Vous êtes sur la page 1sur 50

Power System Protection for Engineers – PROT 401 1

Section 5 - Power System Unbalanced Faults

Power System Protection


for Engineers

Power System
Unbalanced Faults

Copyright © SEL 2004

Power System Unbalanced Faults_r11 1


Power System Protection for Engineers – PROT 401 2

Section 5 - Power System Unbalanced Faults

Unbalanced Fault Analysis


Objectives
l Describe and Analyze Several Types of
Unbalanced Shunt Faults
l Discuss Power System Grounding Methods
l Describe the Methods for Unbalanced
Short-Circuit Current Calculation
l Discuss the Sequence Network
Interconnection for Series and Simultaneous
Faults

Power System Unbalanced Faults_r11 2


Power System Protection for Engineers – PROT 401 3

Section 5 - Power System Unbalanced Faults

Power System Faults

l Short Circuits
l Contacts With Ground
t Isolated-neutral systems
t High-impedance grounded systems

l Open Phases (series faults)

Power System Unbalanced Faults_r11 3


Power System Protection for Engineers – PROT 401 4

Section 5 - Power System Unbalanced Faults

Simple Short-Circuits

a a a a
b b b b
c c c c

Three phase Single phase Phase to Two phases


to ground phase to ground

Unbalanced

Power System Unbalanced Faults_r11 4


Power System Protection for Engineers – PROT 401 5

Section 5 - Power System Unbalanced Faults

Typical Short Circuit Type Distribution

Single-Line-to-Ground: 70 – 80 %
Double-Line-to-Ground: 17 – 10 %
Line-to-Line: 10 – 8 %
Three Phase: 3–2%

Power System Unbalanced Faults_r11 5


Power System Protection for Engineers – PROT 401 6

Section 5 - Power System Unbalanced Faults

Insulator Flashover

l The Most Common Fault is


Single-Phase-to-Ground Fault

ARC
(Flashover)

The most common fault in overhead power systems occurs due to a lightning-
induced overvoltage, when one of the insulators cannot hold the dielectric stress,
producing flashover. In most cases, this fault disappears once it is cleared, so a
reclosing operation has a high probability of success.

Power System Unbalanced Faults_r11 6


Power System Protection for Engineers – PROT 401 7

Section 5 - Power System Unbalanced Faults

Flashover in a Distribution Pole

Flashover

Power System Unbalanced Faults_r11 7


Power System Protection for Engineers – PROT 401 8

Section 5 - Power System Unbalanced Faults

Ground Faults

l An Estimated 80 Percent of all System


Faults (1 kV and Higher) Are Single-
Line-Ground Faults
l System Grounding is an Important
Issue for Utilities and Industrial
Facilities

Power System Unbalanced Faults_r11 8


Power System Protection for Engineers – PROT 401 9

Section 5 - Power System Unbalanced Faults

Effects of Ground Faults

l Hazards to Human Safety


l Thermal Stress Due to Fault Current
l Voltage Stress (Both Transient and
Sustained)
l Interference With Telecommunication
Systems
l Disruption of Power Supply

Power System Unbalanced Faults_r11 9


Power System Protection for Engineers – PROT 401 10

Section 5 - Power System Unbalanced Faults

Power System Neutral Grounding


Ground Fault Currents Depend on
Method of Neutral Grounding

Zg Fault

The neutral grounding impedance limits the ground-fault current.

Power System Unbalanced Faults_r11 10


Power System Protection for Engineers – PROT 401 11

Section 5 - Power System Unbalanced Faults

Goals of Power System Grounding

l Minimization of Equipment Voltage


and Thermal Stresses
l Compliance With Standards for
Personnel
l Safety and Communication System
Interference
l Assistance in Rapid Detection and
Elimination of Ground Faults

Power System Unbalanced Faults_r11 11


Power System Protection for Engineers – PROT 401 12

Section 5 - Power System Unbalanced Faults

Power System Grounding Methods

l Isolated Neutral
l Effective or Solid Grounding
l Low-Impedance Grounding
l High-Impedance Grounding
l Resonant Grounding

Power System Unbalanced Faults_r11 12


Power System Protection for Engineers – PROT 401 13

Section 5 - Power System Unbalanced Faults

Isolated Neutral System


A

CAB CAC
N

CBC

C
CA Ground
CB CC fault
G

A
VAN
N, G A, G
VCN

C B VAN
VBN VCN N VBN

C B

The fault current for isolated neutral systems has a magnitude equal to the
capacitive current produced by connecting one of the phases to ground. For
underground medium voltage systems, these currents are about 5 to 15 Amps,
depending on system voltage and characteristics.

Power System Unbalanced Faults_r11 13


Power System Protection for Engineers – PROT 401 14

Section 5 - Power System Unbalanced Faults

Solidly Grounded Systems

A A

Loads N Ground Fault


N Ground Fault G
G
B
B
G C
Neutral
C Conductor
G

A A
N Ground Fault VAN
A, N, G
G N, G
VCN VBN=VBG
B VCN=VCG
C B B
C VBN C

G Isolated Neutral Conductor

The fault current for solidly grounded systems could be very large. Current
magnitude depends on the fault impedance and the return characteristics of the
system.

Power System Unbalanced Faults_r11 14


Power System Protection for Engineers – PROT 401 15

Section 5 - Power System Unbalanced Faults

Low-Impedance Grounding

Ig

C
Ground
Fault
100 A ≤ Ig ≤ 400 A

The range of fault current for a low-impedance grounded neutral system is several
hundred amperes.

Power System Unbalanced Faults_r11 15


Power System Protection for Engineers – PROT 401 16

Section 5 - Power System Unbalanced Faults

High-Impedance Grounding
A

CAB CAC
N

Rgs B

Ig CBC

C
CA Ground
CB CC fault
G

5 A ≤ Ig ≤ 15 A
A
VAN
N, G A, G
VCN

C B VAN
VBN VCN N VBN

C B

For high impedance grounding systems, the magnitude of the current is similar to
the capacitive currents.

Power System Unbalanced Faults_r11 16


Power System Protection for Engineers – PROT 401 17

Section 5 - Power System Unbalanced Faults

Compensated System

N CAB
CAC
B
CBC
C

Petersen CA CB CC Ground
Coil Fault

The object of the Petersen Coil is to make the current equal to zero during a
single-phase-to-ground fault.

Power System Unbalanced Faults_r11 17


Power System Protection for Engineers – PROT 401 18

Section 5 - Power System Unbalanced Faults

Fault Impedance

l Phase Faults: Arc Resistance


l Ground Faults:
t Arc resistance
t Tower and tower footing
impedance
t Ground return path resistance
t Other components (trees, etc.)

Power System Unbalanced Faults_r11 18


Power System Protection for Engineers – PROT 401 19

Section 5 - Power System Unbalanced Faults

Effect of Fault Impedance

l Reduces Fault Current Values


l Reduces Voltage Sag in the Faulted
Phase
l Increases Measured Impedance
Values
l Limits Protection Sensitivity

Power System Unbalanced Faults_r11 19


Power System Protection for Engineers – PROT 401 20

Section 5 - Power System Unbalanced Faults

Method to Calculate Unbalanced


Short Circuits
l Determine Simulation Point
l Find System Sequence Networks
l Calculate Thevenin Equivalent
l Connect Sequence Networks, Calculate
Fault Current
l Calculate Sequence Voltages and
Currents, Find Phase Quantities

Method for calculating unbalanced short circuits:

1. Determine the point (node or bus) of the system where the short circuit will be
simulated.

2. Find the sequence networks (positive, negative, and zero) of the system

3. Find the Thevenin equivalent at that point. The three-phase Thevenin


equivalent is a simplified generator, which has positive-, negative-, and zero-
sequence networks.

4. Connect the sequence networks depending on the type of fault and calculate
the sequence fault current.

5. Using network techniques, calculate the sequence voltages and currents along
the system and then use the symmetrical components transformation to find
the phase quantities.

Power System Unbalanced Faults_r11 20


Power System Protection for Engineers – PROT 401 21

Section 5 - Power System Unbalanced Faults

The Equivalent Sequence Networks

Zg N1 N2
N
3Zg
N0
Z1 Z2 Z0
ax
bx
cx
x1 x2 x0

The sequence networks of the equivalent three-phase generator are then used to
calculate the fault currents.

Power System Unbalanced Faults_r11 21


Power System Protection for Engineers – PROT 401 22

Section 5 - Power System Unbalanced Faults

Example

What are the


values of the
phase currents
here?

69 kV

13.8 kV
x
Solid Single-Phase-
to-Ground Fault

The procedure will be illustrated by solving a numerical example.

The simple sub- transmission network (69 kV) feeds a distribution substation (13.
8 kV) through two transformers in parallel. A single phase to ground fault occurs
close to the distribution (13.8 kV) bus.

We must know the following:

a. The fault currents at the fault point

b. The currents at one of the 69 kV circuit breakers (as indicated in the


figure)

In this example, we are supposed to know all the sequence impedances of the
elements in per unit.

Power System Unbalanced Faults_r11 22


Power System Protection for Engineers – PROT 401 23

Section 5 - Power System Unbalanced Faults

Positive-Sequence Thèvenin Equivalent


Circuit in Per Unit
1.0
1.0 1.0
j0.8 j0.4 0.032+ 0.042+
j0.958 j0.61

j0.5 j0.5

0.032+j0.158 0.042+j0.210 x

1.0
j0.5 j0.5
Base: 0.0021+
j0.623
100 MVA x x

The Thevenin equivalent is found by simple parallel and series impedance


combinations. The student must work this example and find the currents and
voltages on all the important points of the system.

Note that it is assumed that both generators are at 1.0 p.u. (zero degrees). This
adds simplicity to the problem. In more precise calculations, the actual bus
voltages are considered in finding the Thevenin voltage.

Power System Unbalanced Faults_r11 23


Power System Protection for Engineers – PROT 401 24

Section 5 - Power System Unbalanced Faults

Negative-Sequence Thèvenin Equivalent


Circuit in Per Unit

0.032+ 0.042+
j0.9 j0.6 j1.058 j0.81

j0.5 j0.5

0.032+j0.158 0.042+j0.210
x

j0.5 0.019+
Base: j0.5
j0.709
100 MVA x x

The same procedure is performed over the negative-sequence network. In this


case, no voltage source is involved. Why?

Power System Unbalanced Faults_r11 24


Power System Protection for Engineers – PROT 401 25

Section 5 - Power System Unbalanced Faults

Zero-Sequence Thèvenin Equivalent


Circuit in Per Unit

0.11+ 0.15+
j0.4 j0.2 j0.91 j0.904

j0.5 j0.5

0.11+j0.51 0.15+j0.704
x

j0.5 0.065+
Base: j0.5
j0.704
100 MVA x x

The zero-sequence current considers the Delta-Wye connection of the step-up


transformers in the power plants.

Power System Unbalanced Faults_r11 25


Power System Protection for Engineers – PROT 401 26

Section 5 - Power System Unbalanced Faults

Connect and Calculate

Pos. Neg. Zero

1.0
0.019+ 0.065 +
0.021+
j0.709 j0.704
j0.623

I F1 IF 2 IF0

E
I F1 = I F 2 = I F 0 = = 0.025 - 0.49 j pu
Z1 + Z 2 + Z 0

For a single phase-to-ground fault, the sequence networks are connected in series.
Finding the sequence current at the fault point is straightforward.

Power System Unbalanced Faults_r11 26


Power System Protection for Engineers – PROT 401 27

Section 5 - Power System Unbalanced Faults

Fault Current

3E
IFa = 3IF1 = 3IF2 = 3IF0 =
Z1 + Z2 + Z0
o
= 0.076 - 1.47 j pu = 6158 Ð-87.04 A

ax
bx
cx

I fa

The phase fault current is found through the use of symmetrical components
equations.

Ia = I1 + I2 + I0 = 3I1

Power System Unbalanced Faults_r11 27


Power System Protection for Engineers – PROT 401 28

Section 5 - Power System Unbalanced Faults

Go Back – Current Divider

Pos. Neg. Zero

1.0

0.032+ I L1 0.042+ 0.032+ 0.042+ 0.11+ 0.15+


j0.958 j0.61 j1.058
I L2 j0.81
I L0 j0.904
j0.91

j0.5 j0.5 j0.5 j0.5 j0.5 j0.5


x x x
I F1 IF 2 IF0

Use the classical circuit theory to find the sequence currents in each of the
system’s branches. In this case, the use of current dividers is very effective.

Power System Unbalanced Faults_r11 28


Power System Protection for Engineers – PROT 401 29

Section 5 - Power System Unbalanced Faults

Current Divider
Pos.
0.042 + j 0.61
1.0 I L1 = I F 1 =
0.032 + j 0.958 + 0.042 + j 0.61
0.032+ 0.042+
= 0.00573 - j 0.191 p.u.
I L1
j0.958 j0.61

j0.5 j0.5 l The Same Technique is


x Used for Negative- and
Zero- Sequence Networks
I F1

The current divider technique is applied in finding the positive-sequence current at


one of the network’s branches. The same is done for the negative- and zero-
sequence networks.

Power System Unbalanced Faults_r11 29


Power System Protection for Engineers – PROT 401 30

Section 5 - Power System Unbalanced Faults

Line Sequence Currents

Pos. Neg. Zero

I L1 I L2 I L0

I F1 IF 2 IF0

Note that the three sequence currents found with the current divider technique
correspond to the sequence currents at the desired location in the system.

Power System Unbalanced Faults_r11 30


Power System Protection for Engineers – PROT 401 31

Section 5 - Power System Unbalanced Faults

Sequence and Phase Currents


I L1 = 0.00573 - j 0.191 p.u.
I L 2 = 0.00838 - j 0.213 p.u
I L 0 = 0.00724 - j 0.245 p.u

I La = I L1 + I L 2 + I L 0 = 0.021 - j 0.649 p.u.


I Lb = a 2 I L1 + aI L 2 + I L 0 = 0.019 - j 0.041 p.u.
I Lc = aI L1 + a 2 I L 2 + I L 0 = -0.019 - j 0.046 p.u.

100000
Multiply by the base: I base = A = 836.74 A
3 × 69

Once the sequence currents are known, use the symmetrical components equations
to find the phase currents at the desired location.

These currents are in per unit, and they must be in amps.

The base current is found for the 69 kV voltage level.

Power System Unbalanced Faults_r11 31


Power System Protection for Engineers – PROT 401 32

Section 5 - Power System Unbalanced Faults

Line Phase Currents

ILa = 543.34 ∠−88.12 A


ILb = 37.86 ∠−65.23 A
ILc = 41.26 ∠−112.15 A
69 kV

13.8 kV
x

Finally, multiply by the base current to find the desired currents in amps.

A very similar procedure can be carried out to find the voltages at any given
location of the network.

Power System Unbalanced Faults_r11 32


Power System Protection for Engineers – PROT 401 33

Section 5 - Power System Unbalanced Faults

Transmission Line Faults


Are Most Common

As stated before, overhead transmission lines are the elements of the power
system with the maximum exposure. Therefore, the most common faults occur on
overhead transmission lines.

Power System Unbalanced Faults_r11 33


Power System Protection for Engineers – PROT 401 34

Section 5 - Power System Unbalanced Faults

Transmission Line Faults


L

d
Equivalent Equivalent
BUS S BUS R Source
Source

I=?
V=? Fault

l What is the value if Ia, Ib, Ic, Va, Vb, Vc at


the substation for different types of faults
over the line?

The two-source equivalent is commonly used to analyze line faults. The


contribution of the system to the fault is represented by a simple (unconnected)
two-source equivalent. The simplification does not greatly affect the concept.
However, for more accurate analysis of faults, the equivalent might not produce
good results.

Power System Unbalanced Faults_r11 34


Power System Protection for Engineers – PROT 401 35

Section 5 - Power System Unbalanced Faults

Substation Phasor Voltage and


Current Behavior During Faults (1)
Ic
Va

Ia
Va Ia
Ic
Ib Vc Vb
Vc Vb

Normal Operation Ib 3PH Fault

During a three-phase fault, the three phase current magnitudes increase and the
three voltage magnitudes decrease. If the fault is perfectly balanced, the faulted
quantities stay at 120 degrees.

Power System Unbalanced Faults_r11 35


Power System Protection for Engineers – PROT 401 36

Section 5 - Power System Unbalanced Faults

Substation Voltage and Current


Behavior During Faults (2)
Ic
Va

Va

Ia
Vc Vb
Ib = Ic = 0 Vc Vb
Ia = 0

SLG Fault L-L Fault Ib

The slide shows at the left the phase voltages and currents for a single-line-to-
ground fault and, at the right, the voltages and currents for a line-to-line fault.

Power System Unbalanced Faults_r11 36


Power System Protection for Engineers – PROT 401 37

Section 5 - Power System Unbalanced Faults

Substation Voltage and Current


Behavior During Faults (3)
Ic
Va

Vc Vb

Ia = 0

Ib 2LG Fault

The slide shows the phase voltages and currents for a double line-to-ground fault.

It is very important in protective relaying to know the behavior of voltages and


currents for different fault conditions.

These quantities are the inputs to the relays. The relays make decisions based on
these quantities.

Power System Unbalanced Faults_r11 37


Power System Protection for Engineers – PROT 401 38

Section 5 - Power System Unbalanced Faults

Voltage Profiles During Faults (1)


G Fault H

No Load
Va1 Va1

3PH V1 V1
(a)

F
Va1 V1 V1 Va1
F
L-L Va1
(b) V2 V2
2

Analyze the plots for the faults indicated.

Power System Unbalanced Faults_r11 38


Power System Protection for Engineers – PROT 401 39

Section 5 - Power System Unbalanced Faults

Voltage Profiles During Faults (2)


G Fault H

No Load
Va1 Va1
V1 V1
2LG V2
F
V2
(c)

V0 Va1 V0
3
Va1 Va2
F
V1 2Va1 V1
SLG
(d) V0 3 V0

V2 V2
Va1
3

Analyze the plots for the faults indicated.

Power System Unbalanced Faults_r11 39


Power System Protection for Engineers – PROT 401 40

Section 5 - Power System Unbalanced Faults

Single-Phase-to-Ground Fault

d
Equivalent Equivalent
BUS S BUS R Source
Source

I=?
V=? Phase-A-to-
Ground Fault

Power System Unbalanced Faults_r11 40


Power System Protection for Engineers – PROT 401 41

Section 5 - Power System Unbalanced Faults

Line Fault Transients


4
x 10
2

1.5

1
Currents (A)

0.5

-0.5

-1
ia
-1.5

-2
0 0.01 0.02 0.03 0.04 0.05 0.06

Time (s)

This slide and the next show how the currents and voltages behave in the
substation during a single-phase-to-ground fault. From these figures, it is possible
to determine that the fault was a single-phase-to-ground fault. The detailed
analysis of fault transients is out of the scope of this section of the course, but the
graph is presented to give an idea of the instantaneous evolution of the phase
quantities during the fault.

Power System Unbalanced Faults_r11 41


Power System Protection for Engineers – PROT 401 42

Section 5 - Power System Unbalanced Faults

Line Fault Transients


5
x 10
1.5

Voltages (V) 1

0.5

-0.5

-1

va
-1.5
0 0.01 0.02 0.03 0.04 0.05 0.06

Time (s)

Note that the high frequency components are present not only on the faulted phase
voltage, but also on the sound phases.

Power System Unbalanced Faults_r11 42


Power System Protection for Engineers – PROT 401 43

Section 5 - Power System Unbalanced Faults

Connection of Sequence Networks

N1 N2 N0
- -
ES - ER - -
+ V1
+ V2 V0
ZS1 + ZR1 ZS2 + ZR2 ZS0 + ZR0

I1 I2 I0
IF1 IF2 IF0

The sequence networks must be connected in a series.

Note the following:

1. The positive-, negative-, and zero-sequence currents at the fault point are equal.
These currents can be easily determined by solving the simple circuit of the figure.

2. The negative- and zero-sequence relay currents can be determined by simple


application of the current divider to the corresponding sequence networks. For
example, for the zero-sequence current, we obtain: I0 = ( Zy/(Zx + Zy)) IF0 =
(AejT) IF0.; where Zx is total impedance on the relay side (S), and Zy is total
impedance on the other side ( R). The complex number AejT is the current divider
factor.

3. The relay positive-sequence current can be calculated using the current divider
formula, if the pre-fault currents are low. Otherwise, considering the differences
between ES and ER, a simple network solution is needed in the positive sequence
network.

4. The polarity of each of the sequence voltages is with respect to their


corresponding neutral (N1, N2, N0).

5. This sequence network analysis is valid only for those cases in which the two-
source equivalent used here is acceptable.

Power System Unbalanced Faults_r11 43


Power System Protection for Engineers – PROT 401 44

Section 5 - Power System Unbalanced Faults

Relay Phase Quantities

Ia = I0 + I1 + I 2
I b = I0 + a 2 I1 + aI 2
Ic = I0 + aI1 + a 2 I 2

Va = V0 + V1 + V2
Vb = V0 + a 2 V1 + aV2
Vc = V0 + aV1 + a 2 V2

Power System Unbalanced Faults_r11 44


Power System Protection for Engineers – PROT 401 45

Section 5 - Power System Unbalanced Faults

Series Faults

l Typical Causes: Broken Conductors


and Blown Fuses
l They Create System Unbalance
(Negative- and Zero-Sequence
Currents)
l We Must Consider Load

Series faults include the following:

• One open phase

• Two open phases

• Reverse phase faults

Power System Unbalanced Faults_r11 45


Power System Protection for Engineers – PROT 401 46

Section 5 - Power System Unbalanced Faults

Series Faults
One Phase Open
P n
x y

a a
x b b y N n
c c x y
n n

O n
x y

The sequence network connection shown is non-typical.

Power System Unbalanced Faults_r11 46


Power System Protection for Engineers – PROT 401 47

Section 5 - Power System Unbalanced Faults

Series Faults
One Phase Open

G H
Z1GH, Z0GH Load
V ZL
Phase a
Z1S= Z2S Open
XTG XTH

Let us analyze the example presented in the figure. Note the transformer
connections.

Power System Unbalanced Faults_r11 47


Power System Protection for Engineers – PROT 401 48

Section 5 - Power System Unbalanced Faults

Series Faults
One Phase Open
N1

V
+
ZL
Z1S G
XTG Z1GH H XTH
X Y
I1G I1H
N2

Z2S ZL
XTG G Z1GH X H XTH
Y
I2G I2H
N0

XTG XTH
G Z0GH Y H
X
I0H
I0G

The non-typical sequence network connections consider the transformers’ deltas


off the side of the fault.

If one of the transformers had a delta connection on the fault side, then the zero-
sequence current would not be present.

Power System Unbalanced Faults_r11 48


Power System Protection for Engineers – PROT 401 49

Section 5 - Power System Unbalanced Faults

Series Faults - Two Phases Open

P n
x y

a a
x b b y N
c n
c
n n x y

O n
x y

Another non-standard network connection.

Power System Unbalanced Faults_r11 49


Power System Protection for Engineers – PROT 401 50

Section 5 - Power System Unbalanced Faults

Symmetrical Components
Present During Series Faults
System Grounding
At Both Sides At One Side
One
Phase 1, 2, 0 1, 2
Open

Two
Phases 1, 2, 0 None
Open

Power System Unbalanced Faults_r11 50

Vous aimerez peut-être aussi