1 DESIGN DATA:
Site altitude(in metres above mean sea level) Δs = 153.00 refer drg no
25-50-82-1602
Altitude factor Sa = 1 + 0.001 Δs cl 2.2.2.2.2 of BS 6399-2
= 1.153
Terrain and building factor,Sb eff.ht distance table 4 of BS 6399-2
10 1.78
15 1.85 Considering
11.10 1.7954 critical case
2 DYNAMIC PRESSURE:
3 PRESSURE CO-EFFICIENTS:
table 5 of BS 6399-2
From the above table 5 & 16, External pressure co-effiient 'Cpe' and Internal
pressure co-efficient 'Cpi' taken as below
L=D= 92.95 m
1.3 (-)
W=B
0.3 (-) 37 m
Wind ward direction
(short face) 0.6 0.3 (-) (-) 0.3 0.5
0.3 (-) (-)
1.3 (-)
L=B= 92.95 m
0.5 (-)
W=D
0.3 (-) 37 m
0.66
Wind ward direction
(long face)
Self wt of sheeting
(Two types of sheeting (0.7mm+0.5mm thk) along with polyurethane foam
(Density =16kg/cum) having thickness of 100mm is considered
Total sheet load = = 0.2 kN/m2
c. wind load
1 Internal pressure coefficient,Cpi table 18 of BS 6399-2
0 deg 0.85
by interpolation
wind angle coefficient
0 deg -1.45
90 deg -2.4
0 deg 90 deg
p = qs * Cpe - Cpi * Ca
Considering Ca = 1
The forces are applied in the stadd program for the corresponding dimensions of structure