TREMOUILLE BARRETT LACROUX

02 03/08/2007 03/08/2007 03/08/2007


Updated as per comments included in transmittal E0503 FA
MARCHAND BARRETT LACROUX
01 22/09/2006 22/09/2006 22/09/2006
Original FA

REV ESTABLISHED VERIFIED APPROVED MODIFICATIONS STATUS


% !&
!
!
$
#
!! "

Gulf Cooperation Council


COGELEX Interconnection Authority
GCCIA
Established: Date: Engineer: 455 René-Lévesque Blvd. West
MARCHAND 22/09/2006 Montreal, Quebec. Canada

Verified: Date:
BARRETT 22/09/2006 GCCIA Interconnection Project - Phase I
Approved: Date:
LACROUX 22/09/2006 HVDC Back-to-Back Converter Facility
Scale:

Dimensions:
EARTHING GRID

Sheet N°: Sheet Qty:


CALULATION NOTE
1 20
Contractor DWG N° DRAWING N°
PH001 - COM - 000 - ERT - 0065 - CN 017048-ACA30-47EE-0084 02
COGELEX AL FADHILI HVDC BACK TO BACK CONVERTERS

MODIFICATIONS

Rev. Established Verified Approved Modifications

01 MARCHAND BARRETT LACROUX Original issue


22/09/2006 22/09/2006 22/09/2006

02 TREMOUILLE BARRETT LACROUX Updated as per comments included in transmittal E0503.


03/08/2007 03/08/2007 03/08/2007

EARTHING GRID - CALCULATION NOTE


PH001-COM-000-ERT-0065-CN rev02
page 2/20
COGELEX AL FADHILI HVDC BACK TO BACK CONVERTERS

SUMMARY
Sheet Revision
Cover sheet 1 A

Modifications 2 A

Summary 3 A

1 Lists of references and symbols 4 A


1.1 List of references 4 A
1.2 List of symbols 4 A

2 Calculation hypothesis 6 A
2.1 Contractual data 6 A
2.2 Soil resistivity 6 A

3 Grounding conductor size 7 A


3,1 Hypothesis 7 A
3,1,1 Grid conductor's current 7 A
3,1,2 Miscellaneous 7 A
3,2 Buried conductor 8 A

4. Fault current flowing through the earthing grid 9 A


4.1 Principle 9 A
4.2 Calculation 10 A
4.3 Maximum grid current 11 A

5. Acceptable step and touch voltages 12 A

6. Main results of Capeline Programme 12 A


6.1 Grid resistance 12 A
6.2 Ground Potential Rise 13 A
6.3 Actual step and touch voltages 13 A

Appendix 1 Soil resistivity measurments 14 A


Appendix 2 Earth grid 15 A
Appendix 3a Calculation of Z1 and Z0, 50hZ side 16 A
Appendix 3b Calculation of Z1 and Z0, 60hZ side 17 A

EARTHING GRID - CALCULATION NOTE


PH001-COM-000-ERT-0065-CN rev02
page 3/20
COGELEX AL FADHILI HVDC BACK TO BACK CONVERTERS

1 Lists of references and symbols


1.1 List of references

[1] ANSI / IEEE Std 80 - 2000


IEEE Guide for safety in AC substation grounding

[2] [2-1] IEC 909 (1988), IEC 909-1 (1991), IEC 909-2 (1992), IEC 909-3 (1995)
[2-2] [2-3] Short-circuit current calculation in three-phase a.c systems

[3] IEEE Transactions on Power Apparatus and System


Vol. PAS-99, N° 3 May/June 1980

1.2 List of symbols

f Network frequency Hz
I Initial symmetrical three phases short-circuit current kA
3Io Earth fault short-circuit current kA
r reduction factor on shield wires and cables sheath
Is Current flowing through the shield-wires kA
It Current flowing through the transformers neutral kA
Ig Current passing to earth grid kA
Rg Grid resistance Ω
Zw self impedance of ground wire with ground return Ω
Zwl mutual impedance between phase conductor / ground-wire Ω
Zp Driving point impedance Ω
Z1 positive sequence self impedances Zpu
Z2 negative sequence self impedances Zpu
Z0 zero sequence self impedances Zpu
Esc Maximum allowable step voltage V
Etc Maximum allowable touch voltage V
Cs Reduction factor -
Kw Weight of man factor -
ρ1 Soil resistivity of the upper layer soil Ω.m
ρ2 Soil resistivity of the lower layer soil Ω.m
ρs asphalt resistivity Ω.m

h Depth of grid burial m


hs Thickness of asphalt m
Wm Weight of a man taken into account kg
Tm Maximum allowable temperature for conductors °C
Tm2 Maximum allowable temperature for down leads to the grid conductor °C
Ta Ambient temperature °C
EARTHING GRID - CALCULATION NOTE
PH001-COM-000-ERT-0065-CN rev02
page 4/20
COGELEX AL FADHILI HVDC BACK TO BACK CONVERTERS

K0 K0=1/A0 with A0 thermal coefficient of resistivity at 0°C °C


-1
αr Thermal coefficient of resistivity at reference temperature ( 20°C) °C
ρr Resistivity of the ground conductor at 20°C µΩ/cm

TCAP Thermal capacity of copper J/cm3/°C


A Minimum conductor cross section area mm²

EARTHING GRID - CALCULATION NOTE


PH001-COM-000-ERT-0065-CN rev02
page 5/20
COGELEX AL FADHILI HVDC BACK TO BACK CONVERTERS

2. Calculation data
2.1 Contractual data

Three phases symetrical short circuit current I= 63 kA


Network frequency f= 60 Hz
Short circuit current time (for thermal design) tc = 1s

Duration of shock current (human safety) with configuration of protections system


2 FAUX
Maximum operating time of primary device protection system 0,250 s
0,250s correspond to Timer 2 in Breaker Failure protection (trip of adjacents CB).

so we take into account 0,250 s


Selected value : ts = 0,250 s

2.2 Soil resistivity (See annex 1 )

Surface material resistivity (asphalt) ρs = 5000 Ω.m

Depth of the upper layer soil h1 = 2 m


Resistivity of the upper layer soil ρ 1 = 1000 Ω.m
Resistivity of the lower layer soil ρ 2 = 321 Ω.m

Maximum soil temperature Ta = 35 °C

EARTHING GRID - CALCULATION NOTE


PH001-COM-000-ERT-0065-CN rev02
page 6/20
COGELEX AL FADHILI HVDC BACK TO BACK CONVERTERS

3 Calculation of the earthing conductor size


3.1 Hypothesis
3.1.1 Conductor's current

If is the phase to earth fault current


If1 = 0,6 If
If1 = 37,80 kA

100%

Grid ( If1)

40% 60%

The fault current is diverted through the two parts of the buried horizontal conductor (or the building
earth ring) - IEEE80-2000 chap 11.3.3

3.1.2 Miscellaneous

Nature of grounding conductor


Nature of buried joints
Nature of risen joints

EARTHING GRID - CALCULATION NOTE


PH001-COM-000-ERT-0065-CN rev02
page 7/20
COGELEX AL FADHILI HVDC BACK TO BACK CONVERTERS

3.2 Buried conductor

1 ( [1], Eq 37 sheet 41 )
A=If
TCAP × 10 − 4 K +T
. ln 0 m
t c .α r .ρ r K 0 + Ta

Connnection
apparatuses

down leads
conductor

Outdoor
Indoor /
Buried
Main earth conductor

from
Short circuit current time ( tc in s) 1 1 1
Maximum allowable temperature ( Tm in °C) 1083 1083 1 083
Maximum ambiant temperature ( Ta in °C) 35 55 55
K0=1/α0 with α0 thermal coefficient in °C 234 234 234
Thermal coefficient of resistivity of resistivity at 20°C ( αr in °C-1) 0,00393 0,00393 0,00393
Resistivity of ground conductor at 20°C ( ρr in µΩ.cm ) 1,72 1,72 1,72
Thermal capacity (TCAP in J/cm3/°C) 3,42 3,42 3,42
Short circuit current (kA) 37,8 63,0 63,0
Minimum conductor cross section area ( A in mm²) 133,3 227,4 227,4
selected conductor mm(²) 240 240 240

Power equipments will be connected at least, in two different points to the grounding grid with a
same size of buried conductor (240mm²)

Others equipments will be connected to the grounding grid with a same size of buried conductor.
(240mm²)

See earthing grid in Annex 2

EARTHING GRID - CALCULATION NOTE


PH001-COM-000-ERT-0065-CN rev02
page 8/20
COGELEX AL FADHILI HVDC BACK TO BACK CONVERTERS

4. Fault current flowing through the earthing grid


4.1 Principles (reference [2-3], paragraph 3.1)

Ratio between the symetrical 3 phases short-circuit current and the phase-earth short-circuit current :

3I0 = 3 Z1/(2Z1 + Z0) I [2], equations (29) and (33)

Reduction factor due to overhead line shield wire (or cable sheath)

When a fault current I is flowing in the phase wires, a current (1-r) I is induced in the shield wires, so the
actual current flowing through the ground is "r x I" :
r is the reduction factor due to the shield wires (or cable sheath).
The total current through earth is Ietot = r 3I0 (IEC 909-3 13a)

. Current distribution between different earth electrodes :

Where :
RE is the resistance of earth grid.

Zp is the driving point impedance according to annex 3a & 3b


Zu is the input impedance of sheaths, shielding or armouring of cables.

IEtot
EARTHING GRID - CALCULATION NOTE
PH001-COM-000-ERT-0065-CN rev02
page 9/20
COGELEX AL FADHILI HVDC BACK TO BACK CONVERTERS

so IG = ZE / RE IEtot
Ze RE Zp Zu

Earth fault short-circuit current 3I0


Total current flowing to the earth through the earth grid Ig
Current flowing through the transfomers neutrals (conservative assomption = 0 kA) It

we have : Ig = r 3I0 x ZE/RE

4.2 Calculations

Single phase short-cicuit phase-earth current :


3 I0 = 63,00 kA

Current flowing through the transformers neutrals :


It = 0,00 kA

Reduction factor due to the overhead lines shield wires (or cable sheath) :
r= 0,54
r 3 I(0)= 34,21 kA ( IEC 909-3 13a)

Current flowing actually to the ground through the earthing grid :


Driving point impedance Zp50 : Zp50 = 1,90 Ω (see annex 3a)
number of lines at New GCC S/S : 4 so Zp became 1,9 / 4 = 0,475 Ohm
Driving point impedance Zp60 : Zp60 = 1,90 Ω (see annex 3b)
number of lines at SECO S/S : 6 so Zp became 1,9 / 6 = 0,317 Ohm

Ietot 34,21 kA

Ig= Zpe/(Zpe+RE) x IEtot

0,48 Ohm 0,32 Ohm 0,33 Ohm with :


(Zp50) (Zp60) (RE)* Zpe = 1 / [ 1/Zp50 + 1/Zp60 ]

Ig Zpe = 0,19 Ohm

*(RE)= 0,33 Ohm ( see 6.1 )


Ig = 12,50 kA

EARTHING GRID - CALCULATION NOTE


PH001-COM-000-ERT-0065-CN rev02
page 10/20
COGELEX AL FADHILI HVDC BACK TO BACK CONVERTERS

4.3 Maximum grid current

IG =Df Ig [1] equation 78 page 84

Df decrement factor for the entire duration of fault tf

− 2t f
T [1] equation 79 page 84
Df = 1+ a 1− e Ta

tf

tf = 0,250 s
X/R = 90
Ta = (X/R)/ω 0,239 s

Df = 1,355

IG = Df x Ig = 16,945 kA

EARTHING GRID - CALCULATION NOTE


PH001-COM-000-ERT-0065-CN rev02
page 11/20
COGELEX AL FADHILI HVDC BACK TO BACK CONVERTERS

5. Acceptable step and touch voltages

1000+ 1.5 ⋅ Cs × ρs
Touch voltage : Etouch = Kw [1], equation page 27
ts

1000 + 6 C s ⋅ ρ s
Step voltage : E step = Kw [1], equation page 27
ts

Weight of man factor 2.05 ⋅ Wm + 13.5


Kw =
1000

ρ 1 .0
1 −
ρ s
C s = 1 − 0 . 09 [1], equation 27 page 23
2 h s + 0 . 09

Weight of man Wm = 50 Kg
duration of shock current ts = 0,25 s
Earth resistivity ρ= 1000 Ω.m
ground surface resistivity (asphalt) ρs = 5000 Ω.m
Thickness of asphalt surface layer hs = 0,1 m

KW = 0,116

Cs = 0,75

Acceptable touch voltage Etouch = 1540 V


Acceptable step voltage Estep = 5464 V

6. Main results of Capeline Programme

6.1 Grid resistance

This calculation is performed with the software Capeline, which is using the IEEE Vol PAS 99 N° 3 (May
June 1980).

Rg = 0,33 Ω

EARTHING GRID - CALCULATION NOTE


PH001-COM-000-ERT-0065-CN rev02
page 12/20
COGELEX AL FADHILI HVDC BACK TO BACK CONVERTERS

6.2 Ground Potential Rise

GPR = IG x Rg = 5592 V

6.3 Actual step and touch voltages

Maximum actual touch voltage : 1317 V < 1540 V


Maximum actual step voltage : 362 V < 5464 V

Conclusion :the actual step and touch voltages are within the acceptable limits

"dangerous equipotential curve = GPR- Etouch = 4052 V

location of worst step voltage

362 V

location of worst touch voltage

1317 V

EARTHING GRID - CALCULATION NOTE


PH001-COM-000-ERT-0065-CN rev02
page 13/20
COGELEX AL FADHILI HVDC BACK TO BACK CONVERTERS

Annex 1
Soil resistivity measurments :

Test N° Spacing : a Résistivity Test N° Spacing : a Résistivity


Ohm.m Ohm.m
A 1m 372 F 1m 38
A 4m 504 F 4m 82
A 20 m 237 F 20 m 247
B 1m 302 G 1m 221
B 4m 455 G 4m 380
B 20 m 265 G 20 m 507
C 1m 262 H 1m 46
C 4m 514 H 4m 81
C 20 m 143 H 20 m 208
D 1m 1206
D 4m 552
D 20 m 603
E 1m 227
E 4m 379
E 20 m 361

Mean value at 1m 334,3 Ω.m


4m 368,4 Ω.m
20 m 321,4 Ω.m
Model : the two layer model :
Soil resistivity at depth =0 ρ1 = 800 Ohms.m
Soil resistivity from depth H downward ρ2= 321 Ohms.m
Thickness of the upper layer soil h1 = 2,00 m
1 400
two layer soil model
1 200
measure
resistivity ( Ohm.m)

1 000

800

600

400

200

0
depth
0,0 5,0 10,0 15,0 20,0 25,0

We can notice that the selected earth model ( curve) is conservative compare to measurement ( point)

So taken into account the 2 layers soil model, the resistivity is


787 Ω.m
Ω. at 0,80 m

EARTHING GRID - CALCULATION NOTE


PH001-COM-000-ERT-0065-CN rev02
page 14/20
COGELEX AL FADHILI HVDC BACK TO BACK CONVERTERS

depth two layer soil model


measure
0,1 798
1,0 776
4,4 466
6,6 384
8,8 353
11,0 340
13,2 333
15,4 330
17,6 328
19,8 326
22,0 325
1 372
4 504
20 237
1 302
4 455
20 265
1 262
4 514
20 143
1 1 206
4 552
20 603
0 0
0 0
0 0
1 227
4 379
20 361
1 38
4 82
20 247
1 221
4 380
20 507
1 46
4 81
20 208
0 0
0 0
0 0
0 0
EARTHING GRID - CALCULATION NOTE
PH001-COM-000-ERT-0065-CN rev02
page 15/20
COGELEX AL FADHILI HVDC BACK TO BACK CONVERTERS

0 0
0 0
0 0
0 0
0 0

EARTHING GRID - CALCULATION NOTE


PH001-COM-000-ERT-0065-CN rev02
page 16/20
COGELEX AL FADHILI HVDC BACK TO BACK CONVERTERS

Annex 2

Earthing grid :

equipotential line
4052 V

Depth of the grid : 0,8 m No earthroad in the switchyard

Note : for the checking of the dangerous overvoltages, only the main grid is modelized.

EARTHING GRID - CALCULATION NOTE


PH001-COM-000-ERT-0065-CN rev02
page 17/20
COGELEX AL FADHILI HVDC BACK TO BACK CONVERTERS

Annex 3a
Calculation at New GCC substation AL FADHILI - 50Hz

Calculation of the driving point impedance Zp50 (reference [2-3])


2 1/2
Zp = {Zw/2 + ((Zw/2) + Zw Rt) } ([2-3], equation 1)

Z'w = R'W + ωµ0/8 + j ωµ0/2π (µr/4n + ln (δ/r)) ([2-3], equation 24)

Zw = Z'w . dT ([2-3], equation 1) δ = 1.85/(8π²f10-7/ρaverage)1/2 ([2-3], equation 26)

average soil resistivity ( substation resistivity) ρaverage = 800 Ω.m


tower foot resistance Rt = 10,00 Ohms
shield wire !"

shield wire radius rw = 0,009 m


number of earth wires n= 2
distance between the earth wires dw = 12,3 m
Equivalent earth wire radius rww = 0,333 m
distance between two tower (presumed value) dT = 400 m
Earth wire resistance per unit length R'W = 0,18 Ω/km
Relativ permeability of earth wire µ= 7,5 S.I.
Equivalent earth penetration depth δ = 2404,07 m
Earth wire impedance 0,149 + j 0,741 Z'w = 0,149 + j 0,741 Ohms/km
Between two towers Zw = 0,060 + j 0,296 Zw = 0,06 + j 0,296 Ohms
Zw = 0,30 Ohms

Zp50 = 1,90 Ω

EARTHING GRID - CALCULATION NOTE


PH001-COM-000-ERT-0065-CN rev02
page 18/20
COGELEX AL FADHILI HVDC BACK TO BACK CONVERTERS

Annex 3b
Calculation at SECO GIS substation AL FADHILI - 60Hz

Calculation of the driving point impedance Zp60 (reference [2-3])


Zp = {Zw/2 + ((Zw/2)2 + Zw Rt)1/2} ([2-3], equation 1)

Z'w = R'W + ωµ0/8 + j ωµ0/2π (µr/4n + ln (δ/r)) ([2-3], equation 24)

Zw = Z'w . dT ([2-3], equation 1) δ = 1.85/(8π²f10-7/ρaverage)1/2 ([2-3], equation 26)

average soil resistivity ( substation resistivity) ρaverage = 800 Ω.m


tower foot resistance Rt = 10,00 Ohms
shield wire !"

shield wire radius rw = 0,009 m


number of earth wires n= 2
distance between the earth wires dw = 12,3 m
Equivalent earth wire radius rww = 0,333 m
distance between two tower (presumed value) dT = 400 m
Earth wire resistance per unit length R'W = 0,18 Ω/km
Relativ permeability of earth wire µ= 7,5 S.I.
Equivalent earth penetration depth δ = 2404,07 m
Earth wire impedance 0,149 + j 0,741 Z'w = 0,149 + j 0,741 Ohms/km
Between two towers Zw = 0,060 + j 0,296 Zw = 0,06 + j 0,296 Ohms
Zw = 0,30 Ohms

Zp60 = 1,90 Ω

Reduction factor on overhead line i (reference [2-3])

Z wl
ri = 1 − ([2-3], equation 23)
Z 'w
EARTHING GRID - CALCULATION NOTE
PH001-COM-000-ERT-0065-CN rev02
page 19/20
COGELEX AL FADHILI HVDC BACK TO BACK CONVERTERS

Geometric mean distance between phase conductors and shield-wire : d WL = 26,34 m

Z'w = 0,149 + j 0,741 Ohms/km ([2-3], equation 24)

Mutual impedance between phase conductor / ground-wire :

Z'wL = ωµ0/8 + j ωµ0/2π ln (δ/dwL) ([2-3], equation 25)


Z'wL = 0,06 +j 0,34
Z'wL = 0,06 + j 0,34 Ohms/km
ri = 0,543 +j -0,01
ri = 0,54 + j 0,01 Ohms/km

ri = 0,54

EARTHING GRID - CALCULATION NOTE


PH001-COM-000-ERT-0065-CN rev02
page 20/20