Overhead Electric Distribution Standards

RISER POLES
INTRODUCTION
1. For proper fuse coordination, refer to the SYSTEM PROTECTION section to select the
appropriate fuse for underground risers.
2. Terminators or “Potheads” and their mounting brackets are included with the associated
underground plates.
3. The terminator bracket shall always be installed a minimum of 38 inches below the cutout
and arrester bracket.
4. The feeder riser plates are no longer in this section. They have been re-named and are now
included in the SWITCHING section of this book.
5. Plate options are listed on each construction standard.
6. The plates within this section have had their names changed slightly to be consistent with
other plates within this book.
7. Hot-line clamps are not part of the riser plates and must be plated separately.
8. There is no longer a designation for tangent or deadend riser, so all riser plates can be built
on tangent or deadends, as shown in the drawings. For example, for 26.4kV, there is no
longer a DUA1 and DUA2. All 26.4kV single phase risers are now built with DUA.
9. The 26.4kV plates are shown, but the 4kV and 13.2kV plate names are also listed on each
page. The only difference is the size and kV rating of the arrester.
10. For the 26.4kV system, the 18kV arrester ARR LI 003 is now used in both riser pole and
distribution line applications. Previously, ARR LI 014 served as the riser pole arrester.

Revised: August 1, 2011 Revised By: JAM Approved By: RHS

RISER POLES
IV. 4. - Page 1 of 7
Overhead Electric Distribution Standards

DUA
SINGLE PHASE RISER – 26.4kV (RUA – 4kV, WUA – 13.2kV)
OPTIONS: 10T, 12T, 15T, 20T, 25T, 30T, 40T, 50T, 65T, 80T, 100T
BOLT PLATE: NONE

3 9
8

1
6 2

NO. ITEM ID QTY DESCRIPTION


1 ARR LI *** 1 ARRESTER, LIGHTNING, POLYMER, 3kV, 10kV, or 18kV
2 BKT AC 001 1 BRACKET, ARRESTER AND CUTOUT, SINGLE PHASE, POLE MOUNTED
3 CAI RH 010 5 CABLE, NO. 4 COVERED SOFT DRAWN COPPER, FT
4 CNN VG 003 1 CONNECTOR, VISE TYPE, 6-2 SOL. 10-2 SOL.
5 COB CO 028 5 CONDUCTOR, BARE COPPER, #4 SOFT DRAWN
6 CUT OT 004 1 CUTOUT, FUSED, 125kV BIL, 100 AMP, 27kV
7 FUS OH *** 1 GENERAL CODE FOR T-LINK FUSES
8 GUA AN 002 1 GUARD, ANIMAL, FOR USE WITH TRANSFORMERS AND ARRESTERS
9 GUA AN 006 1 GUARD, ANIMAL, FOR USE WITH FUSE CUTOUTS, SILICONE RUBBER

Revised: August 1, 2011 Revised By: JAM Approved By: RHS

RISER POLES
IV. 4. - Page 2 of 7
Overhead Electric Distribution Standards

DUAF (FIBERGLASS CONSTRUCTION)


SINGLE PHASE RISER – 26.4kV (RUAF – 4kV, WUAF – 13.2kV)
OPTIONS: 10T, 12T, 15T, 20T, 25T, 30T, 40T, 50T, 65T, 80T, 100T
BOLT PLATE: NONE

8
3

5 1
2

NO. ITEM ID QTY DESCRIPTION


1 ARR LI *** 1 ARRESTER, LIGHTNING, POLYMER, 3kV, 10kV, or 18kV
2 BKT AC 009 1 BRACKET, FIBERGLASS, ARRESTER AND CUTOUT
3 CAI RH 010 10 CABLE, NO. 4 COVERED SOFT DRAWN COPPER, FT
4 CNN VG 003 1 CONNECTOR, VISE TYPE, 6-2 SOL. 10-2 SOL.
5 CUT OT 004 1 CUTOUT, FUSED, 125kV BIL, 100 AMP, 27kV
6 FUS OH *** 1 GENERAL CODE FOR T-LINK FUSES
7 GUA AN 002 1 GUARD, ANIMAL, FOR USE WITH TRANSFORMERS AND ARRESTERS
8 GUA AN 006 1 GUARD, ANIMAL, FOR USE WITH FUSE CUTOUTS, SILICONE RUBBER

Revised: August 1, 2011 Revised By: JAM Approved By: RHS

RISER POLES
IV. 4. - Page 3 of 7
Overhead Electric Distribution Standards

DUB
TWO-PHASE RISER – 26.4kV (RUB – 4kV, WUB – 13.2kV)
OPTIONS: 10T, 12T, 15T, 20T, 25T, 30T, 40T, 50T, 65T, 80T, 100T
BOLT PLATE: NONE

1 6
3

NO. ITEM ID QTY DESCRIPTION


1 ARR LI *** 2 ARRESTER, LIGHTNING, POLYMER, 3kV, 10kV, or 18kV
2 BKT AC 002 1 BRACKET, ARRESTER AND CUTOUT, TRI-MOUNT
3 CAI RH 010 10 CABLE, NO. 4 COVERED SOFT DRAWN COPPER, FT
4 CNN VG 003 1 CONNECTOR, VISE TYPE, 6-2 SOL. 10-2 SOL.
5 COB CO 028 10 CONDUCTOR, BARE COPPER, #4 SOFT DRAWN
6 CUT OT 004 2 CUTOUT, FUSED, 125kV BIL, 100 AMP, 27kV
7 FUS OH *** 2 GENERAL CODE FOR T-LINK FUSES
8 GUA AN 002 1 GUARD, ANIMAL, FOR USE WITH TRANSFORMERS AND ARRESTERS
9 GUA AN 006 1 GUARD, ANIMAL, FOR USE WITH FUSE CUTOUTS, SILICONE RUBBER
10 WAS RD 005 3 WASHER, ROUND, 2 IN. DIA., FOR 3/4 IN. BOLT
11 WAS SF 003 1 WASHER, SQUARE, FLAT, 3 IN., FOR 3/4 IN. BOLT
12 WAS SP 002 1 WASHER, SPRING, DOUBLE HELIX, FOR 3/4 IN. BOLT

Revised: August 1, 2011 Revised By: JAM Approved By: RHS

RISER POLES
IV. 4. - Page 4 of 7
Overhead Electric Distribution Standards

DUBF (FIBERGLASS CONSTRUCTION)


TWO-PHASE RISER – 26.4kV (RUBF – 4kV, WUBF – 13.2kV)
OPTIONS: 10T, 12T, 15T, 20T, 25T, 30T, 40T, 50T, 65T, 80T, 100T
BOLT PLATE: NONE

1 5
3

NO. ITEM ID QTY DESCRIPTION


1 ARR LI *** 2 ARRESTER, LIGHTNING, POLYMER, 3kV, 10kV, or 18kV
2 BKT AC 010 1 BRACKET, FIBERGLASS, ARRESTER AND CUTOUT, TRI-MOUNT
3 CAI RH 010 20 CABLE, NO. 4 COVERED SOFT DRAWN COPPER, FT
4 CNN VG 003 1 CONNECTOR, VISE TYPE, 6-2 SOL. 10-2 SOL.
5 CUT OT 004 2 CUTOUT, FUSED, 125kV BIL, 100 AMP, 27kV
6 FUS OH *** 2 GENERAL CODE FOR T-LINK FUSES
7 GUA AN 002 1 GUARD, ANIMAL, FOR USE WITH TRANSFORMERS AND ARRESTERS
8 GUA AN 006 1 GUARD, ANIMAL, FOR USE WITH FUSE CUTOUTS, SILICONE RUBBER
9 WAS RD 005 3 WASHER, ROUND, 2 IN. DIA., FOR 3/4 IN. BOLT
10 WAS SF 003 1 WASHER, SQUARE, FLAT, 3 IN., FOR 3/4 IN. BOLT
11 WAS SP 002 1 WASHER, SPRING, DOUBLE HELIX, FOR 3/4 IN. BOLT

Revised: August 1, 2011 Revised By: JAM Approved By: RHS

RISER POLES
IV. 4. - Page 5 of 7
Overhead Electric Distribution Standards

DUC
THREE-PHASE RISER – 26.4kV (RUC – 4kV, WUC – 13.2kV)
OPTIONS: 10T, 12T, 15T, 20T, 25T, 30T, 40T, 50T, 65T, 80T, 100T
BOLT PLATE: NONE

1 6
3

NO. ITEM ID QTY DESCRIPTION


1 ARR LI *** 3 ARRESTER, LIGHTNING, POLYMER, 3kV, 10kV, or 18kV
2 BKT AC 002 1 BRACKET, ARRESTER AND CUTOUT, TRI-MOUNT
3 CAI RH 010 15 CABLE, NO. 4 COVERED SOFT DRAWN COPPER, FT
4 CNN VG 003 1 CONNECTOR, VISE TYPE, 6-2 SOL. 10-2 SOL.
5 COB CO 028 15 CONDUCTOR, BARE COPPER, #4 SOFT DRAWN
6 CUT OT 004 3 CUTOUT, FUSED, 125kV BIL, 100 AMP, 27kV
7 FUS OH *** 3 GENERAL CODE FOR T-LINK FUSES
8 GUA AN 002 1 GUARD, ANIMAL, FOR USE WITH TRANSFORMERS AND ARRESTERS
9 GUA AN 006 1 GUARD, ANIMAL, FOR USE WITH FUSE CUTOUTS, SILICONE RUBBER
10 WAS RD 005 3 WASHER, ROUND, 2 IN. DIA., FOR 3/4 IN. BOLT
11 WAS SF 003 1 WASHER, SQUARE, FLAT, 3 IN., FOR 3/4 IN. BOLT
12 WAS SP 002 1 WASHER, SPRING, DOUBLE HELIX, FOR 3/4 IN. BOLT

Revised: August 1, 2011 Revised By: JAM Approved By: RHS

RISER POLES
IV. 4. - Page 6 of 7
Overhead Electric Distribution Standards

DUCF (FIBERGLASS CONSTRUCTION)


THREE-PHASE RISER – 26.4kV (RUCF – 4kV, WUCF – 13.2kV)
OPTIONS: 10T, 12T, 15T, 20T, 25T, 30T, 40T, 50T, 65T, 80T, 100T
BOLT PLATE: NONE

1 5
3

NO. ITEM ID QTY DESCRIPTION


1 ARR LI *** 3 ARRESTER, LIGHTNING, POLYMER, 3kV, 10kV, or 18kV
2 BKT AC 010 1 BRACKET, FIBERGLASS, ARRESTER AND CUTOUT, TRI-MOUNT
3 CAI RH 010 30 CABLE, NO. 4 COVERED SOFT DRAWN COPPER, FT
4 CNN VG 003 1 CONNECTOR, VISE TYPE, 6-2 SOL. 10-2 SOL.
5 CUT OT 004 3 CUTOUT, FUSED, 125kV BIL, 100 AMP, 27kV
6 FUS OH *** 3 GENERAL CODE FOR T-LINK FUSES
7 GUA AN 002 1 GUARD, ANIMAL, FOR USE WITH TRANSFORMERS AND ARRESTERS
8 GUA AN 006 1 GUARD, ANIMAL, FOR USE WITH FUSE CUTOUTS, SILICONE RUBBER
9 WAS RD 005 3 WASHER, ROUND, 2 IN. DIA., FOR 3/4 IN. BOLT
10 WAS SF 003 1 WASHER, SQUARE, FLAT, 3 IN., FOR 3/4 IN. BOLT
11 WAS SP 002 1 WASHER, SPRING, DOUBLE HELIX, FOR 3/4 IN. BOLT

Revised: August 1, 2011 Revised By: JAM Approved By: RHS

RISER POLES
IV. 4. - Page 7 of 7