Académique Documents
Professionnel Documents
Culture Documents
DSEGenset
DSE7410/20 SPECIFICATION
DC SUPPLY
AUTO START & AUTO MAINS FAILURE MODULES CONTINUOUS VOLTAGE RATING
8 V to 35 V Continuous
OUTPUTS
OUTPUT A (FUEL)
15 A DC at supply voltage
OUTPUT B (START)
15 A DC at supply voltage
OUTPUTS C & D
8 A AC at 250 V AC (Volt free)
KEY FEATURES • LED and LCD alarm indication KEY BENEFITS GENERATOR
VOLTAGE RANGE
• 4-Line back-lit LCD text display • Power monitoring (kW h, kV Ar, • 132 x 64 pixel ratio display for 15 V to 333 V AC (L-N)
• Five key menu navigation kV A h, kV Ar h) clarity
• Front panel editing with PIN • Load switching (load shedding • Real-time clock provides FREQUENCY RANGE
3.5 Hz to 75 Hz
protection and dummy load outputs) accurate event logging
• Customisable status screens • Automatic load transfer (DSE7420) • Multiple date and time scheduler MAINS (UTILITY) (DSE7420)
• Power save mode • Unbalanced load protection • Set maintenance periods can VOLTAGE RANGE
15 V to 333 V AC (L-N)
• 11 configurable inputs • Independent Earth Fault trip be configured to maintain
• 8 configurable outputs • USB connectivity optimum engine performance FREQUENCY RANGE
• Flexible sensor inputs • Backed up real time clock • Built in ethernet 3.5 Hz to 75 Hz
• Configurable timers and alarms • Fully configurable via DSE communications provides BUS (DSE7410)
• 3 configurable maintenance Configuration Suite PC software advanced remote monitoring VOLTAGE RANGE
alarms • Configurable display languages • Modules can be integrated into 15 V to 333 V AC (L-N)
• Multiple date and time scheduler • Remote SCADA monitoring via building management systems FREQUENCY RANGE
• Configurable event log (250) DSE Configuration Suite PC (BMS) using MODBUS 3.5 Hz to 75 Hz
• Tier 4 CAN engine support software • Increased input and output
MAGNETIC PICK UP
• Integral PLC editor • User selectable simultaneous expansion capability via DSENet® VOLTAGE RANGE
• Easy access diagnostic page RS232, RS485 & Ethernet • Licence-free PC software +/- 0.5 V to 70 V
• CAN and Magnetic Pick-up/Alt. communications • IP65 rating (with supplied
FREQUENCY RANGE
sensing • Configurable MODBUS pages gasket) offers increased 10,000 Hz (max)
• Fuel usage monitor and low fuel • MODBUS RTU & TCP support resistance to water ingress
alarms • Advanced SMS messaging • PLC editor allows user DIMENSIONS
OVERALL
• Charge alternator failure alarm (additional external modem configurable functions to meet 240 mm x 181 mm x 42 mm
• Manual speed control (on required) specific application 9.4” x 6.8” x 1.6”
compatible CAN engines) • Additional display screens to requirements
PANEL CUTOUT
• Manual fuel pump control help with modem diagnostics • Data logging to assist with fault 220 mm x 160 mm
• Engine exerciser • Idle control for starting finding 8.7” x 6.3”
• “Protections disabled” feature • DSENet® expansion compatible
MAXIMUM PANEL THICKNESS
• kW protection • 20 parameter data logging 8 mm
• Reverse power (kW) protection 0.3”
-40 °C to +85°C
STORAGE TEMPERATURE RANGE
-40 °F to +185 °F
RELATED MATERIALS
TITLE PART NO’S
DSE7410 Installation Instructions 053-085
-30 °C to +70 °C
OPERATING TEMPERATURE RANGE
-22 °F to +158 °F
DSE7420 Installation Instructions 053-088
DSE74xx Quick Start Guide 057-162
DSE74xx Operator Manual 057-161
DSE74xx PC Configuration Suite Manual 057-160
Deep Sea Electronics Plc maintains a policy of continuous development and reserves the right to change Registered in England & Wales No.01319649 055-108/01/12 (4) US
the details shown on this data sheet without prior notice. The contents are intended for guidance only. VAT No.316923457
®
DSEGenset
ELECTRO-MAGNETIC COMPATIBILITY
The DSE7410 is an Auto Start The DSE7400 Series modules are TEMPERATURE
Control Module and the DSE7420 compatible with electronic (CAN) BS EN 60068-2-1
Ab/Ae Cold Test -30 oC
is an Auto Mains (Utility) Failure and non-electronic (magnetic pick- BS EN 60068-2-2
Control Module suitable for a wide up/alternator sensing) engines and Bb/Be Dry Heat +70 oC
variety of single, diesel or gas, offer a comprehensive number of VIBRATION
gen-set applications. flexible inputs, outputs and BS EN 60068-2-6
extensive engine protections so the Ten sweeps in each of three
major axes
A sophisticated module monitoring system can be easily adapted to 5 Hz to 8 Hz @ +/-7.5 mm,
an extensive number of engine meet industry requirements. 8 Hz to 500 Hz @ 2 gn
parameters, the DSE74xx will HUMIDITY
annunciate warnings, shutdown The modules can be easily BS EN 60068-2-30
and engine status information on configured using the DSE Db Damp Heat Cyclic 20/55 oC
@ 95% RH 48 Hours
the back-lit LCD screen, illuminated Configuration Suite Software. BS EN 60068-2-78
LED, remote PC, and audible Selected front panel editing is also Cab Damp Heat Static 40 oC
@ 93% RH 48 Hours
alarms. The module includes available.
RS232, RS485 & Ethernet ports as SHOCK
well as dedicated terminals for BS EN 60068-2-27
Three shocks in each of three major axes
system expansion. 15 gn in 11 mS
DEGREES OF PROTECTION
PROVIDED BY ENCLOSURES
BS EN 60529
IP65 - Front of module when installed into the
control panel with the supplied sealing gasket.
DSENET RS232 AND USB USB CONFIGURABLE DC OUTPUTS ANALOGUE EMERGENCY DC POWER
EXPANSION RS485 PORT HOST INPUTS SENDERS STOP SUPPLY 8-35V
ETHERNET
+
DEUTZ
DSE7410/20 ISUZU
PERKINS
CATERPILLAR
MTU
7 VOLVO
CUMMINS
OTHER SCANIA
MAINS (UTILITY) SENSING (DSE7420) N/C VOLT FREE N/O VOLT GENERATOR SENSING CHARGE FUEL & CRANK ELECTRONIC
BUS SENSING (DSE7410) OUTPUT FREE OUTPUT ALTERNATOR OUTPUTS ENGINES &
FLEXIBLE WITH CAN MAGNETIC PICK-UP
VOLTS CURRENT VOLTS
D+
W/L +
ISSUE 1