER : 2
FAULT TRIGGER : RF=TRIG
EVENT TYPE : RF=TRIG
ACTIVE GROUP : 0
TARGETS : NONE
FAULT CLEARING TIME : NO PICKUP
BREAKER OPERATE TIME : NO OPERATION
OSCILLOGRAPHIC REPORTS: 1
IA1; IA2 : 0.00A @ 0; 0.00A @ 0
IB1; IB2 : 0.00A @ 0; 0.00A @ 0
IC1; IC2 : 0.00A @ 0; 0.00A @ 0
IN1; IN2 : 0.00A @ 0; 0.00A @ 0
IQ1; IQ2 : 0.00A; 0.00A
IG : 0.00A @ 0

Oscillographic Records

Recording Oscillographic Records


The fault reporting function can record 240 cycles of sample data at 24 samples per cycle for current
inputs IA, IB, IC, and IG. (optional independent ground input). (With the expanded memory option
(Load Profile option Y, 4000 point data array), 480 cycles are possible.) Each oscillographic record length
is determined by the number of partitions programmed. Table 6-17 lists the possible numbers of
oscillographic records for both the standard and expanded memory. For more information on
programming partitions (record lengths), see Oscillographic Records Settings latter in this Section. The
records are formatted to IEEE Standard C37.111, Common Format for Transient Data Exchange
(COMTRADE).
Table 6-17. Possible Oscillographic Records
Number Length In Cycles Length In Cycles
Of Records (Standard Memory) (Expanded Memory)
6 40 80
8 30 60
6-30 Reporting And Alarm Functions BE1-CDS
10 24 48
12 20 40
15 16 32
16 15 30
20 N/A 24
24 N/A 20
32 N/A 15

Each time the fault reporting function starts recording a fault summary report, it freezes a three cycle pre-
fault buffer and records for the length of the record. If the pickup and logic trigger expressions have not
returned to false within that time, the oscillographic recording function records a second record to capture
the end of the fault. The second record records one-forth cycle to five cycles of pre-trigger depending on
when the second record begins. If the second record begins within five cycles of the end of the first
record, then there is no gap in data between the two records. If the second record begins after five
cycles, there will be a gap (some data not recorded) between the records. Refer to Figure 6-2, Legend E.
In that illustration, the number of records was set to 16 which equates to 15 cycles recorded. The first
record is triggered and has three cycles of pre-trigger data and 12 cycles of post-trigger data. The fault
takes longer than 12 cycles to clear so a second record is necessary. The pickup condition drops out
approximately 3.5 cycles into the second record which is the trigger point for the second record. In this
case, the second record will consist of 3.5 cycles of pre-trigger and 11.5 cycles of post-trigger data.
The oscillographic records are stored in volatile memory. As additional faults are recorded, the oldest
oscillographic records are overwritten.

Oscillographic Records Settings


The oscillographic recording function can be programmed from the ASCII command interface using the
SG-OSC (settings general, oscillography) command or the HMI using screen to be determined. See
Table 6-18 for possible settings.
Table 6-18. Recording Oscillographic Records Settings
Setting Range Increment Unit of Measure Default
Number of record Standard Memory: N/A Oscillographic records 16
partitions 6, 8, 10, 12, 15, 16
Expanded Memory:
6, 8, 10, 12, 15, 16, 20, 24, 32

SG-OSC Command
Purpose: Read or program the number of oscillograph fault records saved
Syntax: SG-OSC[=<number of record partitions>]
Retrieving Oscillographic Records
The fault summary directory and the fault summary reports list the numbers assigned to each fault record
and the number of oscillographic records associated with each fault. Oscillographic records can be
retrieved from the ASCII command interface using the RO (report oscillography) command.

RO Command
Purpose: Read Oscillographic COMTRADE .CFG/.DAT Fault Report
Syntax: RO-<n><A/B>[#]<.CFG/.DAT>
Comments: Read only operation.
n = fault number
A = ASCII
B = Binary
# = report identifier. 1 (start fault) or 2 (end fault)
CFG = configuration file
DAT = data file
HDR = Header file

BE1-CDS Reporting And Alarm Functions 6-31


Only one oscillographic report file can be requested at a time. Reports are transmitted in COMTRADE
format. Either a configuration file (CFG), a data file (DAT), or a header file (HDR) can be requested.
Header files contain the fault summary report followed by all the pertinent settings that are associated with
the requested fault record and are available only in ASCII format. These settings include the following.
• BESTlogic settings for User Programmable Logic Scheme.
• User Programmable Label settings, Global I/O settings.
• The protection setting group active during the fault.
• General protection settings.
• Fault reporting settings.
• Breaker Monitoring setttings.
• Alarm settings.
Files can be requested in ASCII or binary format but both file transfers use the same format. Binary file
transfer is much faster and consumes less disk space. ASCII format data is human readable and can be
analyzed by standard text editing software. Software (BESTwave) for IBM compatible computers is
available from Basler Electric to convert binary files to ASCII format.

Configuration and data files can be downloaded using any standard communications program. The
download protocol may be XMODEM or XMODEM CRC format. For ease of reference, use the command
name for the name of the downloaded file.
Example 1. Initiate transfer of the COMTRADE.CFG report for the beginning of fault #155 :
RO-155B1.CFG (for binary) or RO-155A1.CFG (for ASCII)
Example 2. Initiate transfer of the COMTRADE.DAT report for end of fault #155:
RO-155B2.DAT (for binary) or RO-155A2.DAT (for ASCII)

SEQUENCE OF EVENTS RECORDER FUNCTION


The BE1-CDS provides the functionality of a 100+ point Sequence of Events Recorder (SER) by
monitoring the internal and external status of the relay. An SER report is a very useful tool in
reconstructing the exact sequence and timing of events during a power disturbance or even normal
system operations. Data points are scanned every one-quarter cycle and time tagged to one millisecond
resolution. SER data is recorded in volatile memory. When the buffer is full, the oldest event is
overwritten with each new event. In the standard memory version, the SER memory stores 255 events.
This is doubled to 511 events in the expanded memory version (option Y, 4,000 point data array).
The SER function monitors:
• Single state events such as resetting demands or targets, changing settings, etc.
• Programmable logic variables
• Targets
• Relay trouble alarm variables
• Programmable alarm variables
• Output contact status
• Fault reporting trigger expressions
Whenever a monitored event occurs or a monitored variable changes state, the SER recording function
logs the time and date the event occurred, the event or variable name, and the state to which the variable
changed. For the logic variables that are completely user programmable (contact sensing inputs, virtual
switches, and virtual outputs), the user programmable variable name and state names are logged in the
SER report instead of the generic variable name. For more information on programming variable names,
see Section 7, BESTlogic Programmable Logic.

Retrieving SER Information


SER Directory Report. The SER Function provides a directory report that lists the number of events
currently in memory and the time span that it covers. This directory report can be accessed from the
ASCII command interface using the RS (report SER) command.
New Events Counter. A new events counter register is provided to keep track of how many new entries
have been logged to the SER function since the new events counter was reset to zero. This feature

6-32 Reporting And Alarm Functions BE1-CDS


allows the user to check the SER information and then reset the new events counter. Then, the next time
that the relay is checked, it is easy to determine if there are new events that have not been evaluated.
The new events counter is one line in the directory of events report. It can be reset from the ASCII
command interface using the RS=0 command. Write access to Reports must be gained to reset the new
fault counter from the ASCII command interface. The new events counter can also be read from HMI
screen 4.2. It is not possible to reset the new events counter from the HMI.
SER Report. SER reports can be obtained using the ASCII command interface. An SER Directory is
provided by using the RS (report SER) command. There are six subreports in the RS command: RS-n,
RS-Fn, RS-ALM, RS-I/O, RS-LGC, and RS-NEW. These subreports provide specific types of data and do
not bog the user down with all the internal state changes and event occurrences. Events can be retrieved
for the most recent entries by using the RS-n (report SER, number of most recent events) command.
Events can be retrieved for the period of time specific to a fault event by using the RS-F<n> (report SER,
for Fault <event number>) command. The report will include all events within the time span of the fault
plus one event before and after the fault. Alarm variable changes of state since the last RS=0 command
can be retrieved by using the RS-ALM (report SER, alarm) command. This information is also provided by
the RA-SER command. Entering RS-IO provides an SER report of all input and output events since the
last RS=0 command was issued. Entering RS-LGC provides an SER report of all BESTlogic variables
that changed state since the last RS=0 command was issued. Events can be retrieved for the period of
time covered by the New Events Counter register by using the RS-NEW (report SER, new event records
since RS=0 reset) command. RS=0 resets the NEW records counter to zero. See the paragraphs on
Fault Reporting in this Section for more information on RS-Fn.

RS Command
Purpose: Returns information on sequence of events.
Syntax: RS[-<n>/Fn/ALM/IO/LGC/NEW][=0]
Comments: The subreports are as follows:
The time tag associated with each event represents the time that the change was recognized. The SER
update rate time is every one-forth cycle (4.167 milliseconds at 60 hertz).
Example 1. Read the directory report of records
RS<Enter>
BE1-CDS SEQUENCE OF EVENTS DIRECTORY
REPORT DATE :5/11/98
REPORT TIME :10:05:48
STATION ID :CDS_SUBSTATION
RELAY ID :BE1-CDS
USER1 ID :ID1
USER2 ID :ID2
RELAY ADDRESS :10
NEW RECORDS : 15(10:05:05.152 12/17/96 - 10:05:40.676 12/17/96)
TOTAL RECORDS :255(10:03:59.514 12/17/96 - 10:05:40.676 12/17/96)
>
Example 2. Read the last five event records
RS-5<Enter>
BE1-CDS SEQUENCE OF EVENTS RECORD
REPORT DATE :02/02/99
REPORT TIME :09:07:45
STATION ID :BASLER_SUB
RELAY ID :TF_BANK_1
USER1 ID :MAIN_DIFFERENTIAL_PROTECTION
USER2 ID :NA
RELAY ADDRESS :0
--DATE-- ----TIME---- ----------POINT DESCRIPTION---------- --STATUS--
01/13/99 03:55:50.688 PROT-PU NORMAL
251 PHASE PICKUP FALSE
251QPICKUP FALSE
PU TRIGGER FALSE

BE1-CDS Reporting And Alarm Functions 6-33


01/13/99 03:55:50.605 PROT-PU PICKUP
251 PHASE PICKUP TRUE
251QPICKUP TRUE
PU TRIGGER TRUE
12/09/98 13:44:26.240 SETTING CHANGE ALARM MADE
12/08/98 15:00:42.152 101C FALSE
101SC TRUE
12/08/98 15:00:41.940 101C TRUE
>
Example 3. Read SER record associated with fault record 212
>rs-f212
BE1-CDS SEQUENCE OF EVENTS RECORD
REPORT DATE : 01/26/99
REPORT TIME : 19:44:41
STATION ID : XYZ-HYDRO
RELAY ID : BOB-SUBST
USER1 ID : BANK-T7
USER2 ID : 50MVA-115KV/46KV
RELAY ADDRESS : 0
--DATE-- ----TIME---- ----------POINT DESCRIPTION---------- --STATUS--
12/01/98 15:13:17.481 OUTPUT 3 OPEN
12/01/98 15:13:17.356 PROT-PU NORMAL
251 PHASE PICKUP FALSE
PU TRIGGER FALSE
LOW-OC NORMAL
PROT-TRIP NORMAL
TRIP TRIGGER FALSE
12/01/98 15:13:17.281 251 PHASE B TRIP TRUE
LOW-OC TRIP
PROT-TRIP TRIP
OUTPUT 3 CLOSED
TRIP TRIGGER TRUE
12/01/98 15:13:16.417 251 PHASE PICKUP TRUE
PROT-PU PICKDUP
PU TRIGGER TRUE
>

ALARMS FUNCTION
The alarms function provides for monitoring internal relay systems, external relay interfaces, and power
system equipment. The alarm points are segregated into Relay Trouble Alarms and Programmable
Alarms. The status of each alarm point is stored in non-volatile memory so that if the relay is powered
down, it will restore any alarm information that has not been acknowledged and/or reset.
The ability to program the reporting and display of alarms along with the automatic display priority feature
of the HMI provides the relay with the functionality of a local and remote alarm annunciator. See
Section 10, Human-Machine Interface for more information on the automatic display priority logic.

Relay Trouble Alarms


The Relay Trouble Alarms Function is not programmable. All internal circuitry and software that affect the
relay core functionality are monitored by the continuous self-test diagnostics are included in this function.
These are listed in detail in Table 6-19. If any one of these points asserts, the fail safe alarm output relay
is de-energized which closes the OUTA contact, the Relay Trouble LED on the front panel HMI turns ON,
all of the output relays are disabled, internal logic point ALMREL is set, and the relay is taken off line. For
more information on how ALMREL affects the outputs, see the figures with the paragraphs on Outputs, in
Section 3, Input And Output Functions.

6-34 Reporting And Alarm Functions BE1-CDS


If the application requires a normally closed contact that opens to indicate a relay trouble condition, use
BESTlogic to program the output logic. One of the output relays with normally open contacts (OUT1
through OUT6) can be programmed to be held closed. For example, you wish to use OUT5 for indication
of relay trouble on contact opening. Set the logic expression to SL-VO5=/0 (not zero is equal to logic
one). When the relay is fully functional, the OUT5 output contact is closed. Since all output relays are
disabled when a relay trouble alarm condition exists, the contact opens when this condition occurs.
Table 6-19. Relay Trouble Alarms
ID NO. Diagnostic Description
1 RAM FAILURE Static RAM read/write error
2 ROM FAILURE EPROM program memory checksum error
3 uP FAILURE Microprocessor exception or self test error
4 EEPROM FATAL ERR EEPROM fatal read/write error
5 ANALOG FAILURE Analog to digital converter error
6 CALIBRATION ERR Relay not calibrated or calibration checksum error
7 PWR SUPPLY ERR Power supply out of tolerance
8 WATCHDOG FAILURE Microprocessor inoperative
9 SET DFLTS LOADED Relay using setting defaults
10 CAL DFLTS LOADED Relay using calibration defaults
11 DSP FAILURE Digital signal processor error

Relay trouble alarms, except for CALIBRATION ERR, EEPROM FATAL ERR, SET DFLTS LOADED, and
CAL DFLTS LOADED indicate that the relay is not functional and causes the self-test diagnostics to force
a microprocessor reset to try to correct the problem.
A CALIBRATION ERR, EEPROM FATAL ERROR, or CAL DFLTS LOADED error indicates that the relay
is functional, but needs re-calibration or the settings reprogrammed.
If a relay trouble (RA-REL) alarm is cleared using RA=0, RA-REL=0, or pressing the RESET key from a
STAT\ALARMS ALARM screen, then the relay will attempt a recovery to return the relay back on-line by
issuing a software reset. The relay will reset by going through a full startup and initialization cycle. If no
problems are discovered, the protection will be enabled and the relay will return on-line.

Major/Minor/Logic Programmable Alarms.


The Programmable Alarms Function covers all circuits monitored by the continuous self test diagnostics
function that do not affect the relay core functions. The Programmable Alarms Function also covers all
alarm functions used to monitor the power system and equipment. The programmable alarms are listed in
detail in Table 6-20. The programmable alarm points can be prioritized into Major and Minor Alarms from
the ASCII command interface using the SA-MAJ (setting alarms, major) and SA-MIN (setting alarms,
minor commands. Alarms set to be monitored as Major Alarms cause the Major Alarm LED on the front
panel to light and the BESTlogic variable ALMMAJ to assert. Alarms set to be monitored as Minor Alarms
cause the Minor Alarm LED on the front panel to light and the BESTlogic variable ALMMIN to assert.
The output of any of the programmable alarm functions can also be used in programmable logic
expressions without being programmed to be reported by the programmable alarm reporting function. The
ALMLGC logic variable is provided for this purpose. Programmable alarm variables can be masked to
drive BESTlogic variable ALMLGC from the ASCII command interface using the SA-LGC command.
Table 6-20. Programmable Alarms
ID NO. Name Description
1 OUTPUT CKT OPEN Output circuit continuity monitor alarm (See the following
ALARM* paragraphs on Circuit Monitor Alarm for a circuit description.)
2 BKR FAIL ALARM Breaker Failure Trip
3 DIFFERENTIAL ALARM Differential threshold exceeded
4 ACCESS LOST ALARM Access lost
5 BREAKER ALARM 1 Breaker Alarm 1 threshold (SA-BKR1 setting) exceeded
6 BREAKER ALARM 2 Breaker Alarm 2 threshold (SA-BKR2 setting) exceeded
BE1-CDS Reporting And Alarm Functions 6-35
ID NO. Name Description
7 BREAKER ALARM 3 Breaker Alarm 3 threshold (SA-BKR3 setting) exceeded
8 P DEMAND ALARM* Phase Demand Alarm
9 N DEMAND ALARM* Neutral Demand Alarm
10 Q DEMAND ALARM* Excessive negative sequence unbalance alarm
11 GROUP OVERRIDE* Setting Group Override in effect
12 SYS I/O DELAY Excessive Delay in operation of HMI or Serial Communications
13 COMM ERROR ALARM Communications Failure
14 CLOCK ERROR* Real time clock has not been set
15 uP RESET ALARM Microprocessor has been reset
16 SETTINGS CHANGED Settings Change made by User
17 EE NON-FATAL ERR EEPROM non-fatal recoverable error
18 OUTPUT OVERRIDE* An override condition is active in one or more outputs
19 LOSS OF IRIGB* Loss of IRIG sync
20 SGC ACTIVE Setting Group Change Alarm Active
21 VO13 LOGIC ALARM* VO13 logic is TRUE. (User programmable logic alarm.)
22 VO14 LOGIC ALARM* VO14 logic is TRUE. (User programmable logic alarm.)
23 VO15 LOGIC ALARM* VO15 logic is TRUE. (User programmable logic alarm.)
24 FLT RPT TIMEOUT True if fault event trigger lasts longer than 60 seconds
25 TRANSFORMER ALARM 1 Transformer Alarm 1 threshold (SA-TX1 setting) exceeded
26 TRANSFORMER ALARM 2 Transformer Alarm 2 threshold (SA-TX2 setting) exceeded
27 TRANSFORMER ALARM 3 Transformer Alarm 3 threshold (SA-TX3 setting) exceeded
28 LOGIC=NONE No logic selected.
Note To Table 6-20: Alarms with a asterisk (*) are Non-latching. A Non-latching alarm will clear itself
automatically when the alarm condition goes away. All other alarms are latching and must be manually
reset by the operator using the front panel RESET button or the RA=0 command.

Programming Alarm Priorities


The alarm settings include Major, Minor, and Logic Alarm Priorities, the demand alarm points, the
transformer duty, and the breaker alarm points. Alarm priorities can be set through the ASCII command
interface using SA-MAJ, SA-MIN, and SA-LGC commands. Details on programming the Demand and
Breaker Alarm points is included in this Section in the paragraphs on the Demand Functions, Transformer
Monitoring Functions, and Breaker Monitoring Functions. Table 6-21 describes the programmable alarm
priorities settings.
Table 6-21. Programmable Alarm Priorities Settings
Setting Range/Purpose Default
Major alarm points (drives List of alarm functions per Table 6-20 3/28
Major Alarm LED and Separated by forward slash (/)
ALMMAJ logic variable)
Minor alarm points (drives List of alarm functions per Table 6-20 4
Minor Alarm LED and Separated by forward slash (/)
ALMMIN logic variable)
Logic alarm points (drives List of alarm functions per Table 6-20 0
ALMLGC logic variable) Separated by forward slash (/)

SA-MAJ/MIN/LGC Command
Purpose: Read/Enable Alarms settings
Syntax: SA[-<type>][=[<alarm num 1>][/<alarm num 2>]...[/<alarm num n>]]

6-36 Reporting And Alarm Functions BE1-CDS


Comments: type = MAJ (Major), MIN (Minor), or LGC (Logic)
Example. Set the Major Alarm to monitor when breaker failure occurs, when the trip circuit voltage
and continuity monitor asserts, and when virtual output VO15 is true.
>SA-MAJ=1/2/23

Retrieving And Resetting Alarm Reports


Alarm information can be obtained from the front panel HMI screen 1.2.1, \STAT\ALARMS\DETAILS, or
through the ASCII command interface using the RA (report alarms) and RG-STAT (report general, status)
commands.
When an alarm condition occurs, the relay lights the appropriate LED on the front of the relay and
automatically displays the menu tree screen 1.2, \STAT\ALARMS. See Section 10, Human-Machine
Interface for more information on the automatic display priority logic. The HMI display scrolls between
displaying all alarm points that are currently active including alarms that are not programmable (relay
trouble alarms).
The Reset key of the HMI is context sensitive. That is, the functionality depends upon what screen is
currently being displayed. BESTlogic variable ARSTKEY takes advantage of this to allow the front panel
Reset key on the relay to be used in the programmable logic scheme when the alarm screens 1.2,
(\STAT\ALARMS) is active. An example of the use of this logic variable is to break the seal-in for a logic
expression. The logic expression can be programmed so that the seal-in function uses VO13, VO14, or
VO15. If the virtual output expression is included in one of the programmable alarm masks, the automatic
display priority logic will cause the display to go to the alarm screens 1.2, (\STAT\ALARMS). When the
Reset key is pressed on the front of the relay, the ARSTKEY
ARSTKEY logic variable is asserted and the logic Figure 6-7. Programmable Alarm Function
expression seal-in is broken. See Section 8, HMI RESET KEY
Alarm
Application, Application Tips, for more information. RA-MAJ=0
Pressing the Reset key on the HMI while the alarm RA-MIN=0 Reset
screen is displayed will clear any latched alarms that Logic
Logic D2850-09.vsd
are not currently active. Refer to Table 6-20 for a 06-29-99

listing of alarm points that are latching and those that are self clearing. Figure 6-7 shows the alarm reset
logic.
The status of the three alarm LEDs can be read from the ASCII command interface using the RG-STAT
(report general, status) command.
The RA (report alarms) command can be used to read detailed alarm reports and reset latched alarms.

RA Command
Purpose: Reads and resets Major, Minor, Logic, and Relay Trouble alarm status.
Syntax: RA[-<type>][=0]
Comments: type = LGC (Logic), MAJ (Major), MIN (Minor), or FAIL (Failure)
RA Command Examples

Example 1. Read current alarm status.


>RA
RA-LGC ALARM# 3 – DIFFERENTIAL ALARM
RA-MAJ ALARM# 25 – TRANSFORMER ALARM 1
RA-MIN ALARM# 21 - TEST_ON
RA-FAIL NONE
>
Example 2. Clear the latched minor alarm.
>RA-MIN=0
Example 3. Clear latched diagnostic errors
>RA=0

BE1-CDS Reporting And Alarm Functions 6-37


Links Between Programmable Alarms Function And BESTlogic Programmable Logic
There are several links between the Programmable Alarms Function and BESTlogic Programmable Logic.
These links allow alarm functions to be used in the logic scheme and programmable logic functions to be
used in the alarm reporting function.

Links From BESTlogic To The Programmable Alarms Function.


Virtual Outputs VO13, VO14, and VO15 are driven by BESTlogic expressions. These three logic variables
are also available in the programmable alarm function. The virtual outputs also have the capability of
being assigned user programmable labels. This allows the user to design a logic condition that is to be
used for an alarm and assign a label to it that will be reported in the alarm reporting function. See Section
7, BESTlogic Programmable Logic for more details on setting logic expressions and programmable
variable names.

Programming Alarms Reset


The programmable alarms are reset when the programmable alarms reset logic expression becomes
TRUE. Logic expression variables may include virtual inputs, logic module outputs, and virtual outputs.
Only the OR (+) operator may be used with the variables. Alarms may be reset from the front panel HMI
(Reset pushbutton/key) if the alarm screen 1.2, \STAT\ALARMS is active (ARSTKEY), or through the
ASCII command interface using the SA-RESET (setting alarm, reset), RG-MAJ (report general, major
alarm), or RG-MIN (report general, minor alarm) commands.
Table 6-22. Programming Alarm Reset
Function Range/Purpose Default
Alarm reset logic (+ = OR, / = NOT) Logic expression that resets latched alarms 0
expression when true
SA-RESET Command
Purpose: Reads or programs reset logic for programmable alarms.
Syntax: SA-RESET[=<rst alm logic>]
Comments: Privilege G or S password access is required to change settings.

Example. Reset the programmable alarms when contact input three or four becomes TRUE.
>SA-RESET=IN3+IN4
Links From The Programmable Alarms Function To BESTlogic
The programmable alarm settings for Major, Minor, and Logic alarms drive BESTlogic variables ALMMAJ,
ALMMIN, and ALMLGC. These variables can be used in logic expressions to control logic when the alarm
is active. An example of this is to use these variables to actuate an output relay to signal a SCADA RTU
that an alarm condition exists.

HARDWARE AND SOFTWARE VERSION REPORT


The hardware and software version reporting function is used to determine what style chart selections are
included in the relay, the relay serial number, and what embedded software (firmware) version is in the
relay.
The style chart and serial number information is contained on the label on the front of the relay. The
embedded software information can be obtained on HMI screen 4.6, \REPRT\VERSION. This screen is
also momentarily displayed during the boot-up sequence after the microprocessor is reset.
From the ASCII command interface, a software and hardware version report is obtained by using the
RG-VER (report general, version) command.

RG-VER Command
Purpose: Provides information about relay hardware/software configuration
Syntax: RG-VER

6-38 Reporting And Alarm Functions BE1-CDS


Comments: Reports the relay model number, style number, application program version, digital signal
processor program version, boot program version, and serial number.
No password privileges are required to read status information.

Example. Request the hardware and software version report


>RG-VER
Model Number : BE1-CDS220
Style Number : E0EN0YYOYOH
App Program : VER 1.14.01 07/18/00
DSP Program : VER 1.14.00 02/07/2000
Boot Program : VER 2.11 06/21/99
Serial Number : H00015713

BE1-CDS Reporting And Alarm Functions 6-39


SECTION 7 • BESTlogic PROGRAMMABLE
LOGIC

TABLE OF CONTENTS

List Of Figures......................................................................................................................................... i
List Of Tables .......................................................................................................................................... i
SECTION 7 • BESTLOGIC PROGRAMMABLE LOGIC...........................................................................7-1
GENERAL...............................................................................................................................................7-1
WORKING WITH PROGRAMMABLE LOGIC........................................................................................7-1
Function Element Logic Settings ........................................................................................................7-5
Output Logic Settings..........................................................................................................................7-5
Defining Output Operation.............................................................................................................................. 7-5
Virtual and Hardware Outputs ........................................................................................................................ 7-6
LOGIC SCHEMES..................................................................................................................................7-6
The Active Logic Scheme ...................................................................................................................7-6
Custom Logic Schemes ......................................................................................................................7-8
Copying and Renaming Preprogrammed Logic Schemes .................................................................7-8
Creating Or Customizing A Logic Scheme .........................................................................................7-9
Debugging The Logic Scheme .........................................................................................................7-10
USER INPUT AND OUTPUT LOGIC VARIABLE NAMES ..................................................................7-10
BESTLOGIC APPLICATION TIPS..........................................................................................................7-10

List Of Figures
Figure 7-1. BESTlogic Function Elements ................................................................................................7-2
Figure 7-2. BESTlogic Function Elements – Continued ...........................................................................7-3

List Of Tables
Table 7-1. Logic Variable Names And Descriptions .................................................................................7-4
Table 7-2. SN Command Settings ..........................................................................................................7-10

BE1-CDS BESTlogic Programmable Logic i


SECTION 7 • BESTlogic PROGRAMMABLE
LOGIC
GENERAL
Multifunction relays are similar in nature to a panel of single-function protective relays. Both must be
wired together with ancillary devices to operate as a complete protection and control system. In the
single-function static and electromechanical environment, elementary diagrams and wiring diagrams
provide direction for wiring protective elements, switches, meters, and indicator lights into a unique
protection and control system. In the digital, multifunction environment, the process of wiring individual
protection or control elements is replaced with the entry of logic settings. The process of creating a logic
scheme is the digital equivalent of wiring a panel. It integrates the multifunction protection, control, and
input/output elements into a unique protection and control system.
BESTlogic is a programming method used for managing the input, output, protection, control, monitoring,
and reporting capabilities of Basler Electric’s digital, multifunction, protective relay systems. Each relay
system has multiple, self-contained function elements that have all of the inputs and outputs of its
discrete component counterpart. Each independent function element interacts with control inputs, virtual
outputs, and hardware outputs based on logic variables defined in equation form with BESTlogic.
BESTlogic equations entered and saved in the relay nonvolatile memory integrate (electronically wire) the
selected or enabled protection and control elements with control inputs, virtual outputs, and hardware
outputs. A group of logic equations defining the function of the multifunction relay is called a logic
scheme.
Several preprogrammed logic schemes are stored in relay memory. Each scheme is configured for a
typical protection application and virtually eliminates the need for start-from-scratch programming. Any of
the preprogrammed schemes can be copied and saved as the active logic. Preprogrammed logic
schemes can also be copied and then customized to suit your application. Detailed information about
preprogrammed logic schemes is provided later in this section.
BESTlogic isn’t used to define the operating settings (pickup thresholds and time delays) of the individual
protection and control functions. Operating settings and logic settings are interdependent, but separately
programmed functions. Changing logic settings is similar to rewiring a panel, and is separate and distinct
from making the operating settings that control the pickup thresholds and time delays of a relay. Detailed
information about operating settings is provided in Section 4, Protection and Control Functions.

WORKING WITH PROGRAMMABLE LOGIC


BESTlogic uses two types of logic settings: output logic settings and function element logic settings.
These two types of settings are discussed in the following paragraphs. Output logic settings are entered
in equation form and control the hardware outputs of the relay. BESTlogic function elements are
illustrated in Figures 7-1 and 7-2 and are discussed in the following paragraphs.
Names assigned to inputs, outputs, timers, and protection and control elements represent the logic
variables in the equations. Table 7-1 lists the logic variable names and descriptions.

BE1-CDS BESTlogic Programmable Logic 7-1


87RPU Mode PHASE 150TPT
Mode =
0-disable IOC
BLK 150TPPU
1-ctckt 1 PHASE (150TP)
87RT
Mode = PERCENT 2-ctckt 2 IOC
(50TP) 50TPT
0-disable DIFF 150TNT
1-enabled Mode NEUTRAL
with 87UT BLK 50TPPU IOC
Harmonic BLK 150TNPU
(150TN)
Restraint
(87) 2NDHAR
BLK Mode =
Mode NEG SEQ 150TQT
0-disable
1-ctckt 1 NEUTRAL IOC
5THHAR BLK 150TQPU
2-ctckt 2 IOC (150TQ)
G-ground (50TN) 50TNT

Mode = BLK 50TNPU 250TPT


Mode PHASE
0-disable 87NDT IOC
1- G vs. N1 PERCENT BLK 250TPPU
(250TP)
2- G vs. N2 NEUTRAL
Mode =
DIFF 87NDPU
BLK 0-disable 250TNT
(87ND) NEG SEQ Mode NEUTRAL
1-ctckt 1
IOC IOC
2-ctckt 2 50TQT BLK 250TNPU
(50TQ) (250TN)
BLK 50TQPU
Mode NEG SEQ 250TQT
IOC
BLK 250TQPU
(250TQ)

Mode =
0-disable
1-ctckt 1
2-ctckt 2 BREAKER BFT 151PT
Mode = Mode PHASE
FAILURE
0-disable TOC
INI (BF) BLK 151PPU
1-ctckt 1 PHASE (151P)
2-ctckt 2 TOC
BLK BFPU 51PT
(51P)
Mode NEUTRAL 151NT
BLK 51PPU TOC
BLK 151NPU
(151N)

Mode =
Mode = CKTMON Mode NEG SEQ 151QT
0-disable
0-disable TOC
1-ctckt 1 NEUTRAL BLK 151QPU
1-enable (151Q)
2-ctckt 2 TOC
STATUS CIRCUIT G-ground (51N) 51NT
MONITOR
BLK 51NPU Mode PHASE 251PT
MONITOR
TOC
BLK 251PPU
(251P)

Mode =
0-disable Mode NEUTRAL 251NT
NEG SEQ
1-ctckt 1 TOC
TOC BLK 251NPU
2-ctckt 2 51QT (251N)
Mode = (51Q)
0-disable ALMMAJ BLK 51QPU
1-enable Mode NEG SEQ 251QT
ALMMIN TOC
RSTALM ALARMS BLK 251QPU
(251Q)
ALMLGC
RSTTARG

BLK D2857-17.vsd
11-02-99

Figure 7-1. BESTlogic Function Elements

7-2 BESTlogic Programmable Logic BE1-CDS


Mode =
Mode = Mode = 101T 0-disable
0-disable 0-disable 1-pickup/dropout
1-on/off/pulse 1-enable 2-1shot nonretrig
2-on/off 101C
3-off/momentary on 101 3-1shot retrig
BREAKER 4-oscillator
43 CONTROL
43 AUX SWITCH 5-integrating 62 TIMER
SWITCH
CO-101 =
CO-43 = 101SC 6-latch
T-trip
0-off C-close
1-on INI
P-pulse 62
BLK

Mode Mode
143
143 AUX SWITCH Mode =
CO-143= 0-disable SG0 INI
1-discrete select
162 TIMER
162
2-binary select ACTIVE SG1 BLK
Mode SETTING
243
243 AUX SWITCH GROUP
D0 SG3
CO-243= CONTROL
D1
D2 SG3
Mode D3
343 ARSTKEY
343 AUX SWITCH AUTO
CO-343=
HMI
TRSTKEY

Mode
443
443 AUX SWITCH
CO-443=

Mode VOA
543
543 AUX SWITCH VO7
CO-543=
CO-OUTA =
OUTPUT OUT VO8
0-off
Mode LOGIC A
1-on
643
643 AUX SWITCH P-pulse VO9
CO-643= L-logic
VO10

Mode
743 VO1 VO11
743 AUX SWITCH
OUTPUT OUT
CO-743=
LOGIC 1 VO12
CO-OUT1

VO13
VO2
+ OPTO IN1
OUTPUT OUT VO14
ISOLATION
- LOGIC 2
CO-OUT2
VO15
+ OPTO IN2
ISOLATION
- VO3
OUTPUT OUT
+ OPTO IN3 LOGIC 3
CO-OUT3
ISOLATION
-

+ VO4
OPTO IN4
ISOLATION OUTPUT OUT
- LOGIC 4
CO-OUT4
+ OPTO IN5
ISOLATION VO5
-
OUTPUT OUT
+ OPTO IN6 LOGIC 5
CO-OUT5
ISOLATION
-

+ OPTO IN7
ISOLATION VO6
- OUT6
OUTPUT
LOGIC
+ OPTO IN8 CO-OUT6
ISOLATION D2857-18.vsd
- 08-01-00

Figure 7-2. BESTlogic Function Elements – Continued

BE1-CDS BESTlogic Programmable Logic 7-3


Table 7-1. Logic Variable Names And Descriptions
Variable Description Variable Description
Name Name
Input And Output Logic Variables Breaker Failure Logic Variables
IN1-8 Input1-8 Status (IN1-8) BFT Breaker Failure Tripped
VOA Relay Trouble Alarm Output BFPU Breaker Failure Picked-Up
VO1-VO6 Virtual Output 1-6 (Drives Hardware Instantaneous Overcurrent Logic Variables
Outputs 1-6) 50TPT 50T Phase Tripped
VO7-VO15 Virtual Output 7-15 50TPPU 50T Phase Picked-Up
Control Logic Variables 50TNT 50T Neutral Tripped
ARSTKEY HMI Alarm Reset Key 50TNPU 50T Neutral Picked-Up
TRSTKEY HMI Target Reset Key 50TQT 50T Negative Sequence Tripped
101T Virtual Breaker Control Switch Trip 50TQPU 50T Negative Sequence Picked-Up
Output
101C Virtual Breaker Control Switch Close 150TPT 150T Phase Tripped
Output
101SC Virtual Breaker Control Switch Slip 150TPPU 150T Phase Picked-Up
Contact Output
62 62 Timer Output 150TNT 150T Neutral Tripped
162 162 Timer Output 150TNPU 150T Neutral Picked-Up
43 Virtual Switch 43 Output 150TQT 150T Negative Sequence Tripped
143 Virtual Switch 143 Output 150TQPU 150T Negative Sequence Picked-Up
243 Virtual Switch 243 Output 250TPT 250T Phase Tripped
343 Virtual Switch 343 Output 250TPPU 250T Phase Picked-Up
443 Virtual Switch 443 Output 250TNT 250T Neutral Tripped
543 Virtual Switch 543 Output 250TNPU 250T Neutral Picked-Up
643 Virtual Switch 643 Output 250TQT 250T Negative Sequence Tripped
743 Virtual Switch 743 Output 250TQPU 250T Negative Sequence Picked-Up
SG0 Setting Group 0 Act (Default Group) Time Overcurrent Logic Variables
SG1 Setting Group 1 Active 51PT 51 Phase Tripped
SG2 Setting Group 2 Active 51PPU 51 Phase Picked-Up
SG3 Setting Group 3 Active 51NT 51 Neutral Tripped
Monitor Logic Variables 151PT 151 Phase Tripped
ALMLGC Logic Alarm 151PPU 151 Phase Picked-Up
ALMMAJ Major Alarm 151NT 151 Neutral Tripped
ALMMIN Minor Alarm 151NPU 151 Neutral Picked-Up
CKTMON Monitor Circuit Continuity 151QT 151 Negative Sequence Tripped
Percent Differential Logic Variables 151QPU 151 Negative Sequence Picked-Up
87RPU 87 Restrained Picked-Up 251PT 251 Phase Tripped
87RT 87 Restrained Trip 251PPU 251 Phase Picked-Up
87UT 87 Unrestrained Trip 251NT 251 Neutral Tripped
2NDHAR Second Harmonic Status 251NPU 251 Neutral Picked-Up
5THHAR Fifth Harmonic Status 251QT 251 Negative Sequence Tripped
87NDPU 87ND Picked-Up 251QPU 251 Negative Sequence Picked-Up
87NDT 87ND Trip

7-4 BESTlogic Programmable Logic BE1-CDS


Function Element Logic Settings
Each function element is equivalent to its discrete device counterpart. For example, the phase
percentage differential function element in the BE1-CDS relay shown in Figure 7-1, has many of the
characteristics of a BE1-87T transformer differential relay.
Before using a protection or control function element, two items must be set: the Mode and the Input
Logic. Setting the Mode is equivalent to deciding which protection or control functions will be used in a
logic scheme. The Input Logic establishes control of a function element.
Mode and input logic information is contained in logic setting command strings. Depending on the
command, the mode setting can either enable or disable a logic input or determine how a function
element operates. Input logic defines which logic variables control or disable a logic function. An
example of an input logic equation is SL-87=1,IN2. In this differential logic command string, the 1
parameter indicates that the 87 function is enabled. The IN2 expression indicates that the 87 function will
be blocked when input two goes TRUE.
The AND operator may not be applied to the terms of an input logic equation. Any number of variables or
their inverse can be combined in a function element input logic expression. Section 4, Protection and
Control provides detailed information about setting the logic for each function element.

Output Logic Settings


Defining Output Operation
Output operation is defined by Boolean logic equations. Each variable in an equation corresponds to the
current state (evaluated every quarter cycle) of an input, output, or timer. Figure 1-2 illustrates this
relationship. Every quarter cycle, output expressions are evaluated as TRUE or FALSE. If a logic output
that corresponds to a hardware output changes state, then the corresponding output relay contact also
changes state.

When the relay is powered up, all logic outputs are disabled and most variables (including virtual outputs)
initialize as FALSE. Some variable states are stored in EEPROM and are restored to the last state prior
to loss of power. These variables include 43/143/243/343/443/543/643/743,101SC, and SG0 through
SG3. All control commands, including logic override control, are also stored in EEPROM. If you override
output logic and force an output to open, that condition will be maintained even if operating power is
cycled.
When the logic is running and logic expression SL-VO[n] is FALSE, then output VO[n] = 0. When the
logic is running and logic expression SL-VO[n] is TRUE, then VO[n] = 1. Hardware outputs OUTA and
OUT1 through OUT5 follow the corresponding logic outputs VOA and VO1 through VO6.
Logic equations are defined by logic variables, logic operators, and their position in an equation. The
available logic operators include AND (9), OR (+), and NOT (/). The NOT operator is applied to the
variable immediately following the symbol (/). For virtual output equations, OR logic can be applied to
any number of variables if no AND logic is used in the expression. Similarly, AND logic can be applied to
any number of variables if no OR logic is used. Any number of NOT operators may be used. For
complex expressions that use both AND and OR operators, OR logic is limited to four terms. Up to four
AND terms with any number of variables can be ORed together. When the relay is processing a complex
expression, it performs AND operations before performing OR operations.

SL-VO Command
Purpose: Used to program a logical mode of operation for a virtual output.
Syntax: SL-VO[x] [= <equation>]
Comments: x = virtual output number A or 1-15
<equation> = a Boolean logic expression using variables: virtual inputs (Ix), logic module
outputs, virtual outputs (VOx) and operators: AND (*), OR (+), and NOT (/).
Access at Area G or Area S is required to change setting.
Entering SL-VO by itself will normally read the output logic equation of the active logic. If entered while
programming a custom logic, it will read the output logic of the custom logic.

BE1-CDS BESTlogic Programmable Logic 7-5


Example 1: Turn on output 1 when any 50 or 51 protective element trips.
SL-VO1=50TPT+50TN+150TP+150TN+51P+51N+50TQ+51Q
Example 2: Turn on output 2 when the low set 50 (50 element) trips but the corresponding high set
50 (150 element) does not trip.
SL-VO2=50TP*/150TP+50TN*/150TN
Example 3: Turn on output 5 when the breaker failure logic trips:
SL-VO5=BFT
Virtual and Hardware Outputs
A virtual output exists only as a logical state inside the relay. A hardware output is a physical relay
contact that can be used for protection or control. Each BE1-CDS relay has five isolated Form A output
contacts (OUT1 – OUT5), one isolated Form C output contact (OUT6), and one isolated Form B alarm
output (OUTA). Output contacts OUT1 through OUT6 are controlled by the status of the internal virtual
logic signals VO1 through VO6. If VO[n] becomes TRUE, then the corresponding output relay OUT[n]
energizes and operates the contacts. For the alarm output, if VOA becomes TRUE, the ALM output de-
energizes and opens. For more information about input and output functions see. Section 3, Input and
Output Functions.

LOGIC SCHEMES
A logic scheme is a group of logic variables written in equation form that defines the operation of a multi-
function relay. Each logic scheme is given a unique name of one to eight alphanumeric characters. This
gives you the ability to select a specific scheme and be confident that the selected scheme is in
operation. Six logic schemes, configured for typical protection applications, are stored in nonvolatile
memory. Only one of these logic schemes can be active at a given time. In most applications,
preprogrammed logic schemes eliminate the need for custom programming. Preprogrammed logic
schemes may provide more inputs, outputs, or features than are needed for a particular application. This
is because the preprogrammed schemes are designed for a large number of applications with no special
programming required. Unneeded inputs or outputs may be left open to disable a function, or a function
element can be disabled through operating settings. Unused current sensing inputs should be shorted to
minimize noise pickup.
When a custom logic scheme is required, programming time can be reduced by copying a
preprogrammed scheme into the active logic. The logic scheme can then be modified to meet the
specific application.

The Active Logic Scheme

NOTICE
There has been a fundamental improvement to the way the user sets up BESTlogic in
this device. In some prior implementations of BESTlogic, it was necessary to make a
separate setting that determined whether the user’s logic scheme or one of the pre-
programmed logic schemes was made active. This setting was made from the ASCII
command interface using the SP-LOGIC (Set Protection Logic) command. This setting
has been eliminated.
In the implementation of BESTlogic used in this relay, the logic scheme defined by the
user’s logic settings is always active. If the user wishes to use a preprogrammed logic
scheme, he now copies it into his user logic settings. This process is accomplished from
the ASCII command interface using the SL-N (Set Logic Name) command in this and
previous BESTlogic implementations.

Digital, multifunction relays must have an active logic scheme in order to function. All Basler Electric
multifunction relays are delivered with a default, active logic loaded into memory. The default, active logic
scheme for the BE1-CDS is named BASIC-87. If the function element configuration and output logic of
7-6 BESTlogic Programmable Logic BE1-CDS
BASIC-87 meets the requirements of your application, then only the operating settings (power system
parameters and threshold settings) need to be adjusted before placing the relay in service.
If a different preprogrammed logic scheme is required, it can be easily copied to active logic and used as
is, or customized to your specifications. To accomplish this, communication with the relay must be
established. This is referred to as the on-line method of setting or changing the active logic. It is
accomplished by connecting a computer to the front or rear RS-232 port and establishing communication
through compatible terminal emulation software such as Windows® HyperTerminal or Terminal (VT100
emulation). Section 11, ASCII Command Interface provides detailed information about command
structure and establishing communication with the relay. Appendix D, Setting Terminal Communications
gives instructions for configuring Windows® HyperTerminal and Terminal for use with the BE1-CDS.
Any of the six preprogrammed logic schemes stored in relay memory can be copied to the active logic
and customized or used as is. To copy a logic scheme into active logic, use the SL-N=<name>
command.
The SL (settings logic) command is used to obtain a list of the logic schemes stored in memory or the
equations associated with a logic scheme. Entering SL: returns a list of the logic schemes available. The
first scheme listed is the active logic scheme. Entering SL: followed by the name of a preprogrammed
scheme returns all equations associated with the named scheme (SL:BASIC-87 for example). For
custom schemes, place an equals sign between SL and the logic name (SL=CUSTOM for example).
Similarly, preprogrammed logic commands and parameters are separated by a colon; custom logic
commands and parameters are separated by an equals sign.

SL Command
Purpose: Reads the names of logic schemes in memory or the equations for the named logic.
Syntax: SL[:<name>] or SL-<xxx>
Example 1. Read the stored logic schemes (the first named is the active or custom scheme).
SL: <cr>
BASIC-87, BASIC-87, BASIC-TX, TX-W-CTL, TX-W-BU, BUS-W-BU, MOTOR,
NONE

Example 2. Read all logic equations associated with the active logic scheme, BASIC-87
SL <cr>
SL-N=BASIC-87
SL-87=1,0
SL-87ND=0,0
SL-50TP=0,0; SL-50TN=0,0; SL-50TQ=0,0
SL-150TP=0,0; SL-150TN=0,0; SL-150TQ=0,0
SL-250TP=0,0; SL-250TN=0,0; SL-250TQ=0,0
SL-51P=1,0; SL-51N=1,0; SL-51Q=1,0
SL-151P=0,0; SL-151N=0,0; SL-151Q=0,0
SL-251P=0,0; SL-251N=0,0; SL-251Q=0,0
SL-62=0,0,0
SL-162=0,0,0
SL-BF=0,0,0
SL-GROUP=1,0,0,0,0,/0
SL-43=0
SL-143=0
SL-243=0
SL-343=0
SL-443=0
SL-543=0
SL-643=0
SL-743=0
SL-101=0
SL-CKTMON=0,0,0
SL-VOA=0
SL-VO1=87RT+87UT
SL-VO2=87RT+87UT
SL-VO3=87RT+87UT
BE1-CDS BESTlogic Programmable Logic 7-7
SL-VO4=51PT+51NT+51QT
SL-VO5=0
SL-VO6=ALMMAJ
SL-VO7=0
SL-VO8=0
SL-VO9=0
SL-VO10=0
SL-VO11=51PT+51NT+51QT+87RT+87UT
SL-VO12=87UT+51PPU+51NPU+51QPU+87RPU
SL-VO13=IN6
SL-VO14=IN7
SL-VO15=IN8
>
Example 3. Read the logic equation associated with logic variable VO1.
SL-V01 <cr>
87RT+87UT

Custom Logic Schemes


A custom logic scheme can be created from scratch by copying NONE to active logic and then renaming
the logic. A custom logic scheme can also be created by modifying any one of the preprogrammed logic
schemes after copying it to active logic and renaming. Preprogrammed logic schemes copied to active
logic with no name change are read-only schemes and cannot have their logic expressions altered.
Before modifying a logic scheme copied to active logic, the scheme must be assigned a unique name of
one to eight alphanumeric characters. This scheme is then referred to as a custom or user
programmable logic scheme because the variable expressions of the logic can be customized or created
from scratch to suit the needs of an application. A custom logic scheme may be revised many times, but
only the most recent changes are saved to active logic.

Copying and Renaming Preprogrammed Logic Schemes

CAUTION
Always remove the relay from service prior to changing or modifying the active logic
scheme. Attempting a logic scheme change while the relay is in service could generate
unexpected or unwanted outputs.

Copying a preprogrammed logic scheme to the active logic and assigning a unique name is
accomplished with the SL-N (settings logic, name) command. Changes are not activated until the EXIT
and SAVE commands are executed.
If the previous active logic was a customized scheme, the new custom logic scheme may be given the
same name as the previous scheme or it may be given an entirely new name. However, a custom logic
scheme must be different from any of the preprogrammed logic scheme names as previously discussed.

SL-N Command
Purpose: Reads or sets the custom (active) logic scheme name or copies a preprogrammed logic
scheme to the custom (active) logic scheme.
Syntax: SL-N[=<name>]
The SL-N command is illustrated by the following examples:

Example 1. Read the name of the custom logic scheme (Basic-87 as shipped from the factory).
SL-N <cr>
BASIC-87
Example 2. Copy a different preprogrammed logic scheme, BASIC-TX, to the custom (active) logic
scheme.
SL-N=BASIC-TX <cr>
OVERWRITE CUSTOM (active) LOGIC SETTINGS (Y/N)?

7-8 BESTlogic Programmable Logic BE1-CDS


>y <cr>
Example 3. If this preprogrammed scheme meets the needs of the application, the changes can be
saved.
e <cr> (exit)
SAVE CHANGES (Y/N/C)? (y=yes, n=no, c=exit cancelled, continue
edit)
Y <cr>
CHANGES SAVED
>
If an attempt was made to customize this read-only, preprogrammed logic, the relay would issue the
following message. ERROR! CUSTOM LOGIC NAME EQUALS STANDARD LOGIC NAME
In order to customize the BASIC-TX scheme (modify the logic expressions), the preprogrammed logic
name must be given a unique name that differs from any of the preprogrammed logic scheme names.

Example 4. Rename the active BASIC-TX logic with a unique, meaningful logic name (EUBA-TX,
Electric Utility Basic Transformer).
SL-N=EUBA-TX
EXIT
SAVE CHANGES (Y/N/C)?
Y
CHANGES SAVED
EUBA-TX is now the active logic and the logic expressions can be changed as required. Remember,
changes must be saved to make them active.

Creating Or Customizing A Logic Scheme


Before customizing a preprogrammed logic scheme, the scheme must be renamed. This process is
outlined in the previous SL-N Command Examples. The following procedure outlines the process of
customizing or creating a logic scheme. If a completely new logic scheme is to be created, begin with
Step 5.
Step 1. Copy the preprogrammed scheme by using the SL-N=<preprogrammed logic name>
command.
Step 2. Name the preprogrammed scheme with a unique, non-preprogrammed name by using the
SL-N=<new name> command. This allows the logic scheme to be programmed.
Step 3. Obtain a list of the logic equations with the SL command.
Step 4. Disable unneeded outputs or function elements by setting them equal to zero. For example,
SL-VO10=0
Alternately, all output equations can be programmed or disabled at once by not using a number
suffix. For example, entering SL-VO=0 clears all output equations before writing new ones.
Another way to disable all logic settings is to copy the NONE logic to active logic. Renaming
the NONE logic will then permit the scheme to be programmed. The syntax used would be
SL-N=NONE;Y;SL-N=<new name>.
Step 5. Change the logic expressions as required by using the SL-<function> and SL-VO commands.
Step 6. Use the SL command to review the changes.
Step 7. Save the changes by using the EXIT command.

The active logic scheme can also be saved as a text file and modified off-line using any ASCII text editor.
The text file can then be uploaded to the relay through terminal communications. Also, a Microsoft®
Excel “Settings Record” spreadsheet is available with the BE1-CDS and contains all of the
preprogrammed logic schemes. These schemes can be modified and saved as a text file and then
uploaded to the relay active logic. See Appendix C, BE1-CDS Settings Record for more information.

BE1-CDS BESTlogic Programmable Logic 7-9


Debugging The Logic Scheme
If there are problems with a customized logic scheme, the RG-STAT command can be used to check the
status of all logic variables. More information about the RG-STAT command can be found in Section 6,
Reporting and Alarm Functions.

USER INPUT AND OUTPUT LOGIC VARIABLE NAMES


Assigning meaningful names to the inputs and outputs makes sequence of events reports easier to
analyze. Input and output logic variable names are assigned with the SN command. All SN labels are
used in the RS (reports, sequence of events) reports. Entering SN by itself returns a list of all
programmable names. See Table 7-2 for details on the SN command.
Table 7-2. SN Command Settings
Setting Range/Purpose Default
name 1 to 16 characters. See Note
User name to replace <var> in the RS report
TRUE label 1 to 7 character user label to replace default TRUE TRUE
label for <var>
FALSE label 1 to 7 character user label to replace default FALSE FALSE
label for <var>
Note:
Default name is specific for the inputs and outputs and not shown here. For example,
the default setting for virtual output switch 43 is SWITCH_43. Enter SN through the
ASCII command interface to retrieve the default settings for the active logic.

SN Command
Purpose: Read or set user-programmable names.
Syntax: SN[-[var][=[name],[TRUE label],[FALSE label]]
Comments: var = logic variable 43/143/243/343’443/543/643/743, VOA, VO1 through VO15, or IN1
through IN4
Example 1. Read the current name setting for IN1.
SN-IN1
SN-IN1=IN1,CLOSED,OPEN
Example 2. Change the name for IN1 to better describe its function as a 52b contact.
SN-IN1=BREAKER,OPEN,CLOSED
Example 3. Label the 43 switch operation for use on the HMI.
SN-43=AUTO_SG,DISABLE,ENABLE

BESTlogic APPLICATION TIPS


When designing a completely new logic scheme, logic evaluation order should be considered. Contact
sensing inputs are evaluated first, then the function elements, and then the virtual outputs. VO15 is
evaluated first and VOA is evaluated last. If a virtual output is used in a logic expression to control
another virtual output, the virtual output used in the expression should be numerically higher. Otherwise,
a logic expression for a numerically smaller virtual output won’t be available to a numerically higher virtual
output until the next processing interval. Logic is evaluated every quarter-cycle.
When designing custom protection schemes, avoid confusion by maintaining consistency between input
and output functions in the custom scheme and the preprogrammed schemes.
OUT1 through OUT5 have normally open contacts (coil is de-energized). OUT6 is Form C and has one
normally open and one normally closed contact. Normally open contacts can be used as normally closed
outputs by inverting the logic expressions that drive them. Inverting an output logic expression causes
the coil to be energized with the contacts closed in the normal state. Caution should be taken with
normally closed contact logic because there are no shorting bars to maintain the closed condition if the
7-10 BESTlogic Programmable Logic BE1-CDS
draw-out assembly is removed from the chassis. In applications where a normally closed output is
needed even when the electronics are removed, a normally open contact from the relay can be used to
drive a low-cost auxiliary relay. The normally closed output of the auxiliary relay will maintain the closed
output when the draw-out assembly is removed from the case. Alternately, an external switch can be
used to short across a normally closed relay output when the draw-out assembly is removed. Extra care
is required to ensure that the switch is closed prior to removing the draw-out assembly and that the switch
is open after the relay is placed back in service.
Several links between the programmable alarms function and BESTlogic programmable logic allow alarm
functions to be used in a logic scheme and programmable logic functions to be used in the alarm
reporting function.
Programmable alarm settings for Major, Minor, and Logic alarms drive BESTlogic variables ALMMAJ,
ALMMIN, and ALMLGC. These variables can be used in logic expressions to control logic when an alarm
is active.
Virtual outputs VO13, VO14, and VO15 are driven by BESTlogic expressions. These three logic
variables are also available in the programmable alarm function. Virtual outputs can also be assigned
user programmable labels (described previously). With this feature, a logic condition can be designed
and used for an alarm. The virtual output label would then be reported in the alarm reporting function.

BE1-CDS BESTlogic Programmable Logic 7-11


SECTION 8 • APPLICATION
TABLE OF CONTENTS

List Of Figures.........................................................................................................................................ii
List Of Tables..........................................................................................................................................ii
SECTION 8 • APPLICATION .................................................................................................................... 8-1
INTRODUCTION .................................................................................................................................... 8-1
EXPLANATION OF TERMS................................................................................................................... 8-1
Function Element ................................................................................................................................ 8-1
Virtual Switches .................................................................................................................................. 8-1
OVERVIEW OF PREPROGRAMMED LOGIC SCHEMES .................................................................... 8-1
Basic Differential Protection Logic Scheme ........................................................................................ 8-2
Basic Transformer Logic Scheme....................................................................................................... 8-2
Basic Transformer With Control Logic Scheme.................................................................................. 8-2
Transformer Differential With Backup Logic Scheme ......................................................................... 8-2
Bus Protection With Backup Logic Scheme........................................................................................ 8-2
Motor Protection Logic Scheme.......................................................................................................... 8-3
DETAILS OF PREPROGRAMMED LOGIC SCHEMES......................................................................... 8-3
BASIC DIFFERENTIAL LOGIC SCHEME.............................................................................................. 8-4
Protection Elements............................................................................................................................ 8-6
Integration Of Protection, Control, And I/O Elements ......................................................................... 8-6
Alarms................................................................................................................................................. 8-7
BASIC TRANSFORMER LOGIC SCHEME ........................................................................................... 8-9
Protection Elements.......................................................................................................................... 8-11
Integration Of Protection, Control, And I/O Elements ....................................................................... 8-12
Alarms............................................................................................................................................... 8-12
BASIC TRANSFORMER WITH CONTROL LOGIC SCHEME ............................................................ 8-14
Protection Elements.......................................................................................................................... 8-17
Integration Of Protection, Control, And I/O Elements ....................................................................... 8-17
Alarms............................................................................................................................................... 8-18
TRANSFORMER WITH BACKUP SCHEME ....................................................................................... 8-21
Protection Elements.......................................................................................................................... 8-22
Integration Of Protection, Control, And I/O Elements ....................................................................... 8-22
Test Mode ......................................................................................................................................... 8-23
Alarms............................................................................................................................................... 8-23
BUS WITH BACKUP SCHEME............................................................................................................ 8-29
Protection Elements.......................................................................................................................... 8-35
Integration Of Protection, Control, And I/O Elements ....................................................................... 8-35
Test Mode ......................................................................................................................................... 8-36
Setting Group.................................................................................................................................... 8-36
Alarms............................................................................................................................................... 8-36
MOTOR PROTECTION LOGIC ........................................................................................................... 8-40
Protection Elements.......................................................................................................................... 8-43
Integration Of Protection, Control, And I/O Elements ....................................................................... 8-44
High Inertia Motor Start..................................................................................................................... 8-44
Low Inertia Motor Start...................................................................................................................... 8-45
Emergency Trip................................................................................................................................. 8-45
Alarms............................................................................................................................................... 8-45
MISCELLANEOUS LOGIC EXPRESSIONS ........................................................................................ 8-48
APPLICATION TIPS............................................................................................................................. 8-49
Trip Circuit Continuity And Voltage Monitor ...................................................................................... 8-49
Close-Circuit Monitor ........................................................................................................................ 8-50

BE1-CDS Application i
Block Neutral and Negative Sequence Protection ............................................................................ 8-50
Setting Group Selection .................................................................................................................... 8-50
Output Contact Seal-In ..................................................................................................................... 8-51
Latching a Tripping Contact .............................................................................................................. 8-52
Latching A Programmable Logic Alarm Or Creating A Pseudo Target............................................. 8-54
Logic Settings Associated With Figure 8-20 ..................................................................................... 8-54

List Of Figures
Figure 8-1. Typical One-Line Diagram For BASIC-87............................................................................... 8-5
Figure 8-2. Typical Logic Diagram For BASIC-87..................................................................................... 8-6
Figure 8-3. Typical One-Line Diagram For BASIC-TX ............................................................................ 8-10
Figure 8-4. Typical Logic Diagram For BASIC-TX .................................................................................. 8-11
Figure 8-5. Typical One-Line Diagram For TX-W-CTL ........................................................................... 8-15
Figure 8-6. Typical Logic Diagram For TX-W-CTL.................................................................................. 8-16
Figure 8-7. Device Interconnection For Integrated Protection System Using BE1-CDS220 For
Transformer Protection And BE1-851 or BE1-951 For Bus And Feeder Protection......................... 8-27
Figure 8-8. Typical One-Line Diagram For TX-W-BU ............................................................................. 8-28
Figure 8-9. Typical Logic Diagram For TX-W-BU ................................................................................... 8-29
Figure 8-10. Device Interconnection For Integrated Protection System Using BE1-CDS220 For Bus
Protection And BE1-851 Or BE1-951 For Feeder And Backup Protection....................................... 8-30
Figure 8-11. Device Interconnection For Integrated Protection System Using BE1-CDS220 For
Transformer And Bus Protection And BE1-851 Or BE1-951 For Feeder Protection ........................ 8-31
Figure 8-12. Typical One-Line Diagram For BUS-W-BU ........................................................................ 8-33
Figure 8-13. Typical Logic Diagram For BUS-W-BU............................................................................... 8-34
Figure 8-14. Typical One-Line Diagram For MOTOR ............................................................................. 8-42
Figure 8-15. Typical Logic Diagram For MOTOR ................................................................................... 8-43
Figure 8-16. Trip Circuit Continuity And Voltage Monitor ........................................................................ 8-49
Figure 8-17. Close Circuit Monitor Logic................................................................................................. 8-50
Figure 8-18. Output Seal-In Logic Diagram ............................................................................................ 8-51
Figure 8-19. Station One-Line Drawing................................................................................................... 8-53
Figure 8-20. Latching a Tripping Contact Example................................................................................. 8-53

List Of Tables
Table 8-1. BASIC-87 Logic Settings and Equations ................................................................................. 8-4
Table 8-2. BASIC-87 Contact Input Logic ................................................................................................. 8-7
Table 8-3. BASIC-87 Function Block Logic............................................................................................... 8-7
Table 8-4. BASIC-87 Virtual Switch Logic................................................................................................. 8-7
Table 8-5. BASIC-87 Output Logic............................................................................................................ 8-8
Table 8-6. BASIC-TX Logic Settings And Equations ................................................................................ 8-9
Table 8-7. BASIC-TX Contact Input Logic .............................................................................................. 8-12
Table 8-8. BASIC-TX Function Block Logic ............................................................................................ 8-13
Table 8-9. BASIC-TX Virtual Switch Logic .............................................................................................. 8-13
Table 8-10. BASIC-TX Output Logic ....................................................................................................... 8-13
Table 8-10. BASIC-TX Output Logic - Continued ................................................................................... 8-14
Table 8-11. TX-W-CTL Logic Settings and Equations ............................................................................ 8-16
Table 8-12. TX-W-CTL Contact Input Logic............................................................................................ 8-18
Table 8-13. TX-W-CTL Function Block Logic.......................................................................................... 8-18
Table 8-13. TX-W-CTL Function Block Logic - Continued ...................................................................... 8-19
Table 8-14. TX-W-CTL Virtual Switch Logic ........................................................................................... 8-19
Table 8-15. TX-W-CTL Output Logic ...................................................................................................... 8-19
Table 8-15. TX-W-CTL Output Logic - Continued................................................................................... 8-20
Table 8-16. TX-W-BU Logic Settings and Equations .............................................................................. 8-21
Table 8-17. TX-W-BU Contact Input Logic.............................................................................................. 8-23
Table 8-18. TX-W-BU Function Block Logic ........................................................................................... 8-24
Table 8-19. TX-W-BU Virtual Switch Logic ............................................................................................. 8-25
Table 8-20. TX-W-BU Output Logic ........................................................................................................ 8-25
Table 8-21. BUS-W-BU Logic Settings and Equations ........................................................................... 8-32
Table 8-22. BUS-W-BU Contact Input Logic........................................................................................... 8-37
ii Application BE1-CDS
Table 8-23. BUS-W-BU Function Block Logic......................................................................................... 8-37
Table 8-23. BUS-W-BU Function Block Logic - Continued ..................................................................... 8-38
Table 8-24. BUS-W-BU Virtual Switch Logic .......................................................................................... 8-38
Table 8-25. BUS-W-BU Output Logic ..................................................................................................... 8-38
Table 8-25. BUS-W-BU Output Logic - Continued.................................................................................. 8-39
Table 8-25. BUS-W-BU Output Logic - Continued.................................................................................. 8-40
Table 8-26. Motor Logic Settings And Equations.................................................................................... 8-41
Table 8-27. MOTOR Contact Input Logic................................................................................................ 8-45
Table 8-28. MOTOR Function Block Logic ............................................................................................. 8-45
Table 8-28. MOTOR Function Block Logic - Continued.......................................................................... 8-46
Table 8-29. MOTOR Virtual Switch Logic ............................................................................................... 8-46
Table 8-30. MOTOR Output Logic .......................................................................................................... 8-46
Table 8-30. MOTOR Output Logic - Continued....................................................................................... 8-47
Table 8-30. MOTOR Output Logic - Continued....................................................................................... 8-48
Table 8-31. Miscellaneous Logic Expressions ........................................................................................ 8-48

BE1-CDS Application iii


SECTION 8 • APPLICATION
INTRODUCTION
This section discusses application of the BE1-CDS Current Differential Protection System using
preprogrammed logic schemes. The paragraphs on Details of Preprogrammed Logic Schemes describe
the characteristics of each logic scheme and how they combine to create a differential protection scheme
for transformers, generators, motors, and buses. A detailed description of preprogrammed schemes is
also provided. This section concludes with tips on programming custom logic schemes to meet specific
user applications.
The preprogrammed logic schemes are designed to accommodate the most common differential
protection applications. The protection engineer can choose a logic scheme that closely meets his
application and adapt it by changing the protection and control elements and settings. In most cases, this
eliminates the need to create a custom logic scheme from scratch.
Please note that each preprogrammed logic scheme also illustrates typical ways of using or controlling
various functions. The user may choose to create a custom logic scheme by mixing the logic from several
of the preprogrammed schemes. The logic also can be modified to incorporate some of the features
described in the Application Tips provided at the end of this section. The flexibility of BESTlogic allows the
engineer to create a protection and control scheme that meets the exact requirements of his application.

EXPLANATION OF TERMS
Understanding the following terms and definitions will help to clarify the application discussions that follow.

Function Element
Stand-alone protection or control function that is equivalent to the discrete component counterpart.

Virtual Switches
Virtual switches are logic switches that emulate traditional protection and control panel switches such as
the breaker control switch (101) and on/off, selector switches (43). Virtual switches may be operated via
the ASCII command interface or the front panel HMI. Operation of these switches can be password
protected or disabled if the user chooses not to use them. You might do this when using a
preprogrammed logic scheme without changing the preprogrammed logic.

OVERVIEW OF PREPROGRAMMED LOGIC SCHEMES


The BE1-CDS has six preprogrammed logic schemes. Three of the logic schemes are intended for use
on transformers. One of the schemes is for motor protection with a speed sensing input, one is for bus
protection with backup, and one is a basic 87 function designed for multiple applications including
transformer, motor, bus, or generator protection.
The 87 function as applied to transformer protection is fundamentally different from the application of the
nd th
87 function to motors, generators, and buses. That is, the 2 and 5 harmonic restraint elements are
required on transformer applications to prevent false tripping resulting from magnetizing inrush currents.
However, waveform distortion resulting from heavy current transformer (CT) saturation can cause the
harmonic restraint units to block restrained differential tripping (87RT) for internal faults. Therefore, a
high-speed, unrestrained instantaneous differential element (87UT) is also required for transformer
applications.
When the 87 protection element is applied to other than transformer protection, set the pickup thresholds
nd th
for the 2 , 5 , and 87UT units to 0 (setting disabled).

BE1-CDS Application 8-1


Basic Differential Protection Logic Scheme
This logic scheme (BASIC-87) provides three-phase, percent-restrained differential protection, with high-
speed unrestrained instantaneous differential protection for motor, generator, bus, and transformer
applications. A single zone of time overcurrent phase, neutral, and negative sequence protection (51P, N,
and Q) is also included for backup protection.

Basic Transformer Logic Scheme


This logic scheme (BASIC-TX) provides three-phase, percent-restrained differential protection with high-
nd
speed unrestrained instantaneous differential protection. The differential protection also includes 2 and
th
5 harmonic restraint to improve security for transformer inrush. Time overcurrent phase, neutral, and
negative sequence protection are included on the high side (151P, N, and Q) and low side (251P, N, and
Q) of the transformer to provide time delay backup protection for the transformer and low-side zones. A
separate 51N fed from an optional ground CT (IG) input is also included in this scheme and provides
sensitive, time overcurrent ground fault backup protection for the transformer low-side winding, the bus,
and the feeders.

Basic Transformer With Control Logic Scheme


This logic scheme (TX-W-CTL) provides the same differential and overcurrent protection elements as the
basic transformer logic scheme but with different outputs and the addition of virtual control switch logic
that can be operated locally or remotely (SCADA). The virtual 101-control switch is applied for tripping
and closing the low-side breaker, while 43 and 143 control switch elements are applied for tripping and
closing the high-side breaker. Virtual control switch 243 is used to turn off the differential protection
element, and virtual control switch 343 allows for automatic or manual selection of the active setting group.

Transformer Differential With Backup Logic Scheme


This logic (TX-W-BU ) incorporates nearly all the protection elements available in the BE1-CDS. These
include the differential functions with harmonic restraint as well as 51 phase, neutral, and negative
sequence backup protection as seen from the transformer high side. Also included is a separate 51N fed
from an optional ground CT (IG), 50P, N, and Q definite time bus protection as seen from the transformer
low-side breaker, and low-side breaker BF (breaker failure) protection with fast current reset. A current
supervised, external breaker failure initiate (BFI), 50/62, and a contact supervised BFI, 62, are also
included. The 101 virtual control switch is used to trip and close the low-side breaker while the virtual 43
switch is used to turn off the 87 function. Both virtual functions can be operated locally or remotely
(SCADA).

Bus Protection With Backup Logic Scheme


This logic scheme (BUS-W-BU) provides a primary zone of high-speed, low impedance, bus differential
protection and a backup zone of high-speed instantaneous overcurrent (bus interlocking) protection.
Feeder circuit backup protection and overall backup protection from the bus main to the first down-line
interrupting device for each feeder circuit are also provided.
The percent-restrained differential protection function is the only function of the 87 protection element
nd th
required for this application. Set the pickup of the 2 , 5 , and 87 unrestrained functions to 0 (setting
nd th
disabled). The 87 unrestrained function has a setting only when the 2 and 5 harmonic restraint
functions are set for transformer applications (refer to the discussion in Overview of Preprogrammed Logic
Schemes).
The 87 restrained element provides conventional high speed, low impedance, bus differential protection.
On feeder circuits using the 851 or 951 distribution feeder protection relays, the 50T, P, and Q elements
from the BE1-CDS are hard wired to the feeder protection package, providing a high-speed backup, bus
interlocked, zone of bus protection. When the BE1-CDS detects a feeder relay out of service, the BE1-
CDS 50/51P, N, and Q protection elements and outputs are automatically reconfigured to provide feeder
protection. The 150/151P, N, and Q protection elements of the BE1-CDS are time coordinated with the
bus and feeder circuit protection, providing overall backup protection from the transformer side of the bus
main breaker through the first down-line interrupting device on the distribution circuit.

8-2 Application BE1-CDS


Motor Protection Logic Scheme
This logic scheme (MOTOR) incorporates the essential differential and overcurrent protection elements
that are ideally suited for large motor protection. The 87 restrained element provides high-speed
differential fault protection. Sensitive instantaneous and time overcurrent, negative sequence elements,
50TQ and 51Q, are incorporated for open phase and phase imbalance protection. High-speed ground
fault protection is accomplished with an instantaneous overcurrent element 50TN, and the 51P and 251P
elements provide motor overload and stall (jam) protection. Further protection, locked rotor protection and
start/run detection for low and high inertia motors, is accomplished using a combination of instantaneous
and time overcurrent phase elements, virtual logic switches, and a speed sensing input from the motor.
The percent-restrained differential protection function is the only function of the 87 protection element
nd th
required for this application. Set the pickup of the 2 , 5 , and 87 unrestrained functions to 0 (setting
nd th
disabled). The 87 unrestrained function has a setting only when the 2 and 5 harmonic restraint
functions are set for transformer applications (refer to the discussion in Overview of Preprogrammed Logic
Schemes).

DETAILS OF PREPROGRAMMED LOGIC SCHEMES


The following paragraphs expand on each preprogrammed scheme. The application features of each
logic scheme are broken down into their separate protection elements and described in detail. The
integration of protection and control elements, and alarm elements are also described in detail.
Multifunction protection products are the best thing to happen to the protection industry in the last 30
years. The operating information they provide, along with their flexibility, versatility, and economics,
provide the protection engineer with options that were never available with previous technologies. There
is, however, one cardinal rule that must be followed to ensure continuous, reliable, and secure protection
of the user’s facilities.

Never use a protection element from a multifunction relay to backup another


protection element in the same relay!!!

Regardless of the product manufacturer, common mode failure is a possibility that the protection engineer
must consider in his design. For example, if a BE1-CDS is used to protect a two-winding transformer, the
protection engineer cannot depend on the internal 51 time overcurrent element to backup the primary
differential 87 protection element of the same relay. A common mode failure such as the power supply
could disable the entire relay and leave the transformer with no protection. Also, the self-testing feature of
the product is designed to disable the relay outputs when a problem is detected.
Basler Electric products are among the most reliable in the industry, but we believe that it does not make
good engineering sense to place all your eggs in one basket. That is why Basler strongly recommends
that a second multifunction device be installed to provide independent backup and zone overlapping for
each protected zone. In the transformer example given in the previous paragraph, the 87 protection
element of the BE1-CDS would require 51 backup protection from a separate BE1-851 or BE1-951
device. Conversely, a BE1-CDS 50 or 51 overcurrent element would backup a separate BE1-851 or BE1-
951 zone used for low-side bus protection.
The following paragraphs discuss the protection and control capabilities of each preprogrammed BE1-
CDS protection logic scheme. Although it is not discussed in each paragraph, the reader should be aware
that the application of an independent, overlapping, backup zone of protection is recommended for a
complete protection design.
Each preprogrammed protection logic scheme begins with the application intent of the design. Next, the
protection elements are discussed in detail, including CT connections and typical zone and reach
information, followed by protection and control integration, and alarm information specific to the
preprogrammed design. Unique references for each scheme, including one-line and logic diagrams, and
program codes are included.
Preprogrammed logic can be a starting point or an ending point for the protection engineer depending on
how closely the logic meets engineering requirements. These basic logic schemes were created by

BE1-CDS Application 8-3


applications personnel from the utility industry and are easily modified to meet specific user needs. For
applications assistance, contact your local Basler Electric representative.

BASIC DIFFERENTIAL LOGIC SCHEME


The basic differential logic scheme (BASIC-87) provides a primary zone of low-impedance, differential
protection and one backup zone of time overcurrent protection for transformer, generator, motor, and
radial bus applications.
Figure 8-1 is a one-line drawing and Figure 8-2 is a logic drawing representing the logic settings and
equations shown in Table 8-1. In Table 8-1, the user can see the protection and control elements that are
enabled (set to logic 1) for the BASIC-87 application and see how the elements are logically wired
together (equations). If the user should decide to build on this scheme, all elements required for a more
detailed application are available through programming. For programming details, refer to Section 7,
BESTlogic Programmable Logic.
Table 8-1. BASIC-87 Logic Settings and Equations
SL-N=BASIC-87
SL-87=1,0
SL-87ND=0,0
SL-50TP=0,0; SL-50TN=0,0; SL-50TQ=0,0
SL-150TP=0,0; SL-150TN=0,0; SL-150TQ=0,0
SL-250TP=0,0; SL-250TN=0,0; SL-250TQ=0,0
SL-51P=1,0; SL-51N=1,0; SL-51Q=1,0
SL-151P=0,0; SL-151N=0,0; SL-151Q=0,0
SL-251P=0,0; SL-251N=0,0; SL-251Q=0,0
SL-62=0,0,0
SL-162=0,0,0
SL-BF=0,0,0
SL-GROUP=1,0,0,0,0,/0
SL-43=0
SL-143=0
SL-243=0
SL-343=0
SL-443=0
SL-543=0
SL-643=0
SL-743=0
SL-101=0
SL-CKTMON=0,0,0
SL-VOA=0
SL-VO1=87RT+87UT
SL-VO2=87RT+87UT
SL-VO3=87RT+87UT
SL-VO4=51PT+51NT+51QT
SL-VO5=0
SL-VO6=ALMMAJ
SL-VO7=0
SL-VO8=0
SL-VO9=0
SL-VO10=0
SL-VO11=51PT+51NT+51QT+87RT+87UT
SL-VO12=87UT+51PPU+51NPU+51QPU+87RPU
SL-VO13=IN6
SL-VO14=IN7
SL-VO15=IN8

8-4 Application BE1-CDS


CT Input 2

T r ip
BE1-CDS220
Out1
86G

Trip
52-G
Out2
87
Out3
41
Out4

Field
G 51P 51N 51Q

CT Input 1

CT Input 1
Trip BE1-CDS220
Out4

52-M
51P 51N 51Q

Out1 86M

M 87 Out2
Out3

CT Input 2

CT Input 1
Trip

BE1-CDS220
Out4
52
Bus
Main 51P 51N 51Q

Out1 86B
52 52 52
F1 F2 F3 Out2
87
Out3

CT Input 2

CT Input 1
Trip

BE1-CDS220
Out4

52-T
51P 51N 51Q

Out1 86T

87 Out2
Out3

CT Input 2 D2843-22.vsd
08-02-00

Figure 8-1. Typical One-Line Diagram For BASIC-87

BE1-CDS Application 8-5


IN1 Breaker1 Status 87RT
OPTO
87RPU
IN2 Breaker2 Status VOA
OPTO 87UT Relay
BLK 87
Mode1 Trouble
IN3 86 Status 2NDHAR Output
OUTA
OPTO Logic
5THHAR
IN4 Not Used
OPTO VO1
87 Trip Output
IN5 Not Used OUT1
51PT Logic
OPTO
BLK 51P
VO13 Alarm Point 21 Mode1 51PPU
IN6 Alarm VO2
OPTO
87 Trip Output
OUT2
IN7 Alarm VO14 Alarm Point 22 Logic
OPTO 51NT
BLK 51N
Mode1 51NPU VO3
IN8 Alarm VO15 Alarm Point 23
OPTO 87 Trip Output
OUT3
Logic
51QT
BLK 51Q
Mode1 51QPU VO4
3 51 Trip
Output
OUT4
Logic

Note: For clarity, multiple variables going to


the same OR Gate are shown by a single line VO5
into the OR Gate. Not Used Output
OUT5
ALMMAJ Logic
SG0
D0 ACTIVE
D1 SG1 ALMMIN
SETTING SA- Alarm VO6
D2 GROUP SG2 RESET Major Alarm
ALMLGC Output OUT6
D3 CONTROL
0 SG3 Logic
AUTO Mode1

VO11 PROT TRIP


5

5 VO12 PROT PU
D2843-23.vsd
09-23-99

Figure 8-2. Typical Logic Diagram For BASIC-87

Protection Elements
Referring to all four schemes (Generator, Motor, Bus, and Transformer) in Figure 8-1, the 87 protection
element is connected to CT input 1 and CT input 2. The 51 protection element is also connected to the
CT input 1. The 87 and 51 protection elements are logic enabled by the programming shown in Table 8-1
to provide a trip through the BE1-CDS output contacts.
Typically, the 87 protection element provides high-speed percent restrained, phase and ground protection
for faults inside the differential zone. For the generator, motor, and bus applications shown in Figure 8-1,
the percent-restrained differential protection function is the only function of the 87 protection element
nd th
required. Set the pickup of the 2 , 5 , and 87 unrestrained functions to 0 (setting disabled). The 87
nd th
restrained function has a setting when the 2 and 5 harmonic restraint functions are set for the
transformer application shown in Figure 8-1 (refer to the discussion in Overview Of Preprogrammed Logic
Schemes).
Typically, the 51 protection element is coordinated with down-line protection devices to provide
overlapping Phase, Neutral, and Negative Sequence timed backup protection for zones beyond the
equipment being protected. In the low impedance, bus application, the 51 protection element must
coordinate with the feeder protection of the circuits connected to the bus.

Integration Of Protection, Control, And I/O Elements


The logic settings in Table 8-1 also include the logic equations that connect the various elements of the
basic differential scheme. For example, the three underlined commands in the equations of Table 8-1
provide the electrical connection between the 87 element (trip enabled by the settings) and trip outputs 1,
2, and 3. Referring to Figures 8-1 and 8-2, the 87 protection element trips through outputs 1, 2, and 3.
The user can apply any or all of the outputs. The 51 protection element (also trip enabled by the settings)
trips through output 4. There are no virtual switches used in this application.
Control of the active setting group can be manual or automatic. For the BASIC-87 application, setting
group control is programmed for continuous automatic operation because the /0 (not 0), logic 1 is applied
to the AUTO input of the Active Setting Group Control Logic as shown in Figure 8-2.

8-6 Application BE1-CDS


Alarms
Three logic variables drive the front panel LEDs: Relay Trouble (ALMREL), Major Alarm (ALMMAJ), and
Minor Alarm (ALMMIN). A fourth logic variable, Logic Alarm (ALMLGC), has no associated front panel
LED. When the relay self-test detects a problem in the relay (ALMREL) as programmed for the BASIC-87
scheme, the Relay Trouble LED lights, output A operates, and all other outputs are disabled. When a
Major Alarm is detected (ALMMAJ), the associated LED lights and output six operates. When a Minor
Alarm (ALMMIN) is detected, the associated LED lights, but in this scheme, no output relay is
programmed to operate.

Note
Tables 8-2 through 8-5 provide detailed logic definitions for the inputs, outputs, protection,
and control elements. Only those inputs, logic blocks, virtual switches, and outputs in use
for the BASIC-87 preprogrammed logic are described in the following Tables.

Table 8-2. BASIC-87 Contact Input Logic


Variable Label State Labels, 7 Char.
Input Purpose 16 Characters Closed (1) Open (0)
IN1 Optional input. Used for CT input circuit 1 breaker BREAKER-1 CLOSED OPEN
status indication in SER reports. TRUE when
breaker closed.
IN2 Optional input. Used for CT input circuit 2 breaker BREAKER-2 CLOSED OPEN
status indication in SER reports. TRUE when
breaker closed.
IN3 Optional input. Used for 86 status indication in 86-TRIPPED TRIPPED NORMAL
SER reports. TRUE when 86 tripped.
IN6 to Optional inputs. Used for programmable alarms INPUT_6,
IN8 and SER reporting. For example, sudden pressure INPUT_7, CLOSED OPEN
trip or transformer hot-spot alarm, etc. Drives VO13 INPUT_8
to VO15 which are programmable alarm points 21
to 23. Label inputs as appropriate.

Table 8-3. BASIC-87 Function Block Logic


BESTlogic Mode
Function Purpose Expression Setting
87 Used for percent-restrained differential protection with high- 0 1
speed unrestrained instantaneous differential protection (enabled)
51P Used for timed phase-overcurrent protection for CT input circuit 0 1
1 (enabled)
51N Used for timed neutral-overcurrent protection for CT input 0 1
circuit 1 (enabled)
51Q Used for timed negative sequence overcurrent protection for 0 1
CT input circuit 1 (enabled)
GROUP Auto/Manual Logic: Set to 1 (/0) to enable automatic selection. /0 1
No manual selection is used. (enabled)

Table 8-4. BASIC-87 Virtual Switch Logic


Variable Label State Labels, 7 Char.
Switch Purpose Mode 16 Characters Closed (1) Open (0)
N/A No virtual switches used

BE1-CDS Application 8-7


Table 8-5. BASIC-87 Output Logic
State Labels,
7 Char.
Variable
Output Purpose Description Label 16 Closed Open
Characters (1) (0)

VOA Relay Trouble alarm OUTA contact closes when RELAY- ACTIVE NORMAL
(OUTA) relay trouble alarm occurs TROUBLE
BESTlogic Expression: VOA=0
VO1 Phase differential trip. OUT1 contact closes if 87TRIP- TRIP NORMAL
(OUT1) OUT1 is a high-speed trip restrained or unrestrained trip OUT1
contact occurs
BESTlogic Expression: VO1=87RT+87UT
VO2 Phase differential trip OUT2 contact closes if 87TRIP- TRIP NORMAL
(OUT2) restrained or unrestrained trip OUT2
occurs
BESTlogic Expression: VO2=87RT+87UT
VO3 Phase differential trip OUT3 contact closes if 87TRIP- TRIP NORMAL
(OUT3) restrained or unrestrained trip OUT3
occurs
BESTlogic Expression: VO3=87RT+87UT
VO4 Time overcurrent trip. May OUT4 contact closes if any 51TRIP- TRIP NORMAL
(OUT4) be used to direct trip main time overcurrent (51P, N, or OUT4
breaker or lockout Q) trip occurs
BESTlogic Expression: VO4=51PT+51NT+51QT
VO6 Used to annunciate an OUT6 contact closes when MAJOR- ALARM NORMAL
(OUT6) alarm any programmed major alarm ALARM
condition is TRUE
BESTlogic Expression: VO6=ALMMAJ
VO11 Protective trip expression VO11 is TRUE when any 87 or PROTECTI TRIP NORMAL
51 element trips VE-TRIP
BESTlogic Expression: VO11=51PT+51NT+51QT+87RT+87UT
VO12 Protective pickup VO12 is TRUE when any 87 or PROT- PU NORMAL
expression 51 element picks up PICKED-UP
BESTlogic Expression: VO11=87UT+51PPU+51NPU+51QPU+87RPU (87UT is included to trigger the
fault recorder because there is no unrestrained pickup output)
VO13 Optional. Use to VO13 is TRUE when IN6 is IN6-ALARM ACTIVE NORMAL
(ALARM annunciate an alarm when TRUE
POINT 21) alarm point 21 is enabled
BESTlogic Expression: VO13=IN6
VO14 Optional. Use to VO14 is TRUE when IN7 is IN7-ALARM ACTIVE NORMAL
(ALARM annunciate an alarm when TRUE
POINT 22) alarm point 22 is enabled
BESTlogic Expression: VO14=IN7
VO15 Optional. Use to VO15 is TRUE when IN8 is IN8-ALARM ACTIVE NORMAL
(ALARM annunciate an alarm when TRUE
POINT 23) alarm point 23 is enabled
BESTlogic Expression: VO15=IN8

8-8 Application BE1-CDS


BASIC TRANSFORMER LOGIC SCHEME
The basic transformer logic scheme (BASIC-TX) was designed to provide a primary zone of differential
protection and three backup zones of time overcurrent protection for detecting phase and ground faults in
two-winding transformer applications.
Figure 8-3 is a one-line drawing and Figure 8-4 is a logic drawing that represent the logic settings and
equations shown in Table 8-6. In Table 8-6, the user can see the protection and control elements that are
enabled for the BASIC-TX application and how the elements are logically wired together (equations). If
the user should decide to build on this scheme, all elements required for a more detailed application are
available through programming. For programming details, refer to Section 7, BESTlogic Programmable
Logic.
Table 8-6. BASIC-TX Logic Settings And Equations
SL-N=BASIC-TX
SL-87=1,0
SL-87ND=0,0
SL-50TP=0,0; SL-50TN=0,0; SL-50TQ=0,0
SL-150TP=0,0; SL-150TN=0,0; SL-150TQ=0,0
SL-250TP=0,0; SL-250TN=0,0; SL-250TQ=0,0
SL-51P=0,0; SL-51N=G,0; SL-51Q=0,0
SL-151P=1,0; SL-151N=1,0; SL-151Q=1,0
SL-251P=2,0; SL-251N=2,0; SL-251Q=2,0
SL-62=0,0,0
SL-162=0,0,0
SL-BF=0,0,0
SL-GROUP=1,0,0,0,0,/0
SL-43=0
SL-143=0
SL-243=0
SL-343=0
SL-443=0
SL-543=0
SL-643=0
SL-743=0
SL-101=0
SL-CKTMON=0,0,0
SL-VOA=0
SL-VO1=87RT+87UT
SL-VO2=87RT+87UT
SL-VO3=87RT+87UT
SL-VO4=151PT+51NT+151NT+151QT
SL-VO5=251PT+251NT+251QT
SL-VO6=ALMMAJ
SL-VO7=0
SL-VO8=0
SL-VO9=0
SL-VO10=0
SL-VO11=151PT+251PT+51NT+151NT+251NT+151QT+251QT+87RT+87UT
SL-VO12=87UT+151PPU+251PPU+51NPU+151NPU+251NPU+151QPU+251QPU+87RPU
SL-VO13=IN6
SL-VO14=IN7
SL-VO15=IN8

BE1-CDS Application 8-9


Trip

BE1-CDS220
CT Input 1
Out4

52-1 151P 151N 151Q

Out2

Out1
86T
CT Input 1

Out3
51N 87
CT Input G
(Optional)
CT Input 2
Out5

251P 251N 251Q


52-2
Trip

CT Input 2

D2843-24.vsd
04-20-99

Figure 8-3. Typical One-Line Diagram For BASIC-TX

8-10 Application BE1-CDS


51NT
51N VOA
BLK Output
ModeG 51NPU Relay OUTA
IN1 Breaker1 Status Trouble Logic
OPTO

IN2 Breaker2 Status 151PT


OPTO
BLK 151P
Mode1 151PPU VO1
IN3 86 Status 87 Trip
OPTO Output
OUT1
Logic
IN4 Not Used 151NT
OPTO
BLK 151N
Mode1 151NPU
IN5 Not Used VO2
OPTO
87 Trip
Output
IN6 Alarm VO13 Alarm Point 21 151QT OUT2
OPTO Logic
BLK 151Q
Mode1 151QPU
IN7 Alarm VO14 Alarm Point 22
OPTO
VO3
IN8 Alarm VO15 Alarm Point 23 87RT 87 Trip
OPTO Output
OUT3
87RPU Logic

87 87UT
BLK
Mode1 2NDHAR
VO4
5THHAR 151 Trip
4 Output
OUT4
Logic

251PT
BLK 251P
Mode2 251PPU VO5
251 Trip
3 Output
SG0 OUT5
D0 ACTIVE Logic
SG1 251NT
D1 SETTING BLK 251N
D2 GROUP SG2 Mode2 251NPU ALMMAJ
D3 CONTROL
0 SG3
AUTO Mode1 ALMMIN VO6
SA- Alarm Major
251QT RESET Alarm
251Q ALMLGC Output OUT6
BLK
Note: For clarity, multiple variables Mode2 251QPU Logic
going to the same OR Gate are shown
by a single line into the OR Gate.
9 VO11 PROT TRIP

D2843-25.vsd VO12 PROT PU


09-27-99 9

Figure 8-4. Typical Logic Diagram For BASIC-TX

Protection Elements
Referring to Figure 8-3, the 87 and 151 protection elements are connected to the high-side CT, input 1.
The 87 and 251 protection elements are connected to the low-side CT, input 2. The 51 protection element
(N only) is connected to a ground CT at the grounded side of a delta-wye transformer. The ground-input
(G) is an option on the BE1-CDS and must be ordered. Paralleled CTs inside a delta tertiary (3Io) can
also feed the 51N. The 87, 51, 151, and 251 protection elements are logic enabled by the settings shown
in Table 8-6 to provide a trip through the BE1-CDS output contacts. Protection elements set to 0 are
setting disabled and will not provide a trip output even if logic enabled.
Typically, the BE1-CDS would be applied with an BE1-851 or BE1-951 multifunction overcurrent relay to
provide independent, overlapping, backup protection in the event of a common mode failure. Typically,
the 87 protection element provides high speed restrained differential and unrestrained differential phase
and ground protection for faults inside the differential zone. At the same time, it provides security against
nd
misoperations resulting from transformer inrush by restraining and preventing a trip in the presence of 2
th
and 5 harmonics.
Typically, the 151 protection element is coordinated with the low-side bus protection to provide Phase,
Neutral, and Negative Sequence timed backup protection for the low-side bus if the bus protection is out
of service.
Typically, the 251 protection element is coordinated with the low-side feeder protection to provide Phase,
Neutral, and Negative Sequence timed backup protection for feeder faults if the feeder protection is out of
service.
Typically, the 51N protection element is coordinated with the low-side bus and feeder protection to provide
Neutral (ground) timed backup protection for transformer low-side, bus, and feeder ground faults if any
primary zone of protection is of service.
BE1-CDS Application 8-11
Integration Of Protection, Control, And I/O Elements
The logic equations of Table 8-6 establish the control connections between BASIC-TX scheme elements.
For example, the three underlined logic settings in the equations of Table 8-6 provide the electrical
connection between the 87 element (trip enabled by the settings) and trip outputs 1, 2, and 3. Referring to
Figures 8-3 and 8-4, the 87 protection element trips through outputs 1, 2, and 3. The user can apply any
or all of the outputs. The 151 and 51N protection elements (also trip enabled by the settings) trip through
output 4, while the 251 protective element (also trip enabled by the settings) trips through output 5.
Protection elements set at 0 are setting disabled and will not provide a trip output even if logic enabled.
Control of the active setting group can be manual or automatic. For the BASIC-TX application, setting
group control is programmed for continuous automatic operation because the /0 (not 0), logic 1 is applied
to the AUTO input of the Active Setting Group Control Logic as shown in Figure 8-4. Tables 8-7 through
8-10 provide detailed logic definitions for the inputs, outputs, protection, and control elements.

Alarms
Three logic variables drive the front panel LEDs: Relay Trouble (ALMREL), Major Alarm (ALMMAJ), and
Minor Alarm (ALMMIN). A fourth logic variable, Logic Alarm (ALMLGC), has no associated front panel
LED. When the relay self-test detects a problem in the relay (ALMREL) as programmed for the BASIC-TX
scheme, the Relay Trouble LED lights, output A operates, and all outputs are disabled. When a Major
Alarm is detected (ALMMAJ), the associated LED lights and output 6 operates. When a Minor Alarm
(ALMMIN) is detected, the associated LED lights, but in this scheme, no output relay is programmed to
operate.

Note
Tables 8-7 through 8-10 provide detailed logic definitions for the inputs, outputs,
protection, and control elements. Only those inputs, logic blocks, virtual switches, and
outputs in use for the BASIC-TX preprogrammed logic are described in the following
Tables.

Table 8-7. BASIC-TX Contact Input Logic


Variable Label State Labels, 7 Char
Input Purpose 16 Characters Closed (1) Open (0)
IN1 Optional input. Used for CT input circuit 1 breaker BREAKER-1 CLOSED OPEN
status indication in SER reports. TRUE when breaker
closed.
IN2 Optional input. Used for CT input circuit 2 breaker BREAKER-2 CLOSED OPEN
status indication in SER reports. TRUE when breaker
closed.
IN3 Optional input. Used for 86 status indication in SER 86-TRIPPED TRIPPED NORMAL
reports. TRUE when 86 tripped.
IN6-IN8 Optional inputs. Used for programmable alarms and INPUT_6,
SER reporting. For example, sudden pressure trip or INPUT_7, CLOSED OPEN
transformer hot spot alarm, etc. Drives VO13-VO15 INPUT_8
which are programmable alarm points 21-23. Label
inputs as appropriate.

8-12 Application BE1-CDS


Table 8-8. BASIC-TX Function Block Logic
BESTlogic
Function Purpose Expression Mode Setting
87 Used for percent-restrained differential protection with 0 1
high-speed unrestrained instantaneous differential (ENABLED)
protection
51N Used for timed ground-overcurrent protection for 0 G
independent ground input circuit (OPT GND CT)
151P Used for timed phase-overcurrent protection for CT input 0 1
circuit 1 (CT CKT 1)
151N Used for timed neutral-overcurrent protection for CT input 0 1
circuit 1 (CT CKT 1)
151Q Used for timed negative sequence-overcurrent protection 0 1
for CT input circuit 1 (CT CKT 1)
GROUP Auto/Manual Logic: Set to 1 (/0) to enable automatic /0 1
selection. No manual selection is used. (DISCRETE)
251P Used for timed phase-overcurrent protection for CT input 0 2
circuit 2 (CT CKT 2)
251N Used for timed neutral-overcurrent protection for CT input 0 2
circuit 2 (CT CKT 2)
251Q Used for timed negative sequence-overcurrent protection 0 2
for CT input circuit 2 (CT CKT 2)

Table 8-9. BASIC-TX Virtual Switch Logic


Variable Label State Labels, 7 Char.
Switch Purpose Mode 16 Characters Closed (1) Open (0)
N/A No virtual switches used

Table 8-10. BASIC-TX Output Logic


Variable State Labels, 7 Char
Output Purpose Description Label 16 Closed Open
Characters (1) (0)
VOA Relay Trouble alarm OUTA contact closes when relay RELAY- ACTIVE NORMAL
(OUTA) trouble alarm occurs TROUBLE
BESTlogic Expression: VOA=0
VO1 Phase differential trip. OUT1 contact closes if restrained 87TRIP- TRIP NORMAL
(OUT1) OUT1 is a high-speed trip or unrestrained trip occurs OUT1
contact
BESTlogic Expression: VO1=87RT+87UT
VO2 Phase differential trip OUT2 contact closes if restrained 87TRIP- TRIP NORMAL
(OUT2) or unrestrained trip occurs OUT2
BESTlogic Expression: VO2=87RT+87UT
VO3 Phase differential trip OUT3 contact closes if restrained 87TRIP- TRIP NORMAL
(OUT3) or unrestrained trip occurs OUT3
BESTlogic Expression: VO3=87RT+87UT
VO4 Time overcurrent trip. May OUT4 contact closes if any time 151TRIP- TRIP NORMAL
(OUT4) be used to direct trip main overcurrent (51N, 151P, N, or Q) OUT4
breaker or lockout trip occurs
BESTlogic Expression: VO4=51N+151PT+151NT+151QT
BE1-CDS Application 8-13
Table 8-10. BASIC-TX Output Logic - Continued
Variable State Labels, 7 Char
Output Purpose Description Label 16 Closed Open
Characters (1) (0)
VO5 Time overcurrent trip. May OUT5 contact closes if any time 251 TRIP- TRIP NORMAL
(OUT5) be used to direct trip main overcurrent (251P, N, or Q) trip OUT4
breaker or lockout occurs
BESTlogic Expression: VO5=251PT+251NT+251QT
VO6 Used to annunciate an OUT6 contact closes when any MAJOR- ALARM NORMAL
(OUT6) alarm programmed major alarm ALARM
condition is TRUE
BESTlogic Expression: VO6=ALMMAJ
VO11 Protective trip expression VO11 is TRUE when any 87, 51, PROTECTI TRIP NORMAL
151, or 251 element trips VE-TRIP
BESTlogic Expression: VO11=151PT+251PT+51NT+151NT+251NT+151QT+251QT+87RT+87UT
VO12 Protective pickup VO12 is TRUE when any 87 or 51 PROT- PU NORMAL
expression element picks up PICKED-UP
BESTlogic Expression:
VO11=87UT+151PPU+251PPU+51NPU+151NPU+251NPU+151QPU+251QPU+87RPU
(87UT is included to trigger the fault recorder because there is no unrestrained pickup output)
VO13 Optional. Use to VO13 is TRUE when IN6 is TRUE IN6-ALARM ACTIVE NORMAL
(ALARM annunciate an alarm when
POINT alarm point 21 is enabled
21)
BESTlogic Expression: VO13=IN6
VO14 Optional. Use to VO14 is TRUE when IN7 is TRUE IN7-ALARM ACTIVE NORMAL
(ALARM annunciate an alarm when
POINT alarm point 22 is enabled
22)
BESTlogic Expression: VO14=IN7
VO15 Optional. Use to VO15 is TRUE when IN8 is TRUE IN8-ALARM ACTIVE NORMAL
(ALARM annunciate an alarm when
POINT alarm point 23 is enabled
23)
BESTlogic Expression: VO15=IN8

BASIC TRANSFORMER WITH CONTROL LOGIC SCHEME


The Basic Transformer With Control Logic (TX-W-CTL) scheme was designed to provide a primary zone
of differential relaying and three backup zones of time overcurrent relaying for phase and ground faults in
two-winding transformer applications. This scheme also uses virtual control switch logic to eliminate the
need for external control switches.
The control switch elements are referred to as virtual because they have no physical form. They exist
only in logic form and can only be operated via the ASCII command interface or the front panel HMI. The
virtual 101 switch is used to trip and close the transformer low-side breaker. Virtual control switches 43
and 143 are used to trip and close the transformer high-side breaker. Virtual control switch 243 turns off
the 87 protection element and 343 selects whether the setting group control is automatic or manual.
Figure 8-5 is a one-line drawing and Figure 8-6 is a logic drawing that represents the logic settings shown
in Table 8-11. In Table 8-11, the user can see the protection and control elements that are enabled for the

8-14 Application BE1-CDS


TX-W-CTL application and how the elements are logically wired together (equations). If the user should
decide to build on this scheme, all elements required for a more detailed application are available through
programming. For programming details, refer to Section 7, BESTlogic Programmable Logic.

Trip
BE1-CDS220
CT Input 1
Out1 86T

52-1 43 151P 151N 151Q


C
lo
se

Out3
Out2

143

CT Input 1

51N 87
CT Input G
(Optional)
f
of

CT Input 2
ut
C

Out4
243

251P 251N 251Q

Out5
se

C T
Auto/Manual
lo
C

101
52-2
Group
343
Control
Trip

CT Input 2

D2843-20.vsd
09-21-00

Figure 8-5. Typical One-Line Diagram For TX-W-CTL

BE1-CDS Application 8-15


VOA
51NT Relay
BLK 51N Trouble
51NPU Output
ModeG OUTA
IN1 Breaker1 Status Logic
OPTO
VO1
IN2 Breaker2 Status 151PT 86
OPTO Trip
BLK 151P 6 Output
Mode1 151PPU OUT1
IN3 86 Status Logic
OPTO
VO2
IN4 Not Used 151NT 52-1
OPTO 52-1 6 Trip
BLK 151N 43 43 Output
Trip OUT2
Mode1 151NPU Logic
IN5 Not Used Mode3
OPTO

IN6 Not Used 151QT


OPTO 151Q
BLK
Mode1 151QPU
IN7 Alarm VO14 Alarm Point 22
OPTO
VO3
VO15 Alarm Point 23 87RT 52-1
IN8 Alarm
OPTO 52-1 Close
143 Output
87RPU 143 Close OUT3
Logic
Mode3
243 243 DIFF Cutoff 87 87UT
BLK
Mode2 Mode1 2NDHAR
VO13 Alarm Point 21 VO4
5THHAR 52-2
5 Trip Output
OUT4
101T Logic
SG0
Setting Group D0 ACTIVE 52-2
Control D1 SETTING SG1 251PT 1 0 1 C Close
101
Auto/Manual D2 GROUP SG2 BLK 251P Mode1
Mode2 251PPU
D3 CONTROL 101SC VO5
343 343 SG3
AUTO Mode1 52-2
Mode2
Close Output
251NT OUT5
Logic
BLK 251N
Mode2 251NPU ALMMAJ

ALMMIN VO6
SA- Alarm Major
Note: For clarity, multiple variables going 251QT RESET Alarm Output OUT6
to the same OR Gate are shown by a BLK 251Q ALMLGC
Mode2 251QPU Logic
single line into the OR Gate.

9 VO11 PROT TRIP

D2843-21.vsd
04-20-99 9 VO12 PROT PU

Figure 8-6. Typical Logic Diagram For TX-W-CTL

Table 8-11. TX-W-CTL Logic Settings and Equations


SL-N=TX-W-CTL
SL-87=1,243
SL-87ND=0,0
SL-50TP=0,0; SL-50TN=0,0; SL-50TQ=0,0
SL-150TP=0,0; SL-150TN=0,0; SL-150TQ=0,0
SL-250TP=0,0; SL-250TN=0,0; SL-250TQ=0,0
SL-51P=0,0; SL-51N=G,0; SL-51Q=0,0
SL-151P=1,0; SL-151N=1,0; SL-151Q=1,0
SL-251P=2,0; SL-251N=2,0; SL-251Q=2,0
SL-62=0,0,0
SL-162=0,0,0
SL-BF=0,0,0
SL-GROUP=1,0,0,0,0,/343
SL-43=3
SL-143=3
SL-243=2
SL-343=2
SL-443=0
SL-543=0
SL-643=0
SL-743=0
SL-101=1
SL-CKTMON=0,0,0

8-16 Application BE1-CDS


SL-VOA=0
SL-VO1=151PT+51NT+151NT+151QT+87RT+87UT
SL-VO2=151PT+51NT+151NT+151QT+87RT+87UT+43
SL-VO3=/IN3*143
SL-VO4=251PT+251NT+251QT+87RT+87UT+101T
SL-VO5=/IN3*101C
SL-VO6=ALMMAJ
SL-VO7=0
SL-VO8=0
SL-VO9=0
SL-VO10=0
SL-VO11=151PT+251PT+51NT+151NT+251NT+151QT+251QT+87RT+87UT
SL-VO12=87UT+151PPU+251PPU+51NPU+151NPU+251NPU+151QPU+251QPU+87RPU
SL-VO13=/243
SL-VO14=IN7
SL-VO15=IN8

Protection Elements
Referring to Figure 8-5, the 87 and 151 protection elements are connected to the high-side CT, input 1.
The 87 and 251 protection elements are connected to the low-side CT, input 2. The 51 protection element
(N only) is connected to a ground CT at the grounded side of a delta-wye transformer. The ground input
(G) is an option on the BE1-CDS and must be ordered. Paralleled CTs inside a delta tertiary (3Io) can
also feed the 51N. The 87, 51, 151, and 251 protection elements are logic enabled to provide a trip
through the BE1-CDS outputs. Protection elements set at 0 are setting disabled and will not provide a trip
output, even if logic enabled.
Typically, the BE1-CDS would be applied with an BE1-851 or BE1-951 multifunction overcurrent relay to
provide independent, overlapping, backup protection in the event of a common mode failure. The 87
protection element provides high-speed restrained differential and unrestrained differential phase and
ground protection for faults inside the differential zone. At the same time, it provides security against
nd
misoperations resulting from transformer inrush by restraining and preventing a trip in the presence of 2
th
and 5 harmonics.
Typically, the 151 protection element is coordinated with the low-side bus protection to provide Phase,
Neutral, and Negative Sequence timed backup protection for the low-side bus if the bus protection is out
of service.
Typically, the 251 protection element is coordinated with the low-side feeder protection to provide Phase,
Neutral, and Negative Sequence timed backup protection for feeder faults if the feeder protection is out of
service.
Typically, the 51N protection element is coordinated with the low-side bus and feeder protection to provide
Neutral (ground) timed backup protection for transformer low-side, bus, and feeder ground faults if any
primary zone of protection is of service.

Integration Of Protection, Control, And I/O Elements


The logic settings in Table 8-11 also include the logic equations that establish the control connections
between elements of the TX-W-CTL scheme. For example, the three underlined commands in the logic
equations of Table 8-11 provide the electrical connection between the 87 element (trip enabled by the
settings) and trip outputs 1, 2, and 4. Referring to Figures 8-5 and 8-6, the 87 protection element trips
through outputs 1, 2, and 4. The 151 and 51N protection elements (also trip enabled by the settings) trip
through outputs 1 and 2, and the 251 protective element (also trip enabled by the settings) trips through
output 4. Protection elements set at 0 are setting disabled and will not provide a trip output even if logic
enabled.
Virtual control switch elements enabled for use in this scheme are 101, 043, 143, 243, and 343. The 101
control switch trips the low-side breaker through output 4 and closes the low-side breaker through output 5
if IN3 (86 input) is not TRUE. The high-side breaker is tripped by 043 through output 2 and closed by 143
through output 3 if IN3 (86 input) is not TRUE. Control switch 243 is used to turn the 87 function on or off.

BE1-CDS Application 8-17


Control of the active setting group can be manual or automatic. For the TX-W-CTL application, setting
group control is enabled for discrete input and automatic or manual control as determined by the position
of virtual switch 343.

Alarms
Three logic variables drive the front panel LEDs: Relay Trouble (ALMREL), Major Alarm (ALMMAJ), and
Minor Alarm (ALMMIN). A fourth logic variable, Logic Alarm (ALMLGC), has no associated front panel
LED. When the relay self-test detects a problem in the relay (ALMREL) as programmed for the TX-W-
CTL scheme, the Relay Trouble LED lights, output A operates, and all outputs are disabled. When a
Major Alarm is detected (ALMMAJ), the associated LED lights and output 6 operates. When a Minor
Alarm (ALMMIN) is detected, the associated LED lights, but in this scheme, no output relay is
programmed to operate.

Note
Tables 8-12 through 8-15 provide detailed logic definitions for the inputs, outputs,
protection, and control elements. Only those inputs, logic blocks, virtual switches, and
outputs in use for the TX-W-CTL preprogrammed logic are described in the following
Tables.

Table 8-12. TX-W-CTL Contact Input Logic


Variable State Labels, 7 Char
Input Purpose Label 16 Closed (1) Open (0)
Characters
IN1 Optional input. Used for CT input circuit 1 breaker status BREAKER-1 CLOSED OPEN
indication in SER reports. TRUE when breaker closed.
IN2 Optional input. Used for CT input circuit 2 breaker status BREAKER-2 CLOSED OPEN
indication in SER reports. TRUE when breaker closed.
IN3 Optional input. Used for 86 status indication and locks 86-TRIPPED TRIPPED NORMAL
out the low-side and high-side breakers when TRUE.
TRUE when 86 tripped.
IN7, IN8 Optional inputs. Used for programmable alarms and SER INPUT_7, CLOSED OPEN
reporting. For example, sudden pressure trip or INPUT_8
transformer hot spot alarm, etc. Drives VO14-VO15
which are programmable alarm points 22-23. Label
inputs as appropriate.

Table 8-13. TX-W-CTL Function Block Logic


BESTlogic Mode
Function Purpose Expression Setting
87 Used for percent-restrained differential protection with high- 243 1
speed unrestrained instantaneous differential protection (ENABLED)
51N Used for timed ground-overcurrent protection for independent 0 G
ground input circuit (OPT GND CT)
151P Used for timed phase-overcurrent protection for CT input circuit 0 1
1 (CT CKT 1)
151N Used for timed neutral-overcurrent protection for CT input 0 1
circuit 1 (CT CKT 1)
151Q Used for timed negative sequence-overcurrent protection for 0 1
CT input circuit 1 (CT CKT 1)

8-18 Application BE1-CDS


Table 8-13. TX-W-CTL Function Block Logic - Continued
BESTlogic Mode
Function Purpose Expression Setting
GROUP Auto/Manual Logic: Disable automatic selection when virtual /343 1
switch 343 is in the manual position. (DISCRETE)
251P Used for timed phase-overcurrent protection for CT input circuit 0 2
2 (CT CKT 2)
251N Used for timed neutral-overcurrent protection for CT input 0 2
circuit 2 (CT CKT 2)
251Q Used for timed negative sequence-overcurrent protection for 0 2
CT input circuit 2 (CT CKT 2)

Table 8-14. TX-W-CTL Virtual Switch Logic


Variable Label State Labels, 7 Char
Switch Purpose Mode 16 Characters Closed (1) Open (0)
43 Trip high-side breaker (1) 3 BREAKER1- TRIP NORMAL
(OFF MOM-ON) TRIP
143 Close low-side breaker (1) 3 BREAKER1- CLOSE NORMAL
(OFF MOM-ON) CLOSE
243 Differential Cutoff switch. The 87 2 87-CUTOFF DISABLD NORMAL
function is blocked when the switch (ON/OFF)
is closed
343 Automatic setting group change logic 2 SETGRP- MANUAL AUTO
auto/manual switch (ON/OFF) CONTROL
101 Allows breaker to be tripped or 1 N/A N/A N/A
closed manually from HMI or ASCII (ENABLED)
command interface

Table 8-15. TX-W-CTL Output Logic


Variable State Labels, 7 Char
Output Purpose Description Label 16 Closed (1) Open (0)
Characters
VOA Relay Trouble alarm OUTA contact closes when RELAY- ACTIVE NORMAL
(OUTA) relay trouble alarm occurs TROUBLE
BESTlogic Expression: VOA=0
VO1 Phase differential trip. OUT1 contact closes if a TRIP_86T- TRIP NORMAL
(OUT1) OUT1 is a high-speed trip restrained, unrestrained, or time OUT1
contact overcurrent trip occurs
BESTlogic Expression: VO1=87RT+87UT+51NT+151PT+151NT+151QT
VO2 Breaker 1 Trip OUT2 contact closes if TRIP-BKR1- TRIP NORMAL
(OUT2) restrained or unrestrained trip OUT2
occurs or for 51 or 151 trip or
for control switch trip
BESTlogic Expression: VO2=87RT+87UT+51NT+151PT+151NT+151QT+43
VO3 Breaker 1 close Close breaker if virtual control CLOSE- CLOSE NORMAL
(OUT3) switch is TRUE and 86 lockout BKR1-OUT3
is not tripped.
BESTlogic Expression: VO3=143*/IN3

BE1-CDS Application 8-19


Table 8-15. TX-W-CTL Output Logic - Continued
Variable State Labels, 7 Char
Output Purpose Description Label 16 Closed (1) Open (0)
Characters
VO4 Breaker 2 trip OUT4 contact closes if TRIP-BKR2- TRIP NORMAL
(OUT4) restrained or unrestrained trip OUT4
or any time overcurrent (251P,
N, or Q) trip occurs or for
control switch trip
BESTlogic Expression: VO4=87RT+87UT+251PT+251NT+251QT+101T
VO5 Breaker 2 close Close breaker if virtual control CLOSE- CLOSE NORMAL
(OUT5) switch is TRUE and 86 lockout BKR2-OUT5
is not tripped.
BESTlogic Expression: VO5=101C*/IN3
VO6 Used to annunciate an OUT6 contact closes when any MAJOR- ALARM NORMAL
(OUT6) alarm by contact closure programmed major alarm ALARM
or opening if any of the condition is TRUE
conditions programmed
as a major program-
mable alarm is TRUE.
BESTlogic Expression: VO6=ALMMAJ
VO11 Protective trip expression VO11 is TRUE when any 87, PROTECTIVE TRIP NORMAL
51, 151, or 251 element trips -TRIP
BESTlogic Expression: VO11=87RT+87UT+51NT+151PT+151NT+151QT+251PT+251NT+251QT
VO12 Protective pickup VO12 is TRUE when any 87, PROT- PU NORMAL
expression 51, 151, or 251 element picks PICKED-UP
up
BESTlogic Expression:
VO12=87RPU+87UT+51NPU+151PPU+151NPU+151QPU+251PPU+251NPU+251QPU
(87UT is included to trigger the fault recorder because there is no unrestrained pickup output)
VO13 Alarm to indicate that diff- VO13 is TRUE when virtual 87-BLOCKED ACTIVE NORMAL
(ALARM erential cutoff switch is in switch 243 is in the closed
POINT the block operation posit- position
21) ion. This can be used as
a programmable alarm by
enabling alarm point 21.
The programmable
Variable Label will be
displayed on the alarm
report when TRUE.
BESTlogic Expression: VO13=243
VO14 Optional. Use to VO14 is TRUE when IN7 is IN7-ALARM ACTIVE NORMAL
(ALARM annunciate an alarm TRUE
POINT when alarm point 22 is
22) enabled
BESTlogic Expression: VO14=IN7
VO15 Optional. Use to VO15 is TRUE when IN8 is IN8-ALARM ACTIVE NORMAL
(ALARM annunciate an alarm TRUE
POINT when alarm point 23 is
23) enabled
BESTlogic Expression: VO15=IN8

8-20 Application BE1-CDS


TRANSFORMER WITH BACKUP SCHEME
The Transformer With Backup (TX-W-BU) scheme was designed to provide high-speed phase and ground
fault protection for a two-winding transformer and definite time backup protection for the associated low-
side bus (similar to the BE1-851 BUS and BACKUP Logic Scheme). Figure 8-7 shows the interconnection
of the BE1-851 or BE1-951 relays providing bus and feeder protection with a BE1-CDS220 (TX-W-BU)
providing backup transformer protection. The TX-W-BU scheme also includes a low-side breaker BF
(breaker failure) protection element with fast current reset. Current and contact supervised external
breaker failure initiates (BFI) are included for the low-side breaker BF element. Virtual control switch logic
is used for local or remote (SCADA) control and can be used to replace the equivalent panel control
switch. See the paragraphs on BUS WITH BACKUP SCHEME, in this Section for an interconnection of
BE1-851 or BE1-951 relays providing feeder protection with BE1-CDS220 relays providing bus protection
(BUS-W-BU) and transformer protection (TX-W-BU).
The control switch elements are referred to as virtual because they have no physical form, they exist only
in logic form, and they can only be operated via the ASCII command interface or the front panel HMI. The
virtual 101 switch is used to trip and close the transformer low-side breaker, and 743 is used to select test
mode enable. The user may choose to eliminate the use of external switches, as the virtual switches are
fully functional equivalents of their physical counterparts.
Figure 8-8 is a one-line drawing and Figure 8-9 is a logic drawing that represent the logic settings and
equations shown in Table 8-16. In Table 8-16, the user can see the protection and control elements that
are enabled for the TX-W-BU application and how the elements are logically wired together (equations). If
the user should decide to build on this scheme, all elements required for a more detailed application are
available through programming. For programming details, refer to Section 7, BESTlogic Programmable
Logic.
Table 8-16. TX-W-BU Logic Settings and Equations
SL-N=TX-W-BU
SL-87=1,43
SL-87ND=0,0
SL-50TP=2,0; SL-50TN=2,0; SL-50TQ=2,0
SL-150TP=0,0; SL-150TN=0,0; SL-150TQ=0,0
SL-250TP=2,0; SL-250TN=2,0; SL-250TQ=2,0
SL-51P=0,0; SL-51N=G,0; SL-51Q=0,0
SL-151P=1,0; SL-151N=1,0; SL-151Q=1,0
SL-251P=2,0; SL-251N=2,0; SL-251Q=2,0
SL-62=1,VO9,VO15
SL-162=0,0,0
SL-BF=2,VO10,VO15
SL-GROUP=2,/IN5,0,0,0,0
SL-43=2
SL-143=0
SL-243=0
SL-343=0
SL-443=0
SL-543=0
SL-643=0
SL-743=2
SL-101=1
SL-CKTMON=0,0,0
SL-VOA=0
SL-VO1=151PT+51NT+151NT+151QT+87RT+87UT
SL-VO2=250TPT+250TNT+250TQT
SL-VO3=BFT+62
SL-VO4=251PT+251NT+251QT+87RT+87UT+VO9+101T+BFPU
SL-VO5=/IN3*/IN4*101C
SL-VO6=/IN5
SL-VO7=0

BE1-CDS Application 8-21


SL-VO8=0
SL-VO9=87RT*/VO15*IN2+87UT*/VO15*IN2+/VO15*IN2*IN6
SL-VO10=VO11+IN7*150TPPU+IN7*150TNPU+IN7*150TQPU
SL-VO11=
250TPT+250TNT+250TQT+151PT+251PT+51NT+151NT+251NT+151QT+251QT+87RT+87UT
SL-VO12=
87UT+250TPPU+250TNPU+250TQPU+151PPU+251PPU+51NPU+151NPU+251NPU+151QPU+
251QPU+87RPU
SL-VO13=43
SL-VO14=0
SL-VO15=/IN8+743

Protection Elements
Referring to Figure 8-8, the 87 and 151 protection elements are connected to the high-side CT, input 1
and the 87 and 251 protection elements are connected to the low-side CT, input 2. The 51 protection
element (N only) is connected to a ground CT at the grounded side of a delta-wye transformer. The
ground-input (G) is an option on the BE1-CDS and must be ordered. Paralleled CTs inside a delta tertiary
(3Io) can also feed the 51N. The 87, 51, 151, and 251 protection elements are logic enabled to provide a
trip by the settings shown in Table 8-16. Protection elements set at 0 are setting disabled and will not
provide a trip output even if logic enabled.
Typically, the TX-W-BU scheme would be applied with a BE1-851 on the feeder circuits, and a BE1-851 or
BE1-CDS on the bus main breaker interlocked with the feeder relay to provide high-speed, bus fault
protection. This combination provides independent, overlapping backup protection in the event of a
common mode failure.
Typically, the 87 protection element provides high speed restrained differential and unrestrained
differential phase and ground protection for faults inside the differential zone. At the same time, it provides
security against misoperations resulting from transformer inrush by restraining and preventing a trip in the
nd th
presence of 2 and 5 harmonics.
Typically, the 151 protection element is coordinated with the low-side bus protection to provide Phase,
Neutral, and Negative Sequence timed backup protection for the low-side bus if the bus protection is out
of service.
Typically, the 251 protection element is coordinated with the low-side feeder protection to provide Phase,
Neutral, and Negative Sequence timed backup protection for feeder faults if the feeder protection is out of
service.
Typically, the 51N protection element is coordinated with the low-side bus and feeder protection to provide
Neutral (ground) timed backup protection for transformer low-side, bus, and feeder ground faults if any
primary zone of protection is of service.
Typically, the 250T protection element is set to coordinate with a high-speed bus-interlocking scheme (851
or BE1-CDS) to provide a definite time coordination interval of 18 to 20 cycles for bus fault backup
protection. The 250T protection element should have a pickup setting greater than the highest feeder
instantaneous element to ensure that it will not pickup before any feeder relay.
Typically, the 50T protection element is set to provide fault detection but not to be picked-up on load. This
element provides current supervision for the external BFI input associated with the BF protection element.

Integration Of Protection, Control, And I/O Elements


The logic settings in Table 8-16 also include the logic equations that establish the control connections
between elements of the TX-W-BU scheme. For example, the two underlined commands in the settings
of Table 8-16 provide the electrical connection between the 87 element (trip enabled by the program) and
trip outputs 1 and 4. Referring to Figures 8-9 and 8-10, the 87 protection element trips through outputs 1
and 4. The 151 and 51N protection elements (also trip enabled by the settings) trip through output 1. The
251 protective element trips through output 4. The 250 protection element trips through output 2 and the
BF element trips through output 3. Protection elements set at 0 are setting disabled and will not provide a
trip output even if logic enabled.
8-22 Application BE1-CDS
Input 5 of the TX-W-BU scheme is hard wired from the feeder protection relays (851) (not shown on
Figure 8-8) allowing the TX-W-BU scheme to signal (through output 6) to the primary bus protection
scheme (851 or CDS) to switch to Feeder Backup Mode. This signaling method was chosen because of
limited 851 I/O. Input 6 of the TX-W-BU scheme is a contact supervised BFI input and Input 7 is a current
supervised BFI input.
Virtual control switch elements enabled for use in this scheme are 101, 043, and 743. The 101 control
switch trips the low-side breaker through output 4 and closes the low-side breaker through output 5.
Control switch 043 is used to turn the 87 function on or off and 743 us used to enable Test Mode.
Setting group selection mode 2, binary coded selection, is used to recognize the group setting state.
When Input D0 of the setting group selection element is high, it is interpreted as a binary 1 causing the
logic to switch to group 1. For normal operation, setting group 0 is active for the TX-W-BU scheme. Input
5 to the TX-W-BU scheme indicates when a feeder relay is out of service and causes a switch from setting
group 0 to setting group 1. At the same time, output 6 of the TX-W-BU scheme provides an input to the
primary bus protection relay.

Test Mode
When virtual control switch 743 is enabled, all breaker failure functions are defeated.

CAUTION
Test Mode Enable does not defeat the trip outputs of the relay. External trip test blades
must be opened or the TX-W-BU logic scheme must be modified to suit the user’s test
mode requirements. One option is to trip the breakers through an 86 device only.
Typically, 86 devices are installed with test blades in the breaker trip circuit so that the
protection scheme can be safely operational checked while the primary equipment is in
service. Another option is to inhibit all trip outputs when test mode is enabled; however,
external devices such as auxiliary relays and 86 devices would no longer be included in
the operational test.

Alarms
Three logic variables drive the front panel LEDs: Relay Trouble (ALMREL), Major Alarm (ALMMAJ), and
Minor Alarm (ALMMIN). A fourth logic variable, Logic Alarm (ALMLGC), has no associated front panel
LED. When the relay self-test detects a problem in the relay (ALMREL) as programmed for the TX-W-BU
scheme, the Relay Trouble LED lights, output A operates, and all outputs are disabled. When a Major
Alarm is detected (ALMMAJ), the associated LED lights, but in this scheme, no output relay is
programmed to operate. When a Minor Alarm (ALMMIN) is detected, the associated LED lights, but in this
scheme, no output relay is programmed to operate.

Note
Tables 8-17 through 8-20 provide detailed logic definitions for the inputs, outputs,
protection, and control elements. Only those inputs, logic blocks, virtual switches, and
outputs in use for the TX-W-BU preprogrammed logic are described in the following
Tables.

Table 8-17. TX-W-BU Contact Input Logic


Variable Label State Labels, 7 Char
Input Purpose 16 Characters Closed Open (0)
(1)
IN1 Optional input. Used for CT input circuit 1 breaker status BREAKER-1 CLOSED OPEN
indication in SER reports. TRUE when breaker closed.
IN2 Optional input. Used for CT input circuit 2 breaker status BREAKER-2 CLOSED OPEN
indication in SER reports. TRUE when breaker closed.
IN3 Optional input. Used for 86T status indication and locks 86T-TRIPPED TRIPPED NORMAL
out the low-side breaker when TRUE. TRUE when 86T is
tripped.

BE1-CDS Application 8-23


IN4 Optional input. Used for 86B status indication and locks 86B-TRIPPED TRIPPED NORMAL
out the low-side breaker when TRUE. TRUE when 86B is
tripped.
IN5 Puts transformer and bus relays in feeder backup mode FEEDERS_OK NORMAL FDR_OOS
when feeder relay out-of-service is detected by an open
contact. Feeder relays such as BE1-851 or BE1-951
using one of the preprogrammed schemes with interlock
logic.
IN6 Breaker Failure Initiate by external relays with breaker EXT-BFI-52B- INI NORMAL
status supervision. Typically used for differential or SUPV
sudden pressure tripping.
IN7 Breaker Failure Initiate by external relays with fault EXT-BFI-50- INI NORMAL
detector supervision. Typically used for overcurrent SUPV
tripping relays.
IN8 Puts the relay in test mode so that breaker failure is TEST-MODE- NORMAL TSTMODE
disabled when input 8 is de-energized. DISABL

Table 8-18. TX-W-BU Function Block Logic


BESTlogic Mode
Function Purpose Expression Setting

87 Used for percent-restrained differential protection with high-speed 43 1


unrestrained instantaneous differential protection. Differential (ENABLED)
function is blocked when virtual switch 43 is TRUE.
51N Used for timed ground-overcurrent protection for independent 0 G
ground input circuit (OPT GND CT)
151P Used for timed phase-overcurrent protection for CT input circuit 1 0 1
(CT CKT 1)
151N Used for timed neutral-overcurrent protection for CT input circuit 0 1
1 (CT CKT 1)
151Q Used for timed negative sequence-overcurrent protection for CT 0 1
input circuit 1 (CT CKT 1)
251P Used for timed phase-overcurrent protection for CT input circuit 2 0 2
(CT CKT 2)
251N Used for timed neutral-overcurrent protection for CT input circuit 0 2
2 (CT CKT 2)
251Q Used for timed negative-sequence overcurrent protection for CT 0 2
input circuit 2 (CT CKT 2)
50TP Used as fault detector for Breaker 2 external BFI (IN7) 0 2
supervision. (CT CKT 2)
50TN Used as fault detector for Breaker 2 external BFI (IN7) 0 2
supervision. (CT CKT 2)
50TQ Used as fault detector for Breaker 2 external BFI (IN7) 0 2
supervision. (CT CKT 2)
250TP Used for bus backup overcurrent protection, CT circuit 2. 0 2
(CT CKT 2)
250TN Used for bus backup overcurrent protection, CT circuit 2. 0 2
(CT CKT 2)
250TQ Used for bus backup overcurrent protection, CT circuit 2. 0 2
(CT CKT 2)

8-24 Application BE1-CDS


BESTlogic Mode
Function Purpose Expression Setting

BF INI Logic: Used for CT circuit 2 breaker failure protection. VO10 2


Initiated by BFI with fault detector supervision expression. (CT CKT 2)
BLK Logic: Block breaker failure protection when relay is in test VO15
mode.
62 INI Logic: Used for breaker failure tripping with no current VO9
supervision. 1
(PU/DO)
BLK Logic: Block breaker failure protection when relay is in test VO15
mode.
GROUP Auto/Manual Logic: Switch to setting group 1 if feeder relay is out /IN5 2
of service as indicated by open contact (IN5). (BINARY)

Table 8-19. TX-W-BU Virtual Switch Logic


Variable State Labels, 7 Char
Switch Purpose Mode Label 16 Closed Open
Characters (1) (0)
43 Used as differential cutoff. The 87 is blocked 2 87-CUTOFF DISABLD NORMAL
when the switch is in the closed state. (ON/OFF)
743 Selects test mode so that reclosing and BF 2 TEST-MODE- TSTMODE NORMAL
are disabled when virtual switch is closed. (ON/OFF) ENABLE
101 Allows breaker to be tripped or closed man- 1 N/A N/A N/A
ually from HMI or ASCII command interface (ENABLED)

Table 8-20. TX-W-BU Output Logic


Variable State Labels, 7 Char.
Output Purpose Description Label 16 Closed (1) Open (0)
Characters
VOA Relay Trouble alarm OUTA contact closes when RELAY- ACTIVE NORMAL
(OUTA) relay trouble alarm occurs TROUBLE
BESTlogic Expression: VOA=0
VO1 Transformer fault trip (86T OUT1 contact closes if a TRIP_86T- TRIP NORMAL
(OUT1) for example) restrained, unrestrained, or OUT1
phase differential is TRUE
BESTlogic Expression: VO1=87RT+87UT+51NT+151PT+151NT+151QT
VO2 Transformer fault trip (86B Trip bus breaker via lockout TRIP-86B- TRUE FALSE
(OUT2) for example) for bus faults (250T w/ 18-20 OUT2
cycles delay).
BESTlogic Expression: VO2=250TPT+250TNT+250TQT
VO3 Breaker 2 breaker failure TRUE when BFT or 62 times TRIP-86F- TRUE FALSE
(OUT3) trip. (86F for example) out OUT3
BESTlogic Expression: VO3=BFT+62
VO4 Breaker 2 trip Trip if 87R or 87U trip output TRIP-BKR2- TRIP NORMAL
(OUT4) of the phase diff. protection OUT4
function is TRUE. Or for 251
bus backup over-current trip.
Or for control switch trip. Or
when BF is initiated.
BESTlogic Expression: VO4=87RT+87UT+251PT+251NT+251QT+VO9+BFPU+101T

BE1-CDS Application 8-25


Variable State Labels, 7 Char.
Output Purpose Description Label 16 Closed (1) Open (0)
Characters
VO5 Breaker 2 close Close breaker if virtual control CLOSE- CLOSE NORMAL
(OUT5) switch is TRUE and 86T or BKR2-OUT5
86B LO is not tripped.
BESTlogic Expression: VO5=101C*/IN3*/IN4
VO6 Signal relay on bus source Feeder relay is out of service FDR- BACKUP NORMAL
(OUT6) that is using BUS logic that as indicated by contact open BACKUP-
a feeder relay is out of from the feeder relays. MODE
service.
BESTlogic Expression: VO6=/IN5
VO9 52b supervised breaker Initiate BF timing (62 timer) BFI-62 INI NORMAL
failure initiate expression when 87R or 87U trip is
TRUE or when ex-ternal BFI
contact (IN6) is sensed. Stop
BF timing when breaker
opens (52a status contact).
Prevent initiate when in test
mode (VO15).
BESTlogic Expression: VO9=87RT*IN2*/VO15+87UT*IN2*/VO15+IN6*IN2*/VO15
VO10 Current supervised breaker Initiate BF timing when BFI-BF INI NORMAL
failure initiate expression protective trip expression is
TRUE. Or when external
initiate contact (IN7) is
sensed and any of the fault
detectors is picked up.
BESTlogic Expression: VO10= VO11+IN7*150TPPU+IN7*150TNPU+IN7*150TQPU
VO11 Protective trip expression TRUE when any 87, 250T, PROTECTIVE TRIP NORMAL
51, 151 or 251 element has -TRIP
timed out.
BESTlogic Expression: VO11=
87RT+87UT+250TPT+250TNT+250TQT+51NT+151PT+151NT+151QT+251PT+ 251NT+251QT
VO12 Protective pickup TRUE when any 87, 250T, PROT- PU NORMAL
expression 51, 151, or 251 element is PICKED-UP
picked up.
BESTlogic Expression: VO12=87RPU+87UT+250TPPU+250TNPU+250TQPU+51NPU+151PPU+
151NPU+151QPU+251PPU+ 251NPU+251QPU
(87UT is included to trigger the fault recorder because there is no unrestrained pickup output)
VO13 Alarm to indicate that the TRUE if virtual switch 43 is in 87-BLOCKED ACTIVE NORMAL
(ALARM differential cutoff switch is the closed position
POINT in the block operation
21) position
BESTlogic Expression: VO13=43
VO15 Alarm bit #23 indication that TRUE if IN8 is de-energized IN8-ALARM ACTIVE NORMAL
(ALARM the relay is in test mode or if virtual switch 743 is
POINT and that breaker failure is closed
23) disabled
BESTlogic Expression: VO15=/IN8+743

8-26 Application BE1-CDS


ONE LINE DIAGRAM

TX-W-BU

BE1-851 BE1-
BUS CDS220

(See Note 2)
52
BUS
MAIN

(See Note 1) BE1-CDS220 TX-W-BU RELAY CIRCUIT


+
BE1-851 BE1-851 BE1-851
83 83 83 TS
F1 F2 Fn BUS
F1 F2 Fn
C26 C32
IN5 TX-W-BU IN8 TX-W-BU
RELAY FEEDER RELAY TEST
BACKUP MODE MODE
NOTES: C25 C31

1. BE1-951 relays using FDR-W-IL logic could be substituted for BE1-851 relays. -
2. BE1-951 relays using BUS logic could be substituted for BE1-851 relays.

FEEDER BREAKER CIRCUIT BE1-851 OR BE1-951 FEEDER RELAY CIRCUIT


+ +
94
C1 BUS TS
OUT1 Fn
Fn
C2 83
Fn
B7 C5
52A OUT3
Fn IN4 FEEDER Fn
RELAY C6
52TC P0004-05.vsd TEST MODE
08-14-00
Fn 83 IN2 94BUS
B8
Fn BUS Fn
- -

BE1-851 OR BE1-951 BUS RELAY CIRCUIT


+
C7 C7 C7 C14 C7 C5
C7
OUT4 OUT4 OUT4 OUT6 TS OUT5 OUT4 OUT2
F1 F2 Fn TX-W-BU BUS BUS BUS TX-W-BU
C8 C8 C8 C8 C6
C15 C8

B3 B5 B7
TRIP TRIP TRIP 86B
IN2 BUS RELAY IN3 BUS RELAY
IN4 BUS RELAY F1 F2 . ..Fn OPTIONAL
INSTANTANEOUS FEEDER BACKUP
TEST MODE
BLOCK MODE 94 86B
B4 B6 B8 BUS TC

Figure 8-7. Device Interconnection For Integrated Protection System Using


BE1-CDS220 For Transformer Protection And BE1-851 or BE1-951 For Bus And Feeder Protection

BE1-CDS Application 8-27


D2850-01.vsd
04-23-99
BE1-CDS220
CT Input 1
Out1
86T

52-1 151P 151N 151Q

CT Input 1

51N 87
CT Input G
(Optional)
f
of

CT Input 2
ut
C

43 251P 251N 251Q

Out4

ip Out2
Tr 86B
T

52-2 101 250TP 250TN 250TQ


C
lo
se
C
Out5

50TP 50TN 50TQ

Out3 86F
52-2

BF 62

CT Input 2

Figure 8-8. Typical One-Line Diagram For TX-W-BU

8-28 Application BE1-CDS


87RT 51NT
51N VOA
BLK Relay Output
87RPU ModeG 51NPU OUTA
Trouble Logic
43 43 DIFF Cutoff 87 87UT 6
BLK
Mode2 Mode1 VO1
2NDHAR 151PT
VO13 86T Trip
BLK 151P Output
DIFF Cutoff 5THHAR 151PPU OUT1
Mode1 Logic
Alarm Point 21
VO2
151NT 86B Trip
3 Output
BLK 151N OUT2
Logic
Mode1 151NPU
VO3
250TPT 52-2
BLK 250TP 86F Trip
Mode2 250TPPU 151QT 2 Output
OUT3
BLK 151Q Logic
Mode1 151QPU 101T
IN1 Breaker1 Status 52-2 VO4
OPTO 250TNT Trip 52-2 Trip
BLK 250TN 8 Output
Mode2 250TNPU OUT4
IN2 Breaker2 Status 251PT Logic
OPTO 251P 101C
BLK
Mode2 251PPU 52-2
IN3 86T Status 101 Close
OPTO 250TQT
250TQ Mode1
BLK VO5
Mode2 250TQPU 251NT 101SC 52-2
IN4 86B Status
OPTO BLK 251N Close Output
Mode2 251NPU OUT5
Logic
IN5 Feeders OK
OPTO 4
251QT 5 Feeder
IN6 BFI w/52B SUPV 2
OPTO BLK 251Q Backup
Mode2 251QPU VO11
2 Mode
7 PROT Output OUT6
OPTO IN7 BFI w/50 SUPV TRIP
12 Logic
IN8 Test VO15 7
OPTO Mode Disable Test Mode 12 VO12
Alarm Point 23
PROT PU
50TPT
BLK 50TP VO10
Test Mode Mode2 50TPPU BFI-BF
243 4 INI BFT
743 Enable
Mode2 BF
BLK Mode2 BFPU
50TNT
BLK 50TN
Mode2 50TNPU
VO9
SG0 3 BFI-62 INI 62
D0 ACTIVE
SG1 62
D1 SETTING 50TQT BLK Mode1
D2 GROUP SG2 BLK 50TQ
D3 CONTROL Mode2 50TQPU
SG3
AUTO Mode2

Note: For clarity, multiple variables


D2850-02.vsd
going to the same OR Gate are shown 09-28-99
by a single line into the OR Gate.

Figure 8-9. Typical Logic Diagram For TX-W-BU

BUS WITH BACKUP SCHEME


The BUS With Backup (BUS-W-BU) scheme was designed to provide low impedance, high-speed phase
and ground bus fault protection for distribution buses. This scheme also includes a high-speed bus-
interlocking scheme that provides a second level of bus protection and Feeder Relay Out of Service
backup protection. Figure 8-10 shows the interconnection of BE1-851 or BE1-951 relays for backup and
feeder protection and the BE1-CDS220 (BUS-W-BU). Figure 8-11 shows the interconnection of a BE1-
CDS220 (TX-W-BU) for backup protection, a BE1-851 or BE1-951 for feeder protection, and the BE1-
CDS220 for bus protection. When interconnected with feeder relays using preprogrammed feeder logic
(FDR-W-IL), the BUS-W-BU scheme provides complete backup, except for reclosing, for the feeder relays
if relay failure occurs or when they are out of service for testing or maintenance. Virtual control switch
logic is used for local or remote (SCADA) control and can be used to replace the equivalent panel control
switches.
The control switch elements are referred to as virtual because they have no physical form, they exist only
in logic form, and they can only be operated via the ASCII command interface or the front panel. The
virtual 101 switch is used to trip and close the bus main breaker, virtual control switch 043 is used to turn
off the 87 protection element, and 743 is used to select test mode enable. The user may choose to
eliminate the use of external switches, as the virtual switches are fully functional equivalents of their
physical counterparts.
Figure 8-12 is a one-line drawing and Figure 8-13 is a logic drawing that represent the logic settings
shown in Table 8-21. In Table 8-21, the user can see the protection and control elements that are
enabled for the BUS-W-BU application and how the elements are logically wired together (equations). If
the user should decide to build on this scheme, all elements required for a more detailed application are
available through programming. For programming details, refer to Section 7, BESTlogic Programmable
Logic.
BE1-CDS Application 8-29
ONE LINE DIAGRAM

BACKUP

BE1-851

(See Note 2)
52
BUS
MAIN
BUS-W-BU

BE1-
CDS220

(See Note 1)

BE1-851 OR BE1-951 BACKUP RELAY CIRCUIT


BE1-851 BE1-851 BE1-851 +

83 83 83 TS
F1 F2 Fn F1 F2 Fn BUS

B3 B7
IN2 BACKUP IN4 BACKUP
RELAY FEEDER RELAY TEST
BACKUP MODE MODE
B4 B8
NOTES:
1. BE1-951 relays using FDR-W-IL logic could be substituted for BE1-851 relays. -
2. BE1-951 relays using BACKUP logic could be substituted for BE1-851 relays.

BE1-851 OR BE1-951 FEEDER RELAY CIRCUIT


FEEDER BREAKER CIRCUIT
+
+
94 TS
C1 BUS Fn
OUT1
Fn
C2 83
Fn C5
B7
OUT3
52A IN4 FEEDER Fn
Fn RELAY C6
P0004-09.vsd
08-21-00
TEST MODE
52TC 83 IN2 94BUS
Fn B8
Fn BUS Fn
-
-

BE1-CDS BUS-W-BU RELAY CIRCUIT


+
C7 C7 C7 C14 C3 C7
C7
OUT4 OUT4 OUT4 OUT6 TS OUT1 OUT4
OUT3
F1 F2 Fn TX-W-BU BUS BUS-W-BU BACKUP
BUS-W-BU
C8 C8 C8 C15 C4 C8
C8

C26 C30 C32


TRIP TRIP TRIP 86B
IN5 BUS-W-BU IN7 BUS-W-BU
IN8 BUS-W-BU F1 F2 . .. Fn OPTIONAL
INSTANTANEOUS FEEDER BACKUP
TEST MODE
BLOCK MODE 94 86B
C25 C29 C31 BUS TC

Figure 8-10. Device Interconnection For Integrated Protection System Using


BE1-CDS220 For Bus Protection And BE1-851 Or BE1-951 For Feeder And Backup Protection

8-30 Application BE1-CDS


ONE LINE DIAGRAM

BUS-W-BU
TX-W-BU
BE1-
CDS220 BE1-
CDS220

52
BUS
MAIN

(See Note 1)
BE1-CDS220 TX-W-BU RELAY CIRCUIT
+
BE1-851 BE1-851 BE1-851

83 83 83 TS
F1 F2 Fn BUS
F1 F2 Fn
C26 C32
IN5 TX-W-BU IN8 TX-W-BU
RELAY FEEDER RELAY TEST
BACKUP MODE MODE
C25 C31

NOTES: -
1. BE1-951 relays using FDR-W-IC logic could be substituted for BE1-851 relays.

FEEDER BREAKER CIRCUIT BE1-851 OR BE1-951 FEEDER RELAY CIRCUIT


+ +
94
C1 BUS TS
OUT1 Fn
Fn
C2 83
Fn
B7 C5
52A OUT3
Fn IN4 FEEDER Fn
RELAY C6
52TC TEST MODE
Fn 83 IN2 94BUS
B8
Fn BUS Fn
-
-

BE1-CDS BUS-W-BU RELAY CIRCUIT


+
C7 C7 C7 C14 C3 C5
C7
OUT4 OUT4 OUT4 OUT6 TS OUT1 OUT2
OUT3
F1 F2 Fn TX-W-BU BUS BUS-W-BU BUS-W-BU TX-W-BU
C8 C8 C8 C15 C4 C6
C8

C26 C30 C32


TRIP TRIP TRIP 86B
IN5 BUS-W-BU IN7 BUS-W-BU
IN8 BUS-W-BU F1 F2 . .. Fn OPTIONAL
INSTANTANEOUS FEEDER BACKUP
TEST MODE
BLOCK MODE 94 86B
C25 C29 C31 BUS TC

P0004-07.vsd
08-14-00

Figure 8-11. Device Interconnection For Integrated Protection System Using


BE1-CDS220 For Transformer And Bus Protection And BE1-851 Or BE1-951 For Feeder Protection

BE1-CDS Application 8-31


Table 8-21. BUS-W-BU Logic Settings and Equations
SL-N=BUS-W-BU
SL-87=1,43
SL-87ND=0,0
SL-50TP=1,IN5; SL-50TN=1,IN5; SL-50TQ=1,IN5
SL-150TP=1,0; SL-150TN=1,0; SL-150TQ=1,0
SL-250TP=0,0; SL-250TN=0,0; SL-250TQ=0,0
SL-51P=1,0; SL-51N=1,0; SL-51Q=1,0
SL-151P=1,0; SL-151N=1,0; SL-151Q=1,0
SL-251P=0,0; SL-251N=0,0; SL-251Q=0,0
SL-62=0,0,0
SL-162=0,0,0
SL-BF=0,0,0
SL-GROUP=2,IN7,0,0,0,0
SL-43=2
SL-143=0
SL-243=0
SL-343=0
SL-443=0
SL-543=0
SL-643=0
SL-743=2
SL-101=1
SL-CKTMON=0,0,0
SL-VOA=0
SL-VO1=87RT+VO8*/VO14
SL-VO2=0
SL-VO3=VO9*VO14
SL-VO4=87RT+VO9*/VO14+VO10+101T
SL-VO5=/IN3*/IN4*101C
SL-VO6=VO7*/VO15
SL-VO7=87RT+VO9*/VO14+VO10
SL-VO8=50TPT+50TNT+50TQT
SL-VO9=50TPT+50TNT+50TQT+51PT+51NT+51QT
SL-VO10=150TPT+150TNT+150TQT+151PT+151NT+151QT
SL-VO11=50TPT+150TPT+50TNT+150TNT+50TQT+150TQT+51PT+151PT+51NT+151NT+51QT+
151QT+87RT
SL-VO12=50TPPU+150TPPU+50TNPU+150TNPU+50TQPU+150TQPU+51PPU+151PPU+51NPU+
151NPU+51QPU+151QPU+87RPU
SL-VO13=43
SL-VO14=SG1
SL-VO15=/IN8+743

8-32 Application BE1-CDS


SOURCE BE1-CDS220
CT Input 1

BE1-CDS
Out4

ip
Tr
52
BUS 151P 151N 151Q
MAIN C
lo
se

C T
D2850-03.vsd
04-29-99
101
150TP 150TN 150TQ

Feeder Relay
NOTE 1: Out of Service
If a Feeder relay is (See Note 1) IN7
51P 51N 51Q
out of service, the 50T
and 51 Elements are
rerouted from OUT1 Feeder Relay Out3
IN5 94
and OUT4 to OUT3 to Picked-Up

Application
provide feeder Block
protection. 50TP 50TN 50TQ

PU

PU
PU
851 851 851 CT Input 1
Fa Fa Fa
i l il il
(See (See (See Out1
Note 1) Note 1) Note 1) 86B

Figure 8-12. Typical One-Line Diagram For BUS-W-BU


52 Trip 52 Trip 52 Trip 87
F1 F2 F3
ff

CT Input 2
to
Cu

43

CT Input 2
FEEDER FEEDER FEEDER
1 2 3

8-33
87RT 51PT
51P VOA
BLK

8-34
87RPU 51PPU Relay Output
Mode1 OUTA
Trouble Logic
43 43 DIFF Cutoff 87 87UT
BLK
Mode2 Mode1 VO1
2NDHAR 51NT
VO13 86B Trip
BLK 51N Output
DIFF Cutoff 5THHAR OUT1
Mode1 51NPU Logic
Alarm Point 21 VO14
Feeder
VO2
Backup Alarm
51QT Not Used
IN7 SG0 Point 22 Output
D0 ACTIVE BLK 51Q OUT2
SG1 Logic
D1 SETTING Mode1 51QPU VO3
D2 GROUP SG2 Feeder
D3 CONTROL Breaker
SG3
AUTO Mode2 VO8 Trip Output
OUT3
3 50T Trip Logic
VO9
6 50T + 51 Trip VO4
50TPT Bus Main
BLK 150TPT 101T Breaker
50TP
Mode1 50TPPU BLK 150TP 52-2 Trip Trip Output
Mode1 150TPPU OUT4
IN1 Breaker1 Status Logic
OPTO 101C VO5
52-2 Bus Main
BLK 50TNT
IN2 Not Used 150TNT 101 Close Breaker
OPTO 50TN
Mode1 50TNPU BLK 150TN Mode1 Close Output
Mode1 150TNPU OUT5
IN3 86T Status 101SC Logic
OPTO
50TQT
IN4 86B Status BLK 150TQT
OPTO 50TQ 6
50TQPU 150TQ VO6
Mode1 BLK VO10
IN5 Feeder Mode1 150TQPU VO11 BFI
150T + 151

Application
Relay Picked Up PROT Output OUT6
OPTO TRIP Trip
13 Logic

OPTO IN6 Not Used


13 VO12

OPTO IN7 Feeder Relay Out Of Service PROT PU


151PT
IN8 Test BLK 151P
VO15 151PPU
Mode Disable Mode1
OPTO Test Mode
Alarm Point 23
VO7
151NT BFI

Figure 8-13. Typical Logic Diagram For BUS-W-BU


Test Mode BLK 151N
243 Mode1 151NPU
743 Enable
Mode2

151QT
BLK 151Q
Mode1 151QPU

Note: For clarity, multiple variables D2850-04.vsd


going to the same OR Gate are shown 09-30-99

by a single line into the OR Gate.

BE1-CDS
Protection Elements
Referring to Figure 8-12, the 87, 150/151, 50/51 protection elements are connected to CT input 1, and the
Feeder Side of the 87 protection element is connected to input 2. The 87, 150/151, and 50/51 protection
elements are logic enabled to provide a trip by the settings shown in Table 8-21. Protection elements set
to 0 are setting disabled and will not provide a trip output even if logic enabled.
As shown in Figure 8-12, the BUS-W-BU scheme is typically applied with a BE1-851 on the feeder circuits
and a BE1-CDS on the transformer (not shown) supplying the bus. The transformer BE1-CDS provides
an independent backup for bus faults with a coordination interval of 18 to 20 cycles. This combination
provides independent, overlapping backup protection in the event of a common mode failure (refer to the
discussion in Details Of Preprogrammed Logic Schemes).
Typically, the 87 protection element provides high-speed percent restrained, phase and ground protection
for faults inside the differential zone. For the BUS-W-BU application shown in Figure 8-12, the percent-
restrained differential protection function is the only function of the 87 protection element required. Set the
nd th
pickup of the 2 , 5 , and 87U functions to 0 (setting disabled). The 87U function has a setting only when
nd th
the 2 and 5 harmonic restraint functions are set for transformers (refer to the discussion in Overview Of
Preprogrammed Logic Schemes).
Typically, the 150 and 151 protection elements are coordinated with the bus and feeder protection to
provide Phase, Neutral, and Negative Sequence instantaneous and timed backup protection for bus and
feeder faults.
Typically, the 51 protection element is coordinated with the low-side feeder protection to provide Phase,
Neutral, and Negative Sequence timed backup protection for feeder faults should feeder protection be out
of service. When a Feeder Relay Out of Service signal is detected through IN7 of the BE1-CDS
BUS-W-BU scheme, the relay switches from normal mode to feeder backup mode. The 251 protection
element is reset from setting group 0 to setting group 1 to provide time overcurrent feeder replacement
protection.
Typically, the 50T protection element is set to provide high-speed bus fault protection (2-4 cycles
coordination interval) when used with 851 feeder protection inputs as part of a bus interlocking scheme
(IN5 of the Bus BE1-CDS). For normal mode, the 250T protection element should have a pickup setting
greater than the highest feeder instantaneous element to ensure that it will not pickup before any feeder
relay. When a Feeder Relay Out of Service signal is detected through IN7 of the BE1-CDS BUS-W-BU,
the relay switches from normal mode to feeder backup mode. The 250T protection element is reset from
setting group 0 to setting group 1 to provide instantaneous overcurrent feeder replacement protection.

Integration Of Protection, Control, And I/O Elements


The logic settings in Table 8-21 also include the logic equations that establish the control connections or
logic wiring between elements of the BUS-W-BU scheme. For example, the two underlined equations in
the settings of Table 8-21 provide the electrical connection between the 87 element (trip enabled by the
settings) and trip outputs 1 and 4. Referring to Figures 8-12 and 8-13, during the normal mode, the 87,
50, and 51 protection elements (each trip enabled by the settings) trip through outputs 1 and 4. The 150
and 151 protection elements and the 101 virtual switch element (also trip enabled by the settings) trip
through output 4. During the feeder backup mode, the 50T and 51 protection elements are rerouted from
output 1 and output 4, to output 3 to provide feeder protection. Protection elements set at 0 are setting
disabled and will not provide a trip output even if logic enabled.
As shown in Figure 8-12, IN7 of the BUS-W-BU signals the scheme that a feeder relay is out of service.
This input instructs the BE1-CDS relay to switch from the normal mode of interlocked bus protection to the
feeder backup mode.
As shown in Figure 8-12, IN5 of the BUS-W-BU scheme is hard wired to the feeder protection relays
(BE1-851). This signal path provides the intelligence that allows the BUS-W-BU to determine if a fault is
on the bus or on a feeder circuit. When any feeder overcurrent elements are picked up and timing, a
signal at IN5 of the BE1-CDS bus blocks the 50T protection elements. The pickup of the 50T protection
element is delayed 2 to 4 cycles to allow time for the feeder protection to detect, pickup, and start timing.
If the fault is not on a feeder, the 50T protection element of the BE1-CDS bus is not blocked and trips in 2
to 4 cycles through outputs 1 and 4 as previously discussed. The overlapping 250T protection element
BE1-CDS Application 8-35
from the transformer BE1-CDS (not shown in Figure 8-12) does not get blocked when the feeder relays
are picked up. Therefore, the 250T protection element must be set with a time delay long enough to allow
the feeder breaker to interrupt the fault.
Virtual control switch elements enabled for use in this scheme are 101, 043, and 743. The 101-control
switch trips the low-side breaker through output 4 and closes the low-side breaker through output 5.
Control switch 043 is used to turn the 87 function on or off and 743 us used to enable Test Mode.

Test Mode
When virtual control switch 743 is enabled, breaker failure initiate through output 6 is defeated.

CAUTION
Test Mode Enable does not defeat the trip outputs of the relay. External trip test blades
must be opened or the BUS-W-BU logic scheme must be modified to suit the user’s test
mode requirements. One option is to trip the breakers through an 86 device only.
Typically, 86 devices are installed with test blades in the breaker trip circuit so that the
protection scheme can be safely operational checked while the primary equipment is in
service. Another option is to inhibit all trip outputs when test mode is enabled; however,
external devices such as auxiliary relays and 86 devices would no longer be included in
the operational test.

Setting Group
For normal operation, setting group 0 is active for the BUS-W-BU scheme. IN7 to the BE1-CDS identifies
when a feeder relay (851) is out of service. At the same time, IN5 of the transformer BE1-CDS scheme
gets the same signal. Both relays then switch to setting group 1. Setting group selection mode 2, binary
coded selection, is used to recognize the group setting state. When input D0 to the setting group
selection element is a one, it is interpreted as a binary 1 causing the logic to switch to group 1.
When the bus BE1-CDS is in setting group 1, it is operating in feeder backup mode. This expression is
programmed to virtual output 14 which drives alarm bit #22 in the programmable alarm mask. It can be
masked to drive an alarm LED and alarm display to indicate when the relay is in feeder backup mode and
to trip a feeder breaker instead of the bus breaker.

Alarms
Three logic variables drive the front panel LEDs: Relay Trouble (ALMREL), Major Alarm (ALMMAJ), and
Minor Alarm (ALMMIN). A fourth logic variable, Logic Alarm (ALMLGC), has no associated front panel
LED. When the relay self-test detects a problem in the relay (ALMREL) as programmed for the BUS-W-
BU scheme, the Relay Trouble LED lights, output A operates, and all outputs are disabled. When a Major
Alarm is detected (ALMMAJ), the associated LED lights, but in this scheme, no output relay is
programmed to operate. When a Minor Alarm (ALMMIN) is detected, the associated LED lights, but in this
scheme, no output relay is programmed to operate.

Note
Tables 8-22 through 8-25 provide detailed logic definitions for the inputs, outputs,
protection, and control elements. Only those inputs, logic blocks, virtual switches, and
outputs in use for the BUS-W-BU preprogrammed logic are described in the following
Tables.

8-36 Application BE1-CDS


Table 8-22. BUS-W-BU Contact Input Logic
Variable State Labels, 7 Char
Input Purpose Label 16 Closed (1) Open (0)
Characters
IN1 Optional input. Used for CT input circuit 1 breaker status BREAKER-1 CLOSED OPEN
indication in SER reports. TRUE when breaker closed.
IN3 Used for 86 status indication in SER reports. TRUE when 86T- TRIPPED NORMAL
Transformer 86 tripped. Also blocks virtual breaker close TRIPPED
switch close until 86 is reset .
IN4 Optional input. Used for 86B status indication and locks out 86B- TRIPPED NORMAL
the low-side breaker when TRUE. TRUE when 86B is TRIPPED
tripped.
IN5 Block instantaneous when feeder relay is picked up. Feeder FDR-RLY- PICKDUP NORMAL
relays such as BE1-851 or BE1-951 using one of the PICKEDUP
preprogrammed schemes with interlock logic.
IN7 Signal from relay on bus source that is using BACKUP logic BACKUP- BACKUP NORMAL
that a feeder relay is out of service. BE1-851, BE1-951, or FDR-RELAY
BE1-CDS using preprogrammed logic scheme BACKUP.
IN8 Puts the relay in test mode so that breaker failure is disabled TEST- NORMAL TSTMOD
when input 8 is de-energized. MODE- E
DISABL

Table 8-23. BUS-W-BU Function Block Logic


BESTlogic Mode
Function Purpose Expression Setting
87 Used for percent-restrained differential protection with high-speed 43 1
unrestrained instantaneous differential protection. Differential (ENABLED)
function is blocked when virtual switch 43 is TRUE.
51P Applied to bus main (CT 1). Normally for bus time OC protection 0 1
coordinated with feeder relay time OC. When in feeder relay (CT CKT 1)
backup mode, provides primary time OC protection for feeder.
SG1 settings must coordinate with other feeder 51 elements.
51N Applied to bus main (CT 1). Normally for bus time OC protection 0 1
coordinated with feeder relay time OC. When in feeder relay (CT CKT 1)
backup mode, provides primary time OC protection for feeder.
SG1 settings must coordinate with other feeder 51 elements.
51Q Applied to bus main (CT 1). Normally for bus time OC protection 0 1
coordinated with feeder relay time OC. When in feeder relay (CT CKT 1)
backup mode, provides primary time OC protection for feeder.
SG1 settings must coordinate with other feeder 51 elements.
151P Applied to bus main (CT 1). Used for backup bus time OC trip. 0 1
Provides primary time OC protection when 51 elements are used (CT CKT 1)
for feeder relay backup.
151N Applied to bus main (CT 1). Used for backup bus time OC trip. 0 1
Provides primary time OC protection when 51 elements are used (CT CKT 1)
for feeder relay backup.
151Q Applied to bus main (CT 1). Used for backup bus time OC trip. 0 1
Provides primary time OC protection when 51 elements are used (CT CKT 1)
for feeder relay backup.
50TP Applied to bus main (CT 1). Normally for fast bus OC protection IN5 1
(2-4 cycle delay) as backup to 87. When in feeder relay backup (CT CKT 1)
mode, provides near instantaneous for feeder. Block when feeder
relay is picked up indicating that the fault is on a feeder.

BE1-CDS Application 8-37


Table 8-23. BUS-W-BU Function Block Logic - Continued
BESTlogic Mode
Function Purpose Expression Setting
50TN Applied to bus main (CT 1). Normally for fast bus OC protection (2- IN5 1
4 cycle delay) as backup to 87. When in feeder relay backup (CT CKT 1)
mode, provides near instantaneous for feeder. Block when feeder
relay is picked up indicating that the fault is on a feeder.
50TQ Applied to bus main (CT 1). Normally for fast bus OC protection (2- IN5 1
4 cycle delay) as backup to 87. When in feeder relay backup (CT CKT 1)
mode, provides near instantaneous for feeder. Block when feeder
relay is picked up indicating that the fault is on a feeder.
150TP Applied to bus main (CT 1). Used for backup bus OC trip. 18-20 0 1
cycles delay (no feeder picked up interlock). Provides primary OC (CT CKT 1)
protection when 50T elements are used for feeder relay backup.
150TN Applied to bus main (CT 1). Used for backup bus OC trip. 18-20 0 1
cycles delay (no feeder picked up interlock). Provides primary OC (CT CKT 1)
protection when 50T elements are used for feeder relay backup.
150TQ Applied to bus main (CT 1). Used for backup bus OC trip. 18-20 0 1
cycles delay (no feeder picked up interlock). Provides primary OC (CT CKT 1)
protection when 50T elements are used for feeder relay backup.
GROUP Auto/Manual Logic: Switch to setting group 1 if feeder relay is out of IN7 2
service as indicated by closed contact from relay with BACKUP (BINARY)
logic such as BE1-851, BE1-951, or BE1-CDS.

Table 8-24. BUS-W-BU Virtual Switch Logic


Variable State Labels, 7 Char
Switch Purpose Mode Label 16 Closed Open
Characters (1) (0)
43 Used as differential cutoff. The 87 is blocked 2 87-CUTOFF DISABLD NORMAL
when the switch is in the closed state. (ON/OFF)
743 Selects test mode so that reclosing and BF 2 TEST- TSTMODE NORMAL
are disabled when virtual switch is closed. (ON/OFF) MODE-
ENABLE
101 Allows breaker to be tripped or closed man- 1 N/A N/A N/A
ually from HMI or ASCII command interface (ENABLED)

Table 8-25. BUS-W-BU Output Logic


Variable State Labels, 7 Char.
Output Purpose Description Label 16 Closed (1) Open (0)
Characters
VOA Relay Trouble alarm OUTA contact closes when RELAY- ACTIVE NORMAL
(OUTA) relay trouble alarm occurs TROUBLE
BESTlogic Expression: VOA=0
VO1 Bus fault trip (86B for Trip if bus fault by restrained TRIP_86B- TRIP NORMAL
(OUT1) example) differ-ential trip or for high OUT1
speed bus OC trip (50T) and
not in feeder backup mode
(VO14).
BESTlogic Expression: VO1=87RT+VO8*/VO14

8-38 Application BE1-CDS


Table 8-25. BUS-W-BU Output Logic - Continued
Variable State Labels, 7 Char.
Output Purpose Description Label 16 Closed (1) Open (0)
Characters
VO2 Transformer fault trip (86B Trip bus breaker via lockout TRIP-86B- TRUE FALSE
(OUT2) for example) for bus faults (250T w/ 18-20 OUT2
cycles delay).
BESTlogic Expression: VO2=250TPT+250TNT+250TQT
VO3 Feeder breaker trip Trip feeder breaker via FEEDER- TRIP NORMAL
(OUT3) auxiliary re-lay (94) for 50/51 BKR-TRIP
(VO9) trip when in feeder relay
backup mode (VO14).
BESTlogic Expression: VO3= VO9*VO14
VO4 Breaker 1 trip Trip for bus diff, 87 is TRUE. TRIP-BKR1- TRIP NORMAL
(OUT4) Or, high speed bus OC with OUT4
interlock, 50T, or bus time
OC trip, 51 is TRUE and not
in feeder backup mode
(VO14). Or, for 150T & 151
bus backup overcurrent trip.
Or, for control switch trip.
BESTlogic Expression: VO4=87RT+VO9*/VO14+VO10+101T
VO5 Breaker 1 close Close breaker 1 (main) if CLOSE- CLOSE NORMAL
(OUT5) virtual control switch is TRUE BKR1-
and 86T or 86B LO is not OUT5
tripped.
BESTlogic Expression: VO5=101C*/IN3*/IN4
VO6 Breaker Failure Initiate Initiate breaker failure if BFI BFI-OUT6 INI NORMAL
(OUT6) output. Initiate breaker expression is TRUE (VO7)
failure protection in relay and not in test mode.
using backup logic.
BESTlogic Expression: VO6= VO7*/VO15
VO7 Breaker failure initiate Initiate breaker failure for all BFI INI NORMAL
expression. bus breaker protective
tripping elements. 87RT,
50/51 (when not in feeder
backup mode), or 150/151.
(101T is excluded).
BESTlogic Expression: VO9=87RT+VO9*/VO14+VO10
VO8 Intermediate logic TRUE if any 50T with feeder 50T- TRIP NORMAL
expression for 50T Trip. pickup interlock is TRUE. INTERLKD-
Used for high speed bus Elements have 2-4 cycle OC
OC trip in normal mode or delay due to interlock with
feeder breaker inst. trip in feeder relay pickups.
feeder backup mode.
BESTlogic Expression: VO10=50TPT+50TNT+50TQT

BE1-CDS Application 8-39


Table 8-25. BUS-W-BU Output Logic - Continued
Variable State Labels, 7 Char.
Output Purpose Description Label 16 Closed Open
Characters (1) (0)
VO9 Intermediate logic TRUE for any primary OC trip 50T-51- TRUE FALSE
expression for 50T and 51 (50T or 51). TRIP
Trip. Used for bus OC trip
in normal mode or for
feeder relay backup trip in
feeder backup mode.
BESTlogic Expression: VO9=50TPT+50TNT+50TQT+51PT+51NT+51QT
VO10 Intermediate logic TRUE for any backup 150T-151- TRUE FALSE
expression for 150T Trip. overcurrent trip (150T or TRIP
Used for backup bus OC 151).
trip.
BESTlogic Expression: VO10=150TPT+150TNT+150TQT+151PT+151NT+151QT
VO11 Protective trip expression TRUE when any 87, 250T, PROTECTI TRIP NORMAL
51, 151 or 251 element has VE-TRIP
timed out.
BESTlogic Expression: VO11=87RT+50TPT+50TNT+50TQT+51PT+51NT+51QT+150TPT+150TNT+
150TQT+151PT+151NT+151QT
VO12 Protective pickup None PROT- PU NORMAL
expression PICKED-UP
BESTlogic Expression: VO12=87RPU+50TPPU+50TNPU+50TQPU+51PPU+51NPU+51QPU+
150TPPU+150TNPU+150TQPU+151PPU+151NPU+151QPU
VO13 Alarm to indicate that the TRUE if virtual switch 43 is in 87- ACTIVE NORMAL
(ALARM differential cutoff switch is the closed position BLOCKED
POINT in the block operation
21) position
BESTlogic Expression: VO13=43
VO14 Alarm that relay is in TRUE if in setting group 1. FDR-BU- BACKUP NORMAL
ALARM feeder backup mode. ENABLED
POINT
22
BESTlogic Expression: VO15=SG1
VO15 Alarm bit #23 indication TRUE if IN8 is de-energized TEST_ ACTIVE NORMAL
(ALARM that the relay is in test or if virtual switch 743 is MODE
POINT mode and that breaker closed
23) failure is disabled
BESTlogic Expression: VO15=/IN8+743

MOTOR PROTECTION LOGIC


The Motor Protection (MOTOR) scheme provides high-speed differential and multiple layers of
instantaneous and time overcurrent protection for large motors. This scheme protects against stator
phase and ground faults, locked rotor, jam, thermal overload, and unbalanced current. Basic frequent
starting protection is also provided. Virtual control switch logic is used for local or remote control and can
be used to replace the equivalent panel control switches.

8-40 Application BE1-CDS


The control switch elements are referred to as virtual because they have no physical form, they exist only
in logic form, and they can only be operated via the ASCII command interface or the front panel. When
virtual control switch 143 is on or enabled, motor starting is determined by speed switch. When off or
disabled, starting is determined by current detector set at 85% of locked rotor current. The virtual control
switch 243 is used to customize the protection for high or low starting inertia applications. When high is
selected, 150TP is blocked, and 151P is enabled for locked rotor protection. The user may choose to
eliminate the use of external switches, as the virtual switches are fully functional equivalents of their
physical counterparts.
Figure 8-14 is a one-line drawing and Figure 8-15 is a logic drawing that represent the settings shown in
Table 8-26. In Table 8-26, the user can see the protection and control elements that are enabled for the
MOTOR application and how the elements are logically wired together (equations). If the user should
decide to build on this scheme, all elements required for a more detailed application are available through
programming. For programming details, refer to Section 7, BESTlogic Programmable Logic.
Table 8-26. Motor Logic Settings And Equations
SL-N=MOTOR
SL-87=1,0
SL-87ND=0,0
SL-50TP=1,0; SL-50TN=1,0; SL-50TQ=1,0
SL-150TP=1,250TPT+243; SL-150TN=0,0; SL-150TQ=0,0
SL-250TP=1,0; SL-250TN=0,0; SL-250TQ=0,0
SL-51P=1,0; SL-51N=0,0; SL-51Q=1,0
SL-151P=1,/VO7+/243;SL-151N=0,0; SL-151Q=0,0
SL-251P=1,VO8; SL-251N=0,0; SL-251Q=0,0
SL-62=0,0,0
SL-162=0,0,0
SL-BF=0,0,0
SL-GROUP=0,0,0,0,0,0
SL-43=0
SL-143=2
SL-243=2
SL-343=0
SL-443=0
SL-543=0
SL-643=0
SL-743=0
SL-101=0
SL-CKTMON=0,0,0
SL-VOA=0
SL-VO1=VO11
SL-VO2=0
SL-VO3=0
SL-VO4=VO14
SL-VO5=VO15
SL-VO6=0
SL-VO7=IN2*250TPPU*143+50TPPU*/143
SL-VO8=/250TPT*250TPPU
SL-VO9=VO13+IN3
SL-VO10=0
SL-VO11=150TPT+50TNT+50TQT+51PT+151PT+251PT+51QT+87RT+VO13
SL-VO12=150TPPU+50TNPU+50TQPU+51PPU+151PPU+251PPU+51QPU+87RPU
SL-VO13=VO9*/ARSTKEY
SL-VO14=250TPT*51PPU
SL-VO15=51QPU

BE1-CDS Application 8-41


SOURCE BE1-CDS220
CT Input 1 Out1

ip 50TQ 51Q 50TN


Tr
52 Phase Ground
Unbalance
Loss Fault

Speed
Switch 51P 251P
M

Overload Jam

Locked
150TP 151P Rotor
Speed
Switch
Selector

243
143
IN2 Low/High
Inertia Selector
50TP
Start Detect
High Inertia

Start/Running
Detect
250TP

CT Input 1

87 DIFF

CT Input 2 CT Input 2
D2850-05.vsd
04-29-99

Figure 8-14. Typical One-Line Diagram For MOTOR

8-42 Application BE1-CDS


87RT
VOA
87RP Relay Output
U OUTA
Trouble Logic
87 87UT
IN1 BLK VO1
Mode1 2NDHA
Breaker1 Motor
R
Status Trip Output
5THHAR OUT1
OPTO Logic

VO2
Not Used
50TNT Output
OUT2
BLK 50TN Logic
Mode1 50TNPU
VO3
50TPT Not Used
BLK 50TP Output
50TQT OUT3
Mode1 50TPPU Logic
BLK 5OTQ
Mode1 50TQPU VO4
Overload
143 Speed Alarm
Switch Output
OUT4
Enable 51QT VO15 Logic
143 Unbalance
BLK 51Q VO5
VO7 Mode1 51QPU Alarm Point 23
Unbalance
Starting
IN2 Alarm Output
High Inertia OUT5
Speed Switch Logic
Closed At Rest 51PT VO14
OPTO BLK 51P 51PP Overload
Mode1 U Alarm Point 22 VO6
Not Used OUT6
250TPT Output
BLK 250TP Logic
TRSTKEY
Mode1 250TPPU 151PT
BLK 151P 151PP HMI
ARSTKEY
Mode1 U
High/Low
243 Inertia Select
243 VO13
150TPT Emergency Trip VO9
BLK 150TP Alarm Point 21 Emergency Trip
Mode1 150TPPU
Seal In

VO8
251PT
Starting
BLK 251P 251PP
Mode1 U
9 VO11 PROT TRIP

8 VO12 PROT PU

OPTO IN3 Emergency Trip

LEGEND:
87 = Differential Fault Protection Note: For clarity, multiple variables
50TN = BU Ground Fault Protection going to the same OR Gate are shown
50TQ = Loss Of Phase Protection by a single line into the OR Gate.
51Q = Unbalance Protection
51P = Overload Protection
151P = Locked Rotor (High Inertia)
150TP = Locked Rotor (Low Inertia)
251P = Jam Protection
50TP = Start Detection (High Inertia) D2850-06.vsd
250TP = Start/Running Detection 04-29-99

Figure 8-15. Typical Logic Diagram For MOTOR

Protection Elements
Referring to Figure 8-14, the 87, 50/51, 150/151, and 250 protection elements are connected to CT input
1, and the motor side of the 87 protection element is connected to input 2. The 87, 50/51, 150/151, and
250 protection elements are logic enabled to provide a trip by the settings shown in Table 8-26. Protection
elements set at 0 are setting disabled, and will not provide a trip output even if logic enabled.
Typically, the 87 protection element provides high-speed, percent restrained, phase and ground
protection, for faults inside the differential zone. For the MOTOR application shown in Figure 8-15, the
percent-restrained differential protection function is the only function of the 87 protection element required.
nd th
Set the pickup of the 2 , 5 , and 87U functions to 0 (setting disabled). The unrestrained differential
nd th
function has a setting only when the 2 and 5 harmonic restraint functions are set for transformer
applications (refer to the discussion in Overview Of Preprogrammed Logic Schemes).
In the MOTOR scheme, the 50TQ protection element is used for loss of phase detection, the 51Q
protection element is used for unbalance protection (46), and the 50TN protection element is used for
ground fault backup protection.
In the MOTOR scheme, the 51P protection element is used for motor overload protection. Blocking during
staring is not required since this element is slower than the locked rotor protection. It also serves as
backup during starting. The 251P protection element is used to protect for a jam or stall condition. It is
blocked while the motor is starting as determined by VO8.
In the MOTOR scheme, the 150TP protection element provides locked rotor protection for low inertia
motors. It is blocked when the motor is running (after the 250TP time setting expires) or when virtual

BE1-CDS Application 8-43


control switch 243 is set to high inertia mode. The 151P protection element provides locked rotor
protection for high inertia motors. It is blocked when virtual control switch 243 is set to low inertia mode. If
high Inertia is selected, it is unblocked when starting as determined by intermediate logic VO7. Virtual
control switch 143 selects whether high inertia motor starting is determined by speed switch or by current
detection (50TP protection element set at 85% of locked rotor current).
In the MOTOR scheme, the 50TP protection element is used for motor start detection (50S). The 250TP
protection element is used to detect when the motor is running. It supervises the 150TP locked rotor
protection for low inertia motor applications and the 251P jam or stall protection. Targets should not be
enabled with the SG-TARG setting for either the 50TP or the 250TP function.

Integration Of Protection, Control, And I/O Elements


The logic settings in Table 8-26 also include the logic equations that establish the control connections or
logic wiring between elements of the MOTOR scheme. For example, the two underlined equations in the
settings of Table 8-26 provide the electrical connection between the 87 element (trip enabled by the
settings) and trip output 1. Referring to Figures 8-14 and 8-15, all protection elements in the MOTOR
scheme are enabled to trip. All protection elements with the exception of 250TP start /run detection, are
connected to trip through output 1. Motor phase unbalance alarms are connected through output 5, and
motor overload alarms through output 4. Protection elements set at 0 are setting disabled and will not
provide a trip output even if logic enabled.
The 87, 50TN, 50TQ, 51P, and 251P protection elements provide primary and backup fault/open phase
protection, including stall protection for a running motor. The remainder of the protection is associated
with starting the motor. High and low inertia locked rotor protection is provided by 150TP and 151P
protection elements. Start/Run current detection for low inertia motors is provided by the 250TP
protection element, and start detection for high inertia motors is provided by either speed switch input or
current detection from the 50TP protection element.

High Inertia Motor Start


As shown on Figure 8-14, the first thing the user must do is select the high inertia position of virtual control
switch 243 and then select between motion detection by external speed switch or motion detection by
current sensing. This is accomplished by the position of virtual switch 143. If we assume current sensing
was selected, then, when the breaker is closed, 50TP picks up forcing VO7 high and removing the block
from 151P locked rotor protection. Locked rotor 151P picks up and starts timing. If the motor current
drops below the 50TP setting before 151P times out, the locked rotor protection is blocked and the motor
start was successful. However, if the motor current stays high until 151P times out, the motor is tripped
through output 1 and the Major Alarm LED on the front panel lights.
If speed switch input is selected by the position of virtual switch 143, then, when the breaker is closed,
250TP picks up and a closed external speed sensing contact at input 2 unblocks the locked rotor
protection. If the speed sensing contact opens, or the 250TP drops out, locked rotor protection is blocked
and the motor successfully starts.
For high or low inertia starts, 251P jam or stall protection is blocked by V08 until 250T drops out or times
out.
For high inertia motors, the distance between the burn-up curve and the knee point of the start/run plot is
typically close. Locked rotor protection will reset when the motor comes up to speed, but abnormally high
run current could still be present, but not high enough to trip on overload. If the abnormal run current is
allowed to persist, motor life will be shortened through accelerated thermal aging. To alert the user to this
condition, when 250TP has timed out and 51P is picked up, virtual output 14 is programmed to go high
which drives alarm bit #22 in the programmable alarm mask and alarms through output 4 to the outside
world. It can also be masked to drive an alarm LED, and the alarm display to indicate when the overload
condition exists. If the overload is high enough to time out 51P, the breaker is tripped through output 1.
Phase imbalance can lead to stator and rotor overheating resulting in the same scenario as previously
discussed. For this reason, a circuit similar to the overload alarm is included for phase imbalance. When
51Q picks up, virtual output 15 is programmed to go high which drives alarm bit #23 in the programmable
alarm mask and alarms through output 5 to the outside world. It can also be masked to drive an alarm

8-44 Application BE1-CDS


LED, and the alarm display to indicate when the imbalance condition exists. If the imbalance is high
enough to time out 51Q, the breaker is tripped through output 1.

Low Inertia Motor Start


Selecting the low inertia protection through virtual control switch 243 disables the 151P high inertia locked
rotor protection. When the breaker is closed, 250TP, start/run current detection, and 150TP low inertia
locked rotor protection, start timing. If the motor comes up to speed before time out of the 150TP element,
start is successful. If 150TP times out first, the motor is tripped through output 1. As described under high
inertia start, a motor could successfully start but still have abnormally high run currents. If 250TP,
start/run current detection times out, 150TP (low inertia locked rotor protection) is defeated and the same
motor overload protection discussed above takes over.

Emergency Trip
An external emergency trip as sensed at IN3 initiates a trip of the breaker through output 1 and seals the
trip path through V09. Virtual output 13 goes high which drives alarm bit #21 in the programmable alarm
mask. The breaker cannot be closed until the seal-in is cleared by the alarm reset key (ARSTKEY).

Alarms
Three logic variables drive the front panel LEDs: Relay Trouble (ALMREL), Major Alarm (ALMMAJ), and
Minor Alarm (ALMMIN). There is a fourth logic variable, Logic Alarm (ALMLGC), but there is no
associated front panel LED. When the relay self-test detects a problem in the relay (ALMREL) as
programmed for the MOTOR scheme, the Relay Trouble LED lights, output A operates, and all outputs
are disabled. When a Major Alarm is detected (ALMMAJ), the associated LED lights, but in this scheme,
no output relay is programmed to operate. When a Minor Alarm (ALMMIN) is detected, the associated
LED lights, but in this scheme, no output relay is programmed to operate.

Note
Tables 8-27 through 8-30 provide detailed logic definitions for the inputs, outputs,
protection, and control elements. Only those inputs, logic blocks, virtual switches, and
outputs in use for the MOTOR preprogrammed logic are described in the following
Tables.

Table 8-27. MOTOR Contact Input Logic


Variable State Labels, 7 Char
Input Purpose Label 16 Closed Open (0)
Characters (1)
IN1 Optional input. Used for CT input circuit 1 breaker status BREAKER-1 CLOSED OPEN
indication in SER reports. TRUE when breaker closed.
IN2 Speed switch, closed at rest. Used to block the 51S locked SPEED- RUNNING STOPPED
rotor protection (for high inertia motors) during running. SWITCH-IN2
IN3 Emergency trip. This is an optional input. EMERG- TRIP NORMAL
TRIP-IN3

Table 8-28. MOTOR Function Block Logic


BESTlogic Mode
Function Purpose Expression Setting
87 Used for percent-restrained differential protection with high-speed 43 1
unrestrained instantaneous differential protection. (ENABLED)
51P 51P is used for motor overload protection. Blocking during starting 0 1
is not required since this element is slower than the LR protection. (CT CKT 1)
It serves as backup during starting.

BE1-CDS Application 8-45


Table 8-28. MOTOR Function Block Logic - Continued
BESTlogic Mode
Function Purpose Expression Setting
51Q 51Q is used for unbalance protection (46). 0 1
(CT CKT 1)
151P The 151P element provides locked rotor protection for high inertia /VO7+/243 1
motors. Blocked when low inertia is selected by switch 243. If high (CT CKT 1)
Inertia is selected, it is unblocked when starting as determined by
intermediate logic VO7.
251P This element protects for a jam condition. It is blocked while the VO8 1
motor is starting as determined by VO8. (CT CKT 1)
50TP 50TP is used for motor start detection (50S). Target should not be 0 1
enabled with the SG-TARG setting for this function . (CT CKT 1)
50TN 50TN is used for ground fault backup protection. 0 1
(CT CKT 1)
50TQ 50TQ is used for loss of phase detection. 0 1
(CT CKT 1)
150TP This element provides LR protection for low inertia motors. It is 243+250TP 1
blocked when the motor is running (after the 250TP time setting T (CT CKT 1)
expires) or when the high inertia mode is selected.
250TP The 250TP is used to detect when the motor is running. It 0 1
supervises the 150TP locked rotor protection for low inertia motor (CT CKT 1)
applications and the 251P jam protection. Target should not be
enabled with the SG-TARG setting for this function.

Table 8-29. MOTOR Virtual Switch Logic


Variable State Labels, 7 Char
Switch Purpose Mode Label 16 Closed Open
Characters (1) (0)
143 Speed Switch selector. When enabled, the 2 SPEED- ENABLED NONE
motor starting is determined by speed switch. (ON/OFF) SWITCH
When None, starting is determined by current
detector set at 85% of locked rotor current.
243 Selector switch to customize the protection for 2 INERTIA- HIGH LOW
high or low inertia applications. When high is (ON/OFF) MODE
selected, blocks 150TP and enables 151P for
locked rotor protection.

Table 8-30. MOTOR Output Logic


Variable State Labels, 7 Char
Output Purpose Description Label 16 Closed Open
Characters (1) (0)
VOA Relay Trouble alarm OUTA contact closes when relay RELAY- ACTIVE NORMAL
(OUTA) trouble alarm occurs TROUBLE
BESTlogic Expression: VOA=0
VO1 Breaker trip TRUE when protective trip MOTOR_ TRIP NORMAL
(OUT1) expression is TRUE. TRIP
BESTlogic Expression: VO1=VO11

8-46 Application BE1-CDS


Table 8-30. MOTOR Output Logic - Continued
Variable State Labels, 7 Char.
Output Purpose Description Label 16 Closed Open
Characters (1) (0)
VO4 Overload alarm output Overload protection (51P) is OVERLOAD- ALARM NORMAL
(OUT4) contact picked up and timing to trip. O4
BESTlogic Expression: VO4=VO14
VO5 Unbalance alarm output Unbalance protection (51Q) is UNBALANCE- TRIP NORMAL
(OUT5) contact. picked up and timing to trip. O5
BESTlogic Expression: VO5=VO15
VO7 Intermediate logic SW 143 selects whether STARTING- TRUE FALSE
variable that determines starting is determined by HIGH-I
if a high inertia motor monitoring speed switch or
application is starting. current. TRUE if motor
(Not yet up to speed). energized 250TPPU and speed
switch (IN2) closed. Or, 50TP is
picked up. Used to unblock
151P for Locked Rotor
protection .
BESTlogic Expression: VO9= IN2*250TPPU*143+50TPPU*/143
VO8 Intermediate logic TRUE if 250TP is picked up but STARTING TRUE FALSE
variable that determines not yet timed out. Used to
if the motor is unblock jam (251P) protection.
starting.(time set for
about 120% of
maximum start time)
BESTlogic Expression: VO10=250TPPU*/250TPT
VO9 Emergency Trip TRUE if IN3 is energized EMER-TRIP- TRUE FALSE
intermediate logic causing a trip or if emergency SEALIN
expression for external trip alarm point is TRUE.
trip alarm sealin.
BESTlogic Expression: VO9=IN3+VO13
VO11 Protective trip Restrained diff trip, 50TN PROTECTIVE TRIP NORMAL
expression ground fault, 50TQ loss of -TRIP
phase, 150TP low inertia locked
rotor, 51P overload, 51Q
unbalance, 151P high inertia
locked rotor, 251P Jam, or
VO13 Emergency Trip.
BESTlogic Expression: VO11=87RT+50TNT+50TQT+150TPT+51PT+51QT+151PT+251PT+VO13
VO12 Protective pickup Restrained and unrestrained PROT- PU NORMAL
expression diff trip, 50TN ground fault, PICKED-UP
50TQ loss of phase, 150TP low
inertia locked rotor, 51P
overload, 51Q unbalance, 151P
high inertia locked rotor, 251P
Jam.
BESTlogic Expression:
VO12=87RPU+50TNPU+50TQPU+150TPPU+51PPU+51QPU+151PPU+251PPU

BE1-CDS Application 8-47


Table 8-30. MOTOR Output Logic - Continued
Variable State Labels, 7 Char.
Output Purpose Description Label 16 Closed Open
Characters (1) (0)
VO13 Emergency trip alarm. TRUE if emergency trip input is EMER-TRIP- ALARM NORMAL
(ALARM energized causing a motor trip. RESET
POINT The alarm condition is sealed in
21) for annunciation on the HMI until
the alarm reset key is pressed
on the HMI. Note, sealin
condition cannot be broken
unless optional HMI is
purchased.
BESTlogic Expression: VO13=VO9*/ARSTKEY
VO14 Overload alarm TRUE if overload (51P) OVERLOAD ALARM NORMAL
(ALARM protection is picked up. This
POINT condition will trip the motor if
22) allowed to time out. The alarm
point is supervised by the 250TP
timing out to prevent a spurious
alarm during starting.
BESTlogic Expression: VO15=51PPU*250TPT
VO15 Unbalance alarm TRUE if unbalance (51Q) UNBALANCE ALARM NORMAL
(ALARM protection is picked up. This
POINT condition will trip the motor if
23) allowed to time out.
BESTlogic Expression: VO15=51QPU

MISCELLANEOUS LOGIC EXPRESSIONS


Several logic expressions are classified as miscellaneous. That is, they are not included in the BESTlogic
settings and are not set through the ASCII command interface using the SL (Set Logic) commands.
Several of the Reporting And Alarm Functions provided in the relay require programmable logic
expressions to determine their functionality. These logic expressions are included with the settings
associated with each function. Table 8-31 cross-references the manual Sections and commands
associated with each miscellaneous logic expression.
Each of the preprogrammed logic schemes is designed to be compatible with the factory default logic
expression settings for these Reporting And Alarm Functions. However, when copying a preprogrammed
scheme for modification or direct use, it is important to recognize that these miscellaneous logic
expressions will not be effected. These miscellaneous logic settings must be reviewed to ensure desired
performance for these functions.
Table 8-31. Miscellaneous Logic Expressions
Command Reference
SA-RESET Section 6, Reporting And Alarm Functions, Alarms Functions
SB-DUTY Section 6, Reporting And Alarm Functions, Breaker Monitoring
SB-LOGIC Section 6, Reporting And Alarm Functions, Breaker Monitoring
SG-TARG Section 6, Reporting And Alarm Functions, Fault Reporting
SG-TRIGGER Section 6, Reporting And Alarm Functions, Fault Reporting
ST-DUTY Section 6, Reporting And Alarm Functions, Transformer Monitoring

8-48 Application BE1-CDS


APPLICATION TIPS
Trip Circuit Continuity And Voltage Monitor
The trip circuit monitor drives logic variable CKTMON. This variable can be used to improve breaker
failure logic or to automatically enhance security during testing.
If the relay detects a loss of voltage or continuity in the breaker trip circuit, it is possible to speed up fault
clearing time by bypassing the breaker failure timer. Since relay failure and breaker failure are covered by
different backup actions, it is desirable to reduce common mode failure mechanisms. It is recommended
that the feeder breaker and feeder protection circuits be supplied by separate control power fuses or
breakers. The equation for the Breaker Failure Trip logic (VO5) in Figure 8-16 can be modified by ORing
the Breaker Failure Trip output with the expression VO10∗CKTMON. VO10 is designated as the Breaker
Failure Initiate expression. Example 1 illustrates how the BFT logic expression is modified. It is important
that the breaker failure timer bypass logic also be disabled in test mode. Example 2 shows the expression
for blocking the upstream instantaneous element. Figure 8-16 illustrates using the trip circuit continuity
monitor in breaker failure logic.

Example 1: Breaker failure trip expression:


SL-VO5=BFT+VO10*CKTMON*IN4*/343

Example 2: Block upstream instantaneous expression:


SL-VO4=VO12*/VO5*/CKTMON*IN4*/343
If the internal breaker failure function block is not being used, the trip circuit continuity and voltage monitor
alarm can be used to detect when the test switches have been opened. This will automatically place the
relay in the test mode. Each of the preprogrammed logic schemes has logic to detect when the relay is
out of service for test. This enables the backup logic and enhances security. It should be noted that if the
test mode logic is modified in this manner, it is not possible to differentiate between the relay being out of
service for test and a problem in the circuit breaker trip circuit. Otherwise, the internal breaker failure
function block would be disabled during a known problem in the trip circuit.

CIRCUIT
MONITOR

CKTMON

+
TESTMODE ENABLE
SWITCH
1=NORMAL 0=ENABLED

VO4
IN4 BLOCK UPSTREAM
INSTANTANEOUS
-
TESTMODE ENABLE
VIRTUAL SWITCH
1=ENABLED 0=NORMAL

343

PROTECTION PICKED BREAKER


UP EXPRESSION VO12 FAILURE
INI BFT
TRIP
BF VO5

BREAKER FAILURE BLK BFPU


VO10 D2857-15.vsd
INITIATE EXPRESSION 10-27-99

Figure 8-16. Trip Circuit Continuity And Voltage Monitor


BE1-CDS Application 8-49
Close-Circuit Monitor
A close-circuit monitor is not included in any of the preprogrammed logic schemes. This function may be
added by using a 62 function block and a contact sensing input (INX) to monitor the close circuit. The
logic is shown in Figure 8-17. The output of the 62 protection block will close the designated output
contact (VOY) when an open breaker and an open close-circuit condition exists. The S<g>-62 command
is used to provide a 500 millisecond time delay to inhibit the momentary alarm that will occur due to the
timing difference between the two signals.

0=BREAKER CLOSED
1=BREAKER OPEN
VOX 62 VOY
IN1 INI
(52B) PICKUP
TIME

DROPOUT
TIME

BLK
INX 62 TIMER
(CLOSE CKT)

0=CLOSE CKT OPEN


1=CLOSE CKT OK
VOX=IN1*/INX
SL-62=1,VOX

D2587-02
3-13-97
S<g>-62=500,0
SL-VOY=62

Figure 8-17. Close Circuit Monitor Logic

Block Neutral and Negative Sequence Protection


The neutral and negative sequence overcurrent elements provide greater sensitivity to unbalanced faults
than the phase overcurrent elements because they can be set to pickup below balanced three phase load.
This can lead to a mis-operation during periods of load imbalance. The BE1-CDS provides a neutral and
negative sequence demand function that allows monitoring and alarming to prevent load imbalances.
However, distribution systems with single-pole fault clearing and switching devices or long single-phase
laterals, may have mis-operations during switching activities.
Some of the preprogrammed logic schemes provide for the use of a cutoff switch to block the ground and
negative sequence 50T (used for low set instantaneous) and the 51 (inverse time) function blocks during
switching activities. This is the most conservative approach. The protection engineer may wish to
evaluate this strategy based on his system, his operating practices, and his setting practices. For
instance, on systems with wye connected loads, the ground units are most sensitive to this situation. On
systems with delta connected loads the negative sequence units are most sensitive to this situation. It may
not be necessary to block the instantaneous units if their settings prevent them from tripping for a
switching imbalance.
To maintain proper coordination, the logic of the feeder relays may be interconnected with the upstream
bus relay to block the equivalent ground and/or negative sequence function blocks in the upstream relay.

Setting Group Selection


The BE1-CDS Current Differential System provides multiple settings groups for adaptive relaying. The
preprogrammed logic schemes barely tap the flexibility that is available. The following examples illustrate
how the setting groups can be adapted for different conditions and how different setting groups can be
used to vary the system logic.
Example 1: Adapting the relay settings for different conditions.
In overcurrent protection systems, the source conditions can have a major impact on sensitivity,
coordination intervals, and clearing times. Generally, the pickup and time dial settings are a compromise
between a normal condition and a worst case condition. Contact logic from the position of the source
breakers can select which settings group is active. To do this, assign input D0 or D1 to a contact sensing
input. Set the setting group selection mode at 2 for binary coded selection. If D0 is set, group 0 will be
8-50 Application BE1-CDS
selected when the input is off (binary code 00). Group 1 will be selected when the input is on (binary code
01). Similarly, if D1 is set, group 2 will be selected when the input is on (binary coded 10).
This logic is useful in a situation where two transformers feed a single bus or two busses have a bus tie
between them. The feeder and bus relays must be coordinated for the situation where only one source is
in service (bus tie open or one transformer out of service). However, when both sources are in service,
such as when the bus tie is closed, each bus relay sees only half of the current for a fault. This results in
poor sensitivity and slow clearing time for the bus relays.
Example 2: Adapting the logic in different setting groups.
The logic in most of the preprogrammed logic schemes can be varied in each of the different setting
groups. This is accomplished by disabling functions by setting their primary settings at zero. It is also
possible to do more sophisticated modification of the logic in each of the different setting groups by using
the active setting group logic variables SG0, SG1, SG2, and SG3 in the BESTlogic expressions.

Output Contact Seal-In


Trip contact seal-in circuits have historically been provided with electromechanical relays. These seal-in
circuits consisted of a dc coil in series with the relay trip contact and a seal-in contact in parallel with the
trip contact. The seal-in feature serves several purposes for the EM relays. One is to provide mechanical
energy to drop the target. Second is to carry the dc tripping current from the induction disk contact which
may not have significant closing torque for a low resistance connection. The third is to prevent the relay
contact from dropping out until the current has been interrupted by the 52a contacts in series with the trip
coil. If the tripping contact opens before the dc current is interrupted, the contact may be damaged. The
first two of these items are not an issue for solid state relays, but the third item is an issue.
To prevent the output relay contacts from opening prematurely, a 200 millisecond hold timer can be
selected with the SG-HOLDn=1 command. Refer to Section 4, Input and Output Functions,
Programmable Hold Timer, for more information on this feature. If the protection engineer desires seal-in
logic with feedback from the breaker position logic, he can provide this feature by modifying the BESTlogic
expression for the tripping output. To do this, use one of the general purpose timers, 62 or 162, and set it
for mode 1 (Pickup/Dropout Timer). Set the timer logic so that it is initiated by the breaker position input,
and set the timer for two cycles pickup and two cycles dropout. Then AND the timer output with the
tripping output (VO1) and OR it into the expression for the tripping output. The same can be done for the
closing output. See Figure 8-18 for the seal-in logic diagram and Seal-In Logic Example that follows. This
example is based on the BASIC-TX preprogrammed logic scheme.

+ +

52b

+ VO6
IN1 INI 62 VO1 52TC OUTPUT
OPTO 62 OUT1
LOGIC
BLK
TRIPPING
LOGIC

VO7
VO2 52CC OUTPUT OUT2
LOGIC

CLOSING
LOGIC
52a 52b

52TC 52CC

D2590-10
- - 03-23-98

Figure 8-18. Output Seal-In Logic Diagram

BE1-CDS Application 8-51


Example 1: Seal-In Logic.

Command Purpose
SG-HOLD1=0 Turn off the hold timer for output 1
SL-62=1,IN1,0 Set the timer logic to mode 1 (pickup/dropout), IN1 to
initiate, no blocking
S#-62=2c,2c Set the pickup (2 cycles) and dropout (2 cycles) times
VO1=87RT+87UT+VO1∗/62 Set the tripping logic for restrained 87 or unrestrained
87 or virtual output 1 and not 62
VO2=87RT+87UT+VO7 Set the closing logic for restrained 87 or unrestrained
87 or virtual output 7
VO6=VO1∗/62 Set the virtual output 6 logic to VO1 and not 62
VO7=VO2∗62 Set the virtual output 7 logic to VO2 and 62
E Exit
Y Save settings

Latching a Tripping Contact


On occasion, an application will call for latching an output contact. As an example, assume that a BE1-
CDS is used for protection of a radial transformer as shown in Figure 8-19. The user wants to trip and
lockout the high-side circuit switcher for a differential trip; but, not for an overcurrent trip. He does not
want the transformer to be re-energized until someone locally checks and resets the relay.
Referring to Figure 8-20, which is an adaptation of BASIC-87 logic, an 87 trip will cause VO7 to go true.
This causes OUT1, OUT2, and OUT3 to close and OUT5 which would be wired in the close circuit, to
open. VO7 is sealed in through VO8 and holds the outputs in this condition. The optional front panel HMI
LCD automatically goes to the targets screen per the automatic display priority function. When the
operator presses the reset key while the display is on the targets screen, the TRSTKEY logic variable
goes high and breaks the seal in of logic expressions VO7 and VO8. Outputs OUT1, OUT2, and OUT3
will then open and OUT5 will close.

8-52 Application BE1-CDS


CSW

BE1-
CDS220
52
BUS
MAIN

P0004-06.vsd
08-14-00

52 52 52

Figure 8-19. Station One-Line Drawing

VO7
87RT 87 Trip
87RPU
VO8 VOA
87 87UT 87_Seal-In Relay
BLK
Mode1 Trouble
2NDHAR Output
OUTA
TRSTKEY Logic
5THHAR
HMI VO9
ARSTKEY VO1
SPR_Seal-In 87 Trip Output
OUT1
51PT Logic
BLK 51P
Mode1 51PPU
VO2
87 Trip Output
OUT2
Logic
51NT
BLK 51N
Mode1 51NPU VO3
87 Trip Output
OUT3
Logic
51QT
BLK 51Q
Mode1 51QPU VO4
3 51 Trip
Output
OUT4
Logic

VO5
VO13
Block Close
SPR_Trip Output
OUT5
IN4 63_SPR Logic
OPTO
VO11 PROT TRIP
5

5 VO12 PROT PU

P0004-08.vsd
08-22-00
Note: For clarity, multiple variables going to the same OR Gate are shown by a single line into the OR Gate.

Figure 8-20. Latching a Tripping Contact Example

BE1-CDS Application 8-53


Latching A Programmable Logic Alarm Or Creating A Pseudo Target
Sometimes, a user may want the relay to annunciate and latch for a user defined condition originating
internally or externally to the relay. This can be accomplished using the user programmable labels
functionality and the virtual outputs VO13, VO14, or VO15. These virtual outputs are also programmable
alarm variables. If one of these three logic expressions is true and is also programmed as a major or
minor alarm point, the programmable label will appear on the alarms screen of the optional front panel
HMI display.
The application of this is best illustrated with an example. Use the application shown in Figure 8-19 and
8-20. The user wants to trip and lockout the high side circuit switcher (CSW) for a Sudden Pressure Relay
(63_SPR) trip. The SPR trip is to be supervised and sealed in via the BE1-CDS relay. Since this is an
external function, it is desired that the relay annunciate that the trip came from the SPR instead of an
internal protective element.
Referring to Figure 8-20, when the SPR contact closes, IN4 will cause VO13 to go true. This causes
OUT1, OUT2, and OUT3 to close and OUT5 which would be wired in the close circuit, to open. VO13 is
sealed in through VO9 which holds the outputs in this condition. The HMI LCD automatically goes to the
alarms screen if VO13 is programmed as a major or minor alarm per the automatic display priority
function. The LCD displays the user programmable label for VO13 which in this example might be
programmed to be SN-VO13=SPR_TRIP.
When the operator presses the reset key while the display is on the alarms screen, the ARSTKEY logic
variable goes high and breaks the seal in of logic expressions VO13 and VO9. Outputs OUT1, OUT2, and
OUT3 will then open and OUT5 will close.
Refer to Section 6, Reporting and Alarm Functions for more information on programmable alarms. Refer
to Section 10, Human Machine Interface for more information on Automatic Display Priorities.

Logic Settings Associated With Figure 8-20


SL-87=1,0
SL-51P=1,0; SL-51N=1,0; SL-51Q=1,0
SL-VO1=VO7+VO13
SL-VO2=VO7+VO13
SL-VO3=VO7+VO13
SL-VO4=51PT+51NT+51QT
SL-VO5=/VO7+/VO13
SL-VO6=ALMMAJ
SL-VO7=87RT+87UT+VO8
SL-VO8=VO7*/TRSTKEY
SL-VO9=VO13*/ARSTKEY
SL-VO11=51PT+51NT+51QT+87RT+87UT
SL-VO12=87UT+51PPU+51NPU+51QPU+87RPU
SL-VO13=IN4+VO9

8-54 Application BE1-CDS


SECTION 9 • SECURITY

TABLE OF CONTENTS
List of Tables........................................................................................................................................... i
SECTION 9 • SECURITY........................................................................................................................... 9-1
INTRODUCTION .................................................................................................................................... 9-1
PASSWORDS ........................................................................................................................................ 9-1
Setting Up Password Protection...................................................................................................... 9-1
GS-PW Command ....................................................................................................................... 9-2

List of Tables
Table 9-1. Password Protection Settings .................................................................................................. 9-1

BE1-CDS Security i
SECTION 9 • SECURITY

INTRODUCTION
This section describes the security that is embedded in the BE1-CDS. Security, in the form of multilevel
password protection, is discussed along with the information required for protecting specific function
groups and user interface components against unauthorized access.

PASSWORDS
Passwords provide access security for three distinct functional access areas: Settings, Reports, and
Control. Each functional area can be assigned a unique password or one password can be assigned to
multiple areas. A global password is used to access all three of the functional areas. BE1-CDS
passwords are not case sensitive; either lowercase or uppercase letters may be entered. Password
security only limits write operations; passwords are never required to read information from any area.
Additional security is provided by controlling the functional areas that can be accessed from a particular
communication port. For example, security can be configured so that access to Control commands from
the rear RS-232 port (COM1) is denied. Then, an attempt to issue a Control command through COM1 will
cause the relay to respond with an ACCESS DENIED and/or INVALID PASSWORD message. This will
occur whether a valid password is entered or not. When configuring communication port access areas,
you should be aware that the front RS-232 port (COM0) and the front panel HMI are treated as the same
port.
The communication ports and password parameters act as a two-dimension control to limit changes. For
a command to be accepted, the entered password must be correct and the command must be entered
through a valid port. Only one password can be active at one time for any area or port. For example, if a
user gains write access at COM1, then users at other areas (COM0, front panel HMI, and COM2) won’t be
able to gain write access until the user at COM1 uses the EXIT command to release access control.
If a port holding access privilege sees no activity (command entered or HMI Edit key pressed) for
approximately five minutes, access privilege is lost and any pending changes are lost. This feature
ensures that password protection can’t be accidentally left in a state where access privileges are enabled
for one area and other areas locked out for an indefinite period.
If password protection is disabled, then entering ACCESS= followed by no password or any alphanumeric
character string will obtain access to the unprotected area(s).

Setting Up Password Protection


Password protection is configured for each access area port and communication port with the GS-PW
(Global Security – Password) command. Password protection settings are summarized in Table 9-1.
Table 9-1. Password Protection Settings
Setting Range/Purpose Default
password User defined alphanumeric string with a maximum of 8 characters. 0 (No entry)
A setting of 0 disables password protection.
com ports Multiple ports may be selected by using a slash (/) between each 0/1/2
port designator.
0 = Front RS-232 port
1 = Rear RS-232 port
2 = Rear RS-485 port

BE1-CDS Security 9-1


GS-PW Command
Purpose: Reads or sets passwords, password access areas, and password access ports.
Syntax: GS-PW[ <t>[= <password>, <com ports(0/1/2)>]]
Comments: t = C, G, R, or S (C - provides write access to Control commands; G - provides Global
write access to all commands; R - provides write access to Report commands; S -
provides write access to Setting commands)
Example 1: Read without global access.
GS-PWG
0,0/1/2
Example 2: Read the current passwords, assuming that the current privilege level G password has
already been entered with the ACCESS command.
GS-PW
GS-PWG=G,0/1/2; GS-PWS=S,0/1/2; GS-PWC=C,0/1/2; GS-PWR=R,0/1/2
Example 3: Program password S to be ABC and allow it to be accepted at the front panel HMI, the front
panel RS-232 port, and the rear RS-232 port. Program password R to be ABC and allow it
to be accepted at the front panel HMI and at the front RS-232 port.

With these settings, if ACCESS=ABC is entered at the front RS-232 port (COM0), the relay
responds with ACCESS GRANTED: SETTING AND REPORT. If ACCESS=ABC is entered
at the rear RS-232 port (COM1), the relay responds with ACCESS GRANTED: SETTING.

Example 4: Limit Global access to the front panel but don’t require a password to be used.
GS-PWG=0,0; GS-PWS=XYZ,0/1
Example 5: Limit Control operations to the RS-485 port (COM2) but don’t require a password.
GS-PWC=0,2

9-2 Security BE1-CDS


SECTION 10 • HUMAN-MACHINE INTERFACE
(Controls And Indicators)
TABLE OF CONTENTS

List Of Figures......................................................................................................................................... i
List Of Tables.......................................................................................................................................... i
SECTION 10 • HUMAN-MACHINE INTERFACE (Controls And Indicators)............................................ 10-1
GENERAL ............................................................................................................................................ 10-1
STANDARD FRONT PANEL DISPLAY .............................................................................................. 10-1
OPTIONAL FRONT PANEL ................................................................................................................. 10-2
Menu Tree......................................................................................................................................... 10-3
Automatic Display Priority ................................................................................................................. 10-4
HMI OPERATIONS .............................................................................................................................. 10-5
Menu Tree Branches ........................................................................................................................ 10-7

List Of Figures
Figure 10-1. BE1-CDS Current Differential System HMI ........................................................................ 10-1
Figure 10-2. BE1-CDS Current Differential System With Optional HMI.................................................. 10-2
Figure 10-3. Virtual Control Switch 243 .................................................................................................. 10-6
Figure 10-4. BE1-CDS Menu Tree (Top Level, All Branches) ................................................................ 10-7
Figure 10-5. BE1-CDS Menu Tree (Report Status Branch) .................................................................... 10-8
Figure 10-6. BE1-CDS Menu Tree (Control Branch) .............................................................................. 10-9
Figure 10-7. BE1-CDS Menu Tree (Metering PRI/SEC Branch)........................................................... 10-10
Figure 10-8. BE1-CDS Menu Tree (Reports Branch) ........................................................................... 10-11
Figure 10-9. BE1-CDS Menu Tree (Protection Branch)........................................................................ 10-12
Figure 10-10. BE1-CDS Menu Tree (General Settings Branch) ........................................................... 10-13

List Of Tables
Table 10-1. BE1-CDS Controls And Indicators ....................................................................................... 10-1
Table 10-2. BE1-CDS Controls And Indicators For Optional HMI........................................................... 10-2
Table 10-3. Automatic Screen Display Priority Status ............................................................................ 10-4
Table 10-4. Virtual Control Switches Controls And Indicators ................................................................ 10-6

BE1-CDS HMI i
SECTION 10 • HUMAN-MACHINE INTERFACE
(Controls And Indicators)

GENERAL
This section provides a description of the BE1-CDS human-machine interface and illustrates the menu
tree.

STANDARD FRONT PANEL DISPLAY


Figure 10-1 shows the standard front panel human-machine interface (HMI) for a BE1-CDS Current
Differential System. Refer the callouts in Figure 10-1 to Table 10-1.

Figure 10-1. BE1-CDS Current Differential System HMI

Table 10-1. BE1-CDS Controls And Indicators


A Identification plate showing sensing input current range, power supply type, and serial
number.

B Power LED. When this LED is ON, indicates operating power is applied to the relay.
C Relay Trouble LED. When this LED is ON, indicates that the relay is off-line due to
start-up condition or a relay failure alarm.. Refer to Section 6, Reporting And Alarm
Functions for a compete description of the relay failure alarm diagnostics.
D Minor Alarm LED. When this LED is ON, indicates a minor alarm status. Refer to
Section 6, Reporting And Alarm Functions for a compete description of the Minor
Alarms.
E Major Alarm LED. When this LED is ON, indicates a major alarm status. Refer to
Section 6, Reporting And Alarm Functions for a compete description of the Major
Alarms.

BE1-CDS HMI 10-1


Table 10-1. BE1-CDS Controls And Indicators - Continued

F Trip LED. When this LED is flashing ON, indicates that a protective element is picked
up. When this LED is ON continuously, indicates that a trip output is closed. The
LED is sealed-in if a protective trip has occurred and there are targets being
displayed. (Refer to Section 6, Reporting And Alarm Functions for a complete
description of the trip indicator LED.)
G Communications Port 0. RS-232 serial communications port. A computer terminal or
PC running a terminal emulation program such as Windows Terminal can be
connected to this port so that the user may send commands to the relay or receive
reports from the relay. Communication with the relay uses a simple ASCII command
language.

OPTIONAL FRONT PANEL


Figure 10-2 shows the optional front panel human-machine interface (HMI) for a BE1-CDS Current
Differential System. Refer the callouts in Figure 10-2 to Table 10-2.

Figure 10-2. BE1-CDS Current Differential System With Optional HMI


Table 10-2. BE1-CDS Controls And Indicators For Optional HMI

A Identification plate showing sensing input current range, power supply type, and serial
number.
B Power LED. When this LED is ON, indicates operating power is applied to the relay.
C Relay Trouble LED. When this LED is ON, indicates that the relay is off-line due to
start-up condition or a relay failure alarm.. Refer to Section 6, Reporting And Alarm
Functions for a compete description of the relay failure alarm diagnostics.
D Minor Alarm LED. When this LED is ON, indicates a minor alarm status. Refer to
Section 6, Reporting And Alarm Functions for a compete description of the Minor
Alarms.

10-2 HMI BE1-CDS


Table 10-2. BE1-CDS Controls And Indicators - Continued

E Major Alarm LED. When this LED is ON, indicates a major alarm status. Refer to
Section 6, Reporting And Alarm Functions for a compete description of the Major
Alarms.
F Trip LED. When this LED is flashing ON, indicates that a protective element is picked
up. When this LED is ON continuously, indicates that a trip output is closed. The
LED is sealed-in if a protective trip has occurred and there are targets being
displayed. (Refer to Section 6, Reporting And Alarm Functions for a complete
description of the trip indicator LED.)
G Communications Port 0. RS-232 serial communications port. A computer terminal or
PC running a terminal emulation program such as Windows Terminal can be
connected to this port so that the user may send commands to the relay or receive
reports from the relay. Communication with the relay uses a simple ASCII command
language.
H Reset pushbutton switch. Resets report data including: sealed-in Trip targets, Trip
LED, peak demand currents, and alarms.
I Scrolling pushbuttons (keys). Scrolls UP/DOWN/LEFT/RIGHT through the menu tree
or when in the Edit mode, the LEFT/RIGHT scrolling pushbuttons select the variable
to change and the UP/DOWN scrolling pushbuttons change the variable.
J Edit pushbutton switch. Enables settings changes. When the Edit pushbutton is first
pushed, an LED on the pushbutton turns ON to indicate the edit mode is active.
When changes are complete (using the scrolling pushbuttons) and the Edit
pushbutton is pushed again, the LED turns OFF indicating that the changes are
saved. If changes are not completed and saved within five minutes, the edit mode is
exited without saving changes.
K 64 by 128 pixel graphic liquid crystal display (LCD) with backlighting. Primary source
for receiving information from the relay or when locally programming settings to the
relay. Displays active logic scheme name, targets, metering values, demand values,
communications parameters, diagnostic information, and the menu tree steps or
branches.

Menu Tree
The display uses a menu tree that can be scrolled using the scrolling pushbuttons. The menu tree has six
branches. These branches are:
• REPORT STATUS. Display and resetting of general status information such as targets, alarms,
input and output status, etc.
• CONTROL. Operation of control functions such as controlling virtual switches, selection of active
setting group, etc.
• METERING PRI/SEC. Display of real time metering values.
• REPORTS. Display and resetting of report information such as time and date, demand registers,
breaker duty statistics, etc.
• PROTECTION. Display and setting of protective function setting parameters such as pickups,
time delays, etc.
• GENERAL SETTINGS. Display and setting of non protective function setting parameters such as
communication, CT ratios, and connections, etc.
The branch path is located in the upper left hand corner of the each screen in the menu tree. This path is
like a computer file path and indicates the current branch and level in the menu tree structure. This path
helps so that you do not loose track of where you are in the menu tree. You scroll through each level of
the menu tree by using the right and left scrolling keys. To go to a level of greater detail, you use the
down scrolling key. Each time you go to a lower level in the menu tree, another branch is added to the
screen path and is separated by a backslash.

BE1-CDS HMI 10-3


All branches in the menu tree are shown in the figures at the end of this section. In these figures, notice
near the upper left hand corner of each screen display, one, two, three, or four digit numbers with decimal
points between each digit. These numbers are reference numbers to the screens in the menu tree. They
are frequently referred to in the text of this manual and are necessary for programming the SG-SCREEN
command as described in this section.

Automatic Display Priority


If no front panel scrolling key has been pressed for approximately five minutes, the relay automatically
switches to and displays the highest priority REPORT STATUS menu screen. In a typical application, the
user would return to the relay and prefer to see the data that is of the most interest already on the screen.
The automatic screen display follows the priority logic described in Table 10-3. For example, if a trip has
occurred, the target display screen is the highest priority and will be displayed automatically.
Table 10-3. Automatic Screen Display Priority Status
Priority Priority Logic State Screen Displayed Data
1 Targets active \STAT\TARGETS Scrolling display of Target Elements and
Fault Currents
2 Alarms Active \STAT\ALARMS Scrolling display of Active Alarms
3 Scrolling Screens \STAT\SCRNS\SCRN Scrolling display of user screens
active programmed with the SG-SCREEN
command
4 Scrolling screens \STAT\TARGETS Default Target screen showing TARGETS
disabled NONE

If there are no targets or alarms, then the relay will automatically scroll through the user programmable
scroll list (there is a scrolling display of up to 16 screens). The screen scrolling list is programmed using
the SG-SCREEN command.
When the display is scrolling through the programmed scroll list, you can freeze the display and manually
scroll through the scroll list. Pressing the RIGHT or LEFT scroll pushbutton will freeze the display.
Repeatedly pressing the RIGHT scroll pushbutton will progress through the scroll list in ascending order.
Repeatedly pressing the LEFT scroll pushbutton will progress through the scroll list in descending order.
Pressing the UP scroll pushbutton will leave the automatic scroll list and place you in the menu tree at
screen 1.3, STAT\SCREENS.
Once the user has taken manual control of the display by pressing any of the scrolling pushbuttons,
automatic priority has been disabled until the display times out. Thus, if a trip or alarm occurs during this
time, the trip or alarm LED will light up, but the display will not jump to the appropriate screen. It will be
necessary to manually scroll to the target or alarm screen to see this data and reset it.
The HMI can be returned to automatic priority immediately without waiting for the timer to time out by
scrolling to screen 1.3, STAT\SCREENS and pressing the DOWN scroll pushbutton to return to the
automatic scroll list.

Setting the Screen Scroll list

SG-SCREEN Command
Purpose: Reads or sets the screens displayed in the scrolling screens mode.
Syntax: SG-SCREEN<x>[=<default screen number>]
Comments: x = sequence in screen scroll list (1 to 16)
default screen number = screen number as displayed in upper-left-hand corner of display
screen. Consult Figures 10-4 through 10-10 for assistance when making or interpreting
scrolling screens settings.

10-4 HMI BE1-CDS


The default scrolling screens are:
SG-SCREEN1 = 1.4.6
SG-SCREEN2 = 3.1.1
SG-SCREEN3 = 3.1.1.1
SG-SCREEN4 = 3.1.1.2
SG-SCREEN5 = 3.1.2
SG-SCREEN6 = 3.1.2.1
SG-SCREEN7 = 3.1.2.2
SG-SCREEN8 = 0
SG-SCREEN9 = 0
SG-SCREEN10 = 0
SG-SCREEN11 = 0
SG-SCREEN12 = 0
SG-SCREEN13 = 0
SG-SCREEN14 = 0
SG-SCREEN15 = 0
SG-SCREEN16 = 0
Screen scrolling is disabled by a setting of SG-SCREEN = 0. When scrolling is disabled, and no targets
exist, and no HMI activity has occurred for five minutes, screen 1.2, TARGETS is displayed.

SG-SCREEN Command Example

Example. Program a display scrolling sequence that shows screens in the following order:
operational status time and date (screen 1.4.6), metering, CT circuit 1 (screen 3.1.1),
metering, CT circuit 1, current measurement (screen 3.1.1.1), and metering, CT circuit 1,
calculated current (screen 3.1.1.2).
SG-SCREEN1=1.4.6
SG-SCREEN2=3.1.1
SG-SCREEN3=3.1.1.1
SG-SCREEN4=3.1.1.2

HMI OPERATIONS
The following paragraphs describe how the HMI is used to set and control relay functions.

Entering Settings
Settings for protection functions can be edited from menu branch 5, PROTECTION of the LCD HMI.
Control functions can be edited from menu branch 2, CONTROL. Settings for general and reporting
functions can be edited from menu branch 6, GENERAL SETTINGS. To edit a setting using the manual
scrolling pushbuttons, perform the following procedures.
1. Scroll to the screen that displays the function to be edited.
2. Press the EDIT pushbutton to gain access. If password security has been initiated for settings, you
will be prompted to enter the appropriate password. See the paragraphs, Entering Passwords, for
details on entering passwords from the HMI. Once access has been gained, the EDIT LED will be
lighted and a cursor will appear in the first settings field on the screen.
3. Press the UP or DOWN scrolling key to select the desired setting. Some settings require entering a
number one character at a time. For example, to enter a 51 pickup as 7.3 amps, you would press the
UP pushbutton until the 7 is showing. Then, press the RIGHT pushbutton to move the cursor over
and press the UP pushbutton until the . is showing. Then, press the RIGHT pushbutton to move the
cursor over and press the UP pushbutton until the 3 is showing. Other settings require scrolling
through a list of selections. For example, you would move the cursor over to the CRV field and then
scroll through a list of available TCC curves.

BE1-CDS HMI 10-5


4. Once all of the settings on the screen have been entered, press the EDIT pushbutton a second time
and the settings will be validated. If the settings are in range, the screen will flash CHANGES
SAVED, and the EDIT LED will go out. If you want to abort the edit session without changing any
settings, press the RESET pushbutton before you press the edit pushbutton the second time. The
screen will flash CHANGES LOST and the EDIT LED will go out.

Performing Control Operations


Control operations can be executed from the LCD HMI from menu branch 2, CONTROL. These functions
allow you to control the state of virtual switches, override logic and control the active setting group, and
override the logic and control the state of output contacts. All of these functions work similarly to the
process of entering settings in that you press the EDIT pushbutton, use the UP and DOWN scroll
pushbuttons to select the desired state, and press the EDIT pushbutton for the action to be executed.
Figure 10-3 shows virtual switch 243 as an example of a A
virtual switch screen. See Section 4, Protection And Control 2.1.3
for more details on the x43 and 101 functions. Table 10-4 \CTRL\43\243
E DIFF_CUTOFF B
describes each of the callouts shown on figure 10-3. The
user programmable label for this switch has been set to ACTION NORMAL
DIFF_CUTOFF. The TRUE (closed) state label has been NORMAL 87_OFF C
set to NORMAL. And, the FALSE (open) state label has <143 >343
been set to 87_OFF. The logical mode for this application D
D2840-18.vsd
would be set to Mode 2 (On/Off switch). To operate the 02-09-99

switch, you would use the following procedure:


Figure 10-3. Virtual Control Switch 243

Table 10-4. Virtual Control Switches Controls And Indicators


A User selectable label (meaningful name) for specific virtual switches. Switch 243
identification label set to DIFF_CUTOFF.
B User selectable label for the closed (1) state for virtual switch 243. Switch 243 closed
state label set to NORMAL.
C User selectable label for the open (0) state for virtual switch 243. Switch 243 open
state label set to 87_OFF.
D Icon to show the current switch position (status). In Figure 10-3, the current status is
the closed state which is labeled NORMAL.
E Current switch status. This indicator should correspond to the current user labeled
switch status. The switch is closed (1), and the user label for closed is NORMAL.
1. Using the manual scrolling pushbuttons, scroll to screen 2.1.x, \CTRL\43\. Or, if the screen has been
placed in the automatic scroll list, simply wait for it to appear and press the RIGHT or LEFT scroll
pushbutton to freeze the display.
2. Press the EDIT pushbutton to gain access. If password security has been initiated for control
functions, you will be prompted to enter the appropriate password. See the following paragraphs,
Entering Passwords, for details on entering passwords from the HMI. Once access has been gained
to the control function, the EDIT LED will be lighted and a cursor will appear in the action field.
3. Press the UP or DOWN scrolling key to select the desired action. The selections available are
dependent upon the logic mode setting for that switch. If it is set to Mode 1, the action choices are
pulse, or one of the two positions as defined by the user programmable state labels. If the mode is set
to Mode 2. (ON/OFF Switch) the choices for action are limited to one of the two positions. If the
mode is set to Mode 3. (OFF/Momentary ON Switch) the choice for action is limited to pulse.
4. Press the EDIT pushbutton a second time and the switch will change to the selected position, the
screen will flash CHANGES SAVED, and the EDIT LED will go out. If you want to abort the edit
session without changing any controls, press the RESET pushbutton before you press the edit
pushbutton the second time. The screen will flash CHANGES LOST and the EDIT LED will go out.

10-6 HMI BE1-CDS


Resetting Functions
The reset pushbutton is context sensitive. It’s purpose is dependent upon the screen that is presently
being displayed. For example, pressing the reset key when the demand screen is displayed will reset the
demands but it will not reset the alarms, etc. It is necessary to scroll through the menu tree to the alarm
screen to reset an alarm. You are not prompted for a password when using the reset key.
There are two BESTlogic variables associated with the HMI reset pushbutton. Logic variable TRSTKEY
becomes TRUE when the reset pushbutton is pressed while the target screen is displayed. Logic variable
ARSTKEY becomes TRUE when the reset pushbutton is pressed while the alarm screen is displayed.
See Section 8, Applications, Application Tips for examples on the use of these variables.

Entering Passwords
If password security has been initiated for a function, the HMI will prompt you to enter a password when
the EDIT pushbutton is pressed. To gain access, you must enter the appropriate password. A field of 8
asterisks appears with the cursor located under the leftmost character position. You can enter passwords
by performing the following procedures.
1. Press the UP or DOWN scrolling pushbuttons until the proper first character of the password appears.
Pressing UP scrolls through the alphabet and then the numbers in ascending order. Pressing DOWN
scrolls through the numbers and then the alphabet in descending order.
2. Press the RIGHT scrolling pushbutton to move the cursor to the next character of the password and
select the appropriate character.
3. Continue the process until the entire password has been spelled out. If the password is less than 8
characters, leave the remaining asterisks in place instead of entering blanks.
4. Press the EDIT pushbutton to enter the password. If the proper password has been entered, the
screen will flash ACCESS GRANTED. If an incorrect password has been entered, the screen will
flash ACCESS DENIED, and the EDIT LED will go out.
5. Once you gain access, it remains in affect for five minutes after the last pushbutton has been pressed.
As long as you continue to press the edit key for a function for which you have gained access, the five
minute timer will be refreshed and you will not be prompted for a password.

Menu Tree Branches


Figures 10-4 through 10-10 show all branches and screens in the menu tree. Screens on your unit may
have minor differences from those shown here. The intent for these figures is to show menu progression
and navigation and not the exact screen display.

1 2 3 4 5 6
\STATUS \CONTROL \METER \REPORTS \PROT \SETUP
BE1-CDS220 General
REPORT STATUS CONTROL METERING REPORTS PROTECTION Settings
PRI/SEC FEEDER 2
<SETUP vTARG >CTRL <STAT v43 >METER
<CTRL vCRNT >REPRT <METER vFAULT >PROT <REPRT vSG0 >SETUP <PROT vCOM >STAT

D2840-11.vsd
01-19-99

Figure 10-4. BE1-CDS Menu Tree (Top Level, All Branches)


BE1-CDS HMI 10-7
1
\STATUS
To/From BE1-CDS220
GENERAL To/From
REPORT STATUS CONTROL
SETTINGS
<SETUP vTARG >CTRL

1.1 1.2 1.3 1.4


\STAT\TARGETS \STAT\ALARMS \STAT\SCREENS \STAT\OPER_STAT

SCREEN SCROLL OPERATIONAL


TARGETS ALARMS LIST STATUS
YES YES

<PU vDET >ALMS <TARG vDET >SCRNS <ALMS vSCRN >OPER <SCRNS vINPUT >TARG

1.2.1 1.3.1
\STAT\SCRNS\SCRN
\STAT\ALARM\DETAILS NOTE:
OUT1 CKT OP BKR ALM 2 1. Up to 16 screens
BKR FAIL P DMD 2. No nav aids
see note
RECL FAIL Q DMD 3. Path on scrolled screen
REC LOCKOUT CLOCK ERR remains intact
BKR ALM 1 IRIG LOSS
SGC ACTIVE LOGIC ALM
>MORE

1.1.1 1.1.2 1.1.3 1.1.4


\STAT\TARG\DETAILS \STAT\TARG\CT_1 \STAT\TARG\CT_2 \STAT\TARG\GND
87ABC 150Q-CT1 CT CKT 1 CT CKT 2 CT GROUND
50ABC-CT1 51ABC-CT2 IA 2.00K < 23° IA 2.00K < 23° GND 2.00A
50N-CT1 51N-CTG IB 2.00K < 23° IB 2.00K < 23°
50Q-CT1 51Q-CT2 IC 2.00K < 23° IC 2.00K < 23°
150ABC-CT2 IN 2.00K < 23° IN 2.00K < 23°
150N-CT2 IQ 2.00K IQ 2.00K
<GND >CT_1 <DET >CT_2 <CT_1 >GND <CT_2 >DET

D2840-12.vsd
08-04-00

1.4.1 1.4.2 1.4.3 1.4.4 1.4.5 1.4.6


STAT\OPER\INPUT STAT\OPER\OUT \STAT\OPER\43 \STAT\OPER\ACTIVEG \STAT\OPER\BKR \STAT\OPER\TIME_DATE

INPUTS 12345678 OUTPUTS A123456 X43 -1234567 ACTIVE GROUP BREAKER_LABEL TIME 2:35:12
XXXXXXXX XXXXXXX XXXXXXXX x OFF DATE 05/10/97
CO-OUT A123456
XXXXXXX
<TIME >OUT <INPUT >43 <OUT >ACT <43 >BKR <ACT >TIME <BKR >INPUT

Figure 10-5. BE1-CDS Menu Tree (Report Status Branch)

10-8 HMI BE1-CDS


2
\CONTROL
To/From To/From
REPORT CONTROL METERING
STATUS <STAT v43 >METER
PRI/SEC

2.1 2.2 2.3 2.4


\CTRL\43 \CTRL\BKR \CTRL\SG \CTRL\OUT

43 AUX SWITCHES BREAKER_LABEL SETTING GROUP CONTROL OUTPUT CONTROL


OVERRIDE
NOTUSED LOGIC OVERRIDE x OUT A1234567
xxxxxxxx
<OUT v43 >BKR <43 >SG <BKR >OUT <SG >43

2.1.1 2.1.2 2.1.3 2.1.8


\CTRL\43\43 \CTRL\43\143 \CTRL\43\243 \CTRL\43\743
SWITCH LABEL SWITCH LABEL SWITCH LABEL SWITCH LABEL
ACTION 1 STATE ACTION 1 STATE ACTION 1 STATE etc. ACTION 1 STATE
NOTUSED 0 STATE NOTUSED 0 STATE NOTUSED 0 STATE NOTUSED 0 STATE

<743 >143 <43 >243 <143 >343 <643 >43

D2840-13.vsd
08-04-00

Figure 10-6. BE1-CDS Menu Tree (Control Branch)

BE1-CDS HMI 10-9


3
\METER
To/From To/From
CONTROL METERING
REPORTS
PRI/SEC
<CTRL vCRNT >REPRT

3.1 3.2
\METER\CRNT \METER\DIFF

CURRENT DIFFERENTIAL
MEASURED FREQUENCY
XX.XX HZ <CRNT v COMP
<DIFF vCT_1 >DIFF >CRNT

3.1.1 3.1.2 3.1.3 3.2.1 3.2.2


\METER\CRNT\CT_1 \METER\CRNT\CT_2 \METER\CRNT\GND \METER\DIFF\COMP \METER\DIFF\HARM
CT CIRCUIT 1 CT CIRCUIT 2 CT CIRCUIT GROUND %Iop IA IB IC
COMPENSATED CURRENTS 2nd 2.0% 2.3% 3.6%
VIEW PRI CURRENTS VIEW PRI CURRENTS VIEW PRI CURRENTS
5th 2.1% 5.7% 8.2%
<HARM vIA >HARM <COMP >COMP
<GND vI_MEA >CT_2 <CT_1 vI_MEA >CT_X <CT_X v I_MEA >CT_1

etc.

3.1.1.1 3.1.1.2 3.1.3.1


...\CRNT\CT_1\I_MEAS ...\CRNT\CT_1\I_CALC ...\CRNT\GND\I_MEAS
IA IB IC S IN IQ S GROUND S 3.2.1.1 3.2.1.2
2.000K 2.300K 2.100K 2.000K 2.300K 2.000K \METER\DIFF\COMP\IA \METER\DIFF\COMP\IB
< 12° <133° <255° < 12° < 12° TIMES TAP IA TIMES TAP IB
<I_CAL >I_CAL <I_MEA >I_MEA CT CKT CT CKT
1 1.20< 0° 1 1.25< 12°
2 1.52<180° 2 1.52<192°
IOP 0.32 IOP 0.27

* 3.1.1.1
...\CRNT\CT_1\I_MEAS
3.1.1.2
...\CRNT\CT_1\I_CALC
<IN >IB <IA >IC

IA-IB IB-IC IC-IA S IN IQ S


2.000K 2.300K 2.100K NA 2.300K
< 12° <133° <255° <NA
<I_CAL >I_CAL <I_MEA >I_MEA
3.2.1.3 3.2.1.4
\METER\DIFF\COMP\IC \METER\DIFF\COMP\IN
TIMES TAP IC TIMES TAP IN

* 3.1.1.1
...\CRNT\CT_1\I_MEAS
3.1.1.2
...\CRNT\CT_1\I_CALC
CT CKT
1 1.20< 0°
2 1.52<180°
CT CKT
1 1.25< 12°
2 1.52<192°
IA-IC IB-IA IC-IB S IN IQ S IOP 0.32 G 0.00<000°
2.000K 2.300K 2.100K NA 2.300K IOP 0.27
<IN >IB <IA >IC
< 12° <133° <255° <NA
<I_CAL >I_CAL <I_MEA >I_MEA

* Alternate labeling if CT's D2840-14.vsd


08-04-00
are connected in delta.

Figure 10-7. BE1-CDS Menu Tree (Metering PRI/SEC Branch)

10-10 HMI BE1-CDS


4
\REPORTS

To/From REPORTS
METERING To/From
PRI/SEC <METER vFAULT >PROT PROTECTION

4.1 4.2 4.3 4.4 4.5 4.6


\REPRT\FAULT \REPRT\SEQ \REPRT\BKR_RPTS \REPRT\DEMAND \REPRT\XFORMER \REPRT\VERS
FAULT REPORT SE Q U E N C E O F TRANSFORMER MODEL: BE1-CDS220
SUMMARY EVENTS SUMMARY BREAKER REPORTS DEMAND REPORT REPORT VERSION: xx.xx
NEW FAULTS 2 XX EVENTS SUMMARY
<SEQ vSTAT >DMD <SER vTODAY >XFORM <XFORM >FAULT
<VERS vM_REC >SEQ <FAULT >BRPTS <DMD vDET >VERS

4.5.1
4.1.1 4.1.2 4.3.1
\REPRT\BRPTS\STATUS \REPRT\XFORM\DETAILS
\REPRT\FAULT\M_REC \REPRT\FAULT\PREV
BREAKER OPERATIONS # THRU FAULTS xxxxx
XXXXX THRU FAULT DUTY
MOST RECENT TARGETS PREVIOUS TARGETS
DUTY A DUTY B DUTY C PH A PH B PH C
5/7/97 16:01:23.456 5/3/97 10:01:23.456
XX% XX% XX% x.xxx x.xxx x.xxx

<PREV vDET >PREV <M_REC vDET >M_REC

etc.

4.1.1.1
...\M_REC\DETAILS 4.4.1 4.4.2 4.4.3
87TABC 150Q-CT2 \REPRT\DMD\TODAY \REPRT\DMD\YEST \REPRT\DMD\RESET
50ABC-CT1 51ABC-CT2
50N-CT1 51N-CT2 etc. PEAK DEMAND TODAY PEAK DEMAND YESTERDAY PEAK DEMAND SINCE RST
50Q-CT1 51Q-CT2
150ABC-CT2
150N-CT2
<RESET vI_ABC >YEST <TODAY vI_ABC >RESET <YEST vI_ABC >TODAY
>MORE

etc etc.
4.4.1.1 4.4.1.2
...\DMD\TODAY\I_ABC ...\DMD\TODAY\IN_IQ
IA xxx.xA 15:23 12/31 IN xxx.xA 15:23 12/31
IB xxx.xA 15:23 12/31 IQ xxx.xA 15:23 12/31
IC xxx.xA 15:23 12/31
<IN_IQ >IN_IQ <I_ABC >I_ABC
D2840-15.vsd
01-26-99

Figure 10-8. BE1-CDS Menu Tree (Reports Branch)

BE1-CDS HMI 10-11


5
\PROT
To/From
To/From
PROTECTION GENERAL
REPORTS FEEDER 2 SETTINGS
<REPRT vSG0 >SETUP

5.1 5.2 5.3 5.4 5.5


\PROT\SG0 \PROT\SG1 \PROT\SG2 \PROT\SG3 \PROT\GLOBAL

SETTING SETTING SETTING SETTING GLOBAL


GROUP 0 GROUP 1 GROUP 2 GROUP 3 SETTINGS
<GLOB v87 >SG1 <SG0 v87 >SG2 <SG1 v87 >SG3 <SG2 v87 >GLOB <SG3 vBF >SG0

etc etc etc

5.5.1
\PROT\GLOB\BF
MODE X

TIME DELAY xxxxx

5.1.1 5.1.2 5.1.3 5.1.4 5.1.5


\PROT\SG0\87 \ P R O T \ S G 0\8 7 N D \PROT\SG0\50T \PROT\SG0\51 \PROT\SG0\62

DIFFERENTIAL NEUTRAL INSTANTANEOUS IN V E R S E T I M E LOGIC TIMERS


DIFFERENTIAL OVERCURRENT OVERCURRENT
<62 v87 >87ND <50T v51 >62 <51 vSTGS >87
<87 v87ND >50T <87ND v50T >51

5.1.2.1 5.1.5.1
\PROT\SG0\87ND\87ND
\PROT\SG0\62\SETTINGS
MIN PICKUP = 0.45
SLOPE = 30 62 TIMER 162 TIMER
TIME DELAY = 450m MODE x MODE x
MODE =1
TAP N = 2.00 TD1 xxxx.xxx xxxx.xxx
TAP G = 3.47 TD2 xxxx.xxx xxxx.xxx

5.1.4.1 5.1.4.2 5.1.4.3


\PROT\SG0\51\51 \PROT\SG0\51\151 \PROT\SG0\51\251
MODE PU TD CRV MODE PU TD CRV MODE PU TD CRV
51P 1 10.3 9.99 B1R 151P 2 10.3 9.99 B1R 251P 0 10.3 9.99 B1R
51N G 1.0 0.20 B5 151N 2 1.0 0.21 B5 251N G 1.0 0.21 B5
51Q 0 xx.x x.xx C4R 151Q 2 xx.x x.xx C4R 251Q 1 xx.x x.xx C4R

<151 >151 <51 >251 <151 >51

5.1.3.1 5.1.3.2 5.1.3.3


\PROT\SG0\50T\50T \PROT\SG0\50T\150T \PROT\SG0\50T\250T
MODE PU TDELAY MODE PU TDELAY MODE PU TDELAY
50TP 0 12.3 15 MS 150TP 0 115 15 S 250TP 0 115 15 S
50TN G 1.0 0.2 S 150TN 2 1.0 0.2 S 250TN 2 1.0 0.2 S
50TQ 2 xxx xxx MS 150TQ 1 xxx xxx S 250TQ 1 xxx xxx S

<150T >150T < 50T >250T <150T >50T

5.1.1.1 5.1.1.2 5.1.1.3


\PROT\SG0\87\87 \PROT\SG0\87\MVA \PROT\SG0\87\TAP
MIN 35% X TAP MVA = 0.0
SLOPE 15% TAP1=xxxx KV1=xxxx MVA = 0 (MANUAL)
87 URO 6x to 21x TAP TAP2=xxxx KV2=xxxx
2ND HARMONIC INH= 12% NOTE: ENTER CT INFO TAP1=xxxx
5TH HARMONIC INH= 35% BEFORE TAP CALC TAP2=xxxx
2ND HARM SHARE = ON
<TAP >MVA <87 >TAP <MVA >87 D2840-16.vsd
02-04-99

Figure 10-9. BE1-CDS Menu Tree (Protection Branch)

10-12 HMI BE1-CDS


6
\SETUP
To/From
General
To/From REPORT
Settings
PROTECTION STATUS
<PROT vCOM >STAT

6.6 6.7 To/


To/ \SETUP\TRANSFORMER \SETUP\AUX_STGS From
From 6.1
6.5 T R A N S F O R M E R M O N I T O R GROUP CONTROL SETUP
AND ALARM SETUP
MODE X
<BKR vMON >AUX SGC ON TIME XX SEC
<XFRMR vSG1 >COM

6.6.1 6.6.2 6.7.1


\SETUP\XFRMR\DUTY SETUP\XFORM\ALARM \SETUP\AUX\SG1
TRANSFORMER MONITOR XFORMER ALARM SETUP AUTOMATIC MODE SETUP
MODE X MODE ALARM LIMIT SETTING GROUP 1 etc.
MAXIMUM DUTY XFRM1 X 20 TRACKED ELEMENT XXXXX
X.XXXe+XX XFRM2 X 50 SWITCH RETURN
CT CIRCUIT X XFRM3 X 8C TIME LEVEL TIME LEVEL
<ALARM >ALARM <DUTY >DUTY XX M XX% XX M XX%
<SG3 >SG2

To/ 6.1 6.2 6.3 6.4 6.5 To/


\SETUP\COM \SETUP\LCD \SETUP\PWR_SYST \SETUP\DEMAND \SETUP\BREAKER
From From
6.7 COMMUNICATIONS STGS LCD CONTRAST POWER SYSTEM CURRENT DEMAND BREAKER MONITOR 6.6
xx SETTINGS AND ALARM SETUP AND ALARM SETUP
<AUX vCOM0 >LCD <COM >PWR_S <LCD vCONN >DMD <PWR_S vDET >BKR <DMD vDUTY >XFRMR

6.4.1 6.4.2
\SETUP\DMD\DETAILS \SETUP\DMD\ALARMS
PHASE NEU Q
INTERVAL XX XX XX PHASE NEU Q
CT CIRCUIT X X X ALARM X X X
<DET >DET

6.3.1 6.3.2 6.3.3


\SETUP\PWR_S\CONN \SETUP\PWR_S\FREQ \SETUP\PWR_S\P_SEQ

CT CONNECTIONS SYSTEM FREQUENCY PHASE SEQUENCE


60 HZ ABC
<P_SEQ vCTP >FREQ <CONN >P_SEQ <FREQ >CONN

6.3.1.1 6.3.1.2
...\PWR_S\CONN\CTP ...\PWR_S\CONN\CTG
PHASE CONNECTIONS GROUND CONNECTIONS
CTR CTC TXC GND CTR
CT1 xxxxx xxx xxx x CTG xxxxx
CT2 xxxxx xxx xxx x

<CTG >CTG <CTP >CTP

6.5.1 6.5.2
\SETUP\BKR\DUTY \SETUP\BKR\ALARM
6.1.2 6.1.3 CONTACT DUTY OPER BREAKER ALARM STGS
MODE X MODE ALARM LIMIT
\SETUP\COM\COM0 \SETUP\COM\COM1 \SETUP\COM\COM2
MAXIMUM DUTY BKR1 2 20
X.XXXe+XX PRI AMPS BKR2 1 50
FRONT PANEL 232 REAR PANEL 232 REAR PANEL 485
CT CIRCUIT X BKR3 3 8C
PROTOCOL MODBUS
<ALARM >ALARM <DUTY >DUTY
BAUD RATE 9600 BAUD RATE 9600 BAUD RATE 9600
ADDRESS ADDRESS
<COM2 >COM1 <COM0 >COM2 <COM1 >COM0
D2840-17.vsd
07-07-99

Figure 10-10. BE1-CDS Menu Tree (General Settings Branch)

BE1-CDS HMI 10-13


SECTION 11 • ASCII COMMAND INTERFACE
TABLE OF CONTENTS

ASCII COMMAND INTERFACE ............................................................................................................ 11-1


GENERAL ............................................................................................................................................ 11-1
SERIAL PORT SETTINGS AND CONNECTIONS .............................................................................. 11-1
RS-485 ............................................................................................................................................. 11-1
RS-232 Ports .................................................................................................................................... 11-1
IRIG Input ......................................................................................................................................... 11-1
USING ASCII COMMANDS ................................................................................................................. 11-1
Command Structure ......................................................................................................................... 11-1
Using the ASCII Command Interface ............................................................................................... 11-2
Human to Machine ASCII Command Operations ......................................................................................... 11-2
Command Text File Operations.................................................................................................................... 11-3
Embedding Comments into ASCII Text Files ............................................................................................... 11-3
Miscellaneous Command Descriptions ............................................................................................ 11-3
Obtaining Help Information Through The Serial Port ................................................................................... 11-3
Changing Settings ........................................................................................................................................ 11-3
CHANGES SAVED Confirmation that changes were saved ............................................................ 11-4
Reading All Settings ..................................................................................................................................... 11-4
Reading Specific Groups of Settings............................................................................................................ 11-5
Reading Logic Settings ................................................................................................................................ 11-7
COMMAND SUMMARY....................................................................................................................... 11-8
Miscellaneous Commands ............................................................................................................... 11-8
Metering Commands ........................................................................................................................ 11-8
Control Commands .......................................................................................................................... 11-9
Report Commands ........................................................................................................................... 11-9
Setting Command........................................................................................................................... 11-13
Alarm Setting Commands............................................................................................................... 11-13
Breaker Monitoring And Setting Commands .................................................................................. 11-14
General Setting Commands ........................................................................................................... 11-14
Programmable Logic Setting Commands....................................................................................... 11-15
User Programmable Name Setting Command............................................................................... 11-17
Protection Setting Commands........................................................................................................ 11-17
Global Commands.......................................................................................................................... 11-18

BE1-CDS ASCII Command Interface i


SECTION 11 • ASCII COMMAND INTERFACE

GENERAL
Relay and power system information can be retrieved from a remote location using the ASCII command
interface. The ASCII command interface is also used to enter settings, retrieve reports and metering
information, and perform control operations. A communication port on the relay front panel provides a
temporary, local interface for communication. Communication ports on the rear panel provide a
permanent communication interface.
Front and rear panel communication ports can be connected to computers, terminals, serial printers,
modems, and intermediate communication/control interfaces such as RS-232 serial multiplexors. BE1-
CDS communication protocols support ASCII and binary data transmissions. ASCII data is used to send
and receive human readable data and commands. Binary data is used for computer communication and
transmission of raw oscillographic fault data if available.
Modbus™ and other common protocols are also available. Available communication protocol instruction
manuals include 9 3139 00 991 for Modbus™ and 9 3139 00 992 for DNP. For information about other
protocols, consult your Basler Electric Representative.

SERIAL PORT SETTINGS AND CONNECTIONS


Communication connections consist of two Data Communication Equipment (DCE) RS-232 ports, one RS-
485 port, and an IRIG port. BE1-CDS communication protocol is compatible with readily available
modem/terminal software. If required, password protection provides security against unauthorized
operation. Detailed information about making communication connections is provided in Section 12,
Installation. Communication port setup and security settings are covered in Section 9, Security.

RS-485
RS-485 terminal block connections are located on the rear panel and designated COM2. This port
supports half-duplex, multi-drop operation. Multi-drop (polled mode) operation is possible if a polling
address is programmed for the port.

RS-232 Ports
Two female RS-232 (DB-9) connectors are provided. One port is located on the front panel and is
designated COM0. Another port is located on the rear panel and is designated COM1. Both ports support
full-duplex operation. Polled operation is possible at the rear port using a simple RS-232 splitter if a
polling address is programmed for COM1.

IRIG Input
Connections at the rear panel accept a demodulated IRIG signal and provide the capability to time
synchronize the BE1-CDS internal clock to within one millisecond of the IRIG source.

USING ASCII COMMANDS


A computer terminal or PC running terminal emulation software can be used at any of the three serial
ports to send commands to the relay. Simple ASCII command language is used to communicate with the
relay. When the relay receives a command, it responds with the appropriate action. ASCII commands
can be used in human to machine interactions and in batch download type operations.

Command Structure
An ASCII command consists of a string made up of one or two letters followed by a hyphen and an object
name.

BE1-CDS ASCII Command Interface 11-1


xy-object name
Where:
x Specifies the general command function.
y Specifies the command subgroup.
object name Defines the specific object to which the command refers.
Examples of object names include 51N (neutral inverse time overcurrent function) and PIA (phase-A peak
current demand register). A command string entered by itself is a read command. A command string
followed by an = sign and one or more parameters is a write command.
General command functions are organized into five major groups plus one group of miscellaneous
commands.
Control (C): Control commands perform select-before-operate control actions such as circuit breaker
tripping and closing and active setting group changes. Subgroups include Select (S) and
Operate (O).
Global (G): One Global command performs operations that don’t fall into the other general groups.
The command for reading and changing passwords (GS-PW) is the only global command
available.
Metering (M): Commands in this group report all real-time metering values. No subgroup is used with
metering commands.
Reports (R): Reports commands read and reset reporting functions such as time and date, demand
registers, and breaker duty statistics. Subgroups include Alarms (A), Breaker Monitoring
(B), Demand Recording (D), Fault Summary Reporting (F), General Information (G),
Sequence of Events Recorder (S), and Oscillography (O).
Settings (S): This group contains all of the setting parameters that govern relay function. Subgroups
include Setting Groups 0, 1, 2, and 3 (0, 1, 2, 3), Protection Settings (P) not in setting
groups, Alarm Settings (A), Breaker Monitor Settings (B), General Settings (G), and Logic
Settings (L).
Miscellaneous: Miscellaneous commands include Access, Exit, and Help. Note that only the first letter of
these commands must be entered; entering the full command name is optional.

Using the ASCII Command Interface

Human to Machine ASCII Command Operations


Using ASCII commands, settings can be read and changed on a function by function basis. The
mnemonic format of the commands helps you interact with the relay. It isn’t necessary to remember all of
the object names. Most commands don’t require that you specify a complete object name. If the first two
letters of a command are entered, the relay will respond with all applicable object names.
Example 1: Obtain a breaker operations count by entering RB (Report Breaker). The BE1-CDS
responds with the operations counter value along with all other breaker report objects. If
you know that the object name for the breaker operations counter is OPCNTR, you can
enter RB-OPCNTR and read only the number of breaker operations.
Partial object names are also supported. This allows multiple objects to be read or reset at the same time.
Example 2: Read all peak-since-reset demand registers. Entering RD-PI (Report Demand - Peak
Current (I)) will return demand values and time stamps for phase A, B, C, Neutral, and
Negative Sequence current. To read only the Neutral demand value, the full object name
(RD-PIN) is entered. Entering RD-PI=0 resets all five of the peak-since-reset demand
registers.

11-2 ASCII Command Interface BE1-CDS


Command Text File Operations
In command text file operations, an ASCII text file of commands is created and sent to the relay. For
example, the S command is used to retrieve a complete list of settings from the relay in ASCII command
format. This list of commands is captured, saved to a file, edited with any ASCII text editor, and then
uploaded to the relay. Because the number of relay settings is so large, loading settings with a text file is
the preferred method of setting the BE1-CDS.

Embedding Comments into ASCII Text Files


Adding comments to ASCII settings files is an easy way to organize and label your settings. A comment
line is started with two forward slashes (//) followed by the comment text. When the relay encounters // in
a text file, it ignores all following characters until the next carriage return or linefeed character.
Example 1: An example of using comments in a settings file is shown below.
//Group0 is used during normal operation
S0-50TP=7.50,0m;S0-50TN=2.5,0m . . .
//Group1 is used during cold load pickup
S1-50TP=0,0m; S1-50TN=0,0m; S1-50TQ=0,0m

Miscellaneous Command Descriptions

Obtaining Help Information Through The Serial Port


The HELP (H) command provides general information on command syntax and functionality when the
manual is not available. Entering HELP or H provides information about using the HELP command.
HELP1 or H1 returns a complete list of relay commands. Entering HELP <cmd>, where <cmd> is a
specific command, returns information about the use and format of the command along with an example of
how the command is used.

HELP Command
Purpose: Obtain help with command information.
Syntax: HELP[x/<cmd>]

Changing Settings
Access Command. Before making settings changes through a communication port, the ACCESS (A)
command must be used to obtain programming access. Enter ACCESS=<password> to obtain access to
change settings associated with the password. Different passwords give the ability or access to perform
different operations. The relay will deny access if an invalid password is entered or if another user has
already been granted programming access through another serial port or at the front panel. Only one user
can have access at any one time.
Even if password protection is not used, it is still necessary to obtain access so that accidental changes
are prevented. If password protection is disabled, then ACCESS= will be accepted in place of a
password. The relay will respond with ACCESS GRANTED: GLOBAL if the command entered was
received and executed. The relay will respond with an error message and a ? if the command could not
be executed.
The ACCESS (A) command and the EXIT (E) command are used to change relay settings, reset report
registers, and enable control commands through a serial port. These commands prevent changes from
being made concurrently from two areas. For example, a user cannot make changes through COM0 at
the same time a remote user is making changes through COM2.

ACCESS Command
Purpose: Reads or sets access level in order to change settings.
Syntax: ACCESS[=<password>]
Comments: The ACCESS command must be used before any changes to settings can be made.
Available ACCESS privileges are summarized in the following paragraphs.

BE1-CDS ASCII Command Interface 11-3


READ-ONLY. This is the default access privilege when no passwords are active. Read-only access
allows you to read settings and reports but not make settings changes.
PRIVILEGE G: GLOBAL ACCESS. Global access is obtained by password G (PWG). Global access
permits entry of any command with no restrictions.
PRIVILEGE S: SETTING ACCESS. Setting access is obtained by password S (PWS). Setting access
allows changes to any settings.
PRIVILEGE C: CONTROL ACCESS. Control access is obtained by password C (PWC). Control access
enables relay control operations.
PRIVILEGE R: REPORT ACCESS. Report access is obtained by password R (PWR). Report access
enables report operations to be performed.
An access privilege is obtained only when the appropriate password is entered. When a valid password is
entered, the relay responds with the access privilege provided by the password entered. If an invalid
password is entered, an error message is returned. If password protection is disabled in one or more
privileges, then entering any string will provide access to the unprotected privileges.

Example 1: A valid password is entered.


ACCESS=OPENUP
ACCESS GRANTED: GLOBAL

Example 2: An invalid password is entered.


ACCESS= POENUP
ACCESS DENIED

Example 3: The current access privilege is read.


ACCESS
ACCESS: GLOBAL
Exit Command. After changes are made, the new data is saved or discarded using the EXIT command.
Prior to saving or discarding any changes, you must confirm that you wish to exit the programming mode.
There are three exit options: Y (Yes), N (No), or C (Continue).

EXIT Command
Purpose: Exit the programming mode.
Syntax: EXIT (Note: Relay will prompt for verification.)
Comments: It’s important to make all programming changes before executing the EXIT command. This
prevents a partial or incomplete protection scheme from being implemented.
When access privileges are obtained, all programming changes are made to a temporary, scratchpad
copy of relay settings. These changes aren’t saved to nonvolatile memory and initiated until the EXIT
command is invoked and confirmed. After the EXIT command is entered, the relay prompts to confirm
that the new data should be saved. Three options, Y, N, or C, or available. Entering Y will save the data.
If N is entered, the relay will clear the changes and resume operating with the old settings. Entering C will
abort the EXIT command and allow programming to continue.
Example 1: Release programming privileges and save settings changes.
EXIT<CR>
SAVE CHANGES (Y/N/C)? Prompt to save Yes, No, or Continue
Y<CR> Confirmation to save changes
CHANGES SAVED Confirmation that changes were saved

Reading All Settings


All user programmable settings can be listed using the S command. This read-only command is useful for
documenting relay status during installation. The settings retrieved by the S command can be saved to a
11-4 ASCII Command Interface BE1-CDS
standard text file and sent to another relay to be configured with the same settings. This type of settings
transfer takes less than one minute.

S Command
Purpose: Read all relay setting parameters.
Syntax: S
The S command returns the values of relay setting parameters in the same form that they are
programmed. It can be used at the end of a programming session to make a record of the relay settings.
If saved in a file, the report can be sent to another BE1-CDS that will use the same settings. Because the
report that is created is a set of commands, sending the report to a different relay re-programs that relay
with the settings contained in the S report.

Reading Specific Groups of Settings


While the S command is useful for reading all relay settings, several commands are available to read
specific groups of settings.

SA Command
Purpose: Read all alarm settings for Major and Minor alarms.
Syntax: SA
Example. Read all alarm settings.
SA
SA-DIFF=67
SA-BKR1=0,0; SA-BKR2=0,0; SA-BKR3=0,0
SA-DIP=0.00; SA-DIN=0.00; SA-DIQ=0.00
SA-LGC=0
SA-MAJ=3/28
SA-MIN=4
SA-RESET=0
SA-TX1=0,0; SA-TX2=0,0; SA-TX3=0,0

SB Command
Purpose: Read all breaker settings.
Syntax: SB
Example. Read all breaker settings.
SB
SB-DUTY=0,0.000e+00,2,0
SB-LOGIC=0,BREAKER_LABEL

SG Command
Purpose: Read all general settings.
Syntax: SG
Example. Obtain a report of all general settings.
SG
SG-FREQ=60
SG-PHROT=ABC
SG-CT1=1,WYE,NA,0
SG-CT2=1,WYE,NA,0
SG-CTG=1
SG-IN1= 4, 16; SG-IN2= 4, 16; SG-IN3= 4, 16; SG-
IN4= 4, 16
SG-IN5= 4, 16; SG-IN6= 4, 16; SG-IN7= 4, 16; SG-
IN8= 4, 16
SG-HOLDA=0; SG-HOLD1=1; SG-HOLD2=1; SG-
HOLD3=1
SG-HOLD4=1; SG-HOLD5=1; SG-HOLD6=0

BE1-CDS ASCII Command Interface 11-5


SG-SGCON= 5
SG-DIP=15,T,2; SG-DIN= 1,T,2; SG-DIQ= 1,T,2
SG-LOG=15
SG-
TARG=BF/62/162/250TP/250TN/250TQ/150TP/150TN/150TQ/50TP/50TN/50TQ/
87U/87R/87N
D/251P/251N/251Q/151P/151N/151Q/51P/51N/51Q,0
SG-TRIGGER=BFT+VO11,VO12+BFPU,2NDHAR+5THHAR
SG-ID1=BE1-CDS
SG-ID2=SUBSTATION_1
SG-ID3=USER1_ID
SG-ID4=USER2_ID
SG-CLK=M,24,0
SG-SCREEN1=1.4.6; SG-SCREEN2=3.1.1; SG-SCREEN3=3.1.1.1; SG-
SCREEN4=3.1.1.2
SG-SCREEN5=3.1.2; SG-SCREEN6=3.1.2.1; SG-SCREEN7=3.1.2.2; SG-
SCREEN8=0
SG-SCREEN9=0; SG-SCREEN10=0; SG-SCREEN11=0; SG-
SCREEN12=0
SG-SCREEN13=0; SG-SCREEN14=0; SG-SCREEN15=0; SG-
SCREEN16=0
SG-COM0=9600,A0,P0,R1,X1; SG-COM1=9600,A0,P0,R1,X1
SG-COM2=9600,A0,P0,R1,X0
SG-OSC=16

SN Command
Purpose: Read/Set user programmable names.
Syntax: SN[-<var>[=<name>,<TRUE label>,<FALSE label>]
Example. Read the programmed labels for the alarm output (OUTA).
SN-VOA
SN-VOA=VOA_LBL,TRUE,FALSE

S<g> Command
Purpose: Read all protection settings.
Syntax: S<g>
Example Obtain a list of settings for setting group 2.
S2
S2-TAP87=MANUAL,2.00,2.00
S2-87=0.00,45,18.0,35.0, 0,1
S2-87ND=0.00,20,500m
S2-50TP=0.00, 0m; S2-50TN=0.00, 0m; S2-50TQ=0.00, 0m
S2-150TP=0.00, 0m; S2-150TN=0.00, 0m; S2-150TQ=0.00, 0m
S2-250TP=0.00, 0m; S2-250TN=0.00, 0m; S2-250TQ=0.00, 0m
S2-51P=0.00,0.0,V2; S2-51N=0.00,0.0,V2; S2-51Q=0.00,0.0,V2
S2-151P=0.00,0.0,V2;S2-151N=0.00,0.0,V2;S2-151Q=0.00,0.0,V2
S2-251P=0.00,0.0,V2;S2-251N=0.00,0.0,V2;S2-251Q=0.00,0.0,V2
S2-62= 0m, 0m
S2-162= 0m, 0m
SP-BF= 0m
SP-CURVE= 0.2663, 0.0339, 1.0000, 1.2969, 0.5000
SP-GROUP1= 0, 0, 0, 0,51P; SP-GROUP2= 0, 0, 0,
0,51P
SP-GROUP3= 0, 0, 0, 0,51P

11-6 ASCII Command Interface BE1-CDS


Reading Logic Settings
The SL command is used to view the names of available logic schemes in memory. It also will return all of
the logic equations for a specific logic scheme.

SL Command
Purpose: Obtain setting logic information.
Syntax: SL[:<name>]
Comments: No password access is required to read settings.
Entering SL by itself returns all of the logic equations associated with the active logic scheme. Entering
SL: returns the names of all available logic schemes. Entering SL:<name> returns all logic equations and
settings for the named logic scheme.
Example 1: Read the logic schemes available in memory.
SL:
USER, BASIC-87, BASIC-TX, TX-W-CTL, TX-W-BU, BUS-W-BU, MOTOR, NONE
Example 2: Read all logic settings associated with the BASIC-87 logic scheme.
SL:BASIC-87
SL-N:BASIC-87
SL-87:1,0
SL-87ND:0,0
SL-50TP:0,0; SL-50TN:0,0; SL-50TQ:0,0
SL-150TP:0,0; SL-150TN:0,0; SL-150TQ:0,0
SL-250TP:0,0; SL-250TN:0,0; SL-250TQ:0,0
SL-51P:1,0; SL-51N:1,0; SL-51Q:1,0
SL-151P:0,0; SL-151N:0,0; SL-151Q:0,0
SL-251P:0,0; SL-251N:0,0; SL-251Q:0,0
SL-62:0,0,0
SL-162:0,0,0
SL-BF:0,0,0
SL-GROUP:1,0,0,0,0,/0
SL-43:0
SL-143:0
SL-243:0
SL-343:0
SL-443:0
SL-543:0
SL-643:0
SL-743:0
SL-101:0
SL-CKTMON:0,0,0
SL-VOA:0
SL-VO1:87RT+87UT
SL-VO2:87RT+87UT
SL-VO3:87RT+87UT
SL-VO4:51PT+51NT+51QT
SL-VO5:0
SL-VO6:ALMMAJ
SL-VO7:0
SL-VO8:0
SL-VO9:0
SL-VO10:0
SL-VO11:51PT+51NT+51QT+87RT+87UT
SL-VO12:87UT+51PPU+51NPU+51QPU+87RPU
SL-VO13:IN6
SL-VO14:IN7

BE1-CDS ASCII Command Interface 11-7


SL-VO15:IN8

COMMAND SUMMARY

Miscellaneous Commands

ACCESS Command
Purpose: Read/Set access level in order to change settings.
Syntax: ACCESS[=<password>].
Reference: Section 11, ASCII Command Interface, Using ASCII Commands, Miscellaneous Command
Descriptions

EXIT Command
Purpose: Exit programming mode.
Syntax: EXIT Note: Relay will prompt for verification.
Reference: Section 11, ASCII Command Interface, Using ASCII Commands, Miscellaneous Command
Descriptions

HELP Command
Purpose: Obtain help with command operation.
Syntax: HELP <cmd> or H <cmd> gives help with a command; H1 gives command list.
Reference: Section 11, ASCII Command Interface, Using ASCII Commands, Miscellaneous Command
Descriptions

Metering Commands

M Command
Purpose: Read all metered values.
Syntax: M.
Reference: Section 5, Metering, Metering Command Descriptions

M-FREQ Command
Purpose: Read metered frequency.
Syntax: M-FREQ.
Reference: Section 5, Metering, Metering Command Descriptions

M-I Command
Purpose: Read metered current in primary unit.
Syntax: M-I[<phase>].
Reference: Section 5, Metering, Metering Command Descriptions

M1 Command
Purpose: Read CT circuit #1 current primary or secondary units.
Syntax: M1[-I[p][y]] where p = A/B/C/N/Q, y=P for primary, S for secondary.
Reference: Section 5, Metering, Metering Command Descriptions

M2 Command
Purpose: Read CT circuit #2 current primary or secondary units.
Syntax: M1[-I[p][y]] where p = A/B/C/N/Q, y=P for primary, S for secondary.
Reference: Section 5, Metering, Metering Command Descriptions

MD Command
Purpose: Read differential currents (compensated currents, Iop and Harmonics).
Syntax: MD[,P/,S] where P=primary, S=secondary.
Reference: Section 5, Metering, Metering Command Descriptions

11-8 ASCII Command Interface BE1-CDS


MD-2ND Command
Purpose: Read 2nd harmonics as a percentage of Iop.
Syntax: MD-[Ip]2ND where p = A/B/C.
Reference: Section 5, Metering, Metering Command Descriptions

MD-5TH Command
Purpose: Read 5TH harmonics as a percentage of Iop.
Syntax: MD-[Ip]5TH where p = A/B/C.
Reference: Section 5, Metering, Metering Command Descriptions

MD-I Command
Purpose: Read differential currents (compensated currents and Iop).
Syntax: MD-I[p[,P/,S]] where [p] = A/B/C/G/N, [P] = Primary / [S] = Secondary
Reference: Section 5, Metering, Metering Command Descriptions

Control Commands

CO Command
Purpose: Control operation.
Syntax: CO-<control>[=<mode>].
Reference: Section 3, Input And Output Functions, Outputs (CO-OUT)
Section 4, Protection And Control, Setting Groups (CO-GROUP)
Section 4, Protection And Control, Virtual Switches (CO-43)
Section 4, Protection And Control, Virtual Switches (CO-101)

CS Command
Purpose: Control selection.
Syntax: CS-<control>[=<mode>].
Reference: Section 3, Input And Output Functions, Outputs (CO-OUT)
Section 4, Protection And Control, Setting Groups (CO-GROUP)
Section 4, Protection And Control, Virtual Switches (CO-43)
Section 4, Protection And Control, Virtual Switches (CO-101)

Report Commands

RA Command
Purpose: Report/Reset alarm information.
Syntax: RA[=0].
Reference: Section 6, Reporting And Alarm Functions, Alarms Function

RA-DIFF Command
Purpose: Read/Trigger Differential Report Data.
Syntax: RA-DIFF[=TRIG] where TRIG triggers a Differential Report.
Reference: Section 6, Reporting And Alarm Functions, Differential Current Monitoring Function

RA-LGC Command
Purpose: Report/Reset logic alarm information.
Syntax: RA-LGC[=0].
Reference: Section 6, Reporting And Alarm Functions, Alarms Function

RA-MAJ Command
Purpose: Report/Reset major alarm information.
Syntax: RA-MAJ[=0].
Reference: Section 6, Reporting And Alarm Functions, Alarms Function

BE1-CDS ASCII Command Interface 11-9


RA-MIN Command
Purpose: Report/Reset minor alarm information.
Syntax: RA-MIN[=0].
Reference: Section 6, Reporting And Alarm Functions, Alarms Function

RA-REL Command
Purpose: Report/Reset relay alarm information.
Syntax: RA-REL[=0].
Reference: Section 6, Reporting And Alarm Functions, Alarms Function

RA-SER Command
Purpose: Report Relay Alarm Sequence of Events information.
Syntax: RA-SER[=0].
Reference: Section 6, Reporting And Alarm Functions, SER Function

RB Command
Purpose: Read breaker status.
Syntax: RB.
Reference: Section 6, Reporting And Alarm Functions, Breaker Monitoring

RB-DUTY Command
Purpose: Read/Set breaker contact duty log.
Syntax: RB-DUTY[<phase>[=%duty>]].
Reference: Section 6, Reporting And Alarm Functions, Breaker Monitoring

RB-OPCNTR Command
Purpose: Read/Set breaker operation counter.
Syntax: RB-OPCNTR[=<#operations>].
Reference: Section 6, Reporting And Alarm Functions, Breaker Monitoring

RD Command
Purpose: Report all demand data.
Syntax: RD.
Reference: Section 6, Reporting And Alarm Functions, Demand Functions

RD-LOG Command
Purpose: Report load profile data.
Syntax: RD-LOG,<n>.
Reference: Section 6, Reporting And Alarm Functions, Demand Functions

RD-PI Command
Purpose: Read/Reset peak demand current.
Syntax: RD-PI[<p>[=0]].
Reference: Section 6, Reporting And Alarm Functions, Demand Functions

RD-TI Command
Purpose: Report today’s demand current.
Syntax: RD-TI[<p>].
Reference: Section 6, Reporting And Alarm Functions, Demand Functions

RD-YI Command
Purpose: Report yesterday’s demand current.
Syntax: RD-YI[<p>].
Reference: Section 6, Reporting And Alarm Functions, Demand Functions

11-10 ASCII Command Interface BE1-CDS


RF Command
Purpose: Read/Reset fault report data.
Syntax: RF[-n/NEW][=0/TRIG].
Reference: Section 6, Reporting And Alarm Functions, Demand Functions

RG Command
Purpose: Report general information.
Syntax: RG.
Comments: Section 6, Reporting And Alarm Functions, General Status Reporting

RG-101STAT Command
Purpose: Report 101 status.
Syntax: RG101STAT.
Comments: Section 6, Reporting And Alarm Functions, General Status Reporting

RG-43STAT Command
Purpose: Report 43 status.
Syntax: RG-43STAT.
Comments: Section 6, Reporting And Alarm Functions, General Status Reporting

RG-ADDR Command
Purpose: Report/Set COM1/COM2 Address for Polled Communications.
Syntax: RG-ADDR[n][={com addr}] where n = 1 for COM1 or 2 for COM2.
Comments: Section 6, Reporting And Alarm Functions, General Status Reporting

RG-BREAKER Command
Purpose: Report breaker status.
Syntax: RG-BREAKER.
Comments: Section 6, Reporting And Alarm Functions, General Status Reporting

RG-DATE Command
Purpose: Read/Set date.
Syntax: RG-DATE[=<M/D/Y>] or RG-DATE[=<D-M-Y>].
Comments: Section 6, Reporting And Alarm Functions, General Status Reporting

RG-GRPACTIVE Command
Purpose: Report active group.
Syntax: RG-GRPACTIVE.
Comments: Section 6, Reporting And Alarm Functions, General Status Reporting

RG-GRPCNTRL Command
Purpose: Report group control setting.
Syntax: RG- GRPCNTRL.
Comments: Section 6, Reporting And Alarm Functions, General Status Reporting

RG-INPUT Command
Purpose: Report input status.
Syntax: RG- INPUT.
Comments: Section 6, Reporting And Alarm Functions, General Status Reporting

RG-LOGIC Command
Purpose: Report active logic.
Syntax: RG- LOGIC.
Comments: Section 6, Reporting And Alarm Functions, General Status Reporting

BE1-CDS ASCII Command Interface 11-11


RG-OUTCNTRL Command
Purpose: Report output control status.
Syntax: RG- OUTCNTRL.
Comments: Section 6, Reporting And Alarm Functions, General Status Reporting

RG-OUTSTAT Command
Purpose: Report output status.
Syntax: RG- OUTSTAT.
Comments: Section 6, Reporting And Alarm Functions, General Status Reporting

RG-STAT Command
Purpose: Report relay status.
Syntax: RG-STAT.
Reference: Section 6, Reporting And Alarm Functions, General Status Reporting

RG-TARG Command
Purpose: Report/Reset target status.
Syntax: RG-TARG[=0].
Reference: Section 6, Reporting And Alarm Functions, General Status Reporting

RG-TIME Command
Purpose: Report/Set time.
Syntax: RG-TIME[=hr:mn:sc] or RG-TIME[=hr:mn<f>sc]].
Reference: Section 6, Reporting And Alarm Functions, General Status Reporting

RG-VER Command
Purpose: Read program version, model number, style number, and serial number.
Syntax: RG-VER.
Reference: Section 6, Reporting And Alarm Functions, General Status Reporting

RL Command
Purpose: Read Logic Variables (each Logic Variable is 32 bits long).
Syntax: RL-[n] where n = 1, 2 or 3.
Reference: Section 6, Reporting And Alarm Functions, General Status Reporting

RO Command
Purpose: Read oscillographic COMTRADE.DAT/.CFG fault report.
Syntax: RO-nA/B[#].CFG/DAT.
Reference: Section 6, Reporting And Alarm Functions, Fault Reporting

RS Command
Purpose: Read/Reset sequence of events record data.
Syntax: RS[-n/Fn/ALM/IO/LGC/NEW][=0].
Reference: Section 6, Reporting And Alarm Functions, SER Recorder

RT Command
Purpose: Read Transformer Duty Status.
Syntax: RT.
Reference: Section 6, Reporting And Alarm Functions, Transformer Monitoring

RT-DUTY Command
Purpose: Read/Set Transformer Through Fault Duty Log.
Syntax: T-DUTY[{phase}[={%duty}]] where %duty is % of dmax set with ST-DUTY.
Reference: Section 6, Reporting And Alarm Functions, Transformer Monitoring

11-12 ASCII Command Interface BE1-CDS


RT-TFCNTR Command
Purpose: Read Transformer Duty Status.
Syntax: RT.
Reference: Section 6, Reporting And Alarm Functions, Transformer Monitoring

Setting Command

S Command
Purpose: Read all relay setting parameters.
Syntax: S.
Comments: Section 11, ASCII Command Interface, Using ASCII Commands

Alarm Setting Commands

SA Command
Purpose: Read all major and minor alarm settings.
Syntax: SA.
Reference: Section 11, ASCII Command Interface, Using ASCII Commands

SA-BKR Command
Purpose: Read/Set breaker alarm settings.
Syntax: SA-BKR[n][=<mode>,<alarm limit>].
Reference: Section 6, Reporting And Alarms Function, Breaker Monitoring

SA-DI Command
Purpose: Read/Set demand alarm settings.
Syntax: SA-DI[p][=<alarm level>].
Reference: Section 6, Reporting And Alarms Function, Demand Functions

SA-LGC Command
Purpose: Read/Set logic alarm setting mask.
Syntax: SA-LGC[=<alarm num 1>[/<alarm num 2>] . . . [<alarm num n>]].
Reference: Section 6, Reporting And Alarms Function, Alarms Function

SA-MAJ Command
Purpose: Read/Set major alarm setting mask.
Syntax: SA-MAJ[=<alarm num 1>[/<alarm num 2>] . . . [<alarm num n>]].
Reference: Section 6, Reporting And Alarms Function, Alarms Function

SA-MIN Command
Purpose: Read/Set minor alarm setting mask.
Syntax: SA-MIN[=<alarm num 1>[/<alarm num 2>] . . . [<alarm num n>]].
Reference: Section 6, Reporting And Alarms Function, Alarms Function

SA-RESET Command
Purpose: Read/Set programmable alarms reset logic.
Syntax: SA-RESET[=<rst alm logic>].
Reference: Section 6, Reporting And Alarms Function, Alarms Function

SA-TX Command
Purpose: Read/Set transformer alarm settings.
Syntax: SA-TX[n][={mode},{alarm limit}] where mode=0-2(disabled/%duty/#thflts).
Reference: Section 6, Reporting And Alarm Functions, Transformer Monitoring

BE1-CDS ASCII Command Interface 11-13


Breaker Monitoring And Setting Commands

SB Command
Purpose: Read all breaker settings.
Syntax: SB.
Reference: Section 6, Reporting And Alarms Function, Breaker Monitoring

SB-DUTY Command
Purpose: Read/Set breaker contact duty.
Syntax: SB-DUTY[=<mode>,<DMAX>].
Reference: Section 6, Reporting And Alarms Function, Breaker Monitoring

SB-LOGIC Comman Section 6, Reporting and Alarms Function, Breaker Monitoring d


Purpose: Read/Set breaker contact logic.
Syntax: SB-LOGIC[=<breaker close logic>].
Reference: Section 6, Reporting And Alarms Function, Breaker Monitoring

General Setting Commands

SG Command
Purpose: Read all general settings.
Syntax: SG.
Reference: Section 11, ASCII Command Interface, Using ASCII Commands

SG-CLK Command
Purpose: Read/Program format of time and date display.
Syntax: SG-CLK[=<date format(M/D)>,<time format(12/24)>].
Reference: Section 6, Reporting And Alarms Function, Clock

SG-COM Command
Purpose: Read/Set serial communication protocol.
Syntax: SG-COM[#[=<baud>,A<addr>,P<pglen>,R<reply ack>,X<XON ena>]].
Reference: Section 9, User Interface And Security, User Interface
Section 11, ASCII Command Interface, Serial Port Settings And Connections

SG-CT Command
Purpose: Read/Set Phase/Neutral CT ratio.
Syntax: SG-CT[t][=<CTratio>].
Reference: Section 3, Input And Output Functions, Input Current

SG-DI Command
Purpose: Read/Set P(IA/IB/IC/var/watt), N and Q demand interval.
Syntax: SG-DI[p][=<interval>].
Reference: Section 6, Reporting And Alarms Function, Demand Functions

SG-FREQ Command
Purpose: Read/Enter power system frequency.
Syntax: SG-FREQ[=<freq(Hz)>].
Reference: Section 3, Input And Output Functions, Voltage Inputs

SG-HOLD Command
Purpose: Read/Program output hold operation.
Syntax: SG-HOLD[n][=<1/0 hold ena>].
Reference: Section 3, Input And Output Functions, Outputs

11-14 ASCII Command Interface BE1-CDS


SG-ID Command
Purpose: Read/Set relay ID and station ID used in reports.
Syntax: SG-ID[=<relayID(up to 10 char)>,<StationID(up to 30 char)>].
Reference: Section 3, Input And Output Functions, Relay Identifier Information

SG-IN Command
Purpose: Read/Set input recognition/debounce.
Syntax: SG-IN[#[=<r(ms)>,<db(ms)>]].
Reference: Section 3, Input And Output Functions, Contact Sensing Inputs

SG-LOG Command
Purpose: Read/Set load profile interval.
Syntax: SG-LOG[={interval}] where interval is between 1 and 60 minutes.
Reference: Section 6, Reporting And Alarms Function, Demand Functions

SG-PHROT Command
Purpose: Read/Set phase rotation setting.
Syntax: SG-PHROT[=<phase rotation>].
Reference: Section 3, Input And Output Functions, Voltage Inputs

SG-SCREEN Command
Purpose: Read/Set default screen(s).
Syntax: SG-SCREEN[n][=<default screen number>].
Reference: Section 4, Human-Machine Interface, Front Panel Display

SG-SGCON Command
Purpose: Read/Set SGC output on time.
Syntax: SGSGCON[=<time>].
Reference: Section 4, Protection And Control, Setting Groups

SG-TARG Command
Purpose: Report/Enable Target List and Reset Target Logic.
Syntax: SG-TARG[=<x/x/...x>,<rst TARG logic>].
Reference: Section 6, Reporting And Alarm Functions, Fault Reporting

SG-TRIGGER Command
Purpose: Read/Set trigger logic.
Syntax: SG-TRIGGER[n][=<TRIP trigger>,<PU trigger>,<LOGIC trigger>].
Reference: Section 6, Reporting And Alarm Functions, Fault Reporting

Programmable Logic Setting Commands

SL Command
Purpose: Obtain setting logic information.
Syntax: SL[:<name>].
Reference: Section 11, ASCII Command Interface, Using ASCII Commands

SL-101 Command
Purpose: Read/Set Logic for Virtual Breaker switch (101).
Syntax: SL-101[=mode] where mode=0/1 (disabled/enabled).
Reference: Section 4, Protection And Control Functions, 101 Virtual Breaker Control Switch

SL-x43 Command
Purpose: Read/Set Logic for Virtual switch (x43).
Syntax: SL-{x}43[=mode] where x = blank/1/2/3/4/5/6/7, mode=0/1/2/3.

BE1-CDS ASCII Command Interface 11-15


Reference: Section 4, Protection And Control Functions, Virtual Switches

SL-50T Command
Purpose: Read/Set logic for x50 function modules.
Syntax: SL-x50T[<p>[=<mode>,<BLK logic>]].
Reference: Section 4, Protection And Control, Overcurrent Protection

SL-51P And SL-51N Command


Purpose: Read/Set logic for 51 function modules.
Syntax: SL-x51[<p>[=<mode>,<BLK logic>]].
Reference: Section 4, Protection And Control, Overcurrent Protection

SL-51Q Command
Purpose: Read/Set logic for 51Q function modules.
Syntax: SL-51Q[=<mode>,<BLK logic>].
Reference: Section 4, Protection And Control, Overcurrent Protection

SL-62 Command
Purpose: Read/Set logic for 62 function modules.
Syntax: SL-<f>62[=<mode>,<INI logic>,<BLK logic>]
Reference: Section 4, Protection And Control, 62/162 General Purpose Logic Timers

SL-87 Command
Purpose: Read/Set Logic for the 87 Function.
Syntax: SL-87[={mode},{BLK logic}].
Reference: Section 4, Protection And Control, Differential Protection

SL-87ND Command
Purpose: Read/Set Logic for the 87ND Function.
Syntax: SL-87ND[={mode},{BLK logic}] where mode=0/1/2.
Reference: Section 4, Protection And Control, Differential Protection

SL-BF Command
Purpose: Read/Set logic for breaker failure function modules.
Syntax: SL-BF[<p>][=<mode>,<INI logic>,<BLK logic>]].
Reference: Section 4, Protection And Control, Breaker Failure Protection

SL-CKTMON Command
Purpose: Read/Set Circuit Monitor logic settings.
Syntax: SL-CKTMON[={mode}, {monitor},{status}].
Reference: Section 6, Reporting And Alarm Functions, Trip Circuit Monitor

SL-GROUP Command
Purpose: Read/Set logic for setting group module.
Syntax: SL-GROUP[=<mode>,<BLK logic>].
Reference: Section 4, Protection And Control, Setting Groups

SL-N Command
Purpose: Read, set, or copy the name of the custom logic.
Syntax: SL-N[=<name>].
Reference: Section 7, BESTlogic Programmable Logic, Logic Schemes

SL-VO Command
Purpose: Read/Set output logic.
Syntax: SL-VO[#[=<Boolean equation>]].

11-16 ASCII Command Interface BE1-CDS


Reference: Section 7, BESTlogic Programmable Logic, Working With Programmable Logic

User Programmable Name Setting Command

SN Command
Purpose: Read/Set user programmable names.
Syntax: SN[-<var>[=<name>,<TRUE label>,<FALSE label>].
Reference: Section 7, BESTlogic Programmable Logic, Logic Schemes

Protection Setting Commands

S<#> Command
Purpose: Read all protection settings.
Syntax: S<#>
Reference: Section 11, ASCII Command Interface, Using ASCII Commands

S<#>-50TP Command
Purpose: Read/Set 50TP pickup level and time delay.
Syntax: S<#>-50TP[=<pu(A)>,<td(m)>]
Reference: Section 4, Protection And Control, Overcurrent Protection

S<#>-50TN Command
Purpose: Read/Set 50TN pickup level and time delay.
Syntax: S<#>-<f>50TN[=<pu(A)>,<td(m)>]
Reference: Section 4, Protection And Control, Overcurrent Protection

S<#>-51P Command
Purpose: Read/Set 51 pickup level, time delay, and curve.
Syntax: S<#>-51P[=<pu(A)>,<td(m)>,<crv>]
Reference: Section 4, Protection And Control, Overcurrent Protection

S<#>-51N Command
Purpose: Read/Set 51N pickup level, time delay, and curve.
Syntax: S<#>-<f>51N[=<pu(A)>,<td(m)>,<crv>]
Reference: Section 4, Protection And Control, Overcurrent Protection

S<#>-62 Command
Purpose: Read/Set 62 time delay.
Syntax: S<#>-<f>62[=<t1>,<t2>]
Reference: Section 4, Protection And Control, 62/162 General Purpose Logic Timers

S<#>-87 Command
Purpose: Read/Set the 87 parameters.
Syntax: S{g}-87[=minpu,slope,2nd,5th,URO,2nd harmonic sharing (0=off,1=on)].
Reference: Section 4, Protection And Control, Differential Protection

S<#>-87ND Command
Purpose: Read/Set the 87ND parameters.
Syntax: S{g}-87ND[=minpu,slope,td].
Reference: Section 4, Protection And Control, Differential Protection

S<#>-TAP87 Command
Purpose: Read/Set the 87 TAP parameters.
Syntax: S{g}-TAP87[=mva,kv1/tap1,kv2/tap2].
Reference: Section 4, Protection And Control, Differential Protection

BE1-CDS ASCII Command Interface 11-17


SP-BF Command
Purpose: Read/Set the breaker failure timer setting.
Syntax: SP-BF[=<time>[m/s/c]].
Reference: Section 4, Protection And Control, Breaker Failure Protection

SP-CURVE Command
Purpose: Read/Set the user programmable 51 curve parameters.
Syntax: SP-CURVE[=<A>,<B>,<C>,<N>,<R>].
Reference: Section 4, Protection And Control, Overcurrent Protection

SP-GROUP Command
Purpose: Read/Program auxiliary setting group auto operation.
Syntax: SP-GROUP<#>=[<sw(min)>,<sw level%>,<reset(min)>,<ret level%>].
Reference: Section 4, Protection And Control, Setting Groups

ST-DUTY Command
Purpose: Read/Set Transformer Duty where mode = 0/1/2 (disable/I*t/I^2*t).
Syntax: ST-DUTY[={mode},{dmax},{ct ckt#},{BLKTXFMR logic}].
Reference: Section 6, Reporting And Alarm Functions, Transformer Duty Monitoring

Global Commands

GS-PW Command
Purpose: Read or change a password.
Syntax: GS-PW<t>[=<password>,<com ports(0/1/2)>]] where t=G/S/C/R.
Reference: Section 9, Security, Passwords

11-18 ASCII Command Interface BE1-CDS


SECTION 12 • INSTALLATION
TABLE OF CONTENTS

List Of Figures ........................................................................................................................................ i


List Of Tables..........................................................................................................................................ii
List Of Sidebars ......................................................................................................................................ii
SECTION 12 • INSTALLATION ............................................................................................................... 12-1
GENERAL ............................................................................................................................................ 12-1
MOUNTING .......................................................................................................................................... 12-1
CONNECTIONS ................................................................................................................................... 12-7
Terminal Blocks ................................................................................................................................ 12-7
Typical AC And DC Connections ...................................................................................................... 12-7
CT Polarity ........................................................................................................................................ 12-9
POWER SYSTEM APPLICATIONS ..................................................................................................... 12-9
CONTACT SENSING INPUT JUMPERS........................................................................................... 12-21
Nominal........................................................................................................................................... 12-21
COMMUNICATION CONNECTIONS................................................................................................. 12-22
RS-232 Connectors ........................................................................................................................ 12-22
RS-485 Connector .......................................................................................................................... 12-24
IRIG Connection ............................................................................................................................. 12-24
SETTINGS.......................................................................................................................................... 12-25
PREPARING THE RELAY FOR SERVICE ........................................................................................ 12-25

List Of Figures
Figure 12-1. BE1-CDS, MX Case, 19-Inch Rack Mount, Front View, Overall Dimensions..................... 12-2
Figure 12-2. BE1-CDS, MX Case, 19-Inch Rack Mount, Top View, Overall Dimensions....................... 12-2
Figure 12-3. BE1-CDS, MX Case, 19-Inch Rack Mount, Side View, Overall Dimensions ...................... 12-3
Figure 12-4. BE1-CDS, MX Case, Vertical Panel Mount, Top View, Overall Dimensions ...................... 12-3
Figure 12-5. BE1-CDS, MX Case, Vertical Panel Mount, Front View, Overall Dimensions.................... 12-4
Figure 12-6. BE1-CDS, MX Case, Vertical Panel Mount, Side View, Overall Dimensions ..................... 12-5
Figure 12-7. BE1-CDS, MX Case, Vertical Panel Mount, Panel Drilling Diagram .................................. 12-6
Figure 12-8. BE1-CDS, Rear View, Terminal Connections..................................................................... 12-7
Figure 12-9. Typical AC Connection Diagram......................................................................................... 12-8
Figure 12-10. Typical DC Connection Diagram ...................................................................................... 12-8
Figure 12-11. Standard CT Polarity ........................................................................................................ 12-9
Figure 12-12. CT Action .......................................................................................................................... 12-9
Figure 12-13. Example Of Reversed CT Polarity.................................................................................... 12-9
Figure 12-14. Typical Transformer Differential Connection .................................................................. 12-10
Figure 12-15. Typical Connection For Motor or Reactor Differential Protection ................................... 12-11
Figure 12-16. BE1-CDS220 Connected For Primary Protection With A BE1-951 Connected For
Independent Backup And Metering................................................................................................. 12-12
Figure 12-17. Differential Protection For Wye-Grounded-Delta Transformer With Ground Source Inside
The Protected Zone ........................................................................................................................ 12-14
Figure 12-18. Differential Protection Of Delta-Wye Grounded Transformer With Optional Independent
Ground Input Connected For Low Side Ground Fault Protection ................................................... 12-15
Figure 12-19. Differential Protection For High And Low Side Windings With Optional Independent Ground
Input Connected To Protect Unloaded Tertiary Winding ................................................................ 12-16
Figure 12-20. Differential Protection Of Delta-Wye Resistance Grounded Transformer With Optional
Independent Ground Input Connected For 87ND Protection.......................................................... 12-17
Figure 12-21. Depiction of BE1-CDS220 With Optional Independent Ground Input Connected For 87ND
Protection, Balanced, Normal Load flow, IR’s Cancel, And IOP = 0 ............................................ 12-18
Figure 12-22. BE1-CDS220 Connected For Low-Impedance Bus Differential Protection .................... 12-19

BE1-CDS Installation i
Figure 12-23. Large Generator Protection With BE1-CDS220 Connected For Primary Current Differential
Protection, And BE1-GPS100 Connected For Independent Backup Fault Protection, Detection Of
Abnormal situations, and Metering ................................................................................................. 12-20
Figure 12-24. BE1-CDS, Contact Sensing Input Jumpers .................................................................... 12-22
Figure 12-25. RFL 9060 Protective Relay Switch To BE1-CDS Cable ................................................. 12-23
Figure 12-26. Modem To BE1-CDS ...................................................................................................... 12-23
Figure 12-27. Personal Computer To BE1-CDS ................................................................................... 12-23
Figure 12-28. SEL-2020 Communications Processor To BE1-CDS ..................................................... 12-24
Figure 12-29. RS-485 DB-37 To BE1-CDS........................................................................................... 12-24

List Of Tables
Table 12-1. Contact Sensing Turn-On Voltage ..................................................................................... 12-21
Table 12-2. RS-232 Pinouts (COM 0 And COM 1) ............................................................................... 12-22
Table 12-3. RS-485 Pinouts (COM2) .................................................................................................... 12-24
Table 12-4. IRIG Pinouts....................................................................................................................... 12-25

List Of Sidebars
Sidebar 12-1. CT Polarity ........................................................................................................................ 12-9

ii Installation BE1-CDS
SECTION 12 • INSTALLATION
GENERAL
BE1-CDS Current Differential Systems are delivered with an Instruction Manual(s) and BESTCOMS
software in sturdy cartons to prevent shipping damages. Upon receipt of the unit, check the Model and
Style Number against the requisition and packaging list for agreement. Inspect for damage, and if there is
evidence of such, immediately file a claim with the carrier and notify the Basler Electric Regional Sales
Office, your Sales Representative or Sales Representative at Basler Electric, Highland, Illinois.
If the BE1-CDS is not installed immediately, store it in the original shipping package in a moisture and dust
free environment.

MOUNTING
Because the unit is of solid-state design, it does not have to be mounted vertically. Any convenient
mounting angle may be chosen. BE1-CDS Current Differential Systems are available in Basler Electric’s
MX case design. MX cases are fully drawout with current circuit shorting provisions and can be ordered
with an optional cover. MX cases are available in three configurations: a standard 19 inch rack mount, a
horizontal panel mount, and a vertical panel mount. The vertical panel mount configuration fits cutout,
panel drilling, and behind panel projection dimensions (when mounting flange is moved to the back set of
mounting holes) of Basler M1, GE M1 and M2, and Westinghouse FT31 and FT 32 size cases.
• Figures 12-1 through 12-3 show the overall dimensions for the MX case with rack mount brackets.
Notice that Figure 12-1, Front View shows both the standard and optional front panels.
• Figures 12-4 through 12-6 show the overall dimensions of the MX case with a panel mounting
flange. The examples shown in these figures are vertical panel mounting configurations.
Horizontal panel mounting configurations have the same dimensions except that they are in a
horizontal arrangement. Notice that Figure 12-5 shows the hole locations for the Basler, GE, and
Westinghouse unit case relay cases.
• Figure 12-7 shows the panel cutout and panel drilling dimensions for the MX case vertical panel
mounting configuration. Horizontal panel mounting configurations have the same panel cutout
and panel drilling dimensions except that they are in a horizontal arrangement.
Vertical and horizontal configurations are physically and functionally the same with some controls and
indicators relocated.

BE1-CDS Installation 12-1


Figure 12-1. BE1-CDS, MX Case, 19-Inch Rack Mount, Front View, Overall Dimensions

Figure 12-2. BE1-CDS, MX Case, 19-Inch Rack Mount, Top View, Overall Dimensions

12-2 Installation BE1-CDS


Figure 12-3. BE1-CDS, MX Case, 19-Inch Rack Mount, Side View, Overall Dimensions

Figure 12-4. BE1-CDS, MX Case, Vertical Panel Mount, Top View, Overall Dimensions

BE1-CDS Installation 12-3


Figure 12-5. BE1-CDS, MX Case, Vertical Panel Mount, Front View, Overall Dimensions

12-4 Installation BE1-CDS


Figure 12-6. BE1-CDS, MX Case, Vertical Panel Mount, Side View, Overall Dimensions

BE1-CDS Installation 12-5


Note
These dimensions are for the MX case, vertical panel mount or the MX case, horizontal
panel mount. Rotate this drawing ninety degrees for the MX case, horizontal panel
mount.

Figure 12-7. BE1-CDS, MX Case, Vertical Panel Mount, Panel Drilling Diagram

12-6 Installation BE1-CDS


CONNECTIONS
Relay connections are dependent on the application and logic scheme used. All inputs or outputs may not
be used in a given installation. Incorrect wiring may result in damage to the relay. Be sure to check the
model and style number against the options listed in the Style Number identification chart in Section 1
before connecting and energizing a particular relay.

Terminal Blocks
There are two sizes of terminal blocks used on the BE1-CDS, MX case. Terminals B1 through B16 are for
current inputs and use 8-32 Pan-head (Phillips) screws with a lock washer. Terminals A1 through A6, C1
through C32, and D1 through D6 use 6-32 Pan-head (Phillips) screws with no washer. See Figure 12-8 to
locate these terminals.
The lock washers on terminals B1 through B16 are an integral part of the current input circuit wiring and
should not be removed. Without the lock washer, the 8-32 screw may bottom out and prevent a good
mechanical connection with the terminal block.
Maximum wire lug width accommodated by terminals B1 through B16 is 0.344 inches (8.6 mm). Maximum
wire lug width accommodated by the other terminals is 0.320 inches (8.1 mm). Figure 12-8 is a rear view
of the BE1-CDS case showing the terminal connections.

Figure 12-8. BE1-CDS, Rear View, Terminal Connections

Typical AC And DC Connections


Typical external ac and dc connections are shown in Figures 12-9 and 12-10.

NOTE
Be sure the relay is hard-wired to earth ground with no smaller than 12 AWG copper wire
attached to the ground terminal on the rear of the relay case. When the relay is
configured in a system with other protective devices, it is recommended to use a separate
lead to the ground bus from each relay.

Except as noted above, connections should be made with minimum wire size of 14 AWG. Be sure to use
the correct input power for the power supply specified.

BE1-CDS Installation 12-7


AØ BØ CØ

B7 B5 B3 B1 B14 B12 B10


H1 H2 H3

BE1-CDS220
Transformer IG IC1 IB1 IA1 IC2 IB2 IA2
X1 X2 X3

B8 B6 B4 B2 B13 B11 B9

P0001-01.vsd
07-21-00

Figure 12-9. Typical AC Connection Diagram

CONTROL
POWER 52b

A2 C18 + C20 + C22 + C24 + C26 + C28 + C30 + C32 +

Part of
BE1-CDS

POWER IN IN IN IN IN IN IN IN
SUPPLY 1 2 3 4 5 6 7 8

A3
CONTROL C17 - C19 - C21 - C23 - C25 - C27 - C29 - C31 -
POWER
-

C3 C5 C7 C9 C11 C13 C15 C1 ALARM

Part of
BE1-CDS

OUT OUT OUT OUT OUT OUT OUT


1 2 3 4 5 6 A

P0001-13.vsd
06-07-00 C4 C6 C8 C10 C12 C14 C2

Figure 12-10. Typical DC Connection Diagram

12-8 Installation BE1-CDS


CT Polarity
CT polarity is critical to the proper operation of the BE1-CDS. Sidebar 12-1 provides fundamental
information on CT polarity and protective relays.

Sidebar 12-1. CT Polarity


By ANSI convention, CT polarity will face away from the protected winding of a transformer, motor,
generator, or reactor, and away from the contacts in a circuit breaker. Therefore, primary current flow
towards the winding or contacts (direction of protected zone) will result in a secondary current out X1,
in phase with the primary (see Figures 12-11 and 12-12).

Primary current-in polarity (H1) results in


secondary current-out polarity (X1) for a
Primary H1 Bushing CT.

X1 X1
Secondary
X2 X2

H2

D2877-06
07-17-00

Figure 12-11. Standard CT Polarity Figure 12-12. CT Action


On occasion, however, Protection Engineers will run into situations where CT polarity is reversed for a
specific application. That is, non-polarity of the CT secondary will be in phase with the primary current
flow (Figure 12-13). For example, a transformer differential CT from a breaker with a different polarity
convention, such as low voltage switchgear or a bus differential CT taken from the low side of a
transformer.

Figure 12-13. Example Of Reversed CT Polarity


Orientation of CT polarity relative to primary current flow establishes the secondary CT terminal that
should be connected to polarity of the protective relay

POWER SYSTEM APPLICATIONS


Figures 12-14 through 12-23 are examples of the applications that can be served by the Basler
BE1-CDS220 Current Differential System. These applications can be used in concert with other Basler
numeric systems such as the BE1-951 Overcurrent Protection System and BE1-GPS100 Generator
Protection System.

BE1-CDS Installation 12-9


Circuit
Switcher

B7 B5 B3 B1 B14 B12 B10


H1 H2 H3

Transformer IG
BE1-CDS220
IC1 IB1 IA1 IC2 IB2 IA2
2
X1 X2 X3
Optional

Low Side B8 B6 B4 B2 B13 B11 B9


Breaker 52

4 1

P0001-02.vsd
09-21-00

AØ BØ CØ

1 With the appropriate transformer and CT connection information, the relay can automatically determine the required
compensation. The relay can accommodate any combination of transformer and CT connection (wye, delta AB, or
Delta AC). For more information, refer to Section 4, Input And Output Functions, Input Current.

Optional independent ground input (IG) can be connected for overcurrent or neutral differential protection. For more
2 information on connection details, see the following figures on optional ground inputs.

Phase, Residual, and I2 overcurrent elements can be connected to either CT circuit for backup protectiion. For more
3
information on applying overcurrent backup, refer to Section 8, Application.

4 Overcurrent neutral ground (IN) operates on internally calculated residual (3I0) current.

5 For complete metering and independent backup protection, add a BE1-951 Overcurrent Protection System with the
BE1-CDS220 (see the following figure for a connection diagram). To add only metering to the BE1-CDS220, connect a
BE1-MMS100.

Figure 12-14. Typical Transformer Differential Connection


12-10 Installation BE1-CDS

52

2
B5 B3 B1 B14 B12 B10

Motor BE1-CDS220
IC1 IB1 IA1 IC IB2 IA2
Reactor 2

2 B9
B6 B4 B2 B13 B11

P0001-05.vsd
08-11-00

1 Phase, Residual, andI2 overcurrent elements can be connected to either CT circuit for backup protectiion. For more
information on applying overcurrent backup, refer to Section 8,
Application.

2 Overcurrent neutral ground I( N) operates on internally calculated residual (3I0) current.

3 For complete metering and independent backup protection for motors and reactors, add a BE1-951 Overcurrent
Protection System with the BE1-CDS220 (similar to Figure 12-16). To add only metering to the BE1-CDS220, connect
BE1-MMS100.

Figure 12-15. Typical Connection For Motor or Reactor Differential Protection

BE1-CDS Installation 12-11


Circuit
Switcher
6

9
7

D7 D5 D3 D1 C13 C14 C15

5
BE1-951
8 VA VB VC
Optional IG IC IB IA

VN
D8 D6 D4 D2 C16
4
Power Out

B7 B5 B3 B1 B14 B12 B10


H1 H2 H3

Transformer BE1-CDS220
2
X1 X2 X3
Optional IG IC1 IB1 IA1 IC2 IB2 IA2

Low Side B8 B6 B4 B2 B13 B11 B9


Breaker 52

4 1

P0001-03.vsd
06-20-00

AØ BØ CØ

Figure 12-16. BE1-CDS220 Connected For Primary Protection With


A BE1-951 Connected For Independent Backup And Metering

12-12 Installation BE1-CDS


Notes for Figure 12-16

With the appropriate transformer and CT connection information, the relay can automatically determine the required
1 compensation. The relay can accommodate any combination of transformer and CT connection (wye, delta AB, or
Delta AC). for more information, refer to Section 4, Input And Output Functions, Input Current.

Optional independent ground input (IG) can be connected for overcurrent or neutral differential protection. For more
2
information on connection details, see the following figures on optional ground inputs.

Phase, Residual, and I2 overcurrent elements can be connected to either CT circuit for backup protectiion. For more
3 information on applying overcurrent backup, refer to Section 8, Application.

4 Overcurrent neutral ground (IN) operates on internally calculated residual (3I0) current.

VTP connections shown are for H1 case. For more information on case connections, refer to the BE1-951 Instruction
5
Manual, Section 12, Installation.

6 Four-wire connection shown as typical. For more information on case connections, refer to the BE1-951 Instruction
Manual, Section 12, Installation.

With CT polarity connected to relay polarity, power flow from the high side to the low side is defined as power out and
7 equals positive watts.

Optional independent ground input can be connected for low side ground faults. For more information on case
8
connections, refer to the BE1-951 Instruction Manual, Section 12,Installation.

9 Shown with separate, overlapping CT for independent backup protection.


P0001-04.vsd
09-21-00

BE1-CDS Installation 12-13


AØ BØ CØ
IA1
3 1 B1 B2
IB1
B3 B4
IC1
B5 B6

H1 H2 H3
4

DAC X2 X3 3I0
X1
Grounding
BE1-CDS220
Bank 2

Low Side Breaker

IC2
B13 B14
3 1 IB2
B11 B12
IA2
B9 B10

P0001-08.vsd
09-21-00

1
With the appropriate transformer and CT connection information, the relay can automatically determine
the required compensation. The relay can accommodate any combination of transformer and CT
connection (wye, delta AB, or Delta AC). For more information, refer to Section 4, Input And Output
Functions, Input Current.

To cancel out the zero sequence current source inside the zone of protection, connect circuit 2 CTs in
2 wye and specify a ground source on the delta transformer winding. For more information, refer to
Section 1, General Information, Problem 5.

3 Phase, Residual, and I2 overcurrent elements can be connected to either CT circuit for backup
protection. For more information on applying overcurrent backup, refer to Section 8, Application.

4 Overcurrent neutral ground (IN) operates on internally calculated residual (3I0) current.

5 For complete metering and independent backup protection, add a BE1-951 Overcurrent Protection
System with the BE1-CDS220 (refer to Figure 12-16 for a connection diagram). To add only metering
to the BE1-CDS220, connect a BE1-MMS100.

Figure 12-17. Differential Protection For Wye-Grounded-Delta Transformer


With Ground Source Inside The Protected Zone
12-14 Installation BE1-CDS
AØ Bus or Line

Circuit
Switcher
IA1
3 1 B1 B2
IB1
B3 B4
IC1
B5 B6
4
DAB
H1 H2 H3
IG
B8 B7

X1 X2 X3

BE1-CDS220

Low Side Breaker


4

IC2
B13 B14
3 1 IB2
B11 B12
IA2
B9 B10

P0001-09.vsd
08-22-00

1 With the appropriate transformer and CT connection information, the relay can automatically determine
the required compensation. The relay can accommodate any combination of transformer and CT
connection (wye, delta AB, or Delta AC). for more information, refer to Section 4, Input And Output
Functions, Input Current.

2 Optional independent groupd input (IG) connected to detect low side ground faults.

3 Phase, Residual, and I2 overcurrent elements can be connected to either CT circuit for backup
protectiion. For more information on applying overcurrent backup, refer to Section 8, Application.

4 Overcurrent neutral ground (IN) operates on internally calculated residual (3I0) current.

5 For complete metering and independent backup protection, add a BE1-951 Overcurrent Protection
Element with the BE1-CDS220 (refer to Figure 12-16 for a connection diagram). To add only metering
to the BE1-CDS220, connect a BE1-MMS100.

Figure 12-18. Differential Protection Of Delta-Wye Grounded Transformer With Optional


Independent Ground Input Connected For Low Side Ground Fault Protection

BE1-CDS Installation 12-15


AØ BØ CØ
IA1
3 1 B1 B2
IB1
B3 B4
IC1
B5 B6
Primary

H1 H2 H3
Tertiary I0* 2 4
Y1 Y2 Y3

B7 B8
IG

Secondary
X1 X2 X3
6
Y1 Y2 Y3
BE1-CDS220

Alternate Connection
4

IC2
B13 B14
3 1 IB2
B11 B12
IA2
B9 B10

AØ BØ CØ
P0001-10.vsd
09-26-00

1 With the appropriate transformer and CT connection information, the relay can automatically determine
the required compensation. The relay can accommodate any combination of transformer and CT
connection (wye, delta AB, or Delta AC). for more information, refer to Section 4, Input And Output
Functions, Input Current.

Optional independent ground input (IG)connected to one CT inside the delta (Io) to protect an unloaded
2 tertiary winding and provide overcurrent backup protection for system ground faults. A loaded tertiary
requires the application of a three input current differential scheme.
3
Phase, Residual, and I2 overcurrent elements can be connected to either CT circuit for backup
protection. For more information on applying overcurrent backup, refer to Section 8, Application.

4 Overcurrent neutral ground (IN) operates on internally calculated residual (3I0) current.

For complete metering and independent backup protection, add a BE1-951 Overcurrent Protection
5
System with the BE1-CDS220 (refer to Figure 12-16 for a connection diagram). To add only metering
to the BE1-CDS220, connect a BE1-MMS100.

6 When IG is connected with a single CT inside the delta, IG senses 1IO. When IG is connected per the
alternate connection, IG senses 3IO.

Figure 12-19. Differential Protection For High And Low Side Windings With Optional
Independent Ground Input Connected To Protect Unloaded Tertiary Winding
12-16 Installation BE1-CDS
AØ Bus or Line

Circuit
Switcher
IA1
3 1 B1 B2
IB1
B3 B4
IC1
B5 B6
4
DAB
H1 H2 H3
IG
B8 B7

2
X1 X2 X3

BE1-CDS220
Zo
Low Side Breaker
4

IC2
B13 B14
3 1 IB2
B11 B12
IA2
B9 B10

P0001-11.vsd
08-22-00

1 With the appropriate transformer and CT connection information, the relay can automatically determine
the required compensation. The relay can accommodate any combination of transformer and CT
connection (wye, delta AB, or Delta AC). for more information, refer to Section 4, Input And Output
Functions, Input Current.

2 Optional independent groupd input (IG) connected to detect low side ground faults.

3 Phase, Residual, and I2 overcurrent elements can be connected to either CT circuit for backup
protectiion. For more information on applying overcurrent backup, refer to Section 8, Application.

4 Overcurrent neutral ground (IN) operates on internally calculated residual (3I0) current.

5 For complete metering and independent backup protection, add a BE1-951 Overcurrent Protection
Element with the BE1-CDS220 (refer to Figure 12-16 for a connection diagram). To add only metering
to the BE1-CDS220, connect a BE1-MMS100.

Figure 12-20. Differential Protection Of Delta-Wye Resistance Grounded Transformer


With Optional Independent Ground Input Connected For 87ND Protection

BE1-CDS Installation 12-17


AØ BØ CØ

DAB 87ND
H1 H2 H3
B8 B7
IG

3I0
IR
BE1-CDS220 IOP
X1 X2 X3
Zo

Low Side Breaker 1


IR
-3I0

I0 I0 I0
IC2 I0
B13 B14
IB2 I0
B11 B12
IA2 I0
B9 B10

P0001-12.vsd
09-21-00

1 The zero sequence current exiting the zone of protection is the calculated neutral for the three-phase
CT input circuit designated by the BESTlogic mode setting. The CT's for this three-phase input circuit
must be connected in wye with zero sequence compensation for the grounded winding provided by
internal delta compensation.

Figure 12-21. Depiction of BE1-CDS220 With Optional Independent Ground Input Connected
For 87ND Protection, Balanced, Normal Load flow, IR’s Cancel, And IOP = 0

12-18 Installation BE1-CDS


BE1-CDS220
1 IA1
B1 B2
2
IB1
B3 B4
IC1
B5 B6
3

IC2
BUS SOURCE
BREAKER B14 B13
IB2 2
B12 B11
IA2
B10 B9


52

52 52 52 BUS TIE
BREAKER

1
RADIAL LOAD RADIAL LOAD RADIAL LOAD
P0001-07.vsd
08-11-00

1 High speed bus differential zone. Source currentIN equals the radial load current OUT.

2 Phase, Residual, and I2 overcurrent elements can be connected to either CT circuit for backup protectiion. For more
information on applying overcurrent backup, refer to Section 8,Application.

3 Overcurrent neutral ground (IN) operates on internally calculated residual (3I0) current.

4 For complete metering and independent backup protection, use a BE1-951 Overcurrent Protection System with the
BE1-CDS220. A BE1-951 on the Bus Source Breaker can also be used in conjunction with Feeder BE1-851 or
BE1-951 relays to create a high speed bus interlocking protection scheme. To add only metering to the BE1-CDS220,
connect a BE1-MMS100.

Figure 12-22. BE1-CDS220 Connected For Low-Impedance Bus Differential Protection

BE1-CDS Installation 12-19


Power Out

AØ AØ
High Z
GND BØ BØ D/Y
Generator GSU
DIST CØ CØ TX
TX R
6
5

7
4

D7 D8 C18 C17 D1 D3 D5

IG VTX IA IB IC
C16 C13 C14 C15

VN VTP
D2 D4 D6

VA VB VC

Part of 2 2
BE1-GPS100
Part of
B1 B3 B5 B13 B11 B9 BE1-GPS100
BE1-CDS220
IA1 IB1 IC1 1
IC2 IB2 IA2

B2 B4 B6 B14 B12 B10

P0001-06.vsd
08-11-00
3 3

1 Connected for high speed generator differential protection.

Phase, Residual, and I2 overcurrent elements can be connected to either CT circuit for backup protectiion. For
2 more information on applying overcurrent backup, refer to Section 8, Application .

3 Overcurrent neutral ground (I N) operates on internally calculated residual (3I0) current.

4 Four-wire connection shown as typical. For more information on case connections, see Section 12, Installation , in
the BE1-GPS100 Instruction Manual.

5 With CT polarity connected to relay polarity, power flow from the high side to the low side is defined as power out
and equals positive watts.

6 Optional independent ground input (I G) connected for backup ground fault protection.

7 VTX connected for third harmonic detection.

Figure 12-23. Large Generator Protection With BE1-CDS220 Connected For Primary
Current Differential Protection, And BE1-GPS100 Connected For Independent Backup
Fault Protection, Detection Of Abnormal situations, and Metering

12-20 Installation BE1-CDS


CONTACT SENSING INPUT JUMPERS
Eight contact sensing inputs provide external stimulus to initiate BE1-CDS actions. An external wetting
voltage is required for the contact sensing inputs. The nominal voltage level of the external dc source
must comply with the dc power supply input voltage ranges listed in Section 1, General Information,
Specifications. To enhance user flexibility, the BE1-CDS uses wide range ac/dc power supplies that cover
several common control voltages. The contact sensing input circuits are designed to respond to voltages
at the lower end of the control voltage range while not overheating at the high end of the range.
Energizing levels for the contact sensing inputs are jumper selectable for a minimum of 13 Vdc for 24 Vdc
nominal sensing voltages, 26 Vdc for 48 Vdc nominal sensing voltages, or 69 Vdc for 125 Vdc nominal
sensing voltages. See Table 12-1 for the control voltage ranges.
Table 12-1. Contact Sensing Turn-On Voltage
Nominal Turn-On Range
Control Voltage Pin 1 – Pin 2 Pin 2 – Pin 3
24 Vdc 13-19 Vdc N/A
48/125 Vac/dc 26 to 38 V 69 to 100 V
125/250 Vac/dc 69 to 100 V 138 to 200 V

Each BE1-CDS is delivered with the contact sensing jumpers installed for operation in the lower end of the
control voltage range (pins 1 and 2 shorted). If the contact sensing inputs are to be operated at the upper
end of the control voltage range, the jumpers must be changed to pins 2 and 3 shorted or completely
removed.
The following paragraphs describe how to locate and remove/change the contact sensing input jumpers.
1. Remove the drawout assembly by pulling the two latches upward and sliding the assembly out of the
case. Observe all electrostatic discharge (ESD) precautions when handling the drawout assembly.
2. Locate the eight jumper terminal blocks (W1 through W8) that are mounted on the Input/Output
Circuit Board. The Input/Output Circuit Board is the middle board in the assembly and the jumper
terminal blocks are located on the component side of the circuit board near the left hand side (right
hand side when looking at the unit from the rear by the internal connections). Each terminal block
has three pins. With the jumper as installed at the factory, one pin should be visible when viewed
from the rear of the unit. Figure 12-24 illustrates the location of a jumper placed in the low voltage
position.
3. To select operation at the upper end of the control voltage range, remove the blue jumper entirely
from the unit or position it on the two terminals closest to the rear of the circuit board. Use care when
removing each jumper so that no components are damaged.
4. When all jumpers are positioned for operation in the desired control voltage range, prepare to place
the drawout assembly back into the case.
5. Align the drawout assembly with the case guides and slide the assembly into the case.
6. Push the latches down until they are parallel with the front panel.

BE1-CDS Installation 12-21


REAR
C15 C45
C44

R82 R81

P in 3 R43
P in 2 C O N TA C T
S E N S IN G
JU M P E R
W8

FRONT
P 00 01-14 .C D R
1 0-2 9-9 8
1
P in 1 is R43
la beled

Figure 12-24. BE1-CDS, Contact Sensing Input Jumpers

COMMUNICATION CONNECTIONS
The following paragraphs describe the communication connections for the BE1-CDS. Section 11, ASCII
Command Interface provides information about using the relay communication interface and lists all
communication commands along with a description and the syntax for each command.

RS-232 Connectors
Front and rear panel RS-232 connectors are Data Communication Equipment (DCE) DB-9 female
connectors. Connector pin numbers, functions, names and signal directions are shown in Table 12-2.
RS-232 cable connection diagrams are provided in Figures 12-25 through 12-28. Optional Clear to Send
(CTS) and Request to Send (RTS) connections are required only if hardware handshaking is enabled.
Table 12-2. RS-232 Pinouts (COM 0 And COM 1)
Pin Function Name Direction
1 Shield ---- N/A
2 Transmit Data (TXD) From Relay
3 Receive Data (RXD) Into Relay
4 N/C ---- N/A
5 Signal Ground (GND) N/A
6 N/C ---- N/A
7 N/C ---- N/A
8 N/C ---- N/A
9 N/C ---- N/A

12-22 Installation BE1-CDS


TO BE1-CDS
RFL 9660 REAR PORT MALE DB-9, DCE
MATING CONNECTOR 1 N.C.
3 2 TXD
2 3 RXD
5 4 N.C.
5 SGND
6 N.C.
7 N.C.
8 N.C.
D2839-01.vsd 9 N.C.
06-23-00

Figure 12-25. RFL 9060 Protective Relay Switch To BE1-CDS Cable

TO 25 PIN MODEM TO BE1-CDS


FEMALE DB-25, DCE FEMALE DB-9, DCE
GND 1 1 N.C.
TXD 2 2 TXD
RXD 3 3 RXD
+5V 6 4 N.C.
SGND 7 5 SGND
DTR 20 6 +10V
7 N.C.
8 N.C.
9 N.C.

P0001-16.vsd
50 FEET MAX. 06-23-00

Figure 12-26. Modem To BE1-CDS

9-PIN PC-AT TO BE1-CDS 25-PIN PC-XT TO BE1-CDS


MALE DB-9, DTE FEMALE DB-9, DCE MALE DB-25, DTE FEMALE DB-9, DCE
1 1 N.C. 1 N.C.
RXD 2 2 TXD 3 2 TXD
TXD 3 3 RXD 2 3 RXD
4 4 N.C. N.C. 4 N.C.
SGND 5 5 SGND 7 5 SGND
6 N.C. 6 N.C.
7 N.C. 7 N.C.
8 N.C. 8 N.C.
D2839-02.vsd
06-23-00 9 N.C. 9 N.C.

Figure 12-27. Personal Computer To BE1-CDS

BE1-CDS Installation 12-23


TO SEL-2020 TO BE1-CDS
FEMALE DB-9, DTE FEMALE DB-9, DCE
TXD 2 2 TXD

RXD 3 3 RXD

SGND 5 5 SGND

CTS 7 7 CTS *

RTS 8 8 RTS *

TO BE1-CDS
IRIG TERMINALS
IRIG-B + 4
IRIG-B 6

Figure 12-28. SEL-2020 Communications Processor To BE1-CDS

RS-485 Connector
The RS-485 connector is a three position terminal block connector designed to interface to a standard
communication cable. A twisted-pair cable is recommended. Connector pin numbers, functions, names,
and signal directions are shown in Table 12-3. An RS-485 cable connection diagram is provided in Figure
12-29.
Table 12-3. RS-485 Pinouts (COM2)
Terminal Function Name Direction
A Send/Receive A (SDA/RDA) In/Out
B Send/Receive B (SDB/RDB) In/Out
C Signal Ground (GND) N/A

TO RS-422/RS-485 TO BE1-CDS
DB-37 FEMALE 3 POSITION TB
4
6
22 Rt A D5
BE1-CDS
24 B D4
COM 2
19 C D3
A5

A D5
BE1-CDS
B D4
COM 2
C D3

4000'
MAX.

Rt A D5
BE1-CDS
B D4
COM 2
C D3

D2839-04.vsd
R t = OPTIONAL TERMINATING
06-23-00 RESISTOR (120 OHMS TYP.)

Figure 12-29. RS-485 DB-37 To BE1-CDS

IRIG Connection
The IRIG input is fully isolated and supports IRIG Standard 200-98, Format B002. The demodulated (dc
level-shifted) input signal must be 3.5 volts or higher to be recognized as a high logic level. The maximum
acceptable input voltage range is 20 volts (+10 and –10 or 0 to 20). Input burden is nonlinear and rated at
approximately 4 kilo-ohms at 3.5 Vdc and approximately 3 kilo-ohms at 20 Vdc.

12-24 Installation BE1-CDS


IRIG connections are located on a terminal block shared with the RS-485 and input power terminals.
Terminal designations and functions are shown in Table 12-4.
Table 12-4. IRIG Pinouts
Terminal Function
D2 + Signal
D1 - Reference

SETTINGS
Settings for your application need to be entered and confirmed before placing the relay in service.
Register settings such as breaker operations and breaker duty can be entered to match the current state
of your system.

PREPARING THE RELAY FOR SERVICE


Basler microprocessor-based protection systems are similar in nature to a panel of electromechanical or
solid-state component relays. Both must be wired together with inputs and outputs, and have operating
settings applied. Logic settings determine which protection elements are electronically wired to the inputs
and outputs of the device. Operating settings determine the pickup thresholds and time delays.
The logic and operating settings should be tested by applying actual inputs and operating quantities and
verifying proper output response. For more details, refer to Section 13, Testing and Maintenance. All of
the following connections and functions should be verified during commissioning tests.
• Proper connection and sensing of current and voltage signals
• Input and output contact connections
• I/O sensing versus virtual sensing
• Settings validation
• Proper operation of equipment (main or auxiliary)
• Proper alarming (to SCADA) and/or targeting
Refer to Section 7, BESTlogic Programmable Logic for information about customizing preprogrammed
logic and creating user-defined logic, and Section 8, Application for information about the application of
preprogrammed logic schemes.

BE1-CDS Installation 12-25


SECTION 13 • TESTING AND MAINTENANCE

TABLE OF CONTENTS

List of Figures .........................................................................................................................................ii


List of Tables..........................................................................................................................................iii
List of Sidebars ......................................................................................................................................iv
TESTING AND MAINTENANCE ............................................................................................................. 13-1
GENERAL ............................................................................................................................................ 13-1
TESTING PHILOSOPHIES .................................................................................................................. 13-1
Acceptance Testing .......................................................................................................................... 13-1
Commissioning Testing..................................................................................................................... 13-1
Periodic Testing ................................................................................................................................ 13-1
Functional Testing............................................................................................................................. 13-2
Performance Testing......................................................................................................................... 13-2
TESTING AND TROUBLESHOOTING AIDS....................................................................................... 13-2
Relay Self-Test ................................................................................................................................. 13-2
Status And Event Reporting Features .............................................................................................. 13-3
ACCEPTANCE TESTING .................................................................................................................... 13-3
Test Setup......................................................................................................................................... 13-3
Test Equipment................................................................................................................................. 13-3
Power Up .......................................................................................................................................... 13-4
Communications ............................................................................................................................... 13-4
Style Number And Serial Number Verification .................................................................................. 13-5
IRIG Verification................................................................................................................................ 13-5
Contact Sensing Inputs And Control Outputs ................................................................................... 13-5
Current Circuit Verification ................................................................................................................ 13-7
COMMISSIONING TESTING ............................................................................................................... 13-8
Protection And Control Function Verification .................................................................................... 13-8
Testing Phase Differential Protection With Internal Compensation .................................................. 13-9
Phase Differential Restrained Minimum Pickup Trip .................................................................................. 13-11
Phase Differential Restrained Slope Trip ................................................................................................... 13-12
Phase Differential Unrestrained Trip .......................................................................................................... 13-18
Verify Other Set Points as Appropriate ........................................................................................... 13-18
Digital I/O Connection Verification .................................................................................................. 13-18
Contact Sensing Inputs .............................................................................................................................. 13-18
Output Contacts ......................................................................................................................................... 13-19
Virtual 43 Switches ......................................................................................................................... 13-20
Virtual 101 Switch ........................................................................................................................... 13-20
Reporting And Alarm Functions ...................................................................................................... 13-21
Clock Display ............................................................................................................................................. 13-21
Demand Functions ..................................................................................................................................... 13-21
Transformer Monitoring .............................................................................................................................. 13-21
Breaker Monitoring ..................................................................................................................................... 13-21
Relay Trouble Alarms................................................................................................................................. 13-22
Major/Minor/Logic Programmable Alarms .................................................................................................. 13-22
Targets ....................................................................................................................................................... 13-22
Fault Summary Reports ............................................................................................................................. 13-22
Sequence Of Events Recorder (SER) Function ......................................................................................... 13-22
System Report Documentation .................................................................................................................. 13-23
In Service Current Circuit Verification ............................................................................................. 13-23
Test Scenarios ........................................................................................................................................... 13-23

BE1-CDS Testing And Maintenance i


PERIODIC TESTING.......................................................................................................................... 13-27
Settings Verification ........................................................................................................................ 13-27
Digital I/O Connection Verification .................................................................................................. 13-27
Analog Circuit Verification............................................................................................................... 13-27
FUNCTIONAL TESTING .................................................................................................................... 13-28
Phase Differential (87) .................................................................................................................... 13-28
Minimum Pickup ......................................................................................................................................... 13-28
Restrained Pickup ...................................................................................................................................... 13-30
Restrained Time Verification ...................................................................................................................... 13-39
Second Harmonic Restraint Verification..................................................................................................... 13-41
Fifth Harmonic Restraint Verification .......................................................................................................... 13-42
Unrestrained Pickup Verification ................................................................................................................ 13-43
Unrestrained Time Verification ................................................................................................................... 13-44
Neutral Differential (87ND).............................................................................................................. 13-46
Minimum Pickup ......................................................................................................................................... 13-46
Restrained Pickup Verification (87ND) ....................................................................................................... 13-47
Instantaneous Overcurrent ............................................................................................................. 13-49
Pickup And Dropout Verification (50T/150T/250T)..................................................................................... 13-49
Time Overcurrent ............................................................................................................................ 13-53
Pickup And Dropout Verification (51/151/251) ........................................................................................... 13-53
Timing Verification (51/151/251)................................................................................................................. 13-55
Breaker Failure ............................................................................................................................... 13-56
Virtual Switch Verification (43/143/243/343/443/543/643/743) ....................................................... 13-58
Virtual Switch Mode 1 Operation (On/Off/Pulse) ........................................................................................ 13-58
Virtual Switch Mode 2 Operation (On/Off) .................................................................................................. 13-59
Virtual Switch Mode 3 Operation (Off/Momentary On) ............................................................................... 13-60
101 Virtual Breaker Control Switch ................................................................................................. 13-61
Logic Timer Verification (62/162) .................................................................................................... 13-62
Mode 1 - Pickup/Dropout............................................................................................................................ 13-62
Mode 2 – One Shot Nonretriggerable......................................................................................................... 13-63
Mode 3 – One Shot Retriggerable .............................................................................................................. 13-64
Mode 4 - Oscillator ..................................................................................................................................... 13-65
Mode 5 – Integrating Timer ........................................................................................................................ 13-65
Mode 6 – Latch Timer................................................................................................................................. 13-67
Automatic Setting Group Change ................................................................................................... 13-68
Automatic Change ...................................................................................................................................... 13-68
Manual Change Mode 1 ............................................................................................................................. 13-71
Manual Change Mode 2 ............................................................................................................................. 13-72
MAINTENANCE ................................................................................................................................. 13-73

List of Figures
Figure 13-1. BE1-CDS, Rear View, Terminal Connections..................................................................... 13-4
Figure 13-2. Series Current Connection Diagram................................................................................... 13-7
Figure 13-3. Test Currents For Restrained Trip Test............................................................................ 13-13
Figure 13-4. Test Connection Diagrams For Table 13-11..................................................................... 13-15
Figure 13-5. Test Connection Diagrams For Table 13-11..................................................................... 13-15
Figure 13-6. Test Connection Diagrams For Table 13-11..................................................................... 13-15
Figure 13-7. Test Connection Diagrams For Table 13-11..................................................................... 13-16
Figure 13-8. Test Connection Diagrams For Table 13-11..................................................................... 13-16
Figure 13-9. Test Connection Diagrams For Table 13-11..................................................................... 13-16
Figure 13-10. Test Connection Diagrams For Table 13-11................................................................... 13-17
Figure 13-11. Test Connection Diagrams For Table 13-11................................................................... 13-17
Figure 13-12. Minimum Pickup Characteristic ...................................................................................... 13-29
Figure 13-13. Connections For Restraint Verification ........................................................................... 13-31
Figure 13-14. Connection for Harmonic Restraint Verification.............................................................. 13-41
Figure 13-15. Connection for 87ND Minimum Pickup Verification ........................................................ 13-46
Figure 13-16. Connection for 87ND Restraint Pickup Verification ........................................................ 13-48
Figure 13-17. x62 Mode 1 (Pickup/Dropout) Timing Example .............................................................. 13-63
Figure 13-18. x62 Mode 2 (One-Shot Nonretriggerable) Timing Example............................................ 13-64
ii Testing And Maintenance BE1-CDS
Figure 13-19. x62 Mode 3 (One-Shot Retriggerable) Timing Example................................................. 13-65
Figure 13-20. x62 Mode 5 (Integrating) Timing Example...................................................................... 13-66
Figure 13-21. x62 Mode 6 (Latch) Timing Example .............................................................................. 13-68

List of Tables
Table 13-1. Voltage Input........................................................................................................................ 13-4
Table 13-2. Input Contact Wetting Voltage ............................................................................................. 13-6
Table 13-3. Output Control Override Commands ................................................................................... 13-6
Table 13-4. Circuit 1 Metering Quantities................................................................................................ 13-7
Table 13-5. Circuit 2 Metering Quantities................................................................................................ 13-8
Table 13-6. Commands To Initiate A Differential Check Record .......................................................... 13-11
Table 13-7. Phase and Zero Sequence Compensated Currents .......................................................... 13-11
Table 13-8. Differential Element Minpu Response To IA Test Current ................................................. 13-12
Table 13-9. Differential Element Minpu Response To IB Test Current ................................................. 13-12
Table 13-10. Differential Element Minpu Response To IC Test Current............................................... 13-12
Table 13-11. Starting Test Currents And Test Connections For Slope Test......................................... 13-14
Table 13-12. Output Control Override Commands ............................................................................... 13-20
Table 13-13. Pickup Test Commands................................................................................................... 13-28
Table 13-14. S#-87 Commands ............................................................................................................ 13-29
Table 13-15. Sensing Input Type Accuracy .......................................................................................... 13-29
Table 13-16. Minimum Pickup Accuracy Limits .................................................................................... 13-30
Table 13-17. Commands To Prepare For Pickup Testing .................................................................... 13-31
Table 13-18. Setup Commands ............................................................................................................ 13-32
Table 13-19. Setup Commands ............................................................................................................ 13-34
Table 13-20. Maximum Restraint Pickup Test Points (5 A Sensing Input) ........................................... 13-35
Table 13-21. Maximum Restraint Pickup Test Points (1 A Sensing Input) ........................................... 13-35
Table 13-22. Setup Commands ............................................................................................................ 13-35
Table 13-23. Setup Commands ............................................................................................................ 13-38
Table 13-24. Maximum Restraint Pickup Test Points (5 A Sensing Input) ........................................... 13-38
Table 13-25. Maximum Restraint Pickup Test Points (1 A Sensing Input) ........................................... 13-39
Table 13-26. Setup Commands ............................................................................................................ 13-39
Table 13-27. Restrained Element Response Time Setup Commands ................................................. 13-40
Table 13-28. Restrained Trip Operate Times........................................................................................ 13-41
Table 13-29. Second Harmonic Restraint Elements Setup Commands ............................................... 13-42
Table 13-30. Fifth Harmonic Restraint Elements Setup Commands .................................................... 13-43
Table 13-31. 87 Elements Pickup Setup Commands ........................................................................... 13-44
Table 13-32. Unrestrained Pickup Accuracy Limits .............................................................................. 13-44
Table 13-33. Unrestrained Element Response Time Setup Commands .............................................. 13-45
Table 13-34. Restrained Trip Operate Times........................................................................................ 13-45
Table 13-35. 87ND Pickup Test Commands......................................................................................... 13-46
Table 13-36. Minimum Pickup Accuracy Limits (87ND)........................................................................ 13-47
Table 13-37. 87ND Restraint Operation Accuracy Test Commands .................................................... 13-48
Table 13-38. Restraint Pickup Test Points (87ND – 5 Ampere Sensing Input) .................................... 13-49
Table 13-39. Restraint Pickup Test Points (87ND – 1 Ampere Sensing Input) .................................... 13-49
Table 13-40. 50T/150T/250T Overcurrent Test Commands................................................................. 13-50
Table 13-41. Instantaneous 50T Element Test Values ........................................................................ 13-50
Table 13-42. Instantaneous 50T Element Accuracy ............................................................................. 13-51
Table 13-43. Instantaneous Overcurrent 150T Element Test Logic ..................................................... 13-51
Table 13-44. Instantaneous Overcurrent 250T Element Test Logic ..................................................... 13-51
Table 13-45. 51/151/251 Time Overcurrent Test Commands .............................................................. 13-53
Table 13-46. Time Overcurrent 51 Element Test Settings.................................................................... 13-53
Table 13-47. Time Overcurrent 51 Element Accuracy.......................................................................... 13-53
Table 13-48. Time Overcurrent 151 Element Test Logic ...................................................................... 13-54
Table 13-49. Time Overcurrent 251 Element Test Logic ...................................................................... 13-54
Table 13-50. 51/151/251 Overcurrent Timing Test Commands............................................................ 13-55
Table 13-51. Time Overcurrent 51 Element Test Settings.................................................................... 13-55

BE1-CDS Testing And Maintenance iii


Table 13-52. Time Overcurrent 51 Element Test Values...................................................................... 13-56
Table 13-53. BF Pickup Test Commands ............................................................................................. 13-57
Table 13-54. BF Current Detector Dropout Settings ............................................................................. 13-57
Table 13-55. BF Dropout Limits ............................................................................................................ 13-57
Table 13-56. BF Time Delay Commands.............................................................................................. 13-57
Table 13-57. Mode 1 Test Commands.................................................................................................. 13-58
Table 13-58. Mode 1 Test Commands.................................................................................................. 13-59
Table 13-59. Mode 1 Test Commands.................................................................................................. 13-59
Table 13-60. Mode 1 Test Commands.................................................................................................. 13-59
Table 13-61. Mode 2 Test Commands.................................................................................................. 13-59
Table 13-62. Mode 2 Test Commands.................................................................................................. 13-60
Table 13-63. Mode 2 Test Commands.................................................................................................. 13-60
Table 13-64. Mode 3 Test Commands.................................................................................................. 13-60
Table 13-65. Mode 3 Test Commands.................................................................................................. 13-60
Table 13-66. 101 Virtual Breaker Control Switch Test Commands....................................................... 13-61
Table 13-67. 101 Virtual Breaker Control Switch Trip Test Commands ............................................... 13-61
Table 13-68. 101 Virtual Breaker Control Switch Close Test Commands ............................................ 13-61
Table 13-69. x62 Mode 1 Test Commands........................................................................................... 13-62
Table 13-70. x62 Mode 1 Timer Initiate Commands ............................................................................. 13-62
Table 13-71. x62 Mode 1 Timer Initiate Clear Commands ................................................................... 13-62
Table 13-72. x62 Mode 2 Test Commands........................................................................................... 13-63
Table 13-73. x62 Mode 2 Timer Initiate Commands ............................................................................. 13-63
Table 13-74. x62 Mode 3 Test Commands........................................................................................... 13-64
Table 13-75. x62 Mode 3 Timer Initiate Commands ............................................................................. 13-65
Table 13-76. x62 Mode 5 Test Commands........................................................................................... 13-65
Table 13-77. x62 Mode 5 Timer Initiate Commands ............................................................................. 13-66
Table 13-78. x62 Mode 6 Test Commands........................................................................................... 13-67
Table 13-79. x62 Mode 6 Timer Initiate Commands ............................................................................. 13-67
Table 13-80. Automatic Setting Group Change Function Test Commands .......................................... 13-68
Table 13-81. Automatic Group Control Selection.................................................................................. 13-69
Table 13-82. Time Overcurrent 51P Element Pickup Settings.............................................................. 13-69
Table 13-83. Automatic Setting Group Change Example Accuracy Limits - Increasing Current .......... 13-70
Table 13-84. Automatic Group Control Selection.................................................................................. 13-70
Table 13-85. Automatic Setting Group Change Example Accuracy Limits - Decreasing Current ........ 13-70
Table 13-86. Manual Group Control Selection...................................................................................... 13-71
Table 13-87. Manual Group Control Selection...................................................................................... 13-72
Table 13-88. Binary Group Control Selection Setup ............................................................................. 13-72
Table 13-89. Binary Group Control Selection Test Commands ............................................................ 13-73

List of Sidebars
Sidebar 13-1. Testing With Internal Phase And I0 Compensation....................................................... 13-10
Sidebar 13-2. Percentage Differential Restraint Operating Principle .................................................... 13-31
Sidebar 13-3. Maximum Restraint Operating Characteristic................................................................. 13-32
Sidebar 13-4. Maximum Restraint When Decreasing One Input From Balance................................... 13-34
Sidebar 13-5. Average Restraint Operating Characteristic ................................................................... 13-36
Sidebar 13-6. Average Restraint When Increasing One Input From Balance....................................... 13-36
Sidebar 13-7. Average Restraint When Decreasing One Input From Balance ..................................... 13-37
Sidebar 13-8. Determining The Operating Point On The Curve ........................................................... 13-40
Sidebar 13-9. Auto Tap Compensation................................................................................................. 13-47
Sidebar 13-10. Negative Sequence Overcurrent Element Pickup ........................................................ 13-52

iv Testing And Maintenance BE1-CDS


SECTION 13 • TESTING AND MAINTENANCE

GENERAL
The need to test protective relays to confirm performance as designed by relay manufacturers will always
exist. This Section provides guidelines for performing those tests and others. It also provides guidelines
for performing maintenance on, and troubleshooting the BE1-CDS220 relay. Included are discussions on
testing philosophies and methods, requirements, and expected outcomes. For assistance in conducting
relay self-tests and troubleshooting using internal diagnostics, contact Basler Electric, Customer Service.

TESTING PHILOSOPHIES
Testing is generally divided into several categories and is known by various names:
• Acceptance (or integrity)
• Commissioning
• Periodic (or maintenance)
• Functional (application)
• Performance
While all types of tests may be performed, they are not generally performed by all users. Likewise, the
degree to which you will conduct each type of test depends on need, economics, and perceived system
value.

Acceptance Testing
Acceptance (or integrity) testing is intended to confirm through basic tests, that a particular relay that has
been manufactured and shipped meets published core specifications. Some of the more rudimentary
procedures will provide a good foundation for application-specific tests that may be delved into during
functional or commissioning tests. Generally, while basic in nature, these tests validate proper relay
manufacturing and shipping and usually precede any functional or commissioning tests.
Basler Electric performs detailed acceptance testing on all devices to verify all functions meet published
specifications. All products are packaged and shipped using strict standards and will remain intact and
precise during shipping. The BE1-CDS220 relay is a microprocessor-based relay whose operating
characteristics will not change over time. The relay will not experience changes in operating
characteristics during transit. However, it remains material that you perform these basic acceptance tests
to verify the device has not suffered any degradation in transit. Basler Electric warrants all products
against any decay in performance outside of the published specified tolerances that result from problems
created during transit.

Commissioning Testing
Commissioning testing verifies all physical connections and functional aspects of the protective relay for a
new installation. All of the following connections or functions can be verified during commissioning tests:
• Proper connection and sensing of current and voltage signals as applicable
• Connections of I/O contacts
• I/O sensing versus virtual sensing
• Setting validation
• Proper operation of equipment (main or auxiliary)
• Proper alarming (to SCADA) and/or targeting

Periodic Testing
Periodic (or maintenance) testing can be performed at regularly scheduled intervals or upon an indication
of problems or questionable operations within the relay. Verifying the integrity of the relay performance
(short of playback of recorded events) may be necessary by performing certain tests similar to those
accomplished in the acceptance and/or functional tests. Verification that the relay is measuring signals
BE1-CDS Testing And Maintenance 13-1
faithfully, that relay logic is appropriate, and, that protective elements and equipment (main or auxiliary)
operate correctly are goals that can be achieved during this type of testing.
Basler Electric recommends that all captured fault records and sequence of event records be analyzed
and kept on file as in-service periodic test results for this particular device. This is an indication that all
protective elements and associated equipment are operating satisfactorily.
It is not the intent of this manual to elaborate on every conceivable test possible since this would encroach
on individual preferences, techniques, and philosophies. It is the intent to pursue relevant testing methods
to verify this relay meets published design specifications and applicability.

Functional Testing
Functional (or application) testing is significantly more comprehensive in nature and is intended to test
suitability for a particular application. Functional testing also provides a means to familiarize yourself with
the logic and operation of this device. Test setups are generally more involved and often times include
ancillary equipment beyond voltage or current source type equipment. While economics may at times
prohibit full functional testing, it is recommended that some application testing be performed when
published specifications lack appropriate detail to satisfy application testing requirements.
Basler Electric performs a thorough and comprehensive functional test of all relays before shipping. This
ensures that this device is within specified tolerances, measures accurately, and operates correctly as
designed.

Performance Testing
Performance testing can be accomplished through the capture and playback of system fault records. In
actual applications, this type of test realizes further confirmation of faithful relay responses during system
disturbances. For specific power system disturbances, relays can be subjected to a recreation of
captured events with the aide of equipment capable of replicating COMTRADE record files. In these
instances, there is significant merit in testing relays in this manner to assess relay performance. Correct
response of relay action in a performance test is supplemental verification of the conclusions drawn from
functional (or application) tests.
This type of testing verifies not only whether or not the device operated correctly for a particular system
disturbance, but also offers additional confirmation of your protection philosophy in this application. It is
beyond the scope of this manual to develop performance tests for this device. For assistance in
developing these types of tests, please consult Basler Electric and your test equipment manufacturer.

TESTING AND TROUBLESHOOTING AIDS


Under test or in-service, the BE1-CDS220 provides several ways to check operations, targets, or events.
A continuous self-test monitors the system health and status. The most basic reporting function is targets.
Targets may be viewed through ASCII command interface or through the optional front panel HMI. Fault
Summary Reports, Sequence of Events Recorder (SER) Reports, and Oscillographic Records yield more
detail.
Each time a system disturbance occurs in or around this relay’s zone of protection, it is a test of the relay
performance during the fault. If a questionable operation (or lack of) results in the need for
troubleshooting, you have several ways in which to troubleshoot the relay, the installation, and the overall
application.

Relay Self-Test
All internal circuitry and software that affect the relay core functionality are monitored by the continuous
self-test diagnostics. For specific relay trouble alarms, the self-test diagnostics force the microprocessor
to reset and try to correct the problem. If unsuccessful, OUTA operates, the Relay Trouble LED on the
front panel turns ON, all of the output relays are disabled, internal logic point ALMREL is set, and the relay
is taken off line. For more information on self-test diagnostics and relay trouble alarms, see Section 6,
Reporting And Alarm Functions, Alarms Function.

13-2 Testing And Maintenance BE1-CDS


Status And Event Reporting Features
General status reporting is available through the ASCII command interface using the RG-STAT (report
general, status) command or the optional front panel human-machine interface (HMI) with LCD display.
This report assembles all of the information required to determine the relay status. For more information
on general status reporting, see Section 6, Reporting And Alarm Functions, General Status Reporting,
General Status Report. Several different HMI screens display the same information. Section 6, Reporting
And Alarm Functions, General Status Reporting, General Status Report details the location and number of
each of the HMI screens for every line in the general status report.
Fault reporting and target data is dependent on the proper setting of trip, pickup, and logic trigger
expressions (via the SG-TRIGGER command) and the assignment of protective elements to be logged as
targets (via the SG-TARG command).
The SER function of the relay records protective element output state changes, overcurrent element
pickup or dropout, input/output contact state changes, logic triggers, setting group changes, and setting
changes. For more information on event reporting, see Section 6, Reporting And Alarm Functions,
Sequence Of Events Recorder Function.
The following is a summary of ASCII commands where target and event data may be viewed.
• RF provides a directory of fault summary reports in memory
• RF-# provides a summary report giving targets, timing and event data
• RG-TARG provides target data only
• RS provides a summary of sequence of events records
• RS-F# provides a detailed SER report for the selected fault event #
• RS-# provides a detailed SER report on the last # events
The following summarizes the reporting capabilities of the relay through the optional front panel HMI.
• Flashing Trip LED: flashes during pickup of protective elements based on the pickup logic
expression set in the SG-TRIGGER command.
• Trip LED (sealed-in): stays illuminated after trip logic goes TRUE based on the trip logic
expression set in the SG-TRIGGER command
• \STAT\TARGETS\DETAILS (Screen 1.1.1): provides target data
• \STAT\ALARMS (Screen 1.2.1): provides alarm data (including BKR FAIL, REC FAIL and REC
LO)
• \REPRT\FAULT\M_REC\DETAILS (Screen 4.1.1.1): provides targets and fault summary data
• \REPRT\SEQ (Screen 4.2): provides the number of new events logged by the SER since the last
new counter reset (resettable only through ASCII command RS=0), events must be viewed using
RS and RS-# commands listed in the previous paragraph.
For more information on HMI menu trees, see Section 10, Human Machine Interface.
While the design of the relay facilitates obtaining and verifying targets and event data, it is not always
necessary to utilize the relay functions to determine if the device operated while testing. You may simply
use an ohm-meter or continuity tester to monitor the output contact status.

ACCEPTANCE TESTING
Although Basler Electric performs detailed acceptance testing on all new relays, it is generally
recommended that you perform each of the following acceptance test steps when you receive the relay.
Performing these steps tests each function of the BE1-CDS relay to confirm that no degradation of
performance occurred as a result of shipping.

Test Setup
When performing the test setups (connections) for each of the following steps, refer to Figure 13-1 for
terminal locations.

Test Equipment
Suitable test equipment requires a minimum of two current source elements, two voltage source elements
(for relay power and contact wetting voltage), and circuit monitoring with timing algorithms.
BE1-CDS Testing And Maintenance 13-3
Figure 13-1. BE1-CDS, Rear View, Terminal Connections

Power Up
Purpose: To verify that the relay performs the power-up sequence.
Step 1. Apply voltage to input power terminals A2 and A3. Table 13-1 shows the appropriate voltage
for each relay style.
Table 13-1. Voltage Input
Style Number Voltage Input
BE1-CDS2 2 0 - x x x x x x L x x x x x 24 Vdc
BE1-CDS2 2 0 - x x x x x x Y x x x x x 48/125 Vac/dc
BE1-CDS2 2 0 - x x x x x x Z x x x x x 125/250 Vac/dc

Step 2. Verify that the Power LED is ON, and that characters are displayed on the HMI display (if
option Y - 6 pushbutton HMI with LCD display is selected). Upon power-up, the relay will
perform a brief self test.
During this brief test, all front panel LEDs will flash momentarily, the display will indicate each
step of the self test, relay model, software version and then settle into the default display
screen. Contact Basler Electric, Customer Service if anything appears out of the ordinary or if
the LCD code error messages appear.

Communications
Purpose: To verify that the BE1-CDS relay communicates through all ports.
Reference Commands: ACCESS, EXIT
To communicate with the BE1-CDS220 through any of the three ports, you may use either a VT-100
terminal or a personal computer (PC) with a serial port and suitable communications software. The relay
communication default settings are:
• Baud Rate = 9600 bps
• Data Bits = 8
• Stop Bit =1
• Parity = None
• Flow Control = Xon/Xoff.

13-4 Testing And Maintenance BE1-CDS


Please see appendix D for more information on Terminal and HyperTerminal setups for Windows 3.1,
Windows 95, and Windows 98.
Step 1. If you have a relay with option Y (6-pushbutton HMI with LCD display), continue, otherwise go
to Step 2. Depress the up-arrow pushbutton twice to get to the top level of the menu tree.
Depress the left or right-arrow pushbuttons until the \SETUP\GENERAL SETTINGS screen
appears. Next, depress the down-arrow pushbutton two times to get to the sublevel menu
\SETUP \COM \COM0 screen. With the right-arrow pushbutton, scroll one screen to the right.
These are the settings for the relay rear RS-232 (COM1) port. Verify that the baud rate is 9600
bps.
Step 2. Connect the serial cable between the terminal or PC and the rear RS-232 port (COM1) on the
relay.
Step 3. Initiate the communication program for your computer/terminal.
Step 4. Transmit the command ACCESS= (you may use the shortcut keystrokes and just enter a=).
RESULT: The relay should respond with ACCESS GRANTED: GLOBAL.
Step 5. Transmit EXIT.
Step 6. Repeat steps 1, 2, and 3 for the front RS-232 port (COM0).
Step 7. Connect the male end of the terminal cable to the RS-232 port on a RS-232/485 converter box.
Connect the RS-485 output of the converter box to the relay RS-485 terminals (COM2) and
repeat steps 1, 2 and 3.

Style Number And Serial Number Verification


Purpose: To verify that the BE1-CDS relay model number, style number, and current software program
version matches the unit/unit labels.
Reference Commands: RG-VER
Step 1. Through any communications port, transmit the command RG-VER. The BE1-CDS relay
should respond with the model number, style number, application program version and date,
DSP program version and date, boot program version and date, and the relay serial number.
Verify that all reported data is current, appropriate, and matches the label on the relay front
panel.

IRIG Verification
Purpose: To verify that the BE1-CDS relay acquires and updates IRIG time and date information.
Reference Commands: RG-DATE, RG-TIME
Step 1. Connect a suitable IRIG source to relay terminals D1 and D2.
Step 2. Upon receiving the IRIG signal, the relay clock will be updated with the current time, day, and
month. Verify this on screen \STAT\SCRNS\SCRN on the front panel HMI or by sending the
RG-TIME and RG-DATE commands to the relay through any communications port.

NOTE
The following tests may be skipped if it is critical to expedite the installation of this device.
The commissioning tests later in this Section overlap these tests and verify proper contact
sensing input and control output changes.

Contact Sensing Inputs And Control Outputs


Purpose: To verify that the BE1-CDS relay senses hardware inputs and activates contact outputs.
Reference Commands: ACCESS, CO-OUT, CS-OUT, EXIT, RG-STAT

BE1-CDS Testing And Maintenance 13-5


NOTE
Each BE1-CDS relay is delivered with the eight sensing jumpers installed for operation in
the lower end of the control voltage range (pins 1 and 2 shorted). For contact sensing
inputs at the upper end of the control voltage range, change the jumpers to short pins 2
and 3 or completely remove the jumper. For more information see Section 12,
Installation, Contact Sensing Input Jumpers.

Step 1. Verify that the position of the contact sensing jumpers is correct before applying wetting
voltage to any input contacts.
Step 2. Use Table 13-2 as a reference. Apply an external voltage source above the appropriate
voltage turn-on range listed in Table 13-2 but below the power supply maximum voltage to
contact sensing inputs IN1, IN2, IN3, IN4, IN5, IN6, IN7, and IN8.
Table 13-2. Input Contact Wetting Voltage
Nominal Control Turn-On Range
Voltage (Range) Pin 1 - Pin 2 Pin 2 - Pin 3
24 Vdc (17 to 32 Vdc) 13 to 19 Vdc N/A
48/125 Vac/Vdc 26 to 38 Vdc 69 to 100 Vdc
(35 to 150 Vdc/55 to 135 Vac)
125/250 Vac/Vdc 69 to 100 Vdc 138 to 200 Vdc
(90 to 300 Vdc/90 to 270 Vac)
Step 3. To verify that all inputs have been detected, transmit the command RG-INPUT to retrieve
INPUT (12345678) information or, alternatively, transmit the command RG-STAT and review
the response at the tail end of the line INPUT (12345678). You may also view the input status
on HMI screen 1.4.1, \STAT\OPER\INPUT.
Step 4. Transmit the commands ACCESS=, CS-OUT=ENA, CO-OUT=ENA, EXIT, and YES to enable
the output control override capability of the relay in order to pulse each output contact.

NOTE
If your relay is supplied with the HMI option, skip steps 5 and 6 and proceed directly to
Step 7.

Step 5. Using Table 13-3 as a guide, transmit the commands listed and verify that the appropriate
output contacts change state. When the operate command is transmitted, the corresponding
output changes state for 200 milliseconds and returns to the normal state. An ohm-meter or
continuity tester may be used to monitor the output contacts. Remember, you have to gain
access (as in Step 4) before you begin issuing commands and again if the access time-out
expires.

Step 6. If desired, you may disable the control override capability by transmitting the commands
ACCESS=, CS-OUT=DIS, CO-OUT=DIS, EXIT, and YES to the relay.
Table 13-3. Output Control Override Commands
Output Terminals Commands
ALARM (N.C.) C1 and C2 CS-OUTA=P,CO-OUTA=P
OUT1 (N.O.) C3 and C4 CS-OUT1=P,CO-OUT1=P
OUT2 (N.O.) C5 and C6 CS-OUT2=P,CO-OUT2=P
OUT3 (N.O.) C7 and C8 CS-OUT3=P,CO-OUT3=P
OUT4 (N.O.) C9 and C10 CS-OUT4=P,CO-OUT4=P
OUT5 (N.O.) C11 and C12 CS-OUT5=P,CO-OUT5=P
OUT6 (NC/NO) C13, C14, and C15 CS-OUT6=P,CO-OUT6=P

NOTE

13-6 Testing And Maintenance BE1-CDS


If your relay is not supplied with the front panel HMI option, skip Steps 7 through 10 and
proceed to the Current Circuit Verification test.

Step 7. From the HMI keypad, navigate to the screen \CTRL\OUT (Output Control Override) to
override control of the outputs via the keypad.
Step 8. Once you have accessed the screen, press the EDIT pushbutton. Select an output to override
by using the left/right arrow pushbuttons. Once selected, use the up/down arrow pushbuttons
to choose the type of action (P, 1, or 0) for the selected contact output. Select the pulse (P)
action for the alarm contact (A). Pressing the EDIT pushbutton again will force the alarm
output contact action.
Step 9. Verify that the sequence of events recorder logged the events by sending the command RS-2
to the relay (requesting the last two events it logged). The close-open pulse action should be
listed as two separate events.
Step 10. Repeat Step 8 for all desired output contacts, and then verify that the sequence of events
recorder logged the events.

Current Circuit Verification


Purpose: To verify that the relay internal CT circuits accurately measures currents and polarities.
Reference Commands: M-I, SG-TARG, SG-TRIGGER, RS
Step 1. Connect in series, one current
source to terminals B1, B2 (IA1),
B3, B4 (IB1), B5, B6 (IC1), B7, B8 180 Degrees
(IG if present), B10, B9 (IA2), B12, Circuit Current Current
Monitor Source 1 Source 2
B11 (IB2), B14, B13 (IC2). See
Figure 13-2. Notice that CT
circuit 2 polarities are reversed.
D2857-07.vsd
05-05-00

I A1 I B1 I C1 IG I A2 I B2 I C2

B1 B3 B5 B7 B9 B11 B13 B15

B2 B4 B6 B8 B10 B12 B14 B16

I A1 I B1 I C1 IG I A2 I B2 I C2
Typical Jumpers

Figure 13-2. Series Current Connection Diagram

Step 2. Apply 5 amperes of current to 5 ampere rated CT inputs (or 1 ampere to 1 ampere rated CT
inputs).
Step 3. Transmit the command M1-I to the relay, or navigate to the front panel HMI screen
\METER\CRNT\CT_1\I_MEAS (3.1.1.1) and \METER\CRNT\CT_1\I_CALC (3.1.1.2) and verify
the values listed in Table 13-4.
Table 13-4. Circuit 1 Metering Quantities
CT secondary IA1, IB1, And IC1 IN1 IQ1
5.0 A ( ± 1%) @ 0 15.0 A ( ± 1%) @ 0° 0.0 A ( ± 1%)
o
5A

1.0 A ( ± 1%) @ 0 3.0 A ( ± 1%) @ 0° 0.0 A ( ± 1%)


o
1A

BE1-CDS Testing And Maintenance 13-7


Step 4. Transmit the command M2-I to the relay, or navigate to the front panel HMI screen
\METER\CRNT\CT_2\I_MEAS (3.1.2.1) and \METER\CRNT\CT_2\I_CALC (3.1.2.2) and verify
the values listed in Table 13-5.
Table 13-5. Circuit 2 Metering Quantities
CT secondary IA2, IB2, And IC2 IN2 IQ2
5.0 A ( ± 1%) @ 180 15.0 A ( ± 1%) @ 180° 0.0 A ( ± 1%)
o
5A

1.0 A ( ± 1%) @ 180 3.0 A ( ± 1%) @ 180° 0.0 A ( ± 1%)


o
1A

Step 5. If the unit has an independent ground input, transmit the command M-IG to the relay, or
navigate to the screen \METER\CRNT\GND\I_MEAS (3.1.3.1) on the optional front panel HMI
and verify that IG=5.0 A ( ± 1%) @ 0 (for a 5 A secondary rated CT inputs), or 1.0 A ( ± 1%)
o

o
@ 0 (for a 1 A secondary rated CT inputs).
Step 6. Remove current from the relay.

COMMISSIONING TESTING
Because the commissioning of this relay may be a new installation or a retrofit, special precautions should
be taken to ensure that all tests are performed with safety as the utmost concern. Any CT circuit signals
that are routed through this device as part of a protection scheme including discrete relays or as a stand-
alone device, should be shorted and isolated from this relay during these tests until the final instrument
transformer current circuit check.
If this relay is being installed in an existing installation, please be aware of the equipment monitoring
features of this device, especially if the monitoring logic will be utilized. Make note of any pretest operation
levels, duty levels, etc. on existing equipment (e.g. – breakers or transformers). As the user, you may
set the initial values into the relay to duplicate monitored values in the existing equipment.
Because of the multifunction capabilities of the BE1-CDS relay, it may be necessary to temporarily disable
some of the protective elements while testing others or to change setting logic to test a specific function.
Always remember to enable these functions and install operation settings before placing the relay in
service. To guard against placing the relay in service with unwanted operational or logic settings, it is a
good practice to save a copy of the original setting file before the testing process begins. When testing is
complete, the saved copy could then be loaded into the relay which would guarantee that no setting
changes or testing modifications would remain in the relay.
To assist you in the commissioning testing of this relay, refer to the previous paragraphs in this Section on
Testing And Troubleshooting Aids, and Section 6, Reporting and Alarm Functions for various ways to
retrieve or interpret reporting status, alarms, and targets.
Refer to the other Sections of the instruction manual for assistance on any particular functions of the relay.
If you require further assistance, contact Basler Electric field application personnel or the factory.

Protection And Control Function Verification


Before placing the relay in service, it should be verified that the desired protection and control functions
are enabled and connected to the correct CT input circuits, that the programmable logic settings provide
the proper interconnection of these functions, and that each has the desired set points. This can be
accomplished by a detailed review of the settings as read out of the relay before placing it in service. Or,
it may be desirable to verify the settings by test.

Important
Because this is a numerical relay whose characteristics are defined by software, it is not
necessary to verify that each phase element of a protective function responds. By testing
a single phase of each function and varying the phase input tested for each function, it is
possible to verify the entire relay. For example, to verify the phase overcurrent elements,
one could test phase A for the 51P element, and phase B for the 50TP element, etc.

13-8 Testing And Maintenance BE1-CDS


Before testing each protection and control function, the logic settings should be examined to determine:
• The mode setting for the function so that you know what the relay is supposed to do.
• Which virtual output logic expressions contain the logic variables that represent the outputs of the
function under test so that the proper contact can be monitored.
• The input logic expressions for the function under test (especially the block input because it
renders the function disabled if the block input is asserted).
• That the fault reporting settings are properly set such that the relay properly indicates pickup and
trip states and records targets. These settings are set from the ASCII command interface using
the SG-TRIGGER and SG-TARG setting commands. See Section 6, Reporting and Alarm
Functions, Fault Reporting Functions, for more details.

Testing Phase Differential Protection With Internal Compensation


The internal phase and zero sequence compensation features of the relay can combine the currents from
multiple CT input circuits and/or subtract out the zero sequence components before their use by the phase
differential function. Thus, the testing of this function with the internal compensation features can be
somewhat complicated. For this reason, a detailed test procedure is provided for verifying the set points
of this function with internal compensation. See Sidebar 13-1 in this Section for more information on how
the internal compensation features work.
Step 1. Record settings for the following tests.
The settings for the following tests should be recorded before starting the test. You will refer to these
settings throughout the test procedure.
• Angle Compensation and Ground Source compensation can be determined by matching the SG-
CT or Screen 6.3.1.1 settings with Table 3-2 in Section 3 and reading the right two columns to
determine what angle compensation is applied.
• Tap Compensation settings in each setting group can be determined from screens 5.x.1.2 or
5.x.1.3 on the optional HMI. Or, the S#-TAP87 settings from the ASCII command interface if
manual tap adjust is used. If automatic tap adjust is used, it will be necessary to use the settings
and equations 4-1 and 4-2 from Section 4, Protection And Control Functions, Differential
Protection.
• Restrained Minimum Pickup, Slope, and Unrestrained Pickup settings can be determined from
screens 5.x.1.1 on the optional HMI. Or, the S#-87 settings from the ASCII command interface.
Alternatively, all of these parameters can be determined from reading the Current Check Record provided
by the Differential Alarm Function. To use this method, use the commands in Table 13-6.
Table 13-7 lists the currents that will be seen by each 87 phase differential element after phase and zero
sequence compensation. This table is based upon the internal compensation chart in Section 3, Input And
Output Functions, Input Current. Examination of this table shows that for most cases, test current
injection using only one or two current sources will result in currents being applied to more than one 87
Phase element. See Sidebar 13-1 for more information on testing and compensated currents. The
following test procedures will enable you to determine the test points and which phases will be tested.

BE1-CDS Testing And Maintenance 13-9


Sidebar 13-1. Testing With Internal Phase And I0 Compensation

When the internal phase and zero sequence compensation feature of the BE1-CDS is used, confusing
test results can occur unless the compensation is taken into consideration. The best way to illustrate how
the BE1-CDS relay performs internal phase compensation and thus, what to expect under test situations,
is by looking at an application example. The application below shows a delta/grounded-wye transformer
with wye connected CTs. The currents flowing into and out of the transformer and reflected through the
CTs are shown for this configuration.
IC 1 -I A 1 I C2

C c
H3 X3

IC 1

I B 1 -I C 1 IB 2

B b
H2 X2

IB 1

IA 1 -IB 1 IA 2

A a
H1 X1

IA 1

BE1-CDS
IA 1 -I B 1 IA2
IA 1 ’-IB 1 ’ - (0) IA 2 ’ - (IB 2 ’)
I B 1 -I C 1 IB2
IB 1 ’-IC 1 ’ - (0) I B 2 ’ - (IC 2 ’)
I C 1 -IA 1 IC2
IC 1 ’-IA 1 ’ - (0) IC 2 ’ - (IA 2 ’)

D2857-08.vsd
05-05-00
INTERNAL PHASE
COMPENSATION

Isolating the box marked BE1-CDS, we see that, for the A phase 87 element, the relay subtracts the
measured Ib from the measured Ia on the transformer wye side to compensate for the measured IA-IB
delta currents that are flowing in the line phases on the transformer delta side. Remember that these
currents are the compensating currents when the relay is in service for this application.
Under a test scenario, any set of balanced, 180° out of phase, single-phase, input currents that we apply
to the two phase A connections will result in balanced currents in the 87A element. But, the 87C element
will also see a compensating -IA2 current that will cause it to operate. Table 13-7 shows the compensated
currents that with the various compensation settings will be applied to each 87 phase element.
The relay can also remove the zero sequence component of the current if a zero sequence source exists
on an input that is not delta compensated. When this compensation is applied during testing, it has a
similar effect as subtracting I0 from the phases not under test. This also causes them to operate.
It is this compensating effect that you must be aware of in order to understand what operations and
targets to expect when testing a BE1-CDS relay with internal phase compensation settings. To prevent
unwanted phases from tripping during the slope test which starts from a balanced condition, delta test
injection connections are recommended as shown in Table 13-11 and Figures 13-4 to 13-11.
Tables 13-8 through 13-10 also show what equation to use to calculate the test points for the minimum
pickup (minpu) and slope tests for each possible configuration of compensation.

13-10 Testing And Maintenance BE1-CDS


Table 13-6. Commands To Initiate A Differential Check Record
Command Purpose
A=<reports password if used> Gain write access to the relay
CS-GROUP=0; CO-GROUP=0 Override logic and make sure that relay is in group 0
RA-DIFF=TRIG; Trigger current check record
RA-DIFF Read record and record for group 0
CS-GROUP=1; CO-GROUP=1 Make sure that relay is in group 1
RA-DIFF=TRIG; Trigger current check record
RA-DIFF Read record and record for group 1
CS-GROUP=2; CO-GROUP=2 Make sure that relay is in group 2
RA-DIFF=TRIG; Trigger current check record
RA-DIFF Read record and record for group 2
CS-GROUP=3; CO-GROUP=3 Make sure that relay is in group 3
RA-DIFF=TRIG; Trigger current check record
RA-DIFF Read record and record for group 3
CS-GROUP=0; CO-GROUP=0 Return relay to group 0
CS-GROUP=L; CO-GROUP=L Return setting group control to logic control
E Exit

NOTE
Table 13-7 is based on internal phase angle compensation and not CT compensation.

Table 13-7. Phase and Zero Sequence Compensated Currents


Angle Compensation And 87A Element 87B Element 87C Element
Ground Source Settings
CT1 CT2 CT1 CT2 CT1 CT2 CT1 CT2
WYE (NONE) WYE (NONE) IA IA IB IB IC IC
WYE (NONE) WYE G IA IA-I0 IB IB-I0 IC IC-I0
WYE (NONE) DAB IA (IA-IB)/√3 IB (IB-IC)/√3 IC (IC-IA)/√3
WYE (NONE) DAC IA (IA-IC)/√3 IB (IB-IA)/√3 IC (IC-IB)/√3
WYE G WYE (NONE) IA-I0 IA IB-I0 IB IC-I0 IC
WYE G WYE G IA-I0 IA-I0 IB-I0 IB-I0 IC-I0 IC-I0
WYE G DAB IA-I0 (IA-IB)/√3 IB-I0 (IB-IC)/√3 IC-I0 (IC-IA)/√3
WYE G DAC IA-I0 (IA-IC)/√3 IB-I0 (IB-IA)/√3 IC-I0 (IC-IB)/√3
DAB WYE (NONE) (IA-IB)/√3 IA (IB-IC)/√3 IB (IC-IA)/√3 IC
DAB WYE G (IA-IB)/√3 IA-I0 (IB-IC)/√3 IB-I0 (IC-IA)/√3 IC-I0
DAB DAB (IA-IB)/√3 (IA-IB)/√3 (IB-IC)/√3 (IB-IC)/√3 (IC-IA)/√3 (IC-IA)/√3
DAB DAC (IA-IB)/√3 (IA-IC)/√3 (IB-IC)/√3 (IB-IA)/√3 (IC-IA)/√3 (IC-IB)/√3
DAC WYE (NONE) (IA-IC)/√3 IA (IB-IA)/√3 IB (IC-IB)/√3 IC
DAC WYE G (IA-IC)/√3 IA-I0 (IB-IA)/√3 IB-I0 (IC-IB)/√3 IC-I0
DAC DAB (IA-IC)/√3 (IA-IB)/√3 (IB-IA)/√3 (IB-IC)/√3 (IC-IB)/√3 (IC-IA)/√3
DAC DAC (IA-IC)/√3 (IA-IC)/√3 (IB-IA)/√3 (IB-IA)/√3 (IC-IB)/√3 (IC-IB)/√3

Phase Differential Restrained Minimum Pickup Trip


The test current will be a function of the internal angle and zero sequence compensation and the tap
compensation. For the following test, you will apply a single-phase test current to one CT input circuit at a

BE1-CDS Testing And Maintenance 13-11


time. It is only necessary to apply one phase per input to verify response and correctly entered settings.
For example, apply A phase for CT circuit 1 and 2 for group 0, B phase for CT circuit 1 and 2 for group 1,
etc. to verify all phases and all set points.
Step 2. Calculate test points for minimum-pickup test.
• Calculate the test points using the compensation settings recorded in Step 1 and the appropriate
equations shown in Tables 13-8 through 13-10. Record the calculated test point for each setting
group before running the test.
• Record the phases that will respond to the test.
Table 13-8. Differential Element Minpu Response To IA Test Current
Element
CT Input Compensation
Angle Comp Ground Source 87A 87B 87C
Wye (None) 0=No Minpu*Tap NA NA
Wye (None) 1=Yes 1.5*Minpu*Tap 3*Minpu*Tap 3*Minpu*Tap
DAB NA √3*Minpu*Tap NA √3*Minpu*Tap
DAC NA √3*Minpu*Tap √3*Minpu*Tap NA
Table 13-9. Differential Element Minpu Response To IB Test Current
CT Input Compensation Element
Angle Comp Ground Source 87A 87B 87C
Wye (None) 0=No NA Minpu*Tap NA
Wye (None) 1=Yes 3*Minpu*Tap 1.5*Minpu*Tap 3*Minpu*Tap
DAB NA √3*Minpu*Tap √3*Minpu*Tap NA
DAC NA NA √3*Minpu*Tap √3*Minpu*Tap
Table 13-10. Differential Element Minpu Response To IC Test Current
CT Input Compensation Element
Angle Comp Ground Source 87A 87B 87C
Wye (None) 0=No NA NA Minpu*Tap
Wye (None) 1=Yes 3*Minpu*Tap 3*Minpu*Tap 1.5*Minpu*Tap
DAB NA NA √3*Minpu*Tap √3*Minpu*Tap
DAC NA √3*Minpu*Tap NA √3*Minpu*Tap

Step 3. Test minimum pickup.


Slowly ramp up test current until the relay trips. Monitor an appropriate contact per the logic settings and
the trip LED. Record the value. Record if the proper phases targeted and if the test was passed. The
accuracy should be ±4% or 0.75 milliamperes for 5 ampere units and ±4% or 25 milliamperes for 1
ampere units.

Phase Differential Restrained Slope Trip


This test will verify the percentage restraint characteristic. Since each current input circuit and phase
protective element was verified in the preceding test, it is only necessary to test and verify the slope
characteristic on one phase element for each setting group.
The restrained slope test requires that you start from a balanced condition. To create the Iop
(differential) current, you will vary one test current upward or downward from this balanced condition. The
test point at which a trip should occur will depend upon whether you set the relay to operate on percent of
maximum restraint current or percent of average restraint current. It will also depend upon whether the
Iop is to be developed by increasing or decreasing one current source from balance. See Figure 13-3 for
details.

Step 4. Calculate test starting point (balanced) for restrained slope test.
Step 4-1. Select and record the appropriate test connection from Table 13-11.

13-12 Testing And Maintenance BE1-CDS


Step 4-2. Calculate the balanced starting test currents that are to be applied to each input circuit of the
relay. Use the appropriate equation from Table 13-11, Test Current, and record values before
starting the test. The equations provide a convenient starting balance point at two times tap.
Do this for each setting group.
Step 4-3. Check that the starting (balanced) test current at two times tap is not above the maximum
continuous current rating of the relay. If it is, adjust both starting test currents downward until
both are below this level. Use the same adjustment factor on both currents such that they
remain balanced.

CDS Restraint Characteristic

y 1AI

Iop
y 1MD
y 1AD
slope

1
y 1MI

MIN PU

1 2 3 4

Ir

y 1MD = I1 decreasing with maximum restraint Iop = |I1 - I2|

y 1MI = I1 increasing with maximum restraint Ir = max(|I1|,|I2|) for max restraint


y 1AD = I1 decreasing with average restraint Ir = (|I1|+|I2|)/2 for average restraint

y 1AI = I1 increasing with average restraint

Condition Restraint Min PU? Trip If Min PU Trip If Slope

I1 = I2
Maximum I2<min pu/slope I1 = I2 - min pu I1 = I2*(1 - slope)
Decrease I1

I1 = I2
Maximum I2<min pu(1/slope - 1) I1 = I2 + min pu I1 = I2/(1 - slope)
Increase I1

I1 = I2
Average I2<min pu(1/slope + 1/2) I1 = I2 - min pu I1 = I2(1 - (2*slope/(2+slope)))
Decrease I1

I1 = I2
Average I2<min pu(1/slope - 1/2) I1 = I2 + min pu I1 = I2(1 + (2*slope/(2-slope)))
Increase I1

D2857-09.vsd
10-08-99

Figure 13-3. Test Currents For Restrained Trip Test

BE1-CDS Testing And Maintenance 13-13


Table 13-11. Starting Test Currents And Test Connections For Slope Test
Angle/I0 Comp. Test Current Test Con. Element
CT1 CT2 CT1 CT2 Figure 87A 87B 87C
WYE WYE 2*tap 2*tap 13-4, A Y N N
WYE WYE 2*tap 2*tap 13-4, B N Y N
WYE WYE 2*tap 2*tap 13-4, C N N Y
WYE WYE/G 2*tap 2*tap 13-5, A Y Y N
WYE WYE/G 2*tap 2*tap 13-5, B N Y Y
WYE WYE/G 2*tap 2*tap 13-5, C Y N Y
WYE DAB 2*tap 2*√3*tap 13-6, A Y N Y
WYE DAB 2*tap 2*√3*tap 13-6, B Y Y N
WYE DAB 2*tap 2*√3*tap 13-6, C N Y Y
WYE DAC 2*tap 2*√3*tap 13-7, A Y Y N
WYE DAC 2*tap 2*√3*tap 13-7, B N Y Y
WYE DAC 2*tap 2*√3*tap 13-7, C Y N Y
WYE/G WYE 2*tap 2*tap 13-5, A Y Y N
WYE/G WYE 2*tap 2*tap 13-5, B N Y Y
WYE/G WYE 2*tap 2*tap 13-5, C Y N Y
WYE/G WYE/G 2*tap 2*tap 13-5, A Y Y N
WYE/G WYE/G 2*tap 2*tap 13-5, B N Y Y
WYE/G WYE/G 2*tap 2*tap 13-6, C Y N Y
WYE/G DAB 2*tap 2*√3*tap 13-6, A Y N Y
WYE/G DAB 2*tap 2*√3*tap 13-6, B Y Y N
WYE/G DAB 2*tap 2*√3*tap 13-6, C N Y Y
WYE/G DAC 2*tap 2*√3*tap 13-7, A Y Y N
WYE/G DAC 2*tap 2*√3*tap 13-7, B N Y Y
WYE/G DAC 2*tap 2*√3*tap 13-7, C Y N Y
DAB WYE 2*√3*tap 2*tap 13-8, A Y N Y
DAB WYE 2*√3*tap 2*tap 13-8, B Y Y N
DAB WYE 2*√3*tap 2*tap 13-8, C N Y Y
DAB WYE/G 2*√3*tap 2*tap 13-8, A Y N Y
DAB WYE/G 2*√3*tap 2*tap 13-8, B Y Y N
DAB WYE/G 2*√3*tap 2*tap 13-8, C N Y Y
DAB DAB 2*√3*tap 2*√3*tap 13-4, A Y N Y
DAB DAB 2*√3*tap 2*√3*tap 13-4, B Y Y N
DAB DAB 2*√3*tap 2*√3*tap 13-4, C N Y Y
DAB DAC 2*√3*tap 2*√3*tap 13-9, A N Y Y
DAB DAC 2*√3*tap 2*√3*tap 13-9, B Y N Y
DAB DAC 2*√3*tap 2*√3*tap 13-9, C Y Y N
DAC WYE 2*√3*tap 2*tap 13-10, A Y Y N
DAC WYE 2*√3*tap 2*tap 13-10, B N Y Y
DAC WYE 2*√3*tap 2*tap 13-10, C Y N Y
DAC WYE/G 2*√3*tap 2*tap 13-10, A Y Y N
DAC WYE/G 2*√3*tap 2*tap 13-10, B N Y Y
DAC WYE/G 2*√3*tap 2*tap 13-10, C Y N Y
DAC DAB 2*√3*tap 2*√3*tap 13-11, A N Y Y
DAC DAB 2*√3*tap 2*√3*tap 13-11, B Y N Y
DAC DAB 2*√3*tap 2*√3*tap 13-11, C Y Y N
DAC DAC 2*√3*tap 2*√3*tap 13-4, A Y N Y
DAC DAC 2*√3*tap 2*√3*tap 13-4, B N Y Y
DAC DAC 2*√3*tap 2*√3*tap 13-4, C Y Y N

13-14 Testing And Maintenance BE1-CDS


A B C
B1 B9 B1 B9 B1 B9

IA1 IA1 IA1


IA2 IA2 IA2
B2 B10 B2 B10 B2 B10

B3 B11 B3 B11 B3 B11

IB1 IB1 IB1


IB2 IB2 IB2
B4 B12 B4 B12 B4 B12

B5 B13 B5 B13 B5 B13

IC1 IC1 IC1


IC2 IC2 IC2
B6 B14 B6 B14 B6 B14

D2857-26.vsd
05-05-00

Figure 13-4. Test Connection Diagrams For Table 13-11

A B C
B1 B9 B1 B9 B1 B9

IA1 IA1 IA1


IA2 IA2 IA2
B2 B10 B2 B10 B2 B10

B3 B11 B3 B11 B3 B11

IB1 IB1 IB1


IB2 IB2 IB2
B4 B12 B4 B12 B4 B12

B5 B13 B5 B13 B5 B13

IC1 IC1 IC1


IC2 IC2 IC2
B6 B14 B6 B14 B6 B14
D2857-27.vsd
05-05-00

Figure 13-5. Test Connection Diagrams For Table 13-11

A B C
B1 B9 B1 B9 B1 B9

IA1 IA1 IA1


IA2 IA2 IA2

B2 B10 B2 B10 B2 B10

B3 B11 B3 B11 B3 B11

IB1 IB1 IB1


IB2 IB2 IB2
B4 B12 B4 B12 B4 B12

B5 B13 B5 B13 B5 B13

IC1 IC1 IC1


IC2 IC2 IC2
B6 B14 B6 B14 B6 B14

D2857-28.vsd
05-05-00

Figure 13-6. Test Connection Diagrams For Table 13-11

BE1-CDS Testing And Maintenance 13-15


A B C
B1 B9 B1 B9 B1 B9

IA1 IA1 IA1


IA2 IA2 IA2
B2 B10 B2 B10 B2 B10

B3 B11 B3 B11 B3 B11

IB1 IB1 IB1


IB2 IB2 IB2
B4 B12 B4 B12 B4 B12

B5 B13 B5 B13 B5 B13

IC1 IC1 IC1


IC2 IC2 IC2
B6 B14 B6 B14 B6 B14

D2857-29.vsd
05-05-00

Figure 13-7. Test Connection Diagrams For Table 13-11

A B C
B1 B9 B1 B9 B1 B9

IA1 IA1 IA1


IA2 IA2 IA2
B2 B10 B2 B10 B2 B10

B3 B11 B3 B11 B3 B11

IB1 IB1 IB1


IB2 IB2 IB2
B4 B12 B4 B12 B4 B12

B5 B13 B5 B13 B5 B13

IC1 IC1 IC1


IC2 IC2 IC2
B6 B14 B6 B14 B6 B14
D2857-30.vsd
05-05-00

Figure 13-8. Test Connection Diagrams For Table 13-11

A B C
B1 B9 B1 B9 B1 B9

IA1 IA1 IA1


IA2 IA2 IA2

B2 B10 B2 B10 B2 B10

B3 B11 B3 B11 B3 B11

IB1 IB1 IB1


IB2 IB2 IB2

B4 B12 B4 B12 B4 B12

B5 B13 B5 B13 B5 B13

IC1 IC1 IC1


IC2 IC2 IC2

B6 B14 B6 B14 B6 B14


D2857-31.vsd
05-05-00

Figure 13-9. Test Connection Diagrams For Table 13-11

13-16 Testing And Maintenance BE1-CDS


A B C
B1 B9 B1 B9 B1 B9

IA1 IA1 IA1


IA2 IA2 IA2

B2 B10 B2 B10 B2 B10

B3 B11 B3 B11 B3 B11

IB1 IB1 IB1


IB2 IB2 IB2
B4 B12 B4 B12 B4 B12

B5 B13 B5 B13 B5 B13

IC1 IC1 IC1


IC2 IC2 IC2
B6 B14 B6 B14 B6 B14

D2857-32.vsd
05-05-00

Figure 13-10. Test Connection Diagrams For Table 13-11

A B C
B1 B9 B1 B9 B1 B9

IA1 IA1 IA1


IA2 IA2 IA2

B2 B10 B2 B10 B2 B10

B3 B11 B3 B11 B3 B11

IB1 IB1 IB1


IB2 IB2 IB2
B4 B12 B4 B12 B4 B12

B5 B13 B5 B13 B5 B13

IC1 IC1 IC1


IC2 IC2 IC2
B6 B14 B6 B14 B6 B14

D2857-33.vsd
05-05-00

Figure 13-11. Test Connection Diagrams For Table 13-11

NOTE
It is necessary to convert the slope setting from percent to decimal for use in the
equations used in Step 4-4.

Step 4-4. Check that the starting (balanced) test current will not result in a minimum pickup trip. Use the
appropriate equation under the column heading Min PU? in Figure 13-3. If it will result in a
minimum pickup, adjust both starting test currents upward until they are above minimum
pickup. Use the same adjustment factor on both currents such that they remain balanced.
Step 4-5. Record the phases that are expected to respond.
Step 4-6. Verify that the current sources are configured such that they are 180 degrees out of phase with
each other.

Step 5. Calculate test points (restrained trip) for restrained slope test.
The test point at which a trip should occur will depend upon whether you set the relay to operate on
percent of maximum restraint current or percent of average restraint current. It will also depend upon

BE1-CDS Testing And Maintenance 13-17


whether the Iop (differential current) is to be developed by increasing one current source from balance or
by decreasing one current source from balance.
Step 5-1. Use the starting current calculated in Step 4 and the appropriate equation under the column
heading Trip If Slope in Figure 13-3 to calculate the test point for each setting group and record
that point before starting the test.
Step 5-2. Record the phases that are expected to respond.

Step 6. Test the slope for each setting group.

Step 6-1. Slowly ramp the test current on CT input circuit 1 in desired direction until the relay trips.
Step 6-2. Monitor an appropriate contact per the logic settings and the trip LED, and record the trip
values for each setting group.
Step 6-3. Record whether the proper phases targeted and if the test was passed. The accuracy should
be ±4% of the setting or 0.75 milliamperes, whichever is greater, for 5 ampere units and ±4%
or 25 milliamperes, whichever is greater, for 1 ampere units.

Phase Differential Unrestrained Trip


The following test is similar to the restrained minimum pickup test. For this test, you will apply a single
phase test current to one CT input circuit at a time. It is only necessary to apply one phase per input to
verify response and settings correctly entered. For example, apply phase A for CT circuit 1 and 2 for
group 0, phase B for CT circuit 1 and 2 for group 1, etc. to verify all phases and all set points.

Step 7. Calculate test points for the unrestrained test.


Step 7-1. Calculate the test points using the compensation settings recorded in Step 1 and the
appropriate equations shown in Tables 13-8 through 13-10. In this case, substitute the
unrestrained pickup setting for the restrained minimum pickup setting in the equations. Record
the calculated test point for each setting group before running the test.
Step 7-2. Record the phases that will respond to the test.

NOTE
Depending upon your relay settings, it may be necessary to disable the restrained
differential element to test the unrestrained differential element.

Step 8. Begin the unrestrained pickup test.


Step 8-1. Slowly ramp up the test current until the relay trips.
Step 8-2. Monitor an appropriate contact per the logic settings and the trip LED, and record the value.
Step 8-3. Record whether the proper phases targeted and if the test was passed. The accuracy should
be ±3% of the setting or 0.75 milliamperes, whichever is greater, for 5 ampere units and ±3%
of the setting or 25 milliamperes, whichever is greater, for 1 ampere units.

Verify Other Set Points as Appropriate


Consult Functional Testing in this Section of the manual for guidelines on how to test other functions to
verify set points of other protection and control functions.

Digital I/O Connection Verification

Contact Sensing Inputs


Purpose: To verify contact sensing input settings and connections
Reference Commands: SN-IN, SG-IN

13-18 Testing And Maintenance BE1-CDS


Step 1. Verify contact sensing input settings.
• Transmit the SN-IN1 command to verify the input 1 user-defined name, TRUE label, and FALSE
label.
• Transmit the SN-IN1 command for each of the remaining seven contact sensing inputs that are
used in your system. Add the number of an input to the SN-IN command to check that input’s
name and labels.
• Verify the recognition and debounce settings for each contact sensing input by using the SG-IN
command. When the SG-IN command is transmitted, the relay responds with the recognition and
debounce settings for each input. Reported settings use the format SG-IN1=recognition,
debounce.
Step 2. Verify contact sensing input connections.
• Operate (or cause to operate) each contact associated with all contact sensing inputs that are
used in your system. You may operate them individually and verify that the BE1-CDS recognized
the contact operation or operate all of them and then verify the operation.
To verify that all inputs have been recognized, transmit the command RG-INPUT to retrieve
INPUT (12345678) information or, alternatively, transmit the command RG-STAT and review the
response at the tail end of the line INPUT (12345678). You may also view the input status on HMI
screen 1.4.1, \STAT\OPER\INPUT.
Output Contacts
Purpose: To verify output settings and connections.
Reference Commands: SN-VO, SL-VO, SG-HOLD
Step 1. Verify output settings.
• Transmit the SN-VOA command to verify the virtual output A user-defined name, TRUE label, and
FALSE label.
• Transmit the SN-VOA command for virtual outputs 1 through 15. Add the number of an output to
the SN-VO command to check that output’s name and labels.
• Transmit the SL-VO command to obtain a list of all virtual outputs and their Boolean logic
equations. Verify that the desired virtual output equations match the reported equations.
• Verify the programmable hold timer setting for each hardware output by transmitting the command
SG-HOLD. The output hold timer setting for each output is reported as enabled (1) or disabled
(0).
Step 2. Verify output connections.
• Output logic override control cannot be accessed from the HMI. Transmit the commands
ACCESS=, CS-OUT=ENA, CO-OUT=ENA, EXIT, and YES to enable the output logic control
override capability of the relay in order to operate each output contact.
• Transmit the commands listed in Table 13-12. When the operate command is transmitted, the
corresponding output changes state for 200 milliseconds and returns to the normal state. Monitor
the specific output contacts in whatever manner you require to verify that the output connections
are valid. Remember, you have to gain access before you begin issuing commands and again if
the access time-out expires.
NOTE
In verifying output connections, we pulse the hardware outputs for 200 milliseconds. If
you have a specific output that requires a longer operate time to verify operation,
substitute a 1 or 0 (depending on the output logic) for the P in the commands listed in
Table 13-12. After the output connection is verified, it is important to return the output to
logic control using the commands CS-OUTn=L; CO-OUTn=L <enter>.

• If desired, you may disable the control override capability by transmitting the commands
ACCESS=, CS-OUT=DIS, CO-OUT=DIS, EXIT, and YES to the relay.

BE1-CDS Testing And Maintenance 13-19


Table 13-12. Output Control Override Commands
Output Terminals Commands
ALARM (N.C.) C1 and C2 CS-OUTA=P,CO-OUTA=P
OUT1 (N.O.) C3 and C4 CS-OUT1=P,CO-OUT1=P
OUT2 (N.O.) C5 and C6 CS-OUT2=P,CO-OUT2=P
OUT3 (N.O.) C7 and C8 CS-OUT3=P,CO-OUT3=P
OUT4 (N.O.) C9 and C10 CS-OUT4=P,CO-OUT4=P
OUT5 (N.O.) C11 and C12 CS-OUT5=P,CO-OUT5=P
OUT6 (NC/NO) C13, C14, and C15 CS-OUT6=P,CO-OUT6=P

Virtual 43 Switches
Purpose: To verify the operation, labels, and logic settings of the virtual 43 switches.
Reference Commands: SN-43, SL-43, RG-43STAT, RG-STAT, CS/CO-43
NOTE
If virtual 43 switches are not used, skip the eight associated steps and go to the next test.
Step 1. Transmit the SN-43 command to verify the virtual selector switch 43 name, TRUE label, and
FALSE label. This information is reported using the format SN-x43=name,TRUE label,FALSE
label.
Step 2. Repeat Step 1 for virtual selector switches 143 through 743. Use the number of a switch in the
SN-43 command to retrieve name and label information for that switch.
Step 3. Use the SL-x43 command to obtain the logic setting of virtual switches 43 through 743. Logic
settings for virtual switches can also be obtained by using the SL command. Verify that the
desired virtual selector switch setting matches the reported setting.
Step 4. Transmit the RG-43STAT command to obtain the position of the eight virtual selector switches.
Alternately, the virtual selector switch positions can be obtained through the RG-STAT
command or optional HMI screens 2.1.1 through 2.1.8, \CTRL\43\43 through \CTRL\43\743.
Step 5 Obtain write access to the relay by using the ACCESS= command. For each virtual selector
switch enabled in your logic scheme, change the switch position by entering CS-x43 = 1
(TRUE), 0 (FALSE), or P (Pulse) followed by CO-x43=1,0, or P. The syntax of the CS-x43 and
CO-x43 commands must match or the CO-x43 command won’t be executed.
Step 6. Verify each switch position change by using the CO-x43 command or through optional HMI
screens \CTRL\43\43 through \CTRL\43\743.
Step 7. Leave each virtual 43 switch in the desired position for placing the protection and control
system in service.
Step 8. Verify the 43 switch activity by viewing the sequence of events reports with the RS-###
command.

Virtual 101 Switch


Purpose: To verify the operation, label, and logic setting for the 101 switch.
Reference Commands: SB-LOGIC, SL-101, RG-101STAT, RG-STAT, CS/CO-101
Step 1. Verify the breaker label and breaker-closed logic expression with the SB-LOGIC command.
Step 2. Use the SL-101 command to read the logic mode of the 101 switch. The switch is either
enabled (1) or disabled (0).
Step 3. Verify the virtual control switch status by using the RG-101STAT, RG-STAT, or CO-101
commands or optional HMI screens 2.2, \CTRL\BKR.

13-20 Testing And Maintenance BE1-CDS


Step 4. Transmit the command ACCESS= to obtain write access to the relay. Change the switch
position by entering CS-101=T (Trip) or C (Close) followed by CO-101=T (Trip) or C (Close).
The syntax of the CS-101 and CO-101 commands must match or the CO-101 command won’t
be executed.
Step 5. Verify the switch position change as you did in Step 3.
Step 6. Repeat Step 4 to return the 101 switch to the desired position for your application.
Step 7. Verify the 101 switch activity by viewing the sequence of events reports with the RS-###
command.

Reporting And Alarm Functions


Just prior to placing the relay in service, the following reporting and alarm functions should be reset and
verified. For information on how to use the ASCII command interface or the optional front panel HMI to
enter or edit relay settings, refer to Section 10, Human-Machine Interface, and Section 11, ASCII
Command Interface.

Clock Display
Set the real-time clock to the current date and time. If an IRIG input is used, day and time are
automatically synced to the IRIG source. Remember that the IRIG time code signal does not contain the
current year information.
Purpose: To verify that the reporting and alarm functions are set/reset as required for the system
installation.
Reference Commands: RG-TIME, RG-DATE
For clock setting details, refer to Section 6, Reporting And Alarm Functions, Clock, Setting The Clock. To
use the optional front panel HMI, go to screen 1.4.6.

Demand Functions
If the relay Demand Functions feature is enabled, reset the peak current demand registers to zero or an
existing value.
Purpose: To set the demand registers as required for the system installation.
Reference Commands: RD-PI, RD-PI<p>
Refer to Section 6, Reporting And Alarm Functions, Demand Functions, for setting details. To use the
optional front panel HMI, go to screen 4.4.3.

Transformer Monitoring
If the relay Transformer Through-Fault and Duty Monitoring features are enabled, reset the counter and
duty registers to zero or an existing value.
Purpose: To set the transformer counter and duty registers as required for the system installation.
Reference Commands: RT-TFCNTR, RT-DUTY
Refer to Section 6, Reporting And Alarm Functions, Transformer Monitoring, for setting details. To use
the optional front panel HMI, go to screen 4.5.1.

Breaker Monitoring
If the relay Breaker Monitoring feature is enabled, reset the counter and duty registers to zero or an
existing value.
Purpose: To set the breaker counter and duty registers as required for the system installation.
Reference Commands: RB-OPCNTR, RB-DUTY
Refer to Section 6, Reporting And Alarm Functions, Breaker Monitoring, for setting details. To use the
optional front panel HMI, go to screen 4.3.1.
BE1-CDS Testing And Maintenance 13-21
Relay Trouble Alarms
Reset and verify that the relay trouble alarm is not ON. Alarm information can be read by transmitting the
ASCII commands RA or RG-STAT. To clear (reset) a relay trouble alarm, first gain write access to the
reporting functions (R password) and then initiate the RA=0 or RA-REL=0 commands or press the RESET
key while the optional front panel HMI screen 1.2, \STAT\ALARMS\ALARM screen is displayed.
Purpose: To verify that all alarms are cleared and no alarms are active before initially loading the
system.
Reference Commands: RA, RG-STAT, RA=0, RA-REL=0
Refer to Section 6, Reporting And Alarm Functions, Major/Minor/Logic Programmable Alarms, for
information on setting alarms and retrieving and resetting alarm reports. To use the optional front panel
HMI, go to screen 1.2, \STAT\ALARMS\ALARM.

Major/Minor/Logic Programmable Alarms


Reset and verify that the relay Major/Minor/Logic Programmable alarms are not ON. Alarm information
can be read by transmitting the ASCII commands RA or RG-STAT. To clear (reset) a relay
Major/Minor/Logic alarm, first gain write access to the reporting functions (R password) and then initiate
the RA=0 or RA-MAJ/MIN/LGC=0 commands or press the RESET key while the optional front panel HMI
screen 1.2.1, \STAT\ALARMS\DETAILS screen is displayed.
Purpose: To verify that all Major/Minor/Logic Programmable alarms are cleared and no alarms are active
before initially loading the system.
Reference Commands: RA, RG-STAT, RA=0, RA-MAJ/MIN/LGC =0
Refer to Section 6, Reporting And Alarm Functions, Major/Minor/Logic Programmable Alarms, for
information on setting alarms and retrieving and resetting alarm reports. To use the optional front panel
HMI, go to screen 1.2.1, \STAT\ALARMS\DETAILS.

Targets
Reset and verify that there is no target information. Target information can be read by transmitting the
ASCII command RG-TARG. To clear (reset) a relay target, first gain write access to the reporting
functions (R password) and then initiate the RG-TARG=0 command or press the RESET key while the
optional front panel HMI screen 1.1, \STAT\TARGETS screen is displayed.
Purpose: To verify that all targets are cleared before initially loading the system.
Reference Commands: RG-TARG, RG-TARG=0
Refer to Section 6, Reporting And Alarm Functions, Fault Reporting, Targets, for information on setting
targets and retrieving and resetting target information. To use the optional front panel HMI, go to screen
1.1, \STAT\TARGETS.

Fault Summary Reports


Reset and verify that new fault summary directory records are set to zero. To reset the new fault
summary directory records, first gain write access to the reporting functions (R password) and then initiate
the RF-NEW=0 command two times. Verify that there are no new fault summary records by initiating the
RF command and observe that the NEW FAULTS line indicates zero or view the optional front panel HMI
screen 4.1, \REPRT\FAULT.
Purpose: To verify that there are no new fault records before initially loading the system.
Reference Commands: RF, RF-NEW=0
Refer to Section 6, Reporting And Alarm Functions, Fault Reporting, Fault Summary Reports, for
information on retrieving fault summary reports.

Sequence Of Events Recorder (SER) Function


Reset SER registers and verify that there are no SER events. SER directory reports can be read by
transmitting the ASCII command RS or through the optional front panel HMI screen 4.2. To clear (reset)
13-22 Testing And Maintenance BE1-CDS
SER registers, first gain write access to the reporting functions (R password) and then initiate the RS-
NEW=0 command.
Purpose: To verify that all SER registers are cleared before initially loading the system.
Reference Commands: RS, RS-NEW=0
Refer to Section 6, Reporting And Alarm Functions, Sequence Of Events Recorder Function, for
information on retrieving and resetting SER records.

System Report Documentation


After completing all previous steps in Commissioning Testing and before placing the protection system in
service, it is important to create a record of the relay settings and system status at the time of
commissioning. This report should be kept for comparison in future maintenance procedures.
To create the settings record, transmit the ASCII S command and then use normal personal computer
techniques to save or print the SER report that is returned.
To create the status record, transmit the ASCII RG-STAT command and then use normal personal
computer techniques to save or print the status report that is returned.
Purpose: To create a permanent status and settings record for future reference before initially loading
the system.
Reference Commands: S, RG-STAT
Refer to Section 6, Reporting And Alarm Functions, General Status Reporting, and Sequence Of Events
Recorder Function, for information on retrieving and resetting SER records.

In Service Current Circuit Verification


To verify correct CT circuit connections, internal phase, zero sequence and tap compensation settings for
the differential functions, it is recommended that the load be placed on the protected zone and a
differential check record be triggered, recorded, and examined. See Section 6, Reporting and Alarm
Functions, Differential Current Monitoring Function for more information on differential check records.
To assist you in performing this procedure, an Annotated Differential Check Record and an In Service
Current Circuit Verification Form is provided on the following pages. It is recommended that this form be
copied, completed (filled out), and that the differential check record retrieved from the relay be captured to
a file and printed. These two documents should then be placed with the commissioning records for future
reference.

Test Scenarios
The protected circuit should be loaded prior to triggering a differential check record. It is desirable that the
loading be great enough to result in relay currents that are above the minimum sensitivity of the differential
current diagnostic function, but not great enough to cause a trip if there is a problem in the installation.
The minimum sensitivity of the differential current diagnostic function is 150 milliamperes of secondary
current for 5 ampere relays and 30 milliamperes of secondary current or 1 ampere relays.
When you put initial loading on the differential zone of protection, one of four scenarios may result.
1. Everything is correct and there is no differential alarm or trip.
2. There is a problem with the settings or installation but the initial loading is too low so there is no
differential alarm or trip.

BE1-CDS Testing And Maintenance 13-23


3. There is a problem with the settings or installation and the initial loading is great enough to cause a
differential alarm but not a trip.

NOTE
If the load picked up results in differential current greater than the alarm set point
(scenario 3), a record will be generated automatically by the differential alarm function. If
this occurs, it is still recommended to manually trigger generation of a new differential
check record so that you are assured that you are looking at up-to-date data.

4. There is a problem with the settings or installation and the initial loading is great enough to cause a
trip.

NOTE
If the load picked up results in a trip (scenario 4), examine the fault summary and
oscillography records to determine the cause of the trip. If it is not a fault, re-energize the
transformer and pick up less load; or, block the differential trip, re-energize the
transformer, and pick up the load. After the load is picked up, trigger a differential check
record. Once the problem has been corrected, unblock the differential element. Or, an
Exel spreadsheet template (CDSFAULT.xlt) is available from the web site
www.basler.com. The magnitude and angle of the currents recorded in the fault summary
report at the time of the trip can be entered into this spreadsheet along with the pertinent
differential and connections settings. The spreadsheet will then calculate the differential
currents after compensation which makes it easier to diagnose and correct the problem.

13-24 Testing And Maintenance BE1-CDS


Annotated Differential Check Record
CDS 220 DIFFERENTIAL CHECK RECORD
REPORT DATE : 11/10/98
REPORT TIME : 11:10:08.203
STATION ID : SIMULATED_SUBST
RELAY ID : BANK-T1
USER1 ID : TEST1
USER2 ID : TEST1
RELAY ADDRESS : 0
ACTIVE GROUP : 0

PHASE 87 SETTINGS CTR CT CON TX CON GROUNDED


CT CKT1 240 WYE DAC NO
CT CKT2 400 WYE WYE YES
MINPU 0.20 *TAP
SLOPE 25 %
ALARM 50 %
URO 6 *TAP
P0004-18.vsd
09-22-00
COMPENSATION Angle Tap
CT CKT1 WYE 3.12
CT CKT2 DAC 4.68

ALARMS PHASE A PHASE B PHASE C


DIFFERENTIAL: OK OK OK
POLARITY: OK OK OK
ANGLE COMP: OK OK OK
MISMATCH: OK OK OK

MEASUREMENTS PHASE A PHASE B PHASE C


MEASURED I PRI
CT CKT1: 209 @ 0 206 @ 240 206 @ 121
CT CKT2: 528 @ 211 516 @ 91 528 @ 332
MEASURED I SEC
CT CKT1: 0.87 @ 0 Examine 0.86 @ 240 0.86 @ 121
CT CKT2: 1.32 @ 211 1.29 @ 91 1.32 @ 332
ANGLE COMPENSATED I
CT CKT1: 0.87 @ 0 0.86 @ 240 0.86 @ 121
CT CKT2: Plot these 1.32 @ 181 1.29 @ 61 1.32 @ 302
TAP COMP I currents
CT CKT1: 0.28 @ 0 0.27 @ 240 0.27 @ 121
CT CKT2: 0.28 @ 181 0.28 @ 61 0.27 @ 302
IOP: 0.01 *TAP 0.01 *TAP 0.01 *TAP
SLOPE RATIO 4 % 4 % 4 %
>

BE1-CDS Testing And Maintenance 13-25


In-Service Current Circuit Verification Form
Time and Date:
Station ID: Relay ID:
User1 ID: User2 ID:
Trigger Differential Check Record
To trigger and retrieve a current check record, use the following commands:
A=
RA-DIFF=TRIG
RA-DIFF
Examine Differential Check Record
1. Examine the Measurements portion of the report. Plot on the appropriate polar graph, the currents
under the differential check record lines Measured I Pri and Tap Comp I for each phase and
CT input circuit.
90 90
120 60 120 60

150 30 150 30

180 180
0 0

210 330 210 330

240 300 240 300

270 270 D2558-14.cdr


07-18-00

Plot Primary Currents Plot Compensated Currents


2. Examine the plotted currents.
— Is the phase sequence for both CT circuits the same as expected?
— Does the phase sequence match the phase sequence setting (SG-PHROT) or HMI screen 6.3.3?
— Examine the angle and tap compensated currents on the polar graph from the line labeled Tap
Comp I . For each phase, determine if the currents are approximately the same magnitude for
each CT input circuit and approximately 180 degrees out of phase? Some small amount of
mismatch is expected due to excitation and possible LTC or other tap adjust differences.
3. Examine the Alarms portion of the report.
— The line marked Differential will report Alarm for any phase where the differential current is
above the alarm threshold on that phase.
— The lines marked Polarity, Angle Comp, and Mismatch will report Alarm or OK as
determined by the current circuit diagnostic function if the currents are above the minimum
sensitivity. The diagnostic function for these lines operates even if the differential current is not
above the alarm threshold.

13-26 Testing And Maintenance BE1-CDS


PERIODIC TESTING
Because the relay has extensive internal self test capabilities, periodic testing of the protection system can
be greatly reduced. The relay characteristics are a function of the programming instructions that do not
drift over time. Thus, the user may wish to verify that the:
• Set points that were proven during the commissioning have not been changed.
• Inputs and outputs are properly interfacing with the rest of the protection and control system.
• Power system analog parameters used by the protection and control functions are being
measured accurately.
These are things that the self test capability cannot completely determine.

Settings Verification
Verification of the relay settings can be accomplished in several ways depending upon the user’s
preferences and practices. This step may not be required if the settings changed alarm point is
programmed to an output and is being monitored. This way, any unexpected setting changes would be
logged and investigated. Some settings verification possibilities include:
• Repeating the Protection and Control Function commissioning tests.
• If a file of the settings recorded upon commissioning is available, the settings can be read out of
the relay and captured to a similar file and compared using software tools.
• The settings can be verified by simple inspection of the settings versus those recorded upon
commissioning.

Digital I/O Connection Verification


Verification of the relay digital I/O connections can be accomplished in several ways depending upon the
user’s preferences and practices.
• Repeating the digital I/O connection verification commissioning tests.
• Monitoring SER, Status, and Fault reports for proper sensing of digital signals and proper tripping
during normal operation.

NOTE
If protection systems are redundant such that multiple relays will trip a given breaker or
device for a fault, simply monitoring fault reports may not indicate a failed output contact.
The relay may report that it energized an output. However, tripping was actually
accomplished by the redundant relay. With this situation, actually testing the contact is
recommended.

Analog Circuit Verification

NOTE
If you are going to verify the analog measurement circuits by comparison to independent
devices, you should ensure that the two devices use similar measurement algorithms.
For example, the measurements of a fundamental sensing relay cannot be compared with
the measurements of an RMS sensing device.

Verification of the relay analog measurement circuits can be accomplished in several ways depending
upon the user’s preferences and practices. Some of these ways are:
• Repeating portions of the acceptance or commissioning tests and injecting known test signals into
the relay.
• Using the metering functions of the relay and comparing the measurements to those provided by
other similar devices that are measuring the same signals. Redundant relays and/or metering
devices can provide this source of independent conformation of the measured signals. If the relay
is connected to an integration system, this can even be automated and done on a routine basis.

BE1-CDS Testing And Maintenance 13-27


FUNCTIONAL TESTING
NOTE
Functional testing is NOT required for this unit. It is only necessary if the user wants to
perform a comprehensive assessment to determine suitability for an application.

Functional testing provides a comprehensive assessment of this relay to determine suitability for your
application. Functional testing goes beyond the more basic tests found in acceptance testing, but does
not go into the detail for each function as in Commissioning Testing.
Test each of the following functions to verify that this relay measures accurately, is within specified
tolerances, and operates correctly as designed. In addition, these tests are suitable for assisting in
systematic trouble-shooting in the event of a questionable operation. Revisiting a functional test of a
specific function of the relay can help verify whether the relay is indeed operating within the
manufacturer’s specified tolerance. For further assistance, contact Basler Electric, Customer Services
Department.

Phase Differential (87)

Minimum Pickup
Purpose: To verify the minimum pickup of the 87 elements.
Reference Commands: SL-87, S<g>-87, S<g>-TAP87, SG-CT
Step 1. Connect one current source to terminals B1 and B2 (A-phase, input 1). See Figures 13-1 and
13-2. An ohm-meter or continuity tester may be used to monitor output contact status.
Step 2. To prepare the 87 elements for testing, transmit the commands in Table 13-13 to the relay.
Table 13-13. Pickup Test Commands
Command Purpose
A= Gain access
SL-N=NONE Zero out custom logic settings/overwrite with
logic = none settings
Y Confirm overwrite
SL-N=RDIFF Name custom logic for this test
SL-87=1,0 Enables 87
SL-VO1=87RT Enables OUT1 to close for 87 restrained trip
SG-CT1=1,WYE,NA ctr=1, ct=wye, xfmr=na
SG-CT2=1,WYE,NA ctr=1, ct=wye, xfmr=na
SG-TRIGGER=87RT, Enable 87RT to log and trigger fault recording
7RPU,0
E Exit
Y Save settings

Step 3. Send to the relay the commands listed in Table 13-14.

NOTE
The tap settings listed in the S#-TAP87 command are within the range of settings for a 5
ampere sensing input type relay. If your relay is a 1 ampere sensing input type, change
the TAP 1 and TAP 2 values to 1.0.

13-28 Testing And Maintenance BE1-CDS


Table 13-14. S#-87 Commands
Command Purpose
A= Gain access
S#-TAP87=MANUAL, Set TAP 1=5.00 and TAP 2=5.00
5.00,5.00
nd th
S#-87=0.1,15,0,0,0,1 Minpu = 0.1, slope = 15%, 2 = disable, 5 = dis-
nd
able, URO = disable, 2 harm sharing = 1 (yes)
E Exit
Y Save settings

Step 4. Apply current to phase A, input 1 and slowly ramp up until OUT1 closes. The relay should
pickup at a value of minimum pickup x TAP (see Figure 13-12).
OPERATING CURRENT (IN MULTIPLES OF TAP)
3

D2857-12.vsd
10-13-99
2

minimum pickup
= 0.10 x tap
1

Differential
current 15%
IOP*100/IRESTR =
Slope =
0.1

1 2 3 4 5
RESTRAINT CURRENT (IN MULTIPLES OF TAP)

Figure 13-12. Minimum Pickup Characteristic


Step 5. Verify that pickup occurred within the specified accuracy of the relay (see Table 13-15) as
indicated by the low and high limits in Table 13-16.
Table 13-15. Sensing Input Type Accuracy
CT secondary rating Accuracy
5A ± 4% of setting or 75 milliamperes whichever is greater
1A ± 4% of setting or 25 milliamperes whichever is greater

Step 6. Decrease the phase A, input 1 current until the relay drops out. Remove current.

NOTE
Testing all inputs at various sensitivity settings is optional.

BE1-CDS Testing And Maintenance 13-29


Table 13-16. Minimum Pickup Accuracy Limits
Sensing Phase Terminals MINPU Tap 1/Tap Pickup Low High
Type Inputs 2 values (A) Limit (A) Limit (A)
5A A1 B1,B2 0.10 5.00/5.00 0.50 0.425 0.575
B1 B3,B4 0.50 5.00/5.00 2.50 2.400 2.600
C1 B5,B6 1.00 5.00/5.00 5.00 4.800 5.200
A2 B9,B10 0.10 5.00/10.0 1.00 0.925 1.075
B2 B11,B12 0.50 5.00/10.0 5.00 4.800 5.200
C2 BB13,B14 1.00 5.00/10.0 10.0 9.600 10.40
1A A1 B1,B2 0.10 1.00/1.00 0.10 0.075 0.125
B1 B3,B4 0.50 1.00/1.00 0.50 0.475 0.525
C1 B5,B6 1.00 1.00/1.00 1.00 0.960 1.040
A2 B9,B10 0.10 1.00/2.00 0.20 0.175 0.225
B2 B11,B12 0.50 1.00/2.00 1.00 0.960 1.040
C2 BB13,B14 1.00 1.00/2.00 2.00 1.952 2.080

Step 7. Repeat Steps 3 and 4 by connecting the current sources to the phases indicated in Table 13-
16 and substitute for MINPU (in the S#-87 command) and TAP values in the S#-TAP87
command (or if your relay is supplied with the HMI option, navigate to the \PROT\SGn\87\87
screen to change MINPU values and \PROT\SGn\87\TAP screen to change TAP 1 and TAP 2
values) to verify linearity over the range of MINPU values.
Step 8. (Optional) Confirm that the relay acknowledged each change of state of OUT1 (87 restrained
trip) by using the RS command. Gain write access to the relay (a= ) and reset the new events
counter by sending an RS=0 command to the relay.

NOTE
The action listed in Step 8 will not be introduced again in these tests. It is up to the user
to decide whether it is necessary to do this check after each test.

Step 9. (Optional) Repeat Steps 2 through 8 for setting groups 1 through 3. Use the CS/CO-GROUP
command to change setting groups.

Restrained Pickup
The following tests verify the functional operation of the restrained 87 element. See Sidebar 13-2 for more
information on the percentage differential restraint operating principle.
Purpose: To verify the accuracy of the restraint operation of the 87 element.
Reference Commands: SL-87, SL- VO, SG-CT, S<g>-87, S<g>-TAP87
Step 1. Connect one current source to terminals B1 and B2 (A-phase, input 1) and a second current
source to terminals B9 and B10 (A-phase, input 2). Ensure that the two current sources are
o
180 out of phase. See Figure 13-13 for a connection diagram.
An ohm-meter or continuity tester may be used to monitor output contact status.
Step 2. Send the commands listed in Table 13-17 to the relay to prepare the 87 elements for pickup
testing.

13-30 Testing And Maintenance BE1-CDS


Table 13-17. Commands To Prepare For Pickup Testing
Command Purpose
A= Gain access
SL-N=NONE Zero out custom logic settings/overwrite with
logic = none settings
Y Confirm overwrite
SL-N=RDIFF Name custom logic for this test
SL-87=1,0 Enables 87
SL-VO1=87RT Enables OUT1 to close for 87 restrained trip
SG-CT1=1,WYE,NA ctr=1, ct=wye, xfmr=na
SG-CT2=1,WYE,NA ctr=1, ct=wye, xfmr=na
SG-TRIGGER=87RT, Enable 87RT to log and trigger fault recording
7RPU,0
E Exit
Y Save settings

180 degrees
current current circuit
source 1 source 2 monitor

IA1 IB1 IC1 IG IA2 IB2 IC2

B1 B3 B5 B7 B9 B11 B13 B15

B2 B4 B6 B8 B10 B12 B14 B16

IA1 IB1 IC1 IG IA2 IB2 IC2

Figure 13-13. Connections For Restraint Verification

Sidebar 13-2. Percentage Differential Restraint Operating Principle


The percentage differential restraint characteristic of the BE1-CDS relay is illustrated in Section 1, Figure
1-1. The knee of the operating curve for any slope setting is determined by taking the minimum pickup
operating characteristic and dividing it by the slope.
For example, for a minimum pickup setting of 0.30 and a slope setting of 15%, the knee of the operating
curve is plotted at a point equal to 0.30/0.15=2.00 multiples of tap on the maximum restraint current axis.
This implies that at these settings, the relay requires greater than 2.00 multiples of tap of maximum or
average restraint current to operate along the 15% slope characteristic of the relay.
Thus, for restraint currents less than the knee of the curve, the relay will operate at a differential current
greater than or equal to the minimum pickup operate setting. Beyond the knee of the curve, the
differential current operating characteristic is defined along the slope portion of the curve.
The BE1-CDS relay has two distinct operating principles for performing the restraint operation. Maximum
restraint uses the maximum of the two compensated currents as the restraint while average restraint, uses
the average of the two compensated currents. Either characteristic may be selected via the S<g>-87
command. For more information on the S<g>-87 command, refer to Section 4, Protection And Control
Functions, Differential Protection.

BE1-CDS Testing And Maintenance 13-31


Step 3. Send to the relay the commands listed in Table 13-18.
Table 13-18. Setup Commands
Command Purpose
A= Gain access
For 5 A sensing input:
S#-TAP87=MANUAL,2.00,3.80 Set tap 1=2.00 and tap 2=3.80
For 1 A sensing input:
S#-TAP87=MANUAL,0.40,0.76 Set tap 1=0.40 and tap 2=0.76

You can test the relay either by increasing one current from a balanced condition or decreasing it. Refer
to the descriptions of both methods and Sidebar 13-3 to evaluate the differences in the two approaches.

Sidebar 13-3. Maximum Restraint Operating Characteristic


Under maximum restraint, the relay reaches the trip or operate point depending on the level of restraint
as shown in the associated figure. When only one current is changed, the restraint current can vary
depending on the relative changes between currents. When one current is decreased from balance, the
maximum restraint has a vertical characteristic. When increasing one current relative to the other, it will
shift to the right with a sloping characteristic as it continues to increase toward the trip region of the
operate characteristic.
OPERATING CURRENT (IN MULTIPLES OF TAP)
3

D2857-13.vsd
10-14-99

decreasing current increasing current


from balance from balance

pe
Slo
2

minimum
pickup
1

1 2 3 4 5
MAXIMUM RESTRAINT CURRENT (IN MULTIPLES OF TAP)

In order to test the restrained pickup function of the BE1-CDS relay, you may increase one of two
currents initially applied in balance, to create an operate imbalance. In this narrative, the input 1 current
will be the input to be deviated. A similar analysis can be made for deviating input 2 current.
By increasing input current I1 from balance, I1trip is defined as

slope
I1trip = I1balance/(1-( ))in per unit Sidebar 13-3, Equation 1
100
with the minimum trip point established as
I1trip min = I1balance + minpu in per unit Sidebar 13-3, Equation 2

where: minpu is the minimum pickup setting

13-32 Testing And Maintenance BE1-CDS


Sidebar 13-3. Maximum Restraint Operating Characteristic – Continued
Under test and in-service conditions, the following equations determine whether the relay operates
along the flat minimum pickup or slope of the operating characteristic. If:

Irestraint at balance > minpu x  1 


− 1 in per unit, use Equation 1, or if
 slope / 100 

Irestraint at balance < minpu x  1 


− 1 in per unit, use Equation 2.
 slope / 100 

Example (Increasing One Input From Balance):


TAP 1 = 2.00 Minpu = 0.30
TAP 2 = 3.80 Slope = 15%
Input 1 current at balance = 3 per unit (6 amperes)
Input 2 current at balance = 3 per unit (11.40 amperes)
Input 1 is being increased relative to a fixed input 2 current. Thus, the maximum restraint used by the
relay is input 1, the larger of the two currents in per unit.

 1 
Irestraint at balance = 3 > 0.3  − 1 = 1.70 per unit
 0.15 

Then,

slope
I1trip = I1balance/(1-( )) = 3/(1-0.85) = 3.53 per unit (see the following figure)
100
OPERATING CURRENT (IN MULTIPLES OF TAP)
3
2

minimum pickup
= 0.30 x tap
1

15%
IOP*100 /IRESTR =
Slope =

Differential current

3.53
1 2 3 4 5
MAXIMUM RESTRAINT CURRENT (IN MULTIPLES OF TAP)

Maximum Restraint Characteristic Example

You may also use the maximum restraint operating characteristic and test the relay by decreasing one
current from a balanced condition. For additional information on testing in this manner, see Sidebar 13-4.

BE1-CDS Testing And Maintenance 13-33


Sidebar 13-4. Maximum Restraint When Decreasing One Input From Balance
A second way to test the restrained pickup of the BE1-CDS relay is to decrease one of two currents,
initially applied in balance, to create an imbalance. In this narrative, input 2 current will be the input
deviated. A similar analysis can be made for deviating input 1 current.
By decreasing the input current I2 from balance, the value of I2trip is defined as:

slope
I2trip = I2balance (1- ( )) in per unit Sidebar 13-4, Equation 1
100
with the minimum trip point established as:
I2trip min = I2balance – minpu in per unit Sidebar 13-4, Equation 2
where: minpu is the minimum pickup setting.
Under test and in-service conditions, the following equations determine whether the relay operates along
the flat minimum pickup or the slope of the operating characteristic. If:

slope
Irestraint at balance > (minpu/( ) in per unit, use Equation 1, or, if
100
slope
Irestraint at balance < (minpu/( ) in per unit, use Equation 2.
100
With the maximum restraint operating principle of the BE1-CDS relay, as one input current is decreased
from balance, the other input current, remaining the greater of the two currents, will be the restraint current
(in per unit). Since that current remains fixed while the other is decreased, the operate current plotted
against the restraint current will be a vertical line on the operating characteristic diagram.

If you are applying this relay using the maximum restraint operating characteristic, continue with Step 4.
Otherwise, you may proceed directly to Step 12 to test the average restraint operating characteristic.
Step 4. Send the commands listed in Table 13-19 to the relay.
Table 13-19. Setup Commands
Command Purpose
A= Gain access
nd th
S#-87=0.35,15,0,0,0,1 minpu=0.35,slope=15%,2 =dis,5 =dis,URO=dis,
nd
2 harm sharing=1 (yes)
E Exit
Y Save settings
Step 5. Apply balancing current to phase A, input 1 and phase A, input 2 at the magnitude indicated in
the first row of either Table 13-20 (5 ampere sensing) or 13-21 (1 ampere sensing) and slowly
increase input 1 until OUT1 closes. Reference the appropriate table to verify pickup accuracy.
Step 6. Repeat for all values and (optionally) reconnect to phases B and C, inputs 1 and 2 when
advancing through the set of test values in the table. It is not necessary to test each phase at
all the values listed to verify the response of each phase. If your relay is supplied with the HMI
option, navigate to the \PROT\SGn\87\87 screen to make the listed slope setting changes.
Notice that the test values in Tables 13-20 and 13-21 are intended to show operation on both the minimum
operate and slope portion of the operating curve.
Step 7. Verify that pickup occurred within the specified accuracy of the relay. Accuracy when
increasing or decreasing the input current is ±4% of setting or 75 milliamperes (whichever is
larger) for 5 ampere sensing inputs and ±4% of setting or 25 milliamperes (whichever is larger)
for 1 ampere sensing inputs.

13-34 Testing And Maintenance BE1-CDS


Table 13-20. Maximum Restraint Pickup Test Points (5 A Sensing Input)
Sensing Input 1 Input 2 Increasing Input 1 Decreasing Input 2
Input Minimum slope tap = 2.00 tap = 3.80 From Balance From Balance
Type Pickup (%) Bal. Input (A) PU Bal. Input (A) PU Pickup (A) Pickup (A)

5 0.35 15 2.00 1 3.80 1 2.70 ± 0.108 2.47 ± 0.099


5 0.35 15 10.00 5 19.00 5 11.76 ± 0.470 16.15 ± 0.646
5 0.35 30 2.00 1 3.80 1 2.86 ± 0.108 2.47 ± 0.089
5 0.35 30 10.00 5 19.00 5 14.29 ± 0.572 13.30 ± 0.532
5 0.35 45 2.00 1 3.80 1 3.64 ± 0.146 2.09 ± 0.084
5 0.35 45 10.00 5 19.00 5 18.18 ± 0.727 10.45 ± 0.418
5 0.35 60 2.00 1 3.80 1 5.00 ± 0.200 1.52 ± 0.075
5 0.35 60 10.00 5 19.00 5 25.00 ± 0.100 7.60 ± 0.304

Table 13-21. Maximum Restraint Pickup Test Points (1 A Sensing Input)


Sensing Input 1 Input 2 Increasing Input 1 Decreasing Input 2
Input Minimum slope tap = 2.00 tap = 3.80 From Balance From Balance
Type Pickup (%) Bal. Input (A) PU Bal. Input (A) PU Pickup (A) Pickup (A)

1 0.35 15 0.40 1 0.76 1 0.54 ± 0.025 0.49 ± 0.025


1 0.35 15 2.00 5 3.80 5 2.35 ± 0.094 3.23 ± 0.129
1 0.35 30 0.40 1 0.76 1 0.57 ± 0.025 0.49 ± 0.025
1 0.35 30 2.00 5 3.80 5 2.86 ± 0.114 2.66 ± 0.106
1 0.35 45 0.40 1 0.76 1 0.73 ± 0.029 0.42 ± 0.025
1 0.35 45 2.00 5 3.80 5 3.64 ± 0.146 2.09 ± 0.084
1 0.35 60 0.40 1 0.76 1 1.00 ± 0.040 0.30 ± 0.025
1 0.35 60 2.00 5 3.80 5 5.00 ± 0.200 1.52 ± 0.061
Step 8. Remove both currents.
Step 9. For each change in slope value indicated, send the commands listed in Table 13-22 to the
relay to invoke a change in slope settings (notice the leading comma (,) in the S#-87
command).
Table 13-22. Setup Commands
Command Purpose
A= Gain access
S#-87=,30 Minpu = no change, slope = 30%
E Exit
Y Save settings
Step 10. Repeat Steps 2 through 4 for phases B and C unless all phases were tested during the
restraint pickup tests in Step 5. If so, proceed with the next step.
Step 11. (Optional) Repeat Steps 2 through 5 for setting groups 1 through 3 using the CS/CO-GROUP
command to change setting groups.
If you are applying this relay using the average restraint operating characteristic, you may begin your
testing at Step 12, otherwise go back to Step 4 to test for the maximum restraint operating characteristic.
For more information on testing using the average restraint operating characteristic, see Sidebar 13-5 and
Sidebar 13-6.

BE1-CDS Testing And Maintenance 13-35


Sidebar 13-5. Average Restraint Operating Characteristic
Operating in an average restraint characteristic, the BE1-CDS relay reaches the trip or operate point
depending on the level of restraint per the diagram below.
As illustrated in the associated diagram, when only one current is changed, the restraint current will vary
depending on the relative change in currents. As one current is decreased from balance, the average
restraint will shift to the left with a sloping characteristic as the differential current increases to the point of
operating. The average restraint will shift to the right with a sloping characteristic when one current is
increased relative to the other as the differential current increases.
OPERATING CURRENT (IN MULTIPLES OF TAP)
3

D2857-14.vsd
10-15-99

decreasing current increasing current


from balance from balance

pe
Slo
2

minimum pickup
1

1 2 3 4 5
AVERAGE RESTRAINT CURRENT (IN MULTIPLES OF TAP)

Average Restraint Operating Characteristic

Sidebar 13-6. Average Restraint When Increasing One Input From Balance
In order to test the restrained pickup function of the BE1-CDS relay, you may increase one of two currents
initially applied in balance, to create an operate imbalance. In this narrative, the input 1 current will be the
input to be changed. A similar analysis can be made for changing input 2 current.
By increasing input current I1 from balance, I1trip is defined as:

slope slope
I1trip = I2balance*(1+((2* )/(2- ))) in per unit Sidebar 13-6, Equation 1
100 100
with the minimum trip point established as:
I1trip min = I2balance + minpu in per unit Sidebar 13-6, Equation 2
where: minpu is the minimum pickup setting.
Under test and in-service conditions, the following equations determine whether the relay operates along
the flat minimum pickup or slope of the operating characteristic. If:

Irestraint at balance > minpu x  1 


− 1 / 2  in per unit, use Equation 1, or if
 slope / 100 

Irestraint at balance < minpu x  1 


− 1 / 2  in per unit, use Equation 2.
 slope / 100 

13-36 Testing And Maintenance BE1-CDS


Sidebar 13-6. Average Restraint When Increasing One Input From Balance - Continued
Example (Increasing One Input From Balance):
Tap1 = 2.00 Minpu = 0.30
Tap2 = 3.80 Slope = 15%
Input 1 current at balance = 3 per unit (6 amperes)
Input 2 current at balance = 3 per unit (11.40 amperes)
Input 1 is being increased relative to a fixed input 2 current.

 1 
Irestraint at balance = 3 > 0.3  − 0.5  = 1.85 per unit
 0.15 

Then,

slope slope
I1trip = I2balance * (1+((2* )/(2- ))) = 3(1+0.30/1.85) = 3.486 per unit
100 100
I1 + I2
Irestraint = = (3.0 + 3.486)/2 = 6.486/2 = 3.243 per unit (see the following figure)
2
OPERATING CURRENT (IN MULTIPLES OF TAP)
3
2

minimum pickup
= 0.30 x tap
1

R = 15%
IO *100/IREST
Slope =
P

Differential current

3.243
1 2 3 4 5
AVERAGE RESTRAINT CURRENT (IN MULTIPLES OF TAP)

Average Restraint Characteristic Example

You may also use the average restraint operating characteristic and test the relay by decreasing one
current from a balanced condition. For additional information on testing in this manner, see Sidebar 13-7.

Sidebar 13-7. Average Restraint When Decreasing One Input From Balance
A second way to test the restrained pickup of the BE1-CDS relay is to decrease one of two currents,
initially applied in balance, to create an imbalance. In this narrative, input 1 current will be the input to be
changed. A similar analysis can be made for changing input 2 current.
By decreasing the input current I1 from balance, the value of I1trip is defined as:

slope slope
I1trip = I2balance (1- ((2* )/(2+ )))in per unit
100 100

BE1-CDS Testing And Maintenance 13-37


Sidebar 13-7. Average Restraint When Decreasing One Input From Balance - Continued
with the minimum trip point established as:
I1trip min = I2balance - minpu in per unit
where: minpu is the minimum pickup setting
Under test and in-service conditions, the following equations determine whether the relay operates along
the flat minimum pickup or slope of the operating characteristic. If


Irestraint at balance > minpu x  1  in per unit, use the 1st equation, or if
 slope / 100 + 1 / 2 
 


Irestraint at balance < minpu x  1  in per unit, use the 2nd equation.
 slope / 100 + 1 / 2 
 

Step 12. Send the commands listed in Table 13-23 to the relay.
Table 13-23. Setup Commands
Command Purpose
A= Gain access
S#-87=0.35,15A,0,0,0,1 Minpu = 0.35, slope = 15% (of average restraint),
nd th nd
2 = disabled, 5 = disabled, URO= disabled, 2
harm sharing =1 (yes)
E Exit
Y Save settings

Step 13. Apply balancing current to phase A input 1 and phase A input 2 at the magnitude indicated in
each row of either Table 13-24 (5 ampere sensing) or 13-25 (1 ampere sensing) and slowly
increase phase A input 1 until OUT1 closes. Reference the corresponding table to verify
pickup accuracy.

Table 13-24. Maximum Restraint Pickup Test Points (5 A Sensing Input)


Sensing Input 1 Input 2 Increasing Input 1 Decreasing Input 2
Input Minimum slope tap = 2.00 tap = 3.80 From Balance From Balance
Type Pickup (%) Bal. Input (A) PU Bal. Input (A) PU Pickup (A) Pickup (A)

5 0.35 15 2.00 1 3.80 1 2.70 ± 0.108 2.47 ± 0.099


5 0.35 15 10.00 5 19.00 5 11.62 ± 0.465 16.35 ± 0.654
5 0.35 30 2.00 1 3.80 1 2.70 ± 0.108 2.47 ± 0.089
5 0.35 30 10.00 5 19.00 5 13.53 ± 0.541 14.04 ± 0.562
5 0.35 45 2.00 1 3.80 1 3.16 ± 0.126 2.40 ± 0.096
5 0.35 45 10.00 5 19.00 5 15.81 ± 0.632 12.03 ± 0.481
5 0.35 60 2.00 1 3.80 1 3.71 ± 0.148 2.04 ± 0.096
5 0.35 60 10.00 5 19.00 5 18.57 ± 0.743 10.22 ± 0.409

13-38 Testing And Maintenance BE1-CDS


Table 13-25. Maximum Restraint Pickup Test Points (1 A Sensing Input)
Sensing Input 1 Input 2 Increasing Input 1 Decreasing Input 2
Input Minimum slope tap = 2.00 tap = 3.80 From Balance From Balance
Type Pickup (%) Bal. Input (A) PU Bal. Input (A) PU Pickup (A) Pickup (A)

1 0.35 15 0.40 1 0.76 1 0.54 ± 0.025 0.49 ± 0.025


1 0.35 15 2.00 5 3.80 5 2.32 ± 0.093 3.27 ± 0.131
1 0.35 30 0.40 1 0.76 1 0.54 ± 0.025 0.49 ± 0.025
1 0.35 30 2.00 5 3.80 5 2.71 ± 0.108 2.81 ± 0.112
1 0.35 45 0.40 1 0.76 1 0.63 ± 0.025 0.481 ± 0.025
1 0.35 45 2.00 5 3.80 5 3.16 ± 0.126 2.406 ± 0.096
1 0.35 60 0.40 1 0.76 1 0.74 ± 0.030 0.408 ± 0.025
1 0.35 60 2.00 5 3.80 5 3.71 ± 0.148 2.046 ± 0.082

Step 14. Repeat for all values and optionally, reconnect to phases B and C, inputs 1 and 2 when
advancing through the set of test values in the table. It is not necessary to test each phase at
all the values listed to verify the response of each phase. If your relay is supplied with the HMI
option, navigate to the \PROT\SGn\87\87 screen to make the listed slope setting changes.
Notice that the test values in Tables 13-24 and 13-25 are intended to show operation on both the minimum
operate and slope portion of the operating curve. These tables have values for testing the relay either by
increasing one current from a balanced condition or decreasing it. Either technique can be utilized to test
this function. Refer to the descriptions of both methods to evaluate the differences in the two approaches.
Step 15. Verify that pickup occurred within the specified accuracy of the relay. Accuracy when
increasing or decreasing the input current is ±4% of setting or 75 milliamperes (whichever is
larger) for 5 ampere sensing inputs and ±4% of setting or 25 milliamperes (whichever is larger)
for 1 ampere sensing inputs.
Step 16. Remove both currents.
Step 17. For each indicated change in slope value, send the commands listed in Table 13-26 to the
relay to invoke a change in slope settings (notice the leading comma (,) in the S#-87
command).
Table 13-26. Setup Commands
Command Purpose
A= Gain access
S#-87=,30 Minpu = no change, slope = 30%
E Exit
Y Save settings

Step 18. Repeat Steps 12, 13, and 14 for phases B and C unless all phases were tested during the
restraint testing in Steps 13 and 14. If so, proceed with the next step.
Step 19. (Optional) Repeat Steps 2 through 4 and 12 through 14 for setting groups 1 through 3 using
the CS/CO-GROUP command to change setting groups.

Restrained Time Verification


A timing circuit or a contact monitor with timing algorithm must be used to time the output contact status
change. For more information on determining the minimum pickup current, see Sidebar 13-8.

BE1-CDS Testing And Maintenance 13-39


Sidebar 13-8. Determining The Operating Point On The Curve

Irestraint at balance < > minpu x  1 


− 1 in per unit
 slope / 100 

1 < (0.35 * ((1/0.15)-1))= (0.35 * 5.67) = 1.98 per unit


where: The operating point is on the flat part of the curve.
Thus, we use the following to derive the trip condition. Notice the added multiples of tap variable which we
know in this case is 1.5 times tap or, 1.5 per unit.
I2trip min = I2balance + minpu * multiples of tap in per unit
I2trip min = 1 + 0.35 * 1.5 = 1.53 per unit
where: I2 current (@ 2 x tap) = tap X I2trip min = 2.00 * 1.53 = 3.05 amps
Because 1.53 per unit is less than 1.98 per unit, we know that our trip point is on the flat part of the curve
and the applied current is actually 1.5 pu.

Step 1. Connect one current source to terminals B1, B2 (A-phase, input 1) and a second current
source to terminals B9, B10 (A-phase, input 2).
Step 2. Send the commands listed in Table 13-27 to the relay to setup a test of the response time of
the 87 restrained elements.
Table 13-27. Restrained Element Response Time Setup Commands
Command Purpose
A= Gain access
SL-N=NONE Zero out custom logic settings/overwrite with logic =
none settings
Y Confirm overwrite
SL-N=DIFF Sets DIFF as custom logic name
SL-87=1,0 Enables 87
SL-VO1=87RT Enables OUT1 to close with 87 restrained trip
SG-CT1=1,WYE,NA,0 ctr=1, ct=wye, xfmr=na, no grd source
SG-CT2=1,WYE,NA,0 ctr=1, ct=wye, xfmr=na, no grd source
SG-TRIGGER=87RT,87RPU,0 Enable 87RT to log and trigger fault recording
S#-TAP87=MANUAL,2.00,2.00 set tap 1=2.00 and tap 2=2.00
nd th
S#-87=0.35,15,0,0,0,1 Minpu = 0.35, slope = 15%, 2 = disabled, 5 =
nd
disabled, URO= disabled, 2 harm sharing = shared
E Exit
Y Save settings

Step 3. Apply 1 multiple of tap current (2 amperes) to both A-phase input 1 and A-phase input 2 (at
o
180 phase relation to input 1).
Step 4. To force a restrained trip at 1.5 times pickup, you must apply a step change in the current on
input 2 to 3.05 amps. Apply the step change in current to input 2 and record the time interval
between the time the step change was initiated to the time OUT1 output contact closes (the
restrained trip (87RT)).
Step 5. Reduce the current to input 2 until OUT1 contact opens.

13-40 Testing And Maintenance BE1-CDS


Step 6. Apply 1 multiple of tap current (2 amperes) to both A-phase input 1 and A-phase input 2 (at
o
180 phase relation to input 1).
Step 7. To force a restrained trip at 5 times pickup, you must apply a step change in the current on
input 2 to 8.0 amperes. This value (8.0 amperes) was derived from the following:
Iop = 5 * Iop trip
I2 – I = 5 * (I2 * slope)
I2 – I1 = 5 * (I2 * 0.15)
I2 – I = 0.75 I2
0.25 I2 = 1
I2 = 4 per unit
I2 = 8 amperes
Step 8. Apply the step change in current to input 2 and record the time interval between the time the
step change was initiated to the time OUT1 output contact closes (the restrained trip (87RT)).
Step 9. Reduce the current to input 2 until OUT1 contact opens.
Step 10. The time measured in Steps 4 and 8 should be less than those shown in Table 13-28.
Table 13-28. Restrained Trip Operate Times
Function Differential current Time
Restrained trip 1.5 times pu Less than 3 cycles
Restrained trip 5 times pu Less than 2 cycles

Second Harmonic Restraint Verification


nd
Purpose: To verify the operation of the 2 harmonic restraint function of the 87 element.
Reference Commands: SL-87, S(n)-87, S(n)-TAP87, SL-VO, SG-CT
Step 1. Parallel a 60 Hz current source and a second 120 Hz current source to terminals B1, B2
(A-phase, input 1). Reference Figure 13-14.
An ohm-meter or continuity tester may be used to monitor output contact status.

87RT 2NDHAR 60 Hz 120 Hz


circuit circuit current current
monitor monitor source 1 source 2

IA1 IB1 IC1 IG IA2 IB2 IC2

B1 B3 B5 B7 B9 B11 B13 B15

B2 B4 B6 B8 B10 B12 B14 B16

IA1 IB1 IC1 IG IA2 IB2 IC2

Figure 13-14. Connection for Harmonic Restraint Verification

Step 2. Send the commands listed in Table 13-29 to the relay to setup a test of the pickup of the
second harmonic restraint elements.

BE1-CDS Testing And Maintenance 13-41


Table 13-29. Second Harmonic Restraint Elements Setup Commands
Command Purpose
A= Gain access
SL-N=NONE Zero out custom logic settings/overwrite with logic =
none settings
Y Confirm overwrite
SL-N=2HAR Sets 2HAR as custom logic name
SL-87=1,0 Enables 87
SL-VO1=87RT Enables OUT1 to close with 87 restrained trip
nd
SL-VO2=2NDHAR Enables OUT2 to close when 2 harmonic restrains
87RT
SG-CT1=1,WYE,NA,0 ctr=1, ct=wye, xfmr=na, no grd source
SG-CT2=1,WYE,NA,0 ctr=1, ct=wye, xfmr=na, no grd source
SG-TRIGGER=87RT,87RPU,0 Enable 87RT to log and trigger fault recording
S#-TAP87=MANUAL,2.00,3.80 set tap 1=2.00 and tap 2=3.80
nd th
S#-87=0.35,15,18,0,0,1 Minpu = 0.35, slope = 15% ,2 = 18%, 5 = disabled,
nd
URO = disabled, 2 harm sharing = shared
E Exit
Y Save settings

Step 3. Apply 2.0 amps of 60 Hz current to the A-phase input 1. The OUT1 (87RT restrained trip)
output contact should close upon application of current.
Step 4. Apply 120 Hz current on the source paralleled to A-phase input 1 and slowly increase the
current from zero until OUT2 closes (and conversely, OUT1 opens).
Step 5. Record the current magnitude from Step 4 that caused OUT 2 to close and OUT1 to open.
nd
These output contact changes indicated that the 2 harmonic restraint function is now
restraining the 87RT operation.
Step 6. Remove both 60 Hz and 120 Hz currents.
nd nd
Step 7. To arrive at a 2 harmonic inhibit percentage value, divide the magnitude of the applied 2
harmonic current (120 Hz) by the magnitude of the applied 60 Hz input current. For this
particular test, this value should be equal to 0.36 amperes @ 120 Hz ÷ 2 A @ 60 Hz = 18 %.
nd
Verify that the 2 harmonic inhibit function restrains operation at the expected value based on
settings from Step 2.
Step 8. (Optional) Repeat steps 2 through 7 for phases B and C. Because the relay was set for
harmonic sharing in the S#-87 command (the last ‘1’ in the string) in Step 2, the harmonic
content on all phases is shared, or summed, and this magnitude is used by the second
harmonic comparators for each phase. Thus, the same operation will occur regardless of
which phase of the 120 hertz test current is applied.
Step 9. (Optional) Repeat Steps 2 through 8 for setting groups 1 through 3 using the CS/CO-GROUP
command to change setting groups.

Fifth Harmonic Restraint Verification


th
Purpose: To verify the operation of the 5 harmonic restraint function of the 87 element.
Reference Commands: SL-87, S(n)-87, S(n)-TAP87, SL-VO, SG-CT

13-42 Testing And Maintenance BE1-CDS


Step 1. Parallel a 60 Hz current source and a second 300 Hz current source to terminals B1, B2
(A-phase, input 1). Same as Figure 13-14 except for the applied harmonic frequency.
An ohm-meter or continuity tester may be used to monitor output contact status.
Step 2. Send the commands listed in Table 13-30 to the relay to setup a test of the pickup of the fifth
harmonic restraint elements.
Table 13-30. Fifth Harmonic Restraint Elements Setup Commands
Command Purpose
A= Gain access
SL-N=NONE Zero out custom logic settings/overwrite with logic =
none settings
Y Confirm overwrite
SL-N=5HAR Sets 5HAR as custom logic name
SL-87=1,0 Enables 87
SL-VO1=87RT Enables OUT1 to close with 87 restrained trip
th
SL-VO2=5THHAR Enables OUT2 to close when 5 harmonic restrains
87RT
SG-CT1=1,WYE,NA,0 ctr=1, ct=wye, xfmr=na, no grd source
SG-CT2=1,WYE,NA,0 ctr=1, ct=wye, xfmr=na, no grd source
SG-TRIGGER=87RT,87RPU,0 Enable 87RT to log and trigger fault recording
S#-TAP87=MANUAL,2.00,3.80 set tap 1=2.00 and tap 2=3.80
nd th
#-87=0.35,15,0,35,0,1 Minpu = 0.35, slope = 15%, 2 = disabled, 5 = 35%,
nd
URO = disabled, 2 harm sharing = shared
E Exit
Y Save settings

Step 3. Apply 2.0 amps of 60 Hz current to the A-phase input 1. The OUT1 (87RT restrained trip)
output contact should close upon application of current.
Step 4. Apply 300 Hz current on the source paralleled to A-phase input 1 and slowly increase the
current from zero until OUT2 closes (and conversely, OUT1 opens).
Step 5. Record the current magnitude from Step 4 that caused OUT 2 to close and OUT1 to open.
th
These output contact changes indicated that the 5 harmonic restraint function is now
restraining the 87RT operation.
Step 6. Remove both 60 Hz and 300 Hz currents.
th th
Step 7. To arrive at a 5 harmonic inhibit percentage value, divide the magnitude of the applied 5
harmonic current (300 Hz) by the magnitude of the applied 60 Hz input current. For this
particular test, this value should be equal to 0.70 amperes @ 300 Hz ÷ 2 A @ 60 Hz = 35 %.
th
Verify that the 5 harmonic inhibit function restrains operation at the expected value based on
settings from Step 2.
Step 8. (Optional) Repeat steps 2 through 7 for phases B and C.
Step 9. (Optional) Repeat Steps 2 through 8 for setting groups 1 through 3 using the CS/CO-GROUP
command to change setting groups.

Unrestrained Pickup Verification


Purpose: To verify the accuracy of the unrestrained operation of the 87 element.
Reference Commands: SL-87, SL- VO, SG-CT, S(n)-87, S(n)-TAP87

BE1-CDS Testing And Maintenance 13-43


Step 1. Connect one current source to terminals B1, B2 (A-phase, input 1). Refer to Figure 13-1.
An ohm-meter or continuity tester may be used to monitor output contact status.
Step 2. Send the commands listed in Table 13-31 to the relay to setup a test of the pickup of the 87
elements.
Table 13-31. 87 Elements Pickup Setup Commands
Command Purpose
A= Gain access
SL-N=NONE Zero out custom logic settings/overwrite with logic =
none settings
Y Confirm overwrite
SL-N=UDIFF Name custom logic for this test
SL-87=1,0 Enables 87
SL-VO1=87UT Enables OUT1 to close with 87 unrestrained trip
th
SL-VO2=5THHAR Enables OUT2 to close when 5 harmonic restrains
87RT
SG-CT1=1,WYE,NA,0 ctr=1, ct=wye, xfmr=na, no grd source
SG-CT2=1,WYE,NA,0 ctr=1, ct=wye, xfmr=na, no grd source
SG-TRIGGER=87UT,87UT,0 Enable 87UT to log and trigger fault recording
S#-TAP87=MANUAL,2.00,3.80 set tap 1=2.00 and tap 2=3.80
nd th
S#-87=0,15,0,0,1,1 Minpu = disabled, slope = 15%, 2 = disabled, 5 =
nd
disabled, URO = disabled, 2 harm sharing = shared
E Exit
Y Save settings
Step 3. Apply current to A-phase input 1, increasing the magnitude until OUT1 closes. Since the URO
setting is 1 and Tap 1= 2, this should occur at 2 amperes. Accuracy when increasing or
decreasing the input current is ±4% of setting or 75 milliamperes (whichever is larger) for 5
ampere sensing inputs and ±4% of setting or 25 milliamperes (whichever is larger) for 1
ampere sensing inputs. Verify that pickup occurred within the specified accuracy of the relay.
Step 4. Reduce the input current until OUT1 opens.
Step 5. Using the values in Table 13-32, repeat Step 3 for the other values of unrestrained settings
indicated.
Table 13-32. Unrestrained Pickup Accuracy Limits
URO Setting Tap 1 Pickup (A) Low Limit (A) High Limit (A)
1 2.00 2 1.925 2.075
5 2.00 10 9.700 10.30
10 2.00 20 19.40 20.60

Step 6. (Optional) Repeat steps 1 through 5 for phases B and C.


Step 7. (Optional) Repeat Steps 2 through 6 for setting groups 1 through 3 using the CS/CO-GROUP
command to change setting groups.

Unrestrained Time Verification


A timing circuit or a contact monitor with timing algorithm must be used to time the output contact status
change. For more information on determining the minimum pickup current, refer to Sidebar 13-8.

13-44 Testing And Maintenance BE1-CDS


Step 1. Connect one current source to terminals B1, B2 (A-phase, input 1) and a second current
source to terminals B9, B10 (A-phase, input 2).
Step 2. Send the commands listed in Table 13-33 to the relay to setup a test of the response time of
the 87 unrestrained elements.
Table 13-33. Unrestrained Element Response Time Setup Commands
Command Purpose
A= Gain access
SL-N=NONE Zero out custom logic settings/overwrite with logic =
none settings
Y Confirm overwrite
SL-N=DIFF Sets DIFF as custom logic name
SL-87=1,0 Enables 87
SL-VO1=87UT Enables OUT1 to close with 87 unrestrained trip
SG-CT1=1,WYE,NA,0 ctr=1, ct=wye, xfmr=na, no grd source
SG-CT2=1,WYE,NA,0 ctr=1, ct=wye, xfmr=na, no grd source
SG-TRIGGER=87UT,87UT,0 Enable 87UT to log and trigger fault recording
S#-TAP87=MANUAL,2.00,2.00 set tap 1=2.00 and tap 2=2.00
nd th
S#-87=0,15,0,0,2,1 Minpu = 0, slope = 15%, 2 = disabled, 5 = disabled,
nd
URO = 2 times TAP unrestrained pickup, 2 harm
sharing = shared
E Exit
Y Save settings

Step 3. Apply 1 multiple of tap current (2 amperes) to both A-phase input 1 and A-phase input 2 (at
o
180 phase relation to input 1).
Step 4. To force an unrestrained trip at 1.5 times pickup, you must apply a step change in the current
on input 2 to 8.0 amps. Apply step change in current to input 2 and record the time interval
between the time the step change was initiated to the time OUT1 output contact closes (the
unrestrained trip (87UT)).
Step 5. Reduce the current to input 2 until OUT1 contact opens.
Step 6. Apply 1 multiple of tap current (2 amperes) to both A-phase input 1 and A-phase input 2 (at
o
180 phase relation to input 1).
Step 7. To force an unrestrained trip at 5 times pickup, you must apply a step change in the current on
input 2 to 22 amperes.
Step 8. Apply step change in current to input 2 and record the time interval between the time the step
change was initiated to the time OUT1 output contact closes (the unrestrained trip (87UT)).
Step 9. Reduce the current to input 2 until OUT1 contact opens.
Step 10. The time measured in Steps 4 and 8 should be less than those shown in Table 13-34.
Table 13-34. Restrained Trip Operate Times
Function Differential current Time
Unrestrained trip 1.5 times pu Less than 2 cycles
Unrestrained trip 5 times pu Less than 1 cycle
Step 11. (Optional) Repeat steps 1 through 10 for phases B and C.

BE1-CDS Testing And Maintenance 13-45


Step 12. (Optional) Repeat Steps 3 through 11 for setting groups 1 through 3 using the CS/CO-GROUP
command to change setting groups.

Neutral Differential (87ND)

Minimum Pickup
Purpose: To verify the accuracy of the restraint operation of the 87ND element.
Reference Commands: SL-87ND, SL- VO, SG-CT, S(n)-87, S(n)-TAP87
Step 1. Connect current source 1 to terminals B7 and B8 (ground input). See Figure 13-15. An ohm-
meter or continuity tester may be used to monitor output contact status.

180 degrees
circuit current current
monitor source 1 source 2

IA1 IB1 IC1 IG IA2 IB2 IC2

B1 B3 B5 B7 B9 B11 B13 B15

B2 B4 B6 B8 B10 B12 B14 B16

IA1 IB1 IC1 IG IA2 IB2 IC2

Figure 13-15. Connection for 87ND Minimum Pickup Verification


Step 2. To prepare the 87ND element for testing, transmit the commands in Table 13-35 to the relay.
Table 13-35. 87ND Pickup Test Commands
Command Purpose
A= Gain access
SL-N=NONE Zero out custom logic settings/overwrite with logic =
none settings
Y Confirm overwrite
SL-N=NDIFF Name custom logic for this test
SL-87=0 Disables 87
SL-87ND=2,0 Enables 87ND, mode=IG v. CT2, no blk
SL-VO1=87NDT Enables OUT1 to close for 87ND restrained trip
SG-CT2=1,WYE,NA,0 input 2 ctr=1, ct=wye, xfmr=na, no grd source
SG-CTG=1 gnd input ctr=1
SG-TRIGGER=87NDT, Enable 87NDT to log and trigger fault recording
87NDPU,0
S#-87ND=0.1,15,50m Minpu = 0.1, slope = 15%, 50 ms (minimum time
delay)
E Exit
Y Save settings

13-46 Testing And Maintenance BE1-CDS


NOTE
With the relay in service, it is necessary to view the 87ND tap factors by accessing the
HMI screen \PROT\SGn\87ND\87ND.

Step 3. The relay auto tap compensation logic will calculate TAPN and TAPG values based on the CT
ratios for the designated phase CTs and the ground CT. Since CTR2 and CTRG are both
equal to 1:1 for this test, the TAPN and TAPG values are both equal to the minimum settings
for either 5 ampere or 1 ampere relays (2.0 and 0.4 respectively). For more information on
auto tap compensation, see Sidebar 13-9.

Sidebar 13-9. Auto Tap Compensation


Tap adjustment factors for the 87ND function are automatically calculated based on the equation:
TAPN * CTRn = TAPG * CTRG
where CTRn is the CT ratio for the CT designated in the SL-87ND setting in the active logic. Currents are
tap adjusted based on the CT ratios with the driving tap (CT input with the highest CTR) set at the
minimum setting (2.0 for 5 ampere sensing relays and 0.4 for 1 ampere sensing relays) and the other tap
adjusted to the driving tap based on the equation above. For more information on Auto Tap
Compensation, refer to Section 4, Protection And Control Functions, Differential Protection, 87ND Neutral
Differential Function.

Step 4. Apply current to the ground input and slowly ramp up until OUT1 closes.
Step 5. Accuracy when increasing or decreasing the input current is ±4% of setting or 75 milliamperes
(whichever is larger) for 5 ampere sensing inputs and ±4% of setting or 25 milliamperes
(whichever is larger) for 1 ampere sensing inputs. Verify that pickup occurred within the
specified accuracy of the relay.
Step 6. Decrease the current to the ground input until the relay drops out.
Step 7. Repeat for all other values shown in Table 13-36 by substituting for minpu in the S#-87ND
command or if supplied with the HMI option, by navigating to screen \PROT\SGn\87ND\87ND
and editing the MIN PICKUP value.
Table 13-36. Minimum Pickup Accuracy Limits (87ND)
Sensing Type MINPU Calculated TAPG Pickup (A) Low Limit (A) High Limit (A)
5A 0.10 2.00 0.20 0.125 0.275
0.50 2.00 1.00 0.925 1.075
1.00 2.00 2.00 1.920 2.080
1A 0.10 0.40 0.04 0.015 0.065
0.50 0.40 0.20 0.175 0.225
1.00 0.40 0.40 0.375 0.425
Step 8. (Optional) Repeat Steps 2 through 8 for setting groups 1 through 3, using the CS/CO-GROUP
command to change setting groups.

Restrained Pickup Verification (87ND)


Purpose: To verify the accuracy of the restraint operation of the 87ND element.
Reference Commands: SL-87ND, SL- VO, SG-CT, S(n)-87, S(n)-TAP87
Step 1. Connect one current source to terminals B9 and B10 (A-phase input 2) and a second source at
o
180 to terminals B7 and B8 (ground input). See Figure 13-16. An ohm-meter or continuity
tester may be used to monitor output contact status.

BE1-CDS Testing And Maintenance 13-47


180 degrees
circuit current current
monitor source 1 source 2

IA1 IB1 IC1 IG IA2 IB2 IC2

B1 B3 B5 B7 B9 B11 B13 B15

B2 B4 B6 B8 B10 B12 B14 B16

IA1 IB1 IC1 IG IA2 IB2 IC2

Figure 13-16. Connection for 87ND Restraint Pickup Verification


Step 2. To prepare the 87ND element for testing the restraint operation accuracy, transmit the
commands in Table 13-37 to the relay.
Table 13-37. 87ND Restraint Operation Accuracy Test Commands
Command Purpose
A= Gain access
SL-N=NONE Zero out custom logic settings/overwrite with
logic = none settings
Y Confirm overwrite
SL-N=NDIFF Name custom logic for this test
SL-87=0 Disables 87
SL-87ND=2,0 Enables 87ND, mode=IG v. CT2, no blk
SL-VO1=87NDT Enables OUT1 to close for 87ND restrained trip
SG-CT2=1,WYE,NA,0 input 2 ctr=1, ct=wye, xfmr=na, no grd source
SG-CTG=1 gnd input ctr=1
SG-TRIGGER=87NDT, Enable 87NDT to log and trigger fault recording
87NDPU,0
S#-87ND=0.35,15,50m Minpu = 0.35, slope = 15%, minimum time delay
E Exit
Y Save settings

NOTE
The ground differential function always uses the maximum restraint principle as its
operating characteristic. Thus, the slope setting is simply a number between 15 and 60.

Step 3. The auto tap compensation logic of the relay will calculate TAPN and TAPG values based on
CT ratios for the designated phase CTs and the ground CT. Since CTR2 and CTRG are both
equal to 1:1 for this test, the TAPN and TAPG values are both equal to the minimum settings
for either 5 ampere or 1 ampere relays (2.0 and 0.4 respectively).

13-48 Testing And Maintenance BE1-CDS


NOTE
Tables 13-38 and 13-39 show values for testing the relay either by increasing input 2
(neutral) current or decreasing the ground input current. Both methods are shown for
convenience and either method may be used. For differences in measurement of the two
methods, refer to the paragraphs in this Section, Functional Testing, Restrained Pickup
and Sidebar 13-3, Maximum Restraint Operating Characteristic.

Step 4. Input current values for this step are provided in Table 13-38 or 13-39. Apply balancing current
to phase A input 2 (represented as the Neutral column) and the ground input as indicated in
each row and slowly increase phase A input 2 until OUT1 closes.
Step 5. Remove both currents.
Step 6. Verify the restrained pickup accuracy as listed in the appropriate Table (13-38 or 13-39).
Step 7. (Optional) Repeat Steps 2 through 6 for setting groups 1 through 3 using the CS/CO-GROUP
command to change setting groups.

Table 13-38. Restraint Pickup Test Points (87ND – 5 Ampere Sensing Input)
Sensing Neutral (Input 2) Ground Increasing Input 2 Decreasing IG
Input Minimum slope Calc. Tap = 2.00 Calc. Tap = 2.00 From Balance From Balance
Type Pickup (%) Bal. Input (A) PU Bal. Input (A) PU Pickup (A) Pickup (A)

5 0.35 15 2.00 1 2.00 1 2.70 ± 0.108 1.30 ± 0.075


5 0.35 15 10.00 5 10.00 5 11.76 ± 0.470 8.50 ± 0.340
5 0.35 30 2.00 1 2.00 1 2.86 ± 0.108 1.30 ± 0.075
5 0.35 30 10.00 5 10.00 5 14.29 ± 0.572 7.00 ± 0.280
5 0.35 45 2.00 1 2.00 1 3.64 ± 0.146 1.10 ± 0.075
5 0.35 45 10.00 5 10.00 5 18.18 ± 0.727 5.50 ± 0.220
5 0.35 60 2.00 1 2.00 1 5.00 ± 0.200 0.80 ± 0.075
5 0.35 60 10.00 5 10.00 5 25.00 ± 0.100 4.00 ± 0.160

Table 13-39. Restraint Pickup Test Points (87ND – 1 Ampere Sensing Input)
Sensing Input 1 Input 2 Increasing Input 1 Decreasing Input 2
Input Minimum slope tap = 2.00 tap = 3.80 From Balance From Balance
Type Pickup (%) Bal. Input (A) PU Bal. Input (A) PU Pickup (A) Pickup (A)

1 0.35 15 0.40 1 0.40 1 0.54 ± 0.025 0.26 ± 0.025


1 0.35 15 2.00 5 2.00 5 2.35 ± 0.094 1.70 ± 0.068
1 0.35 30 0.40 1 0.40 1 0.57 ± 0.025 0.26 ± 0.025
1 0.35 30 2.00 5 2.00 5 2.86 ± 0.114 1.40 ± 0.056
1 0.35 45 0.40 1 0.40 1 0.73 ± 0.029 0.22 ± 0.025
1 0.35 45 2.00 5 2.00 5 3.64 ± 0.146 1.10 ± 0.044
1 0.35 60 0.40 1 0.40 1 1.00 ± 0.040 0.16 ± 0.025
1 0.35 60 2.00 5 2.00 5 5.00 ± 0.200 0.80 ± 0.032

Instantaneous Overcurrent

Pickup And Dropout Verification (50T/150T/250T)


Purpose: To verify the accuracy of the operation of the 50T/150T/250T elements.
Reference Commands: SL-50T/150T/250T, SL-GROUP, SL-VO

BE1-CDS Testing And Maintenance 13-49


Step 1. Connect a current source to terminals B1 and B2 (A phase input 1).
Step 2. To initially prepare the 50T/150T/250T elements for testing, transmit the commands in Table
13-40 to the relay.
Table 13-40. 50T/150T/250T Overcurrent Test Commands
Command Purpose
A= Gain access
SL-N=NONE Zero out custom logic settings/overwrite with
logic = none settings
Y Confirm overwrite
SL-N=PU50 Name custom logic for this test
SL-50T=1,0 Enables 50TP/50TN/50TQ, CT input 1
SL-VO1=50TPT Enables OUT1 to close for 50T P trip
SL-VO2=50TNT Enables OUT2 to close for 50T N trip
SL-VO3=50TQT Enables OUT3 to close for 50T Q trip
SG-CT1=1,WYE,NA,0 Input 1 ctr=1, ct=wye, xfmr=na, no grd source
SG-TRIGGER=50TPT+ Enable 50TP+50TN+50TQ to log and trigger fault
50TNT,+50TQT50TPPU+5 recording
0TNPU,+50TQN,0
E Exit
Y Save settings

Step 3. Send the first appropriate row of the setting commands S0-50TP, S0-50TN, and S0-50TQ from
Table 13-41 to the relay. If your relay is supplied with the HMI option, you may also go to the
front panel interface screen \PROT\SG0\50T\50T and edit the S0-50TP, S0-50TN, and S0-
50TQ settings.
Table 13-41. Instantaneous 50T Element Test Values
Sensing Negative
Input Type Phase Sequence Neutral Comments
5A S0-50TP=0.5,0 S0-50TQ=0,0 S0-50TN=0.5,0 Note 1
S0-50TP=5.0,0 S0-50TQ=1.67,0 S0-50TN=5.0,0 Note 2
S0-50TP=25.0,0 S0-50TQ=8.33,0 S0-50TN=25.0,0 Note 2
1A S0-50TP=0.1,0 S0-50TQ=0,0 S0-50TN=0.1,0 Note 1
S0-50TP=1.0,0 S0-50TQ=0.33,0 S0-50TN=1.0,0 Note 2
S0-50TP=5.0,0 S0-50TQ=1.67,0 S0-50TN=5.0,0 Note 2
Notes For Table 13-41:
1. Sets 50TP and 50TN to pickup at 0.5 amperes test current, and 50TQ is disabled.
2. Sets all 50T<x> to pickup at 0.5 amperes test current.
3. See Sidebar 13-10 for more information on negative sequence pickup.
Step 4. Slowly ramp up current on the phase A input until OUT1, OUT2, and OUT3 close. (In
accordance with Note 1 for Table 13-41, OUT3 will not close when 50TQ is disabled.) Verify
that pickup occurred within the specified accuracy of the relay as listed in Table 13-42.

13-50 Testing And Maintenance BE1-CDS


Table 13-42. Instantaneous 50T Element Accuracy
Sensing Type Pickup Accuracy - Phase and Neutral
A or B (1 ampere nominal systems) ± 2% of setting or ± 10 milliamperes
D, E, or F (5 ampere nominal systems) ± 2% of setting or ± 50 milliamperes

Step 5. After pickup occurs, slowly ramp the current down until both OUT1, OUT2, and OUT3 open.
Verify that dropout occurred as specified (95% ± 2%).
Step 6. Repeat Steps 3, 4, and 5 for all values in Table 13-42. Optionally, reconnect the current
source to B-phase (B3, B4) and C-phase (B5, B6) inputs to test the response of all phases for
each succeeding test.
Step 7. (Optional) Repeat steps 3 through 6 for phases B and C of the relay unless each phase was
tested in step 4. If so, skip this step and proceed to Step 8.
Step 8. (Optional) Repeat steps 1 through 7 for the 150T and 250T elements. Use Table 13-43 or 13-
44 as a reference for substituting the commands used in Step 1.

Table 13-43. Instantaneous Overcurrent 150T Element Test Logic


Replace These Commands With These Commands For 150T Element Tests
SL-50T=1,0 SL-150T=1,0
SL-VO1=50TPT SL-VO1=150TPT
SL-VO2=50TNT SL-VO2=150TNT
SL-VO3=50TQT SL-VO3=150TQT
SG-TARG=50T SG-TARG=150T
SG-TRIGGER=50TPT+50TNT+50TQT, SG-TRIGGER=150TPT+150TNT+150TQT,150TPPU+
50TPPU+ 50TNPU,+50TQPU,0 150TNPU+150TQTPU,0

Table 13-44. Instantaneous Overcurrent 250T Element Test Logic


Replace These Commands With These Commands For 250T Element Tests
SL-50T=1,0 SL-250T=1,0
SL-VO1=50TPT SL-VO1=250TPT
SL-VO2=50TNT SL-VO2=250TNT
SL-VO3=50TQT SL-VO3=250TQT
SG-TARG=50T SG-TARG=250T
SG-TRIGGER=50TPT+50TNT+50TQT, SG-TRIGGER=250TPT+250TNT+250TQT,250TPPU+
50TPPU+50TNPU+50TQPU,0 250TNPU+250TQTPU,0

Step 9. (Optional) Repeat steps 1 through 8 for the 50T, 150T, and 250T elements in setting groups 1,
2, and 3. Use the following information as a guide to program the 50T/150T/250T elements in
higher order setting groups.
In order to program the pickup of the elements in a higher order setting group, you would
replace the 0 in the S0-50TP, S0-50TN, and S0-50TQ commands in Table 13-41 with either a
1, 2, or 3 for setting groups 1, 2, or 3. Or, if your relay is supplied with the HMI option, you can
program each set of values by navigating to the appropriate setting group screen
\PROT\SGn\50T\50T, where n is equal to the setting group you desire. Refer to the CS/CO-
GROUP command in Section 4, Protection And Control Functions for more information on
changing the active setting group.

BE1-CDS Testing And Maintenance 13-51


To change from group 0 to group 1, execute the following commands.
CS-GROUP=1 select setting group 1
CO-GROUP=1 execute setting group 1
Using the basic information in Table 13-41, program the pickup of the elements for setting
group 1 and, optionally, proceed with group 1 testing.

Sidebar 13-10. Negative Sequence Overcurrent Element Pickup


A three-phase electric power system can be modeled using a set of balanced equations known as
symmetrical components. These components provide a practical method of analyzing power system
operation during unbalanced conditions such as would occur during a fault.
The symmetrical components of a power system are segregated into positive, negative, and zero
sequence components. At any given time, all of these components may be present in load current due to
unbalanced load, etc. In practice however, asymmetrical current or voltage conditions are more typical
due to unbalanced loads, unbalanced system faults, open conductors, etc. In the case of an unbalanced
load, this condition may be detrimental to the operation of a power system and the equipment. Under
unbalanced fault conditions, these components will very likely be harmful to equipment and potentially, to
personnel. Positive sequence components are comprised of balanced three-phase currents and line-to-
neutral voltages supplied by power system generators. Under any of these scenarios, negative sequence
and zero sequence components will be present. The associated figure shows the sequence components
in phasor form.
Ic1 Ib2
positive negative zero

Ia0 = Ib0 = Ic0


Ia1 Ia2

Ib1 Ic2

Sequence Components In Phasor Form


These sequence component quantities are very useful in that they can be measured and used as
operating parameters to help safeguard equipment. Proper management of the power system conserves
resources and minimizes potentially harmful exposure to the public and operating personnel.
Using symmetrical components, we can say the following about phase currents.
Ia = I1 + I2 + I0(see the associated figure)
Ib = α 2I1 + α I2 + I0
Ic = α I1 + α 2I2 + I0where α is an operator equal to 1.0 ∠120o.
From this we can derive that the equation for negative sequence current I2, is
I2 = /3 (Ia + α Ib + α Ic)
1 2

Under balanced conditions, this value would be zero. If a single-phase input is applied, then a negative
sequence quantity will appear to the relay. If we let Ib = Ic = 0, then, I2 = Ia ! 3 .

13-52 Testing And Maintenance BE1-CDS


Time Overcurrent

Pickup And Dropout Verification (51/151/251)


Purpose: To verify the accuracy of the operation of the 51/151/251 elements.
Reference Commands: SL-51/151/251, S<n>-51
Step 1. Connect a current source to terminals B1 and B2 (A-phase input 1).
Step 2. To initially prepare the 51/151/251 elements for pickup and dropout testing, send the
commands in Table 13-45 to the relay.
Table 13-45. 51/151/251 Time Overcurrent Test Commands
Command Purpose
A= Gain access
SL-N=NONE Zero out custom logic settings/overwrite with
logic = none settings
Y Confirm overwrite
SL-N= 51 Name custom logic for this test
SL-51=1,0 Enables 51P/51N/51Q, CT input 1
SL-VO1=51PT Enables OUT1 to close for 50P trip
SL-VO2=51NT Enables OUT2 to close for 51N trip
SL-VO3=51QT Enables OUT3 to close for 51Q trip
SG-CT1=1,WYE,NA,0 Input 1 ctr=1, ct=wye, xfmr=na, no grd source
SG-TRIGGER=51PT+ Enable 51PT+51NT+51QT to log targets and
51NT+51QT,51PPU+ trigger fault recording
51NPU+51QPU,0
E Exit
Y Save settings

Step 3. Transmit to the relay the appropriate row of the setting commands S0-51P from Table 13-46.
If your relay is supplied with the HMI option, you may also go to the front panel interface
screen \PROT\SG0\51\51 and edit the 51P, 51N, and 51Q settings.
Table 13-46. Time Overcurrent 51 Element Test Settings
Sensing Phase Neutral Negative Sequence
Input Type
1A S0-51P=1.0,0.5,I2 S0-51N=1.0,0.5,I2 S0-51QN=0.33,0.5,I2
5A S0-51P=5.0,0.5,I2 S0-51N=5.0,0.5,I2 S0-51QN=1.67,0.5,I2
Notes For Table 13-46
1. See Sidebar 13-10 for more information on negative sequence pickup.
Step 4. Slowly ramp up current on the phase A input until OUT1, OUT2, and OUT3 close. Verify that
pickup occurred within the specified accuracy of the relay as listed in Table 13-47
Table 13-47. Time Overcurrent 51 Element Accuracy
Sensing Type Pickup Accuracy - Phase and Neutral
A or B (1 ampere nominal systems) ± 2% of setting or ± 10 milliamperes
D, E, or F (5 ampere nominal systems) ± 2% of setting or ± 50 milliamperes

BE1-CDS Testing And Maintenance 13-53


Step 5. After pickup occurs, slowly ramp the current down until both OUT1, OUT2, and OUT3 open.
Verify that dropout occurred as specified (95% ± 2%).
Step 6. Repeat Steps 3, 4, and 5 for all values in Table 13-46. Optionally, reconnect the current
source to B-phase (B3, B4) and C-phase (B5, B6) inputs to test the response of all phases for
each succeeding test.
Step 7. (Optional) Repeat steps 3 through 6 for phases B and C of the relay unless each phase was
tested in step 4. If so, skip this step and proceed to Step 8.
Step 8. (Optional) Repeat steps 1 through 7 for the 151 and 251 elements. Use Table 13-48 or 13-49
as a reference for substituting the commands used in Step 1.

Table 13-48. Time Overcurrent 151 Element Test Logic


Replace These Commands With These Commands For 151 Element Tests
SL-51=1,0 SL-151=1,0
SL-VO1=51PT SL-VO1=151PT
SL-VO2=51NT SL-VO2=151NT
SL-VO3=51QT SL-VO3=151QT
SG-TARG=51 SG-TARG=151
SG-TRIGGER=51PT+51NT+51QT, 51PPU+ SG-TRIGGER=151PT+151NT+151QT,151PPU+
51NPU,+51QPU,0 151NPU+151QTPU,0

Table 13-49. Time Overcurrent 251 Element Test Logic


Replace These Commands With These Commands For 251 Element Tests
SL-51=1,0 SL-251=1,0
SL-VO1=51PT SL-VO1=251PT
SL-VO2=51NT SL-VO2=251NT
SL-VO3=51QT SL-VO3=251QT
SG-TARG=51 SG-TARG=251
SG-TRIGGER=51PT+51NT+51QT, 51PPU+ SG-TRIGGER=251PT+251NT+251QT,251PPU+
51NPU,+51QPU,0 251NPU+251QTPU,0

Step 9. (Optional) Repeat steps 1 through 8 for the 51, 151, and 251 elements in setting groups 1, 2,
and 3. Use the following information as a guide to program the 51/151/251 elements in higher
order setting groups.
In order to program the pickup of the elements in a higher order setting group, you would
replace the 0 in the S0-51P, S0-51N, and S0-51Q commands in Table 13-45 with either a 1, 2,
or 3 for setting groups 1, 2, or 3. Or, if your relay is supplied with the HMI option, you can
program each set of values by navigating to the appropriate setting group screen
\PROT\SGn\51\51, where n is equal to the setting group you desire. Refer to the CS/CO-
GROUP command in Section 4, Protection And Control Functions for more information on
changing the active setting group.
To change from group 0 to group 1, execute the following commands.
CS-GROUP=1 select setting group 1
CO-GROUP=1 execute setting group 1

13-54 Testing And Maintenance BE1-CDS


Using the basic information in Table 13-45, program the pickup of the elements for setting
group 1 and, optionally, proceed with the testing.

Timing Verification (51/151/251)


Purpose: To verify the accuracy of the timing operation of the 51/151/251 elements.
Reference Commands: SL-51/151/251, S<n>-51
Step 1. Connect a current source to terminals B1 and B2 (A-phase input 1).
Step 2. To initially prepare the 51/151/251 elements for testing, send the commands in Table 13-50 to
the relay.
Table 13-50. 51/151/251 Overcurrent Timing Test Commands
Command Purpose
A= Gain access
SL-N=NONE Zero out custom logic settings/overwrite with
logic = none settings
Y Confirm overwrite
SL-N= 51 Name custom logic for this test
SL-51=1,0 Enables 51P/51N/51Q, CT input 1
SL-VO1=51PT Enables OUT1 to close for 50P trip
SL-VO2=51NT Enables OUT2 to close for 51N trip
SL-VO3=51QT Enables OUT3 to close for 51Q trip
SG-CT1=1,WYE,NA,0 Input 1 ctr=1, ct=wye, xfmr=na, no grd source
SG-TRIGGER=51PT+ Enable 51PT+51NT+51QT to log targets and
51NT+51QT,51PPU+ trigger fault recording
51NPU+51QPU,0
E Exit
Y Save settings

Step 3. Transmit to the relay the appropriate row of the setting commands S0-51P from Table 13-51.
If your relay is supplied with the HMI option, you may also go to the front panel interface
screen \PROT\SG0\50T\50T and edit the 51P, 51N, and 51Q settings.
Table 13-51. Time Overcurrent 51 Element Test Settings
Sensing Phase Neutral Negative Sequence
Input Type
1A S0-51P=1.0,0.5,I2 S0-51N=1.0,0.5,I2 S0-51QN=0.33,0.5,I2
5A S0-51P=5.0,0.5,I2 S0-51N=5.0,0.5,I2 S0-51QN=1.67,0.5,I2
Notes For Table 13-51
1. See Sidebar 13-10 for more information on negative sequence pickup.
Step 4. Using the values listed in Table 13-52, apply the current listed to the A phase current input and
measure the time between the application of current and the time it takes for the relay outputs
OUT1, OUT2, and OUT3 to close. Verify that the relay performs with the specified limits. An
ohm-meter or continuity tester may be used to monitor the output contacts status.
Step 5. After each pickup occurs, slowly ramp current down until OUT1, OUT2, and OUT3 open.
Dropout should occur at 95% ± 2%.

BE1-CDS Testing And Maintenance 13-55


Table 13-52. Time Overcurrent 51 Element Test Values
Relay Trip
Sensing Input Type Time Dial Applied Current Lower Limit Higher Limit
1A 0.5 1.50 A 0.748 sec 0.827 sec
5.00 A 0.190 sec 0.240 sec
5.0 1.50 A 7.244 sec 8.007 sec
5.00 A 1.798 sec 1.988 sec
9.9 1.50 A 14.318 sec 15.825 sec
5.00 A 3.535 sec 3.907 sec
5A 0.5 7.5 A 0.748 sec 0.827 sec
25.0 A 0.190 sec 0.240 sec
5.0 7.5 A 7.244 sec 8.007 sec
25.0 A 1.798 sec 1.988 sec
9.9 7.5 A 14.318 sec 15.825 sec
25.0 A 3.535 sec 3.907 sec

Step 6. Repeat Steps 3, 4, and 5 for all current and time dial settings listed (using the command S0-
51P, 51N, and 51Q or, if your relay is supplied with the HMI option, by navigating to screen
\PROT\SG0\51\51 to edit the 51P, 51N, and 51Q settings) and optionally, reconnect the
current source to B-phase (B3, B4) and C-phase (B5, B6) inputs to test the response of all
phases for each succeeding test.
Step 7. (Optional) Repeat Steps 2 through 6 for B and C phase elements unless each phase was
tested in previous steps. If so, skip this step and proceed to Step 8.
Step 8. (Optional) Repeat Steps 1 through 7 for the 151 and 251 elements respectively. Use Table 13-
51 or 13-52 as a reference for substituting the commands used in Step 1.
Step 9. (Optional) Repeat steps 1 through 8 for the 51, 151, and 251 elements in setting groups 1, 2,
and 3. Use the following information as a guide to program the 51/151/251 elements in higher
order setting groups.
In order to program the pickup of the elements in a higher order setting group, you would
replace the 0 in the S0-51P, S0-51N, and S0-51Q commands in Table 13-50 with either a 1, 2,
or 3 for setting groups 1, 2, or 3. Or, if your relay is supplied with the HMI option, you can
program each set of values by navigating to the appropriate setting group screen
\PROT\SGn\51\51, where n is equal to the setting group you desire. Refer to the CS/CO-
GROUP command in Section 4, Protection And Control Functions for more information on
changing the active setting group.
To change from group 0 to group 1, execute the following commands.
CS-GROUP=1 select setting group 1
CO-GROUP=1 execute setting group 1
Using the basic information in Table 13-50, program the pickup of the elements for setting
group 1 and, optionally, proceed with the testing.

Breaker Failure
Purpose: To verify the operation of the breaker failure (BF) function.
Reference Commands: SL-BF, SP-BF
Step 1. Prepare the BF function block for testing by transmitting the commands in Table 13-53 to the
relay.
13-56 Testing And Maintenance BE1-CDS
Table 13-53. BF Pickup Test Commands
Command Purpose
A= Gain write access
SL-N=NONE Zero out custom logic settings. Overwrite with
logic = none settings.
Y Confirm overwrite
SL-N=BF Sets BF as custom logic name
SL-BF=1,IN4,/IN3 Enables BF CT input 1, IN4 initiate, /IN3 block
SL-VO1=BFT Enables OUT1 to close for BF trip
SL-VO2=BFPU Enables OUT2 to close for BF pickup
SG-CT=1,WYE,NA,0 Input 1 ctr=1, ct=wye, xfmr=na, no grd source
SG-TRIGGER=BFT,BFPU,0 Enable BFT to log and trigger fault recording
SP-BF=50m Set BF time delay at minimum
EXIT Exit
Y Save settings

Step 2. Apply wetting voltage to relay inputs IN3 and IN4. This applies the BF initiate, and removes
the BF block..
The BF current detector dropout setting is a fixed value that is determined by the relay current
sensing type. Table 13-54 lists the pickup setting for each current sensing type.
Table 13-54. BF Current Detector Dropout Settings
Sensing Type Dropout Setting
A or B (1 ampere nominal systems) 0.1 A

D, E, or F (5 ampere nominal systems) 0.5 A

Step 3. Connect a current source to terminals B1 and B2 (A-phase input). Slowly decrease the current
applied until OUT2 (and subsequently OUT1) opens. Compare the applied current to the
current values listed in Table 13-55. Verify that dropout occurred between the lower and upper
limits for your relay.
Table 13-55. BF Dropout Limits
Sensing Type Lower Dropout Limit Upper Dropout Limit
A or B (1 ampere nominal systems) 0.09 A 0.11 A

D, E, or F (5 ampere nominal systems) 0.45 A 0.55 A

Step 4. Transmit the commands in Table 13-56 to set the BF time delay.
Table 13-56. BF Time Delay Commands
Command Purpose
A= Gain write access
SP-BF=100m Sets BF time delay at 100 milliseconds
EXIT Exit
Y Save settings
Step 5. Verify the BF time delay by applying nominal current for the duration given in the following
steps.
1. Apply nominal current to phase A for 4 cycles (67 ms at 60 Hz). No trip should occur.
2. Apply nominal current to phase A for 5 cycles. (83 ms at 60 Hz). No trip should occur.

BE1-CDS Testing And Maintenance 13-57


3. Apply nominal current to phase A for 7 cycles (117 ms at 60 Hz). A BF trip should
occur. Use the RS-LGC command to retrieve an SER report and verify that a BF trip
was logged 100 milliseconds ±0.5 percent or +1¼, -¼ cycles, whichever is greater

Step 6. (Optional) Remove the wetting voltage from relay input IN3. This blocks the breaker fail logic.
Apply nominal current to phase A. Verify that relay outputs OUT1 and OUT2 open and remain
open (BF element does not operate) in spite of pickup current being applied. Apply the wetting
voltage to relay input IN3 and verify that OUT2 (and subsequently OUT1) closes. Remove
current from phase A.
Step 7. (Optional) Apply nominal current to phase A. OUT2 and OUT1 should close. Remove the
wetting voltage from relay input IN4 and verify that OUT1 and OUT2 open. Remove current
from phase A.
Step 8. Apply wetting voltage to relay input IN4 and nominal current to the phase A current input.
Measure the time between the application of current and OUT1 closing. OUT2 should have
closed immediately when current was applied. Verify that the BF timer operated within the
specified accuracy of ±0.5 percent of setting or +1¼, -¼ cycles, whichever is greater.
Step 9. (Optional) Repeat Steps 3 through 8 for the phase B and phase C elements.

Virtual Switch Verification (43/143/243/343/443/543/643/743)


To test the virtual switches, we verify each mode of operation but do not verify each of the eight virtual
switches. In your testing, you may substitute any or all of the switches as you choose. If you give an
invalid command such as CS-243=1/CO-243=1 when switch 243 is programmed for mode 3 operation, the
relay will not operate on the command and if you were using the ASCII command interface, the monitor
would return an INVALID PARAMETER. For more information on virtual switch operation, see Section 4,
Protection And Control Functions, Virtual Switches. You may verify operation of virtual switches by
monitoring the programmed output contacts, by monitoring the front panel interface screen \CTRL\xx, or
by using the RS-LGC command to retrieve logic variable data from the SER. You may also use the RG-
STAT command. See Section 6, Reporting And Alarm Functions for more information on reports.

Virtual Switch Mode 1 Operation (On/Off/Pulse)


Purpose: To verify virtual switch Mode 1 operation.
Reference Commands: SL-43, CS/CO-43
Step 1. Prepare for Mode 1 testing by transmitting the commands in Table 13-62 to the relay.
Table 13-57. Mode 1 Test Commands
Command Purpose
A= Gain write access
SL-N=NONE Zero out custom logic settings. Overwrite with
logic = none settings.
Y Confirm overwrite
SL-N=MODE1 Sets MODE1 as custom logic name
SL-43=1 Sets 43 to Mode 1 operation
SL-VO1=43 Enables OUT1 to close for 43
EXIT Exit
Y Save settings

Step 2. Prepare to monitor the virtual switch operation.


Step 3. Transmit the commands in Table 13-58 to the relay or, if the optional HMI is supplied, navigate
to screen \CTRL\43\43 to set the mode of the 43 switch to the TRUE state (logic 1).
Result: OUT1 contact closes and remains closed.

13-58 Testing And Maintenance BE1-CDS


Table 13-58. Mode 1 Test Commands
Command Purpose
A= Gain write access
CS-43=1 Selects virtual switch 43 for change to closed (true) state
CO-43=1 Executes virtual switch 43 for change to closed (true) state

Step 4. Transmit the commands in Table 13-59 to the relay or, if the optional HMI is supplied, navigate
to screen \CTRL\43\43 to set the mode of the 43 switch to the FALSE state (logic 0). It is not
necessary to gain access for the following steps unless access times out.
Result: OUT1 contact opens and remains open.
Table 13-59. Mode 1 Test Commands
Command Purpose
CS-43=0 Selects virtual switch 43 for change to open (false) state
CO-43=0 Executes virtual switch 43 for change to open (false) state

Step 5. Transmit the commands in Table 13-60 to the relay or, if the optional HMI is supplied, navigate
to screen \CTRL\43\43 to set the mode of the 43 switch to the pulse state.
Result: OUT1 contact closes for 200 milliseconds and returns to the open state.
Table 13-60. Mode 1 Test Commands
Command Purpose
CS-43=P Selects virtual switch 43 for change to closed (true) state and return open
CO-43=P Executes virtual switch 43 for change to closed (true) state and return open

Virtual Switch Mode 2 Operation (On/Off)


Purpose: To verify virtual switch Mode 2 operation.
Reference Commands: SL-143, CS/CO-143
Step 1. Prepare for Mode 2 testing by transmitting the commands in Table 13-61 to the relay.
Table 13-61. Mode 2 Test Commands
Command Purpose
A= Gain write access
SL-N=NONE Zero out custom logic settings. Overwrite with
logic = none settings.
Y Confirm overwrite
SL-N=MODE2 Sets MODE2 as custom logic name
SL-143=2 Sets 143 to Mode 2 operation
SL-VO1=143 Enables OUT1 to close for 143
EXIT Exit
Y Save settings

Step 2. Prepare to monitor the virtual switch operation.


Step 3. Send the commands in Table 13-62 to the relay or, if the optional HMI is supplied, navigate to
screen \CTRL\43\143 to set the mode of the 143 switch to the TRUE state (logic 1).
Result: OUT1 contact closes and remains closed.

BE1-CDS Testing And Maintenance 13-59


Table 13-62. Mode 2 Test Commands
Command Purpose
A= Gain write access
CS-143=1 Selects virtual switch 143 for change to closed (true) state
CO-143=1 Executes virtual switch 143 for change to closed (true) state

Step 4. Send the commands in Table 13-63 to the relay or, if the optional HMI is supplied, navigate to
screen \CTRL\43\143 to set the mode of the 143 switch to the FALSE state (logic 0). It is not
necessary to gain access for the following step unless access times out.
Result: OUT1 contact opens and remains open.
Table 13-63. Mode 2 Test Commands
Command Purpose
CS-143=0 Selects virtual switch 143 for change to open (false) state
CO-143=0 Executes virtual switch 143 for change to open (false) state

Virtual Switch Mode 3 Operation (Off/Momentary On)


Purpose: To verify virtual switch Mode 3 operation.
Reference Commands: SL-243, CS/CO-243
Step 1. Prepare for Mode 3 testing by transmitting the commands in Table 13-64 to the relay.
Table 13-64. Mode 3 Test Commands
Command Purpose
A= Gain write access
SL-N=NONE Zero out custom logic settings. Overwrite with
logic = none settings.
Y Confirm overwrite
SL-N=MODE3 Sets MODE3 as custom logic name
SL-243=3 Sets 243 to Mode 3 operation
SL-VO1=243 Enables OUT1 to close for 243
EXIT Exit
Y Save settings

Step 2. Prepare to monitor the virtual switch operation.


Step 3. Send the commands in Table 13-65 to the relay or, if the optional HMI is supplied, navigate to
screen \CTRL\43\243 to set the mode of the 243 switch to the pulse state.
Result: OUT1 contact closes for 200 milliseconds and returns to the open state.
Table 13-65. Mode 3 Test Commands
Command Purpose
CS-243=P Selects virtual switch 243 for change to closed (true) state and return open
CO-243=P Executes virtual switch 243 for change to closed (true) state and return open

13-60 Testing And Maintenance BE1-CDS


101 Virtual Breaker Control Switch
Purpose: To verify 101 virtual breaker control switch operation.
Reference Commands: SL-101, CS/CO-101C, CS/CO-101T
Step 1. Prepare for 101 virtual breaker control switch testing by sending the commands in Table 13-66
to the relay.
Table 13-66. 101 Virtual Breaker Control Switch Test Commands
Command Purpose
A= Gain write access
SL-N=NONE Zero out custom logic settings. Overwrite with
logic = none settings.
Y Confirm overwrite
SL-N= S101 Sets S101 as custom logic name
SL-101=1 Enables 101 switch
SL-VO1=101T Enables OUT1 to close for 101T TRUE
SL-VO2=101C Enables OUT2 to close for 101C TRUE
SL-VO3=101SC Enables OUT3 to close for 101SC TRUE
EXIT Exit
Y Save settings

Step 2. Prepare to monitor the 101 virtual breaker control switch operation. You may verify operation
of the virtual switch by monitoring the programmed output contacts or from the front panel
interface screen \CTRL\BKR or by using the RG-STAT command. See Section 6, Reporting
And Alarm Functions for more information.
Step 3. Send the commands in Table 13-67 to the relay or, if the optional HMI is supplied, navigate to
screen \CTRL\BKR to set the mode of the 101 virtual breaker control switch to the trip state.
Result: OUT1 contact closes for 200 milliseconds and returns to the open state, and OUT3 contact
opens (trip state) and remains open.
Table 13-67. 101 Virtual Breaker Control Switch Trip Test Commands
Command Purpose
A= Gain write access
CS-101T=T Selects 101T for trip operation
CO-101T=T Executes 101T for trip operation

Step 4. Send the commands in Table 13-68 to the relay or, if the optional HMI is supplied, navigate to
screen \CTRL\BKR to set the mode of the 101 virtual breaker control switch to the close state.
Result: OUT2 contact closes for 200 milliseconds and returns to the open state, and OUT3 contact
closes (close state) and remains closed.
Table 13-68. 101 Virtual Breaker Control Switch Close Test Commands
Command Purpose
A= Gain write access
CS-101C=C Selects 101C for close operation
CO-101C=C Executes 101C for close operation

BE1-CDS Testing And Maintenance 13-61


Logic Timer Verification (62/162)

Mode 1 - Pickup/Dropout
Purpose: To verify the operation of the 62 timer elements.
Reference Commands: SL-62/162, S<g>-62/162
Step 1. Prepare for mode 1 logic timer verification testing by sending the commands in Table 13-69 to
the relay.
Table 13-69. x62 Mode 1 Test Commands
Command Purpose
A= Gain write access
SL-N=NONE Zero out custom logic settings. Overwrite with
logic = none settings.
Y Confirm overwrite
SL-N=T62 Sets T62 as custom logic name
SL-43=2 Enables 43 switch ON/OFF mode
SN-43=62_INITIATE,PU,DO Name switch to make SER easier to read
SL-62=1,43 Enables 62 PU/DO mode, 43 initiate, no block
S# -62=400m,2000m Sets 62 pickup = 400 ms, dropout = 2,000 ms
EXIT Exit
Y Save settings
Step 2. Send the commands in Table 13-70 to the relay. These commands will initiate the 62 timer by
changing the 43 switch state to closed (logic 1). Once initiated, the 62 timer will force an
output based on the 400 millisecond pickup time setting.
Table 13-70. x62 Mode 1 Timer Initiate Commands
Command Purpose
A= Gain write access
CS-43=1 Selects 43 for close operation
CO-43=1 Executes 43 for close operation
Step 3. Send the commands in Table 13-71 to the relay. These commands will remove the initiate
input from the 62 timer by changing the 43 switch state to open (logic 0) ). It is not necessary
to gain access for the following steps unless access times out.
Table 13-71. x62 Mode 1 Timer Initiate Clear Commands
Command Purpose
CS-43=0 Selects 43 for open operation
CO-43=0 Executes 43 for open operation

Step 4. Use the RS-LGC command to retrieve logic variable data from the SER. Verify that the 43
switch change to a closed state, was logged, and approximately 400 milliseconds later, the 62
timer picked up. Then, some time later, the 43 switch changed to an open state, was logged,
and the 62 timer dropped out approximately 2,000 milliseconds later. The state of the 43
switches in the SER report use the programmable name parameters applied to the switch.
Figure 13-17 illustrates the timing relationship of the 43 switch and 62 timer.

13-62 Testing And Maintenance BE1-CDS


~
~
PU D2595-02.vsd
08-10-00
43 >400 ms

DO

~
~
1

x62 400 ms 2,000 ms

Figure 13-17. x62 Mode 1 (Pickup/Dropout) Timing Example

Mode 2 – One Shot Nonretriggerable


Step 1. Prepare for mode 2 logic timer verification testing by sending the commands in Table 13-72 to
the relay.
Table 13-72. x62 Mode 2 Test Commands
Command Purpose
A= Gain write access
SL-N=NONE Zero out custom logic settings. Overwrite with
logic = none settings.
Y Confirm overwrite
SL-N=T162 Sets T162 as custom logic name
SL-143=3 Enables 143 switch pulse mode
SN-143=162_INI,INI,NORMAL Name switch to make SER easier to read
SL-162=2,143,0 Enables 162 1-shot, nonretriggerable mode,
143 initiate, no blocking
S0-162=400m,20s Sets 162 delay at 400 milliseconds, 162
dropout at 20 seconds
EXIT Exit
Y Save settings

Step 2. Send the commands in Table 13-73 to the relay. These commands supply the 162 timer with a
momentary initiate input by pulsing the 143 switch from a FALSE state to a TRUE state and
then back to a FALSE state. You may view the state changes of the 143 switch at front panel
interface \CTRL\43\143, screen 2.1.2.

NOTE
The 143 switch action is performed twice in this test. To illustrate the action of the timer
mode, the commands of Table 13-73 should be executed as quickly as possible. Ideally,
this test should be repeated within 20 seconds. If this is a problem, try extending the
dropout timer setting to 30 seconds.

Table 13-73. x62 Mode 2 Timer Initiate Commands


Command Purpose
A= Gain write access
CS-143=P Selects 143 for pulse operation
CO-143=P Executes 143 for pulse operation
CS-143=P Selects 143 for pulse operation
CO-143=P Executes 143 for pulse operation

Step 3. Use the RS-LGC command to retrieve logic variable data from the SER. Verify that a 143 pulse
action (FALSE-TRUE-FALSE) was logged and that approximately 400 milliseconds after the
initial 143 FALSE-TRUE-FALSE initiate signal action, the 162 timer output went TRUE. Then,
approximately 20 seconds later, duration timer T2 expired and the timer output went FALSE

BE1-CDS Testing And Maintenance 13-63


despite a second 143 FALSE to TRUE initiate signal while the duration timer was active.
Figure 13-18 illustrates the timing relationship of the 143 switch and x62 timer.

INI
D2595-03.vsd
143 200 ms 200 ms 08-10-00

~
~
Normal

~
~
1

400 ms 20 s

Figure 13-18. x62 Mode 2 (One-Shot Nonretriggerable) Timing Example

Mode 3 – One Shot Retriggerable


Step 1. Prepare for mode 3 logic timer verification testing by sending the commands in Table 13-74 to
the relay.
Table 13-74. x62 Mode 3 Test Commands
Command Purpose
A= Gain write access
SL-N=NONE Zero out custom logic settings. Overwrite with
logic = none settings.
Y Confirm overwrite
SL-N=T62 Sets T62 as custom logic name
SL-343=3 Enables 343 switch pulse mode
SN-343=62_INI,INI,NORMAL Name switch to make SER easier to read
SL-62=3,343,0 Enables 62 1-shot, retriggerable mode, 343
initiate, no blocking
S0-62=15s,20s Sets 62 delay at 15 seconds, 62 dropout at 20
seconds
EXIT Exit
Y Save settings

Step 2. Send the commands in Table 13-75 to the relay. These commands supply the 62 timer with a
momentary initiate input by pulsing the 343 switch from a FALSE state to a TRUE state and
then back to a FALSE state. You may view the state changes of the 343 switch at front panel
interface \CTRL\43\343, screen 2.1.4.

NOTE
The 343 switch action is performed three times in this test. To illustrate the action of the
timer mode, the second 343 switch action should be executed as quickly as possible
(within the 15 second duration of the pickup time delay). Perform the third 343 switch
action after at least 15 seconds (the pickup timer setting) have elapsed, but before the 20
second dropout time delay expires. This will illustrate the action of the timer mode. The
time delay settings may be increased if difficulty is encountered with repeating the 343
switch actions.

13-64 Testing And Maintenance BE1-CDS


Table 13-75. x62 Mode 3 Timer Initiate Commands
Command Purpose
A= Gain write access
CS-343=P Selects 343 for pulse operation
CO-343=P Executes 343 for pulse operation
CS-343=P Selects 343 for pulse operation
CO-343=P Executes 343 for pulse operation
Wait at least 15 seconds (but no longer than 35 seconds) to execute the next commands
CS-343=P Selects 343 for pulse operation
CO-343=P Executes 343 for pulse operation

Step 3. Use the RS-LGC command to obtain an SER report and verify that the following actions were
logged. These events are illustrated in the timing diagram of Figure 13-19.
After a 343 pulse action (FALSE-TRUE-FALSE) was logged, the 62 timer output did not go
TRUE because of a second FALSE to TRUE initiate signal action.
Approximately 15 seconds after the second 343 FALSE to TRUE initiate signal, the 62 timer
output went TRUE. The timer output went FALSE when the third FALSE to TRUE initiate
signal forced the 62 timer (T1) to restart.
Fifteen seconds after the third 343 FALSE to TRUE initiate signal, the 62 timer output went
TRUE again and then went FALSE after the duration timer (T2) expired 20 seconds later.
INI
D2595-04.vsd
08-10-00
343 200 ms 200 ms 200 ms
~
~
~
~

Normal

~
~
1
T1 T2 T2
162 T1 T1

~
~
0

Figure 13-19. x62 Mode 3 (One-Shot Retriggerable) Timing Example

Mode 4 - Oscillator

Because this operating mode is not intended for general use, no testing procedure is provided. Information
about Mode 4 is available in Section 4, Protection and Control, General Purpose Logic Timers.

Mode 5 – Integrating Timer


Step 1. Prepare for mode 5 logic timer verification testing by sending the commands in Table 13-76 to
the relay.
Table 13-76. x62 Mode 5 Test Commands
Command Purpose
A= Gain write access
SL-N=NONE Zero out custom logic settings. Overwrite with logic = none
settings.
Y Confirm overwrite
SL-N=T62 Sets T62 as custom logic name
SL-43=2 Enables 43 switch ON/OFF mode
SN-43=62_INI,PU,DO Name switch to make SER easier to read
SL-62=5,43,0 Enables 62 integrating mode, 43 initiate, no blocking

BE1-CDS Testing And Maintenance 13-65


Command Purpose
S0-62=15s,5s Sets T1 at 15 seconds, T2 at 5 seconds
EXIT Exit
Y Save settings

Step 2. Send the commands in Table 13-77 to the relay. These commands supply a block input to the
62 timer by changing the 43 switch state to TRUE.

NOTE
The CS and CO commands of Table 13-77 are performed three times. Follow the timing
sequence to illustrate timer mode action. The time delay settings may be increased if
difficulty is encountered with repeating the 43 switch actions.

Table 13-77. x62 Mode 5 Timer Initiate Commands


Command Purpose
A= Gain write access
CS-43=1 Selects 43 for TRUE operation
CO-43=1 Executes 43 for TRUE operation
Wait no longer than 10 seconds to interrupt the T1 timer
CS-43=0 Selects 43 for FALSE operation
CO-43=0 Executes 43 for FALSE operation
Wait at least 5 seconds for the T2 timer to time out and reset the integration
CS-43=1 Selects 43 for TRUE operation
CO-43=1 Executes 43 for TRUE operation
Wait at least 20 seconds for the T1 timer to elapse
E Exit

Step 3. Use the RS-LGC command to obtain an SER report and verify that the following actions were
logged. These events are illustrated in the timing diagram of Figure 13-20.
Timer T1 failed to time out in the first 43 switch action (TRUE).
Timer T2 timed out after the second 43 switch action (FALSE).
Timer T1 timed out and the 62 timer output went TRUE.
Timer T2 timed out and the 62 timer output returned to a FALSE state
1

BLK D 2 5 9 5-0 5 .cd r


0 7 -1 9 -00
0

43
0

>5 s 15 s 5s

1 0 0%
Tim e r
0%

x6 2
0

Figure 13-20. x62 Mode 5 (Integrating) Timing Example

13-66 Testing And Maintenance BE1-CDS


Step 4. (Optional) Repeat the 62 timer tests for Modes 1, 2, 3, and 5 for setting groups 1, 2, and 3.

Mode 6 – Latch Timer


Step 1. Prepare for mode 6 logic timer verification testing by sending the commands in Table 13-78 to
the relay.
Table 13-78. x62 Mode 6 Test Commands
Command Purpose
A= Gain write access
SL-N=NONE Zero out custom logic settings. Overwrite with
logic = none settings.
Y Confirm overwrite
SL-N=T62 Sets T62 as custom logic name
SL-43=3 Enables 43 switch pulse mode
SL-143=3 Enables 143 switch pulse mode
SN-43=62_LATCH,INI,NORMAL Name switch to make SER easier to read
SN-143=62_RESET,RESET,NORMAL Name switch to make SER easier to read
SL-62=6,43,143 Enables 62 latch mode, 43 initiate, 143 block
(reset latch)
S0-62=30s Sets T1 at 30 seconds, T2 time not applicable
EXIT Exit
Y Save settings

Step 2. Sent the commands in Table 13-79 to the relay. These commands supply a latch input to the
62 timer by changing the 43 switch state to TRUE and a reset command by changing the BLK
input (143 switch) to TRUE.

NOTE
The CS and CO commands of Table 13-79 are performed two times. Follow the timing
sequence to illustrate timer mode action. The time delay settings may be increased if
difficulty is encountered with repeating the 43 and 143 switch actions.

Table 13-79. x62 Mode 6 Timer Initiate Commands


Command Purpose
A= Gain write access
CS-43=P Selects 43 for pulse operation
CO-43=P Executes 43 for pulse operation (initiates 62 timing)
Execute the following commands in less than 30 seconds
CS-43=P Selects 43 for pulse operation
CO-43=P Executes 43 for pulse operation (no effect)
Wait at least 30 seconds (total elapsed time) to initiate the latch reset (block) command (this
allows timer T1 to time out (output goes TRUE) and latch until the BLK input goes TRUE)
CS-143=P Selects 143 for pulse operation
CO-143=P Executes 143 for pulse operation (applies BLK input)
E Exit

Step 3. Use the RS-LGC command to obtain an SER report and verify that the following actions were
logged. These events are illustrated in the timing diagram of Figure 13-21.
Timer T1 continued to time out after the first 43 switch action (TRUE).

BE1-CDS Testing And Maintenance 13-67


Timer T1 timed out and the 62 timer output went TRUE 30 seconds after 43 switch action
(TRUE).
62 timer output returned to a FALSE state with the 143 switch action (TRUE).
1
200 ms
BLK
0

1 D2595-06.vsd
08-10-00
INI 200 ms

0 ~
~
1
T1
x62
0

Figure 13-21. x62 Mode 6 (Latch) Timing Example


Step 4. (Optional) Repeat the 62 timer tests for Modes 1, 2, 3, and 5 for setting groups 1, 2, and 3.

Automatic Setting Group Change

Automatic Change
Purpose: To verify the operation of the automatic setting group change function.
Reference Commands: SL-GROUP, SG-SGCON, SP-GROUP, CS/CO-GROUP, SL-51/151/251,
S<n>-51
Step 1. Connect a current source to terminals B1 and B2 (A-phase input 1).
Step 2. To initially prepare the automatic setting group change function for testing, transmit the
commands in Table 13-80 to the relay.
Table 13-80. Automatic Setting Group Change Function Test Commands
Command Purpose
A= Gain access
SL-N=NONE Zero out custom logic settings/overwrite with logic = none
settings
Y Confirm overwrite
SL-N=ASG Name custom logic for this test
SL-GROUP=1,43,143,243,343, 443 Sets logic mode to discrete selection with virtual switches to
control
SL-51P=1,0 Enables 51P CT input 1
SG-SGCON=1 Sets SGC alarm = 1 sec, and anti-pump = 2 sec
SL-VO1=SG1 Enables OUT1 to close when SG1 active
SL-VO2=SG2 Enables OUT2 to close when SG2 active
SL-VO3=SG3 Enables OUT3 to close when SG3 active
SG-CT1=1,WYE,NA,0 Input 1 ctr=1, ct=wye, xfmr=na, no grd source
SG-TRIGGER=51PT,51PPU,0 Enable 51PT to log and trigger fault recording
SL-43=2 Enables 43 switch ON /OFF mode
SL-143=2 Enables 143 switch ON /OFF mode
SL-243=2 Enables 243 switch ON /OFF mode
SL-343=2 Enables 343 switch ON /OFF mode
SL-443=2 Enables 443 switch ON /OFF mode
SN-43=GROUP_MAN_SELECT, Set Switch Names
GROUP0,NORMAL
13-68 Testing And Maintenance BE1-CDS
Command Purpose
SN-143=GROUP_MAN_SELECT, Set Switch Names
GROUP1,NORMAL
SN-243=GROUP_MAN_SELECT, Set Switch Names
GROUP2,NORMAL
SN-343=GROUP_MAN_SELECT, Set Switch Names
GROUP3,NORMAL
SN-443=GROUP_CONTROL, Set Switch Names
AUTO,MANUAL
SP-GROUP1=1,75,1,70,51P SG1 ts=1min@75%, tr=1min@70% of SG0 51P
SP-GROUP2=1,90,1,85,51P SG2 ts=1min@90%, tr=1min@85% of SG0 51P
SP-GROUP3=1,110,1,100,51P SG3 ts=1min@110%, tr=1min@100% of SG0 51P
E Exit
Y Save settings

Step 3. Switch group control to automatic using virtual switch 443. Use Table 13-81 ASCII commands
or front panel interface \CTRL\43\543, screen 2.1.6.
Table 13-81. Automatic Group Control Selection
Command Purpose
A= Gain access
CS-443=1 Selects 443 for TRUE operation
CO-443=1 Executes 443 TRUE operation (AUTO)

Step 4. Gain access if access timed out from the previous step. Send to the relay the appropriate
setting commands from Table 13-82. If your relay is supplied with the HMI option, you may
also go to the front panel interface screen \PROT\SG0\51\51 and edit the 51P settings. After
you send the commands to your relay, EXIT’ and (save) ‘Y’) the changes.
An ohmmeter or continuity tester may be used to monitor the output contacts (OUT1, OUT2,
OUT3) status.
Table 13-82. Time Overcurrent 51P Element Pickup Settings
Sensing Input Type Command Comments
1A S0-51P=1.0,5.0,I2 pu=1.0, td=5, curve=I2
S1-51P=1.5,5.0,I2 pu=1.5, td=5, curve=I2
S2-51P=1.8,5.0,I2 pu=1.8, td=5, curve=I2
S3-51P=2.2,5.0,I2 pu=2.2, td=5, curve=I2
5A S0-51P=5.0,5.0,I2 pu=5.0, td=5, curve=I2
S1-51P=7.5,5.0,I2 pu=7.5, td=5, curve=I2
S2-51P=9.0,5.0,I2 pu=9.0, td=5, curve=I2
S3-51P=11.0,5.0,I2 pu=10.5, td=5, curve=I2

Step 5. Using the values listed in Table 13-83, apply current to the A phase current input, beginning at
the starting point, then stepping up to just slightly above the threshold limit for the amount of
time listed. If the active setting group does not change, step the current up to just below the
next group switch limit for the duration indicated. The setting group change should occur
between the low and high limits. Monitor the output contacts to verify that the change occurred

BE1-CDS Testing And Maintenance 13-69


within the time limits programmed at an accuracy of ± 0.5% of setting or ± 2 seconds,
whichever is greater. Step the current up to each new level and verify the setting group
change and pickup accuracy.
Table 13-83. Automatic Setting Group Change Example Accuracy Limits - Increasing Current
Current Value
But Below Next
Sensing Above Switch Group Switch
Type Threshold Threshold and
Time Comments
51P PU
1A 0.51 A 0.73 A - Starting point 50% of S0-51P pickup
0.77 A 0.88 A > 1 min Switch to SG1 (75% S0 51P pickup)
0.92 A 1.07 A > 1 min Switch to SG2 (90% S0 51P pickup)
1.13 2.1 > 1 min Switch to SG3 (110% S0 51P pickup)
5A 2.55 A 3.6 A - Starting point 50% pickup
3.83 A 4.4 A > 1 min Switch to SG1 (75% S0 51P pickup)
4.59 A 4.595 A > 1 min Switch to SG2 (90% S0 51P pickup)
5.61 A 10.78 A > 1 min Switch to SG3 (110% S0 51P pickup)

Step 6. Verify that SG3 is the active setting group by sending the command RG-GRPACTIVE to the
relay. It should echo back that the SG3 is the active group. If your relay is supplied with the
HMI option, you may also verify the active setting group at the front panel interface screen
\STAT\OPER\ACTIVEG, 1.4.4.
Step 7. Send to the relay the commands in Table 13-84.
Table 13-84. Automatic Group Control Selection
Command Purpose
A= Gain access
CS-143=1 Selects 143 for TRUE operation
CO-143=1 Executes 143 TRUE operation (setting group 1)
E Exit
Step 8. Verify that the relay did not change to setting group 1 (SG1) by transmitting the RG-
GRPACTIVE to the relay. It should echo back that the SG3 is still the active group. This
verifies that the relay will not make any setting group changes from logic inputs while the
AUTO input logic is TRUE.
Step 9. Begin stepping down the level of current from one level to the next as shown in Table 13-85.
First step the current to just below the threshold limit for the amount of time listed. Monitor the
output contacts to verify that the setting group changed. If the active setting group does not
change, step the current down to just above the next group switch limit for the duration
indicated. This will verify the accuracy of the pickup return threshold. Continue stepping down
to each new level.
Table 13-85. Automatic Setting Group Change Example Accuracy Limits - Decreasing Current
Current Value
Sensing Below Switch But Above Next
Type Timing Group Switch Time Comments
Threshold Threshold
1A 2.1 A 1.13 A > 1 min SG3 (110% SG0 51P)
0.98 A 0.86 A > 1 min Switch to SG2 (100% SG0 51P)
0.83 A 0.71 A > 1 min Switch to SG1 (85% S0 51P pickup)
1.13 2.1 > 1 min Switch to SG0 (70% S0 51P pickup)
13-70 Testing And Maintenance BE1-CDS
Current Value
Sensing Below Switch But Above Next
Type Timing Group Switch Time Comments
Threshold Threshold
5A 10.78 A 5.61 A > 1 min SG3 (110% SG0 51P)
4.9 A 4.4 A > 1 min Switch to SG2 (100% SG0 51P)
4.16 A 3.57 A > 1 min Switch to SG1 (85% S0 51P pickup)
3.43 A 2.55 A > 1 min Switch to SG0 (70% S0 51P pickup)

Step 10. Remove the current from A-phase, input 1.


Step 11. Using the RS-LGC command to retrieve logic variable data from the SER, verify that the
following actions were logged.
Verify that all setting group changes were logged.
Verify that VO1 went TRUE and closed relay output OUT1 when SG1 became the active
setting group.
Verify that VO2 went TRUE and closed relay output OUT2 when SG2 became the active
setting group and that relay output OUT1 opened.
Verify that VO3 went TRUE and closed relay output OUT3 when SG3 became the active
setting group and that relay output OUT2 opened.
Verify that when the virtual switch 143 went TRUE (as a discrete input to the SG1 input of the
setting group logic block) that the active setting group remained SG3.
Verify the events that occurred in reverse order, when the current was being stepped down.

Manual Change Mode 1


Manual Change Mode 1 test procedures are a continuation of the automatic test procedures. Do not
change the logic or settings except for those in Step 1 and subsequent.
Step 1. Transmit to the relay the commands in Table 13-86.
Table 13-86. Manual Group Control Selection
Command Purpose
A= Gain access
CS-443=0 Selects 443 for FALSE operation to enable logic
control (manual mode)
CO-443=0 Executes 443 for FALSE operation to enable logic
control (manual mode)
E Exit
Step 2. Verify that VO1 went TRUE and closed relay output OUT1 when SG1 became the active
setting group (remember in Step 6, switch 143 was made TRUE).
Step 3. Send to the relay the commands in Table 13-87. Monitor the output contacts to verify the
setting group changes. After all commands have been sent, verify that SG3 is the active
setting group by sending the command RG-GRPACTIVE to the relay. It should echo back that
the SG3 is the active group. If your relay is supplied with the HMI option, you may also verify
the active setting group at the front panel interface screen \STAT\OPER\ACTIVEG, 1.4.4.

BE1-CDS Testing And Maintenance 13-71


Table 13-87. Manual Group Control Selection
Command Purpose
A= Gain access
CS-143=0 Deselects setting group 1 for operation
CO-143=0 Executes Deselecting setting group 1 for operation
CS-43=1 Selects setting group 0 for operation
CO-43=1 Executes setting group 0 for operation
CS-43=0 Deselects setting group 0 for operation
CO-43=0 Executes Deselecting setting group 0 for operation
CS-243=1 Selects setting group 2 for operation
CO-243=1 Executes setting group 2 for operation
CS-243=0 Deselects setting group 2 for operation
CO-243=0 Executes Deselecting setting group 2 for operation
CS-343=1 Selects setting group 3 for operation
CO-343=1 Executes setting group 3 for operation
E Exit
Y Save settings

Step 4. Using the RS-LGC command to retrieve logic variable data from the SER, verify that the
setting group change actions were logged.

Manual Change Mode 2


Manual Change Mode 2 test procedures are a continuation of the Mode 1 test procedures. Do not change
the logic or settings except for those in Step 1 and subsequent.
Step 1. Send to the relay the commands in Table 13-88.
Table 13-88. Binary Group Control Selection Setup
Command Purpose
A= Gain access
SL-GROUP=2 Sets setting group control function to binary coded
selection (AUTO logic is unchanged from Table 13-80)
E Exit
Y Save settings
Step 2. Verify that relay outputs OUT3 opened when the commands in Table 13-88 were completed
and OUT1 and OUT2 remained open. With the existing logic and discrete select enabled, D0
and D1 inputs are FALSE, and D2 and D3 inputs have no effect on setting group selection.
For more information on setting group selection, see Section 4, Protection And Control
Functions, Setting Groups.
Step 3. Verify that SG0 is the active setting group by sending the command RG-GRPACTIVE to the
relay. It should echo back that the SG0 is the active group. If your relay is supplied with the
HMI option, you may also verify the active setting group at the front panel interface screen
\STAT\OPER\ACTIVEG, 1.4.4.
Step 4. Send to the relay the commands in Table 13-89.

13-72 Testing And Maintenance BE1-CDS


Table 13-89. Binary Group Control Selection Test Commands
Command Purpose
A= Gain access
CS-43=1 Selects setting group 1 for operation
CO-43=1 Executes setting group 1 for operation (D0=1)
CS-43=0 Deselects setting group 1 for operation
CO-43=0 Executes Deselecting setting group 1 for operation
CS-143=1 Selects setting group 2 for operation
CO-143=1 Executes setting group 2 for operation (D1=1)
CS-43=1 Selects setting group 3 for operation
CO-43=1 Executes setting group 3 for operation (D0=1 and
D1=1)
E Exit

Step 4. Verify that the appropriate setting groups became active and relay outputs OUT1 through
OUT3 closed in accordance with the discrete inputs of Table 13-89. Refer to Step 3 for more
information on verifying active setting groups.

MAINTENANCE
BE1-CDS220 Current Differential Systems require no preventive maintenance. The fully numeric design
of the BE1-CDS contains no internal jumpers or mechanical settings except for contact sensing ranges. It
also requires no calibration. Testing, however, should be performed according to scheduled practices.
The BE1-CDS can be fully drawn out of the case. When the drawout assembly is removed, the current
transformer input circuits are automatically shorted by internal case contacts. The case contains no
components that are likely to require service; all critical components are contained in the drawout
assembly. When removing the drawout assembly from the case, care should be taken to prevent
electrostatic discharge (ESD) and mechanical damage.
There is no need to disturb the circuit interconnections within the drawout assembly. Repair of the
drawout assembly by replacement of individual circuit boards is not recommended. The printed circuit
boards are constructed using surface-mount technology and are not intended to be field serviceable.
If a relay failure occurs in a critical application without sufficient redundancy, protection can be restored by
inserting a spare relay in the mounted and wired case of the relay requiring service. The drawout
assembly requiring service can then be returned to the factory in the case from the spare relay. If a spare
case isn’t available, care should be used when packing the drawout assembly for shipment. Use antistatic
packing material that prevents mechanical damage during transit.
Before returning the drawout assembly for repair, contact the Basler Electric Technical Services
Department at 618-654-2341 for a return authorization number.

BE1-CDS Testing And Maintenance 13-73


APPENDIX A • TIME OVERCURRENT
CHARACTERISTIC CURVES
TABLE OF CONTENTS

List Of Figures......................................................................................................................................... i
List Of Tables.......................................................................................................................................... i
APPENDIX A • TIME OVERCURRENT CHARACTERISTIC CURVES ....................................................A-1
GENERAL ..............................................................................................................................................A-1
CURVE SPECIFICATIONS ....................................................................................................................A-1
TIME OVERCURRENT CHARACTERISTIC CURVE GRAPHS............................................................A-2
Time Dial Setting Cross Reference.....................................................................................................A-3

List Of Figures
Figure A-1. Time Characteristic Curve S, S1 Short Inverse, 99-1369, (Similar to ABB CO-2) .................A-5
Figure A-2. Time Characteristic Curve S2, Short Inverse, 99-1595 (Similar To GE IAC-55)....................A-6
Figure A-3. Time Characteristic Curve L, L1, Long Inverse, 99-1370, (Similar to ABB CO-5) ..................A-7
Figure A-4. Time Characteristic Curve L2, Long Inverse, 99-1594, (Similar To GE IAC-66)....................A-8
Figure A-5. Time Characteristic Curve D, Definite Time, 99-1371, (Similar To ABB CO-6) .....................A-9
Figure A-6. Time Characteristic Curve M, Moderately Inverse, 99-1372, (Similar to ABB CO-7)...........A-10
Figure A-7. Time Characteristic Curve I, I1 Inverse Time, 99-1373 (Similar to ABB CO-8) ...................A-11
Figure A-8. Time Characteristic Curve I2, Inverse Time, 99-1597 (Similar to GE IAC-51).....................A-12
Figure A-9. Time Characteristic Curve V, V1, Very Inverse, 99-1374 (Similar to ABB CO-9) ................A-13
Figure A-10. Time Characteristic Curve V2, Very Inverse, 99-1596 (Similar to GE IAC-53) ..................A-14
Figure A-11. Time Characteristic Curve E, E1, Extremely Inverse, 99-1375 (Similar to GE IAC-11) .....A-15
Figure A-12. Time Characteristic Curve E2, Extremely Inverse, 99-1598 (Similar to GE IAC-77) .........A-16
Figure A-13. Time Characteristic Curve A, Standard Inverse, 99-1621..................................................A-17
Figure A-14. Time Characteristic Curve B, Very Inverse, 99-1376.........................................................A-18
Figure A-15. Time Characteristic Curve C, Extremely Inverse, 99-1377 ................................................A-19
Figure A-16. Time Characteristic Curve G, Long Time Inverse, 99-1622...............................................A-20

List Of Tables
Table A-1. 51P, 51N, And 51Q Time Characteristic Curve Constants ....................................................A-2
Table A-2. Characteristic Curve Cross Reference....................................................................................A-3
Table A-3. Time Dial Setting Cross Reference ..........................................................................................A-4

BE1-CDS Time Current Characteristic Curves i


APPENDIX A • TIME OVERCURRENT
CHARACTERISTIC CURVES

GENERAL
Basler Electric inverse time overcurrent relays (ANSI Device 51) provide time/current characteristic curves
that very closely emulate most of the common electro-mechanical, induction disk relays that were
manufactured in North America. To further improve proper relay coordination, selection of integrated reset
or instantaneous reset characteristics is also provided.

CURVE SPECIFICATIONS
Timing Accuracy (All 51 Functions) Within ±5% or ±1❽ cycles, whichever is greater,
for time dial settings greater than 0.1 and
multiples of 2 to 40 times the pickup setting but
not over 150 A for 5 A CT units or 30 A for 1 A CT
units.
Sixteen inverse time functions and one fixed time
function and one programmable time function can
be selected. Characteristic curves for the inverse
and definite time functions are defined by the
following equations and comply with IEEE
C37.112 - 1996.
A ⋅D
TT = N + B ⋅D + K Equation A-1
M −C

R⋅D
TR = Equation A-2
M2 − 1
TT = Time to trip when M ≥ 1
TR = Time to reset if relay is set for integrating
reset when M < 1. Otherwise, reset is 50
milliseconds or less
D = TIME DIAL setting (0.0 to 9.9)
M = Multiple of PICKUP setting (0 to 40)
A, B, C, N, K = Constants for the particular curve
R = Constant defining the reset time.

See Table A-1 for the time characteristic curve


constants. See Figures A-1 through A-16 for
graphs of the characteristics.

BE1-CDS Time Current Characteristic Curves A-1


Table A-1. 51P, 51N, And 51Q Time Characteristic Curve Constants
BE1-CDS Reset
Curve BE Curve Name Trip Characteristic Constants * (Note 2)
Selection A B C N K R
S1 S, Short Inverse 0.2663 0.03393 1.000 1.2969 0.028 0.5000
S2 S2, Short Inverse 0.0286 0.02080 1.000 0.9844 0.028 0.0940
L1 L1, Long Inverse 5.6143 2.18592 1.000 1.000 0.028 15.750
L2 L2, Long Inverse 2.3955 0.00000 1.000 0.3125 0.028 7.8001
D D, Definite Time 0.4797 0.21359 1.000 1.5625 0.028 0.8750
M M, Moderately Inverse 0.3022 0.12840 1.000 0.5000 0.028 1.7500
I1 I, Inverse Time 8.9341 0.17966 1.000 2.0938 0.028 9.0000
I2 Inverse Time 0.2747 0.10426 1.000 0.4375 0.028 0.8868
V1 V, Very Inverse 5.4678 0.10814 1.000 2.0469 0.028 5.5000
V2 V2, Very Inverse 4.4309 0.09910 1.000 1.9531 0.028 5.8231
E1 Extremely Inverse 7.7624 0.02758 1.000 2.0938 0.028 7.7500
E2 E2, Extremely Inverse 4.9883 0.01290 1.000 2.0469 0.028 4.7742
A Standard Inverse 0.01414 0.00000 1.000 0.0200 0.028 2.0000
B B, Very Inverse (It) 1.4636 0.00000 1.000 1.0469 0.028 3.2500
2
C Extremely Inverse (I t) 8.2506 0.00000 1.000 2.0469 0.028 8.0000
G Long Time Inverse 12.1212 0.00000 1.000 1.0000 0.028 29.0000
F Fixed Time*(Note 1) 0.0000 1.00000 0.000 0.0000 0.028 1.0000
P Programmable 0 to 600 0 to 25 0 to 1 0.5 to 2.5 0.028 0 to 30
* NOTE 1: The Fixed Time characteristic curve has a fixed delay of one second times the Time Dial
setting.
NOTE 2: To get integrated reset, you append R to the curve name. For example, curve S1 has
instantaneous reset. Curve S1R has integrated reset.

TIME OVERCURRENT CHARACTERISTIC CURVE GRAPHS


Figures A-1 through A-17 illustrate the characteristic curves that are programmed into the nonvolatile
memory of this relay. A drawing number is given under each caption and listed in Table A-2. Table A-2
also cross references the BE1-CDS curves to existing electromechanical relay characteristics. The
equivalent time dial settings were calculated at a value of five times pickup. Contact Basler Electric
Technical Support Services Department, and request the drawing number to order a full-size (10 inch x 12
inch) Characteristic Curve graph on transparent paper (vellum). A complete set of all drawings is
available by requesting Publication 9 2520 00 990.

A-2 Time Current Characteristic Curves BE1-CDS


Table A-2. Characteristic Curve Cross Reference
BE1-CDS
Curve Curve Name Drawing No. Similar To
S1 S, Short Inverse 99-1369 ABB CO-2
S2 S2, Short Inverse 99-1595 GE IAC-55
L1 L, L1, Long Inverse 99-1370 ABB CO-5
L2 L2, Long Inverse 99-1594 GE IAC-66
D D, Definite Time 99-1371 ABB CO-6
M M, Moderately Inverse 99-1372 ABB CO-7
I1 I, I1 Inverse Time 99-1373 ABB CO-8
I2 I2 Inverse Time 99-1597 GE IAC-51
V1 V, V1 Very Inverse 99-1374 ABB CO-9
V2 V2, Very Inverse 99-1596 GE IAC-53
E1 E, E1 Extremely Inverse 99-1375 ABB CO-11
E2 E2, Extremely Inverse 99-1598 GE IAC-77
A A Standard Inverse 99-1621 BS, IEC Standard Inverse
B B, Very Inverse (It) 99-1376 BS, IEC Very Inverse (It)
2 2
C Extremely Inverse (I t) 99-1377 BS, IEC Extremely Inverse (I t)
G Long Time Inverse 99-1622 BS, IEC Long Time Inverse
F Fixed Time
P Programmable

Time Dial Setting Cross Reference


Even though the time characteristic curve shapes have been optimized for each relay, the time dial
settings between electro-mechanical induction disk overcurrent relays and Basler Electric relays are not
equivalent. Table A-3 has been designed to serve as a tool for converting time dial settings for induction
disk relays to the correct equivalent time dial setting for your Basler Electric solid state and numerical
overcurrent relays. Time dial settings can be entered from the optional HMI screen 5.X.4.X,
\PROT\SGX\51\X51 and from the ASCII command interface using the S<g>-5/151/251 command. For more
information, refer to Section 4, Protection And Control, 51 Overcurrent Functions.

Notes On The Use Of Table A-3


The values in the time dial setting cross reference table were obtained by inspection of the published
electro-mechanical time current characteristic curve. The time delay for each time dial setting at a current
of five times tap was entered into the time dial calculator function. The equivalent Basler Electric time dial
setting was then entered into the cross reference table.
If your electro-mechanical relay time dial setting is between the values provided in the table, it will be
necessary to interpolate (estimate the correct intermediate value) between the electro-mechanical setting
and the Basler Electric setting.
The maximum time dial setting provided by Basler electric relays is 9.9. The Basler Electric equivalent
time dial setting for the maximum time dial setting provided in the electro-mechanical relay is provided in
the cross reference table even if it is calculated to be above 9.9. This is provided for the purpose of
allowing interpolation as noted above.
Basler Electric time/current characteristics are determined by a linear mathematical equation. An
induction disk has a certain degree of non-linearity due to inertial and friction effects. For this reason,
even though every effort has been made to provide equation constants that provide characteristic curves
with minimum deviation from the published electro-mechanical curves, slight deviations can be observed
between them.

BE1-CDS Time Current Characteristic Curves A-3


In applications where the time coordination between curves is extremely close, we recommend that you
choose the optimal time dial setting by inspection of the coordination study. Also, in these applications
where coordination is tight, it is recommended that you retrofit your circuits with Basler Electric solid state
relays due to their high timing accuracy.
Table A-3. Time Dial Setting Cross Reference
Electromechanical Relay Time Dial Setting
BE1-CDS Equivalent Drawing 0.5 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0 11.0
Curve To Number Basler Electric Equivalent Time Dial Setting
S, S1 ABB CO-2 99-1369 0.3 0.8 1.7 2.4 3.4 4.2 5.0 5.8 6.7 7.7 8.6 9.7
L, L1 ABB CO-5 99-1370 0.4 0.8 1.5 2.3 3.3 4.2 5.0 6.0 7.0 7.8 8.8 9.9
D ABB CO-6 99-1371 0.5 1.1 2.0 2.9 3.7 4.5 5.0 5.9 7.2 8.0 8.9 10.1
M ABB CO-7 99-1369 0.4 0.8 1.7 2.5 3.3 4.3 5.3 6.1 7.0 8.0 9.0 9.8
I, I1 ABB CO-8 99-1373 0.3 0.7 1.5 2.3 3.2 4.0 5.0 5.8 6.8 7.6 8.7 10.0
V, V1 ABB CO-9 99-1374 0.3 0.7 1.4 2.1 3.0 3.9 4.8 5.7 6.7 7.8 8.7 9.6
E, E1 ABB CO-11 99-1375 0.3 0.7 1.5 2.4 3.2 4.2 5.0 5.7 6.6 7.8 8.5 10.3
I2 GE IAC-51 99-1597 0.6 1.0 1.9 2.7 3.7 4.8 5.7 6.8 8.0 9.3 10.6
V2 GE IAC-53 99-1596 0.4 0.8 1.6 2.4 3.4 4.3 5.1 6.3 7.2 8.4 9.6
S2 GE IAC-55 99-1595 0.2 1.0 2.0 3.1 4.0 4.9 6.1 7.2 8.1 8.9 9.8
L2 GE IAC-66 99-1594 0.4 0.9 1.8 2.7 3.9 4.9 6.3 7.2 8.5 9.7 10.9
E2 GE IAC-77 99-1598 0.5 1.0 1.9 2.7 3.5 4.3 5.2 6.2 7.4 8.2 9.9

A-4 Time Current Characteristic Curves BE1-CDS


Figure A-1. Time Characteristic Curve S, S1 Short Inverse, 99-1369, (Similar to ABB CO-2)

BE1-CDS Time Current Characteristic Curves A-5


Figure A-2. Time Characteristic Curve S2, Short Inverse, 99-1595 (Similar To GE IAC-55)

A-6 Time Current Characteristic Curves BE1-CDS


Figure A-3. Time Characteristic Curve L, L1, Long Inverse, 99-1370, (Similar to ABB CO-5)

BE1-CDS Time Current Characteristic Curves A-7


Figure A-4. Time Characteristic Curve L2, Long Inverse, 99-1594, (Similar To GE IAC-66)
A-8 Time Current Characteristic Curves BE1-CDS
Figure A-5. Time Characteristic Curve D, Definite Time, 99-1371, (Similar To ABB CO-6)
BE1-CDS Time Current Characteristic Curves A-9
Figure A-6. Time Characteristic Curve M, Moderately Inverse, 99-1372, (Similar to ABB CO-7)
A-10 Time Current Characteristic Curves BE1-CDS
Figure A-7. Time Characteristic Curve I, I1 Inverse Time, 99-1373 (Similar to ABB CO-8)
BE1-CDS Time Current Characteristic Curves A-11
Figure A-8. Time Characteristic Curve I2, Inverse Time, 99-1597 (Similar to GE IAC-51)
A-12 Time Current Characteristic Curves BE1-CDS
Figure A-9. Time Characteristic Curve V, V1, Very Inverse, 99-1374 (Similar to ABB CO-9)
BE1-CDS Time Current Characteristic Curves A-13
Figure A-10. Time Characteristic Curve V2, Very Inverse, 99-1596 (Similar to GE IAC-53)
A-14 Time Current Characteristic Curves BE1-CDS
Figure A-11. Time Characteristic Curve E, E1, Extremely Inverse, 99-1375 (Similar to GE IAC-11)
BE1-CDS Time Current Characteristic Curves A-15
Figure A-12. Time Characteristic Curve E2, Extremely Inverse, 99-1598 (Similar to GE IAC-77)

A-16 Time Current Characteristic Curves BE1-CDS


Figure A-13. Time Characteristic Curve A, Standard Inverse, 99-1621
BE1-CDS Time Current Characteristic Curves A-17
Figure A-14. Time Characteristic Curve B, Very Inverse, 99-1376
A-18 Time Current Characteristic Curves BE1-CDS
Figure A-15. Time Characteristic Curve C, Extremely Inverse, 99-1377
BE1-CDS Time Current Characteristic Curves A-19
Figure A-16. Time Characteristic Curve G, Long Time Inverse, 99-1622
A-20 Time Current Characteristic Curves BE1-CDS
APPENDIX B • COMMAND CROSS-REFERENCE

INTRODUCTION
This appendix lists all ASCII commands, command syntax, brief command descriptions, and any
corresponding HMI screens. Commands are organized by function in the following groups and tables.
 Miscellaneous (Table B-1)
 Metering (Table B-2)
 Control (Table B-3)
 Report (Table B-4)
 Setting (Table B-5)
 Alarm Setting (Table B-6)
 General Setting (Table B-7)
 Breaker Monitoring and Setting (Table B-8)
 Programmable Logic Setting (Table B-9)
 User Programmable Name Setting (Table B-10)
 Protection Setting (Table B-11)
 Global (Table B-12)

BE1-CDS Command Cross-Reference B-1


An entry of x in the following tables represents multiple entry possibilities such as 0, 1, 2, or 3 for setting
groups or 43, 143, 243, etc. for virtual switches.
Table B-1. Miscellaneous Commands
ASCII Command Function HMI Screen
ACCESS[=<password>] Read/Set access level in order to change settings. N/A
EXIT Exit programming mode. N/A
HELP <cmd> or H <cmd> Obtain help with command operation. N/A

Table B-2. Metering Commands


ASCII Command Function HMI Screen
M Read all metered values. N/A
M-FREQ Read metered frequency. 3.1
M-I Read metered current in primary units (all phases). 3.1*
M-I[<phase>] Read metered current in primary units. 3.1*
M1 Read CT circuit #1 current primary or secondary 3.1.1*
units (all phases).
M1[<phase>] Read CT circuit #1 current primary or secondary 3.1.1.1
units.
M2 Read CT circuit #2 current primary or secondary 3.1.2*
units (all phases).
M2[<phase>] Read CT circuit #2 current primary or secondary 3.1.2.1
units.
MD Read differential currents (all phases, compensated 3.2*
currents, operating current and harmonics).
MD[<x>] Read differential current. 3.2.x.x
NOTE * Multiple screens required.

Table B-3. Control Commands


ASCII Command Function HMI Screen
CO-<control>[=<mode>] Control operation. N/A
CS-<control>[=<mode>] Control selection. N/A
CS/CO-43 Control Virtual Switches 2.1.x
CS/CO-101 Control Breaker control switch 2.2.1
CS/CO-GROUP Control Group 2.3.1
CS/CO-OUTn Control Output n 2.4.1

Table B-4. Report Commands


ASCII Command Function HMI Screen
RA Report/Reset alarm information (logic, major, minor, 1.2
relay).
RA[<x>] Report/Reset alarm information. 2.1
RA-DIFF[=TRIG] Read/Trigger Differential Report Data. N/A
RA-LGC[=0] Report/Reset logic alarm information. N/A
RA-MAJ[=0] Report/Reset major alarm information. 1.2
RA-MIN[=0] Report/Reset minor alarm information. 1.2

B-2 Command Cross-Reference BE1-CDS


ASCII Command Function HMI Screen
RA-REL[=0] Report/Reset relay alarm information. 1.2
RA-SER[=0] Report relay alarm sequence of events information. N/A
RB Read breaker status. 1.4.5, 4.3
RB-DUTY[<phase>[=%duty>]] Read/Set breaker contact duty log. 4.3.1
RB-OPCNTR[=<#operations>] Read/Set breaker operation counter. 4.3.1
RD Report all demand data. 4.4
RD-LOG<n> Report load profile data. N/A
RD-PI[<p>[=0]] Read/Reset peak demand current. 4.4.3.1*
RD-TI[<p>] Report today’s demand current. 4.4.1.1*
RD-YI[<p>] Report yesterday’s demand current. 4.4.2.1*
RF[-n/NEW][=0/TRIG] Read/Reset fault report data. N/A
RG Report general information. N/A
RG-101STAT Report general information, 101 status. 2.2
RG-43STAT Report general information, 43 status. 2.1.x,1.4.3
RG-ADDR[x] Report/Set COM1/COM2 Address for Polled 6.1.x
Communications.
RG-BREAKER Report general information, breaker status. 1.4.5
RG-DATE[=<M/D/Y>] Read/Set date. 1.4.6
RG-GRPACTIVE Report active group. 1.4.4
RG-GRPCNTRL Report group logic override control status. 2.3.x
RG-INPUT Report input status. 1.4.1
RG-LOGIC Report active logic. 5.0
RG-OUTCNTROL Report output control status. 2.4, 1.4.2
RG-OUTSTAT Report output status. 1.4.2
RG-STAT Report relay status. N/A
RG-TARG Report/Reset target status. 1.1
RG-TIME[=hr:mn:sc] Report/Set time. 1.4.6
RG-VER Read program version, model number, style 4.6
number, and serial number.
RL Read logic variables. N/A
RO-nA/B[#].CFG/DAT/HDR Read oscillographic COMTRADE .DAT/.CFG/.HDR N/A
fault report.
RS Read sequence of events directory N/A
RS[-n/Fn/ALM/IO/LGC/NEW] [=0] Read/Reset sequence of events record data N/A
RT Read Transformer Duty Status 4.5.1
RT-DUTY Read/Set transformer through-fault duty log 4.5.1
RT-TFCNTR[=0] Read/Set transformer through fault counter 4.5.1

Table B-5. Setting Command


ASCII Command Function HMI Screen
S Read all relay setting parameters. N/A

BE1-CDS Command Cross-Reference B-3


Table B-6. Alarm Setting Commands
ASCII Command Function HMI Screen
SA Read all major and minor alarm settings. N/A
SA-BKR[n][=<mode>, <alarm limit>] Read/Set breaker alarm settings. 6.5.2
SA-DI[p][=<alarm level>] Read/Set demand alarm settings. 6.4.2
SA-DIFF[=<alarm level>] Read/Set differential alarm setting N/A
SA-LGC[=<alarm num 1> [/<alarm num 2>] . Read/Set logic alarm setting mask. N/A
. . [<alarm num n>]]
SA-MAJ[=<alarm num 1> [/<alarm num 2>] . Read/Set major alarm setting mask. N/A
. . [<alarm num n>]]
SA-MIN[=<alarm num 1> [/<alarm num 2>] . . Read/Set minor alarm setting mask N/A
. [<alarm num n>]]
SA-RESET[=<rst alm logic>] Read/Set programmable alarms reset logic. N/A
SA-TX[n][=<mode>,<alarm limit>] Read/Set transformer alarm settings 6.6.2

Table B-7. General Setting Commands


ASCII Command Function HMI Screen
SG Read all general settings. N/A
SG-CLK[=<date format(M/D)>, Read/Program time and date format . N/A
<timeformat(12/24)>]
SG-COM[#[=<baud>, A<addr>,P<pglen>, Read/Set serial communication protocol. 6.1.x
R<reply ack>,X<XON ena>]]
SG-CT[t][=<CTratio>] Read/Set Phase/Neutral CT ratio. 6.3.1.x
SG-DI[p][=<interval>, <method>,<ct ckt#>] Read/Set demand interval, method, and CT circuit. 6.4.1
SG-FREQ[=<freq(Hz)>] Read/Enter power system frequency. 6.3.2
SG-HOLD[n][=<1/0 hold ena>] Read/Program output hold operation. N/A
SG-ID[=<relayID>, <StationID>] Read relay IDs used in reports. N/A
SG-ID[n][={ID label}] Read/Set relay ID used in reports. N/A
SG-IN[#[=<r(ms)>,<db(ms)>]] Read/Set input recognition/denounce. N/A
SG-LOG[={interval}] Read/Set load profile interval. N/A
SG-PHROT[=<phase rotation>] Read/Set phase rotation setting. 6.3.3
SG-SCREEN[n][=<default screen number>] Read/Set default screen(s). N/A
SG-SGCON[=<time>] Read/Set SGC output on time. 6.7
SG-TARG[=<x/x/...x>,<rst TARG logic>] Report/Enable Target List and Reset Target Logic. N/A
SG-TRIGGER[n][=<TRIPtrigger>, Read/Set trigger logic. N/A
<PUtrigger>, <LOGIC trigger>]

Table B-8. Breaker Monitoring and Setting Commands


ASCII Command Function HMI Screen
SB Read all breaker settings. N/A
SB-DUTY[=<mode>,<DMAX>] Read/Set breaker contact duty. 6.5.1
SB-LOGIC[=<breaker close logic>] Read/Set breaker contact logic. N/A

B-4 Command Cross-Reference BE1-CDS


Table B-9. Programmable Logic Setting Commands
ASCII Command Function HMI Screen
SL[:<name>] Obtain setting logic information. N/A
SL-101[=<mode >] Read/Set logic for virtual breaker switch (101). N/A
SL-x43[=<mode >] Read/Set logic for virtual switch (x43). N/A
SL-x50T[<p>[=<mode>,<BLK logic>]] Read/Set logic for x50 function modules. N/A
SL-x51[<p>[=<mode>,<BLK logic>]] Read/Set logic for 51 function modules. N/A
SL-51Q[=<mode>,<BLK logic>] Read/Set logic for 51Q function modules. N/A
SL-x62[=<mode>,<INI logic>,<BLK logic>] Read/Set logic for 62 function modules. N/A
SL-87[=<mode>,<BLK logic>] Read/Set logic for the 87 function. N/A
SL-87ND[=<mode>,<BLK logic>] Read/Set logic for the 87ND function. N/A
SL-BF[<p>][=<mode>,<INI logic>,<BLK Read/Set logic for breaker failure function modules. N/A
logic>]]
SL-CKTMON[=<mode>,<monitor>,<status>]] Read/Set circuit monitor logic setting N/A
SL-GROUP[=<mode>,<input logic>] Read/Set logic for setting group module. N/A
SL-N[=<name>] Read/Set or copy the name of the custom logic. N/A
SL-VO[#[=<Boolean equation>]] Read/Set output logic. N/A

Table B-10. User Programmable Name Setting Command


ASCII Command Function HMI Screen
SN[-<var>[=<name>,<TRUE label>,<FALSE Read/Set user programmable names. N/A
label>]

Table B-11. Protection Setting Commands


ASCII Command Function HMI Screen
S<#> Read all protection settings. N/A
S<#>-x50TP[=<pu(A)>,<td(m)>] Read/Set x50TP pickup level and time delay. 5.#3.x
S<#>-x50TN[=<pu(A)>,<td(m)>] Read/Set x50TN pickup level and time delay. 5.#.3.x
S<#>-x50TQ[=<pu(A)>,<td(m)>] Read/Set x50TQ pickup level and time delay. 5.#.3.x
S<#>-x51P[=<pu(A)>,<td(m)>,<crv>] Read/Set x51 pickup level, time delay, and curve. 5.#.4.x
S<#>-x51N[=<pu(A)>,<td(m)>,<crv>] Read/Set x51N pickup level, time delay, and curve. 5.#.4.x
S<#>-x51Q[=<pu(A)>,<td(m)>,<crv>] Read/Set x51Q pickup level, time delay, and curve. 5.#.4.x
S<#>-62[=<t1>,<t2>] Read/Set 62 time delay. 5.#.5.1
nd th
S<#>-87[=<minpu>,<slope>,<2 >,<5 >,<UR Read/Set the 87 parameters. 5.#.5.1
O>,<2nd harmonic sharing (0=off,1=on)>]
S<#>-87ND[=<minpu>,<slope>,<td)>] Read/Set the 87ND parameters. 5.#.2.1
S<#>-TAP87[=<mva>,<kv1/tap1>,<kv2/tap2] Read/Set the 87 tap parameters 5.#.1.2
>]
SP-BF[=<time>[m/s/c]] Read/Set the breaker failure timer setting 5.5.1
SP-CURVE[=<A>,<B>,<C>,<N>,<R>] Read/Set the user programmable 51 curve N/A
parameters.
SP-GROUP<g>=[<sw_time>,<sw_level%>,< Read/Program auxiliary setting group auto 6.7x
ret_time>,<ret_level%>,<prot_ele>] operation.
ST[=<mode>,<dmax>,<ct Read/Set transformer duty. 6.6.1
ckt#>,<BLKTXFMR logic>

BE1-CDS Command Cross-Reference B-5


Table B-12. Global Command
ASCII Command Function HMI Screen
GS-PW<t>[=<password>,<com Read or change a password. N/A
ports(0/1/2)>]]

B-6 Command Cross-Reference BE1-CDS


APPENDIX C • BE1-CDS SETTINGS RECORD

INTRODUCTION
This appendix provides a complete listing of all BE1-CDS settings. This listing is in the form of a settings
record that you may use to record information relative to your protection system. These settings sheets
may be removed and photo copied. This listing is grouped in the following order with a reminder at the
end to exit with the save settings procedure.
• Global Security Settings
• BESTlogic Settings For User Programmable Logic Scheme
• User Programmable Label Settings
• Global Input And Output Settings
• Protection Setting Groups
• Active Protection And Control Logic
• General Protection Settings
• Reporting And Alarm Function Settings
• Demand Reporting Settings
• Fault Reporting Settings
• Display And Communication Settings
• Transformer Monitoring Settings
• Breaker Monitoring Settings
• Alarm Settings
• Exit With Save Settings

BE1-CDS Settings Record C-1


BE1-CDS SETTINGS RECORD

Substation ID ___________________ Relay ID _________________ Date _____________ Page of _____

BE1-CDS Style Number __________________ Serial Number___________________ Version Number _______

//GLOBAL SECURITY SETTINGS


//Global PW and Access Ports = Password, 8 Char , Ports, 0/1/2
GS-PWG =

//Control PW and Access Ports = Password, 8 Char , Ports, 0/1/2


GS-PWC =

//Reports PW and Access Ports = Password, 8 Char , Ports, 0/1/2


GS-PWR =

//Settings PW and Access Ports = Password, 8 Char , Ports, 0/1/2


GS-PWS =

//BESTLOGIC SETTINGS FOR USER PROGRAMMABLE LOGIC SCHEME


//Name for User Prog Logic = Name
SL-N =

//Protection Function Blk Logic Settings


//Phase Differential = Mode, 0,1 , Blk Input Expr
SL-87 = ,

//Ground Differential = Mode, 0,1,2 , Blk Input Expr


SL-87ND = ,

//Inst OC w/ Time Delay = Mode, 0,1,2,G * , Blk Input Expr


//* G can be selected for "N" functions in relays with the independent ground CT option.
SL-50TP = ,
SL-50TN = ,
SL-50TQ = ,
SL-150TP = ,
SL-150TN = ,
SL-150TQ = ,
SL-250TP = ,
SL-250TN = ,
SL-250TQ = ,

//Time Overcurrent = Mode, 0,1,2,G * , Blk Input Expr


//* G can be selected for "N" functions in relays with the independent ground CT option.
SL-51P = ,
SL-51N = ,
SL-51Q = ,
SL-151P = ,

C-2 Settings Record BE1-CDS


Substation ID ___________________ Relay ID_________________ Date _____________ Page of _____

BE1-CDS Style Number __________________ Serial Number ___________________Version Number_______

SL-151N = ,
SL-151Q = ,
SL-251P = ,
SL-251N = ,
SL-251Q = ,

//General Purpose Logic Timer = Mode, 0,1,2,3,4,5,6 , Ini Input Expr , Blk Input Expr
SL-62 = , ,
SL-162 = , ,

//Breaker Failure = Mode, 0,1,2 , BFI Input Expr , Blk Input Expr
SL-BF = , ,

//Setting Grp Selection = Mode, 0,1,2 , D0 Input Expr , D1 Input Expr , D2 Input Expr
SL-GROUP = , , ,

//Setting Grp Sel-2nd Line = Delimiters , D3 Input Expr , Auto Input Expr
SL-GROUP = ,,, , ,

//Virtual Switches = Mode, 0,1,2,3


SL-43 =
SL-143 =
SL-243 =
SL-343 =
SL-443 =
SL-543 =
SL-643 =
SL-743 =

//Virtual Bkr Control Switch = Mode, 0,1


SL-101 =

//Monitoring Function Blk Logic Settings


//Circuit Monitor Function = Mode, 0,1 , Monitor Input , Status Input
SL-CKTMON = , ,

//Virtual Output Logic Settings


//VO w/ HW Outputs = Output Expression-AND *, OR +, NOT /
SL-VOA =
SL-VO1 =
SL-VO2 =
SL-VO3 =
SL-VO4 =
SL-VO5 =
SL-VO6 =

BE1-CDS Settings Record C-3


Substation ID ___________________ Relay ID _________________ Date _____________ Page of _____

BE1-CDS Style Number __________________ Serial Number___________________ Version Number _______

//Additional VO = Output Expression--AND *, OR +, NOT /


SL-VO7 =
SL-VO8 =
SL-VO9 =
SL-VO10 =
SL-VO11 =
SL-VO12 =
SL-VO13 =
SL-VO14 =
SL-VO15 =

//USER PROGRAMMABLE LABEL SETTINGS


//Contact Sensing 16 Character 7 Character 7 Character
//Input Labels = Variable Label , 1 State Label , 0 State Label
SN-IN1 = , ,
SN-IN2 = , ,
SN-IN3 = , ,
SN-IN4 = , ,
SN-IN5 = , ,
SN-IN6 = , ,
SN-IN7 = , ,
SN-IN8 = , ,

//Virtual Switch Labels = Variable Label , 1 State Label , 0 State Label


SN-43 = , ,
SN-143 = , ,
SN-243 = , ,
SN-343 = , ,
SN-443 = , ,
SN-543 = , ,
SN-643 = , ,
SN-743 = , ,

//Virtual Output Labels = Variable Label , 1 State Label , 0 State Label


SN-VOA = , ,
SN-VO1 = , ,
SN-VO2 = , ,
SN-VO3 = , ,
SN-VO4 = , ,
SN-VO5 = , ,
SN-VO6 = , ,
SN-VO7 = , ,
SN-VO8 = , ,
SN-VO9 = , ,

C-4 Settings Record BE1-CDS


Substation ID ___________________ Relay ID_________________ Date _____________ Page of _____

BE1-CDS Style Number __________________ Serial Number ___________________Version Number_______

SN-VO10 = , ,
SN-VO11 = , ,
SN-VO12 = , ,
SN-VO13 = , ,
SN-VO14 = , ,
SN-VO15 = , ,

//GLOBAL I/O SETTINGS


//Power System Settings
//Nominal Frequency = Hz
SG-FREQ =

//System Rotation = Mode,=ABC,CBA


SG-PHROT =

//CT Input Circuit Setup = Ratio , CT Connection , TX Connection , Ground Source


//CT Input Circuit Setup = Turns,P:S,P/S , WYE,DAB,DAC , NA,WYE,DAB, DAC , 0=No,1=Yes
SG-CT1 = , , ,
SG-CT2 = , , ,
SG-CTG =

//Input Conditioning = Recognition, ms , Debounce, ms


SG-IN1 = ,
SG-IN2 = ,
SG-IN3 = ,
SG-IN4 = ,
SG-IN5 = ,
SG-IN6 = ,
SG-IN7 = ,
SG-IN8 = ,

//Output Hold Attribute = Hold, 0,1


SG-HOLDA =
SG-HOLD1 =
SG-HOLD2 =
SG-HOLD3 =
SG-HOLD4 =
SG-HOLD5 =
SG-HOLD6 =

BE1-CDS Settings Record C-5


Substation ID ___________________ Relay ID _________________ Date _____________ Page of _____

BE1-CDS Style Number __________________ Serial Number___________________ Version Number _______

//PROTECTION SETTING GROUPS


//GROUP 0
//Phase Differential Tap = Base MVA/Manual * , CT1 Base KV/Tap , CT2 Base KV/Tap
//* Enter Base MVA and KV to have tap automatically calculated or enter Manual, Tap1, and Tap2
S0-TAP87 = , ,
//Phase Differential = Min PU, X tap , Slope, % , 2nd Harm, % Iop , 5th Harm, % Iop
S0-87 = , , ,

//Phase Differential-2nd Line = Delimiters , URO PU, X tap , 2nd Harm Sharing, 0,1
S0-87 = ,,, , ,

//Neutral Differential = Min PU, X tap , Slope, % , Time M=ms,C=Cyc,S=Sec(M is deflt)


S0-87ND = , ,

//Inst OC w/ Time Delay = Pick Up, Sec A , Time M=ms,C=Cyc,S=Sec(M is deflt if not specified)
S0-50TP = ,
S0-50TN = ,
S0-50TQ = ,
S0-150TP = ,
S0-150TN = ,
S0-150TQ = ,
S0-250TP = ,
S0-250TN = ,
S0-250TQ = ,

//Time Overcurrent = Pick Up, Sec A , Time Dial , Curve


S0-51P = , ,
S0-51N = , ,
S0-51Q = , ,
S0-151P = , ,
S0-151N = , ,
S0-151Q = , ,
S0-251P = , ,
S0-251N = , ,
S0-251Q = , ,

//Timers = T1 Time , T2 Time M=ms,C=Cyc,S=Sec(M is deflt if not specified)


S0-62 = ,
S0-162 = ,

//GROUP 1
//Phase Differential Tap = Base MVA/Manual* , CT1 Base KV/Tap , CT2 Base KV/Tap
//* Enter Base MVA and KV to have tap automatically calculated or enter Manual, Tap1, and Tap2
S1-TAP87 = , ,

C-6 Settings Record BE1-CDS


Substation ID ___________________ Relay ID_________________ Date _____________ Page of _____

BE1-CDS Style Number __________________ Serial Number ___________________Version Number_______

//Phase Differential = Min PU, X tap , Slope, % , 2nd Harm, % Iop , 5th Harm, % Iop
S1-87 = , , ,

//Phase Differential-2nd Line = Delimiters , URO PU, X tap , 2nd Harm Sharing, 0,1
S1-87 = ,,, , ,

//Neutral Differential = Min PU, X tap , Slope, % , Time M=ms,C=Cyc,S=Sec(M is deflt)


S1-87ND = , ,

//Inst OC w/ Time Delay = Pick Up, Sec A , Time M=ms,C=Cyc,S=Sec(M is deflt if not specified)
S1-50TP = ,
S1-50TN = ,
S1-50TQ = ,
S1-150TP = ,
S1-150TN = ,
S1-150TQ = ,
S1-250TP = ,
S1-250TN = ,
S1-250TQ = ,

//Time Overcurrent = Pick Up, Sec A , Time Dial , Curve


S1-51P = , ,
S1-51N = , ,
S1-51Q = , ,
S1-151P = , ,
S1-151N = , ,
S1-151Q = , ,
S1-251P = , ,
S1-251N = , ,
S1-251Q = , ,

//Timers = T1 Time , T2 Time M=ms,C=Cyc,S=Sec(M is deflt if not specified)


S1-62 = ,
S1-162 = ,

//GROUP 2
//Phase Differential Tap = Base MVA/Manual * , CT1 Base KV/Tap , CT2 Base KV/Tap
//* Enter Base MVA and KV to have tap automatically calculated or enter Manual, Tap1, and Tap2
S2-TAP87 = , ,

//Phase Differential = Min PU, X tap , Slope, % , 2nd Harm, % Iop , 5th Harm, % Iop
S2-87 = , , ,

//Phase Differential-2nd Line = Delimiters , URO PU, X tap , 2nd Harm Sharing, 0,1
S2-87 = ,,, , ,

BE1-CDS Settings Record C-7


Substation ID ___________________ Relay ID _________________ Date _____________ Page of _____

BE1-CDS Style Number __________________ Serial Number___________________ Version Number _______

//Neutral Differential = Min PU, X tap , Slope, % , Time M=ms,C=Cyc,S=Sec(M is deflt)


S2-87ND = , ,
//Inst OC w/ Time Delay = Pick Up, Sec A , Time M=ms,C=Cyc,S=Sec(M is deflt if not specified)
S2-50TP = ,
S2-50TN = ,
S2-50TQ = ,
S2-150TP = ,
S2-150TN = ,
S2-150TQ = ,
S2-250TP = ,
S2-250TN = ,
S2-250TQ = ,

//Time Overcurrent = Pick Up, Sec A , Time Dial , Curve


S2-51P = , ,
S2-51N = , ,
S2-51Q = , ,
S2-151P = , ,
S2-151N = , ,
S2-151Q = , ,
S2-251P = , ,
S2-251N = , ,
S2-251Q = , ,

//Timers = T1 Time , T2 Time M=ms,C=Cyc,S=Sec(M is deflt if not specified)


S2-62 = ,
S2-162 = ,

//GROUP 3
//Phase Differential Tap = Base MVA/Manual * , CT1 Base KV/Tap , CT2 Base KV/Tap
//* Enter Base MVA and KV to have tap automatically calculated or enter Manual, Tap1, and Tap2
S3-TAP87 = , ,

//Phase Differential = Min PU, X tap , Slope, % , 2nd Harm, % Iop , 5th Harm, % Iop
S3-87 = , , ,

//Phase Differential-2nd Line = Delimiters , URO PU, X tap , 2nd Harm Sharing, 0,1
S3-87 = ,,, , ,

//Neutral Differential = Min PU, X tap , Slope, % , Time M=ms,C=Cyc,S=Sec(M is deflt)


S3-87ND = , ,

C-8 Settings Record BE1-CDS


Substation ID ___________________ Relay ID_________________ Date _____________ Page of _____

BE1-CDS Style Number __________________ Serial Number ___________________Version Number_______

//Inst OC w/ Time Delay = Pick Up, Sec A , Time M=ms,C=Cyc,S=Sec(M is deflt if not specified)
S3-50TP = ,
S3-50TN = ,
S3-50TQ = ,
S3-150TP = ,
S3-150TN = ,
S3-150TQ = ,
S3-250TP = ,
S3-250TN = ,
S3-250TQ = ,

//Time Overcurrent = Pick Up, Sec A , Time Dial , Curve


S3-51P = , 0,
S3-51N = , 0,
S3-51Q = , 0,
S3-151P = , 0,
S3-151N = , 0,
S3-151Q = , 0,
S3-251P = , 0,
S3-251N = , 0,
S3-251Q = , 0,

//Timers = T1 Time , T2 Time M=ms,C=Cyc,S=Sec(M is deflt if not specified)


S3-62 = ,
S3-162 = ,

//GENERAL PROTECTION SETTINGS


//Breaker Failure = Time M=ms,C=Cyc,S=Sec(M is deflt if not specified)
SP-BF =

//Programmable Curve = A Coefficient , B Coefficient , C Coefficient , N Coefficient


SP-CURVE = , , ,
//Programmable Curve-2nd Line = Delimiters , R Coefficient
SP-CURVE = ,,, ,

//Automatic Group Selection Switch Settings , Return Settings


//Grp 1 Auto Settings = Time, Min , Level,%GRP0 51x , Time, Min , Level,%GRP0 51x
SP-GROUP1 = , , ,
//Grp 1 Auto Settings-2nd Line = Delimiters , GRP0 51x element, 51X, 151X, 251X; X=P, N, Q
SP-GROUP1 = ,,, ,

//Automatic Group Selection Switch Settings , Return Settings


//Grp 2 Auto Settings = Time, Min , Level,%GRP0 51x , Time, Min , Level,%GRP0 51x

BE1-CDS Settings Record C-9


Substation ID ___________________ Relay ID _________________ Date _____________ Page of _____

BE1-CDS Style Number __________________ Serial Number___________________ Version Number _______

SP-GROUP2 = , , ,
//Grp 2 Auto Settings-2nd Line = Delimiters , GRP0 51x element, 51X, 151X, 251X; X=P, N, Q
SP-GROUP2 = ,,, ,

//Automatic Group Selection Switch Settings , Return Settings


//Grp 3 Auto Settings = Time, Min , Level,%GRP0 51x , Time, Min , Level,%GRP0 51x
SP-GROUP3 = , , ,
//Grp 3 Auto Settings-2nd Line = Delimiters , GRP0 51x element, 51X, 151X, 251X; X=P, N, Q
SP-GROUP3 = ,,, ,

//Setting Group Changed Timer = Time, Sec


SG-SGCON =

//REPORTING AND ALARM FUNCTION SETTINGS


//DEMAND REPORTING SETTINGS
//Demand Interval = Time, Min , Mode, T, B, S , CT Circuit, 1,2,G *
//* G can be selected for "N" functions in relays with the independent ground CT option.
SG-DIP = , ,
SG-DIN = , ,
SG-DIQ = , ,

//The following settings are only for relays with Load Profile Recording (Style # BE1-CDS x0x N0x xxYxx).
//Demand Logging Interval = Time, Min
SG-LOG =

//FAULT REPORTING SETTINGS


//Targets = Protective Functions Separated by /'s
SG-TARG =

//Targets-2nd Line = Delimiters , Target Reset via Programmable Logic Expr


SG-TARG = ,

//FAULT RECORD TRIGGERS


//Fault Record Trigger = Delimiters Trip Logic Expr
SG-TRIGGER =
//Flt Record Trigger-2nd Line = Delimiters , PU Logic Expr
SG-TRIGGER = ,
//Flt Record Trigger-3rd Line = Delimiters , Logic Trigger Expr
SG-TRIGGER = , ,

//DISPLAY AND COMMUNICATION SETTINGS


//Identifier Information
//ID Field 1 = Relay ID, 30 Char--Used in COMTRADE file as "rec_dev_id" field
SG-ID1 =

C-10 Settings Record BE1-CDS


Substation ID ___________________ Relay ID_________________ Date _____________ Page of _____

BE1-CDS Style Number __________________ Serial Number ___________________Version Number_______

//ID Field 2 = Station ID, 30 Char--Used in COMTRADE file as "station_name" field


SG-ID2 =

//ID Field 3 = User ID1, 30 Char--Misc. identifier field


SG-ID3 =

//ID Field 4 = User ID2, 30 Char--Misc. identifier field


SG-ID4 =

//Clock Display Mode = Date, M or D , Time, 12 or 24 , Auto Daylight Savings, 0=OFF,1=ON


SG-CLK = , ,

//Auto Scroll List = HMI Screen #


SG-SCREEN1 =
SG-SCREEN2 =
SG-SCREEN3 =
SG-SCREEN4 =
SG-SCREEN5 =
SG-SCREEN6 =
SG-SCREEN7 =
SG-SCREEN8 =
SG-SCREEN9 =
SG-SCREEN10 =
SG-SCREEN11 =
SG-SCREEN12 =
SG-SCREEN13 =
SG-SCREEN14 =
SG-SCREEN15 =
SG-SCREEN16 =

//Communications
//Front RS232 Port = Baud , Address , Pg Length,P0-40 , Reply Ack, R0,1
SG-COM0 = , A0 , ,

//Front RS232 Port--2nd Line = Delimiters , Handshake, X0,1


SG-COM0 = ,,, ,

//Rear RS232 Port = Baud , Addr., A0-65534 , Pg Length,P0-40 , Reply Ack, R0,1
SG-COM1 = , , ,

//Rear RS232 Port-2nd Line = Delimiters , Handshake, X0,1


SG-COM1 = ,,, ,

//Rear RS485 Port = Baud , Addr., A0-65534 , Pg Length,P0-40 , Reply Ack, R0,1
SG-COM2 = , , ,

BE1-CDS Settings Record C-11


Substation ID ___________________ Relay ID _________________ Date _____________ Page of _____

BE1-CDS Style Number __________________ Serial Number___________________ Version Number _______

//Rear RS485 Port-2nd Line = Delimiters , Handshake


SG-COM2 = ,,, , X0

//The following settings are only for relays with Modbus (Style # BE1-CDS x0x N0x x1xxx).
//RS485 Port Modbus Settings = EP Format, MF0,1 , Parity, MPN,O,E , Remote , Stop Bits,
Delay,MRms MS1,2
//SG-COM2=,,,,, , , ,

//TRANSFORMER MONITORING SETTINGS


//Transformer Duty = Mode, 1=I,2=I2 , 100% Duty, x.xxxE+xx,Amps , CT Circuit, 1,2
ST-DUTY = , ,

//Transformer Duty-2nd Line = Delimiters , Block Duty Accumulation via Programmable Logic Expr
ST-DUTY = ,, ,

//BREAKER MONITORING SETTINGS


//Breaker Duty = Mode, 1=I,2=I2 , 100% Duty, x.xxxE+xx,Amps , CT Circuit, 1,2
SB-DUTY = , ,

//Breaker Duty-2nd Line = Delimiters , Block Duty Accumulation via Programmable Logic Expr
SB-DUTY = ,, ,

//BREAKER STATUS
//Breaker Status = Logic Expression , Breaker Label, 16 Char.
SB-LOGIC = ,

//ALARM SETTINGS
//Differential Alarm = Threshold, % 87R MinPU and Slope
SA-DIFF =

//Transformer Alarms = Mode, 0,1,2 , Threshold


SA-TX1 = ,
SA-TX2 = ,
SA-TX3 = ,

//Breaker Alarms = Mode, 0,1,2,3 , Threshold


SA-BKR1 = ,
SA-BKR2 = ,
SA-BKR3 = ,

//Demand Alarms = Threshold, Sec A


SA-DIP =
SA-DIN =
SA-DIQ =

C-12 Settings Record BE1-CDS


Substation ID ___________________ Relay ID_________________ Date _____________ Page of _____

BE1-CDS Style Number __________________ Serial Number ___________________Version Number_______

//Alarm Priority = Mask of Alarm Points, Separated by /'s


SA-LGC =
SA-MAJ =
SA-MIN =

//Alarm Reset Logic = Alarm Reset via Programmable Logic Expr


SA-RESET =

//EXIT WITH SAVE SETTINGS--YES


E
Y

BE1-CDS Settings Record C-13


APPENDIX D • TERMINAL COMMUNICATION
This appendix provides instructions for configuring Windows 95® HyperTerminal and Windows® Terminal
to communicate with your BE1-CDS relay.

WINDOWS 95® HYPERTERMINAL


Step 1. Click Start: Highlight Programs, Accessories, HyperTerminal.
Step 2. Click HyperTerminal to open the folder.
Step 3. Select the file or icon labeled Hypertrm or Hypertrm.exe. Once the program has started, you will be
presented with a series of dialog boxes.
Step 4. Dialog Box: CONNECTION DESCRIPTION
See Figure D-1.
a. Type the desired file name, for example,
BE1-CDS
b. Click “OK”
Step 5. Dialog Box: PHONE NUMBER
a. Click drop-down menu: CONNECT USING
Select Direct To ComX, where X is the port you
are using on your computer.
b. Click “OK”

Step 6. Dialog Box: COMX Properties Figure D-1. Connection Description Dialog Box

a. Make the following selections using Figure D-2


as a guide.
Set the bits per second setting so that it
matches the setting of the relay. The default
baud rate of the relay is 9600.
Set the data bits at 8.
Set the stop bits at 1.
Set flow control to Xon/Xoff.
b. Click “OK”. This creates an icon with the file
name entered in Step 4 and places it in the
HyperTerminal folder. Future communication
sessions can then be started by clicking the
appropriate icon.
Step 7. Click File/Properties on the menu bar. Click the
Settings tab.
a. Make the following selections:
Check the Terminal Keys radio button.
Figure D-2. COM Properties Dialog Box
Select VT-100 emulation.
Set the Backscroll Buffer to the maximum setting of 500.

BE1-CDS Terminal Communication D-1


b. Click the ASCII Setup button. Make the
following selections using Figure D-3 as a
guide.
ASCII Sending
Place a check at Send line ends...
Place a check at Echo typed...
Select a line delay setting of 100 to 200
milliseconds.
Select the Character delay at 0.
ASCII Receiving
Disable Append line feeds... by leaving
unchecked.
Disable Force incoming... by leaving
unchecked.
Place a check at Wrap lines... Figure D-3. ASCII Setup Dialog Box
c. Click “OK”.
d. Click “OK”.
Step 8. Click File and click Save.

NOTE
Settings changes do not become active until the settings are saved.

Step 9. HyperTerminal is now ready to communicate with the relay. Table D-1 describes the required
connection for each RS-232 port.
Table D-1. RS-232 Communication Ports
Connection Type

Front Port 9-pin female DCE

PC to Front RS-232 port cable Straight

Rear Port 9-pin female DCE

Modem to Rear RS-232 port cable Null modem

PC to Rear RS-232 port cable Straight

WINDOWS® TERMINAL
Step 1. In Program Manager, open the Accessories program group and double click the Terminal icon to
start the program.
Step 2. On the menu bar, select Settings/Terminal Emulation.
a. In the dialog box, click DEC VT-100 (ANSI).
b. Click “OK”.

D-2 Terminal Communication BE1-CDS


Step 3. Select Settings/Terminal Preferences.
a. Using Figure D-4 as a guide, make the
following selections in the dialog box:
Check the Line Wrap and Local Echo
boxes to enable these functions.
Disable the CR->CR/LF Inbound function.
Enable the CR->CR/LF Outbound function.
b. Set the Buffer Lines at 244.
c. Click “OK”.
Step 4. Select Settings/Text Transfers
a. Make the following selections using Figure
D-5 as a guide.
Figure D-4. Terminal Preferences Dialog Box
Set Flow Control at Line at a Time.
Enable Delay Between Lines and set the
delay at 1 or 2/10 Sec.
Disable Word Wrap...
b. Click “OK”.
Step 5. Select Settings/Communications
a. Make the following selections:
Under Connector, select the appropriate
communication port for your computer.
Adjust the Baud Rate setting so that it matches
the setting of the relay. The default baud rate
of the BE1-CDS is 9600. Figure D-5. Text Transfers Dialog Box

Set the Data Bits at 8.


Disable Parity Check.
Set the Stop Bits at 1.
Set Flow Control to Xon/Xoff.
b. Click “OK”.
Step 6. Click File/Save. Enter a desired file name such as
BE1-CDS.trm. For future communication
sessions, click File and open this file. Terminal will
automatically be setup properly to communicate
with the BE1-CDS relay.
Step 7. Terminal is now ready to communicate with the
relay. Table D-1 describes the required
connection for each RS-232 port. Figure D-6. Communications Dialog Box

BE1-CDS Terminal Communication D-3


APPENDIX E • SETTINGS CALCULATIONS
TABLE OF CONTENTS

List Of Figures......................................................................................................................................... i
List Of Tables.......................................................................................................................................... i
APPENDIX E • SETTINGS CALCULATIONS............................................................................................E-1
GENERAL ..............................................................................................................................................E-1
VERIFY CT PERFORMANCE................................................................................................................E-1
Verify CT Performance .......................................................................................................................E-2
DETERMINE TAP SETTINGS ...............................................................................................................E-3
Calculate Ideal Taps ...........................................................................................................................E-3
Calculate Minpu ..................................................................................................................................E-4
Choose Unrestrained Pickup Setting ..................................................................................................E-5
Calculate Maximum External Fault .....................................................................................................E-6
Calculate Slope...................................................................................................................................E-7
Harmonic Restraint Settings ...............................................................................................................E-9
Saturation Factor Defined From The ANSI C Classification .............................................................E-12
Saturation Factor Defined From The CT Excitation Curve ...............................................................E-13
Saturation Factor Definitions Compared...........................................................................................E-13
Conclusion ........................................................................................................................................E-15

List Of Figures
Figure E-1. Two Winding Transformer Relay Setting Calculation Example..............................................E-1
Figure E-2. Slope And Operating Margin ..................................................................................................E-8
Figure E-3. CT Burden, Delta Connected CTs, 3-Phase Fault ...............................................................E-10
Figure E-4. Phase-To-Phase Fault, Delta Connected CTs .....................................................................E-11
Figure E-5. CT Equivalent Circuit............................................................................................................E-12
Figure E-6. CT Terminal And Excitation Voltages...................................................................................E-13
Figure E-7. SF`/SF Ratio.........................................................................................................................E-14
Figure E-8. Comparing SF And SF` ........................................................................................................E-14
Figure E-9. Reducing The Difference Between SF And SF’ ...................................................................E-15

List Of Tables
Table E-1. Example Specifications ...........................................................................................................E-1
Table E-2. Parameters For Equations E-1 And E-2 ..................................................................................E-4

Volume 1 BE1-CDS Settings Calculations i


APPENDIX E • SETTINGS CALCULATIONS

GENERAL
These settings calculations are provided to assist in developing the required settings for the BE1-CDS
Current Differential System. To develop these settings, the paragraphs in this section discuss each task.
• Verify CT Performance
• Determine Tap Settings
• Calculate Minimum Pickup Restraint Setting
• Select Unrestrained Pickup Setting
• Calculate Slope
• Select Harmonic Restraint Settings
For additional information on selected examples, see the associated Setting Notes.

VERIFY CT PERFORMANCE
Refer to Figure E-1 and Table E-1 for the application parameters used in this example.

Data
12/20MVA
Z S= 2 % @ 1 0 0 M V
A 69 kV 12.47 kV
600/5MR 1200/5MR
F
300/5T
S (3) (3) 800/5T
LOAD

1916 (3 ∅) 10,603 (3 ∅)
1171 (1 ∅) 11,231 (1 ∅)
+10%LTC D1873-21
ZT= 5 % @ 1 2 M V A 11-05-99

Figure E-1. Two Winding Transformer Relay Setting Calculation Example

Table E-1. Example Specifications


SPECIFICATIONS HIGH SIDE LOW SIDE
Nominal Voltage 69 kV 12.47 kV
No-Load Taps 70.725 kV 12.47 kV
72.450 kV
69.000 kV
67.275 kV
65.550 kV
MVA 12/20 12/20
CT Ratio 600:5 1200:5
CT Tap 300:5 800:5
CT Accuracy Class 400 800
One-Way Lead Burden (ohms) 0.7 0.7
XFMR Connection* DELTA WYE
CT Connection WYE WYE
Input # 1 2
Fault Current (Three-Phase) 1,916 10,603
Fault Current (Single-Phase) 1,171 11,231
* Standard connection: High voltage leads the low voltage by 30°.
BE1-CDS Settings Calculations E-1
Verify CT Performance

NOTE
This procedure uses the ANSI accuracy class method. See Setting Note 3 for more
information.

Step 1. Determine the maximum CT secondary fault current for external faults at F (IF3 for three-phase,
and IFG for single-phase). Refer to Figure E-1 for this example.
HIGH LOW
1916 10603
I F3 = I F3 =
60 160
= 32 A = 66 A
1171 11231
I FG = I FG =
60 160
= 19.5 A = 70 A

Step 2. Determine the worst case CT burden voltage for a three-phase fault (VB3).
• For wye-connected CTs:
VB3 = IF3(RL + RR)
• For delta-connected CTs, for three-phase fault:
VB3 = 3 IF3(RL + RR)
Note that the wye connection produces a lower burden on the CTs (see Setting Note 1).

Where:
IF3 = determined in Step 1
RL = one-way lead resistance in ohms
RR = relay resistance in ohms (< 0.05 ohm)

Neglecting RR, use RL from Table E-1.

HIGH LOW
VB3 = (32)(0.7) VB3 = (66)(0.7)
= 22.4 V = 46.2 V

Step 3. Determine the worst case burden voltage for a line-to-ground fault (VBG).
• For wye-connected CTs:

VBG = IFG(2RL + RR)

Where:
IFG = determined in Step 1
RL = one-way lead resistance in ohms
RR = relay resistance in ohms

• For delta-connected CTs:

VBG is a function of the proportion of positive-sequence to zero-sequence currents, but may be


approximated by the same equation (for worst case).

E-2 Settings Calculations BE1-CDS


Neglecting RR, use RL from Figure E-1:

HIGH * LOW
VBG =19.5(0.7) VBG = 70 (2(0.7))
= 13.6 V = 98.0 V
*NOTE
Since a phase-to-ground fault looks like a phase-to-phase fault on the delta side of a
delta/wye transformer, each CT has to carry only one times the one way lead burden.

Step 4. Determine the effective CT accuracy class (VCE):

(Base Accuracy) (Number of CT Turns in Use)


VCE =
Maximum Ratio
NA
= VC ( )
N

HIGH LOW
60 160
VCE = (400) VCE = (800)
120 240
= 200 = 533.3

Step 5. Determine the saturation factor (SF):

VB is the largest of the burden voltages calculated in steps 13 and 14.


VB
SF =
VCE
HIGH LOW
22.4 98.0
SF = SF =
200 533.3
= 0.11 = 0.18

NOTE
Maximum Recommended SF = 0.5. Larger saturation factors will make the relay insecure
for external faults. Possible solutions are to increase the CT quality, adjust the CT tap
connections to increase effective accuracy class, or to use internal phase compensation
instead of delta connecting CTs.

DETERMINE TAP SETTINGS

Calculate Ideal Taps

Step 1. Use equations E-1 and E-2 to calculate ideal taps. Parameters for these equations are in Table
E-2. For more information refer to Volume 1, Section 4, Protection And Control Functions, 87
Phase Differential Function, Setting Tap Compensation Settings, 87 Phase Differential Function.
MVA * 1000 * COMP1 MVA * 1000 * COMP 2
TAP1 = TAP 2 =
3 * KV 1 * CTR1 3 * KV 2 * CTR 2

Equation E-1 Equation E-2

BE1-CDS Settings Calculations E-3


Table E-2. Parameters For Equations E-1 And E-2
Parameter Description Explanation
MVA MVA Base Full load MVA or top rating of the protected equipment
KVn KV Base for CT input n L-L Voltage in KV for each CT input circuit
CTRn CT Ratio for CT input n Actual ratio not effective ratio
COMPn Phase Compensation √3 if CT’s are connected in Delta (ctcon = DAB or DAC).
Adjustment Factor for
1 in all other cases.
CT input n
See Volume 1, Section 3, Table 3-2 and Figure 3-3

NOTE
When calculating the tap adjust settings for the BE1-87T, the √3 COMPn factor had to be
included regardless of whether phase compensation was done by connecting the CTs in
delta or by using internal delta compensation. The BE1-CDS relay does not magnify the
secondary current when performing the phase compensation internally (for more
information see the internal Compensation Chart under the SG-CT command in Volume
1, Section 3). The COMP factor is 1 unless the CTs are connected in Delta. The
BE1-CDS automatically takes the √3 factor into account prior to the tap adjustment when
internal phase compensation is applied to a set of CT input currents.

Step 2. Calculate ideal tap values. Use the top (e.g. FA) MVA rating of the transformer when making
the calculations. Since both CTs are wye connected, COMP1 and COMP2 are 1 per Table E-2.
If the actual power transformer ratings at the no load tap position are used for the KV Base, the
tap adjust factor calculation can completely cancel this source of mismatch. However, if the no
load taps in the protected transformer could be changed without the BE1-CDS tap adjust factors
being reset, it would be safer to use the system nominal values and account for the additional
mismatch in the slope setting.
20 * 1000 * 1 20 * 1000 * 1
TAP1 = = 2.79 TAP 2 = = 5.79
3 * 69 * 60 3 * 12.47 * 160
Equation E-3 Equation E-4

Step 3. If the calculated TAP1 and TAP2 are in range, (2.00 - 20.0 for 5 ampere sensing input types or
0.40 - 4.00 for 1 ampere sensing input types) proceed to Calculate Minpu . If they are not in
range, proceed with Step 4.

Step 4. Calculate spread ratio. Determine the ratio of TAP1 to TAP2. If greater than 10:1, adjust the
CT ratios to bring them closer together.

Step 5. Calculate actual tap settings. Choose the tap that is out of range, and adjust to the nearest
valid tap setting.

Step 6. Calculate the opposite actual tap such that Equation E-5 is true.
Ideal TAP1 Actual TAP1
=
Ideal TAP 2 Actual TAP 2

Equation E-5

Calculate Minpu
The minimum pickup restraint setting (minpu) adjusts the sensitivity of the relay. In non-numerical relays,
the minpu was fixed at a typical value of 0.35 of the relay tap. In the BE1-CDS relay, the user can choose
lower or higher values to optimize the protection in each particular application. Selecting a lower minpu

E-4 Settings Calculations BE1-CDS


setting will tend to raise the slope setting to maintain a given margin at the knee-point of the differential
tripping characteristic (for more information, see the Calculate Slope paragraphs later in this section).
Conversely, it is sometimes necessary to accommodate unmonitored loads in the differential zone. In that
case, the minpu setting may be higher. A setting of 0.25 per unit of transformer full load (FA) rating is
recommended for typical installations where no unmonitored load needs to be considered. This value is
well above the magnetizing current and provides a safe margin at the knee point of the slope
characteristic. If unmonitored loads such as station service or small capacitor banks are connected in the
differential zone, the minpu must be increased by the magnitude of the unmonitored current in multiples of
tap.

NOTE
Unmonitored capacitor banks should be avoided if possible, or they must be treated very
carefully to avoid false tripping due to inrush currents.

Step 1. Calculate desired minimum pickup setting in times tap. Choose the desired minimum pickup in
per unit on the transformer full load base (0.25). Multiply this times the factor X calculated using
Equation E-6. If the ideal tap (TAPnI) is equal to the actual tap (TAPnA), the factor will be 1. For
this example, this is the case, so the minimum pickup of 0.25 per unit will equal a minimum
pickup of 0.25 times tap.
TAPnI MVA * 1000 * COMPn
X= =
TAPnA TAPnA * 3 * KVn * CTRn

Equation E-6

Step 2. Calculate the unmonitored load in times tap. Use Equation E-7.
Iunmon pri * COMPn
Iunmon =
TAPn * CTRn
Iunmon = 0
Equation E-7

Step 3. Calculate the Minpu setting. Add the two to get the minpu setting.
Minpu = 0.25 + 0
= 0.25

Step 4. Convert pickup setting to primary amps


As a reality check, convert the minimum sensitivity to high side and low side primary amperes. The pickup
settings in times tap can be related to primary amperes by Equation E-8.

Mpu * TAPn * CTRn 0.25 * 2.79 * 60


Ipri = Ipri = = 41 amperes @ 69 kV
COMPn 1
Equation E-8

0.25 * 5.79 * 160


Ipri = = 231 amperes @ 12.47 kV
1

Choose Unrestrained Pickup Setting


This two step process selects the unrestraint element setting to provide security for both inrush and
external fault conditions.

Step 1. Calculate the expected inrush current based upon the self cooled rating of the transformer.
nd
Asymmetrical CT saturation during a heavy internal fault generates 2 harmonics that can inhibit the
sensitive percentage restrained unit until the CT recovers. The unrestrained unit provides fast clearing for

BE1-CDS Settings Calculations E-5


these internal faults. Thus, the unrestrained unit should be set as sensitively as possible without operating
on inrush.
Typical numbers used in the industry for inrush have been eight to twelve times the rating of the
transformer. Due to the operating characteristics of the BE1-CDS unrestrained differential element, a
setting of six times the self cooled rating provides security for inrush. We can use a lower URO pickup
setting and maintain security for unrestrained tripping because inrush current typically has a high peak
that is non-sinusoidal. The relay extracts the fundamental component of the operate current for use by the
unrestrained element to greatly reduce its sensitivity to this non-sinusoidal inrush current. Also, the high
initial peak generally decays quickly to a lower value. As shown in Figure 1-9, the slight inverseness of
the tripping characteristic provides additional security from unrestrained tripping on inrush with a sensitive
setting.
Since the tap values are based upon the forced cooled rating and adjusted if necessary by the factor
X calculated in Calculate Minpu, Step 1, Equation E-6, the pickup can be calculated by Equation E-9.
MVA self cooled 12
URO = 6 * X * URO = 6 * 1 *
MVA forced cooled 20

Equation E-9 URO = 3.6


This URO value (3.6 rounded up to 4.0) is the minimum setting to avoid tripping during inrush. The next
step will determine the value required to avoid tripping for the maximum external fault under worst case
CT saturation.

Calculate Maximum External Fault

Step 1. Calculate the maximum external fault (IE) in multiples of tap. Use Equation E-10 or E-11.
For wye connected CT’s For delta connected CT’s (See Setting Note 2)

Maximum Fault Maximum Fault 3 phase * 3


IE = IE =
Tap Tap

Equation E-10 Equation E-11

69 kV Side 12.47 kV Side

 1916   10603 
   
 60   160 
IE = = 11.5 IE = = 11.4
2.79 5.79

Step 2. The transient monitor function provides security from tripping for external through faults by
doubling the unrestrained unit pickup setting when saturation is detected. Calculate the
unrestrained pickup such that 2 times the unrestrained pickup is greater than 70% of the
maximum external through fault in times tap. This calculation assumes that the CTs carrying
the maximum fault saturate severely, yielding only 30% of the expected ratio current. This
leaves 70% of the fault current as false differential current.
0.70 * 11.5 0.70 * 11.4
URO = = 4.02 URO = = 3.99
2 2
Equation E-12 Equation E-13

Step 3. Select the unrestrained pickup setting. Choose the larger of the unrestrained pickup values
calculated in Equations E-9 and E-12 or E-13, and round it up to the next integer value. (In
Equation E-12, because 4.02 is very close to 4.0, do not round up to 5.) This results in a setting
of URO = 4 times tap for this example.

Step 4. Convert pickup setting to primary amperes.

E-6 Settings Calculations BE1-CDS


As a reality check, convert the unrestrained pickup sensitivity to high side and low side primary amperes.
The equation to do so is similar to Equation E-8.
4 * 2.79 * 60 4 * 5.79 * 160
Ipri = = 670 Amps @ 69 KV Ipri = = 3,706 Amps @ 12.47 KV
1 1
Equation E-14 Equation E-15

Calculate Slope
The percentage restrained tripping characteristic is defined by the slope ratio. The slope setting S is the
ratio of the differential current (Iop) versus the restraint current (Irestraint) that will cause a trip. The percentage
differential characteristic can operate on a slope setting that is a percent of the maximum of the through
currents or a percent of the average of the through currents.

Step 1. Calculate the Operating Slope Si.


The operating slope Si is the ratio of the differential current (Iop) caused by the sum of all the mismatch
sources versus the through current. The following sources of Iop current must be taken into account.
• No load tap changer (this can be compensated for in the tap calculation). You may choose to include
this source of mismatch if it is possible that the no load taps may be adjusted without the relay taps
being reset.
• Load tap changer.
• Tap mismatch (assumed to negligible due to the fine tap adjustment available in the relay).
• Quality of the CTs (If the saturation factor calculated previously is greater than 0.5, additional margin
is recommended. For SF<0.5, we assume that the CTs perform within the 10% limit defined in the
ANSI Accuracy Class. When accounting for CT error, the total CT error should be 10%*(n-1) where n
is the number of restraint current inputs (2 for two restraint relay, 3 for three restraint relay). If more
than one CT is nearing the performance limit, the errors tend to cancel.
• Relay measuring errors. A total of 4% applies to the BE1-CDS (2% per input circuit).
The following errors are not included in the Si operating slope value (these sources of mismatch do not
vary with through current so they affect the minpu setting only).
• Transformer excitation current IE (assumed to be less than 4% of the self cooled rating). This
mismatch does not vary with through current (load) so it tends to not add to the slope mismatch line.
It will offset the slope characteristic from the origin in the operate direction on the operate versus
restraint characteristic (see Figure E-2).
• Unmonitored loads “Iunmon” such as station service or small capacitor banks in the differential zone
add to the constant excitation current.
When the saturation factor exceeds 0.5 on any of the CTs, CT saturation is likely. For this condition, the
BE1-CDS improves security by delaying restrained tripping by two cycles when the transient monitor
function detects operate (differential) current that is a result of CT saturation. For applications where the
saturation factor is greater than 0.5, additional slope margin is recommended. For applications where the
saturation factor exceeds 1.0, severe distortion is likely at high fault current and the maximum slope
setting (60%) is recommended. For more information see Setting Note 4.
In the example, the tap factors were calculated on system nominal ratings so the no load tap changer
position is included as a source of mismatch.
SI = (5% NLTC) + (10% LTC) + (10% CT) + (4% Relay) = 29%
Equation 16

BE1-CDS Settings Calculations E-7


D2857-20.vsd
Io p 11-08-99

In Multiples
Of Tap
1.0

9%
=3
minimum pickup (S)
e
= 0.25 lop
in gS M
gin o
pp Mar
Tri e r a ting
B Op 20%
Offset = (S ) =
0.024 atin g Slope i
C Oper
A
1.0 I R In Multiples Of Tap

M o = AB − AC
 S min pu 
M o = min pu −  i + I OFFSET 
 S 
 S 
M o = min pu 1 − i  − I OFFSET
 S

Figure E-2. Slope And Operating Margin

Step 2. Choose slope setting S. The tripping slope S must be greater than Si to provide a safety margin
at the differential tripping characteristic knee point (intersection of the minimum pickup tripping
characteristic and the slope tripping characteristic). This safety margin is required to accom-
modate the additional mismatch caused by the excitation current and the unmonitored load
current. Refer to Figure E-2. A slope margin of 10% is recommended.
S = Si + Slope Margin S = 29% + 10% = 39%
Equation 17

Step 3. Calculate Offset Current IOFFSET. The margin at the knee point of the tripping characteristic is
illustrated in Figure E2. The additional mismatch caused by excitation current and unmonitored
loads does not vary with through current loading so it tends to offset the operating slope Si up-
ward from the origin. Thus, it decreases the safety margin at the differential tripping charact-
eristic knee point (intersection of the minimum pickup tripping characteristic and the slope
tripping characteristic).
IOFFSET = IE + Iunmon IOFFSET = 0.24 + 0 = 0.24
Where:
IE is assumed to be less than 4% of the self cooled rating.

MVA self cooled 12


IE = IE self cooled * X * IE = 0.04 * 1 * = 0.024
MVA forced cooled 20
Equation E-18 Equation E-19
Where:
X is the tap conversion factor defined in Calculate Minpu, Step 1, Equation E-6.
Iunmon is the unmonitored load calculated in Calculate Minpu, Step 2, Equation E-7.

Step 4. Calculate Operating Margin Mo. The Operating Margin Mo is given by Equation E-20.

E-8 Settings Calculations BE1-CDS


S
M o = Minpu (1 − i ) − I OFFSET
S
Equation E-20
The conservative calculation of margin at the knee point uses Si as calculated in Calculate Slope, Step 1.
For this example, Mo in times tap is Equation E-21.

29
M o = 0.25 * (1 − ) − 0.024 = 0.040 times tap
39
Equation E-21
The above calculation of margin is conservative. For the low current level where the margin at the tripping
characteristic knee point is of interest, the CT error will typically be less than 1%. Thus, calculating the
margin using SI = 20 (replace 10% CT error with 1% CT error) yields the following result in Equation E-22.
20
M o = 0.25 * (1 − ) − 0.024 = 0.098 times tap
39
Equation E-22
If the conservative calculation yielded a margin < or = 0, the minpu and/or the slope settings should be
increased.

Step 5. Convert the margin to primary amperes. As a reality check, convert the margin to high side and
low side primary amperes. The equation to do so is similar to Equation E-8.
0.098 * 2.79 * 60 0.098 * 5.79 * 160
Ipri = = 16.4 Amps @ 69 kV Ipri = = 90.8 Amps @ 12.47 kV
1 1
Equation E-23 Equation E-24

Harmonic Restraint Settings


The recommended harmonic restraint settings have been in effect successfully for many years. Most
applications should use these settings. When second harmonic sharing is enabled, restraint for the A
phase differential element is determined by:

 IAop 2nd + IBop 2 nd + ICop 2 nd 


100 *   ≥ 2nd Re stra int Setting
 IAop1st + 
 

The B phase and C phase differential elements respond similarly with IBop1st and ICop1st substituted in the
respective equation. This unique method of second harmonic sharing is recommended to ensure proper
restraint on all phases without blocking tripping on faulted phases.
For special transformers cases, contact the transformer manufacturer or the Basler Electric Technical
Services Department.

Step 1. If second harmonic sharing is enabled, set the second harmonic restraint unit setting at 18%. If
second harmonic sharing is disabled, set the second harmonic restraint unit at 12%.

Step 2. Set the fifth harmonic restraint unit setting.


th
5 = 35%

BE1-CDS Settings Calculations E-9


Setting Note 1. CT Burden, Delta Connected CTs, 3-Phase Fault

RW IA IA- IC RL RELAY
A

VS RR
VT

RW IB- IA RL
B
IB
RR

RW IC- IB RL
C
IC
RR

D2857-22.vsd
11-09-99

Figure E-3. CT Burden, Delta Connected CTs, 3-Phase Fault


IA+IB+IC=0
IA=-(IB+IC)
VS=IARW+(IA-IC)(RL+RR)-(IB-IA)(RL+RR)
=IA(RW+RL+RR+RL+RR)-IB(RL+RR)-IC(RL+RR)
=IA(RW+2RL+2RR)-(IB+IC)(RL+RR)

Since IA=-(IB+IC)
VS=IA(RW+3RL+3RR)
VT=VS -RW IA
VT=3IA(RL+RR)

Where:

IA = 3-Phase fault current


RR = Relay burden
RL = Lead burden
RW = Winding burden

E-10 Settings Calculations BE1-CDS


Setting Note 2. Phase-To-Phase Fault, Delta Connected CTs

RELAY
IA I 1 I

IB 2I 2 2I

I 3 I

(0)

D2779-01
11-09-99

Figure E-4. Phase-To-Phase Fault, Delta Connected CTs

3
Assuming Z1=Z2, Iφφ = × I 3φ
2
Phase 2 carries twice the fault current returning from the relay to the CTs. Therefore, the maximum
current is:
I MAX = 2 × I φφ
 3 
= 2× I 
 2 3φ 
 
I MAX = 3 × I 3φ

BE1-CDS Settings Calculations E-11


Setting Note 3. CT Performance Evaluation: Saturation Factor

The secondary current delivered by a current transformer to a relay circuit is always less than the current
available from an ideal CT. The ideal, or ratio current (Ist=IP/RCT), is reduced by the excitation current
(Ie) to yield the actual current (Is). This relationship is illustrated in the CT equivalent circuit shown in
Figure E-5.

Is

Ist
IP
Rs Rl

Rr
Ie
Ve
VT

Figure E-5. CT Equivalent Circuit


For relaying applications, the CT performance is considered acceptable if the ratio correction is less than
10%. The ratio error is defined in C57.13-1993, section 8.1.10 as Ie/Is. This criterion is expressed in the
ANSI C accuracy class which is defined in the following sentence. Under steady state (symmetrical
current) conditions, the excitation current must be less than 10 amperes for a relay current of 100
amperes into the specified standard burden. Since fault currents necessarily start with some degree of
transient DC offset, good design practice requires that the ratio error remain below 10% during the initial
transient offset period, if possible, particularly when fast tripping is in effect. It has been generally
accepted that a design for a saturation factor (SF) of 0.5 or less is acceptable. The following analysis
provides two definitions of the saturation factor, using a C200 application as an example.

Saturation Factor Defined From The ANSI C Classification


In Figure E-6, the CT terminal voltage increases linearly with the secondary current along the V=ZBxI line
where ZB is the total CT burden (leads plus relays for a particular fault and connection). A terminal
voltage (VT) corresponds to the maximum fault current. This voltage is lower than the maximum voltage
(VC) that the C200 CT can support. Saturation will occur (i.e. ratio error will exceed 10%) for secondary
currents in excess of IFs where the corresponding terminal voltage crosses the accuracy class limit VC
(point C in Figure E-6). We can define a measure of the degree of saturation with the Saturation Factor:
IF
SF =
IFs

By examination of triangles OAB and OCD, the same saturation factor can be expressed as

VT
SF =
VC

E-12 Settings Calculations BE1-CDS


EXCITATION VOLTAGE

CT TERMINAL VOLTAGE
400
C400

R
V10
Vk ZB
V10`
Q
VK`
Ve Rs.100 200 VC
C200
Rs.IF VT
C
VT
A

B D
P 10A O 20 40 IFs 100
IF
EXCITATION CURRENT RELAY CURRENT

Figure E-6. CT Terminal And Excitation Voltages


This first definition of saturation relates the CT terminal voltage to the accuracy class of the CT (effective
class in the case of multi-ratio CTs). It is practical and easy to calculate since it requires only readily
available data. An application is considered reasonably secure when SF is less than 0.5

Saturation Factor Defined From The CT Excitation Curve


The definition of the saturation factor given above appears to be conservative because it assumes the
worst case ratio error. However, a closer look is required since it neglects the CT internal resistance. It
corresponds to an excitation voltage on a curve passing through point Q in Figure 2 at which the excitation
current is 10 amperes (the maximum error allowed by the accuracy class definition). The Rsx100 term
represents the voltage drop across the CT internal resistance. A new SF which takes the internal CT
resistance into account can be defined on the excitation curve, as:

Ve
SF `=
V 10`
Where Ve is the internal excitation voltage (VT+Rs.IF) at the maximum fault current IF and V10` is the
voltage of the curve passing through point Q where the exciting is 10A. This voltage is practically close to
the knee-point voltage VK` which would yield nearly the same (a slightly more conservative) result.
Since in all likelihood, the excitation voltage capability of the CT will be higher ( passing through point R in
Figure E-6 for instance), the saturation factor defined on the excitation curve appears to be lower, i.e. -
more favorable. A detailed analysis can be performed to compare the two saturation factor definitions.

Saturation Factor Definitions Compared


Using the equivalent circuit in Figure E-5 and the ANSI Accuracy Class definition that the CT must be able
to source 20 times nominal current into a standard burden Zc, we now develop a comparative analysis
between the two definitions :
VT Ve
SF = SF `=
VC V 10`

SF =
ZB.IF IF .( ZB + Rs )
SF `=
100.Zc 100.( Zc + Rs )
BE1-CDS Settings Calculations E-13
To compare the two expressions, we take the ratio SF`/SF

SF ` Zc ( ZB + Rs)
= .
SF ZB ( Zc + Rs )
Since this expression varies with the ratio of the actual relay circuit burden (ZB) to the accuracy class
burden (Zc) and the CT internal resistance (Rs), it is best visualized with a surface plot (Figure E-7)
showing simultaneous variations of the parameters. The following example is based on a C200 (Zc=2)
with Rs varying from 0.1 to 0.8 ohms and ZB varying from 0.1 to 2 times ZC ohms. (load angles are
neglected).

0
2
4 3
6
8 2
10
12 1
14
16 0
18 6 8
20 2 4
0

Figure E-7. SF`/SF Ratio


The 0 to 20 axis represents the variations X10 of ZB (20 is 2xZC). The 0 to 8 axis represents the
variations x10 of Rs in ohms. The vertical axis (0 to 4) shows that for ZB values equal to or greater than
the burden value Zc, the two saturation factor equations are nearly identical. The ANSI Accuracy Class
method yields the larger, more conservative result. For low values of ZB and large values of Rs, the
Excitation Curve method yields a larger saturation factor. Since the Excitation Curve method is closely
following the CT characteristics, it may be said that the ANSI Class method which neglects the CT internal
resistance, is too optimistic in this range and should be discarded in favor of the Excitation Curve method.
The absolute values of SF and SF` are compared in Figure E-8 for the particular case where Zc=2,
ZB=0.5, and Rs=0.8 when IF varies from 0 to 100A.

SF and SF` for Zc=2, ZB=0.5, Rs=0.2


0.4

SF
IF

SF' 0.2
IF

0
0 20 40 60 80 100
IF
Figure E-8. Comparing SF And SF`

E-14 Settings Calculations BE1-CDS


Figure E-9 illustrates how a lower Rs value reduces the difference between SF and SF`.

SF and SF` for Zc=2, ZB=0.5, Rs=0.2


0.4

SF
IF

SF' 0.2
IF

0
0 20 40 60 80 100
IF
Figure E-9. Reducing The Difference Between SF And SF’

Conclusion
This analysis shows that the easy to apply SF based on the ANSI Accuracy Class may yield optimistic
results in cases where the CT internal resistance is significant. The Excitation curve method, requiring
more data, yields more accurate results and should be used when the SF is marginal.

BE1-CDS Settings Calculations E-15


Setting Note 4. Slope Setting When CT Saturation Factor (SF) > 0.5
In this case, the maximum slope is set to 60 percent (S = 60). This occurs when poor CTs are used. This
situation should be avoided if possible, since no accurate calculations can be made to verify the security
of the protection.
The effect of this setting is illustrated in the following hypothetical case, where it can be seen that the
slope based on the linear operation may be too low when severe saturation occurs.
20

15
IOP In Multiples Of Tap

60%
S=
10

I OP

5%
S=2

0
0 5 10 15 20 25 30 IMax

IR In Multiples Of Tap
Slope for saturating CTs
Slope for linear CTs
D2857-21.vsd
IOP Vs IR Max 11-09-99

E-16 Settings Calculations BE1-CDS


BASLER ELECTRIC
ROUTE 143, BOX 269
HIGHLAND, IL 62249 USA
http://www.basler.com, info@basler.com
PHONE 618-654-2341 FAX 618-654-2351
INSTRUCTION MANUAL
FOR
BE1-CDS
CURRENT DIFFERENTIAL SYSTEM
MODBUS  PROTOCOL

D2590-07
05-15-97

Publication: 9 3139 00 991


Revision: B 03/2001
INTRODUCTION

This manual provides detailed communications protocol information for the BE1-CDS, Current Differential
System with the Modbus Protocol.

WARNING
TO AVOID PERSONAL INJURY OR EQUIPMENT DAMAGE, ONLY
QUALIFIED PERSONNEL SHOULD PERFORM THE PROCEDURES
PRESENTED IN THIS MANUAL.

CAUTION
MEGGERS AND HIGH POTENTIAL TEST EQUIPMENT SHOULD BE
USED WITH EXTREME CARE. INCORRECT USE OF SUCH
EQUIPMENT COULD DAMAGE COMPONENTS CONTAINED IN THE
DEVICE.

Introduction i
First Printing: November 1999

Printed in USA

© 1999 –2001, Basler Electric Co., Highland, IL 62249

March 2001

CONFIDENTIAL INFORMATION
OF BASLER ELECTRIC COMPANY, HIGHLAND, IL. IT IS LOANED
FOR CONFIDENTIAL USE, SUBJECT TO RETURN ON REQUEST,
AND WITH THE MUTUAL UNDERSTANDING THAT IT WILL NOT BE
USED IN ANY MANNER DETRIMENTAL TO THE INTEREST OF
BASLER ELECTRIC COMPANY.

It is not the intention of this manual to cover all details and variations in
equipment, nor does this manual provide data for every possible
contingency regarding installation or operation. The availability and
design of all features and options are subject to modification without
notice. Should further information be required, contact Basler Electric
Company, Highland, Illinois.

BASLER ELECTRIC
ROUTE 143, BOX 269
HIGHLAND, IL 62249 USA
http://www.basler.com, info@basler.com
PHONE 618-654-2341 FAX 618-654-2351

ii Introduction
TABLE OF CONTENTS
GENERAL INFORMATION..........................................................................................................1
FUNCTIONAL DESCRIPTION ....................................................................................................1
Message Structure..........................................................................................................1
Device Address Field .........................................................................................1
Function Code Field ...........................................................................................2
Data Block Field .................................................................................................2
Error Check Field ...............................................................................................2
Serial Transmission Details.............................................................................................2
Message Framing And Timing Considerations ...............................................................2
Error Handling And Exception Responses......................................................................3
COMMUNICATIONS HARDWARE REQUIREMENTS ...............................................................3
DETAILED MESSAGE QUERY AND RESPONSE .....................................................................3
Read Holding Registers ..................................................................................................3
Query .................................................................................................................3
Response...........................................................................................................4
Return Query Data..........................................................................................................4
Restart Communications Option .....................................................................................4
Listen Only Mode ............................................................................................................5
Preset Multiple Registers ................................................................................................5
Query .................................................................................................................5
Response...........................................................................................................6
Preset Single Register (Write Single Holding Register) ..................................................6
Query .................................................................................................................6
Response...........................................................................................................6
DATA FORMATS .........................................................................................................................7
Floating Point Data Format (FP) ....................................................................................7
Long Integer Data Format (LI) .......................................................................................7
Integer Data Format (INT)...............................................................................................8
Short Integer Data Format (SI) .......................................................................................8
ASCII Character Data Format ( ASC(1) ).......................................................................8
ASCII String Data Format ( ASC(x) ) .............................................................................8
Bit Mapped Data Format ( BM(x) ) ..................................................................................9
CRC Error Check ............................................................................................................9
Session Access Registers ..............................................................................................9
MAPPING BE1-CDS-220 PARAMETERS INTO .........................................................................12
MODICON HOLDING REGISTER ADDRESS SPACE ...............................................................12
General ...........................................................................................................................12
Conventions ....................................................................................................................12
PS ...................................................................................................................................- Effective only w
PW ..................................................................................................................................- Effective for an
REGISTER TABLE – ORDERED BY REGISTER NUMBER.......................................................13
REGISTER DETAILS...................................................................................................................31
ASCII COMMAND VERSUS MODBUS REGISTER CROSS REFERENCE ...........................62

Introduction  Protocol
BE1-CDS With Modbus iii
PRODUCT REVISION HISTORY
The following information provides a historical summary of the changes made to the embedded software
(firmware) of this device. The corresponding revisions made to this instruction manual are also
summarized. This revision history is separated into two categories: Software Changes and Manual
Revisions. All revisions are listed in reverse chronological order.

Modbus™ Program
Firmware Version Change
01.51.00 – Mar 2001 Added Password Security so that the security features may or may not be in
use. With Modbus™, the default for write access security is disabled.
01.12.00 – Apr. 1999 Initial release

The following information provides a historical summary of the changes made to this manual. All revisions
are listed in chronological order.

Revision - Date Change


B – March 2001 Added Password Security features and corrected Floating Point Data Format
text and Table 3.
A – April 2000 Changed the publication number of this manual from 9 3139 00 992 to 9 3139
00 991 to coordinate the manual number with the published bulletin and the
AS-400 data base. (For more information see ECO 8891). Changed the front
cover to show Publication 9 3139 00 991, Revision A. Added Revision
History to the introduction. Changed 47274-77, ASC(8) to 47274-78,
ASC(10).
None – May 2000 Initial release

iv BE1-CDS With Modbus Protocol Introduction


GENERAL INFORMATION

This document describes the Modbus communications protocol employed by BE1-CDS relays, and how to
exchange information with BE1-CDS relays over a Modbus network. The BE1-CDS communicates by
emulating a subset of the Modicon 984 Programmable Controller.

FUNCTIONAL DESCRIPTION

Modbus communications use a master-slave technique in which only the master can initiate a transaction. This
transaction is called a query. When appropriate, a slave (BE1-CDS-220) responds to the query. When a
Modbus master communicates with a slave, information is provided or requested by the master. Information
residing in the BE1-CDS-220 is grouped categorically as follows:

Category
Session Parameters
Global Parameters
Control Parameters (Select Before Operate)
Setting Parameters
Report Parameters
Metering Parameters

All supported data can be read as specified in the register table. Abbreviations are used in the Register Table to
indicate the register type. Register types are:

Read/Write = RW
Read Only = R-

Select Before Operate (SBO) functions are used to change active settings groups and control outputs. There are
four settings groups in the BE1-CDS-220, one of which may be selected as active using SBO commands.

When a slave receives a query, the slave responds by either supplying the requested data to the master or
performing the requested action. A slave device never initiates communications on the Modbus, and will
always generate a response to the query unless certain error conditions occur. The BE1-CDS-220 is designed to
communicate on the Modbus only as a slave device.

A master can query slaves individually or universally. A universal (“broadcast”) query, when allowed, evokes no
response from any slave device. If a query to an individual slave device requests actions unable to be performed
by the slave, the slave response message contains an exception response code defining the error detected.
Exception response codes are quite often enhanced by the information found in the “Error Details” block of
holding registers.

Message Structure

Master initiated queries and BE1-CDS-220 responses share the same message structure. Each message is
comprised of four message fields. They are:

• Device Address (1 byte)


• Function Code (1 byte)
• Data Block (n bytes)
• Error Check field (2 bytes)

Device Address Field

The device address field contains the unique Modbus address of the slave being queried. The addressed
slave repeats the address in the device address field of the response message. This field is 1 byte.

 Protocol
BE1-CDS With Modbus 1
Although Modbus protocol limits a device address from 1 - 247, a BE1-CDS-220 can be assigned a device
address in the range of 1 - 65534. The address is user-selectable at installation, and can be altered during
real-time operation.

Function Code Field

The function code field in the query message defines the action to be taken by the addressed slave. This field is
echoed in the response message, and is altered by setting the most significant bit (MSB) of the field to 1 if the
response is an error response. This field is 1 byte.

The BE1-CDS-220 maps all available data into the Modicon 984 holding register address space (4XXXX) and
supports the following function codes.

• Function 03 (03 hex) - read holding registers


• Function 06 (06 hex) - preset single register (write single holding register)
• Function 08 (08 hex), subfunction 00 - diagnostics: return query data
• Function 08 (08 hex), subfunction 01 - diagnostics: restart communications option
• Function 08 (08 hex), subfunction 04 - diagnostics: force listen only mode
• Function 16 (10 hex) - preset multiple registers, non-broadcast and broadcast
Data Block Field

The query data block contains additional information needed by the slave to perform the requested function. The
response data block contains data collected by the slave for the queried function. An error response will
substitute an exception response code for the data block. The length of this field varies with each query. See
the paragraphs on Register Definitions in this manual for interpretation of data.

Error Check Field

The error check field provides a method for the slave to validate the integrity of the query message contents and
allows the master to confirm the validity of response message contents. This field is 2 bytes.

Serial Transmission Details

A standard Modbus network offers two transmission modes for communication: ASCII or remote terminal unit
(RTU). The BE1-CDS-220 supports only the RTU mode.

Each 8-bit byte in a message contains two 4-bit hexadecimal characters. The message is transmitted in a
continuous stream with the LSB of each byte of data transmitted first. Transmission of each 8-bit data byte
occurs with one start bit and either one or two stop bits. Parity checking is performed, when enabled, and can be
either odd or even. The transmission baud rate is user-selectable, and can be set at installation and altered
during real-time operation. The BE1-CDS-220 Modbus supported baud rates are 1200, 2400, 4800, 9600, and
19200. The factory default baud rate is 9600.

BE1-CDS-220 supports both RS-232-C and RS-485 compatible serial interfaces. Both interfaces are accessible
from the rear panel of the BE1-CDS-220. The RS-232-C interfaces (front and rear) are configured for ASCII
command mode while the RS-485 interface is configured for Modbus communication, when this option is
installed. The tenth character of the relay style number must be ‘1’ for the relay to be configured for Modbus.
Message Framing And Timing Considerations

When receiving a message, the BE1-CDS-220 requires an inter-byte latency of 3.5 character times before
considering the message complete.

Once a valid query is received, the BE1-CDS-220 waits a specified amount of time before responding. This time
delay is set in the remote delay time parameter with the SG-COM ASCII command. This parameter contains a
value from 10 - 200 milliseconds. The default value is 10 milliseconds.

2 BE1-CDS With Modbus Protocol


Table 1 provides the response message transmission time (in seconds) and 3.5 character times (in milliseconds)
for various message lengths and baud rates.

Table 1. Timing Considerations


Baud Rate 3.5 character Time (mSec) Message Tx Time (Sec.)
128 Bytes 256 Bytes
1200 32.1 1.17 2.35
2400 16.04 0.59 1.17
4800 8.021 0.29 0.59
9600 4.0104 0.15 0.29
19200 2.0052 0.07 0.15

Error Handling And Exception Responses

Any query received that contains a non-existent device address, a framing error, or CRC error is ignored. No
response is transmitted. Queries addressed to a BE1-CDS-220 with an unsupported function or illegal values in
the data block result in an error response message with an exception response code. The exception response
codes supported by the BE1-CDS-220 are provided in Table 2.

Table 2. Supported Exception Response Codes


Code Name Meaning
01 Illegal Function The query Function/Subfunction Code is unsupported;
query read of more than 125 registers; query preset of
more than 100 registers
02 Illegal Data Address A register referenced in the data block does not support
queried read/write; query preset of a subset of a numerical
register group.
03 Illegal Data Value A preset register data block contains an incorrect number
of bytes or one or more data values out of range.

COMMUNICATIONS HARDWARE REQUIREMENTS

The BE1-CDS-220 RS-485 physical interface is three positions of a terminal strip with locations for
Send/Receive A (A), Send/Receive B (B) and Signal Ground (C). Refer to the BE1-CDS-220 Instruction Manual
( 9 3139 00 990 ) for further details.

DETAILED MESSAGE QUERY AND RESPONSE

A detailed description of BE1-CDS-220 supported message queries and responses is provided in the following
paragraphs.

Read Holding Registers

Query

This query message requests a register or block of registers to be read. The data block contains the starting
register address and the quantity of registers to be read. A register address of N will read holding register N+1. If
the query is a broadcast (device address = 0), no response message is returned.
 Protocol
BE1-CDS With Modbus 3
Device Address
Function Code = 03 (hex)
Starting Address Hi
Starting Address Lo
No. of Registers Hi
No. of Registers Lo
CRC Hi error check
CRC Lo error check

The number of registers cannot exceed 125 without causing an error response with the exception code for an
illegal function.

Response

The response message contains the data queried. The data block contains the block length in bytes followed by
the data (one Data Hi byte and one Data Lo byte) for each requested register.

Reading an unassigned holding register returns a value of zero.

Device Address
Function Code = 03 (hex)
Byte Count
Data Hi (For each requested register, there is one Data Hi and one Data Lo.)
Data Lo
.
.
Data Hi
Data Lo
CRC Hi error check
CRC Lo error check

Return Query Data

This query contains data to be returned (looped back) in the response. The response and query messages
should be identical. If the query is a broadcast (device address = 0), no response message is returned.
Device Address
Function Code = 08 (hex)
Subfunction Hi = 00 (hex)
Subfunction Lo = 00 (hex)
Data Hi = xx (don't care)
Data Lo = xx (don't care)
CRC Hi error check
CRC Lo error check

Restart Communications Option

This query causes the remote communications function of the BE1-CDS-220 to restart, terminating an active
listen only mode of operation. No effect is made upon primary relay operations. Only the remote
communications function is effected. If the query is a broadcast (device address = 0), no response message is
returned.

If the BE1-CDS-220 receives this query while in the listen only mode, no response message is generated.
Otherwise, a response message identical to the query message is transmitted prior to the communications
restart.

4 BE1-CDS With Modbus Protocol


Device Address
Function Code = 08 (hex)
Subfunction Hi = 00 (hex)
Subfunction Lo = 01 (hex)
Data Hi = xx (don't care)
Data Lo = xx (don't care)
CRC Hi error check
CRC Lo error check

Listen Only Mode

This query forces the addressed BE1-CDS-220 to the listen only mode for Modbus communications, isolating it
from other devices on the network. No responses are returned.

While in the listen only mode, the BE1-CDS-220 continues to monitor all queries. The BE1-CDS-220 does not
respond to any other query until the listen only mode is removed. All write requests with a query to Preset
Multiple Registers (Function Code = 16) are also ignored. When the BE1-CDS-220 receives the restart
communications query, the listen only mode is removed.

Device Address
Function Code = 08 (hex)
Subfunction Hi = 00 (hex)
Subfunction Lo = 04 (hex)
Data Hi = xx (don't care)
Data Lo = xx (don't care)
CRC Hi error check
CRC Lo error check

Preset Multiple Registers

A preset multiple registers query could address multiple registers in one slave or multiple slaves. If the query is a
broadcast (device address = 0), no response message is returned.
Query

A Preset Multiple Register query message requests a register or block of registers to be written. The data block
contains the starting address and the quantity of registers to be written, followed by the Data Block byte count
and data. The BE1-CDS-220 will perform the write when the device address is the same as the BE1-CDS-220’s
remote address or when the device address is 0. A device address is 0 for a broadcast query.

A register address of N will write Holding Register N+1.

Data will cease to be written if any of the following exceptions occur.

• Queries to write to Read Only registers result in an error response with Exception Code of “Illegal Data
Address”.
• Queries attempting to write more than 100 registers cause an error response with Exception Code “Illegal
Function”.
• An incorrect Byte Count will result in an error response with Exception Code of “Illegal Data Value”.
• There are several instances of registers that are grouped together to collectively represent a single
numerical BE1-CDS-220 data value (i.e. - floating point data and 32-bit integer data). A query to write a
subset of such a register group will result in an error response with Exception Code “Illegal Data Address”.
• A query to write a not allowed value (out of range) to a register results in an error response with Exception
Code of “Illegal Data Value”.

Device Address
Function Code = 10 (hex)
Starting Address Hi
Starting Address Lo

 Protocol
BE1-CDS With Modbus 5
No. of Registers Hi
No. of Registers Lo
Byte Count
Data Hi
Data Lo
.
.
Data Hi
Data Lo
CRC Hi error check
CRC Lo error check

Response

The response message echoes the starting address and the number of registers. There is no response message
when the query is a broadcast (device address = 0).

Device Address
Function Code = 10 (hex)
Starting Address Hi
Starting Address Lo
No. of Registers Hi
No. of Registers Lo
CRC Hi Error Check
CRC Lo Error Check

Preset Single Register (Write Single Holding Register)

A Preset Single Register query message requests a single register to be written. The BE1-CDS-220 will perform
the write when the device address is the same as the BE1-CDS-220’s remote address.

Query

Data will cease to be written if any of the following exceptions occur.

• Queries to write to Read Only registers result in an error response with Exception Code of “Illegal Data
Address”.
• A query to write an unallowed value (out of range) to a register results in an error response with
Exception Code of “Illegal Data Value”.
Device Address
Function Code = 06 (hex)
Address Hi
Address Lo
Data Hi
Data Lo
CRC Hi error check
CRC Lo error check

Response

The response message echoes the Query message after the register has been altered.

6 BE1-CDS With Modbus Protocol


DATA FORMATS

BE1-CDS-220 data varies from one to four bytes in length. Single byte data resides in the holding register least-
significant byte with the most-significant byte set to zero. Floating point data and long integer data (each 32-bits in
length) place the two most-significant bytes in the higher holding register address of the associated register pair.

Floating Point Data Format (FP)

The Modbus floating point data format uses two consecutive holding registers to represent a data value. The
first register contains the low-order 16 bits of the following 32 bit format:

• MSB is the sign bit for the floating point value (0 = positive).
• The next 8 bits are the exponent biased by 127 decimal.
• The 23 LSBs comprise the normalized mantissa. The most-significant bit of the mantissa is always
assumed to be 1 and is not explicitly stored, yielding an effective precision of 24 bits.

The value of the floating point number is obtained by multiplying the binary mantissa times two raised to the
power of the unbiased exponent. The assumed bit of the binary mantissa has the value of 1.0, with the
remaining 23 bits providing a fractional value. Table 3 shows the floating point format.

Table 3. Floating Point Format


Sign Exponent + 127 Mantissa
1 Bit 8 Bits 23 Bits

-37 38
The floating point format allows for values ranging from approximately 8.43X10 to 3.38X10 . A floating point
value of all zeroes is the value zero. A floating point value of all ones (not a number) signifies a value currently not
applicable or disabled.

Example: The value 95,800 represented in floating point format is hexadecimal 47BB1C00. This number will read
from two consecutive holding registers as follows:

Holding Register Value


K (Hi Byte) hex 1C
K (Lo Byte) hex 00
K+1 (Hi Byte) hex 47
K+1 (Lo Byte) hex BB

The same byte alignments are required to write.

Long Integer Data Format (LI)

The Modbus long integer data format uses two consecutive holding registers to represent a 32 bit data value.
The first register contains the low-order 16 bits and the second register contains the high-order 16 bits.

Example: The value 95,800 represented in long integer format is hexadecimal 0x00017638. This number will
read from two consecutive holding registers as follows:

Holding Register Value


K (Hi Byte) hex 76
K (Lo Byte) hex 38
K+1 (Hi Byte) hex 00
K+1 (Lo Byte) hex 01

The same byte alignments are required to write.

 Protocol
BE1-CDS With Modbus 7
Integer Data Format (INT)

The Modbus integer data format uses a single holding register to represent a 16 bit data value.

Example: The value 4660 represented in integer format is hexadecimal 0x1234. This number will read from a
holding register as follows:

Holding Register Value


K (Hi Byte) hex 12
K (Lo Byte) hex 34

The same byte alignments are required to write.

Short Integer Data Format (SI)

The Modbus short integer data format uses a single holding register to represent an 8 bit data value. The
holding register high byte will always be zero.

Example: The value 132 represented in short integer format is hexadecimal 0x84. This number will read from a
holding register as follows:

Holding Register Value


K (Hi Byte) hex 00
K (Lo Byte) hex 84

The same byte alignments are required to write.

ASCII Character Data Format ( ASC(1) )

The Modbus ASCII character data format uses a single holding register to represent a single character value.
The holding register high byte will always be zero with the ASCII character code in the low byte.

Example: The character ‘D’ represented in ASCII character format is hexadecimal 44. This number will read
from a holding register as follows:

Holding Register Value


K (Hi Byte) hex 00
K (Lo Byte) hex 44

The same byte alignments are required to write.

ASCII String Data Format ( ASC(x) )

The Modbus ASCII string data format uses one or more holding registers to represent a sequence, or string, of
character values. If the string contains a single character, the holding register high byte will contain the ASCII
character code and the low byte will be zero.

Example: The string “PASSWORD” represented in ASCII string format will read as follows:

Holding Register Value


K (Hi Byte) ‘P’
K (Lo Byte) ‘A’
K+1 (Hi Byte) ‘S’
K+1 (Lo Byte) ‘S’
K+2 (Hi Byte) ‘W’
K+2 (Lo Byte) ‘O’
K+3 (Hi Byte) ‘R’
K+3 (Lo Byte) ‘D’
Example: If the above string is changed to “P”, the new string will read as follows:
8 BE1-CDS With Modbus Protocol
Holding Register Value
K (Hi Byte) ‘P’
K (Lo Byte) hex 00
K+1 (Hi Byte) hex 00
K+1 (Lo Byte) hex 00
K+2 (Hi Byte) hex 00
K+2 (Lo Byte) hex 00
K+3 (Hi Byte) hex 00
K+3 (Lo Byte) hex 00

The same byte alignments are required to write.

Bit Mapped Data Format ( BM(x) )

The bit mapped data format uses two or more holding registers to represent a sequence of bit values. The
Modbus Bit Map data format can represent an 8 bit, 16 bit, 32 bit or 64 bit value.

Example: The Bit Map value of the hexidemal number 0x123456789ABCDEF0 using a BM64 format
will read as follows:

Holding Register Value


K (Hi Byte) 0x12
K (Lo Byte) 0x34
K+1 (Hi Byte) 0x56
K+1 (Lo Byte) 0x78
K+2 (Hi Byte) 0x9A
K+2 (Lo Byte) 0xBC
K+3 (Hi Byte) 0xDE
K+3 (Lo Byte) 0xF0

CRC Error Check

This field contains a two-byte CRC value for transmission error detection. The master first calculates the CRC
and appends it to the query message. The BE1-CDS-220 recalculates the CRC value for the received query and
performs a comparison to the query CRC value to determine if a transmission error has occurred. If so, no
response message is generated. If no transmission error has occurred, the slave calculates a new CRC value for
the response message and appends it to the message for transmission.

The CRC calculation is performed using all bytes of the device address, function code and data block fields. A
16-bit CRC-register is initialized to all 1's. Then each eight-bit byte of the message is used in the following
algorithm:
First, exclusive-OR the message byte with the low-order byte of the CRC-register. The result, stored in the
CRC-register, will then be right-shifted eight times. The CRC-register MSB is zero-filled with each shift. After
each shift, the CRC-register LSB is examined. If the LSB IS a 1, the CRC-register is then exclusive-ORed with
the fixed polynomial value A001 (hex) prior to the next shift. Once all bytes of the message have undergone the
above algorithm, the CRC-register will contain the message CRC value to be placed in the error check field.

Session Access Registers

The ACCESS REQUEST and the EXIT registers are used to access and release write privileges while
changing relay settings, resetting report registers, or using control commands through the Modbus port.
This feature is important because it prevents changes from being made concurrently from two areas. For
example, a user cannot make changes from COM0 at the same time a remote user is making changes via
Modbus from COM2.
Changing the settings through the Modbus port requires that the operator write to the ACCESS REQUEST
register to obtain programming access. This must follow writing the ACCESS PASSWORD register(s) with a
BE1-CDS With Modbus  Protocol 9
password to obtain access to change settings associated with the password. Different passwords give the
ability or access to perform different operations. The relay will deny access if an invalid password is entered
or if another user has already been granted programming access through another serial port or at the front
panel. Only one user can have access at any one time.

If no password protection is used, it is still necessary to obtain access in order to protect against accidental
changes. If password protection is disabled, then writing the ACCESS REQUEST register will be accepted in
place of a password. The relay will transmit a valid response message if the access query was received and
executed. The relay will respond with an error message if the access query could not be executed.

Changing settings through a Modbus communication port consists of the following sequence :

Step 1. Preset Multiple Registers query to ACCESS PASSWORD register(s) to specify password.
Step 2. Preset Multiple Registers query to ACCESS REQUEST register to access write privileges.
Step 3. Preset Multiple Registers queries to change the current settings.
Step 4. Preset Multiple Registers query to EXIT register to clear access and save.

Changes are not made to the working settings but to a scratch-pad copy of the settings. After the change(s)
are made, the new data will be copied to the working settings and saved to non-volatile memory when the
EXIT register is written with a ‘Y’. It is important to make all changes to relay parameters before writing the
EXIT register. This prevents a partial or incomplete protection scheme from being implemented.

Template Registers

The BE1-CDS-220 uses three templates. A template is a block of holding registers to which the user assigns one
of a number of similar groups of parameters. Templates are used for settings groups, fault summaries and report
generation.

The BE1-CDS-220 has four settings groups. The GRP template is assigned the parameters of a settings group.
Therefore, before reading or writing settings group values, a user must first specify which settings group is to
be associated with the template. This is accomplished by writing the desired settings group number (0-3) into
the SETTINGS GROUP SELECTION Template holding register.

The BE1-CDS-220 stores up to 16 faults (with Load Profile option, 32 faults). Each fault is accessed by its fault
number which ranges from 1 to 255. The FLT template is assigned the parameters of a particular fault
occurrence. Therefore, before reading fault summary values, a user must first specify which fault number is to
be associated with the template. This is accomplished by writing the desired fault number (1-255) into the
FAULT SELECTION Template holding register.

The BE1-CDS-220 generates 10 ASCII reports. The RPT template is assigned the text of a report. Therefore,
before reading report text, a user must first specify which report is to be associated with the template. This is
accomplished by writing the desired report number into the REPORT SELECTION Template holding register
along with the associated report identifier, if any, into the REPORT FOCUS Template holding register.

Fault Summary Registers

The user can enter any fault number (1 – 255) into the FAULT SELECTION Template holding register to
associate summary parameters for that fault number with the FLT Template. The Fault Template Status
register (47513) indicates whether or not that fault number specifies a recent fault (one of 12 stored faults). If
so, the Fault Template Status register value is the fault number; otherwise, it is zero and all FLT template
values will read zero.

The Fault Indicator register (47512) value is the fault number (1 – 255) of the most recent fault. The user may
construct his front-end GUI to link this register value into the FAULT SELECTION Template holding register,
thereby automatically associating the FLT template with the most recent fault occurrence.
Report Generation Registers

10 BE1-CDS With Modbus Protocol


The BE1-CDS-220 generates numerous ASCII reports available via serial commands. Several of these
reports are available intact via the Modbus communication port. The desired report is first specified by
writing the REPORT SELECTION holding register. If the report requires a number to be specified, such as a
fault number or number of events, that number is written into the REPORT FOCUS holding register. The
report is then available via the RPT template. The report can be read from 1 to 125 registers at a time, with
each register containing 2 ASCII characters of information. The report read queries can be interspersed
among other query types. The RPT template is continually re-read until the report has completed. Once the
report is complete, reading from the RPT template will continually return the ASCII character code of 127 (“7F”
hexadecimal). The report cannot be re-read or another report read until the REPORT SELECTION holding
register is re-written.

Contiguous Poll Block Registers

The user may allocate up to 125 holding registers to the Contiguous Poll Block (49875-999). This allocation
allows dispersed registers which are frequently read to be polled via a single read query. A register is
assigned to a position in the Poll Block by writing its address value into the corresponding position in the
Contiguous Poll Block Assignments registers (40746-870). Writing a zero value leaves that Poll Block position
unassigned. Once assignments are made, the values of the assigned registers may be read by polling the
Contiguous Poll Block. Polling an unassigned position will return a value of zero.

For example, if you wanted to continuously monitor the Date (47364), Time (47365-66), Fault Indicator
(47512) and Breaker Status (47388) Holding Registers, you would first configure the Contiguous Poll Block
Registers by writing the desired register address values 7364, 7365, 7366, 7512 and 7388 into the
Contiguous Poll Block Assignment registers 40746 thru 40750, respectively. You may now begin monitoring
the specified registers by reading the first 5 locations in the Contiguous Poll Block; ie, reading register
49875 for the Date (as specified in it’s corresponding assignment register 40746), reading register
49876 and 77 for the Time (as specified in their corresponding assignment registers 40747 and 48),
reading register 49878 for the Fault Indicator (as specified in it’s corresponding assignment register
40749), and reading register 49879 for the Breaker Status (as specified in it’s corresponding
assignment register 40750).

Exception Code Enhancement Registers

When a BE1-CDS-220 responds to a Preset Multiple Register query with an error response message,
additional information detailing the cause of the error may be available in the ERROR DETAILS block of
holding registers (49835-54). The information is in ASCII format and available by reading the message string
from the ERROR DETAILS block. The message remains available until the next Preset Multiple Register
query is executed unless that query is to the FAULT SELECTION Template holding register. Since this
register can be written automatically and randomly in time, the ERROR DETAILS block will not be updated.

The ERROR DETAILS block will also contain the exit status following a Preset Multiple Register query to the
EXIT (40001) register. You may clear the ERROR DETAILS message at any time without affecting system
operation by sending a Preset Multiple Register query to any unassigned holding register.

 Protocol
BE1-CDS With Modbus 11
MAPPING BE1-CDS-220 PARAMETERS INTO
MODICON HOLDING REGISTER ADDRESS SPACE

General

Parameters are mapped into the holding register address space (40001 – 49999) in blocks according to access
type.

Any Holding Register not listed in the Register Table is an unassigned Holding Register. A value of zero
always results when reading an unassigned Holding Register. Writes to unassigned Holding Registers are
legal, but no action will be taken (the write is ignored).

Conventions

The Data Format column uses the following abbreviations.

ASC(x) - ASCII string, where x = the maximum defined string length


BM(x) - Bit-map, where x = the number of related bits
FP - Floating point
INT - Integer (16-bit integer)
LI - Long Integer (32-bit integer)
SI - Short Integer (8-bit integer)

The Notes column uses the following abbreviations:

GRP - Group Template Member


FLT - Fault Template Member
RPT - Report Template Member
NS - Not Supported
TS - Time Stamp format: MSEC of the day (0 to 86,400,000 ms) and DAYs since 01/01/1984.
PS - Effective only when the Password Security parameter is enabled. See REGISTER DETAILS for
Password Security holding register 40989.
PW - Effective for any communication port active with ASCII protocol and for the modbus port (COM 2)
when Password Security is enabled.

12 BE1-CDS With Modbus Protocol


REGISTER TABLE – ORDERED BY REGISTER NUMBER

Holding Read/Write Data


Register Parameter Supported Format Notes

Session Parameters

40001 Exit RW ASC(1) PS

40002-05 Access Password RW ASC(8) PS


40006 Access Request RW BM(16) PS

Template Parameters

40036 Settings Group Selection RW SI


40038 Fault Selection RW SI
40039 Report Selection RW SI
40040 Report Focus RW INT

Global Parameters

40080-83 Global Password RW ASC(8) PW


40084 Global Path RW BM(8) PW

40085-88 Setting Password RW ASC(8) PW


40089 Setting Path RW BM(8) PW

40090-93 Control Password RW ASC(8) PW


40094 Control Path RW BM(8) PW

40095-98 Report Password RW ASC(8) PW


40099 Report Path RW BM(8) PW

Control Parameters

40117 Select Group RW ASC(1)


40118 Operate Group RW ASC(1)

40119 Select Virtual Selector Switch 43 RW ASC(1)


40120 Operate Virtual Selector Switch 43 RW ASC(1)
40121 Select Virtual Selector Switch 143 RW ASC(1)
40122 Operate Virtual Selector Switch 143 RW ASC(1)
40123 Select Virtual Selector Switch 243 RW ASC(1)
40124 Operate Virtual Selector Switch 243 RW ASC(1)
40125 Select Virtual Selector Switch 343 RW ASC(1)
40126 Operate Virtual Selector Switch 343 RW ASC(1)
40127 Select Virtual Selector Switch 443 RW ASC(1)
40128 Operate Virtual Selector Switch 443 RW ASC(1)
40129 Select Virtual Selector Switch 543 RW ASC(1)
40130 Operate Virtual Selector Switch 543 RW ASC(1)
40131 Select Virtual Selector Switch 643 RW ASC(1)
40132 Operate Virtual Selector Switch 643 RW ASC(1)
40133 Select Virtual Selector Switch 743 RW ASC(1)
40134 Operate Virtual Selector Switch 743 RW ASC(1)

 Protocol
BE1-CDS With Modbus 13
Holding Read/Write Data
Register Parameter Supported Format Notes

40135 Select 101 Virtual Breaker Control Switch RW ASC(1)


40136 Operate 101 Virtual Breaker Control Switch RW ASC(1)

40137 Select All Outputs RW ASC(1)


40138 Operate All Outputs RW ASC(1)

40139 Select Output A RW ASC(1)


40140 Operate Output A RW ASC(1)
40141 Select Output 1 RW ASC(1)
40142 Operate Output 1 RW ASC(1)
40143 Select Output 2 RW ASC(1)
40144 Operate Output 2 RW ASC(1)
40145 Select Output 3 RW ASC(1)
40146 Operate Output 3 RW ASC(1)
40147 Select Output 4 RW ASC(1)
40148 Operate Output 4 RW ASC(1)
40149 Select Output 5 RW ASC(1)
40150 Operate Output 5 RW ASC(1)
40151 Select Output 6 RW ASC(1)
40152 Operate Output 6 RW ASC(1)

Group Setting Parameters

The following is the Group Template (GRP)

40269-70 50TP Pickup RW FP GRP


40271-72 50TP Time Delay RW LI GRP
40273-74 50TN Pickup RW FP GRP
40275-76 50TN Time Delay RW LI GRP
40277-78 50TQ Pickup RW FP GRP
40279-80 50TQ Time Delay RW LI GRP

40281-82 150TP Pickup RW FP GRP


40283-84 150TP Time Delay RW LI GRP
40285-86 150TN Pickup RW FP GRP
40287-88 150TN Time Delay RW LI GRP
40289-90 150TQ Pickup RW FP GRP
40291-92 150TQ Time Delay RW LI GRP

40293-94 250TP Pickup RW FP GRP


40295-96 250TP Time Delay RW LI GRP
40297-98 250TN Pickup RW FP GRP
40299-300 250TN Time Delay RW LI GRP
40301-02 250TQ Pickup RW FP GRP
40303-04 250TQ Time Delay RW LI GRP

40305-06 51P Pickup RW FP GRP


40307-08 51P Time Dial RW FP GRP
40309-10 51P Curve Type RW ASC(3) GRP

40311-12 51N Pickup RW FP GRP


40313-14 51N Time Dial RW FP GRP
40315-16 51N Curve Type RW ASC(3) GRP
40317-18 51Q Pickup RW FP GRP
40319-20 51Q Time Dial RW FP GRP
40321-22 51Q Curve Type RW ASC(3) GRP

14 BE1-CDS With Modbus Protocol


Holding Read/Write Data
Register Parameter Supported Format Notes

40323-24 151P Pickup RW FP GRP


40325-26 151P Time Dial RW FP GRP
40327-28 151P Curve Type RW ASC(3) GRP

40329-30 151N Pickup RW FP GRP


40331-32 151N Time Dial RW FP GRP
40333-34 151N Curve Type RW ASC(3) GRP

40335-36 151Q Pickup RW FP GRP


40337-38 151Q Time Dial RW FP GRP
40339-40 151Q Curve Type RW ASC(3) GRP

40341-42 251P Pickup RW FP GRP


40343-44 251P Time Dial RW FP GRP
40345-46 251P Curve Type RW ASC(3) GRP

40347-48 251N Pickup RW FP GRP


40349-50 251N Time Dial RW FP GRP
40351-52 251N Curve Type RW ASC(3) GRP

40353-54 251Q Pickup RW FP GRP


40355-56 251Q Time Dial RW FP GRP
40357-58 251Q Curve Type RW ASC(3) GRP

40359-60 62 Time Delay 1 RW LI GRP


40361-62 62 Time Delay 2 RW LI GRP
40363-64 162 Time Delay 1 RW LI GRP
40365-66 162 Time Delay 2 RW LI GRP

40375-76 87T Minimum Pickup RW FP GRP


40377 87T Restraint Slope RW INT GRP
nd
40378-79 87T 2 Harmonic Threshold RW FP GRP
40380-81 87T 5th Harmonic Threshold RW FP GRP
40382 87T Unrestrained Pickup RW INT GRP
nd
40383 87T 2 Harmonic Sharing RW INT GRP

40384-85 87ND CT CKT G Tap R- FP GRP


40386-87 87ND Calculated Neutral Tap R- FP GRP
40388-89 87ND Minimum Pickup RW FP GRP
40390 87ND Restraint Slope RW INT GRP
40391 87ND Restraint Time Delay RW INT GRP

40392-93 Transformer Mega-Volt-Amps (MVA) Rating RW FP GRP


40394-95 87T CT CKT #1 Tap RW FP GRP
40396-97 Transformer Tap 1 Kilo-Volt (KV) Rating RW FP GRP
40398-99 87T CT CKT #2 Tap RW FP GRP
40400-01 Transformer Tap 2 Kilo-Volt (KV) Rating RW FP GRP

Global Setting Parameters

40606-07 Breaker Fail Time Delay RW LI

40608-09 Programmable 51 Curve Constant A RW FP


40610-11 Programmable 51 Curve Constant B RW FP
40612-13 Programmable 51 Curve Constant C RW FP
40614-15 Programmable 51 Curve Constant N RW FP
40616-17 Programmable 51 Curve Constant R RW FP

 Protocol
BE1-CDS With Modbus 15
Holding Read/Write Data
Register Parameter Supported Format Notes

40618 Input 1 Contact Recognition Time Delay RW SI


40619 Input 1 Contact Debounce Time Delay RW SI
40620 Input 2 Contact Recognition Time Delay RW SI
40621 Input 2 Contact Debounce Time Delay RW SI
40622 Input 3 Contact Recognition Time Delay RW SI
40623 Input 3 Contact Debounce Time Delay RW SI
40624 Input 4 Contact Recognition Time Delay RW SI
40625 Input 4 Contact Debounce Time Delay RW SI
40626 Input 5 Contact Recognition Time Delay RW SI
40627 Input 5 Contact Debounce Time Delay RW SI
40628 Input 6 Contact Recognition Time Delay RW SI
40629 Input 6 Contact Debounce Time Delay RW SI
40630 Input 7 Contact Recognition Time Delay RW SI
40631 Input 7 Contact Debounce Time Delay RW SI
40632 Input 8 Contact Recognition Time Delay RW SI
40633 Input 8 Contact Debounce Time Delay RW SI

40746-870 Contiguous Poll Block Assignments RW INT

40871 Setting Group Control On Time RW INT

40872 Setting Group 1 Automatic Control Switch Time RW SI


40873 Setting Group 1 Automatic Control Switch Level RW SI
40874 Setting Group 1 Automatic Control Return Time RW SI
40875 Setting Group 1 Automatic Control Return Level RW SI
40876 Setting Group 1 Tracking Element RW INT

40877 Setting Group 2 Automatic Control Switch Time RW SI


40878 Setting Group 2 Automatic Control Switch Level RW SI
40879 Setting Group 2 Automatic Control Return Time RW SI
40880 Setting Group 2 Automatic Control Return Level RW SI
40881 Setting Group 2 Tracking Element RW INT

40882 Setting Group 3 Automatic Control Switch Time RW SI


40883 Setting Group 3 Automatic Control Switch Level RW SI
40884 Setting Group 3 Automatic Control Return Time RW SI
40885 Setting Group 3 Automatic Control Return Level RW SI
40886 Setting Group 3 Tracking Element RW INT

Serial Port Setting Parameters

40962 Serial Port 0 Baud Rate RW INT


40964 Serial Port 0 Software Flow Control RW SI
40965 Serial Port 0 Page Length RW SI
40966 Serial Port 0 Acknowledgement Format RW SI

40971 Serial Port 1 Baud Rate RW INT


40972 Serial Port 1 Relay Address RW INT
40973 Serial Port 1 Software Flow Control RW SI
40974 Serial Port 1 Page Length RW SI
40975 Serial Port 1 Acknowledgement Format RW SI

40980 Serial Port 2 Baud Rate RW INT


40981 Serial Port 2 Relay Address RW INT
40986 Serial Port 2 Modbus Parity RW SI
40987 Serial Port 2 Modbus Remote Delay RW SI
40988 Serial Port 2 Modbus Stop Bits RW SI
40989 Password Security RW SI
16 BE1-CDS With Modbus Protocol
Holding Read/Write Data
Register Parameter Supported Format Notes

System Data Setting Parameters

41019 System Frequency RW SI


41020 Phase Rotation RW SI
41021 Phase CT Ratio, CT CKT #1 RW INT
41022 Ground CT Ratio RW INT
41023 Phase CT Ratio, CT CKT #2 RW INT

41025 CT Connection, CT CKT #1 RW INT


41026 CT Connection, CT CKT #2 RW INT

41028 TX Connection, CT CKT #1 RW INT


41029 TX Connection, CT CKT #2 RW INT

41031 Ground Source, CT CKT #1 RW INT


41032 Ground Source, CT CKT #2 RW INT

Breaker Duty Setting Parameters

41092 Breaker Duty Type RW SI


41093-94 Maximum Breaker Duty RW FP
41095 Breaker Duty CT CKT Number RW SI

41096 Programmable Breaker Alarm #1 Mode RW INT


41097-98 Programmable Breaker Alarm #1 Limit RW FP

41099 Programmable Breaker Alarm #2 Mode RW INT


41100-01 Programmable Breaker Alarm #2 Limit RW FP

41102 Programmable Breaker Alarm #3 Mode RW INT


41103-04 Programmable Breaker Alarm #3 Limit RW FP

41110-15 Breaker Block Logic Mask RW BM(96)


41118-23 Breaker Block Logic Term RW BM(96)

41126-31 Breaker Close Logic Mask RW BM(96)


41134-39 Breaker Close Logic Term RW BM(96)

41142-49 Breaker Label RW ASC(16)

Transformer Duty Setting Parameters

41184 Transformer Duty Mode RW SI


41185-86 Maximum Transformer Duty RW FP
41187 Transformer Duty CT CKT Number RW SI

41188 Programmable Transformer Alarm #1 Mode RW INT


41189-90 Programmable Transformer Alarm #1 Limit RW FP

41191 Programmable Transformer Alarm #2 Mode RW INT


41192-93 Programmable Transformer Alarm #2 Limit RW FP

41194 Programmable Transformer Alarm #3 Mode RW INT


41195-96 Programmable Transformer Alarm #3 Limit RW FP

41197-202 Transformer Block Logic Mask RW BM(96)

 Protocol
BE1-CDS With Modbus 17
Holding Read/Write Data
Register Parameter Supported Format Notes

41205-10 Transformer Block Logic Term RW BM(96)

Relay Data Setting Parameters

41259-60 Phase Demand Alarm Level RW FP


41261-62 Neutral Demand Alarm Level RW FP
41263-64 Negative Sequence Demand Alarm Level RW FP

41265-66 Major Alarm Mask RW BM(32)


41267-68 Minor Alarm Mask RW BM(32)
41269-70 Logic Alarm Mask RW BM(32)
41271 87T Differential Alarm RW INT

41272 Clock Format – Date RW ASC(1)


41273 Clock Format – Time RW SI
41274 Clock Format – Daylight Savings RW SI

41275 Phase Demand Interval RW SI


41276 Neutral Demand Interval RW SI
41277 Negative Sequence Demand Interval RW SI

41278 Phase Demand Calculation Method RW ASC(1)


41279 Neutral Demand Calculation Method RW ASC(1)
41280 Negative Sequence Demand Calculation Method RW ASC(1)

41281 Phase Demand CT CKT Number RW ASC(1)


41282 Neutral Demand CT CKT Number RW ASC(1)
41283 Negative Sequence Demand CT CKT Number RW ASC(1)

41284 Output Hold Mask RW BM(8)

41286 Load Profile Interval RW SI

41287-90 Target Mask RW BM(64)

41291-94 Programmable Screen #1 RW ASC(7)


41295-98 Programmable Screen #2 RW ASC(7)
41299-302 Programmable Screen #3 RW ASC(7)
41303-06 Programmable Screen #4 RW ASC(7)
41307-10 Programmable Screen #5 RW ASC(7)
41311-14 Programmable Screen #6 RW ASC(7)
41315-18 Programmable Screen #7 RW ASC(7)
41319-22 Programmable Screen #8 RW ASC(7)
41323-26 Programmable Screen #9 RW ASC(7)
41327-30 Programmable Screen #10 RW ASC(7)
41331-34 Programmable Screen #11 RW ASC(7)
41335-38 Programmable Screen #12 RW ASC(7)
41339-42 Programmable Screen #13 RW ASC(7)
41343-46 Programmable Screen #14 RW ASC(7)
41347-50 Programmable Screen #15 RW ASC(7)
41351-54 Programmable Screen #16 RW ASC(7)

41355-60 Fault Record Trigger (Trip) Logic Mask RW BM(96)


41363-68 Fault Record Trigger (Trip) Logic Term RW BM(96)

41371-76 Fault Record Trigger (Pickup) Logic Mask RW BM(96)


41379-84 Fault Record Trigger (Pickup) Logic Term RW BM(96)
18 BE1-CDS With Modbus Protocol
Holding Read/Write Data
Register Parameter Supported Format Notes

41387-92 Fault Record Trigger (Logic) Logic Mask RW BM(96)


41395-400 Fault Record Trigger (Logic) Logic Term RW BM(96)

41403-08 Reset Target Logic Mask RW BM(96)


41411-16 Reset Target Logic Term RW BM(96)

41419-24 Reset Alarm Logic Mask RW BM(96)


41427-32 Reset Alarm Logic Term RW BM(96)

Custom Logic Setting Parameters

41465-68 User Custom Logic Name RW ASC(8)


41469-72 Current Active Logic Scheme RW ASC(8)
41473-76 Custom Logic Name R- ASC(8)
41477-80 Standard Logic #1 Name R- ASC(8)
41481-84 Standard Logic #2 Name R- ASC(8)
41485-88 Standard Logic #3 Name R- ASC(8)
41489-92 Standard Logic #4 Name R- ASC(8)
41493-96 Standard Logic #5 Name R- ASC(8)
41497-500 Standard Logic #6 Name R- ASC(8)
41501-04 Standard Logic #7 Name R- ASC(8)

41505 Programmable 50TP Logic Mode RW INT


41506-11 Programmable 50TP Block Logic Mask RW BM(96)
41514-19 Programmable 50TP Block Logic Term RW BM(96)

41522 Programmable 50TN Logic Mode RW INT


41523-28 Programmable 50TN Block Logic Mask RW BM(96)
41531-36 Programmable 50TN Block Logic Term RW BM(96)

41539 Programmable 50TQ Logic Mode RW INT


41540-45 Programmable 50TQ Block Logic Mask RW BM(96)
41548-53 Programmable 50TQ Block Logic Term RW BM(96)

41556 Programmable 150TP Logic Mode RW INT


41557-62 Programmable 150TP Block Logic Mask RW BM(96)
41565-70 Programmable 150TP Block Logic Term RW BM(96)

41573 Programmable 150TN Logic Mode RW INT


41574-79 Programmable 150TN Block Logic Mask RW BM(96)
41582-87 Programmable 150TN Block Logic Term RW BM(96)

41590 Programmable 150TQ Logic Mode RW INT


41591-96 Programmable 150TQ Block Logic Mask RW BM(96)
41599-604 Programmable 150TQ Block Logic Term RW BM(96)

41607 Programmable 250TP Logic Mode RW INT


41608-13 Programmable 250TP Block Logic Mask RW BM(96)
41616-21 Programmable 250TP Block Logic Term RW BM(96)
41624 Programmable 250TN Logic Mode RW INT
41625-30 Programmable 250TN Block Logic Mask RW BM(96)
41633-38 Programmable 250TN Block Logic Term RW BM(96)

41641 Programmable 250TQ Logic Mode RW INT


41642-47 Programmable 250TQ Block Logic Mask RW BM(96)
41650-55 Programmable 250TQ Block Logic Term RW BM(96)
41658 Programmable Breaker Fail Logic Mode RW INT

 Protocol
BE1-CDS With Modbus 19
Holding Read/Write Data
Register Parameter Supported Format Notes

41659-64 Programmable Breaker Fail Initiate Logic Mask RW BM(96)


41667-72 Programmable Breaker Fail Initiate Logic Term RW BM(96)
41675-80 Programmable Breaker Fail Block Logic Mask RW BM(96)
41683-88 Programmable Breaker Fail Block Logic Term RW BM(96)

41691 Programmable 51P Logic Mode RW INT


41692-97 Programmable 51P Block Logic Mask RW BM(96)
41700-05 Programmable 51P Block Logic Term RW BM(96)

41708 Programmable 51N Logic Mode RW INT


41709-14 Programmable 51N Block Logic Mask RW BM(96)
41717-22 Programmable 51N Block Logic Term RW BM(96)

41725 Programmable 51Q Logic Mode RW INT


41726-31 Programmable 51Q Block Logic Mask RW BM(96)
41734-39 Programmable 51Q Block Logic Term RW BM(96)

41742 Programmable 151P Logic Mode RW INT


41743-48 Programmable 151P Block Logic Mask RW BM(96)
41751-56 Programmable 151P Block Logic Term RW BM(96)

41759 Programmable 151N Logic Mode RW INT


41760-65 Programmable 151N Block Logic Mask RW BM(96)
41768-73 Programmable 151N Block Logic Term RW BM(96)

41776 Programmable 151Q Logic Mode RW INT


41777-82 Programmable 151Q Block Logic Mask RW BM(96)
41785-90 Programmable 151Q Block Logic Term RW BM(96)

41793 Programmable 251P Logic Mode RW INT


41794-99 Programmable 251P Block Logic Mask RW BM(96)
41802-07 Programmable 251P Block Logic Term RW BM(96)

41810 Programmable 251N Logic Mode RW INT


41811-16 Programmable 251N Block Logic Mask RW BM(96)
41819-24 Programmable 251N Block Logic Term RW BM(96)

41827 Programmable 251Q Logic Mode RW INT


41828-33 Programmable 251Q Block Logic Mask RW BM(96)
41836-41 Programmable 251Q Block Logic Term RW BM(96)

41844 Programmable 62 Timer Logic Mode RW INT


41845-50 Programmable 62 Timer Start Logic Mask RW BM(96)
41853-58 Programmable 62 Timer Start Logic Term RW BM(96)
41861-66 Programmable 62 Timer Block Logic Mask RW BM(96)
41869-74 Programmable 62 Timer Block Logic Term RW BM(96)

41877 Programmable 162 Timer Logic Mode RW INT


41878-83 Programmable 162 Timer Start Logic Mask RW BM(96)
41886-91 Programmable 162 Timer Start Logic Term RW BM(96)
41894-99 Programmable 162 Timer Block Logic Mask RW BM(96)
41902-07 Programmable 162 Timer Block Logic Term RW BM(96)

41976 Programmable 87 Differential Logic Mode RW INT


41977-82 Programmable 87 Differential Block Logic Mask RW BM(96)
41985-90 Programmable 87 Differential Block Logic Term RW BM(96)
41993 Programmable 87ND Differential Logic Mode RW INT
41994-99 Programmable 87ND Differential Block Logic Mask RW BM(96)
20 BE1-CDS With Modbus Protocol
Holding Read/Write Data
Register Parameter Supported Format Notes

42002-07 Programmable 87ND Differential Block Logic Term RW BM(96)

42010 Programmable Settings Group Logic Mode RW INT


42011-16 Programmable Settings Group Block Logic Mask RW BM(96)
42019-24 Programmable Settings Group Block Logic Term RW BM(96)

42027-32 Programmable Settings Group0 Select Logic Mask RW BM(96)


42035-40 Programmable Settings Group0 Select Logic Term RW BM(96)

42043-48 Programmable Settings Group1 Select Logic Mask RW BM(96)


42051-56 Programmable Settings Group1 Select Logic Term RW BM(96)

42059-64 Programmable Settings Group2 Select Logic Mask RW BM(96)


42067-72 Programmable Settings Group2 Select Logic Term RW BM(96)

42075-80 Programmable Settings Group3 Select Logic Mask RW BM(96)


42083-88 Programmable Settings Group3 Select Logic Term RW BM(96)

42091 Programmable 43 Virtual Switch Logic Mode RW INT


42092 Programmable 143 Virtual Switch Logic Mode RW INT
42093 Programmable 243 Virtual Switch Logic Mode RW INT
42094 Programmable 343 Virtual Switch Logic Mode RW INT
42095 Programmable 443 Virtual Switch Logic Mode RW INT
42096 Programmable 543 Virtual Switch Logic Mode RW INT
42097 Programmable 643 Virtual Switch Logic Mode RW INT
42098 Programmable 743 Virtual Switch Logic Mode RW INT

42099 Programmable 101 Virtual Breaker Control Logic Mode RW INT

42100 Programmable Circuit Monitor Logic Mode RW INT


42101-06 Programmable Circuit Monitor Monitor Logic Mask RW BM(96)
42109-14 Programmable Circuit Monitor Monitor Logic Term RW BM(96)
42117-22 Programmable Circuit Monitor Status Logic Mask RW BM(96)
42125-30 Programmable Circuit Monitor Status Logic Term RW BM(96)

42133 Programmable Virtual Output A Term Count RW SI


42134-39 Programmable Virtual Output A Logic Mask 1 RW BM(96)
42142-47 Programmable Virtual Output A Logic Term 1 RW BM(96)
42150-55 Programmable Virtual Output A Logic Mask 2 RW BM(96)
42158-63 Programmable Virtual Output A Logic Term 2 RW BM(96)
42166-71 Programmable Virtual Output A Logic Mask 3 RW BM(96)
42174-79 Programmable Virtual Output A Logic Term 3 RW BM(96)
42182-87 Programmable Virtual Output A Logic Mask 4 RW BM(96)
42190-95 Programmable Virtual Output A Logic Term 4 RW BM(96)

42198 Programmable Virtual Output 1 Term Count RW SI


42199-204 Programmable Virtual Output 1 Logic Mask 1 RW BM(96)
42207-12 Programmable Virtual Output 1 Logic Term 1 RW BM(96)
42215-20 Programmable Virtual Output 1 Logic Mask 2 RW BM(96)
42223-28 Programmable Virtual Output 1 Logic Term 2 RW BM(96)
42231-36 Programmable Virtual Output 1 Logic Mask 3 RW BM(96)
42239-44 Programmable Virtual Output 1 Logic Term 3 RW BM(96)
42247-52 Programmable Virtual Output 1 Logic Mask 4 RW BM(96)
42255-60 Programmable Virtual Output 1 Logic Term 4 RW BM(96)

42263 Programmable Virtual Output 2 Term Count RW SI


42264-69 Programmable Virtual Output 2 Logic Mask 1 RW BM(96)
42272-77 Programmable Virtual Output 2 Logic Term 1 RW BM(96)
 Protocol
BE1-CDS With Modbus 21
Holding Read/Write Data
Register Parameter Supported Format Notes

42280-85 Programmable Virtual Output 2 Logic Mask 2 RW BM(96)


42288-93 Programmable Virtual Output 2 Logic Term 2 RW BM(96)
42296-301 Programmable Virtual Output 2 Logic Mask 3 RW BM(96)
42304-09 Programmable Virtual Output 2 Logic Term 3 RW BM(96)
42312-17 Programmable Virtual Output 2 Logic Mask 4 RW BM(96)
42320-25 Programmable Virtual Output 2 Logic Term 4 RW BM(96)

42328 Programmable Virtual Output 3 Term Count RW SI


42329-34 Programmable Virtual Output 3 Logic Mask 1 RW BM(96)
42337-42 Programmable Virtual Output 3 Logic Term 1 RW BM(96)
42345-50 Programmable Virtual Output 3 Logic Mask 2 RW BM(96)
42353-58 Programmable Virtual Output 3 Logic Term 2 RW BM(96)
42361-66 Programmable Virtual Output 3 Logic Mask 3 RW BM(96)
42369-74 Programmable Virtual Output 3 Logic Term 3 RW BM(96)
42377-82 Programmable Virtual Output 3 Logic Mask 4 RW BM(96)
42385-90 Programmable Virtual Output 3 Logic Term 4 RW BM(96)

42393 Programmable Virtual Output 4 Term Count RW SI


42394-99 Programmable Virtual Output 4 Logic Mask 1 RW BM(96)
42402-07 Programmable Virtual Output 4 Logic Term 1 RW BM(96)
42410-15 Programmable Virtual Output 4 Logic Mask 2 RW BM(96)
42418-23 Programmable Virtual Output 4 Logic Term 2 RW BM(96)
42426-31 Programmable Virtual Output 4 Logic Mask 3 RW BM(96)
42434-39 Programmable Virtual Output 4 Logic Term 3 RW BM(96)
42442-47 Programmable Virtual Output 4 Logic Mask 4 RW BM(96)
42450-55 Programmable Virtual Output 4 Logic Term 4 RW BM(96)

42458 Programmable Virtual Output 5 Term Count RW SI


42459-64 Programmable Virtual Output 5 Logic Mask 1 RW BM(96)
42467-72 Programmable Virtual Output 5 Logic Term 1 RW BM(96)
42475-80 Programmable Virtual Output 5 Logic Mask 2 RW BM(96)
42483-88 Programmable Virtual Output 5 Logic Term 2 RW BM(96)
42491-96 Programmable Virtual Output 5 Logic Mask 3 RW BM(96)
42499-504 Programmable Virtual Output 5 Logic Term 3 RW BM(96)
42507-12 Programmable Virtual Output 5 Logic Mask 4 RW BM(96)
42515-20 Programmable Virtual Output 5 Logic Term 4 RW BM(96)

42523 Programmable Virtual Output 6 Term Count RW SI


42524-29 Programmable Virtual Output 6 Logic Mask 1 RW BM(96)
42532-37 Programmable Virtual Output 6 Logic Term 1 RW BM(96)
42540-45 Programmable Virtual Output 6 Logic Mask 2 RW BM(96)
42548-53 Programmable Virtual Output 6 Logic Term 2 RW BM(96)
42556-61 Programmable Virtual Output 6 Logic Mask 3 RW BM(96)
42564-69 Programmable Virtual Output 6 Logic Term 3 RW BM(96)
42572-77 Programmable Virtual Output 6 Logic Mask 4 RW BM(96)
42580-85 Programmable Virtual Output 6 Logic Term 4 RW BM(96)

42588 Programmable Virtual Output 7 Term Count RW SI


42589-94 Programmable Virtual Output 7 Logic Mask 1 RW BM(96)
42597-602 Programmable Virtual Output 7 Logic Term 1 RW BM(96)
42605-10 Programmable Virtual Output 7 Logic Mask 2 RW BM(96)
42613-18 Programmable Virtual Output 7 Logic Term 2 RW BM(96)
42621-26 Programmable Virtual Output 7 Logic Mask 3 RW BM(96)
42629-34 Programmable Virtual Output 7 Logic Term 3 RW BM(96)
42637-42 Programmable Virtual Output 7 Logic Mask 4 RW BM(96)
42645-50 Programmable Virtual Output 7 Logic Term 4 RW BM(96)

22 BE1-CDS With Modbus Protocol


Holding Read/Write Data
Register Parameter Supported Format Notes

42653 Programmable Virtual Output 8 Term Count RW SI


42654-59 Programmable Virtual Output 8 Logic Mask 1 RW BM(96)
42662-67 Programmable Virtual Output 8 Logic Term 1 RW BM(96)
42670-75 Programmable Virtual Output 8 Logic Mask 2 RW BM(96)
42678-83 Programmable Virtual Output 8 Logic Term 2 RW BM(96)
42686-91 Programmable Virtual Output 8 Logic Mask 3 RW BM(96)
42694-99 Programmable Virtual Output 8 Logic Term 3 RW BM(96)
42702-07 Programmable Virtual Output 8 Logic Mask 4 RW BM(96)
42710-15 Programmable Virtual Output 8 Logic Term 4 RW BM(96)

42718 Programmable Virtual Output 9 Term Count RW SI


42719-24 Programmable Virtual Output 9 Logic Mask 1 RW BM(96)
42727-32 Programmable Virtual Output 9 Logic Term 1 RW BM(96)
42735-40 Programmable Virtual Output 9 Logic Mask 2 RW BM(96)
42743-48 Programmable Virtual Output 9 Logic Term 2 RW BM(96)
42751-56 Programmable Virtual Output 9 Logic Mask 3 RW BM(96)
42759-64 Programmable Virtual Output 9 Logic Term 3 RW BM(96)
42767-72 Programmable Virtual Output 9 Logic Mask 4 RW BM(96)
42775-80 Programmable Virtual Output 9 Logic Term 4 RW BM(96)

42783 Programmable Virtual Output 10 Term Count RW SI


42784-89 Programmable Virtual Output 10 Logic Mask 1 RW BM(96)
42792-97 Programmable Virtual Output 10 Logic Term 1 RW BM(96)
42800-05 Programmable Virtual Output 10 Logic Mask 2 RW BM(96)
42808-13 Programmable Virtual Output 10 Logic Term 2 RW BM(96)
42816-21 Programmable Virtual Output 10 Logic Mask 3 RW BM(96)
42824-29 Programmable Virtual Output 10 Logic Term 3 RW BM(96)
42832-37 Programmable Virtual Output 10 Logic Mask 4 RW BM(96)
42840-45 Programmable Virtual Output 10 Logic Term 4 RW BM(96)

42848 Programmable Virtual Output 11 Term Count RW SI


42849-54 Programmable Virtual Output 11 Logic Mask 1 RW BM(96)
42857-62 Programmable Virtual Output 11 Logic Term 1 RW BM(96)
42865-70 Programmable Virtual Output 11 Logic Mask 2 RW BM(96)
42873-78 Programmable Virtual Output 11 Logic Term 2 RW BM(96)
42881-86 Programmable Virtual Output 11 Logic Mask 3 RW BM(96)
42889-94 Programmable Virtual Output 11 Logic Term 3 RW BM(96)
42897-902 Programmable Virtual Output 11 Logic Mask 4 RW BM(96)
42905-10 Programmable Virtual Output 11 Logic Term 4 RW BM(96)

42913 Programmable Virtual Output 12 Term Count RW SI


42914-19 Programmable Virtual Output 12 Logic Mask 1 RW BM(96)
42922-27 Programmable Virtual Output 12 Logic Term 1 RW BM(96)
42930-35 Programmable Virtual Output 12 Logic Mask 2 RW BM(96)
42938-43 Programmable Virtual Output 12 Logic Term 2 RW BM(96)
42946-51 Programmable Virtual Output 12 Logic Mask 3 RW BM(96)
42954-59 Programmable Virtual Output 12 Logic Term 3 RW BM(96)
42962-67 Programmable Virtual Output 12 Logic Mask 4 RW BM(96)
42970-75 Programmable Virtual Output 12 Logic Term 4 RW BM(96)

42978 Programmable Virtual Output 13 Term Count RW SI


42979-84 Programmable Virtual Output 13 Logic Mask 1 RW BM(96)
42987-92 Programmable Virtual Output 13 Logic Term 1 RW BM(96)
42995-3000 Programmable Virtual Output 13 Logic Mask 2 RW BM(96)
43003-08 Programmable Virtual Output 13 Logic Term 2 RW BM(96)
43011-16 Programmable Virtual Output 13 Logic Mask 3 RW BM(96)
43019-24 Programmable Virtual Output 13 Logic Term 3 RW BM(96)
43027-32 Programmable Virtual Output 13 Logic Mask 4 RW BM(96)
 Protocol
BE1-CDS With Modbus 23
Holding Read/Write Data
Register Parameter Supported Format Notes

43035-40 Programmable Virtual Output 13 Logic Term 4 RW BM(96)

43043 Programmable Virtual Output 14 Term Count RW SI


43044-49 Programmable Virtual Output 14 Logic Mask 1 RW BM(96)
43052-57 Programmable Virtual Output 14 Logic Term 1 RW BM(96)
43060-65 Programmable Virtual Output 14 Logic Mask 2 RW BM(96)
43068-73 Programmable Virtual Output 14 Logic Term 2 RW BM(96)
43076-81 Programmable Virtual Output 14 Logic Mask 3 RW BM(96)
43084-89 Programmable Virtual Output 14 Logic Term 3 RW BM(96)
43092-97 Programmable Virtual Output 14 Logic Mask 4 RW BM(96)
43100-05 Programmable Virtual Output 14 Logic Term 4 RW BM(96)

43108 Programmable Virtual Output 15 Term Count RW SI


43109-14 Programmable Virtual Output 15 Logic Mask 1 RW BM(96)
43117-22 Programmable Virtual Output 15 Logic Term 1 RW BM(96)
43125-30 Programmable Virtual Output 15 Logic Mask 2 RW BM(96)
43133-38 Programmable Virtual Output 15 Logic Term 2 RW BM(96)
43141-46 Programmable Virtual Output 15 Logic Mask 3 RW BM(96)
43149-54 Programmable Virtual Output 15 Logic Term 3 RW BM(96)
43157-62 Programmable Virtual Output 15 Logic Mask 4 RW BM(96)
43165-70 Programmable Virtual Output 15 Logic Term 4 RW BM(96)

System Labels And Id Setting Parameters

43438-52 Relay ID RW ASC(30)


43453-67 Station ID RW ASC(30)
43468-82 User ID #1 RW ASC(30)
43483-97 User ID #2 RW ASC(30)

43498-502 Virtual Selector Switch 43 – Name Label RW ASC(10)


43503-06 Virtual Selector Switch 43 – True Label RW ASC(7)
43507-10 Virtual Selector Switch 43 – False Label RW ASC(7)

43511-15 Virtual Selector Switch 143 – Name Label RW ASC(10)


43516-19 Virtual Selector Switch 143 – True Label RW ASC(7)
43520-23 Virtual Selector Switch 143 – False Label RW ASC(7)

43524-28 Virtual Selector Switch 243 – Name Label RW ASC(10)


43529-32 Virtual Selector Switch 243 – True Label RW ASC(7)
43533-36 Virtual Selector Switch 243 – False Label RW ASC(7)

43537-41 Virtual Selector Switch 343 – Name Label RW ASC(10)


43542-45 Virtual Selector Switch 343 – True Label RW ASC(7)
43546-49 Virtual Selector Switch 343 – False Label RW ASC(7)

43550-54 Virtual Selector Switch 443 – Name Label RW ASC(10)


43555-58 Virtual Selector Switch 443 – True Label RW ASC(7)
43559-62 Virtual Selector Switch 443 – False Label RW ASC(7)

43563-67 Virtual Selector Switch 543 – Name Label RW ASC(10)


43568-71 Virtual Selector Switch 543 – True Label RW ASC(7)
43572-75 Virtual Selector Switch 543 – False Label RW ASC(7)

43576-80 Virtual Selector Switch 643 – Name Label RW ASC(10)


43581-84 Virtual Selector Switch 643 – True Label RW ASC(7)
43585-88 Virtual Selector Switch 643 – False Label RW ASC(7)

24 BE1-CDS With Modbus Protocol


Holding Read/Write Data
Register Parameter Supported Format Notes

43589-93 Virtual Selector Switch 743 – Name Label RW ASC(10)


43594-97 Virtual Selector Switch 743 – True Label RW ASC(7)
43598-601 Virtual Selector Switch 743 – False Label RW ASC(7)

43602-06 Virtual Output A – Name Label RW ASC(10)


43607-10 Virtual Output A – True Label RW ASC(7)
43611-14 Virtual Output A – False Label RW ASC(7)

43615-19 Virtual Output 1 – Name Label RW ASC(10)


43620-23 Virtual Output 1 - True Label RW ASC(7)
43624-27 Virtual Output 1 – False Label RW ASC(7)

43628-32 Virtual Output 2 – Name Label RW ASC(10))


43633-36 Virtual Output 2 – True Label RW ASC(7)
43637-40 Virtual Output 2 – False Label RW ASC(7)

43641-45 Virtual Output 3 – Name Label RW ASC(10)


43646-49 Virtual Output 3 – True Label RW ASC(7)
43650-53 Virtual Output 3 – False Label RW ASC(7)

43654-58 Virtual Output 4 – Name Label RW ASC(10)


43659-62 Virtual Output 4 – True Label RW ASC(7)
43663-66 Virtual Output 4 – False Label RW ASC(7)

43667-71 Virtual Output 5 – Name Label RW ASC(10)


43672-75 Virtual Output 5 – True Label RW ASC(7)
43676-79 Virtual Output 5 – False Label RW ASC(7)

43680-84 Virtual Output 6 – Name Label RW ASC(10)


43685-88 Virtual Output 6 – True Label RW ASC(7)
43689-92 Virtual Output 6 – False Label RW ASC(7)

43693-97 Virtual Output 7 – Name Label RW ASC(10)


43698-701 Virtual Output 7 – True Label RW ASC(7)
43702-05 Virtual Output 7 – False Label RW ASC(7)

43706-10 Virtual Output 8 – Name Label RW ASC(10)


43711-14 Virtual Output 8 – True Label RW ASC(7)
43715-18 Virtual Output 8 – False Label RW ASC(7)

43719-23 Virtual Output 9 – Name Label RW ASC(10)


43724-27 Virtual Output 9 – True Label RW ASC(7)
43728-31 Virtual Output 9 – False Label RW ASC(7)

43732-36 Virtual Output 10 – Name Label RW ASC(10)


43737-40 Virtual Output 10 – True Label RW ASC(7)
43741-44 Virtual Output 10 – False Label RW ASC(7)

43745-49 Virtual Output 11 – Name Label RW ASC(10)


43750-53 Virtual Output 11 – True Label RW ASC(7)
43754-57 Virtual Output 11 – False Label RW ASC(7)

43758-62 Virtual Output 12 – Name Label RW ASC(10)


43763-66 Virtual Output 12 – True Label RW ASC(7)
43767-70 Virtual Output 12 – False Label RW ASC(7)

43771-75 Virtual Output 13 – Name Label RW ASC(10)


43776-79 Virtual Output 13 – True Label RW ASC(7)
 Protocol
BE1-CDS With Modbus 25
Holding Read/Write Data
Register Parameter Supported Format Notes

43780-83 Virtual Output 13 – False Label RW ASC(7)

43784-88 Virtual Output 14 – Name Label RW ASC(10)


43789-92 Virtual Output 14 – True Label RW ASC(7)
43793-96 Virtual Output 14 – False Label RW ASC(7)

43797-801 Virtual Output 15 – Name Label RW ASC(10)


43802-05 Virtual Output 15 – True Label RW ASC(7)
43806-09 Virtual Output 15 – False Label RW ASC(7)

43849-53 Input 1 – Name Label RW ASC(10)


43854-57 Input 1 – True Label RW ASC(7)
43858-61 Input 1 – False Label RW ASC(7)

43862-66 Input 2 – Name Label RW ASC(10)


43867-70 Input 2 – True Label RW ASC(7)
43871-74 Input 2 – False Label RW ASC(7)

43875-79 Input 3 – Name Label RW ASC(10)


43880-83 Input 3 – True Label RW ASC(7)
43884-87 Input 3 – False Label RW ASC(7)

43888-92 Input 4 – Name Label RW ASC(10)


43893-96 Input 4 – True Label RW ASC(7)
43897-900 Input 4 – False Label RW ASC(7)

43901-05 Input 5 – Name Label RW ASC(10)


43906-09 Input 5 – True Label RW ASC(7)
43910-13 Input 5 – False Label RW ASC(7)

43914-18 Input 6 – Name Label RW ASC(10)


43919-22 Input 6 – True Label RW ASC(7)
43923-26 Input 6 – False Label RW ASC(7)

43927-31 Input 7 – Name Label RW ASC(10)


43932-35 Input 7 – True Label RW ASC(7)
43936-39 Input 7 – False Label RW ASC(7)

43940-44 Input 8 – Name Label RW ASC(10)


43945-48 Input 8 – True Label RW ASC(7)
43949-52 Input 8 – False Label RW ASC(7)

Report Parameters

47274-78 Model Number R- ASC(10)

47282-89 Application SW Version # / Date R- ASC(16)

47296-302 Boot SW Version # / Date R- ASC(14)

47310-16 Serial Number R- ASC(13)

47324-34 Style Number R- ASC(21)

47346-53 DSP SW Version # / Date R- ASC(16)

47362 COM1 Serial Port Relay Address RW INT


26 BE1-CDS With Modbus Protocol
Holding Read/Write Data
Register Parameter Supported Format Notes

47363 COM2 Serial Port Relay Address RW INT

47364 Date and Time – Day RW INT TS


47365-66 Date and Time – Milliseconds RW LI TS

47367-72 System Status R– BM(96)

47373 Current Active Group Setting R– SI


47374 Current Group Control Setting R- ASC(1)
47375-76 Current Output Control Settings (OutputPulse) R- BM(32)
47377-78 Current Output Control Settings (OutputLatch) R– BM(32)
47379 Current Output Contact Status R– BM(16)
47380-81 Active Alarm Flags (SumFlags) R– BM(32)
47382-83 Active Alarm Flags (ProgAlarms) R– BM(32)
47384-87 Target Status RW BM(64)
47388 Current Breaker Status R- ASC(1)
47389-92 Current Active Logic R- ASC(8)

47394-95 Breaker Contact Duty Log – Phase A RW FP


47396-97 Breaker Contact Duty Log – Phase B RW FP
47398-99 Breaker Contact Duty Log – Phase C RW FP
47400-01 Breaker Operation Counter RW LI

47402-03 Transformer Duty Log Settings – Phase A RW FP


47404-05 Transformer Duty Log Settings – Phase B RW FP
47406-07 Transformer Duty Log Settings – Phase C RW FP
47408-09 Transformer Through Faults Counter RW LI

47410-11 Yesterday’s Peak Demand Current – Phase A R- FP


47412 Yesterday’s Peak Demand Timestamp - Day R- INT TS
47413-14 Yesterday’s Peak Demand Timestamp – Millisecond R- LI TS

47415-16 Yesterday’s Peak Demand Current – Phase B R- FP


47417 Yesterday’s Peak Demand Timestamp - Day R- INT TS
47418-19 Yesterday’s Peak Demand Timestamp – Millisecond R- LI TS

47420-21 Yesterday’s Peak Demand Current – Phase C R- FP


47422 Yesterday’s Peak Demand Timestamp - Day R- INT TS
47423-24 Yesterday’s Peak Demand Timestamp – Millisecond R- LI TS

47425-26 Yesterday’s Peak Demand Current – Neutral R- FP


47427 Yesterday’s Peak Demand Timestamp - Day R- INT TS
47428-29 Yesterday’s Peak Demand Timestamp – Millisecond R- LI TS

47430-31 Yesterday’s Peak Demand Current – Negative Seq R- FP


47432 Yesterday’s Peak Demand Timestamp - Day R- INT TS
47433-34 Yesterday’s Peak Demand Timestamp – Millisecond R- LI TS

47435-36 Today’s Peak Demand Current – Phase A R- FP


47437 Today’s Peak Demand Timestamp - Day R- INT TS
47438-39 Today’s Peak Demand Timestamp – Millisecond R- LI TS

47440-41 Today’s Peak Demand Current – Phase B R- FP


47442 Today’s Peak Demand Timestamp - Day R- INT TS
47443-44 Today’s Peak Demand Timestamp – Millisecond R- LI TS

47445-46 Today’s Peak Demand Current – Phase C R- FP


47447 Today’s Peak Demand Timestamp - Day R- INT TS
 Protocol
BE1-CDS With Modbus 27
Holding Read/Write Data
Register Parameter Supported Format Notes

47448-49 Today’s Peak Demand Timestamp – Millisecond R- LI TS

47450-51 Today’s Peak Demand Current – Neutral R- FP


47452 Today’s Peak Demand Timestamp - Day R- INT TS
47453-54 Today’s Peak Demand Timestamp – Millisecond R- LI TS

47455-56 Today’s Peak Demand Current – Negative Seq R- FP


47457 Today’s Peak Demand Timestamp - Day R- INT TS
47458-59 Today’s Peak Demand Timestamp – Millisecond R- LI TS

47460-61 Peak Demand Current Since Reset – Phase A RW FP


47462 Peak Demand Since Reset Timestamp - Day R- INT TS
47463-64 Peak Demand Since Reset Timestamp – Millisecond R- LI TS

47465-66 Peak Demand Current Since Reset – Phase B RW FP


47467 Peak Demand Since Reset Timestamp - Day R- INT TS
47468-69 Peak Demand Since Reset Timestamp – Millisecond R- LI TS

47470-71 Peak Demand Current Since Reset – Phase C RW FP


47472 Peak Demand Since Reset Timestamp - Day R- INT TS
47473-74 Peak Demand Since Reset Timestamp – Millisecond R- LI TS

47475-76 Peak Demand Current Since Reset – Neutral RW FP


47477 Peak Demand Since Reset Timestamp - Day R- INT TS
47478-79 Peak Demand Since Reset Timestamp – Millisecond R- LI TS

47480-81 Peak Demand Current Since Reset – Negative Seq RW FP


47482 Peak Demand Since Reset Timestamp - Day R- INT TS
47483-84 Peak Demand Since Reset Timestamp – Millisecond R– LI TS

47485 Trigger Differential Alarm Report RW SI


47486 Reset Logic Alarm Information RW SI
47487 Reset Major Alarm Information RW SI
47488 Reset Minor Alarm Information RW SI
47489 Reset Relay Alarm Information RW SI
47490 Reset Load Profile RW SI
47491 Clear Fault Log RW SI
47492 Trigger Fault Record RW SI
47493 Clear Events Report RW SI

47512 Fault Indicator R- SI


47513 Fault Template Status R- SI

The following is the Fault Template (FLT).

47514 Fault Date and Time – Day R- INT FLT, TS


47515-16 Fault Date and Time – Milliseconds R- LI FLT, TS
47517 Fault Event Type R- BM(16) FLT
47518 Fault Active Group R- SI FLT
47519-22 Fault Targets R- BM(64) FLT

47524 Fault Clearing Time Status R- SI FLT


47525-26 Fault Clearing Time R- FP FLT
47527 Fault Breaker Operate Time Status R- SI FLT
47528-29 Fault Breaker Operate Time R- FP FLT

47530-31 Fault CT CKT #1 Phase A Current Magnitude R- FP FLT


47532 Fault CT CKT #1 Phase A Angle R- INT FLT
28 BE1-CDS With Modbus Protocol
Holding Read/Write Data
Register Parameter Supported Format Notes

47533-34 Fault CT CKT #1 Phase B Current Magnitude R- FP FLT


47535 Fault CT CKT #1 Phase B Angle R- INT FLT
47536-37 Fault CT CKT #1 Phase C Current Magnitude R- FP FLT
47538 Fault CT CKT #1 Phase C Angle R- INT FLT
47539-40 Fault CT CKT #1 Residual Current Magnitude R- FP FLT
47541 Fault CT CKT #1 Residual Angle R- INT FLT
47542-43 Fault CT CKT #1 Negative Seq. Current Magnitude R- FP FLT

47544-45 Fault CT CKT #2 Phase A Current Magnitude R- FP FLT


47546 Fault CT CKT #2 Phase A Angle R- INT FLT
47547-48 Fault CT CKT #2 Phase B Current Magnitude R- FP FLT
47549 Fault CT CKT #2 Phase B Angle R- INT FLT
47550-51 Fault CT CKT #2 Phase C Current Magnitude R- FP FLT
47552 Fault CT CKT #2 Phase C Angle R- INT FLT
47553-54 Fault CT CKT #2 Residual Current Magnitude R- FP FLT
47555 Fault CT CKT #2 Residual Angle R- INT FLT
47556-57 Fault CT CKT #2 Negative Seq. Current Magnitude R- FP FLT

47572-73 Fault Ground Current Magnitude R- FP FLT


47574 Fault Ground Angle R- INT FLT

The following is the Report Template (RPT)

47595-719 Report Text R- ASC(250) RPT

Metering Parameters

49720 Part Number R- INT

49721-22 Measured Frequency R- FP

49723-24 Ground Current Magnitude R- FP


49725 Ground Angle R- INT

49726-27 CT CKT #1 Phase A Current Magnitude R- FP


49728 CT CKT #1 Phase A Angle R- INT

49729-30 CT CKT #1 Phase B Current Magnitude R- FP


49731 CT CKT #1 Phase B Angle R- INT

49732-33 CT CKT #1 Phase C Current Magnitude R- FP


49734 CT CKT #1 Phase C Angle R- INT

49735-36 CT CKT #1 Residual Current Magnitude R- FP


49737 CT CKT #1 Residual Angle R- INT

49738-39 CT CKT #1 Negative Sequence Current Magnitude R- FP

49740-41 CT CKT #2 Phase A Current Magnitude R- FP


49742 CT CKT #2 Phase A Angle R- INT

49743-44 CT CKT #2 Phase B Current Magnitude R- FP


49745 CT CKT #2 Phase B Angle R- INT

49746-47 CT CKT #2 Phase C Current Magnitude R- FP


49748 CT CKT #2 Phase C Angle R- INT

 Protocol
BE1-CDS With Modbus 29
Holding Read/Write Data
Register Parameter Supported Format Notes

49749-50 CT CKT #2 Residual Current Magnitude R- FP


49751 CT CKT #2 Residual Angle R- INT

49752-53 CT CKT #2 Negative Sequence Current Magnitude R- FP

49782-83 CT CKT #1 Differential per Unit Phase A Current R- FP


49784 CT CKT #1 Phase A Differential Compensation Angle R- INT

49785-86 CT CKT #2 Differential per Unit Phase A Current R- FP


49787 CT CKT #2 Phase A Differential Compensation Angle R- INT

49791-92 Phase A Differential Operating Current R- FP

49793-94 CT CKT #1 Differential per Unit Phase B Current R- FP


49795 CT CKT #1 Phase B Differential Compensation Angle R- INT

49796-97 CT CKT #2 Differential per Unit Phase B Current R- FP


49798 CT CKT #2 Phase B Differential Compensation Angle R- INT

49802-03 Phase B Differential Operating Current R- FP

49804-05 CT CKT #1 Differential per Unit Phase C Current R- FP


49806 CT CKT #1 Phase C Differential Compensation Angle R- INT

49807-08 CT CKT #2 Differential per Unit Phase C Current R- FP


49809 CT CKT #2 Phase C Differential Compensation Angle R- INT

49813-14 Phase C Differential Operating Current R- FP

49815-16 Differential per Unit Ground Current R- FP


49817 Ground Differential Compensation Angle R- INT

49818-19 CT CKT #1 Differential per Unit Residual Current R- FP


49820 CT CKT #1 Residual Differential Compensation Angle R- INT

49821-22 CT CKT #2 Differential per Unit Residual Current R- FP


49823 CT CKT #2 Residual Differential Compensation Angle R- INT

49827-28 Ground Differential Operating Current R- FP

49829 Phase A Differential Second Harmonic Percentage R- INT


49830 Phase B Differential Second Harmonic Percentage R- INT
49831 Phase C Differential Second Harmonic Percentage R- INT

49832 Phase A Differential Fifth Harmonic Percentage R- INT


49833 Phase B Differential Fifth Harmonic Percentage R- INT
49834 Phase C Differential Fifth Harmonic Percentage R- INT

49835-54 Error Details R- ASC(40)


49875-999 Contiguous Poll Block R- Mixed

30 BE1-CDS With Modbus Protocol


REGISTER DETAILS

This section details the register formats and data ranges of the previous section. The two sections combined
provide all information necessary to communicate with the BE1-CDS-220 Modbus Holding Registers.

Any Holding Register not listed in the Register Table is an unassigned Holding Register. A value of zero always
results when reading an unassigned Holding Register. Writes to unassigned Holding Registers are legal, but no
action will be taken (the write is ignored).

Logic Settings

Logic settings consist of a combination of modes, masks, terms and term counts. Logic modes are specific to
each logic set, while the masks, terms and term counts have value definitions consistent throughout all logic
sets. A single logic equation consists of a “mask” and “term” pair. The logic”term count” is used only in VOA,
VO1-VO15 virtual output logic blocks.

The logic “mode” enables or disables the logic equation for that logic block.
The logic “mask” corresponds to the SystemStatus bits to be evaluated. These bits are referenced in the
desired logic equation and are set to 1 (non-used bits masked out as 0‘s).
The logic “term” corresponds to the SystemStatus bit’s TRUE or FALSE state, referenced in the desired logic
equation where only the TRUE bits in the equation are set to 1.
The logic “term count” may be of one of four logic types which are NONE (logic disabled), OR only ( a + b + c),
AND only (a*b*c) or MIXED (a*b + b*c).

The following defines all logic set parameters.

Logic Modes:

41505 Programmable 50TP Block Logic Mode INT


41522 Programmable 50TN Block Logic Mode INT
41539 Programmable 50TQ Block Logic Mode INT
41556 Programmable 150TP Block Logic Mode INT
41573 Programmable 150TN Block Logic Mode INT
41590 Programmable 150TQ Block Logic Mode INT
41607 Programmable 250TP Block Logic Mode INT
41624 Programmable 250TN Block Logic Mode INT
41641 Programmable 250TQ Block Logic Mode INT
Read and Write:
0 for disabled
1 for winding 1
2 for winding 2
3 for ground CT (only for element ‘N’)

41658 Programmable Breaker Fail Logic Mode INT


Read and Write:
0 for disabled
1 for winding 1
2 for winding 2

41691 Programmable 51P Logic Mode INT


41708 Programmable 51N Logic Mode INT
41725 Programmable 51Q Logic Mode INT
41742 Programmable 151P Logic Mode INT
41759 Programmable 151N Logic Mode INT
41776 Programmable 151Q Logic Mode INT
41793 Programmable 251P Logic Mode INT
41810 Programmable 251N Logic Mode INT

 Protocol
BE1-CDS With Modbus 31
41827 Programmable 251Q Logic Mode INT
Read and Write:
0 for disabled
1 for winding 1
2 for winding 2
3 for ground CT (only for element ‘N’)

41844 Programmable 62 Timer Logic Mode INT


41877 Programmable 162 Timer Logic Mode INT
Read and Write:
0 for disabled
1 for Pickup / Dropout
2 for One-Shot Non-Retriggerable
3 for One-Shot Retriggerable
4 for Oscillator
5 for Integrating

41976 Programmable 87 Differential Logic Mode INT


Read and Write:
0 for disabled
1 for enabled all windings

41993 Programmable 87ND Differential Logic Mode INT


Read and Write:
0 for disabled
1 for winding 1
2 for winding 2

42010 Programmable Settings Group Logic Mode INT


Read and Write:
0 for all setting groups disabled except group 0
1 for selecting setting group via pulsed input logic
2 for selecting setting group via sustained input logic

42091 Programmable 43 Virtual Switch Logic Mode INT


42092 Programmable 143 Virtual Switch Logic Mode INT
42093 Programmable 243 Virtual Switch Logic Mode INT
42094 Programmable 343 Virtual Switch Logic Mode INT
42095 Programmable 443 Virtual Switch Logic Mode INT
42096 Programmable 543 Virtual Switch Logic Mode INT
42097 Programmable 643 Virtual Switch Logic Mode INT
42098 Programmable 743 Virtual Switch Logic Mode INT
Read and Write:
0 for disabled
1 for on / off / pulse (all)
2 for on / off
3 for pulse

42099 Programmable 101 Virtual Breaker Control Logic Mode INT


Read and Write:
0 for disabled
1 for enabled

42100 Programmable Circuit Monitor Logic Mode INT


Read and Write:
0 for disabled
1 for enabled

32 BE1-CDS With Modbus Protocol


Logic Mask And Terms:

Each set bit in the "mask" parameter indicates a significant variable in the equation. A corresponding bit in the
"term" parameter indicates that the variable must be TRUE / 1 if set or FALSE / 0 if not set.

Mask and Term – First Register (Logic Var 0 to 15) BM(16)


Read and Write:
Bit 15 – 51Q tripped
Bit 14 – 251 neutral tripped
Bit 13 – 151 neutral tripped
Bit 12 – 51 neutral tripped
Bit 11 – 251 phase tripped
Bit 10 – 151 phase tripped
Bit 9 – 51 phase tripped
Bit 8 – 250Q tripped
Bit 7 – 150Q tripped
Bit 6 – 50Q tripped
Bit 5 – 250 neutral tripped
Bit 4 – 150 neutral tripped
Bit 3 – 50 neutral tripped
Bit 2 – 250 phase tripped
Bit 1 – 150 phase tripped
Bit 0 – 50 phase tripped

Mask and Term – Second Register (Logic Var 16 to 31) BM(16)


Read and Write:
Bit 15 – Logic always false L-VOx=0
Bit 14 – Setting Group 3 active
Bit 13 – Setting Group 2 active
Bit 12 – Setting Group 1 active
Bit 11 – Setting Group 0 active
Bit 10 – 162 tripped
Bit 9 – 62 tripped
Bit 8 – <unassigned>
th
Bit 7 – 87 5 harmonic
nd
Bit 6 – 87 2 harmonic
Bit 5 – 87 unrestrained trip
Bit 4 – 87 restrained trip
Bit 3 – 87ND trip
Bit 2 – BF tripped
Bit 1 – 251Q tripped
Bit 0 – 151Q tripped

Mask and Term – Third Register (Logic Var 32 to 47) BM(16)


Read and Write:
Bit 15 – Virtual Output 15 status
Bit 14 – Virtual Output 14 status
Bit 13 – Virtual Output 13 status
Bit 12 – Virtual Output 12 status
Bit 11 – Virtual Output 11 status
Bit 10 – Virtual Output 10 status
Bit 9 – Virtual Output 9 status
Bit 8 – Virtual Output 8 status
Bit 7 – Virtual Output 7 status
Bit 6 – Virtual Output 6 status
Bit 5 – Virtual Output 5 status
Bit 4 – Virtual Output 4 status
Bit 3 – Virtual Output 3 status
Bit 2 – Virtual Output 2 status

 Protocol
BE1-CDS With Modbus 33
Bit 1 – Virtual Output 1 status
Bit 0 – Virtual Output A status

Mask and Term – Fourth Register (Logic Var 48 to 63) BM(16)


Read and Write:
Bit 15 – 101 slip contact
Bit 14 – 101 close
Bit 13 – 101 trip
Bit 12 – Output circuit trip coil monitor
Bit 11 – Alarm logic
Bit 10 – Alarm minor
Bit 9 – Alarm major
Bit 8 – <unassigned>
Bit 7 – Input 8 status
Bit 6 – Input 7 status
Bit 5 – Input 6 status
Bit 4 – Input 5 status
Bit 3 – Input 4 status
Bit 2 – Input 3 status
Bit 1 – Input 2 status
Bit 0 – Input 1 status

Mask and Term – Fifth Register (Logic Var 64 to 79) BM(16)


Read and Write:
Bit 15 – 51Q picked-up
Bit 14 – 251 neutral picked-up
Bit 13 – 151 neutral picked-up
Bit 12 – 51 neutral picked-up
Bit 11 – 251 phase picked-up
Bit 10 – 151 phase picked-up
Bit 9 – 51 phase picked-up
Bit 8 – 250Q picked-up
Bit 7 – 150Q picked-up
Bit 6 – 50Q picked-up
Bit 5 – 250 neutral picked-up
Bit 4 – 150 neutral picked-up
Bit 3 – 50 neutral picked-up
Bit 2 – 250 phase picked-up
Bit 1 – 150 phase picked-up
Bit 0 – 50 phase picked-up

Mask and Term – Sixth Register (Logic Var 80 to 95) BM(16)


Read and Write:
Bit 15 – Serial controlled switch 743
Bit 14 – Serial controlled switch 643
Bit 13 – Serial controlled switch 543
Bit 12 – Serial controlled switch 443
Bit 11 – Serial controlled switch 343
Bit 10 – Serial controlled switch 243
Bit 9 – Serial controlled switch 143
Bit 8 – Serial controlled switch 43
Bit 7 – Target reset key
Bit 6 – Alarm reset key
Bit 5 – <unassigned>
Bit 4 – 87 restrained pickup
Bit 3 – 87ND pickup
Bit 2 – BF picked-up
Bit 1 – 251Q picked-up
Bit 0 – 151Q picked-up

34 BE1-CDS With Modbus Protocol


Logic Term Count:

Term Count Register SI


Read and Write:
0 means the logic equation is disabled (NONE)
-1 means the logic equation consists of a single term of OR-ed variables
1 means the logic equation consists of a single term of AND-ed variables
2 means the logic equation consists of the OR-ing of 2 terms of AND-ed variables
3 means the logic equation consists of the OR-ing of 3 terms of AND-ed variables
4 means the logic equation consists of the OR-ing of 4 terms of AND-ed variables

Session Parameters

40001 Exit ASC(1)


Read: always the ASCII character ‘0’ (zero)
Write: ASCII characters ‘Y’ or ‘N’ (‘Y’ to save changes, ‘N’ to ignore changes)
Note 1: ERROR DETAIL block (49835-54) contains Exit status message following a write.
Note 2: Writing to this register is effective only when Password Security register 40989 is enabled.

40002-5 Access Password ASC(8)


Read: always the ASCII string of ‘*’ characters.
Write: access password in ASCII string.
Note 1: If password written is less than 8 characters long, a binary zero value must be included
following the final password character.
Note 2: Writing to this register is effective only when Password Security register 40989 is enabled.

40006 Access Request BM(16)


Read: returns the current write access available to the Modbus user
Bit 3 is set for Global Access
Bit 2 is set for Setting Access
Bit 1 is set for Control Access
Bit 0 is set for Report Access
Zero value for Read Only Access
Write: To request write privileges using the password written into Access Password registers. Value
written into Access Request register is arbitrary (any value will initiate the request).
Note 1: If write access is denied, the response message will be an error response message with
Illegal Function exception code.
Step 1. Write the desired password to PASSWORD registers 40002 to 40005
Step 2. Write any value to ACCESS REQUEST register 40006
Step 3. Read Access Level from ACCESS REQUEST register 40006
Note 2: Writing to this register is effective only when Password Security register 40989 is enabled.

Template Parameters

40036 Settings Group Selection SI


Read: returns the current value of Settings Group Selection.
Write: the desired value to assign a Settings Group to the Group (GRP) Template.
O for Settings Group 0
1 for Settings Group 1
2 for Settings Group 2
3 for Settings Group 3

40038 Fault Selection SI


Read: returns the current value of Fault Selection.
Write: the desired value to assign a Fault Record to the Fault (FLT) Template.
Allowed values are 1 – 255.
Note: Refer to Fault Indicator (47512) and Fault Template Status (47513) Registers.
 Protocol
BE1-CDS With Modbus 35
40039 Report Selection SI
Read: returns the current value of Report Selection.
Writing to Report Selection terminates previous report and initializes new report. See table for values.

40040 Report Focus INT


Read: returns the current value of Report Focus.
Write: see table for values.
Note: If an illegal Report Focus value is written, the user is not notified until a read of the Report Text
is attempted.

Note: Write to Report Selection and Report Focus to specify the report which will be made available
via the Report (RPT) Template. The template is the Report Text Block at 47595-719.

Report Text Report Selection Report Focus


47595-719 40039 40040
RA-DIFF Report 0 Not used
RA-LGC Report 1 Not used
RA-MAJ Report 2 Not used
RA-MIN Report 3 Not used
RA-REL Report 4 Not used
RD-LOG 5 Not used
RD-L# 6 Value of # (non-zero)
RF Report 7 Not used
RF-# Report 8 Value of # ( 1 – 255 )
RF-NEW Report 9 Not used
RS Report 10 Not used
RS-# Report 11 Value of # ( 1 – 255 )
RS-NEW Report 12 Not used
RS-F# Report 13 Value of # ( 1 – 255 )
RS-ALM or RA-SER 14 Not used
RS-IO 15 Not used
RS-LGC 16 Not used

Global Parameters
Global Parameter registers 40080 – 40099 are effective only for serial communication ports active with ASCII
protocol and for the modbus serial port, COM2, when Password Security register 40989 is enabled.

40080-83 Global Password ASC(8)


40085-88 Setting Password ASC(8)
40090-93 Control Password ASC(8)
40095-98 Report Password ASC(8)
Read: If global access granted, password ASCII strings are read. Otherwise,
The ASCII string of ‘*’ characters is read.
Write: Password in ASCII string.
Note: If password written is less than 8 characters long, a binary zero value must be included
following the final password character.

40084 Global Path BM(8)


40089 Setting Path BM(8)
40094 Control Path BM(8)

36 BE1-CDS With Modbus Protocol


40099 Report Path BM(8)
Read: path associated with password.
Write: path associated with password.
Bit 2 is set for COM 2 access.
Bit 1 is set for COM1 access.
Bit 0 is set for COM0 / FP access.
Control Parameters

All values read from and written to Select and Operate registers are ASCII characters. Select registers must
be written first ,followed by a write to the Operate register. A 30 second window starts after the first write to
the Select register. If the second write to the Operate register is not received within the 30 second window,
an error response will be returned.

Writes to Operate registers 40138, 40140 – 40150 with ASCII data ‘E ‘ (Enable Output override control) or ‘D’
(Disable Output override control) requires an additional write of ‘Y’ to Exit register 40001 to allow these control
settings to be saved to the relay internal EEPROM.

NOTE: All values read from and written to Select and Operate registers are ASCII characters.

40117 Select Group ASC(1)


Read: To read a value other than ASCII character ‘X’, the Select Group register must be the most
recent control register written AND must have been written within the previous 30 seconds.
0 if Group 0 selection has been made.
1 if Group 1 selection has been made.
2 if Group 2 selection has been made.
3 if Group 3 selection has been made.
L if Logic selection has been made.
X if Group control not selected or control timer has expired
Write: the desired ASCII character.
0 to select Group 0.
1 to select Group 1.
2 to select Group 2.
3 to select Group 3.
L to select Logic.

40118 Operate Group ASC(1)


Read: Current control.
0 if Group 0.
1 if Group 1.
2 if Group 2.
3 if Group 3.
L if Logic.
Write: the desired ASCII character to alter control (corresponding Select register must contain same
value, written within previous 30 seconds).
0 to select Group 0.
1 to select Group 1.
2 to select Group 2.
3 to select Group 3.
L to select Logic.

40119 Select Virtual Selector Switch 43 ASC(1)


40121 Select Virtual Selector Switch 143 ASC(1)
40123 Select Virtual Selector Switch 243 ASC(1)
40125 Select Virtual Selector Switch 343 ASC(1)
40127 Select Virtual Selector Switch 443 ASC(1)
40129 Select Virtual Selector Switch 543 ASC(1)
40131 Select Virtual Selector Switch 643 ASC(1)
40133 Select Virtual Selector Switch 743 ASC(1)

 Protocol
BE1-CDS With Modbus 37
Read: To read a value other than ASCII character ‘X’, the Select Virtual Selector Switch register must
be the most recent control register written AND must have been written within the previous 30
seconds.
P if Pulse Switch selection has been made.
0 if Latch Switch at 0 selection has been made.
1 if Latch Switch at 1 selection has been made.
X if Virtual Selector Switch control not selected or control timer has expired
Write: the desired ASCII character.
P to select Pulsing the Switch.
0 to select Latching the Switch at 0.
1 to select Latching the Switch at 1.

40120 Operate Virtual Selector Switch 43 ASC(1)


40122 Operate Virtual Selector Switch 143 ASC(1)
40124 Operate Virtual Selector Switch 243 ASC(1)
40126 Operate Virtual Selector Switch 343 ASC(1)
40128 Operate Virtual Selector Switch 443 ASC(1)
40130 Operate Virtual Selector Switch 543 ASC(1)
40132 Operate Virtual Selector Switch 643 ASC(1)
40134 Operate Virtual Selector Switch 743 ASC(1)
Read: Current control.
P if Pulse Switch.
0 if Latch Switch at 0.
1 if Latch Switch at 1.
Write: the desired ASCII character to alter control (corresponding Select register must contain same
value, written within previous 30 seconds).
P to Pulse Switch.
0 to Latch Switch at 0.
1 to Latch Switch at 1.

40135 Select 101 Virtual Breaker Control Switch ASC(1)


Read: To read a value other than ASCII character ‘X’, the Select 101 Virtual Breaker Control Switch
register must be the most recent control register written AND must have been written within the
previous 30 seconds.
C if Close selection has been made.
T if Trip selection has been made.
X if 101 Virtual Breaker Control Switch control not selected or control timer has expired
Write: the desired ASCII character.
C to select Closing the Switch.
T to select Triping the Switch.

40136 Operate 101 Virtual Breaker Control Switch ASC(1)


Read: Current control.
C if Close Switch.
T if Trip Switch.
Write: the desired ASCII character to alter control (corresponding Select register must contain same
value, written within previous 30 seconds).
C to Close Switch.
T to Trip Switch.

40137 Select All Outputs ASC(1)


Read: To read a value other than ASCII character ‘X’, the Select All Output register must be the most
recent control register written AND must have been written within the previous 30 seconds.
P if Pulse All Outputs selection has been made.
0 if Latch All Outputs at 0 selection has been made.
1 if Latch All Outputs at 1 selection has been made.
L if programmable Logic selection has been made.
E if Enable All Outputs override control has been set.
D if Disable All Outputs override control has been set.
X if All Outputs control not selected or control timer has expired
38 BE1-CDS With Modbus Protocol
Write: the desired ASCII character.
P to select Pulsing All Outputs.
0 to select Latching All Outputs at 0.
1 to select Latching All Outputs at 1.
L to select programmable Logic.
E to select Enabling All Outputs override control.
D to select Disabling All Outputs override control.
40138 Operate All Outputs ASC(1)
Read: Current control.
E if All Outputs override control Enabled.
D if All Outputs override control Disabled.
Write: the desired ASCII character to alter control (corresponding Select register must contain
same value, written within previous 30 seconds).
P to Pulse All Outputs.
0 to Latch All Outputs at 0.
1 to Latch All Outputs at 1.
L to select programmable Logic.
E to Enable All Outputs override control. *
D to Disable All Outputs override control. *

40139 Select Output A ASC(1)


40141 Select Output 1 ASC(1)
40143 Select Output 2 ASC(1)
40145 Select Output 3 ASC(1)
40147 Select Output 4 ASC(1)
40149 Select Output 5 ASC(1)
Read: To read a value other than ASCII character ‘X’, the Select Output register must be the most
recent control register written AND must have been written within the previous 30 seconds.
P if Pulse Output selection has been made.
0 if Latch Output at 0 selection has been made.
1 if Latch Output at 1 selection has been made.
L if programmable Logic selection has been made.
E if Enable All Outputs serial control has been made.
D if Disable All Outputs serial control has been made.
X if Output control not selected or control timer has expired
Write: the desired ASCII character.
P to select Pulsing Output.
0 to select Latching Output at 0.
1 to select Latching Output at 1.
L to select programmable Logic.
E to select Enabling All Outputs override control.
D to select Disabling All Outputs override control.

40140 Operate Output A ASC(1)


40142 Operate Output 1 ASC(1)
40144 Operate Output 2 ASC(1)
40146 Operate Output 3 ASC(1)
40148 Operate Output 4 ASC(1)
40150 Operate Output 5 ASC(1)
Read: Current control.
P to Pulse Output.
0 to Latch Output at 0.
1 to Latch Output at 1.
L to select programmable Logic.
D if All Outputs override control Disabled
Write: the desired ASCII character to alter control (corresponding Select register must contain same
value, written within previous 30 seconds).
P to Pulse Output.
0 to Latch Output at 0.
1 to Latch Output at 1.
BE1-CDS With Modbus  Protocol 39
L to select programmable Logic.
E to Enable All Outputs override control. *
D to Disable All Outputs override control. *

* Requires an additional write of ‘Y’ to Exit register 40001 to allow these control settings to be saved to the
relay internal EEPROM.

Group Setting Parameters

40269-70 50TP Pickup FP


40273-74 50TN Pickup FP
40277-78 50TQ Pickup FP
40281-82 150TP Pickup FP
40285-86 150TN Pickup FP
40289-90 150TQ Pickup FP
40293-94 250TP Pickup FP
40297-98 250TN Pickup FP
40301-02 250TQ Pickup FP
Read and Write: 0.50 to 150.00 Amps

40271-72 50TP Time Delay LI


40275-76 50TN Time Delay LI
40279-80 50TQ Time Delay LI
40283-84 150TP Time Delay LI
40287-88 150TN Time Delay LI
40291-92 150TQ Time Delay LI
40295-96 250TP Time Delay LI
40299-300 250TN Time Delay LI
40303-04 250TQ Time Delay LI
Read and Write: 0 to 60,000 Mill i-seconds

40305-06 51P Pickup FP


40311-12 51N Pickup FP
40317-18 51Q Pickup FP
40323-24 151P Pickup FP
40329-30 151N Pickup FP
40335-36 151Q Pickup FP
40341-42 251P Pickup FP
40347-48 251N Pickup FP
40353-54 251Q Pickup FP
Read and Write: 0.50 to 16.00 Amps

40307-08 51P Time Dial FP


40313-14 51N Time Dial FP
40319-20 51Q Time Dial FP
40325-26 151P Time Dial FP
40331-32 151N Time Dial FP
40337-38 151Q Time Dial FP
40343-44 251P Time Dial FP
40349-50 251N Time Dial FP
40355-56 251Q Time Dial FP
Read and Write: 0.0 to 9.9

40309-10 51P Curve Type ASC(3)


40315-16 51N Curve Type ASC(3)
40321-22 51Q Curve Type ASC(3)
40327-28 151P Curve Type ASC(3)
40333-34 151N Curve Type ASC(3)
40 BE1-CDS With Modbus Protocol
40339-40 151Q Curve Type ASC(3)
40345-46 251P Curve Type ASC(3)
40351-52 251N Curve Type ASC(3)
40357-58 251Q Curve Type ASC(3)
Read and Write: one of the following ASCII strings
S1, S2, L1, L2, D, M, I1, I2, V1, V2, E1, E2, S1R, S2R, L1R, L2R, DR, MR, I1R,
I2R, V1R, V2R, E1R, E2R, A, B, C, G, F, P, AR, BR, CR, GR, FR, PR
40359-60 62 Time Delay 1 LI
40361-62 62 Time Delay 2 LI
40363-64 162 Time Delay 1 LI
40365-66 162 Time Delay 2 LI
Read and Write: 0 to 3,600,000 Milli-seconds

40375-76 87T Minimum Pickup FP


Read and Write: 0.00 to 1.00 Amps

40377 87T Restraint Slope INT


Read and Write: 15 to 60

40378-79 87T Second Harmonic Threshold FP


40380-81 87T Fifth Harmonic Threshold FP
Read and Write: 5.0 to 75.0

40382 87T Unrestrained Pickup INT


Read and Write: 0 to 21

40383 87T Second Harmonic Sharing INT


Read and Write: 0 to 1

40384-85 87ND CT CKT G Tap FP


40386-87 87ND Calculated Neutral Tap FP
Read Only: 2.00 to 20.00 Amps

40388-89 87ND Minimum Pickup FP


Read and Write: 0.00 to 1.00 Amps

40390 87ND Restraint Slope INT


Read and Write: 15 to 60

40391 87ND Restraint Time Delay INT


Read and Write: 50 to 60,000 Milli-seconds

40392-93 Transformer Mega-Volt-Amps (MVA) Rating FP


Read: 0, 0.5 to 1000.0
Write: 0.45 to 999.95

40394-95 87T CT CKT #1 Tap FP


40398-99 87T CT CKT #2 Tap FP
For CT Type 1A:
Read: 0.40 to 4.00
Write: 0.395 to 3.995
For CT Type 5A:
Read: 2.00 to 20.00
Write: 1.995 to 19.995

40396-97 Transformer Tap 1 Kilo-Volt (KV) Rating FP


40400-01 Transformer Tap 2 Kilo-Volt (KV) Rating FP
Read: 0, 0.01 to 1000.00
Write: 0.005 to 999.995
BE1-CDS With Modbus  Protocol 41
Global Setting Parameters

40606-07 Breaker Fail Time Delay LI


Read and Write: 100 to 999 Milli-seconds

40608-09 Programmable 51 Curve Constant A Delay FP


Read and Write: 0.0000 to 600.0000
40610-11 Programmable 51 Curve Constant B Delay FP
Read and Write: 0.0000 to 25.0000
40612-13 Programmable 51 Curve Constant C Delay FP
Read and Write: -1.0000 to +1.0000
40614-15 Programmable 51 Curve Constant N Delay FP
Read and Write: 0.5000 to 2.5000
40616-17 Programmable 51 Curve Constant R Delay FP
Read and Write: 0.0000 to 30.0000

40618 Input 1 Contact Recognition Time Delay SI


40619 Input 1 Contact Debounce Time Delay SI
40620 Input 2 Contact Recognition Time Delay SI
40621 Input 2 Contact Debounce Time Delay SI
40622 Input 3 Contact Recognition Time Delay SI
40623 Input 3 Contact Debounce Time Delay SI
40624 Input 4 Contact Recognition Time Delay SI
40625 Input 4 Contact Debounce Time Delay SI
40626 Input 5 Contact Recognition Time Delay SI
40627 Input 5 Contact Debounce Time Delay SI
40628 Input 6 Contact Recognition Time Delay SI
40629 Input 6 Contact Debounce Time Delay SI
40630 Input 7 Contact Recognition Time Delay SI
40631 Input 7 Contact Debounce Time Delay SI
40632 Input 8 Contact Recognition Time Delay SI
40633 Input 8 Contact Debounce Time Delay SI
Read and Write: 4 to 255 Milli-seconds

40746-870 Contiguous Poll Block Assignments INT


Read and Write:
0 if Unassigned
1 to 9874: Holding Register 40001 to 49874

40871 Setting Group Control On Time INT


Read and Write: 0 to 10 Milli-seconds

40872 Setting Group 1 Automatic Control Switch Time SI


40874 Setting Group 1 Automatic Control Return Time SI
40877 Setting Group 2 Automatic Control Switch Time SI
40879 Setting Group 2 Automatic Control Return Time SI
40882 Setting Group 3 Automatic Control Switch Time SI
40884 Setting Group 3 Automatic Control Return Time SI
Read and Write: 0 to 60 Milli-seconds

40873 Setting Group 1 Automatic Control Switch Level SI


40875 Setting Group 1 Automatic Control Return Level SI
40878 Setting Group 2 Automatic Control Switch Level SI
40880 Setting Group 2 Automatic Control Return Level SI
40883 Setting Group 3 Automatic Control Switch Level SI
40885 Setting Group 3 Automatic Control Return Level SI
Read and Write: 0 to 150%

42 BE1-CDS With Modbus Protocol


40876 Setting Group 1 Tracking Element INT
40881 Setting Group 2 Tracking Element INT
40886 Setting Group 3 Tracking Element INT
Read and Write: 0 to 8

Serial Port Setting Parameters

40962 Serial Port 0 Baud Rate INT


40971 Serial Port 1 Baud Rate INT
40980 Serial Port 2 Baud Rate INT
Read and Write:
0 – 300 Baud (Do not select for port 2 Modbus communications)
1 – 600 Baud (Do not select for port 2 Modbus communications)
2 – 1200 Baud
3 – 2400 Baud
4 – 4800 Baud
5 – 9600 Baud
6 – 19K Baud

40963 Serial Port 0 Relay Address INT


Read and Write: 0 only
40972 Serial Port 1 Relay Address INT
40981 Serial Port 2 Relay Address INT
Read and Write: 0 to 65,534

40964 Serial Port 0 Software Flow Control SI


40973 Serial Port 1 Software Flow Control SI
Read:
0 if XON / XOFF Control is disabled
1 if XON / XOFF Control is enabled
Write:
0 to disable XON / XOFF Control
1 to 255 to enable XON / XOFF Control
40982 Serial Port 2 Software Flow Control SI
Read and Write: 0 only (XON / XOFF Control fixed and disabled)

40965 Serial Port 0 Page Length SI


40974 Serial Port 1 Page Length SI
Read and Write:
0 for disabled
1 to 40 for number of lines / page
40983 Serial Port 2 Page Length SI
Not Supported

40966 Serial Port 0 Acknowledgement Format SI


40975 Serial Port 1 Acknowledgement Format SI
Read:
0 if No acknowledge
1 if Acknowledge enabled
Write:
0 for No acknowledge
1 to 255 to enable acknowledge
40984 Serial Port 2 Acknowledgement Format SI
Not Supported

40967 Serial Port 0 Echo Control SI


40976 Serial Port 1 Echo Control SI
40985 Serial Port 2 Echo Control SI
Not Supported
 Protocol
BE1-CDS With Modbus 43
40968 Serial Port 0 Modbus Parity SI
40977 Serial Port 1 Modbus Parity SI
Not Supported

40986 Serial Port 2 Modbus Parity SI


Read and Write:
0 for No parity
1 for Even parity
2 for Odd parity

40969 Serial Port 0 Modbus Remote Delay SI


40978 Serial Port 1 Modbus Remote Delay SI
Not Supported
40987 Serial Port 2 Modbus Remote Delay SI
Read and Write:
1 to 20: 10 to 200 Milli-seconds

40970 Serial Port 0 Modbus Stop Bits SI


40979 Serial Port 1 Modbus Stop Bits SI
Not Supported
40988 Serial Port 2 Modbus Stop Bits SI
Read and Write:
1 for One stop bit
2 for Two stop bits
40989 Password Security SI
Read and Write:
Default value is disabled
1 to enable Password Security.
When Password Security is enabled, relay parameters can be changed via modbus only if
access is obtained via the Access Password and Access Request holding registers, and
released via the Exit register with value 89 (ASCII character ‘Y’).

0 to disable Password Security.


When Password Security is disabled, no access is required (Access Password, Access
Request, and Exit holding registers have no effect) and no password protection is used.
Global Parameters, holding registers 40080 – 40099 ( ASCII command GF-PW), have no
effect on the modbus serial port, COM2.

System Data Setting Parameters

41019 System Frequency SI


Read and Write:
50 for 50 Hertz
60 for 60 Hertz

41020 Phase Rotation SI


Read and Write:
1 for ABC
2 for ACB

41021 Phase CT Ratio, CT CKT #1 INT


41022 Ground CT Ratio INT
Read and Write: 1 to 50,000
41023 Phase CT Ratio, CT CKT #2 INT
Read and Write: 1 to 50,000

41025 CT Connection, CT CKT #1 INT


41026 CT Connection, CT CKT #2 INT
44 BE1-CDS With Modbus Protocol
Read and Write: 0 to 2

41028 TX Connection, CT CKT #1 INT


41029 TX Connection, CT CKT #2 INT
Read and Write: 0 to 3

41031 Ground Source, CT CKT #1 INT


41032 Ground Source, CT CKT #2 INT
Read and Write: 0 to 1

Breaker Duty Setting Parameters

41092 Breaker Duty Type SI


Read and Write:
0 for Off
1 for Sum I, primary centi-amps
2 for Sum I², primary centi-amps

41093-94 Maximum Breaker Duty FP


Read and Write: 0 to 4.29E 09 Amps

41095 Breaker Duty CT CKT Number SI


Read and Write:
1 for Ckt #1
2 for Ckt #2

41096 Programmable Breaker Alarm #1 Mode INT


41099 Programmable Breaker Alarm #2 Mode INT
41102 Programmable Breaker Alarm #3 Mode INT
Read and Write:
0 for Disabled
1 for Percent duty
2 for Breaker operations
3 for Clearing time

41097-98 Programmable Breaker Alarm #1 Limit FP


41100-01 Programmable Breaker Alarm #2 Limit FP
41103-04 Programmable Breaker Alarm #3 Limit FP
Read and Write:
If mode is 0: Reads 0, Any value writes 0
If mode is 1: 0.00 to 100.00%
If mode is 2: 0 to 99,999
If mode is 3: 0, 20 to 1000 Milli-seconds

41105-09 Breaker Label ASC(10)


Read and Write of ASCII strings.

Transformer Duty Setting Parameters

41184 Transformer Duty Mode SI


Read and Write:
0 for Off
1 for Sum I, primary centi-amps
2 for Sum I², primary centi-amps

41185-86 Maximum Transformer Duty FP


Read and Write: 0 to 4.29E 09 Amps

41187 Transformer Duty CT CKT Number SI


 Protocol
BE1-CDS With Modbus 45
Read and Write:
1 for Ckt #1
2 for Ckt #2

41188 Programmable Transformer Alarm #1 Mode INT


41191 Programmable Transformer Alarm #2 Mode INT
41194 Programmable Transformer Alarm #3 Mode INT
Read and Write:
0 for Disabled
1 for Percent duty
2 for Through faults

41189-90 Programmable Transformer Alarm #1 Limit FP


41192-93 Programmable Transformer Alarm #2 Limit FP
41195-96 Programmable Transformer Alarm #3 Limit FP
Read and Write:
If mode is 0: Reads 0, Any value writes 0
If mode is 1: 0.00 to 100.00%
If mode is 2: 0 to 99,999

Relay Data Setting Parameters

41259-60 Phase Demand Alarm Level FP


41261-62 Neutral Demand Alarm Level FP
41263-64 Negative Sequence Demand Alarm Level FP
Read and Write: 0.00 to 16.00 Amps

41265 Major Alarm Mask MSBs BM(16)


41267 Minor Alarm Mask MSBs BM(16)
41269 Logic Alarm Mask MSBs BM(16)
Read and Write:
Bits 15 to 12 - Spare
Bit 11 - Logic = None alarm
Bit 10 - Transformer Alarm 3
Bit 9 - Transformer Alarm 2
Bit 8 - Transformer Alarm 1
Bit 7 - Fault Record Time Out
Bit 6 - Virtual Output 15 alarm
Bit 5 - Virtual Output 14 alarm
Bit 4 - Virtual Output 13 alarm
Bit 3 - Setting Group Change Active alarm
Bit 2 - Loss of IRIG-B sync or IRIG-B decode problem
Bit 1 - An override is active in one or more outputs
Bit 0 - EEPROM Non fatal error

41266 Major Alarm Mask LSBs BM(16)


41268 Minor Alarm Mask LSBs BM(16)
41270 Logic Alarm Mask LSBs BM(16)
Read and Write:
Bit 15 - User settings changed, ( 'EXIT' with 'Y' )
Bit 14 - Power reset alarm, hard reset of MPU
Bit 13 - Clock problem, real time clock has not been set
Bit 12 - Communicating failure alarm, read error on serial port
Bit 11 - Operating System Overload detected alarm
Bit 10 - Setting group override in effect
Bit 9 - Q demand alarm, excessive negative sequence unbalance
Bit 8 - Neutral demand alarm
Bit 7 - Phase demand alarm
Bit 6 - Breaker alarm #3
46 BE1-CDS With Modbus Protocol
Bit 5 - Breaker alarm #2
Bit 4 - Breaker alarm #1
Bit 3 - Password access lost alarm
Bit 2 - Differential alarm
Bit 1 - Breaker fail alarm
Bit 0 - Circuit Monitor alarm
41271 87T Differential Alarm INT
Read and Write: 50 to 100%

41272 Clock Format – Date ASC(1)


Read and Write:
M for mm/dd/yy format
D for dd/mm/yy format

41273 Clock Format – Time SI


Read and Write:
12 for 12 hour clock
24 for 24 hour clock

41274 Clock Format – Daylight Savings SI


Read and Write:
0 for disabling Daylight Savings
1 for enabling Daylight Savings

41275 Phase Demand Interval SI


41276 Neutral Demand Interval SI
41277 Negative Sequence Demand Interval SI
Read and Write: 0 to 60 minutes

41278 Phase Demand Calculation Method ASC(1)


41279 Neutral Demand Calculation Method ASC(1)
41280 Negative Sequence Demand Calculation Method ASC(1)
Read and Write: ASCII character ‘T’

41281 Phase Demand CT CKT Number ASC(1)


41283 Negative Sequence Demand CT CKT Number ASC(1)
Read and Write:
ASCII character ‘1’
ASCII character ‘2’
41282 Neutral Demand CT CKT Number ASC(1)
Read and Write:
ASCII character ‘1’
ASCII character ‘2’
ASCII character ‘G’

41284 Output Hold Mask BM(8)


Read and Write:
Bit 7 - Spare
Bit 6 - Output 6 Status
Bit 5 - Output 5 Status
Bit 4 - Output 4 Status
Bit 3 - Output 3 Status
Bit 2 - Output 2 Status
Bit 1 - Output 1 Status
Bit 0 - Output A Status

41286 Load Profile Interval SI


Read and Write: 1 to 60

 Protocol
BE1-CDS With Modbus 47
41287 Target Mask MSBs BM(16)
Read and Write:
Bit 15 - Spare
Bit 14 - Spare
Bit 13 - Spare
Bit 12 - 50TQ
Bit 11 - 50TN
Bit 10 - 50TC
Bit 9 - 50TB
Bit 8 - 50TA
Bit 7 - Spare
Bit 6 - Spare
Bit 5 - Spare
Bit 4 - 150TQ
Bit 3 - 150TN
Bit 2 - 150TC
Bit 1 - 150TB
Bit 0 - 150TA

41288 Target Mask Second MSBs BM(16)


Read and Write:
Bit 15 - Spare
Bit 14 - Spare
Bit 13 - Spare
Bit 12 - 250TQ
Bit 11 - 250TN
Bit 10 - 250TC
Bit 9 - 250TB
Bit 8 - 250TA
Bit 7 - Spare
Bit 6 - Spare
Bit 5 - Spare
Bit 4 - Spare
Bit 3 - Spare
Bit 2 - Spare
Bit 1 - Spare
Bit 0 - BF

41289 Target Mask Third MSBs BM(16)


Read and Write:
Bit 15 - Spare
Bit 14 - Spare
Bit 13 - Spare
Bit 12 - 51Q
Bit 11 - 51N
Bit 10 - 51C
Bit 9 - 51B
Bit 8 - 51A
Bit 7 - Spare
Bit 6 - Spare
Bit 5 - Spare
Bit 4 - 151Q
Bit 3 - 151N
Bit 2 - 151C
Bit 1 - 151B
Bit 0 - 151A

41290 Target Mask LSBs BM(16)


Read and Write:
Bit 15 - Spare
48 BE1-CDS With Modbus Protocol
Bit 14 - Spare
Bit 13 - Spare
Bit 12 - 251Q
Bit 11 - 251N
Bit 10 - 251C
Bit 9 - 251B
Bit 8 - 251A
Bit 7 - Spare
Bit 6 - 87ND
Bit 5 - 87RC
Bit 4 - 87RB
Bit 3 - 87RA
Bit 2 - 87UC
Bit 1 - 87UB
Bit 0 - 87UA

41291-94 Programmable Screen #1 ASC(7)


41295-98 Programmable Screen #2 ASC(7)
41299-302 Programmable Screen #3 ASC(7)
41303-06 Programmable Screen #4 ASC(7)
41307-10 Programmable Screen #5 ASC(7)
41311-14 Programmable Screen #6 ASC(7)
41315-18 Programmable Screen #7 ASC(7)
41319-22 Programmable Screen #8 ASC(7)
41323-26 Programmable Screen #9 ASC(7)
41327-30 Programmable Screen #10 ASC(7)
41331-34 Programmable Screen #11 ASC(7)
41335-38 Programmable Screen #12 ASC(7)
41339-42 Programmable Screen #13 ASC(7)
41343-46 Programmable Screen #14 ASC(7)
41347-50 Programmable Screen #15 ASC(7)
41351-54 Programmable Screen #16 ASC(7)
Read and Write: screen identifier. For example, the Output Status Screen would be 1.5.2

Custom Logic Setting Parameters

41465-68 User Custom Logic Name ASC(8)


Read: If programming, reads custom logic name; otherwise, reads active standard logic name.
Write: New custom logic name or standard logic name of logic scheme to be copied to custom
scheme.

41469-72 Current Active Logic Scheme ASC(8)


Read: Current active logic name.
Write: Name of logic scheme to which you desire to change.

41473-76 Custom Logic Name ASC(8)

Read: Custom logic name.

41477-80 Standard Logic #1 Name ASC(8)


Read: Standard logic name #1.

41481-84 Standard Logic #2 Name ASC(8)


Read: Standard logic name #2.

41485-88 Standard Logic #3 Name ASC(8)


Read: Standard logic name #3.

 Protocol
BE1-CDS With Modbus 49
41489-92 Standard Logic #4 Name ASC(8)
Read: Standard logic name #4.

41493-96 Standard Logic #5 Name ASC(8)


Read: Standard logic name #5.

41497-500 Standard Logic #6 Name ASC(8)


Read: Standard logic name #6.

41501-04 Standard Logic #7 Name ASC(8)


Read: Standard logic name #7.

System Labels And Id Setting Parameters

All are Read and Write of ASCII strings.

Report Parameters

47274-78 Model Number ASC(10)

47282-89 Application SW Version # / Date ASC(16)


47296-302 Boot SW Version # / Date ASC(14)
47310-16 Serial Number ASC(13)
47324-36 Style Number ASC(21)
47346-53 DSP SW Version # / Date ASC(16)
Read Only: ASCII strings

47362 COM1 Serial Port Relay Address INT


47363 COM2 Serial Port Relay Address INT
Read and Write: 0 to 65,534

47364 Date and Time – Day INT


Read and Write: any value (days since 01/01/1984).
47365-66 Date and Time – Milliseconds LI
Read and Write: 0 to 86,399,999 Milli-seconds

47367 System Status (Logic Var 0 to 15) BM(16)


Read only:
Bit 15 - 51Q tripped
Bit 14 - 251 neutral tripped
Bit 13 - 151 neutral tripped
Bit 12 - 51 neutral tripped
Bit 11 - 251 phase tripped
Bit 10 - 151 phase tripped
Bit 9 - 51 phase tripped
Bit 8 - 250TQ tripped
Bit 7 - 150TQ tripped
Bit 6 - 50TQ tripped
Bit 5 - 250T neutral tripped
Bit 4 - 150T neutral tripped
Bit 3 - 50T neutral tripped
Bit 2 - 250T phase tripped
Bit 1 - 150T phase tripped
Bit 0 - 50T phase tripped

47368 System Status (Logic Var 16 to 31) BM(16)


50 BE1-CDS With Modbus Protocol
Read only:
Bit 15 - Logic always false
Bit 14 - Setting Group 3 active
Bit 13 - Setting Group 2 active
Bit 12 - Setting Group 1 active
Bit 11 - Setting Group 0 active
Bit 10 - 162 tripped
Bit 9 - 62 tripped
Bit 8 - Spare
Bit 7 - Fifth harmonic inhibit
Bit 6 - Second harmonic inhibit
Bit 5 - 87U tripped
Bit 4 - 87R tripped
Bit 3 - 87ND tripped
Bit 2 - BF tripped
Bit 1 - 251Q tripped
Bit 0 - 151Q tripped

47369 System Status (Logic Var 32 to 47) BM(16)


Read only:
Bit 15 - Virtual Output 15 status
Bit 14 - Virtual Output 14 status
Bit 13 - Virtual Output 13 status
Bit 12 - Virtual Output 12 status
Bit 11 - Virtual Output 11 status
Bit 10 - Virtual Output 10 status
Bit 9 - Virtual Output 9 status
Bit 8 - Virtual Output 8 status
Bit 7 - Virtual Output 7 status
Bit 6 - Virtual Output 6 status
Bit 5 - Virtual Output 5 status
Bit 4 - Virtual Output 4 status
Bit 3 - Virtual Output 3 status
Bit 2 - Virtual Output 2 status
Bit 1 - Virtual Output 1 status
Bit 0 - Virtual Output A status

47370 System Status (Logic Var 48 to 63) BM(16)


Read only:
Bit 15 - 101 slip contact
Bit 14 - 101 close
Bit 13 - 101 trip
Bit 12 - Output circuit monitor
Bit 11 - Alarm logic
Bit 10 - Alarm minor
Bit 9 - Alarm major
Bit 8 - Spare
Bit 7 - Input 8 status
Bit 6 - Input 7 status
Bit 5 - Input 6 status
Bit 4 - Input 5 status
Bit 3 - Input 4 status
Bit 2 - Input 3 status
Bit 1 - Input 2 status
Bit 0 - Input 1 status

47371 System Status (Logic Var 64 to 79) BM(16)


Read only:
Bit 15 - 51Q picked-up
Bit 14 - 251 neutral picked-up
BE1-CDS With Modbus  Protocol 51
Bit 13 - 151 neutral picked-up
Bit 12 - 51 neutral picked-up
Bit 11 - 251 phase picked-up
Bit 10 - 151 phase picked-up
Bit 9 - 51 phase picked-up
Bit 8 - 250Q picked-up
Bit 7 - 150Q picked-up
Bit 6 - 50Q picked-up
Bit 5 - 250T neutral picked-up
Bit 4 - 150T neutral picked-up
Bit 3 - 50T neutral picked-up
Bit 2 - 250T phase picked-up
Bit 1 - 150T phase picked-up
Bit 0 - 50T phase picked-up

47372 System Status (Logic Var 80 to 95) BM(16)


Read only:
Bit 15 - 743
Bit 14 - 643
Bit 13 - 543
Bit 12 - 443
Bit 11 - 343
Bit 10 - 243
Bit 9 - 143
Bit 8 - 43
Bit 7 - Target reset key
Bit 6 - Alarm reset key
Bit 5 - Spare
Bit 4 - 87R picked-up
Bit 3 - 87ND picked-up
Bit 2 - BF picked-up
Bit 1 - 251Q picked-up
Bit 0 - 151Q picked-up

47373 Current Active Group Setting SI


Read only: 0 to 3

47374 Current Group Control Setting ASC(1)


Read only: ASCII character 0, 1, 2, 3, L

47375 Current Output Control Settings (OutputPulse0) MSBs BM(16)


Read only:
Bits 15 to 7 - Spare
Bit 6 - Output 6 pulse low
Bit 5 - Output 5 pulse low
Bit 4 - Output 4 pulse low
Bit 3 - Output 3 pulse low
Bit 2 - Output 2 pulse low
Bit 1 - Output 1 pulse low
Bit 0 - Output A pulse low

47376 Current Output Control Settings (OutputPulse1) LSBs BM(16)


Read only:
Bits 15 to 7 - Spare
Bit 6 - Output 6 pulse high
Bit 5 - Output 5 pulse high
Bit 4 - Output 4 pulse high
Bit 3 - Output 3 pulse high
Bit 2 - Output 2 pulse high
Bit 1 - Output 1 pulse high
52 BE1-CDS With Modbus Protocol
Bit 0 - Output A pulse high

47377 Current Output Control Settings (OutputLatch0) MSBs BM(16)


Read only:
Bits 15 to 7 - Spare
Bit 6 - Output 6 latch low
Bit 5 - Output 5 latch low
Bit 4 - Output 4 latch low
Bit 3 - Output 3 latch low
Bit 2 - Output 2 latch low
Bit 1 - Output 1 latch low
Bit 0 - Output A latch low

47378 Current Output Control Settings (OutputLatch1) LSBs BM(16)


Read only:
Bits 15 to 7 - Spare
Bit 6 - Output 6 latch high
Bit 5 - Output 5 latch high
Bit 4 - Output 4 latch high
Bit 3 - Output 3 latch high
Bit 2 - Output 2 latch high
Bit 1 - Output 1 latch high
Bit 0 - Output A latch high

47379 Current Output Contact Status BM(16)


Read only:
Bits 15 to 7 - Spare
Bit 6 - Output 6
Bit 5 - Output 5
Bit 4 - Output 4
Bit 3 - Output 3
Bit 2 - Output 2
Bit 1 - Output 1
Bit 0 - Output A

47380 Active Alarm Flags (SumFlags) MSBs BM(16)


Read only:
Bits 15 to 0 - Spare

47381 Active Alarm Flags (SumFlags) LSBs BM(16)


Read only:
Bits 15 to 11 - Spare
Bit 10 - DSP Failure
Bit 9 - Calibration defaults loaded
Bit 8 - Setting defaults loaded
Bit 7 - Watchdog failure
Bit 6 - Power Supply error
Bit 5 - Calibration error
Bit 4 - Analog failure
Bit 3 - EEPROM Read / Write Fatal error
Bit 2 - MPU Self-test error
Bit 1 - ROM (flash) Failure detected
Bit 0 - RAM Failure detected

47382 Active Alarm Flags (ProgAlarms) MSBs BM(16)


Read only:
Bits 15 to 12 - Spare
Bit 11 - Logic = None alarm
Bit 10 - Transformer alarm 3
Bit 9 - Transformer alarm 2
BE1-CDS With Modbus  Protocol 53
Bit 8 - Transformer alarm 1
Bit 7 - Fault Record Time Out
Bit 6 - Virtual Output 15 alarm
Bit 5 - Virtual Output 14 alarm
Bit 4 - Virtual Output 13 alarm
Bit 3 - Setting Group Change Active alarm
Bit 2 - Loss of IRIG-B sync or IRIG-B decode problem
Bit 1 - An override is active in one or more outputs
Bit 0 - EEPROM Non fatal error

47383 Active Alarm Flags (ProgAlarms) LSBs BM(16)


Read only:
Bit 15 - User settings changed, ( 'EXIT' with 'Y' )
Bit 14 - Power reset alarm, hard reset of MPU
Bit 13 - Clock problem, real time clock has not been set
Bit 12 - Communicating failure alarm, read error on serial port
Bit 11 - Operating System Overload detected alarm
Bit 10 - Setting group override in effect
Bit 9 - Excessive unbalance alarm, 50TQ unbalance output picked up
Bit 8 - Neutral demand alarm, neutral demand maximum exceeded
Bit 7 - Phase demand alarm, phase demand maximum exceeded
Bit 6 - Breaker alarm #3
Bit 5 - Breaker alarm #2
Bit 4 - Breaker alarm #1
Bit 3 - Password access lost alarm
Bit 2 - Differential alarm
Bit 1 - Breaker fail alarm
Bit 0 - Circuit Monitor alarm

47384 Target Status MSBs BM(16)


Read:
Bit 15 - Spare
Bit 14 - Spare
Bit 13 - Spare
Bit 12 - 50TQ
Bit 11 - 50TN
Bit 10 - 50TC
Bit 9 - 50TB
Bit 8 - 50TA
Bit 7 - Spare
Bit 6 - Spare
Bit 5 - Spare
Bit 4 - 150TQ
Bit 3 - 150TN
Bit 2 - 150TC
Bit 1 - 150TB
Bit 0 - 150TA
Write any value to any of 4 registers to reset all

47385 Target Status Second MSBs BM(16)


Read:
Bit 15 - Spare
Bit 14 - Spare
Bit 13 - Spare
Bit 12 - 250TQ
Bit 11 - 250TN
Bit 10 - 250TC
Bit 9 - 250TB
Bit 8 - 250TA
Bits 7 to 1 - Spare
54 BE1-CDS With Modbus Protocol
Bit 0 - BF
Write any value to any of 4 registers to reset all

47386 Target Status Third MSBs BM(16)


Read:
Bit 15 - Spare
Bit 14 - Spare
Bit 13 - Spare
Bit 12 - 51Q
Bit 11 - 51N
Bit 10 - 51C
Bit 9 - 51B
Bit 8 - 51A
Bit 7 - Spare
Bit 6 - Spare
Bit 5 - Spare
Bit 4 - 151Q
Bit 3 - 151N
Bit 2 - 151C
Bit 1 - 151B
Bit 0 - 151A
Write any value to any of 4 registers to reset all

47387 Target Status LSBs BM(16)


Read:
Bit 15 - Spare
Bit 14 - Spare
Bit 13 - Spare
Bit 12 - 251Q
Bit 11 - 251N
Bit 10 - 251C
Bit 9 - 251B
Bit 8 - 251A
Bit 7 - Spare
Bit 6 - 87ND
Bit 5 - 87RC
Bit 4 - 87RB
Bit 3 - 87RA
Bit 2 - 87UC
Bit 1 - 87UB
Bit 0 - 87UA
Write any value to any of 4 registers to reset all

47388 Current Breaker Status ASC(1)


Read only:
O for Open
C for Closed
D for Disabled (off)

47389-92 Current Active Logic ASC(8)


Read only: Current active logic name

47394-95 Breaker Contact Duty Log – Phase A FP


47396-97 Breaker Contact Duty Log – Phase B FP
47398-99 Breaker Contact Duty Log – Phase C FP
Read: If Breaker Duty Type = Off or Maximum Breaker Duty = 0, reads undefined floating point value
of 0xFFFFFFFF. Otherwise, reads 0.00 to 200.00%.
Write: 0.00 to 200.00%.

47400-01 Breaker Operation Counter LI


BE1-CDS With Modbus  Protocol 55
Read and Write:
0 to 99,999

47402-03 Transformer Duty Log Settings – Phase A FP


47404-05 Transformer Duty Log Settings – Phase B FP
47406-07 Transformer Duty Log Settings – Phase C FP
Read: If Transformer Duty Mode = Off or Maximum Transformer Duty = 0, reads undefined floating
point value of 0xFFFFFFFF. Otherwise, reads 0.00 to 200.00%.
Write: 0.00 to 200.00%.

47408-09 Transformer Through Faults Counter LI


Read and Write:
0 to 99,999

47410-11 Yesterday’s Peak Demand Current – Phase A FP


47415-16 Yesterday’s Peak Demand Current – Phase B FP
47420-21 Yesterday’s Peak Demand Current – Phase C FP
47425-26 Yesterday’s Peak Demand Current – Neutral FP
47430-31 Yesterday’s Peak Demand Current – Negative Seq FP
Read only: Any value (Amps)

47412 Yesterday’s Peak Demand Timestamp - Day INT


47417 Yesterday’s Peak Demand Timestamp - Day INT
47422 Yesterday’s Peak Demand Timestamp - Day INT
47427 Yesterday’s Peak Demand Timestamp - Day INT
47432 Yesterday’s Peak Demand Timestamp - Day INT
Read only: any value (days since 01/01/1984).

47413-14 Yesterday’s Peak Demand Timestamp – Millisecond LI


47418-19 Yesterday’s Peak Demand Timestamp – Millisecond LI
47423-24 Yesterday’s Peak Demand Timestamp – Millisecond LI
47428-29 Yesterday’s Peak Demand Timestamp – Millisecond LI
47433-34 Yesterday’s Peak Demand Timestamp – Millisecond LI
Read only: 0 to 86,399,999 Milli-seconds

47435-36 Today’s Peak Demand Current – Phase A FP


47440-41 Today’s Peak Demand Current – Phase B FP
47445-46 Today’s Peak Demand Current – Phase C FP
47450-51 Today’s Peak Demand Current – Neutral FP
47455-56 Today’s Peak Demand Current – Negative Seq FP
Read only: Any value (Amps)

47437 Today’s Peak Demand Timestamp - Day INT


47442 Today’s Peak Demand Timestamp - Day INT
47447 Today’s Peak Demand Timestamp - Day INT
47452 Today’s Peak Demand Timestamp - Day INT
47457 Today’s Peak Demand Timestamp - Day INT
Read only: any value (days since 01/01/1984).

47438-39 Today’s Peak Demand Timestamp – Millisecond LI


47443-44 Today’s Peak Demand Timestamp – Millisecond LI
47448-49 Today’s Peak Demand Timestamp – Millisecond LI
47453-54 Today’s Peak Demand Timestamp – Millisecond LI
47458-59 Today’s Peak Demand Timestamp – Millisecond LI
Read only: 0 to 86,399,999 Milli-seconds

47460-61 Peak Demand Current Since Reset – Phase A FP


47465-66 Peak Demand Current Since Reset – Phase B FP
47470-71 Peak Demand Current Since Reset – Phase C FP
47475-76 Peak Demand Current Since Reset – Neutral FP
56 BE1-CDS With Modbus Protocol
47480-81 Peak Demand Current Since Reset – Negative Seq FP
Read and Write: Any value (Amps)
47462 Peak Demand Since Reset Timestamp - Day INT
47467 Peak Demand Since Reset Timestamp - Day INT
47472 Peak Demand Since Reset Timestamp - Day INT
47477 Peak Demand Since Reset Timestamp - Day INT
47482 Peak Demand Since Reset Timestamp - Day INT
Read only: any value (days since 01/01/1984).

47463-64 Peak Demand Since Reset Timestamp – Millisecond LI


47468-69 Peak Demand Since Reset Timestamp – Millisecond LI
47473-74 Peak Demand Since Reset Timestamp – Millisecond LI
47478-79 Peak Demand Since Reset Timestamp – Millisecond LI
47483-84 Peak Demand Since Reset Timestamp – Millisecond LI
Read only: 0 to 86,399,999 Milli-seconds

47485 Trigger Differential Alarm Report SI


47486 Reset Logic Alarm Information SI
47487 Reset Major Alarm Information SI
47488 Reset Minor Alarm Information SI
47489 Reset Relay Alarm Information SI
47490 Reset Load Profile SI
47491 Clear Fault Log SI
47492 Trigger Fault Record SI
47493 Clear Events Report SI
Read: 0
Write: Any value will perform reset / trigger / clear.

47512 Fault Indicator SI


Read only: Most recent Fault number (1 – 255)

47513 Fault Template Status SI


Read only:
0: Template not valid for current Fault Selection (Refer to Register 40038). All FLT template
values will read 0.
1 to 255: Valid user selected Fault Number.

The following is the Fault Template (FLT)

47514 Fault Date and Time – Day INT


Read only: any value (days since 01/01/1984).

47515-16 Fault Date and Time – Milliseconds LI


Read only: 0 to 86,399,999 Milli-seconds

47517 Fault Event Type BM(16)


Read only:
Bit 0 for Breaker Fail
Bit 1 for Trip
Bit 2 for Logic
Bit 3 for Pickup
Bit 4 for Fault Record Trigger (Refer to Register 47492)

47518 Fault Active Group SI


Read only: 0 to 3

47519 Fault Targets MSBs BM(16)


Read only:
Bit 15 - Spare
 Protocol
BE1-CDS With Modbus 57
Bit 14 - Spare
Bit 13 - Spare
Bit 12 - 50TQ
Bit 11 - 50TN
Bit 10 - 50TC
Bit 9 - 50TB
Bit 8 - 50TA
Bit 7 - Spare
Bit 6 - Spare
Bit 5 - Spare
Bit 4 - 150TQ
Bit 3 - 150TN
Bit 2 - 150TC
Bit 1 - 150TB
Bit 0 - 150TA

47520 Fault Targets Second MSBs BM(16)


Read only:
Bit 15 - Spare
Bit 14 - Spare
Bit 13 - Spare
Bit 12 - 250TQ
Bit 11 - 250TN
Bit 10 - 250TC
Bit 9 - 250TB
Bit 8 - 250TA
Bits 7 to 1 - Spare
Bit 0 - BF

47521 Fault Targets Third MSBs BM(16)


Read only:
Bit 15 - Spare
Bit 14 - Spare
Bit 13 - Spare
Bit 12 - 51Q
Bit 11 - 51N
Bit 10 - 51C
Bit 9 - 51B
Bit 8 - 51A
Bit 7 - Spare
Bit 6 - Spare
Bit 5 - Spare
Bit 4 - 151Q
Bit 3 - 151N
Bit 2 - 151C
Bit 1 - 151B
Bit 0 - 151A

47522 Fault Targets LSBs BM(16)


Read only:
Bit 15 - Spare
Bit 14 - Spare
Bit 13 - Spare
Bit 12 - 251Q
Bit 11 - 251N
Bit 10 - 251C
Bit 9 - 251B
Bit 8 - 251A
Bit 7 - Spare
Bit 6 - 87ND
58 BE1-CDS With Modbus Protocol
Bit 5 - 87RC
Bit 4 - 87RB
Bit 3 - 87RA
Bit 2 - 87UC
Bit 1 - 87UB
Bit 0 - 87UA

47524 Fault Clearing Time Status SI


Read only:
0 if Valid Fault Clearing Time (Registers 47525-26) value
1 if No pickup
2 if N/A; Out of range

47525-26 Fault Clearing Time FP


Read only:
0 if Fault Clearing Time Status is not 0 (not valid).
Time (xxx.xxx) in Seconds if Fault Clearing Time Status is 0 (valid).

47527 Fault Breaker Operate Time Status SI


Read only:
0 if Valid Fault Breaker Operate Time (Registers 47528-29) value
1 if Unknown
2 if N/A; Out of range
3 if No operation
4 if Disabled

47528-29 Fault Breaker Operate Time FP


Read only:
0 if Fault Breaker Operate Time Status is not 0 (not valid).
Time (xxx.xxx) in Seconds if Fault Breaker Operate Time Status is 0 (valid).

47530-31 Fault CT CKT #1 Phase A Current Magnitude FP


47533-34 Fault CT CKT #1 Phase B Current Magnitude FP
47536-37 Fault CT CKT #1 Phase C Current Magnitude FP
47539-40 Fault CT CKT #1 Residual Current Magnitude FP
47542-43 Fault CT CKT #1 Negative Seq. Current Magnitude FP
47544-45 Fault CT CKT #2 Phase A Current Magnitude FP
47547-48 Fault CT CKT #2 Phase B Current Magnitude FP
47550-51 Fault CT CKT #2 Phase C Current Magnitude FP
47553-54 Fault CT CKT #2 Residual Current Magnitude FP
47556-57 Fault CT CKT #2 Negative Seq. Current Magnitude FP
47572-73 Fault Ground Current Magnitude FP
Read only: Value in Amps

47532 Fault CT CKT #1 Phase A Angle INT


47535 Fault CT CKT #1 Phase B Angle INT
47538 Fault CT CKT #1 Phase C Angle INT
47541 Fault CT CKT #1 Residual Angle INT
47546 Fault CT CKT #2 Phase A Angle INT
47549 Fault CT CKT #2 Phase B Angle INT
47552 Fault CT CKT #2 Phase C Angle INT
47555 Fault CT CKT #2 Residual Angle INT
47574 Fault Ground Angle INT
Read only: 0 to 359 Degrees

The following is the Report Template (RPT)

47595-719 Report Text


Read only: ASCII string ( Illegal message response generated for invalid Report Focus value ).
 Protocol
BE1-CDS With Modbus 59
Metering Parameters

49720 Part Number INT


Read only: 0 to 999

49721-22 Measured Frequency FP


Read only: Value in Hertz

49723-24 Ground Current Magnitude FP


49726-27 CT CKT #1 Phase A Current Magnitude FP
49729-30 CT CKT #1 Phase B Current Magnitude FP
49732-33 CT CKT #1 Phase C Current Magnitude FP
49735-36 CT CKT #1 Residual Current Magnitude FP
49738-39 CT CKT #1 Negative Sequence Current Magnitude FP
49740-41 CT CKT #2 Phase A Current Magnitude FP
49743-44 CT CKT #2 Phase B Current Magnitude FP
49746-47 CT CKT #2 Phase C Current Magnitude FP
49749-50 CT CKT #2 Residual Current Magnitude FP
49752-53 CT CKT #2 Negative Sequence Current Magnitude FP
Read only: Value in Amps. If not applicable, reads undefined floating point value of 0xFFFFFFFF.

49725 Ground Angle INT


49728 CT CKT #1 Phase A Angle INT
49731 CT CKT #1 Phase B Angle INT
49734 CT CKT #1 Phase C Angle INT
49737 CT CKT #1 Residual Angle INT
49742 CT CKT #2 Phase A Angle INT
49745 CT CKT #2 Phase B Angle INT
49748 CT CKT #2 Phase C Angle INT
49751 CT CKT #2 Residual Angle INT
Read only: 0 to 359 Degrees

49782-83 CT CKT #1 Differential per Unit Phase A Current FP


49785-86 CT CKT #2 Differential per Unit Phase A Current FP
49791-92 Phase A Differential Operating Current FP
49793-94 CT CKT #1 Differential per Unit Phase B Current FP
49796-97 CT CKT #2 Differential per Unit Phase B Current FP
49802-03 Phase B Differential Operating Current FP
49804-05 CT CKT #1 Differential per Unit Phase C Current FP
49807-08 CT CKT #2 Differential per Unit Phase C Current FP
49813-14 Phase C Differential Operating Current FP
49815-16 Differential per Unit Ground Current FP
49818-19 CT CKT #1 Differential per Unit Residual Current FP
49821-22 CT CKT #2 Differential per Unit Residual Current FP
49827-28 Ground Differential Operating Current FP
Read only: Value in Amps XTAP. If not applicable, reads undefined floating point value of
0xFFFFFFFF.

49784 CT CKT #1 Phase A Differential Compensation Angle INT


49787 CT CKT #2 Phase A Differential Compensation Angle INT
49795 CT CKT #1 Phase B Differential Compensation Angle INT
49798 CT CKT #2 Phase B Differential Compensation Angle INT
49806 CT CKT #1 Phase C Differential Compensation Angle INT
49809 CT CKT #2 Phase C Differential Compensation Angle INT
49817 Ground Differential Compensation Angle INT
49820 CT CKT #1 Residual Differential Compensation Angle INT
49823 CT CKT #2 Residual Differential Compensation Angle INT
60 BE1-CDS With Modbus Protocol
Read only: 0 to 359 Degrees

49829 Phase A Differential Second Harmonic Percentage INT


49830 Phase B Differential Second Harmonic Percentage INT
49831 Phase C Differential Second Harmonic Percentage INT
49832 Phase A Differential Fifth Harmonic Percentage INT
49833 Phase B Differential Fifth Harmonic Percentage INT
49834 Phase C Differential Fifth Harmonic Percentage INT
Read only: Values in %IOP

49835-54 Error Details ASC(40)


Read only: ASCII string

49875-999 Contiguous Poll Block Mixed


Read Only: Mixed values.

 Protocol
BE1-CDS With Modbus 61
ASCII COMMAND VERSUS MODBUS REGISTER CROSS REFERENCE

ASCII Command Modbus Registers


A=<password> 40002-40005
CO-101 40136
CO-43 40120
CO-143 40122
CO-243 40124
CO-343 40126
CO-443 40128
CO-543 40130
CO-643 40132
CO-743 40134
CO-GROUP=<settings group> 40118
CO-OUT1 40142
CO-OUT2 40144
CO-OUT3 40146
CO-OUT4 40148
CO-OUT5 40150
CO-OUT6 40152
CO-OUTA 40140
CO-OUTALL 40138
CS-101 40135
CS-43 40119
CS-143 40121
CS-243 40123
CS-343 40125
CS-443 40127
CS-543 40129
CS-643 40131
CS-743 40133
CS-GROUP=<settings group> 40117
CS-OUT1 40141
CS-OUT2 40143
CS-OUT3 40145
CS-OUT4 40147
CS-OUT5 40149
CS-OUT6 40151
CS-OUTA 40139
CS-OUTALL 40137
EXIT 40001
GS-PWC=<Control password>,<Control path> 40090-40093,40094
GS-PWG=<Global password>,<Global path> 40080-40083,40084
GS-PWR=<Report password>,<Report path> 40095-40098,40099
GS-PWS=<Settings password>,<Settings path> 40085-40088,40089
M1-IA 49726-49727,49728
M1-IB 49729-49730,49731
M1-IC 49732-49733,49734
M1-IN 49735-49736,49737
M1-IQ 49738-49739
M2-IA 49740-49741,49742
M2-IB 49743-49744,49745
M2-IC 49746-49747,49748
M2-IN 49749-49750,49751
M2-IQ 49752-49753
M-FREQ 49721-49722
M-IG 49723-49724,49725
MD-IA1COMP 49782-49783,49784

62 BE1-CDS With Modbus Protocol


ASCII Command Modbus Registers
MD-IA2COMP 49785-49786,49787
MD-IAOP 49791-49792
MD-IB1COMP 49793-49794,49795
MD-IB2COMP 49796-49797,49798
MD-IBOP 49802-49803
MD-IC1COMP 49804-49805,49806
MD-IC2COMP 49807-49808,49809
MD-ICOP 49813-49814
MD-IGCOMP 49815-49816,49817
MD-IN1COMP 49818-49819,49820
MD-IN2COMP 49821-49822,49823
MD-INOP 49827-49828
MD-IA2ND 49829
MD-IA5TH 49832
MD-IB2ND 49830
MD-IB5TH 49833
MD-IC2ND 49831
MD-IC5TH 49834
RA-MAJ 47595-47719,40039
RA-MAJ=0 47487
RA-LGC 47595-47719,40039
RA-LGC=0 47486
RA-MIN 47595-47719,40039
RA-MIN=0 47488
RA-REL 47595-47719,40039
RA-REL=0 47489
RB-DUTYA=<% of duty> 47394-47395
RB-DUTYB=<% of duty> 47396-47397
RB-DUTYC=<% of duty> 47398-47399
RB-OPCNTR=<number of operations> 47400-47401
RD-PIA 47460-47461,47463-47464,47462
RD-PIB 47465-47466,47468-47469,47467
RD-PIC 47470-47471,47473-47474,47472
RD-PIN 47475-47476,47478-47479,47477
RD-PIQ 47480-47481,47483-47484,47482
RD-TIA 47435-47436,47438-47439,47437
RD-TIB 47440-47441,47443-47444,47442
RD-TIC 47445-47446,47448-47449,47447
RD-TIN 47450-47451,47453-47454,47452
RD-TIQ 47455-47456,47458-47459,47457
RD-YIA 47410-47411,47413-47414,47412
RD-YIB 47415-47416,47418-47419,47417
RD-YIC 47420-47421,47423-47424,47422
RD-YIN 47425-47426,47428-47429,47427
RD-YIQ 47430-47431,47433-47434,47432
RF 47595-47719,40039
RF-# 47595-47719,40039,40040
RF-NEW 47595-47719,40039
RF=0 47491
RF=TRIG 47492
RG-DATE=<date> 47364
RG-STAT 47367-47383,47388-47392
RG-TARG 47384-47385
RG-TIME=<time> 47365-47366
RG-VER 47274-47278,47324-47334,47282-47289,47296-
47302,47310-47316
RG-ADDR1 47362
RG-ADDR2 47363
RG-GRPACTIVE 47373
 Protocol
BE1-CDS With Modbus 63
ASCII Command Modbus Registers
RG-GRPCNTRL 47374
RG-LOGIC 47389
RG-OUTCNTRL 47375-47376,47377-47378
RG-OUTSTAT 47379
RS 47595-47719,40039
RS-# 47595-47719,40039,40040
RS-F# 47595-47719,40039,40040
RS-NEW 47595-47719,40039
RS=0 47493
S#-50TN=<pickup>,<time delay> 40273-40274,40275-40276
S#-50TP=<pickup>,<time delay> 40269-40270,40271-40272
S#-50TQ=<pickup>,<time delay> 40277-40278,40279-40280
S#-150TN=<pickup>,<time delay> 40285-40286,40287-40288
S#-150TP=<pickup>,<time delay> 40281-40282,40283-40284
S#-150TQ=<pickup>,<time delay> 40289-40290,40291-40292
S#-250TN=<pickup>,<time delay> 40297-40298,40299-40300
S#-250TP=<pickup>,<time delay> 40293-40294,40295-40296
S#-250TQ=<pickup>,<time delay> 40301-40302,40303-40304
S#-51N=<pickup>,<time dial>,<curve> 40311-40312,40313-40314,40315-40316
S#-51P=<pickup>,<time dial>,<curve> 40305-40306,40307-40308,40309-40310
S#-51Q=<pickup>,<time dial>.<curve> 40317-40318,40319-40320,40321-40322
S#-151N=<pickup>,<time dial>.<curve> 40329-40330,40331-40332,40333,40334
S#-151P=<pickup>,<time dial>.<curve> 40323-40324,40325-40326,40327-40328
S#-151Q=<pickup>,<time dial>.<curve> 40335-40336,40337-40338,40339-40340
S#-251N=<pickup>,<time dial>.<curve> 43047-40348,40379-40350,40351,40352
S#-251P=<pickup>,<time dial>.<curve> 40341-40342,40343-40344,40345-40346
S#-251Q=<pickup>,<time dial>.<curve> 40353-40354,40355-40356,40357-40358
S#-TAP87 40392-49393,40394-40395,40396-40397,40398-
40399,40400-40401
S#-87 40375-40376,40377,40378-40379,40380-40381,
40382,40383
S#-87ND 40384-40385,40386-40387,40388-40389,40390,40391
S#-62=<time delay 1>,<time delay 2> 40359-40360,40361-40362
S#-162=<time delay 1>,<time delay 2> 40363-40364,40365-40366
SA-BKR1=<mode>,<alarm limit> 41096,41097-41098
SA-BKR2=<mode>,<alarm limit> 41099,41100-41101
SA-BKR3=<mode>,<alarm limit> 41102,41103-41104
SA-DIN=<alarm level> 41261-41262
SA-DIP=<alarm level> 41259-41260
SA-DIQ=<alarm level> 41263-41264
SA-LGC=<alarm number> 41269-41270
SA-MAJ=<alarm number> 41265-41266
SA-MIN=<alarm number> 41267-41268
SA-RESET=<reset Alarm Logic> 41419-41422,41427-41430
SA-DIFF 47485
SA-TX1 41188,41189-41190
SA-TX2 41191,41192-41193
SA-TX3 41194,41195-41196
ST-DUTY=<mode>,<dmax>,<CT circuit #>,<blk txfrmr 41184,41185-41186,41187,41197-41202,41205-41210
logic>
SB-DUTY=<mode>,<dmax.>,<CT circuit #>,<blk bkr 41092,41093-41094,41095,41110-41115,41118-41123
logic>
SB-LOGIC=<breaker close logic equation>, <breaker 41126-41129,41134-41137,41142-41149
label>
SG-CLK=<date format>,<time format><dst enable> 41272,41273,41274
SG-COM0=<baud rate>,<flow control>, 40962,40964,40965,40966
<page length>,<ack>

64 BE1-CDS With Modbus Protocol


ASCII Command Modbus Registers
SG-COM1=<baud rate>,<relay address>, 40971,40972,40973,40974,40975
<flow control>,<page length>,<ack>
SG-COM2=<baud rate>,<relay address>,,,,, 40980,40981,40986,40987,40988
<parity>,<remote delay>,<stop bits>
SG-CT1=<ratio>,<CT connection>, 41021,41025,41028,41031
<TX connection>,<ground source>
SG-CT2=<ratio>,<CT connection>, 41023,41026,41029,41032
<TX connection>,<ground source>
SG-CTG=<ratio> 41022
SG-DIN=<alarm interval>,<calculation method>, 41276,41279,41282
<CT circuit number>
SG-DIP=<alarm interval>,<calculation method>, 41275,41278,41281
<CT circuit number>
SG-DIQ=<alarm interval>,<calculation method>, 41277,41280,41283
<CT circuit number>
SG-DSPN=<filter> 41436
SG-DSPP=<filter> 41435
SG-FREQ=<frequency> 41019
SG-HOLD=<output hold enable> 41284
SG-ID1=<relay ID> 43438-43452
SG-ID2=<station ID> 43453-43467
SG-ID3=<station ID> 43476-43482
SG-ID4=<station ID> 43482-43497
SG-CLK=<date format>,<clock format><daylight 41272,41273,41274
savings format>
SG-IN1=<input recognition>,<input debounce > 40619,40620
SG-IN2=<input recognition>,<input debounce > 40620,40621
SG-IN3=<input recognition>,<input debounce > 40622,40623
SG-IN4=<input recognition>,<input debounce > 40624,40625
SG-IN5=<input recognition>,<input debounce > 40626,40627
SG-IN6=<input recognition>,<input debounce > 40628,40629
SG-IN7=<input recognition>,<input debounce > 40630,40631
SG-IN8=<input recognition>,<input debounce > 40632,40633
SG-PHROT=<rotation sequence> 41020
SG-SCREEN10=<menu screen> 41327-41330
SG-SCREEN11=<menu screen> 41331-41334
SG-SCREEN12=<menu screen> 41335-41338
SG-SCREEN13=<menu screen> 41339-41342
SG-SCREEN14=<menu screen> 41343-41346
SG-SCREEN15=<menu screen> 41347-41350
SG-SCREEN16=<menu screen> 41351-41354
SG-SCREEN1=<menu screen> 41291-41294
SG-SCREEN2=<menu screen> 41295-41298
SG-SCREEN3=<menu screen> 41299-41302
SG-SCREEN4=<menu screen> 41303-41306
SG-SCREEN5=<menu screen> 41307-41310
SG-SCREEN6=<menu screen> 41311-41314
SG-SCREEN7=<menu screen> 41315-41318
SG-SCREEN8=<menu screen> 41319-41322
SG-SCREEN9=<menu screen> 41323-41326
SG-SGCON=<time> 40871
SG-TARG=<target list>,<reset Targ Logic> 41287-41290,41403-41408,41411-41416
SG-TRIG=<trip trigger logic equation>,<pu trigger logic 41355-41360,41363-41368,41371-41376,41379-
equation>,<logic trigger logic equation> 41384,41387-41392,41395-41400
SL-43=<mode> 42091
SL-143=<mode> 42092
SL-243=<mode> 42093
SL-343=<mode> 42094

 Protocol
BE1-CDS With Modbus 65
ASCII Command Modbus Registers
SL-443=<mode> 42095
SL-543=<mode> 42096
SL-643=<mode> 42097
SL-743=<mode> 42098
SL-101=<mode> 42099
SL-CKTMON=<mode><monitor logic>, 42100,42101-42106,42109-42114,42117-
<status logic> 42122,42125-42130
SL-87=<mode>,<block logic equation> 41976,41977-41982,41985-41990
SL-87ND=<mode>,<block logic equation> 41993,41994-41999,42002-42007
SL-150TN=<mode>,<block logic equation> 41573,41574-41579,41582-41587
SL-150TP=<mode>,<block logic equation> 41556,41557-41562,41565-41570
SL-150TQ=<mode>,<block logic equation> 41590,41591-41596,41599-41604
SL-250TN=<mode>,<block logic equation> 41624,41625-41630,41633-41638
SL-250TP=<mode>,<block logic equation> 41607,41608-41613,41616-41621
SL-250TQ=<mode>,<block logic equation> 41641,41642-41647,41650-41655
SL-162=<mode>,<ini logic equation>,<block logic 41877,41878-41883,41886-41891,41894-899,41902-
equation> 41907
SL-50TN=<mode>,<block logic equation> 41522,41523-41528,41531-41536
SL-50TP=<mode>,<block logic equation> 41505,41506-41511,41514-41519
SL-50TQ=<mode>,<block logic equation> 41539,41540-41545,41548-41553
SL-51N=<mode>,<block logic equation> 41708,41709-41714,41717-41722
SL-51P=<mode>,<block logic equation> 41691,41692-41697,41700-41705
SL-51Q=<mode>,<block logic equation> 41725,41726-41731,41734-41739
SL-151N=<mode>,<block logic equation> 41759,41760-41765,41768-41773
SL-151P=<mode>,<block logic equation> 41742,41743-41748,41751-41756
SL-151Q=<mode>,<block logic equation> 41776,41777-41782,41785-41790
SL-251N=<mode>,<block logic equation> 41810,41811-41816,41819-41824
SL-251P=<mode>,<block logic equation> 41793,41794-41799,41802-41807
SL-251Q=<mode>,<block logic equation> 41827,41828-41833,41836-41841
SL-62=<mode>,< ini logic equation>, 41844,41845-41850,41853-41858,41861-
<block logic equation> 41866,41869-41874
SL-BF=<mode>,<ini logic equation>, 41658,41659-41664,41667-41672,41675-
<block logic equation> 41680,41683-41688
SL-GROUP=<mode>,<D0 logic equation>, 42010,42027-42032,42035-42040,42043-
<D1 logic equation>,<D2 logic equation>, 42048,42051-42056,42059-42064,42067-
<D3 logic equation>,<auto logic equation> 42072,42075-42080,42083-42088,42011-
42016,42019-42024
SL-N=<name> 41465-41468
SL-VOA=<boolean logic equation> 42133,42134-42139,42142-42147,42150-42155,
42158-42163,42166-42171,42174-42179,42182-
42187,42190-42195
SL-VO1=<boolean logic equation> 42198,42199-42204,42207-42212,42215-42220,
42223-42228,42231-42236,42239-42244,42247-
42252,42255-42260
SL-VO2=<boolean logic equation> 42263,42264-42269,42272-42277,42280-42285,
42288-42293,42296-42301,42304-42309,42312-
42317,42320-42325
SL-VO3=<boolean logic equation> 42328,42329-42334,42337-42342,42345-42350,
42353-42358,42361-42366,42369-42374,42377-
42382,42385-42390
SL-VO4=<boolean logic equation> 42393,42394-42399,42402-42407,42410-42415,
42418-42423,42426-42431,42434-42439,42442-
42447,42450-42455
SL-VO5=<boolean logic equation> 42458,42459-42464,42467-42472,42475-42480,
42483-42488,42491-42496,42499-42504,42507-
42512,42515-42520
SL-VO6=<boolean logic equation> 42523,42524-42529,42532-42537,42540-42545,
42548-42553,42556-42561,42564-42569,42572-
42577,42580-42585
66 BE1-CDS With Modbus Protocol
ASCII Command Modbus Registers
SL-VO7=<boolean logic equation> 42588,42589-42594,42597-42602,42605-42610,
42613-42618,42621-42626,42629-42634,42637-
42642,42645-42650
SL-VO8=<boolean logic equation> 42653,42654-42659,42662-42667,42670-42675,
42678-42683,42686-42691,42694-42699,42702-
42707,42710-42715
SL-VO9=<boolean logic equation> 42718,42719-42724,42727-42732,42735-42740,
42743-42748,42751-42756,42759-42764,42767-
42772,42775-42780
SL-VO10=<boolean logic equation> 42783,42784-42789,42792-42797,42800-42805,
42808-42813,42816-42821,42824-42829,42832-
42837,42840-42845
SL-VO11=<boolean logic equation> 42848,42849-42854,42857-42862,42865-42870,
42873-42878,42881-42886,42889-42894,42897-
42902,42905-42910
SL-VO12=<boolean logic equation> 42913,42914-42919,42922-42927,42930-42935,
42938-42943,42946-42951,42954-42959,42962-
42967,42970-42975
SL-VO13=<boolean logic equation> 42978,42979-42984,42987-42992,42995-43000,
43003-42008,43011-43016,43019-42024,43027-
42032,43035-42040
SL-VO14=<boolean logic equation> 43043,43044-42049,43052-42057,43060-42065,
43068-42073,43076-43081,43084-42089,43092-
42097,43100-42105
SL-VO15=<boolean logic equation> 43108,43109-42114,43117-42122,43125-42130,
43133-42138,43141-43146,43149-42154,43157-
42162,43165-42170
SL: <custom logic>,<logic1>,<logic2>,<logic3>, 41473-41478,41477-41482,41481-41486,41485-
<logic4>,<logic5>,<logic6>,<logic7> 41490,41489-41494,41493-41498,41497-41502,
41501-41506
SN-43=<name>,<true label>,<false label> 43498-43502,43503-43506,43507-43510
SN-143=<name>,<true label>,<false label> 43511-43515,43516-43519,43520-43523
SN-243=<name>,<true label>,<false label> 43524-43528,43529-43532,43533-43536
SN-343=<name>,<true label>,<false label> 43537-43541,43542-43545,43546-43549
SN-443=<name>,<true label>,<false label> 43550-43554,43555-43558,43559-43562
SN-543=<name>,<true label>,<false label> 43563-43567,43568-43571,43572-43575
SN-643=<name>,<true label>,<false label> 43576-43580,43581-43584,43585-43588
SN-743=<name>,<true label>,<false label> 43589-43593,43594-43597,43598-43601
SN-IN1=<name>,<true label>,<false label> 43849-43853,43854-43857,43858-43861
SN-IN2=<name>,<true label>,<false label> 43862-43866,43867-43870,43871-43874
SN-IN3=<name>,<true label>,<false label> 43875-43879,43880-43883,43884-43887
SN-IN4=<name>,<true label>,<false label> 43888-43892,43893-43896,43897-43900
SN-IN5=<name>,<true label>,<false label> 43901-43905,43906-43909,43910-43913
SN-IN6=<name>,<true label>,<false label> 43914-43918,43919-43922,43923-43926
SN-IN7=<name>,<true label>,<false label> 43927-43931,43932-43935,43936-43939
SN-IN8=<name>,<true label>,<false label> 43940-43944,43945-43948,43949-43952
SN-VOA=<name>,<true label>,<false label> 43602-43606,43607-43610,43611-43614
SN-VO1=<name>,<true label>,<false label> 43615-43619,43620-43623,43624-43627
SN-VO2=<name>,<true label>,<false label> 43628-43632,43633-43636,43637-43640
SN-VO3=<name>,<true label>,<false label> 43641-43645,43646-43649,43650-43653
SN-VO4=<name>,<true label>,<false label> 43654-43658,43659-43662,43663-43666
SN-VO5=<name>,<true label>,<false label> 43667-43671,43672-43675,43676-43679
SN-VO6=<name>,<true label>,<false label> 43680-43684,43685-43688,43689-43692
SN-VO7=<name>,<true label>,<false label> 43693-43697,43698-43701,43702-43705
SN-VO8=<name>,<true label>,<false label> 43706-43710,43711-43714,43715-43718
SN-VO9=<name>,<true label>,<false label> 43719-43723,43724-43727,43728-43731
SN-VO10=<name>,<true label>,<false label> 43732-43736,43737-43740,43741-43744
SN-VO11=<name>,<true label>,<false label> 43745-43749,43750-43753,43754-43757
SN-VO12=<name>,<true label>,<false label> 43758-43762,43763-43766,43767-43770

 Protocol
BE1-CDS With Modbus 67
ASCII Command Modbus Registers
SN-VO13=<name>,<true label>,<false label> 43771-43775,43776-43779,43780-43783
SN-VO14=<name>,<true label>,<false label> 43784-43788,43789-43792,43793-43796
SN-VO15=<name>,<true label>,<false label> 43797-43801,43802-43805,43806-43809
SP-BF=<time delay> 40606-40607
SP-CURVE=<a>,<b>,<c>,<n>,<r> 40608-40609,40610-40611,40612-40613,40614-
40615,40616-40617
SP-GROUP1=<switch time>,<switch level>,<return 40872,40873,40874,40875,40876
time>,<return level>,<prot element>
SP-GROUP2=<switch time>,<switch evel>,<return 40877,40878,40879,40880,40881
time>,<return level>,,<prot element>
SP-GROUP3=<switch time>,<switch evel>,<return 40882,40883,40884,40885,40886
time>,<return level>,<prot element>

68 BE1-CDS With Modbus Protocol


ROUTE 143, BOX 269
HIGHLAND, IL 62249 USA
http://www.basler.com, info@basler.com
PHONE 618-654-2341 FAX 618-654-2351
INSTRUCTION MANUAL
for

BE1-CDS
CURRENT DIFFERENTIAL SYSTEM

DISTRIBUTED NETWORK PROTOCOL


(DNP V3.00)

Publication Number: 9 3139 00 992


Revision : A 04/2000
INTRODUCTION

This manual provides detailed information for the BE1-CDS Current Differential System with the
Distributed Network Protocol (DNP V3.00).

PRODUCT REVISION HISTORY


The following information provides a historical summary of the changes made to this manual. All
revisions are listed in chronological order.

Revision - Date Change


None – Nov. 1999 Initial release. This manual (9 3139 00 992) was initially released for the
Modbus™ protocol. To coordinate with the AS-400 data base and the
published product bulletin, the Modbus™ Instruction Manual publication
number was changed to 9 3139 00 991. (For more information see ECO
8891.)
A – April 2000 Changed the complete manual to the DNP protocol. With ECO 8969, upped
the revision level on 9 3139 00 991 and 9 3139 00 992 to Rev A. Now the
991 is for Modbus™ protocol and the 992 is for DNP protocol.

BE1-CDS DNP Protocol i


First Printing: November 1999

Printed in USA

© 1999, 2000 Basler Electric Co., Highland, IL 62249

April 2000

CONFIDENTIAL INFORMATION
OF BASLER ELECTRIC COMPANY, HIGHLAND, IL. IT IS LOANED FOR
CONFIDENTIAL USE, SUBJECT TO RETURN ON REQUEST, AND WITH THE
MUTUAL UNDERSTANDING THAT IT WILL NOT BE USED IN ANY MANNER
DETRIMENTAL TO THE INTEREST OF BASLER ELECTRIC COMPANY.

It is not the intention of this manual to cover all details and variations in equipment, nor
does this manual provide data for every possible contingency regarding installation or
operation. The availability and design of all features and options are subject to
modification without notice. Should further information be required, contact Basler
Electric Company, Highland, Illinois.

BASLER ELECTRIC
ROUTE 143, BOX 269
HIGHLAND, IL 62249 USA
http://www.basler.com, info@basler.com
PHONE 618-654-2341 FAX 618-654-2351
ii DNP Protocol BE1- CDS
CONTENTS
SECTION 1 • GENERAL INFORMATION .................................................................................................1-1
INTRODUCTION ....................................................................................................................................1-1
REFERENCES .......................................................................................................................................1-1
SECTION 2 • DNP V3.00 DEVICE PROFILE DOCUMENT ......................................................................2-1

SECTION 3 • IMPLEMENTATION TABLE ...............................................................................................3-1


DNP V3.00 IMPLEMENTATION TABLE ................................................................................................3-1
SECTION 4 • DNP V3.00 CONFIGURATION PARAMETERS .................................................................4-1
DNP CONFIGURATION PARAMETERS ...............................................................................................4-1
SECTION 5 • DNP V3.00 POINT LIST ......................................................................................................5-1
BINARY INPUT POINTS ........................................................................................................................5-1
BINARY OUTPUT STATUS POINTS AND CONTROL RELAY OUTPUT BLOCKS .............................5-5
ANALOG INPUTS...................................................................................................................................5-7
ANALOG OUTPUT STATUS POINTS AND CONTROL BLOCKS ......................................................5-16
8-BIT UNSIGNED INTEGER, OBJECT 102 ........................................................................................5-20

BE1-CDS DNP Protocol iii


SECTION 1 • GENE RAL INFORMATION
INTRODUCTION
This document describes the Basler Electric Distributed Network Protocol (DNP) implementation in the
BE1-CDS Current Differential System. The BE1-CDS is classified as an intelligent electronic device (IED)
that is capable of reacting or responding to specific requests conforming to a level two slave device, as
defined in the DNP V3.00 Subset Definitions Document. This manual contains a list of DNP data objects
accessible by a master station.

NOTE
This implementation of DNP V3.00 is fully compliant with DNP V3.00 Subset Definition
Level 2, contains many Subset Level 3 features, and contains some functionality even
beyond Subset Level 3.

REFERENCES
• Instruction Manual for BE1-CDS Current Differential System
• DNP V3.00 Basic 4 Document Set
• DNP Subset Definitions Document
• The DNP website (www.DNP.org)

BE1- CDS DNP Protocol 1-1


SECTION 2 • DNP V 3.00 DEVICE PROFILE
DOCUMENT
Table 1 provides a Device Profile Document in the standard format defined in the DNP V3.00 subset
definition document. The table, in combination with the implementation table provided in Section 3 and
the point list tables provided in Section 5, provide a complete application configuration guide for including
the BE1-CDS DNP protocol in any DNP environment.
Table 1. DNP V3.00 Device Profile Document

DNP V3.00
DEVICE PROFILE DOCUMENT
Vendor Name: Basler Electric Company
Device Name: BE1-CDS Current Differential System
Highest DNP Level Supported: Device Function:
DNP-L2. Master Slave
Notable objects, functions, and/or qualifiers supported in addition to the highest DNP levels supported
(the complete list is described in DNP V3.00 Implementation Table):
- For static (non-change-event) object requests, request qualifier codes 00 and 01(start-stop), 07
and 08 limited quantity), and 17 and 28(index) are supported in addition to request qualifier code
06 (no range – or all points).
- Static object requests sent with qualifiers 00,01,06,07, and 08, will be responded to with qualifiers
00 or 01.
- Static object requests sent with qualifiers 17 and 28 will be responded to with qualifiers 17 or 28.
- The read function code for object 102 (8-bit unsigned integer), variation 1, is supported.
- Time period when device requires time-synchronization from the master is configurable via object
41, point 30.
- Dead band for current analog input events is configurable via object 41, point 31.

Maximum Data Link Frame Size (octets): Maximum Application Fragment Size (octets):
Transmitted 292 Transmitted 2048
Received 292 Received 1024

Maximum Data Link Re-tries: Maximum Application Layer Re-tries:


None None
Fixed at Fixed at
Configurable Configurable, range ______ to ______

Requires Data Link Layer Confirmation:


Never
Always
Sometimes If 'Sometimes', when?
Configurable If 'Configurable', how?

Requires Application Layer Confirmation:


Never
Always (not recommended)
When reporting Event Data (Slave devices only)
When sending multi-fragment responses (Slave devices only)

BE1- CDS DNP Protocol 2-1


DNP V3.00
DEVICE PROFILE DOCUMENT
Timeouts while waiting for:

Data Link Confirm None Fixed at 3000 ms Variable Configurable


Complete Appl. Fragment None Fixed at Variable Configurable
Application Confirm None Fixed at 5000 ms Variable Configurable
Complete Appl. Response None Fixed at Variable Configurable

Sends/Executes Control Operations:

WRITE Binary Outputs Never Always Sometimes Configurable


SELECT/OPERATE Never Always Sometimes Configurable
DIRECT OPERATE Never Always Sometimes Configurable
DIRECT OPERATE - NO ACK Never Always Sometimes Configurable

Count > 1 Never Always Sometimes Configurable


Pulse On Never Always Sometimes Configurable
Pulse Off Never Always Sometimes Configurable
Latch On Never Always Sometimes Configurable
Latch Off Never Always Sometimes Configurable

Queue Never Always Sometimes Configurable


Clear Queue Never Always Sometimes Configurable

Reports Binary Input Change Events when no Reports time-tagged Binary Input Change Events
specific variation requested (Slave Only): when no specific variation requested:
Never Never
Only time-tagged Binary Input Change With Time
Only non-time-tagged Binary Input Change With Relative Time
Configurable to send both, one or the other Configurable (attach explanation)
(attach explanation)

Master Expects Binary Input Change Events:


Never
Either time-tagged or non-time-tagged for a single event
Both time-tagged and non-time-tagged for a single event
Configurable (attach explanation)

Sends Unsolicited Responses Sends Static Data in Unsolicited Responses


(Slave Only): (Slave Only):
Never
Configurable (attach explanation) Never
Only certain objects When Device Restarts
Sometimes (attach explanation) When Status Flags Change
ENABLE/DISABLE UNSOLICITED
Function codes supported No other options are permitted.

Default Counter Object/Variation: Counters Roll Over at:


No Counters Reported No Counters Reported
Configurable (attach explanation) Configurable (attach explanation)
Default Object 16 Bits
Default Variation 32 Bits
Point-by-point list attached Other Value:
Point- by-point list attached
Sends Multi-Fragment Responses (Slave Only): Yes No

2-2 DNP Protocol BE1- CDS


SECTION 3 • IMPLE MENTATION TABLE
DNP V3.00 IMPLEMENTATION TABLE
Table 2 identifies which object variations, function codes, and qualifiers the BE1-CDS DNP supports in
both request messages and in response messages.
For static (non-change-event) objects, requests sent with qualifiers 00, 01, 06, 07, or 08 will be responded
to with qualifiers 00 or 01. Static object requests sent with qualifiers 17 or 28 will be responded to with
qualifiers 17 or 28.
For change-event objects, qualifiers 17 and 28 are always responded.
Table 2. BE1-CDS DNP Implementation Table
OBJECT REQUEST RESPONSE
(BE1-CDS-220 will parse) (BE1-CDS-220 will respond with)
Object Variation Function Codes Qualifier Codes Function Codes Qualifier Codes
No. No. Description (dec) (hex) (hex) (hex)
1 0 Binary Inputs – (Variation 0 is 1 (read) 00,01 (start- stop)
used to request default 06 (no range)
variation) 07,08 (limited qty)
17,28 (index)
1 1 Single-Bit Binary Input 1 (read) 00,01 (start- stop) 81 00,01 (start-stop)
06 (no range)
(default – (response) 17,28 (index)
07,08 (limited qty)
see note 1)
17,28 (index)
2 0 1 (read) 06 (no range)
Binary Input Change
07,08 (limited qty)
(Variation 0 is used to request
default variation)
06 (no range)
2 1 Binary Input Change without 1 (read) 81 17,28 (index)
time 07,08 (limited qty)
(response)
06 (no range)
2 2 Binary Input Change with time 1 (read) 81 17,28 (index)
07,08 (limited qty)
(default – (response)
see note 1)
00,01 (start- stop)
10 0 Binary Output – (Variation 0 is 1 (read)
used to request default 06 (no range)
variation) 07,08 (limited qty)
17,28 (index)
10 2 Binary Output Status 1 (read) 00,01 (start- stop) 81 00,01 (start-stop)
06 (no range)
(default – 07,08 (limited qty) 17,28 (index)
see note 1) 17,28 (index)
12 1 Control Relay Output Block 3 (select) 00,01 (start-stop) 81 echo of request
07,08 (limited qty)
4 (operate) 17,28 (index)
5 (direct op)
6 (dir op Noack)
00,01 (start- stop)
30 0 Analog Input (Variation 0 is 1 (read) 81(response) 00,01 (start-stop)
used to request default 06 (no range)
07,08 (limited qty) 17,28 (index)
variation)
17,28 (index)
30 1 32-Bit Analog Input With Flag 1 (read) 00,01 (start- stop) 81 00,01 (start-stop)
06 (no range)
07,08 (limited qty) 17,28 (index)
17,28 (index)
00,01 (start- stop)
30 2 16-Bit Analog Input With Flag 1 (read) 81 00,01 (start-stop)
06 (no range)
07,08 (limited qty) 17,28 (index)
17,28 (index)
00,01 (start- stop)
30 3 32-Bit Analog Input Without 1 (read) 81 00,01 (start-stop)
Flag 06 (no range)
(default – 07,08 (limited qty) 17,28 (index)
see note 1) 17,28 (index)

BE1- CDS DNP Protocol 3-1


OBJECT REQUEST RESPONSE
(BE1-CDS-220 will parse) (BE1-CDS-220 will respond with)
Object Variation Function Codes Qualifier Codes Function Codes Qualifier Codes
No. No. Description (dec) (hex) (hex) (hex)
30 4 1 (read) 00,01 (start- stop) 81 00,01 (start-stop)
16-Bit Analog Input Without
06 (no range)
Flag
07,08 (limited qty) 17,28 (index)
17,28 (index)
06 (no range)
32 0 Analog Change Event 1 (read)
(Variation 0 is used to request 07,08 (limited qty)
default variation)
32 1 32-Bit Analog Input without 1 (read) 06 (no range) 81 17,28 (index)
time 07,08 (limited qty)
(default –
see note 1)
32 2 16-Bit Analog Input without 1 (read) 06 (no range) 81 17,28 (index)
time 07,08 (limited qty)
06 (no range)
32 3 32-Bit Analog Input with time 1 (read) 81 17,28 (index)
07,08 (limited qty)
06 (no range)
32 4 16-Bit Analog Input with time 1 (read) 81 17,28 (index)
07,08 (limited qty)
40 0 Analog Output Status – 1 00,01 (start-stop)
06 (no range)
(Variation 0 is used to request
07,08 (limited qty)
default variation)
17,28 (index)
40 1 32-bit Analog Output Status 1 (read) 00,01 (start-stop) 81 00,01 (start-stop)
06 (no range)
07,08 (limited qty) 17,28 (index)
17,28 (index)
40 2 16-bit Analog Output Status 1 (read) 00,01 (start-stop) 81 00,01 (start-stop)
06 (no range)
(default - 07,08 (limited qty) 17,28 (index)
see note 1) 17,28 (index)
41 1 32-bit Analog Output Block 3 (select) 00,01 (start-stop) 81 echo of request
4 (operate) 07,08 (limited qty)
5 (direct op) 17,28 (index)
6 (dir op noack)
3 (select) 00,01 (start-stop)
41 2 16-bit Analog Output Block 81 echo of request
4 (operate) 07,08 (limited qty)
17,28 (index)
5 (direct op)
6 (dir op noack)
50 1 Time and Date 1 (read) 00,01 (start-stop) 81 00,01 (start-stop)
06 (no range or all)
2 (write) 17,28 (index)
07 (limited qty=1)
08 (limited qty)
17,28 (index)
60 1 Class 0 Data (Note 1) (Note 4) 1 (read) 06 (no range or all) 81
06 (no range or all)
60 2 Class 1 Data 1 (read) 81
07,08 (limited qty)
60 3 Class 2 Data 1 (read) 06 (no range or all) 81
07,08 (limited qty)
60 4 Class 3 Data 1 (read) 06 (no range or all) 81
07,08 (limited qty)
80 1 Internal Indications 2 (write) 00 (start-stop)
(index must=7)
00,01 (start- stop)
102 1 8-Bit Unsigned Integer (Note 1 (read) 81(response) 00,01 (start-stop)
2) 06 (no range)
07,08 (limited qty) 17,28 (index)
17,28 (index)
No Object (function code only) 13 (cold restart)
(See Note 3)
No Object (function code only) 14 (warm
(See Note 3) restart)
No Object (function code only) 23 (delay meas)

3-2 DNP Protocol BE1- CDS


Notes for Table 2:
1. A Default variation refers to the variation responded to when variation 0 is requested and/or in class
0,1,2, or 3 scans.
2. Object 102 is not included in Class 0 poll response.
3. A cold restart is implemented as a warm restart – the DNP process is restarted.
4. In Class 0 are included all Binary Inputs (object 1), and a selected set of Analog Inputs (object 30).
Binary Output Status points and Analog Output Status points are not included in Class 0.

BE1- CDS DNP Protocol 3-3


SECTION 4 • DNP V 3.00 CONFIGURATION
PARAMETERS
DNP CONFIGURATION PARAMETERS
These paragraphs describe configuration settings that may be verified/changed from the BE1-CDS front
panel or using ASCII protocol commands.

Relay Style Number


BE1-CDS relays that support the DNP protocol must have a Style Number with the eighth character as a
number 3. This can be verified by reading the relay Style Number via the front communication port using
the RG-VER ASCII command. (Reference the BE1-CDS Instructional Manual, part number 9 3139 00
990).
Example:
>rg-ver
Model Number: BE1-CDS220
Style Number: E0EN0YY3N0R
App Program: VER 1.14.00 03/03/00
DSP Program: VER 1.13.00 06/28/99
Boot Program: VER 2.11.00 10/28/98
Serial Number: H00069997

BE1-CDS Slave Address


BE1-CDS relays support DNP through the rear RS-485 communication port, which is communication port
2 (COM2). This port supports Baud Rates: 1200, 2400, 4800, 9600, and 19200, and the default Baud
Rate is 9600.
DNP Slave IED Address Range is from 0 to 65534. Address 65535 (hex FFFF) is used to broadcast
messages to all devices. The communication address can be set by the SG-COM ASCII command. For
more information about changing the relay parameters, refer to the BE1-CDS Instructional Manual, part
number 9 3139 00 990.
Example: Set the BE1-CDS address to be 125, and baud rate to be 9600.
(In the following example, the operator’s commands are in bold.)
>a=<global_password> <enter> //enter global password
>ACCESS GRANTED: GLOBAL
> sg-com2=9600,a125(enter)
>exit (enter)
>SAVE CHANGES (Y/N/C) ?
>y <enter>
>CHANGE COMM PARAMETERS
>
To verify port address, enter command
>sg-com2(enter)
>SG-COM2=9600, A125, P0,R1,X0

BE1- CDS DNP Protocol 4-1


SECTION 5 • DNP V 3.00 POINT LIST
BINARY INPUT POINTS
Binary Input changes are scanned every four milliseconds. Events are pending in the Slave application
buffer until the Master device sends conformation that response with pending events were received.
Table 3 describes the binary input points.
Table 3. Binary Input Points
Binary Input Points
Static Object Number: 1
Change Event Object Number: 2
Request Function Codes Supported: 1 (read)
Static Variation Reported When Variation 0 Requested: 1 (Binary Input Without Status)
Change Event Variation Reported When Variation 0 Requested: 2 (Binary Input Change With Time)

Point Description Change Event Notes


Index Assigned Class
(1,2,3 or none)
0 50T Phase A Trip 1
1 50T Phase B Trip 1
2 50T Phase C Trip 1
3 150T Phase A Trip 1
4 150T Phase B Trip 1
5 150T Phase C Trip 1
6 250T Phase A Trip 1
7 250T Phase B Trip 1
8 250T Phase C Trip 1
9 51 Phase A Trip 1
10 51 Phase B Trip 1
11 51 Phase C Trip 1
12 151 Phase A Trip 1
13 151 Phase B Trip 1
14 151 Phase C Trip 1
15 251 Phase A Trip 1
16 251 Phase B Trip 1
17 251 Phase C Trip 1
18 87U Phase A Trip 1
19 87U Phase B Trip 1
20 87U Phase C Trip 1
21 87R Phase A Trip 1
22 87R Phase B Trip 1
23 87R Phase C Trip 1
24 50T Neutral Trip 1
25 150T Neutral Trip 1
26 250T Neutral Trip 1
27 50T Negative Sequence Trip 1

BE1- CDS DNP Protocol 5-1


Point Description Change Event Notes
Index Assigned Class
(1,2,3 or none)
28 150T Negative sequence Trip 1
29 250T Negative sequence Trip 1
30 51 Neutral Trip 1
31 151 Neutral Trip 1
32 251 Neutral Trip 1
33 51Q Trip 1
34 151Q Trip 1
35 251Q Trip 1
36 Breaker Failure Trip 1
37 87ND Trip 1
38 87 Restrained Trip 1
39 87 UnRestrained Trip 1
40 87 2nd Harmonic 1
41 87 5th harmonic 1
42 62 1
43 162 1
Active Group Status (points 44 – 47)
44 Setting Group 0 Active 1
45 Setting Group 1 Active 1
46 Setting Group 2 Active 1
47 Setting Group 3 Active 1
Input Status (points 48 – 55)
48 Input Contact 1 State 1
49 Input Contact 2 State 1
50 Input Contact 3 State 1
51 Input Contact 4 State 1
52 Input Contact 5 State 1
53 Input Contact 6 State 1
54 Input Contact 7 State 1
55 Input Contact 8 State 1
56 Major Alarm 1
57 Minor Alarm 1
58 Logic Alarm 1
59 Output Trip Coil Monitor 1
60 101 TRIP 1
61 101 CLOSE 1
62 101 SLIP CONTACT ( 0= Breaker Tripped, 1 = Breaker is 1
Closed )
63 43 1
64 143 1
65 243 1
66 343 1

5-2 DNP Protocol BE1- CDS


Point Description Change Event Notes
Index Assigned Class
(1,2,3 or none)
67 443 1
68 543 1
69 643 1
70 743 1
Hardware Output Status (points 71 - 77)
71 Output A 1
72 Output 1 1
73 Output 2 1
74 Output 3 1
75 Output 4 1
76 Output 5 1
77 Output 6 1
Relay Trouble Alarms (points 78 - 87)
78 RAM Failure 1
79 FLASH FAILURE 1
80 uP Failure 1
81 EEPROM Fatal Error 1
82 Analog Failure 1
83 Calibration Error 1
84 Power Supply Error 1
85 Default Settings Loaded 1
86 Calibration Defaults Loaded 1
87 DSP Failure 1
Programmable Alarms (points 88 – 115) See Note 1
88 Output Circuit Open Alarm 1
89 Breaker Fail Alarm 1
90 Differential Alarm 1
91 Settings Changes Lost due to Access Time Out 1
92 Breaker Alarm 1 1
93 Breaker Alarm 2 1
94 Breaker Alarm 3 1
95 P Demand Maximum Exceed Alarm 1
96 N Demand Maximum Exceed Alarm 1
97 Q Demand Alarm 1
98 Group Override Alarm (0=Local Control, 1= Group Override) 1
99 Sys I/O Delay Alarm (Operating System Overload) 1
100 Communication Error Alarm 1
101 Clock Error Alarm 1
102 MPU Reset Alarm 1
103 Settings Changed Alarm 1
104 EEPROM Non fatal error 1

BE1- CDS DNP Protocol 5-3


Point Description Change Event Notes
Index Assigned Class
(1,2,3 or none)
105 An override is active in one or more outputs 1
(Output Overide Alarm)
106 Loss of IRIG 1
107 Setting Group Change Active alarm 1
108 VO13 Logic Alarm 1
109 VO14 Logic Alarm 1
110 VO15 Logic Alarm 1
111 FLT RPT(Report) Time Out 1
112 Transformer Alarm 1 1
113 Transformer Alarm 2 1
114 Transformer Alarm 3 1
115 Logic = NONE Alarm 1
State Of Fault Trigger Logic Expression (See Note 2)
116 Pick Up trigger expressions state (1=TRUE,0 =FALSE) 1
117 Trip trigger logic expressions state (1=TRUE,0 =FALSE) 1
118 Logic trigger expressions state (1=TRUE,0 =FALSE) 1
119 1 - New Fault triggered. Fault data will be saved as the Most 1 3
Recent Fault Summary Report, and available when this point
becomes 0.
0 - The Most Recent Fault Summary Report available.
Notes for Table 3:
1. Any alarm from this Programmable Alarms group may be declared as major, minor, or logic alarm.
Refer to ASCII Serial Command SG-LGC, SA-MAJ, and SA-MIN.
2. Refer to ASCII Serial Command SG-TRIGGER=<trip>,<pu>,<logic>.
3. The time stamp from transition 0 to 1 is the fault trigger time (equal to the time of the most recent
Fault Summary Report).
The time stamp from transition 1 to 0 is the time since the Fault Summary Report for the most
recent fault is available (see object 30 points from 67 to 104).
The total count of point 119 transitions from zero to one (new faults triggered) in response to a
Class 1 request represents the number of faults that have occurred between two consecutive
Class 1 scans. A Class 1 scan reports only the Most Recent Fault Summary Report as analog
events of object 32, points 67 to 104. If there are more than one New Fault Triggered events in
the Class 1 response, the previous Fault Summary Reports can be retrieved through the Select
Fault Summary Report (see object 30, points 134 to 171).

5-4 DNP Protocol BE1- CDS


BINARY OUTPUT STATUS POINTS AND CONTROL RELAY OUTPUT BLOCKS
Table 4 lists both the Binary Output Status Points (Object 10) and the Control Relay Output Blocks
(Object 12). It is important to note that Binary Output Status Points are not included in Class 0.
Table 4. Binary Output Status Points And Control Relay Output Blocks
Binary Output Status Points:
Object Number: 10
Variations supported: 2
Request Function Codes supported: 1 (read)
Default Variation reported when variation 0 requested: 2 (Binary Output Status)
Control Relay Output Blocks
Object Number: 12
Variations supported: 1
Request Function Codes supported: 3(select), 4(operate), 5(direct operate), 6 (direct operate, noack)

Point Description Control Codes And Their Description


Index
0 Hardware Output A State Latch On: Set Output x to state 1
Hardware Output 1 State Latch Off: Set Output x to state 0
1 Pulse On: Pulse output x to opposite of
2 Hardware Output 2 State current state then restore to
Hardware Output 3 State previous state ( pulsed output
3
is active 200 to 250 ms)
4 Hardware Output 4 State
5 Hardware Output 5 State
6 Hardware Output 6 State
7 All Hardware Outputs State
8 Hardware Output A Local Control Latch On: Set Hardware Output x to relay
9 Hardware Output 1 Local Control logic or local control

10 Hardware Output 2 Local Control


11 Hardware Output 3 Local Control
12 Hardware Output 4 Local Control
13 Hardware Output 5 Local Control
14 Hardware Output 6 Local Control
15 All Hardware Outputs Local Control
16 43 Selector Switch Status Latch On: Set x Selector Switch to 1
143 Selector Switch Status Latch Off: Set x Selector Switch to 0
17 Pulse On: Pulse x Selector Switch state
18 243 Selector Switch Status to opposite of the current state
343 Selector Switch Status then restore to previous state
19
(pulsed input is active 200 to
20 443 Selector Switch Status 250 ms).
21 543 Selector Switch Status
22 643 Selector Switch Status
23 743 Selector Switch Status
24 Setting Group 0 Latch On: Select Group x to be Active
25 Setting Group 1
26 Setting Group 2
27 Setting Group 3
28 Local Setting Group Control Switch Latch On: Return Setting Group Control
to relay local logic

BE1- CDS DNP Protocol 5-5


Point Description Control Codes And Their Description
Index
29 101 Virtual Breaker Control Switch Close: Close Breaker (changes 101C
Binary Input from 0 to 1 for 200
ms )
Trip: Trip Breaker (changes 101T
from 0 to 1 for 200 ms)
Notes for Table 4:
1. Reads Of Points
- Reads of points from 0 to 6 returns the current state of corresponding hardware output points.
- Reads of points from 8 to 14 returns 1 if corresponding hardware output is under relay Local
control, or 0 if output is override.
- Reads of points from 16 to 23 returns the current state of the corresponding x43 selector
switches.
- Reads of point 24 to 27 returns 1 if Setting Group is active. Notice that only one of these points
can be active at any time.
- Read of point 28 returns value 1 if the Setting Group Control is under relay local logic.
- Reads of points 7,15, and 29 always returns 0.
2- When used to control the points listed in Table 3, the Control Code field of object 12 is parsed as
described in the following paragraphs.
- If the Control Code is NULL, then the command will be accepted without any action being
taken.
- If Queue, and Clear sub-fields are not zero, the returned Control Status is 4 (Control operation
not supported).
- A Code sub-field of “Pulse On” (1) in combination with a value in the Trip/Close sub-field, form
a Trip or Close value. A “Trip” value consists of a “PULSE ON” (1) in the Code sub-field and a
2 in the Trip/Close sub-field. This results in a value of 81(hex) in the Control Code field. A
“Close” value consists of a “PULSE ON” (1) in the Code sub-field and a 1 in the Trip/Close sub-
field. This results in a value of 41 (hex) in the Control Code field.
3. Valid Control Code values are:
- 0x00 = No action will be taken.
- 0x01 = Pulse output to opposite of current state, then restore to previous state. Pulsed output
is active 200 to 250 ms.
- 0x03 = Latch On
- 0x04 = Latch Off
- 0x41 = Close (Breaker Close)
- 0x81 = Trip (Breaker Open)
All operations not defined above are invalid and will be rejected. If the Control Code is legal, but not
supported for the requested point, the Status Return value is “Control operation not supported for this
point” (value 4).
- The Count, OnTime, and OffTime fields are ignored.
- Arm timer value for all Select/Operate operations is 30 seconds.
It is important to notice that any control function may be rejected because of the relay internal state.
When this happens, the Status Return value is “Request not accepted because of hardware
problems” (value 6). One of the reasons for the rejection may be that that point Logic Function Block
has the Logic(Control) Mode disabled.
For example: Control functions for the hardware output points (points 0 to 15) will be rejected if the
Output Control for all hardware outputs is disabled.
The Logic (Control) Mode of any object 12 point can be changed (enabled/disabled) via the specific
point of object 41 (Analog Output Control Blocks). Refer to Analog Output Status Points and Analog
Output Control Block points from 0 to 10.

5-6 DNP Protocol BE1- CDS


ANALOG INPUTS
The following table lists Analog Inputs (Objects 30 and 32). It is important to note that 16-bit and 32-bit
variations of Analog Inputs, Analog Output Control Blocks, and Analog Output Statuses are transmitted
through DNP as signed numbers. Even for analog input points that are not valid as negative values, the
maximum positive representation for a 16-bit variation is <215-1> = 32,767. For a 32-bit variation the
maximum positive representation is <231-1> = 2,147,483,647.
Points not assigned to any class can be read as object 30 points in any supported variation or qualifier
implemented for object 30.
Change events for analog inputs are reported in CURRENT mode (when a change is detected, the report
of the change contains the current value of the time of the report - not the time the change was detected.
Table 5. Analog Inputs
Analog Inputs
Static Object Number : 30
Change Event Object Number : 32
Request Function Codes Supported: 1 (read)
Static Variation Reported When Variation 0 Requested: 3 (32-bit Analog Input without Flag)
Change Event Variation Reported When Variation 0 Requested: 1 (32-bit Analog Change Event without
Time)

Index Description Change Event Notes


Assigned Class
(1, 2, 3, or none)
Current Magnitudes (See Note 1)
0 Winding #1 Phase A Current Magnitude 2 1, 20
1 Winding #1 Phase B Current Magnitude 2 1, 20
2 Winding #1 Phase C Current Magnitude 2 1, 20
3 Winding #1 Neutral Current Magnitude 2 1, 20
4 Winding #1 Negative Sequence Current Magnitude 2 1, 20
5 Winding #2 Phase A Current Magnitude 2 1, 20
6 Winding #2 Phase B Current Magnitude 2 1, 20
7 Winding #2 Phase C Current Magnitude 2 1, 20
8 Winding #2 Neutral Current Magnitude 2 1, 20
9 Winding #2 Negative Sequence Current Magnitude 2 1, 20
10 Ground Current Magnitude 2 1, 20
Phase Angles
11 Winding #1 Phase A Angle 2 7
12 Winding #1 Phase B Angle 2 7
13 Winding #1 Phase C Angle 2 7
14 Winding #1 Neutral Angle 2 7
15 Winding #2 Phase A Angle 2 7
16 Winding #2 Phase B Angle 2 7
17 Winding #2 Phase C Angle 2 7
18 Winding #2 Neutral Angle 2 7
19 Ground Angle 2 7
Differential Compensated Per Centi-Unit Currents
20 Winding #1 Phase A Compensated Current 2 21
21 Winding #1 Phase B Compensated Current 2 21
22 Winding #1 Phase C Compensated Current 2 21

BE1- CDS DNP Protocol 5-7


Index Description Change Event Notes
Assigned Class
(1, 2, 3, or none)
23 Winding #1 Neutral Compensated Current 2 21
24 Winding #2 Phase A Compensated Current 2 21
25 Winding #2 Phase B Compensated Current 2 21
26 Winding #2 Phase C Compensated Current 2 21
27 Winding #2 Neutral Compensated Current 2 21
28 Ground Compensated Current 2 21
Differential Compensated Angles
29 Winding #1 Phase A Compensated Angle 2 7
30 Winding #1 Phase B Compensated Angle 2 7
31 Winding #1 Phase C Compensated Angle 2 7
32 Winding #1 Neutral Compensated Angle 2 7
33 Winding #2 Phase A Compensated Angle 2 7
34 Winding #2 Phase B Compensated Angle 2 7
35 Winding #2 Phase C Compensated Angle 2 7
36 Winding #2 Neutral Compensated Angle 2 7
37 Ground Compensated Angle 2 7
Differential Operating Per Centi-Unit Currents
38 Differential Operating Phase A Current 2 22
39 Differential Operating Phase B Current 2 22
40 Differential Operating Phase C Current 2 22
41 Differential Operating Ground Current 2 22
Differential Second Harmonic Centi-Percentage
nd
42 Phase A 2 Harmonic Percentage 2 23
nd
43 Phase B 2 Harmonic Percentage 2 23
nd
44 Phase C 2 Harmonic Percentage 2 23
Differential Fifth Harmonic Centi-Percentage
th
45 Phase A 5 Harmonic Percentage 2 23
th
46 Phase B 5 Harmonic Percentage 2 23
th
47 Phase C 5 Harmonic Percentage 2 23
48 Measured Frequency 2 17
Present Demand Currents
49 Present Demand Current- Phase A 2 1, 20
50 Present Demand Current- Phase B 2 1, 20
51 Present Demand Current- Phase C 2 1, 20
52 Present Neutral Demand Current 2 1, 20
53 Present Negative Sequence Demand Current 2 1, 20
Breaker Duty Information
54 Breaker Duty – Phase A 2 12
55 Breaker Duty – Phase B 2 12
56 Breaker Duty – Phase C 2 12
57 Breaker Operation Counter 2 13

5-8 DNP Protocol BE1- CDS


Index Description Change Event Notes
Assigned Class
(1, 2, 3, or none)
Transformer Duty Information
58 Transformer Phase A duty 2 15
59 Transformer Phase B duty 2 15
60 Transformer Phase C duty 2 15
61 Transformer Through Fault Operations Counter 2 16
Latched Targets Status (62 – 65)
62 Target Status-part 1 1 18
63 Target Status-part 2 1 18
64 Target Status-part 3 1 18
65 Target Status-part 4 1 18
66 BF Status 1 19
Most Recent Fault Summary Report (67 – 104)
67 Fault Number 1 2 ,24
68 Fault Trigger Time Stamp – part 1; days 1 3,24
69 Fault Trigger Time Stamp – part 2; ms 1 3,24
70 Active Setting Group 1 4,24
71 Trigger 1 5,24
72 System Status – Part 1 1 34
73 System Status – Part 2 1 34
74 System Status – Part 3 1 34
75 System Status – Part 4 1 34
76 System Status – Part 5 1 34
77 System Status – Part 6 1 34
78 Targets- part1 1 6,24
79 Targets- part2 1 6,24
80 Targets- part3 1 6,24
81 Targets- part4 1 6,24
82 Fault Clearing Time 1 8,24
83 Breaker Operate Time 1 9,24
84 Number of Oscillographic Reports 1 10,24
85 Winding 1 Phase A Fault Current 1 1,24
86 Winding 1 Phase B Fault Current 1 1,24
87 Winding 1 Phase C Fault Current 1 1,24
88 Winding 1 Neutral Fault Current 1 1,24
89 Winding 1 Negative Sequence Fault Current 1 1,24
90 Winding 1 Phase A Angle 1 7,24
91 Winding 1 Phase B Angle 1 7,24
92 Winding 1 Phase C Angle 1 7,24
93 Winding 1 Neutral Angle 1 7,24
94 Winding 2 Phase A Fault Current 1 1,24
95 Winding 2 Phase B Fault Current 1 1,24

BE1- CDS DNP Protocol 5-9


Index Description Change Event Notes
Assigned Class
(1, 2, 3, or none)
96 Winding 2 Phase C Fault Current 1 1,24
97 Winding 2 Neutral Fault Current 1 1,24
98 Winding 2 Negative Sequence Fault Current 1 1,24
99 Winding 2 Phase A Angle 1 7,24
100 Winding 2 Phase B Angle 1 7,24
101 Winding 2 Phase C Angle 1 7,24
102 Winding 2 Neutral Angle 1 7,24
103 Ground Current 1 1,24
104 Ground Angle 1 7,24
105 Phase Rotation 3 25,24
106 Winding 1 CT Ratio 3 26,24
107 Winding 2 CT Ratio 3 26,24
108 Ground CT Ratio 3 26,24
109 Winding 1 CT Connection 3 27,24
110 Winding 2 CT Connection 3 27,24
111 Winding 1 TX Connection 3 28,24
112 Winding 2 TX Connection 3 28,24
113 Winding 1 Ground Source 3 29,24
114 Winding 2 Ground Source 3 29,24
Active Logic Name
115 1. character of Active Logic Name 3 24
116 2. character of Active Logic Name 3 24
117 3. character of Active Logic Name 3 24
118 4. character of Active Logic Name 3 24
119 5. character of Active Logic Name 3 24
120 6. character of Active Logic Name 3 24
121 7. character of Active Logic Name 3 24
122 8. character of Active Logic Name 3 24
Logic Function Block Settings
123 Hardware Outputs’ Control Mode 3 30,24
124 43 Aux Virtual Switch Logic Mode 3 31,24
125 143 Aux Virtual Switch Logic Mode 3 31,24
126 243 Aux Virtual Switch Logic Mode 3 31,24
127 343 Aux Virtual Switch Logic Mode 3 31,24
128 443 Aux Virtual Switch Logic Mode 3 31,24
129 543 Aux Virtual Switch Logic Mode 3 31,24
130 643 Aux Virtual Switch Logic Mode 3 31,24
131 743 Aux Virtual Switch Logic Mode 3 31,24
132 Setting Group Logic Mode 3 32,24
133 101 Breaker Switch Control Mode 3 33,24

5-10 DNP Protocol BE1- CDS


Index Description Change Event Notes
Assigned Class
(1, 2, 3, or none)
Selected Fault Summary Report (134 – 171)
134 Fault Number none 2
135 Fault Trigger Time Stamp – part 1; days none 3
136 Fault Trigger Time Stamp – part 2; ms none 3
137 Active Setting Group none 4
138 Trigger none 5
139 System Status – Part 1 none 34
140 System Status – Part 2 none 34
141 System Status – Part 3 none 34
142 System Status – Part 4 none 34
143 System Status – Part 5 none 34
144 System Status – Part 6 none 34
145 Targets- part1 none 6
146 Targets- part2 none 6
147 Targets- part3 none 6
148 Targets- part4 none 6
149 Fault Clearing Time none 8
150 Breaker Operate Time none 9
151 Number of Oscillographic Reports none 10
152 Winding 1 Phase A Fault Current none 1
153 Winding 1 Phase B Fault Current none 1
154 Winding 1 Phase C Fault Current none 1
155 Winding 1 Neutral Fault Current none 1
156 Winding 1 Negative Sequence Fault Current none 1
157 Winding 1 Phase A Angle none 7
158 Winding 1 Phase B Angle none 7
159 Winding 1 Phase C Angle none 7
160 Winding 1 Neutral Angle none 7
161 Winding 2 Phase A Fault Current none 1
162 Winding 2 Phase B Fault Current none 1
163 Winding 2 Phase C Fault Current none 1
164 Winding 2 Neutral Fault Current none 1
165 Winding 2 Negative Sequence Fault Current none 1
166 Winding 2 Phase A Angle none 7
167 Winding 2 Phase B Angle none 7
168 Winding 2 Phase C Angle none 7
169 Winding 2 Neutral Angle none 7
170 Ground Current none 1
171 Ground Angle none 7

BE1- CDS DNP Protocol 5-11


Index Description Change Event Notes
Assigned Class
(1, 2, 3, or none)
Demand Currents Historical Data
Peak Demand Current Since Reset
172 Phase A Current none 1
173 Phase A Time Stamp – part 1; days none 11
174 Phase A Time Stamp – part 2; ms none 11
175 Phase B Current none 1
176 Phase B Time Stamp – part 1; days none 11
177 Phase B Time Stamp – part 2; ms none 11
178 Phase C Current none 1
179 Phase C Time Stamp – part 1; days none 11
180 Phase C Time Stamp – part 2; ms none 11
181 Neutral Current none 1
182 Neutral Time Stamp – part 1; days none 11
183 Neutral Time Stamp – part 2; ms none 11
184 Negative Sequence none 1
185 Negative Sequence Time Stamp – part 1; days none 11
186 Negative Sequence Time Stamp – part 2; ms none 11
Today’s Peak Demand Current
187 Phase A Current none 1
188 Phase A Time Stamp – part 1; days none 11
189 Phase A Time Stamp – part 2; ms none 11
190 Phase B Current none 1
191 Phase B Time Stamp – part 1; days none 11
192 Phase B Time Stamp – part 2; ms none 11
193 Phase C Current none 1
194 Phase C Time Stamp – part 1; days none 11
195 Phase C Time Stamp – part 2; ms none 11
196 Neutral Current none 1
197 Neutral Time Stamp – part 1; days none 11
198 Neutral Time Stamp – part 2; ms none 11
199 Negative Sequence Current none 1
200 Time Stamp – part 1; days none 11
201 Time Stamp – part 2; ms none 11
Yesterday’s Peak Demand Current
202 Phase A Current none 1
203 Phase A Time Stamp – part 1; days of none 11
204 Phase A Time Stamp – part 2; ms none 11
205 Phase B Current none 1
206 Phase B Time Stamp – part 1; days none 11
207 Phase B Time Stamp – part 2; ms none 11

5-12 DNP Protocol BE1- CDS


Index Description Change Event Notes
Assigned Class
(1, 2, 3, or none)
208 Phase C Current none 1
209 Phase C Time Stamp – part 1; days none 11
210 Phase C Time Stamp – part 2; ms none 11
211 Neutral Current none 1
212 Neutral Time Stamp – part 1; days none 11
213 Neutral Time Stamp – part 2; ms none 11
214 Negative Sequence Current none 1
215 Negative Sequence Time Stamp – part 1; days None 11
216 Negative Sequence Time Stamp – part 2; ms None 11

Notes for Table 5:


1. Current value is in primary centiamps. For example value of 123 means 1.23 Amps.
1* If the winding is set to WYE configuration, the quantities returned are IAn, IBn, ICn, INn, and Iqn
where n is equal to 1 for CT circuit 1 or 2 for CT circuit 2. If the winding is set to DAB
configuration, then quantities returned are IAn-IBn, IBn-ICn, ICn-IAn, INn, and Iqn where n is equal
to 1 for CT circuit 1 or 2 for CT circuit 2. If the winding is set to DAC configuration, then quantities
returned are IAn-ICn, IBn-IAn, ICn-IBn, Inn, and IQn where n is equal to 1 for CT circuit 1 or 2 for
CT circuit 2.
2. Fault Number range is from 1 to 255. For example, after 255, fault number is going to be 1.
3. This time is a fault trigger time presented in relay’s internal format: part 1 contains days ( 1 to
65535), and part 2 contains milliseconds (1 to 86,400,000) since January 1, 1984. This time is
equal to the time of Binary Input Event “New Fault “ triggered (transition from 0 to 1).
Notice, that the Binary Input Event time stamp is presented in DNP time stamp format, since
January 1, 1970.
4. Active setting group at time of fault (0 or 1 or 2 or 3).
5. Event type (value is 1, 2, 4, 8, or 16 ) reports the classification assigned to the fault event. Fault
events are classified into five categories.
1. Breaker Failure (Event Type value is 1): A fault was initiated by the pickup expression and
the breaker failure trip became true before fault was cleared.
2. Trip (Event Type value is 2): A fault was initiated by overcurrent pickup and the relay tripped
to clear the fault.
3. Logic (Event Type value is 4): A fault was detected as defined by the relay logic trigger
expression, but no fault was detected as defined by the pickup expression.
4. Pickup (Event Type value is 8): A fault was initiated by the pickup expression but the relay
never tripped indicating that the fault was cleared by some other device.
5. RF=TRIG (Event Type value is 16): A Fault was triggered by the ASCII command
RF=TRIGGER received via the front or rear RS-232 communication port.
6. Targets: are bit mapped variables. (1= TRUE, 0=FALSE).
If Targets are Latched (points 62 to 65), Table 6 represents the bit position of the element at the
time the reading is taken.
If Fault Report, these targets are logged to the fault report between the time that the trip
expression became true until the end of the fault.

BE1- CDS DNP Protocol 5-13


Table 6. Target Status Format
BIT Mask (hex) Part 1 Part 2 Part 3 Part 4
0001 87UA 151A BF 150TA
0002 87UB 151B 62 150TB
0004 87UC 151C 162 150TC
0008 87RA 151N spare 150TN
0010 87RB 151Q spare 150TQ
0020 87RC spare spare spare
0040 87ND spare spare spare
0080 spare spare spare spare
0100 251A 51A 250TA 50TA
0200 251B 51B 250TB 50TB
0400 251B 51C 250TC 50TC
0800 251N 51N 250TN 50TN
1000 251Q 51Q 250TQ 50TQ
2000 spare spare spare spare
4000 spare spare spare spare
8000 spare spare spare spare

7. Unit for angle is in degrees ( from 0 to 359). Delta of 1 degree deviation will cause an event.
8. Fault Clearing Time is time in milliseconds from 0 to 60,000.
9. Breaker Operate Time is time in milliseconds from 0 to 60,000.
10. The number of recorded oscillographic records per fault (read value of this point) can be 1 or 2.
11. Time presented in relay internal format: part 1 contains days (1 to 65,535), and part 2 milliseconds
(1 to 86,400,000) since January 1, 1984.
12. Point represents assigned phase accumulated breaker pole duty as a centipercent of the
maximum duty (DMAX) that the breaker contacts can withstand before they need service.
Breaker Accumulated Duty for Phase A, B, and C is calculated as ΣI or ΣI2. This is defined by the
Breaker Contact Duty Operation Mode 0/1/2 entered via the ASCII protocol command SB-DUTY.
DMAX is defined through the same SB-DUTY command (for more information, see the BE1-CDS
Instruction Manual, Section 4, Protection And Control). Value range is from 0 to 20,000 where
20,000 represents 200% of DMAX. Delta of 20 centipercent will cause an event.
13. This is the number of recorded breaker operations (0 – 99,999). If the operations counter exceeds
99,999, the counter will wrap back to zero. This value can be changed via object 41, point 3 to any
value from 0 to 99,999. Delta of 1 will cause an event.
14. The selected Fault Summary Report contains fault data for the fault number defined by the value
of the Analog Output Status (object 40) point 29, Fault Number for Selected Fault Summary
Report.
15. Point represents assigned phase accumulated transformer pole duty as a centipercent of the
maximum duty (DMAX) that the transformer contacts can withstand before they need service.
Transformer Duty for Phase A, B and C is calculated as ΣI or ΣI2. This is defined by Transformer
Duty Operation Mode 0/1/2 entered via ASCII protocol command ST-DUTY. DMAX is defined
through the same ST-DUTY command (refer to BE1-CDS Instruction Manual). Point value range
is from 0 to 20,000, where 20,000 represents 200% of DMAX. Delta of 20 centipercent will cause
an event.
16. This is the number of recorded transformer through-fault operations (0 to 99,999). If the
operations counter exceeds 99,999, the counter will wrap back to 0 (zero). This value can be
changed via object 41, point 8 to any value from 0 to 99,999. Delta of 1 will cause an event.
17. Measured freq. value is in centihertz. For example 5506 value is 55.06 hertz. Frequency Delta of
0.01 hertz deviation will cause an event.
5-14 DNP Protocol BE1- CDS
18. Latched Targets Status format is described in Table 6, under Note 6. Delta of 1 deviation will
cause en event. Latched Targets can be reset via object 41, point 11.
19. BF status is a bit mapped variable with format described in Table 7. Delta of 1 deviation will cause
an event.
Table 7. Breaker Status Format
Value / Bit Mask (hex) Description
0001 Breaker Operation Control State: {1=Breaker Operation
Enabled; 0= Breaker Operation Disabled }
0002 Breaker State { 1=Breaker Opened ; 0= Breaker Closed }

20. Current analog input point generates an analog event if the current value is greater than the
previous current value plus the dead band, or less than previous current value minus the dead
band. The dead band for an analog event is configurable via Analog Output point 31, Current
Dead band. The default value for dead band is set to be ±2.5% of the primary nominal current.
For more information about dead band configuration see the paragraphs under Analog Output
Status And Control Points, point 31, Note 16.
21. Differential Compensated Current is expressed as differential compensated per unit current
multiplied by TAP. Read of this point returns differential compensated per centiunit current (value
from 0 to 10,000). For example, if the return read value is 27 it means that the differential
compensated current is equal to 27 times 0.01 times TAP which is equal to 0.27 time TAP. Delta
of 10 per centiunit deviation will cause en event.
22. Differential operating current is expressed as differential operating per unit current multiplied by
TAP. Read of this point returns differential operating per centiunit current (value from 0 to 10,000).
For example, if the return read value is 40 it means that the differential operating current is equal
to 40 times 0.01 times TAP which is equal to 0.40 times TAP. Delta of 10 per centiunit deviation
will cause an event.
23. Differential 5TH and 2nd harmonic currents are expressed as a percentage of the operating current.
Read of this point returns centipercent value (value from 0 to 10,000) of the operating current. For
example, if the return read value is 1400, it means that the harmonic current is equal to 14 percent
of IOP. Delta of 10 centipercent deviation will cause an event.
24. Delta of 1 bit (any change) will cause an event.
25. Read value of phase rotation is 1 for ABC and 2 for ACB.
26. Read value presents ratio in turns.
27. Read values for CT Connection is 0 =WYE , 1=DAB, 2=DAC and 3=NA (Not Available).
28. Read values for TX Connection is 0 =WYE , 1=DAB, 2=DAC and 3=NA (Not Available).
29. Read values for Ground Source is 0=NO, 1=YES, and 2=NA.
30. Read values for Hardware Output Control is 1 = Enabled, and 0=Disabled.
31. Logic Mode of AUX x43 switch can be 0(disable), 1(enable), 2(on/off), and 3 (off/momentary on).
(See ASCII command SL-43x in Instruction Manual for the BE1-CDS.)
32. Read values for Setting Group Mode are 0=Disabled, 1=discrete select, and 2= binary select.
Setting group can be controlled via DNP object 12 if value is 1 or 2.
33. Read values for 101 Breaker Control Switch Mode is 0=Disabled and 1=Enabled.
34. The BE1-CDS relay system status is represented as six, 16-bit mapped variables (see Table 8).
Table 8. Relay Status
BIT Mask (hex) Part 1 Part 2 Part 3 Part 4 Part 5 Part 6
0001 50TPT 151 QT VO A IN 1 50TPPU 151QPU
0002 150TPT 251 QT VO 1 IN 2 150TPPU 251QPU
0004 250TPT BFT VO 2 IN 3 250TPPU BFPU
0008 50TNT 87NDT VO 3 IN 4 50TNPU 87NDPU
0010 150TNT 87RT VO 4 IN 5 150TNPU 87RPU

BE1- CDS DNP Protocol 5-15


BIT Mask (hex) Part 1 Part 2 Part 3 Part 4 Part 5 Part 6
0020 250TNT 87UT VO 5 IN 6 250TNPU spare
0040 50TQT 2NDHAR VO 6 IN 7 50TQPU ARST KEY
0080 150TQT 5THHAR VO 7 IN 8 150TQPU TRST KEY
0100 250TQT spare VO 8 spare 250TQPU 43
0200 51PT 62 VO 9 ALMMAJ 51PPU 143
0400 151PT 162 VO 10 ALMMIN 151PPU 243
0800 251PT SG0 VO 11 ALMLGC 251PPU 343
1000 51NT SG1 VO 12 CKTMON 51NPU 443
2000 151NT SG2 VO 13 101T 151NPU 543
4000 251NT SG3 VO 14 101C 251NPU 643
8000 51QT LOGIC 0 VO 15 101SC 51QPU 743
(always 0)

ANALOG OUTPUT STATUS POINTS AND CONTROL BLOCKS


Table 9 lists both the Analog Status Points (Object 40) and the Analog Output Control Blocks (Object 41).
It is important to note that Analog Output Status Points are not included into Class 0.
The Return Status Value for object 41 for all control operations may be 6 (hardware problem) due to a
value out of range, or a relay internal state. One of the reasons for rejection may be if another
communication port or front panel HMI is actively programming. For more information, see the BE1-CDS
Instructional Manual, Section 7, Communications, Command Descriptions, Changing Settings Through
The Serial Port.

Table 9. Analog Output Status Points and Control Blocks


Analog Output Status Points
Object Number: 40
Variations Supported: 1, 2
Request Function Codes supported: 1 (read)
Default Variation Reported When Variation 0 Requested: 2 (16-Bit Analog Output Status)
Analog Output Blocks
Object Number: 41
Variations Supported: 1, 2
Request Function Codes supported: 3(select), 4(operate), 5(direct operate), 6 (direct operate, noack)

Index Description Notes


0 Hardware Output Logic Control Mode 1,2
1 43 AUX Virtual Switch Logic Mode 1,3
2 143 AUX Virtual Switch Logic Mode 1,3
3 243 AUX Virtual Switch Logic Mode 1,3
4 343 AUX Virtual Switch Logic Mode 1,3
5 443 AUX Virtual Switch Logic Mode 1,3
6 543 AUX Virtual Switch Logic Mode 1,3
7 643 AUX Virtual Switch Logic Mode 1,3
8 743 AUX Virtual Switch Logic Mode 1,3
9 Active Setting Group Control Mode 1,4
10 101 Breaker Control Switch Mode 1,5

5-16 DNP Protocol BE1- CDS


Index Description Notes
11 Target Status Reset 6
12 Major Alarms Reset 7
13 Minor Alarms Reset 7
14 Logic Alarms Reset 7
15 Relay Trouble Alarms Reset 8
16 Breaker Accumulated Duty for Phase A 9
17 Breaker Accumulated Duty for Phase B 9
18 Breaker Accumulated Duty for Phase C 9
19 Breaker Operation Counter 10
20 Transformer Accumulated Duty for Phase A 11
21 Transformer Accumulated Duty for Phase B 11
22 Transformer Accumulated Duty for Phase C 11
23 Transformer Through Fault Operation Counter 12
24 Peak Demand Current Since Reset - Phase A 13
25 Peak Demand Current Since Reset - Phase B 13
26 Peak Demand Current Since Reset - Phase C 13
27 Peak Demand Current Since Reset - Neutral 13
28 Peak Demand Current Since Reset - Negative Sequence 13
29 Fault Number for Selected Fault Summary Report 14
30 Synchronization Time Period 15
31 Current Dead Band 16

Notes for Table 9:


1. Note that this data is a setting, and as a such, it takes effect after being saved to a non-volatile
memory.
The procedure for saving data to a non-volatile memory is performed only once per request for all
points requested to be changed through function Operate(4), Direct Operate(5) or Direct Operate
No Ack (6).
Saving to a non-volatile memory is not implemented on a per point basis because it would
significantly prolong requested message processing time and cause response time-out. It is
important to note that object 12 (Binary Output Status) points from 0 to 21 can be successfully
controlled only if the function blocks mode are enabled at the time of parsing. This is the reason
that in the same request, with FC= 5 or 6, specific Binary Output Status points can not be first
Enabled via the Mode point of object 41, and controlled immediately after that (object 12).
For example: To control any 43 Aux Control Relay Output Block, Master should do the following
steps:
1. Enable control of x43 Aux Switch(s) via request(s) with FC=(3, 4) or 5 or 6 for specific point(s)
of object 41.
2. Control Binary Output Status point(s) (object 12) with via next request(s).
2. Hardware Output Logic Control Mode can be 0 (Disable) or 1(Enable). If hardware outputs are to
be controlled via object 12 (Control Relay Output Blocks), their control must be Enabled through
this point. (See ASCII command CS/CO-OUT=ENA/DIS in Instruction Manual for the BE1-CDS.)
3. Logic Mode of AUX x43 switch can be 0(disable), 1(enable), 2(on/off), and 3 (off/momentary on).
(See ASCII command SL-43x in Instruction Manual for the BE1-CDS.) Depending on the Logic
Mode value, AUX x43 Switch can or can not be successfully controlled via the Control Relay
Output Block x43.

BE1- CDS DNP Protocol 5-17


4. Setting Group Mode can be 0(disable), 1 (discrete select ) or 2 ( binary select). If the Setting
Group is to be switched via object 12 (Control Relay Output Block), it must be first Enabled via this
point. (See ASCII command SL-GROUP in Instruction Manual for the BE1-CDS.)
5. Logic Mode of the 101 Breaker Control Switch can be 0(disable) or 1(enable). Depending on this
point value, the 101 Virtual Breaker Control Switch can or can not be successfully controlled via
Control Relay Output Block point for 101 Virtual Breaker Control Switch. (See ASCII command
SL-101 in Instruction Manual for the BE1-CDS.)
6. Target Status Reset Control can only be reset with write value equal zero. A read of this point
returns 1 if there are active targets, or 0 if targets are not active. Targets Status can be read as
Analog Input objects (object 30) points 62, 63, 64, and 65.
7. Major, Minor, and Logic Alarms are 32 bit mapped variables as described in Table 10. Writing
value 0 will reset the alarms. Note that only latched alarms will be cleared.
Table 10. Major, Minor, And Alarms Status Format
Bit Mask (hex) Name Bit Mask Name
(hex)
00000001 Output Circuit Open 00010000 EE NON –FATAL ERR
00000002 Breaker Fail 00020000 OUTPUT OVERRIDE
00000004 Differential 00040000 LOSS OF IRIG
00000008 Access Lost 00080000 Setting Group Change Alarm Active
00000010 Breaker Alarm #1 00100000 VO13 LOGIC ALARM
00000020 Breaker Alarm #2 00200000 VO14 LOGIC ALARM
00000040 Breaker Alarm #3 00400000 VO15 LOGIC ALARM
00000080 P Demand 00800000 FLT RPT TIMEOUT
00000100 N Demand 01000000 TRANSFORMER ALARM 1
00000200 Q Demand 02000000 TRANSFORMER ALARM 2
00000400 Group Override 04000000 TRANSFORMER ALARM 3
00000800 SYS I/O Delay 08000000 LOGIC=NONE
00001000 Comm Error 10000000 spare
00002000 Clock Error 20000000 spare
00004000 uP Reset 40000000 spare
00008000 Settings Changed 80000000 spare

8. Relay Trouble Alarms can be reset by writing value 0 to this point. This is a 16-bit mapped
variable and is described in Table 11. Only alarms with an asterisk (*) are implemented and can
be read as Binary Input (object 1) points. (For more detailed information, see Section 6 Reporting
And Alarm Functions, Relay Trouble Alarms, in the BE1-CDS Instruction Manual.)
Table 11. Relay Trouble Alarm Format
Bit Mask (hex) Name Bit Mask (hex) Name
0001 RAM FAILURE 0100 SET DFLT LOADED
0002 ROM FAILURE 0200 CAL DFLT LOADED
0004 uP FAILURE 0400 DSP FAILURE
0008 EEPROM FATAL ERROR * 800 Spare
0010 ANALOG FAILURE * 1000 Spare
0020 CALIBRATION ERR * 2000 Spare
0040 PWR SUPPLY ERR 4000 Spare
0080 WATCHDOG FAILURE 8000 Spare
9. This point represents assigned phase accumulated breaker pole duty as a centipercent of the
maximum duty (DMAX) that the breaker contacts can withstand before they need service. Breaker
Accumulated Duty for Phase A, B, and C is calculated as ΣI or ΣI2. This is defined by Breaker

5-18 DNP Protocol BE1- CDS


Contact Duty Operation Mode 0/1/2 entered via ASCII protocol command SB-DUTY. DMAX is
defined through the same SB-DUTY command ( refer to Instruction Manual for BE1-CDS).
Allowed value range is from 0 to 20000, where 20000 represents 200% of DMAX.
Example: To change accumulated breaker duty for Phase B to 134 % of DMAX, set point 17 using
the appropriate control function(s) code, with value 13400. A read of point 17 will return a value of
13400 (134% of DMAX)
10. Read value of this point is a number of recorded breaker operations (0 – 99999). If the operations
counter exceeds 99999, the counter will wrap back to 0 (zero). It acts as a counter, but is
implemented as analog object so that the initial value can be set or current value changed to any
value from 0 to 99999.
11. This point represents assigned phase accumulated transformer pole duty as a centipercent of the
maximum duty (DMAX) the transformer contacts can withstand before they need service.
Transformer Duty for Phase A, B, and C is calculated as ΣI or ΣI2. This is defined by Transformer
Duty Operation Mode 0/1/2 entered via ASCII protocol command ST-DUTY. DMAX is defined
through the same ST-DUTY command ( refer to the Instruction Manual for BE1-CDS-220).
Example: To change accumulated transformer duty for Phase B to 134 % of DMAX, set point 21
via object 41, variation 1 or 2, using appropriate control function(s), with value 13400. To read the
value of Accumulated Transformer Duty for Phase B, Read point 21, Obj 40, variation 1 or 2. The
returned value of 13400 means 134% of DMAX.
12. Read value of point 23 is a number of recorded transformer through fault operations (0 – 99999).
If the operations counter exceeds 99999, the counter will wrap back to 0 (zero). It acts as a
counter, but is implemented as analog object so that the initial value can be set, or the current
value changed to any value from 0 to 99999.
13. Peak Demand currents, points 24 to 28, can only be set to value 0 (Reset). Point read value
presents Peak Demand current in centiamps. For Example: 670 represents 6.7 amperes.
14. Fault Number for Selected Fault Summary Report. This point value range is from 1 to 255. The
Fault Summary Report for this selected fault number will be available as analog objects from point
134 to 171. If the Fault Summary Report for the Selected Fault does not exist in the relay at that
time, the Return Status Value for object 41 will be 6 (hardware problem).
15. Time period, in milliseconds, when the relay (slave) sets “NEED TIME” bit in first octet of the
Application Response Header Internal Indication. When time is set by the Master via object 50
(write function), the relay resets this bit. Relay sets this bit again, periodically, if the time period is
not zero. Default value on Cold and Warm Restarts is 0. This means that on Cold and Warm
Restarts, this bit will never be set. Allowed value is from 0 to 231-1 = 2,147,483,647 milliseconds.
16. Change Event Dead band is programmable via this point. Point value must be entered as a
percentage of primary nominal current multiplied by 10. Allowed range is from 10 to 100 in steps
of 1. This represents 1 to 10% in steps of 0.1%. The Default value is 25 (2.5%).
Example: To configure Current Change Event Dead Band to 4% of primary nominal current, enter
for point 31 the value 40. Relay converts this percentage into an ampere value. For a 5 ampere
relay, and CT1 ratio =120 turns, dead band value in amperes for winding 1 current is 5 times 120
times 4 times 0.01 = 24 primary A (2400 centiamps).
Current threshold for winding 1 = previous current value ±24 amps.
If the CT2 ratio = 60 turns, dead band value in amperes for winding 2 current is 0.04 times 60
times 5 = 12 primary amperes (1200 centiamps). Current threshold for winding 2 = previous
current value ±12 amps.
If the CT ratio for ground is 12, then utilized dead band for ground current is 0.04 times 12 times 5
= 2.4 primary amperes (240 centiamps). Ground threshold = previous ground current value ±2.4
amps.

BE1- CDS DNP Protocol 5-19


8-BIT UNSIGNED INTEGER, OBJECT 102
Table 12 is the point list for Object 102, and lists the 8-Bit Unsigned Integer Points. Note that this object
has only variation 1 and can not be requested with default variation 0.
Table 12. Object 102, 8-Bit Unsigned Integer Points
8-Bit Unsigned Integer
Object Number: 102
Variations Supported: 1
Request Function Codes supported: 1 (read)

Index Description
0-9 Model Number
10 - 28 Application Software Version Number and Date
29 - 47 DSP Software Version Number and Date
48 - 66 Boot Software Version Number and Date
67 - 80 Serial Number
81 - 102 Style Number
103 - 118 Part Number
119 - 150 Relay ID
151 - 182 Station ID
183 - 214 User ID #1
215 - 246 User ID #2

Explanation:
Each point represents one character of a particular string.
Example: To read the Model Number, which is BE1-CDS220, the returned read values for points 0 to 9
are:
Point 0 1 2 3 4 5 6 7 8 9
Read Value in B E 1 - C D S 2 2 0
ASCII format

Object 102 is not included in Class 0 poll response.

5-20 DNP Protocol BE1- CDS


ROUTE 143, BOX 269
HIGHLAND, IL 62249 USA
http://www.basler.com, info@basler.com
PHONE 618-654-2341 FAX 618-654-2351

Vous aimerez peut-être aussi