Vous êtes sur la page 1sur 4

2011 IEEE GCC Conference and Exhibition (GCC), February 19-22, 2011, Dubai, United Arab Emirates

MITIGATION OF MAGNETIC FIELDS NEAR TRANSMISSION


LINES USING A PASSIVE LOOP CONDUCTOR

Redy Mardiana and Majid Poshtan

Department of Electrical Engineering, The Petroleum Institute


PO Box 2533, Abu Dhabi, United Arab Emirates

ABSTRACT established [2-5], the concept described here includes the


investigation of the effect of width and height of passive
This paper presents a concept to reduce the magnetic field loop conductor on the reduction of magnetic field. In this
generated from ac overhead transmission lines. The study, a transmission line with a flat conductor
mitigation of magnetic field is performed by using a configuration is considered. The magnetic field density
passive loop conductor. The method is applied to a flat above the ground along lateral distance is calculated.
transmission line configuration which is used frequently Application of the passive loop concept to other
in extra high-voltage system. The effect of width and configurations (e.g. delta, vertical) may provide relative
height of passive loop conductor on the reduction of performance different from that shown for the flat
magnetic field intensity is further investigated. Numerical
configuration [2], but investigation of such applications is
results of magnetic field mitigation and further discussion
not performed in this initial study.
are provided.
2. MITIGATION OF MAGNETIC FIELDS
Index Terms — Magnetic Fields, Passive Loop,
Transmission Line, Magnetic Field Mitigation.
2.1. Review of Magnetic Field Calculation

At power frequency, the magnetic-field calculation can be


regarded as a quasi-static problem, thus, the magnetic
1. INTRODUCTION
field can be solved by static techniques. Dealing with ac
Power transmission utilities are challenged by the need to overhead transmission lines, the following assumptions
expand transmission system capacity to meet growing are commonly made:
energy demands. The acquisition of new transmission
right-of-way (ROW) is very difficult and expensive due to 1. Electrical resistivity of the soil is assumed as infinite.
land use public concerns and, more recently, the 2. The effect of phase current unbalance is neglected.
biological effects of ELF (extremely low frequency) 3. Currents induced inconductive elements within the
soil or close to line are ignored.
magnetic fields from power facilities [1]. As a
4. The effect of harmonic currents is neglected.
consequence, the transmission systems must increase their
5. Phase conductors and shield wires are straight,
capability and minimize land use while attenuating
horizontal, and infinitely long.
electromagnetic fields at ROW edge [2]. Some concepts,
such as modified transmission tower configurations, are If the above assumptions hold, the Ampere’s law is
very effective in reducing magnetic fields but are suitable equivalent to the Biot-Savart law [6]. So the Biot-Savart
only for new or completely rebuilt lines. This approach is law can be used to determine the magnetic field at an
expensive and needs power shut-down of existing lines. arbitrary observer position. As shown in Fig. 1, the
A magnetic field mitigation concept is presented in
magnetic field flux density B at observer point (xj, yj)
this paper. The mitigation concept can be applied without
produced by an infinite straight conductor is expressed by
requiring any modification to an existing transmission
line. Installation of this concept also can be achieved
P0 I i
without de-energizing the existing circuits. Moreover, the Bij aI (1)
concept can also be adopted for new transmission line 2S rij
construction. The mitigation of magnetic field is
performed by using overhead passive loop conductor where I is the conductor current, P 0 is the magnetic
paralleling the existing transmission line between the line permeability of free space, r is the distance from ith phase
and the ROW edge. While the concept of passive loop
conductors to mitigate magnetic fields has been
conductor to the jth point, and aI is a unit vector. In case
of three phase line, the total unmitigated magnetic field is

978-1-61284-119-9/11/$26.00 ©2011 IEEE 665


the vectorial sum of the magnetic field vectors produced 2.2. Magnetic Field Reduction Concept
by each phase at the observer point,
A pasive loop conductor is installed beneath the outside
ª ( x  x j )a y  ( yi  y j )ax º phases of the transmission lines as shown in Fig. 2. A
P0 n
Bij ¦ Ii « i
2S i 1 «¬ ( xi  x j ) 2  ( yi  y j ) 2 »¼
» (2) horizontal passive loop is considered in this study. The
two auxiliary conductors (M1 and M2) form a loop and
ª ( yi  y j ) º are located at (xm1, ym1) and (xm2, ym2) beneath the phase
P0 n
Bx ¦
2S i 1
 Ii « 2» (3) conductors. Here, the formula to estimate an induced
«¬ ( xi  x j )  ( yi  y j ) »¼
2
current to a passive loop is derived based on the well-
known Faraday’s law. The voltage induction to the loop is
P0 n ª ( xi  x j ) º
By ¦ Ii «
2S i 1 «¬ ( xi  x j )  ( yi  y j ) »¼
2 2 » (4) obtained using the formula given by

V  jZI (8)
where n is the total number of current-carrying
conductors, a x and a y are the unit vector in x- and y- where V is the voltage induction, Z the angular frequency,
and I the magnetic flux perpendicular to the plane where
directions, respectively. It is assumed that the phase
the loop conductor exists. The amount of flux penetration
current are pure sinusodal waveforms and they can be
caused by the sinusoidally varying current in each phase
represented by
is given by [2]
I1 I max cos(Zt ) x2
I2 I max cos(Zt  120) (5) I ". ³ Bn dx
I3 I max cos(Zt  120). x1
(9)
P I" n ( x  xi ) 2  ( ym 2  yi ) 2
 0 ¦ ln m 2
Then, the total magnetic flux density vector is 4S i 1 ( xm1  xi ) 2  ( ym1  yi ) 2

B Bx ax  By a y . (6) where, Bn is the flux density component perpendicular to


the plane of the loop conductor, " is the length of
The standard technique for the measurement of transmission line, I is the phase current, and P0 is the
magnetic fields is to measure the energy of resultant field. relative permeability in air. The voltage induction to the
The energy of resultant field is commonly defined in term loop is obtained by the formula below
of rms (root-mean-square) value of magnetic field. The
j (TI 90 )
rms of resultant field of single frequency fields is the sum Ve jTV jZIe . (10)
of the of the rms values from each axis as expressed by
Induced voltage in the mitigating loop drives the
Brms Bx ( rms )  By ( rms ) . (7) mitigating current Imit through the impedance Z of the
passive loop. The induced current Imit on the loop
conductor for multiple-phase current is expressed as
This approach, however, requires separate consideration
when the fields of the higher harmonics exist.
V j (TV TZ )
I mit e jTmit e . (11)
Z

Here, Tv and Tmit are the phases of the voltage induction,


and the induced current, respectively. This induced
current Imit creates a mitigating magnetic flux density Bm
at all points of right-of-way,

Bm Bmx a x  Bmy a y (12)

ª ( ym1  y j ) º
« »
I mit P0 « ( xm1  x j )  ( ym1  y j ) »
2 2

Bmx (13)
2S « ( ym 2  y j ) »
Figure 1. Illustration of magnetic field vector. « »
«¬ ( xm 2  x j )  ( ym 2  y j ) »¼
2 2

666
unmitigated magnetic field (B), mitigating magnetic field
ª ( xm1  x j ) º (Bm), and mitigated magnetic field (Bt) for the width of 10
« » m. The peak of magnetic field density without installation
 I mit P0 « ( xm1  x j )  ( ym1  y j ) »
2 2
of passive loop (unmitigated field) is 10.34 µT. This
Bmy . (14)
2S « ( xm 2  x j ) » magnetic field is independent on the length of passive
« » loop. When a passive loop is installed 10 m above the
«¬ ( xm 2  x j )  ( ym 2  y j ) »¼
2 2
ground, the peak of magnetic field density is reduced by
1.209 µT and becomes 9.373 µT.
The mitigated magnetic field Bt(xj, yj) at each point of the
right-of-way is vectorial sum of the local original
(unmitigated) magnetic field B(xj, yj) and of the local
auxiliary (mitigating) magnetic field Bm(xj, yj).

Magnetic field density (µT)


Y

-10.575 m 10.575 m

EW EW

14.25 m
- 15 m 15 m

Lateral distance (m)


10 m
-15 m 15 m
Figure 3. Magnetic field density versus lateral distance from
centre line. The width of passive loop is 10 m.
M1 M2
10 m

Figure 2. Geometrical dimension of transmission line


Percentage reduction

configuration. EW is earth wire, while M1 and M2 are


auxilary conductors that form a passive loop.

3. CALCULATION RESULTS

The study is divided into two catagories; (a) the effect of


widht (or the distance between conductors M1 and M2) of
a passive loop on the magnetic field reduction, and (b) the
effect of height of a passive loop on the magnetic field
Lateral distance (m)
reduction. The horizontal passive loop is considered. The
calculation of magnetic field is applied to a flat Figure 4. Comparison of the percentage reduction for the
transmission line configuration which has geometrical height of passive loop of 10 m.
dimension as shown in Fig. 2. It is assumed that each
phase line carries 1500 Ampere of balanced currents. The Fig. 4 shows the comparison of percentage reduction
magnetic field distribution is calculated at tower level and for different width of passive loop. When the loop
1 meter above the ground level. The resistance of loop becomes wider, the induced voltage increases and, hence,
conductor is R = 0.051 ohm/km and geometric mean the current flowing on the loop also increases. This would
radius Ds = 0.0142 m. result in the increase of mitigating magnetic field and,
consequently, the percentage reduction becomes larger. It
3.1. Effect of Width of Passive Loop on Magnetic is interesting to note that when the width of passive loop
Field Reduction is enlarged from 40 m to 50 m, the mitigated magnetic
field is almost the same. This can be understood that
The height of passive loop conductor is constant at 10 m when the passive loop becomes wider, the impedance of
above ground level, while the width of passive loop passive loop becomes larger, meanwhile the mitigating
varies. The width varies from 10 m to 40 m with the magnetic flux to the passive loop is relatively unchanged.
increment of 10 m. As for example, Fig. 3 shows the

667
Therefore, the induced current on the passive loop is Fig. 6 shows the comparison of the percentage
almost unchanged. This result provides important reduction for different heights of the passive loop. It is
information that there is a certain width of passive loop worth noting that when the passive loop is installed above
that gives maximum reduction to the unmitigated the phase lines (i.e., at 25 m and 30 m), the magnetic field
magnetic field density. In other words, there is a certain reduction becomes smaller because the distance from the
width of passive loop that gives a lowest mitigated passive loop conductor to the point being observed is
magnetic field density. In this example, this width is larger. Also, the highest reduction is located beyond the
between 40 m and 50 m. centre line along the lateral distance. Note that the current
flowing on the passive loop at the height of 15 m has the
same amplitude as the current at the height of 25 m due to
3.2. Effect of Height of Passive Loop on Magnetic the same amount of induced current.
Field Reduction
4. CONCLUSION
The width of passive loop conductor is constant at 30 m,
while the height of passive loop above ground level The concept to reduce the magnetic field generated
varies. Fig. 5 shows the magnetic field profiles of the from overhead transmission lines has been presented. The
unmitigated magnetic field (B), induced magnetic field mitigation of magnetic field has been performed by means
(Bm) and mitigated magnetic field (Bt) for the height of 15 of a passive loop conductor. From the simulation results,
m. The peak of magnetic field density without installation the conclusion can be drawn as follows:
of the passive loop (unmitigated field) is 10.34 µT. The 1. The magnetic field reduction is affected by the width
peak of mitigating magnetic field density is 3.092 µT and and height of passive loop conductor.
peak of mitigated magnetic field is 7.641 µT. 2. When the loop becomes wider, the magnetic field
reduction becomes larger. However, there is a certain
width of passive loop that gives maximum reduction
to the unmitigated magnetic field density.
3. The higher the passive loop the lower the percentage
reduction.
Magnetic field density (µT)

REFERENCES

[1] Olsen, R.G, “The Magnetic Field Environment of Electric


Power Lines,” Panel Session on Biological Effects of
Power Frequency Electric and Magnetic Fields, IEEE
Publication 86TH0139-6-PWR, pp. 4-10, 1986.

[2] Yamazaki, K., Kawamoto, A., and Fujinami, H.,


"Requirements for power line magnetic field mitigation
using a passive loop conductor", IEEE Trans. Power
Lateral distance (m) Delivery, vol. 15, no. 2, pp. 646-651, April 2000.
Figure 5. Magnetic field density versus lateral distance from
centre line. The height of passive loop is 15 m. [3] Romero, P.C., Santos, J.R., del Pino Lopez, J.C., de la
Villa Jaen, A., Ramos, J.L.M., " A Comparative Analysis
of Passive Loop-Based Magnetic Field Mitigation of
Overhead Lines", IEEE Trans. Power Delivery, vol. 22,
no. 3, pp. 1773 - 1781, July 2007.

[4] Memari A.R., and Janischewsky, W., "Mitigation of


Percentage reduction

magnetic field near power lines", IEEE Trans. Power


Delivery, vol. 11, no. 3, pp. 1577-1586, July 1996.

[5] Walling, R.A., Paserba, J.J., and Burns, C.W., “Series-


capacitor compensated shield scheme for enhanced
mitigation of transmission line magnetic fields”, IEEE
Trans. Power Delivery, vol. 8, no. 1, pp. 461-468, January
1993.

[6] Mazzanti, G., “The Role played by Current Phase Shift on


Magnetic Field Established by AC Double-Circuit
Lateral distance (m)
Overhead Transmission Lines-Part I: Static Analysis”,
IEEE Trans. Power Delivery, vol. 21, no. 2, pp. 939-948,
Figure 6. Comparison of the percentage reduction for the April 2006.
width of passive loop of 30 m.

668

Vous aimerez peut-être aussi