Granular
LAB EXPERIMENTS
filtration
Filter run
granular filtration - filter run lab experiments
Framework
This module explains the lab experiment on granular filtration; filter run.
Contents
This module has the following contents:
1. Objective
2. Experiment set-up
3. Theory
4. Procedure
5. Results
6. Design
7. Turbidity measurement
Data Forms
lab experiments granular filtration - filter run
sewer
sewer sewer
10 10
9 9
8 8
7 7
sewer
raw
water
1 1
+
Fe
backwash
sewer
water
granular filtration - filter run lab experiments
lab experiments granular filtration - filter run
- ��������������������������������������������
measure the pressure loss of the clean beds Flow rate: 2500 m3/h
by reading the water manometers. Required turbidity removal: 80 %
- measure at certain time intervals the water tem- Filter type: gravity, down flow, single layer
perature and give the values in the report. Filter control: constant level supernatant, constant
- switch on the dosing pump and adjust to the filtration rate (downstream control)
desired flow rate. Determine this flow rate
based on a required dosing concentration of 4 Use in your design the Lindquist diagram and the
to 8 mg Fe3+/l (the exact value is dependant of turbidity graphs.
the water quality and will be given during the
experiment). Check the dosing rate from time Suggest a number of filtration units and determine
to time. the dimensions. Have in mind the water depth
- read the water manometers every half hour. above the bed, the thickness of the bed, the free-
- take effluent samples after 15 minutes and then board, the thickness of the supporting layers and
every half hour and measure the turbidity. the construction height of the bottom.
- take samples from the single layer bed over the
total bed height, starting after 30 minutes and Part of this design is the backwash unit, thereby
then every hour and measure the turbidity. using the results of the experiment “Hydraulics of
- the filtration process is stopped as soon as a filtration”. The required backwash rate can influ-
filter breaks through or when the maximum ence the size of the filter units.
pressure loss is reached. After the experiment
the filters have to be backwashed one by one Give the hydraulic gradient of the clean filter, the
with an expansion of 30%. Backwashing is con- clogged filter and during backwashing.
tinued until the supernatant water is completely
clear. Close the backwash valve slowly.
7. Turbidity measurement
6. Design
granular filtration - filter run lab experiments
Data forms
Data form 1
lab experiments granular filtration - filter run
Data form 2
granular filtration - filter run lab experiments
Data form 3
Runtime
Uniform
Double