Installation Planning Instructions

2.0. Auxpac generating set

Wärtsilä Auxpac 1000W6L20, engine data


Auxpac generating set output 1000 kWe
Cylinder configuration 6 L
Engine speed 900 rpm
Engine output 1072 kWm
Bore 200 mm
Stroke 280 mm
Mean effective pressure 2,32 MPa
Mean piston speed 8,4 m/s
Combustion air system
Flow of air at 100% load 1,9 kg/s
Ambient air temperature, max 45 °C
Air temperature after air cooler, min 50 °C
Air temperature after air cooler, max 70 °C
Air temperature after air cooler, alarm 70 °C
Exhaust gas system (Note 1)
Exhaust gas flow at 100% load 1,95 kg/s
Exhaust gas flow at 85% load 1,69 kg/s
Exhaust gas flow at 75% load 1,52 kg/s
Exhaust gas flow at 50% load 1,08 kg/s
Exhaust gas temperature after turbocharger at 100% load 319 °C
Exhaust gas temperature after turbocharger at 85% load 323 °C
Exhaust gas temperature after turbocharger at 75% load 330 °C
Exhaust gas temperature after turbocharger at 50% load 358 °C
Exhaust gas temperature after cylinder, alarm 480 °C
Exhaust gas backpressure, max 3 kPa
Exhaust gas pipe diameter, min 350 mm
Calculated exhaust diameter for 35 m/s 344 mm
Heat balance (Note 2)
Jacket water 210 kW
Charge air (LT-circuit) 260 kW
Lubrication oil 143 kW
Radiation etc. 45 kW
Fuel system (Note 3)
Pressure before injection pumps 700 50 (7 0.5) kPa (bar)
Pressure before injection pumps, unifuel system 1000 50 (10 0.5) kPa (bar)
Viscosity range before the engine (HFO) 16...24 cSt
Viscosity range before the engine (HFO), unifuel system 12...24 cSt
Viscosity before engine (MDF), min 1.8 cSt
Temperature before engine (HFO), max 140 °C
Temperature before engine (HFO), unifuel system, max 150 °C
Fuel consumption at 100% load 199 g/kWh
Fuel consumption at 85% load 199 g/kWh
Fuel consumption at 75% load 201 g/kWh
Fuel consumption 50% load 208 g/kWh
Leak fuel quantity (MDF), clean fuel at 100% load 3,7 kg/h

Institut Maritime du Quebec 2-3


Installation Planning Instructions
2.0. Auxpac generating set

Leak fuel quantity (HFO), clean fuel at 100% load 0,7 kg/h
Lubricating oil system
Pressure before engine, nom 450 (4.5) kPa (bar)
Pressure before engine, alarm 300 (3.0) kPa (bar)
Pressure before engine, stop 200 (2.0) kPa (bar)
Priming pressure, nom 80 (0.8) kPa (bar)
Priming pressure, alarm 30 (0.3) kPa (bar)
Temperature before engine, nom 66 °C
Temperature before engine, alarm 75 °C
Temperature after engine, about 78 °C
Pump capacity (main), engine driven 32 m³/h
Priming pump capacity 10,5 m³/h
Oil volume, nom 0.76 m3
Filter fineness 25 microns
Filter difference pressure alarm 100 (1.0) kPa (bar)
Oil consumption at 100% load, approx. 0.5 g/kWh
Crankcase ventilation flow rate at full load 780 l/min
Crankcase ventilation backpressure, max. 0.4 kPa
High temperature cooling water system:
Pressure at engine, after pump, nom 200+static kPa
Pressure at engine, after pump, alarm 100+static kPa
Pressure at engine, after pump, max 500 kPa
Temperature before cylinders, approx. 83 °C
Temperature after cylinders, nom 91 °C
Temperature after engine, alarm 105 °C
Temperature after engine, stop 110 °C
Capacity of engine driven pump, nom 29 m³/h
Pressure drop over engine, total 90 kPa
Pressure drop in external system, max 120 kPa
Pressure from expansion tank, min 70 kPa
Pressure from expansion tank, max 150 kPa
Water volume in engine 0,105 m³
Low temperature cooling water system:
Pressure at engine, after pump, nom 200+static kPa
Pressure at engine, after pump, alarm 100+static kPa
Pressure at engine, after pump, max 500 kPa
Temperature before engine, min 25 °C
Temperature before engine, max 38 °C
Temperature before charge air cooler, nom 45 °C
Temperature after lube oil cooler, nom 49 °C
Capacity of engine driven pump, nom 34 m³/h
Pressure drop over charge air cooler 30 kPa
Pressure drop over oil cooler 30 kPa
Pressure drop in external system, max 120 kPa
Pressure from expansion tank, min 70 kPa
Pressure from expansion tank, max 150 kPa
Starting air system
Air pressure, nom 3000 (30) kPa (bar)

Institut Maritime du Quebec 2-4


Installation Planning Instructions
2.0. Auxpac generating set

Air pressure, alarm 1800 (18) kPa (bar)


Air pressure, max 3000 (30) kPa (bar)
Low pressure limit in air vessels 1800 (18) kPa (bar)
Air consumption per start at 20 °C 1.2 Nm3

Engine data notes:


Note 1 At an ambient temperature of 25°C.
Note 2 ISO-optimized engine at ambient conditions according to ISO 3046/1. With engine driven pumps.
Fuel net caloric value: 42700 kJ/kg. Radiation includes generator cooling power.
Note 3 According to ISO 3046/1, lower calorific value 42 700 kJ/kg at constant engine speed, with engine
driven pumps. Tolerance 5%.

Wärtsilä Auxpac 1000W6L20, generator data


Generator brand Fenxi
Frequency 60 Hz
Rated output 1250 kVa
Voltage 450 V
Rated current 1604 A
Power factor 0.8
Temperature rise F
Insulation class F

Reactances
Xd (unsat) 486 %
Xd' (sat) 24 %
X''d (sat) 12 %
Xq (unsat) 365 %
X''q (sat) 16,6 %

Time constants
Td' 0.084 s
Td'' 0.003 s
Ta 0.020 s

Air cooled generator


Heat dissipation of air cooled generator (Note 1) 57,6 kW

Generator data notes:


Note 1 Acc. to IEC 34.