BARRETT 22/09/2006 GCCIA Interconnection Project - Phase I
Approved: Date:
LACROUX 22/09/2006 HVDC Back-to-Back Converter Facility
Scale:
Dimensions:
EARTHING GRID
MODIFICATIONS
SUMMARY
Sheet Revision
Cover sheet 1 A
Modifications 2 A
Summary 3 A
2 Calculation hypothesis 6 A
2.1 Contractual data 6 A
2.2 Soil resistivity 6 A
[2] [2-1] IEC 909 (1988), IEC 909-1 (1991), IEC 909-2 (1992), IEC 909-3 (1995)
[2-2] [2-3] Short-circuit current calculation in three-phase a.c systems
f Network frequency Hz
I Initial symmetrical three phases short-circuit current kA
3Io Earth fault short-circuit current kA
r reduction factor on shield wires and cables sheath
Is Current flowing through the shield-wires kA
It Current flowing through the transformers neutral kA
Ig Current passing to earth grid kA
Rg Grid resistance Ω
Zw self impedance of ground wire with ground return Ω
Zwl mutual impedance between phase conductor / ground-wire Ω
Zp Driving point impedance Ω
Z1 positive sequence self impedances Zpu
Z2 negative sequence self impedances Zpu
Z0 zero sequence self impedances Zpu
Esc Maximum allowable step voltage V
Etc Maximum allowable touch voltage V
Cs Reduction factor -
Kw Weight of man factor -
ρ1 Soil resistivity of the upper layer soil Ω.m
ρ2 Soil resistivity of the lower layer soil Ω.m
ρs asphalt resistivity Ω.m
2. Calculation data
2.1 Contractual data
100%
Grid ( If1)
40% 60%
The fault current is diverted through the two parts of the buried horizontal conductor (or the building
earth ring) - IEEE80-2000 chap 11.3.3
3.1.2 Miscellaneous
1 ( [1], Eq 37 sheet 41 )
A=If
TCAP × 10 − 4 K +T
. ln 0 m
t c .α r .ρ r K 0 + Ta
Connnection
apparatuses
down leads
conductor
Outdoor
Indoor /
Buried
Main earth conductor
from
Short circuit current time ( tc in s) 1 1 1
Maximum allowable temperature ( Tm in °C) 1083 1083 1 083
Maximum ambiant temperature ( Ta in °C) 35 55 55
K0=1/α0 with α0 thermal coefficient in °C 234 234 234
Thermal coefficient of resistivity of resistivity at 20°C ( αr in °C-1) 0,00393 0,00393 0,00393
Resistivity of ground conductor at 20°C ( ρr in µΩ.cm ) 1,72 1,72 1,72
Thermal capacity (TCAP in J/cm3/°C) 3,42 3,42 3,42
Short circuit current (kA) 37,8 63,0 63,0
Minimum conductor cross section area ( A in mm²) 133,3 227,4 227,4
selected conductor mm(²) 240 240 240
Power equipments will be connected at least, in two different points to the grounding grid with a
same size of buried conductor (240mm²)
Others equipments will be connected to the grounding grid with a same size of buried conductor.
(240mm²)
Ratio between the symetrical 3 phases short-circuit current and the phase-earth short-circuit current :
Reduction factor due to overhead line shield wire (or cable sheath)
When a fault current I is flowing in the phase wires, a current (1-r) I is induced in the shield wires, so the
actual current flowing through the ground is "r x I" :
r is the reduction factor due to the shield wires (or cable sheath).
The total current through earth is Ietot = r 3I0 (IEC 909-3 13a)
Where :
RE is the resistance of earth grid.
IEtot
EARTHING GRID - CALCULATION NOTE
PH001-COM-000-ERT-0065-CN rev02
page 9/20
COGELEX AL FADHILI HVDC BACK TO BACK CONVERTERS
so IG = ZE / RE IEtot
Ze RE Zp Zu
4.2 Calculations
Reduction factor due to the overhead lines shield wires (or cable sheath) :
r= 0,54
r 3 I(0)= 34,21 kA ( IEC 909-3 13a)
Ietot 34,21 kA
− 2t f
T [1] equation 79 page 84
Df = 1+ a 1− e Ta
tf
tf = 0,250 s
X/R = 90
Ta = (X/R)/ω 0,239 s
Df = 1,355
IG = Df x Ig = 16,945 kA
1000+ 1.5 ⋅ Cs × ρs
Touch voltage : Etouch = Kw [1], equation page 27
ts
1000 + 6 C s ⋅ ρ s
Step voltage : E step = Kw [1], equation page 27
ts
ρ 1 .0
1 −
ρ s
C s = 1 − 0 . 09 [1], equation 27 page 23
2 h s + 0 . 09
Weight of man Wm = 50 Kg
duration of shock current ts = 0,25 s
Earth resistivity ρ= 1000 Ω.m
ground surface resistivity (asphalt) ρs = 5000 Ω.m
Thickness of asphalt surface layer hs = 0,1 m
KW = 0,116
Cs = 0,75
This calculation is performed with the software Capeline, which is using the IEEE Vol PAS 99 N° 3 (May
June 1980).
Rg = 0,33 Ω
GPR = IG x Rg = 5592 V
Conclusion :the actual step and touch voltages are within the acceptable limits
362 V
1317 V
Annex 1
Soil resistivity measurments :
1 000
800
600
400
200
0
depth
0,0 5,0 10,0 15,0 20,0 25,0
We can notice that the selected earth model ( curve) is conservative compare to measurement ( point)
0 0
0 0
0 0
0 0
0 0
Annex 2
Earthing grid :
equipotential line
4052 V
Note : for the checking of the dangerous overvoltages, only the main grid is modelized.
Annex 3a
Calculation at New GCC substation AL FADHILI - 50Hz
Zp50 = 1,90 Ω
Annex 3b
Calculation at SECO GIS substation AL FADHILI - 60Hz
Zp60 = 1,90 Ω
Z wl
ri = 1 − ([2-3], equation 23)
Z 'w
EARTHING GRID - CALCULATION NOTE
PH001-COM-000-ERT-0065-CN rev02
page 19/20
COGELEX AL FADHILI HVDC BACK TO BACK CONVERTERS
ri = 0,54