17 Comprehensive Maintenance and Service

19/20
Hitachi FSDNQ series realize energy saving by part-load working operation mode in case not all indoor units are under
running operation in an office building. The system auto-restarts and recovers to the former operation mode.

efficiency

efficiency

This graph shows that the air-conditioning system is under operation of part load of 40%~ 70% during the majority of running hours. Therefore, energy saving under
part-load operation is significant.
enhancing

is the longest
and achieve low noise.

arisen realizing

The operating speed of compressor DC motor can be adjusted freely with


system capacity variability in 1Hz increment. Integrated with auto-adaptive
control technique, the capacity output can be adjusted automatically
according to actual air conditioning load to achieve a smoother curve of
temperature fluctuation to satisfy higher coziness requirements.
Great

FSDNQ Series system adopts Hitachi proprietary compressor


which has high efficient function on oil separating to conduct
the first stage oil separating.
Meanwhile, oil separator is adopted as the second stage oil
separating. Therefore the system can operate safely and
reliably.

ensuring

Equalizing operation time of each outdoor unit leads to compressors load reduction. The compressor rotation operation
effectively spreads the operation time of each compressor, extending the unit life.

1st Circle 2nd Circle 3rd Circle


sub-cooling
degrees triggered

Enthalpy

FSDNQ

Pressure

DC variable-speed motor is installed in outdoor unit, which leads to input power reduction and efficiency promotion.

which has an obvious effect


To suit with variable applications, Hitachi products realized noise reduction of indoor units via various aspects of fan motor, fan
High efficient axial fan is designed with computer blade and air duct layout, which provides customers with the quietest air conditioned environment.
fluid analysis, finite element method and
aerodynamic simulation analysis. Also the inlet and
outlet angle and structure are optimized to lead to
much higher external static pressure allowance and
sound air circulation.

In-the-ceiling
(Compact Ducted)

enables minimum

Wave mode is designed to switch demand control between ON and OFF alternatively at time intervals of 10 or 20 minutes.
The room temperature is maintained at a comfortable level with energy saving.

special
83 10
Designer
Space Saving

which helps to meet various personalized customer requirements.


due to

each H-LINK II can support up to 64 outdoor units and 160 indoor units.
HC-A648BNP1

The PC-AR has a design that matches the interior. A "self-diagnosis function" checks for problems on
printed boards in indoor and outdoor units.
The new large LCD display permits users to see the
operating conditions and settings. Equipped with energy-saving functions such as a preset
temperature range limiting function for preventing
The timer can be set at half-hour intervals up to 72 hours. excessive cooling/heating and a preset temperature
All the functions can be selected by remote control switches. automatic reset function, as well as an operation locking
mechanism and the capability to prevent users from
The PC-AR monitors the operating conditions in the forgetting to turn off the system.
system and an alarm is issued if a problem occurs. (Function selection setting is required)
HC-A648BNP1

Half-size Remote Control Switch

The main function of this easy-to-use remote control "2 remote control" or "group control" (up to 16 max.)
system is temperature setting. can be used.

Operation modes can be switched over If a problem occurs, an alarm code immediately
(when function selection setting is made). shows the details of the problem.

Suitable for facilities used by various people, such as


hotels.
Comprehensive Maintenance By using this automatic judgment function, the
sufficiency of refrigerant amount can be checked in one
and Service refrigerant cycle.

SET-FREE FSDNQ series can be operated


intelligently with no requirement for special
operating room, thus the system can be
controlled with high flexibility and convenience.

a complete stop

1.If one outdoor unit fails, the other outdoor


unit(s) can keep running if no oil
contamination occurs.

Through remote controller or 7-segment LED displays on outdoor units, the self-diagnosing error code and information can 2.If one compressor fails, the other
be easily achieved. System can be operated, managed and maintained conveniently by monitoring the system operating compressor(s) can keep running if no oil
contamination occurs.
status remotely.

Auto-restart Function
The operating data can be recorded automatically in case of accidental power failure. The system auto-restarts and recovers
to the former operation mode intelligently.

Problems can be detected


easily and resolved quickly.
Improved Indoor Air Quality

Compared with temperature control of conventional indoor air conditioning system, FSDNQ series adopt an outlet air
temperature sensor to adjust refrigerant flow by controlling high-precision EEV and to maintain the room temperature within Hitachi FSDNQ series introduce outdoor fresh air into indoor space via
0.5℃ of setting temperature, satisfying sensitive users' requirements. the all-fresh air indoor units connected. Indoor oxygen content is
improved with fresh air to create a healthy environment for living
conditions.

Environment-Friendly

requirement

environment-friendly

Hitachi 4-way cassette type distributes the airflow to every corner of


the room in 360 degree air supply by adjusting louver positions.
By adopting 4-Way circulating airflow structure, air-conditioned flow
can be distributed in all directions.
(H)

In-the-ceiling
(Compact Ducted)

In-the-ceiling
(Slim Ducted)

Floor

RPF-FSN2E

21 22
AC3Ф,380V~415V/50Hz,
380V/60Hz *3)

4.*3):For the area that the power supply type is 380V/60Hz.

23 24
AC3Ф,380V~415V/50Hz,
AC1Ф,220V/60Hz *4)
380V/60Hz *3)

22.4 28.0

19,300 24,100

76,500 95,600

23.2 28.6

20,000 24,600

79,200 97,600

25.0 31.5

21,500 27,100

85,300 107,500

52 54

470 470

1250 1250

1120 1120

118 118

(259) (259)

67 72

1100 1100

Φ9.53 Φ9.53

(3/8) (3/8)

Φ19.05 Φ22.2

(3/4) (7/8)

(H) 50(52)dB 240 200


(H) 52(54)dB
1.077 1.077

4.*3):For the area that the power supply type is 380V/60Hz.*4):For the area that the power supply type is 220V/60Hz.

25 26
In-the-ceiling (Compact Ducted)

In-the-ceiling
(Compact Ducted)

20 20 26 26 26 26

27 28
In-the-ceiling (Slim Ducted)

In-the-ceiling
(Slim Ducted)

22 22

29 30
With

22 22 22 25 25 25 25 27 27 30 30 30

31 32
Indoor Unit 2-Way Cassette Type

RCD-0.8FSN3 RCD-1.0FSN3 RCD-1.5FSN3 RCD-2.0FSN3 RCD-2.5FSN3 RCD-3.0FSN3 RCD-4.0FSN3 RCD-5.0FSN3 RCD-6.0FSN3

kW 2.3 2.9 4.1 5.8 7.3 8.3 11.6 14.5 16.5


Improvement of Energy-Saving Operation by Nominal Cooling
Adopting Motion Sensor Capacity*1)
kcal/h 2,000 2,500 3,550 5,000 6,300 7,100 10,000 12,500 14,200

Btu/h 7,900 9,900 14,100 19,800 25,000 28,200 39,700 49,600 56,300
Motion Sensor Function
The motion sensor function can adjust the setting kW 2.2 2.8 4.0 5.6 7.1 8.0 11.2 14.0 16.0
Nominal Cooling
temperature according to the human activity and it
kcal/h 1,900 2,400 3,400 4,800 6,100 6,900 9,600 12,000 13,800
controls the air flow volume and the air flow direction. Capacity*2)
Btu/h 7,500 9,600 13,600 19,100 24,200 27,300 38,200 47,800 54,600
The energy-saving is improved by combining the motion
sensor function and individual operating function kW 2.5 3.2 4.8 6.3 8.5 9.0 12.5 16.0 18.0
Nominal Heating
comparing with the standard operation.
kcal/h 2,100 2,800 4,100 5,400 7,300 7,700 10,700 13,800 15,500
Capacity
Btu/h 8,500 10,900 16,400 21,500 29,000 30,700 42,600 54,600 61,400

Improvement of Drain Pump Sound Pressure Level


dB 30/29/28/27 31/29/28/27 37/34/31/30 39/36/33/30 42/39/36/33 45/42/38/33 43/40/37/34 47/44/41/35 48/45/42/39
High-lift DC drain pump makes it possible to raise the drain (High2/High/Medium/Low)

pipe straight up, up to 850mm from the false ceiling


surface. Dimensions H x W x D mm 298 x 860 x 630 298 x 1,420 x 630

Net Weight kg 23 25 39

New Design & High Performance Air Panel Refrigerant R410A (Nitrogen-Charged for Corrosion-Resistance)

m3/min. 10/9/7.5/6.5 11/9.5/8.5/7 15/13/11.5/10 16.5/14.5/12.5/10.5 18.5/16.5/14.5/12.5 21/18.5/16/12.5 30/26.5/23/20 35/31/27/21 37/32.5/28.5/24
Simple & Stylish Design Air Flow Rate
Hi2/Hi/Me/Lo (cfm) (353/318/265/230) (388/335/300/247) (530/459/406/353) (583/512/441/371) (653/583/512/441) (742/653/565/441) (1,059/936/812/706) (1,236/1,095/953/742) (1,306/1,148/1,006/847)
Brand new design air panel. Simple stylish design yet
applicable for air inlet flat grill. Can be used as shutter at Motor W 57 57 x 2
time of OFF operation.
Connections Flare-Nut Connection (With Flare Nuts)

2-way Individual Louver Liquid / Gas mm Ф 6.35 / Ф 12.7 Ф 9.52 / Ф 15.88


Up
The newly equipped Condensate Drain VP25
individual louver setting
function allows the angle Approximate
Packing Measurement m3 0.24 0.36
of 2 louvers to be individually
Swing
adjusted.
Adaptable Panel Model P-AP90DNA (without Monitor Sensor) P-AP160DNA (without Monitor Sensor)

Color Neutral White

Dimensions H x W x D mm 30 x 1,100 x 710 30 x 1,660 x 710

Net Weight kg 7.5 10.5

Approximate 3
Packing Measurement
m 0.13 0.20

1 meter beneath the unit and 1 meter from the inlet grille.

33 34
Indoor Unit Wall Type

RPK-0.8FSNQS RPK-1.0FSNQS RPK-1.3FSNQS RPK-1.5FSNQS RPK-1.8FSNQS RPK-2.0FSNQS RPK-2.3FSNQS

2.3 2.9 3.8 4.1 5.2 5.8 6.5

2,000 2,500 3,300 3,550 4,500 5,000 5,600

7,800 9,900 13,000 14,100 17,700 19,800 22,200

2.2 2.8 3.6 4.0 5.0 5.6 6.3

1,900 2,400 3,100 3,450 4,300 4,800 5,400

7,500 9,600 12,300 13,600 17,000 19,100 21,500

2.5 3.3 4.0 4.5 5.6 6.3 7.1

2,150 2,800 3,450 3,900 4,800 5,400 6,100

8,500 11,100 13,600 15,300 19,100 21,500 24,200

38/36/32 38/36/32 40/36/34 41/38/36 42/39/35 42/39/35 45/42/39

280 280 280 280 290 290 290

11 11 11 11 12 12 12

780 780 780 780 1,050 1,050 1,050

31 31 31 31 41 41 41

220 220 220 220 220 220 220

9 9 9 9 9 9 9

10 10 10 10 13.5 13.5 13.5

22 22 22 22 30 30 30
0.8~1.5 10
1.8~2.5 13.5
8.5/7.5/6.5 8.5/7.5/6.5 9.2/7.5/6.5 10/8.5/7.5 12/10.3/8.7 12/10.3/8.7 13.7/12/10.3

30 30 30 40 50 50 60
Wireless Remote Controller as
Standard Part
Φ6.35 Φ6.35 Φ6.35 Φ6.35 Φ6.35 Φ6.35 Φ6.35
Units are equipped with wireless remote switch
(standard) and remote control switch can be supplied (1/4) (1/4) (1/4) (1/4) (1/4) (1/4) (1/4)
as optional part which can meet various central control
needs in many cases. Φ12.7 Φ12.7 Φ12.7 Φ12.7 Φ15.88 Φ15.88 Φ15.88

(1/2) (1/2) (1/2) (1/2) (5/8) (5/8) (5/8)

VP16 VP16 VP16 VP16 VP16 VP16 VP16

0.12 0.12 0.12 0.12 0.15 0.15 0.15

1 meter beneath the unit and 1 meter from the inlet grille.

35 36
Indoor Unit Ceiling Type

RPC-1.5FSN3 RPC-2.0FSN3 RPC-2.5FSN3 RPC-3.0FSN3 RPC-4.0FSN3 RPC-5.0FSN3 RPC-6.0FSN3

AC1Ф,220V~240V/50Hz,220V/60Hz

4.1 5.8 7.3 8.3 11.6 14.5 16.5

3,550 5,000 6,300 7,100 10,000 12,500 14,200

14,100 19,800 25,000 28,200 39,700 49,600 56,300

4.0 5.6 7.1 8.0 11.2 14.0 16.0

3,400 4,800 6,100 6,900 9,600 12,000 13,800

13,600 19,100 24,200 27,300 38,200 47,800 54,600

4.8 6.3 8.5 9.0 12.5 16.0 18.0

4,100 5,400 7,300 7,700 10,700 13,800 15,500

16,400 21,500 29,000 30,700 42,600 54,600 61,400

(High2/High/Medium/Low) 37/35/31/28 38/35/31/28 38/35/32/29 40/37/33/29 44/42/37/32 48/45/41/35 49/47/42/36

Neutral White

235 235 235 235 235 235 235

960 960 1270 1270 1580 1580 1580

690 690 690 690 690 690 690

26 27 35 35 41 41 41
(57) (59) (77) (77) (90) (90) (90)

R410A (Nitrogen-charged for Corrosion-resistance)

15/13/11/9 15/13/11/9 19/16.5/14/11.5 21/18.5/15.5/12.5 30/26.5/22/17 35/31/25.5/20 37/32.5/27/21


(High2/High/Medium/Low)
(530/459/388/318) (530/459/388/318) (671/583/494/406) (742/653/547/441) (1059/936/777/600) (1236/1095/900/706) (1306/1148/953/742)

50 50 80 80 160 160 160

Flare-nut Connection (with Flare Nuts)

Ф6.35 Ф6.35 Ф9.53 Ф9.53 Ф9.53 Ф9.53 Ф9.53


(1/4) (1/4) (3/8) (3/8) (3/8) (3/8) (3/8)

Ф12.7 Ф15.88 Ф15.88 Ф15.88 Ф15.88 Ф15.88 Ф15.88


(1/2) (5/8) (5/8) (5/8) (5/8) (5/8) (5/8)

VP20 VP20 VP20 VP20 VP20 VP20 VP20

0.23 0.23 0.31 0.31 0.38 0.38 0.38

Wall Mounting Bracket

1 meter beneath the unit and 1 meter from the inlet grille.

37 38
Spring White

18 22 26 27

(40) (49) (57) (60)

Floor type: 1.5 meters from floor level.


Floor concealed type: 1.5 meters from the unit and 1.5 meters from the floor level.

39 40
~

41 42
~

43 44
4-Way Cassette Type
Model RCI-1.0~6.0FSN1Q

Air-Panel P-N23NAQ

Wireless Controller Receiver PC-RLHN8Q3

2-Way Cassette Type


Model RCD-1.0~3.0FSN3 RCD-4.0~6.0FSN3

Air-Panel P-AP90DNA P-AP160DNA

Antibacterial Long-life Filter F-90MD-K1 F-160MD-K1

Filter Box B-90HD B-160HD

Receiver Kit for Wireless Control PC-ALHD1

Motion Sensor Kit SOR-NED

Duct Adapter PD-150D

In-the-Ceiling Types (Low/High Static Pressure)


RPI-0.8~2.5FSNQL RPI-3.0~6.0FSNQL
Model
RPI-0.8~2.5FSNQH RPI-3.0~6.0FSNQH

Drain Pump DUPI-132CQ DUPI-162Q

Wireless Controller Receiver PC-RLH11

Ceiling Type
Model RPC-1.5FSN3 RPC-2.0FSN3 RPC-2.5~6.0FSN3

Drain-up Mechanism Kit DUPC-63K1 DUPC-71K1 DUPC-160K1

Receiver Kit for Wireless Control PC-ALHP1

Motion Sensor Kit SOR-NEP

45 46