Académique Documents
Professionnel Documents
Culture Documents
fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSTE.2018.2825655, IEEE
Transactions on Sustainable Energy
1
1949-3029 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSTE.2018.2825655, IEEE
Transactions on Sustainable Energy
2
inverters. The power is transferred from the fully reduced below its nominal value and the amount of deviation
charged/discharged battery to the one with less of the frequency determines the amount of power to be
charging/discharging power without the limitation of the RES supplied by the auxiliary unit. Therefore, the main
power. Noncritical loads are regulated/disconnected or the contributions of the paper are as follows.
system stops when the frequency is low. F. Tidjani et al. [17] 1) Development of an energy management system for an
proposed a fuzzy logic based energy management in stand- islanded microgrid that is based on the combination of
alone mode to manage the power between the battery, gas Fuzzy Logic and bus-signalling. The supervisory
generator and PV. It also took in consideration the battery controller can be implemented wirelessly using the bus
power and SOC. However, to prevent the battery frequency of the AC microgrid.
overcharging, they used a water pump as a dummy load. This 2) Assessment of the proposed system performance in
solution is not applicable in all cases of power as the pump has meeting the design requirements and considering the
one set of rating values. constrains of the battery maximum power and SOC.
The aforementioned references for power management 3) The proposed system aims to decrease auxiliary unit
strategies with frequency bus-signalling technique use run time and then the cost while satisfying the load
conventional controllers such as Proportional-Integral (PI) demand and the battery needs.
controller for power management. No intelligent or artificial 4) Real time simulation and experimental validation of the
methods have been used with that technique where the non- proposed controller under different scenarios of
uniform nature of powers requires kind of intelligent operation and a comparison with a traditional
controller. Furthermore, some of the literature work controller.
emphasized the power management issues without bringing The paper is organized as follows. Section II gives system
any constrains to some of the energy elements as the battery overview and Section III shows droop control strategy. In
power maximum limits. Also, managing different modes of Section IV, the proposed FLC is described. Section V provides
DG units (voltage/current sources) within some constrains has real-time simulation results. Section VI shows experimental
not been fully resolved yet and research into obtaining optimal results. Finally, Section VII gives the conclusion.
operational modes continues to increase [18]. Non-
conventional type of control such as fuzzy logic controller III. SYSTEM OVERVIEW
(FLC) could be an excellent candidate for this. In an island AC microgrid with BESS and RES, the BESS
In this paper, a FLC is proposed to manage an islanded AC is used as a grid forming unit regulating the AC bus, while the
microgrid with a PV, Battery-based ESS (BESS) and micro RES is used as a grid feeding unit injecting the power into the
gas turbine units. It prevents the battery SOC and charging/ system [14], [21]. The proposed stand-alone AC microgrid
discharging power from exceeding their limits regardless of control topology is shown in Fig. 1 and it operates as follows.
the variation in the load and intermittent power generated by 1) PV unit is interfaced by a uni-directional DC/DC
the RES. It is worth mentioning here that the focus of the converter and a DC/AC inverter. The converter
study is only on the islanded mode of the microgrid. The main controls the PV output voltage to achieve maximum
contributions can be emphasized when the microgrid is power point tracking (MPPT) while the inverter
islanded. In grid-connected mode, each unit behaves regulates the DC link voltage. The PV output power is
differently without having the same concerns which this paper curtailed if the battery is fully charged and the available
addresses. However, smoothing the grid power profile needs PV power is higher than that required by the load.
to handle the same challenges as in [19], [20]. By varying the 2) BESS unit is interfaced by a bi-directional DC/DC
AC bus frequency that is used by local droop controllers; the converter and a DC/AC inverter. The converter
FLC, located in the BESS, is implemented without the need regulates the DC link voltage. The inverter is the
for any communication links between the microgrid units. The master unit that maintains and controls the AC bus
FLC decides whether to curtail the power generated by the PV frequency and voltage of the microgrid. It alters the bus
or to supplement the power from the auxiliary unit. To assess frequency according to FLC command. The BESS unit
the performance of the proposed controller, a validation has forms the AC bus by controlling the local AC voltage
been carried out using Matlab simulation and experimentally. and frequency. The BESS absorbs surplus power from
the PV unit if it exceeds the load. In the same way, the
Usually, diesel generators or gas turbines are used as the main
BESS supply required power when there is a shortage
sources which dictates the AC bus. However, the auxiliary
from the PV unit that can’t meet the load requirement.
unit (micro gas turbine) here is floating and hence it provides
3) Auxiliary unit (micro gas turbine in this case) is
power via the FLC command whenever needed (low power interfaced by a uni-directional AC/DC converter and a
from RES and/or low SOC). This can be performed without DC/AC inverter. The converter regulates the DC link
using any communication between the different generation voltage while the inverter controls the output power
units and loads. The supervisory controller is implemented according to the AC bus frequency altered based on
wirelessly using the bus frequency for the AC microgrid. The FLC command. The main role of the auxiliary unit is to
paper covers the design of a droop control which enables the support the BESS unit during low battery SOC and/or
auxiliary unit to respond automatically to the change in the low PV generation scenarios that can’t meet the load
bus frequency, so it supplies power only when the frequency is requirement.
1949-3029 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSTE.2018.2825655, IEEE
Transactions on Sustainable Energy
3
Energy Source
v PV
DC AC the bus frequency is varied either positively or negatively by
PV
DC DC Pinv ∆𝜔 which is the output from the FLC. The frequency
PWM PWM
Voltage
increment allows curtailment of the PV power and the
vPV Current Controller decrement determines the power of the auxiliary unit. Thus,
vdc
Controller
*
vPV Droop the output frequency of the battery unit is given by (3).
PI v PV Controller
I ref
𝜔𝑜
- PI dc
-
PI MPPT Vdc*
∗
𝑃𝑃𝑉
𝜔 = 𝜔𝑜 + ∆𝜔 (3)
𝜔 vPV iPV
PLL
∗
The droop control of the PV unit is given by (4) where 𝑃𝑝𝑣
∗
is the PV power demand (see Fig. 1). The 𝑃𝑝𝑣 is given by (5)
Energy Source
DC AC
∗
DC DC Pinv
where 𝑉𝑑𝑐 and 𝑉𝑑𝑐 are the DC link voltage and its set-point
Battery
PWM PWM value. 𝑘𝑝−𝑑𝑐 and 𝑘𝑖−𝑑𝑐 are the PI controller gains of the PV
DC voltage regulator and ‘s’ is the Laplace operator.
vdc Voltage
Voltage Controller Controller
Vdc*
Droop
∗
Controller
𝜔 = 𝜔𝑜 − 𝑚𝑝𝑣 (𝑃𝑝𝑣 − 𝑃𝑝𝑣 ) (4)
Pref
Supervisory
Controller
∗ 𝑘𝑖−𝑑𝑐 ∗ (5)
𝑃𝑝𝑣 = (𝑘𝑝−𝑑𝑐 + )(𝑉𝑑𝑐 − 𝑉𝑑𝑐 )
𝑠
Energy Source
DC AC
AC DC Pinv
µGT The droop control of the auxiliary unit is given by (6). The
PWM
∗
PWM
vdc Voltage power set-point 𝑃𝑎𝑢𝑥 is set to zero in the island microgrid to
Voltage Controller Controller
Vdc* supplement power automatically in response to change in the
Droop
Controller bus frequency.
Fig. 1. Proposed stand-alone AC microgrid control topology.
∗
𝜔 = 𝜔𝑜 − 𝑚𝑎𝑢𝑥 (𝑃𝑎𝑢𝑥 − 𝑃𝑎𝑢𝑥 ) (6)
Droop control [22], [23] is used in all the three DC/AC
inverters as a frequency responsive technique. The details of
𝜔
power management based on droop control and bus frequency
Varied by MPPT
signalling techniques will be discussed in the next section. It is ∗
𝜔 = 𝜔𝑜 − 𝑚𝑃𝑉 (𝑃 − 𝑃𝑃𝑉 )
important to note that the supervisory control just requires to PV
communicate with the BESS to manage the microgrid powers.
Battery ∆𝜔𝑚𝑎𝑥 +
𝑚𝑃𝑉
IV. DROOP CONTROL STRATEGY 𝜔 = 𝜔𝑜
𝑚𝑎𝑢𝑥
Frequency and voltage drooping techniques are applied to ∆𝜔𝑚𝑎𝑥 −
generators in a microgrid to have load sharing of parallel
generators. With droop control in AC systems, decentralized Auxiliary unit (aux)
control for each converter is achieved with no communication ∗
𝜔 = 𝜔𝑜 − 𝑚𝑎𝑢𝑥 (𝑃 − 𝑃𝑎𝑢𝑥 )
or only low bandwidth communication, such as power line
communication [24]. Any DC/AC inverter in a traditional 𝑃 = 𝑃𝑃𝑉 P
droop control does have an output frequency 𝜔 and a voltage Fig. 2. Power – frequency droop control curves.
amplitude 𝑉 defined by (1) and (2), respectively [25].
PPV v PV
∗
𝜔 = 𝜔𝑜 − 𝑚(𝑃 − 𝑃 ) (1) Maximum Power
Point (MPP)
PMPP v OC
𝑉 = 𝑉𝑜 − 𝑛(𝑄 − 𝑄 ∗ ) (2) v MPP
Lower Power
where 𝜔𝑜 , 𝑉𝑜 , 𝑚, and 𝑛 are the nominal frequency, nominal
voltage, frequency drooping coefficient, and voltage drooping
coefficient, respectively. 𝑃 and 𝑄 are the measured average
active and reactive powers while 𝑃 ∗ and 𝑄 ∗ are the active and v MPP v OC v PV ωo ωmax ω
reactive power demands or set-points, respectively. (a) (b)
The same droop control equation as in (2) defines the Fig. 3. PV MPP shifting operation: (a) PV power versus output voltage.
reactive power/voltage relation of the three DC/AC inverters. (b) output voltage versus frequency.
As the BESS regulates the AC bus frequency, the droop
1949-3029 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSTE.2018.2825655, IEEE
Transactions on Sustainable Energy
4
∗
Fig. 2 shows the power/frequency droop control for the power and 𝑃𝑑𝑖𝑠𝑐ℎ𝑎𝑟𝑔𝑒_𝑚𝑎𝑥 is its maximum discharging power
three units [25] based on (3), (4) and (6). When the bus value. The output is a negative shift in the frequency ∆𝜔−
frequency is shifted up, the PV power is curtailed. On the which deviates the bus frequency causing the auxiliary unit to
other hand, the auxiliary unit produces power when the supplement power.
frequency is shifted down. The output power P of the PV unit The two FLC subsystems work simultaneously. Therefore,
∗
equals the demanded power 𝑃𝑝𝑣 when the bus frequency 𝜔 the shift of frequency ∆𝜔 is the result of ∆𝜔+ and ∆𝜔− as
equals the nominal frequency 𝜔𝑜 . If the bus frequency is given by (11) where the top and bottom FLC subsystems are
shifted up, this will send a message to the MPPT controller to responsible for protection from over-charging and over-
curtail the PV power. Phase Looked Loop (PLL) is used by discharging respectively. The limit for the frequency deviation
the MPPT controller to measure the bus frequency (see Fig. 1) is set as ± 1% of the nominal value (50Hz). This provides a
and it shifts the MPP to a lower value by increasing the PV variation in the frequency between 49.5Hz and 50.5Hz. The
output voltage as shown in Fig. 3. If the bus frequency is change in frequency occurs automatically based on the results
shifted down, the DC/AC inverter of the PV unit will deliver from the two FLC subsystems. It is important to note that the
power limited by its maximum power determined by the PV curtailment wouldn’t happen if the auxiliary unit is
MPPT [25], [26]. generating power.
1949-3029 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSTE.2018.2825655, IEEE
Transactions on Sustainable Energy
5
∗
𝑆𝑂𝐶𝑚𝑎𝑥 The design requirements of interest are the
𝑆𝑂𝐶 + 1 ∆𝑆𝑂𝐶1 charging/discharging maximum power, the SOC and optimum
∗ ∗
𝑆𝑂𝐶𝑚𝑎𝑥 − 𝑆𝑂𝐶𝑚𝑖𝑛
- [0-1] Δω+ µGT running.
∆𝜔𝑚𝑎𝑥 +
𝑃𝑐ℎ𝑎𝑟𝑔𝑒 - 1 ∆𝑃𝑐ℎ𝑎𝑟𝑔𝑒 A simplified model of the AC microgrid consists of a PV,
∗
𝑃𝑐ℎ𝑎𝑟𝑔𝑒 _𝑚𝑎𝑥
+ FLC top + battery and auxiliary units along with the proposed controllers
∗
𝑃𝑐ℎ𝑎𝑟𝑔𝑒 _𝑚𝑎𝑥 subsystem has been developed and built in Matlab/Simulink and Fuzzy
Δω
∗
𝑆𝑂𝐶𝑚𝑖𝑛
- Logic tool boxes using RT-LAB (real-time simulator). The
𝑆𝑂𝐶 - 1 ∆𝑆𝑂𝐶2 purpose of this simulation is to assess the performance of the
+
∗
𝑆𝑂𝐶𝑚𝑖𝑛 ∗
+10% − 𝑆𝑂𝐶𝑚𝑖𝑛 [0-1] Δω- FLC in keeping the battery power and SOC within their limits.
∆𝜔𝑚𝑎𝑥 −
𝑃𝑑𝑖𝑠𝑐 ℎ𝑎𝑟𝑔𝑒 - 1 ∆𝑃𝑑𝑖𝑠𝑐 ℎ𝑎𝑟𝑔𝑒 Each unit in the simplified model is represented only by its
+
∗
𝑃𝑑𝑖𝑠𝑐 ℎ𝑎𝑟𝑔𝑒 _𝑚𝑎𝑥 droop controller as the power steady state values are the
∗
FLC bottom
𝑃𝑑𝑖𝑠𝑐 ℎ𝑎𝑟𝑔𝑒 _𝑚𝑎𝑥 subsystem concern. The PV unit will produce maximum possible power
Fig. 4. Proposed fuzzy logic controller. according to its MPPT as long as the bus frequency 𝜔 equals
or less than the nominal frequency 𝜔𝑜 . However, if the bus
1
L M H frequency is increased above the nominal frequency, then the
power is curtailed. Therefore, the PV power is given by (12).
0.5
The auxiliary unit will only produce power if the bus
0 frequency dropped below the nominal frequency. The power
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 ∆𝑆𝑂𝐶1
(a) produced by the auxiliary unit (𝑃𝑎𝑢𝑥 ) based on (6) is given by
1
L M H (13).
0.5 ∆𝜔
𝑃𝑃𝑉 = 𝑃𝑃𝑉_𝑀𝑃𝑃𝑇 (1 − ) , 0 ≤ ∆𝜔 ≤ ∆𝜔𝑚𝑎𝑥+ (12)
∆𝜔𝑚𝑎𝑥+
0
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 ∆𝑃𝑐ℎ𝑎𝑟𝑔𝑒
(b) ∆𝜔
𝑃𝑎𝑢𝑥 = , ∆𝜔𝑚𝑎𝑥− ≤ ∆𝜔 < 0 (13)
1
L M H 𝑚𝑎𝑢𝑥
0.5
where 𝑃𝑃𝑉_𝑀𝑃𝑃𝑇 is the maximum power tracking point of the
0 PV power. ∆𝜔, ∆𝜔𝑚𝑎𝑥+ and ∆𝜔𝑚𝑎𝑥− are the bus frequency
0 0.2 0.4 0.6 0.8 1 ∆𝜔+
(c) deviation/variation, its maximum positive and maximum
Fig. 5. Membership functions of top FLC: (a) Input ∆𝑆𝑂𝐶1 (b) Input ∆𝑃𝑐ℎ𝑎𝑟𝑔𝑒 negative deviation values, respectively.
(c) Output ∆𝜔+.
SOC calculation has been carried out as in [7] based on
1
L M H coulomb counting principle. The simplified simulation model
is as shown in Fig. 7. Solar radiation is recorded at the
0.5
Environment and Sustainability Institute (ESI) roof in Penryn
0
Campus at Penryn, UK. Fig. 8 shows 12 hours duration of
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 ∆𝑆𝑂𝐶2 actual solar radiation recorded on 25 th October 2015, which is
(a)
1
L M H used for real-time simulation. However, the solar radiation
profile is multiplied by a factor of 4 to have higher values for
0.5
simulation assuming larger PV area. Many simulation cases
0 have been conducted and sample results are shown as follows.
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 ∆𝑃𝑑𝑖𝑠 𝑐ℎ𝑎𝑟𝑔𝑒
(b) The system parameters used in the simulation are shown in
1
L M H Table III.
The first scenario represents a battery having high SOC
0.5
with initial value approaching the maximum limit of 95%. Fig.
0 9(a) shows the power output of the PV, battery and auxiliary
0 0.6
0.2 0.8 1 ∆𝜔− 0.4
(c) units along with the load power. The expectation is that the
Fig. 6. Membership functions of bottom FLC: (a) Input ∆𝑆𝑂𝐶2 (b) Input PV power should be used to supply the load and any excess
∆𝑃𝑑𝑖𝑠𝑐ℎ𝑎𝑟𝑔𝑒 (c) Output ∆𝜔−. power will be curtailed. Initially, there is no power generated
by the PV since the solar radiation is almost zero during the
VI. REAL-TIME SIMULATION RESULTS first 30min. The battery is completely supplying the load
A real-time simulator can emulate the actual performance (starting from 200W) and the auxiliary unit is not supplying
of a system or controller. This does avoid the need for any power as the battery SOC is high. After the PV starts
building the whole actual system at full capacity [27], [28]. generating more power, the contribution from the battery is
The robustness of the system can be assessed by whether the reduced. At t=1h, the PV generation is almost following the
controller can meet the design requirement with the existence load’s profile and the extra power is curtailed. Most of the
of diverse uncertainty in the generation and the load powers. time, the used PV is a little bit higher than the load as shown
1949-3029 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSTE.2018.2825655, IEEE
Transactions on Sustainable Energy
6
in Fig. 9(a) and the battery is not really used much as per the 600
FLC command since the priority is given for full utilization of 500
07:00:00
07:45:04
08:30:09
09:15:14
10:00:19
10:45:24
11:30:29
12:15:34
13:00:39
13:45:44
14:30:49
15:15:54
16:00:59
16:46:04
17:31:09
18:16:14
remains almost constant and it is prevented from exceeding its
-100
maximum limit. Fig. 9(c) shows the frequency curve where the
frequency is maintained within its limits as well irrespective of Time (h)
the changes in the load or the PV generation. Fig. 8. Solar radiation.
The second scenario describes the case when the battery
has a low SOC with initial value equals to the minimum limit TABLE III
SIMULATED SYSTEM PARAMETERS
value (40%). However, this time the load profile is multiplied
by a factor of 4 to have higher values for simulation with Parameter Symbol Value
similar trend and the rest remains the same. This helps in PV power rating 𝑃𝑝𝑣 2230W
having a wide range of load to check the performance of the Auxiliary power rating 𝑃𝑎𝑢𝑥 1000W
FLC. In this scenario, most of the time, the available PV Battery capacity Cbat, 100Ah
power is lower than the load profile which means there is Battery voltage Vbat, 120V
∗
Maximum state of charge 𝑆𝑂𝐶𝑚𝑎𝑥 95%
more need for support from the battery and auxiliary unit. Fig. Minimum state of charge plus 10% ∗
𝑆𝑂𝐶𝑚𝑖𝑛+10% 50%
10(a) shows the power output along with the load power. The ∗
Minimum state of charge 𝑆𝑂𝐶𝑚𝑖𝑛 40%
∗
FLC has the decision to run the auxiliary unit to provide Maximum charging power 𝑃𝑐ℎ𝑎𝑟𝑔𝑒_𝑚𝑎𝑥 1000W
∗
power to charge the battery and to supply the load if the PV Maximum discharging power 𝑃𝑑𝑖𝑠𝑐ℎ𝑎𝑟𝑔𝑒_𝑚𝑎𝑥 1000W
Nominal bus frequency 𝜔𝑜 314.16rad/s
power is low. After the first half an hour, the PV starts Active power droop coefficients mpv, maux 0.75e-4 rad/s/W
generating power. Since the SOC value is low, the battery is Reactive power droop coefficients n 0.75e-4 V/Var
straight away in charging mode using the auxiliary unit to
avoid possible decline of the SOC value to a value less than VII. EXPERIMENTAL RESULTS
the SOC minimum allowable limit (40%). The auxiliary unit is A single phase microgrid consisting of three units as
floating throughout the simulation period and providing the illustrated in Fig. 11 has been built in the laboratory. A bank
required power as per the FLC command. It is obvious that the of lead-acid batteries and a PV simulator are used. An AC
maximum charging/discharging power of the battery is well voltage source is used to represent the micro gas turbine
preserved within the maximum allowable limit (1000W) alternator. A bi-directional DC/DC converter is used to
throughout the full period of the simulation. Fig. 10(b) shows interface the battery and a uni-directional boost converter with
the SOC curve which reflects good performance towards the MPPT controller used to interface the PV simulator. The
increasing the SOC regardless of the generation and demand AC source representing the micro gas turbine is interfaced by
variations. The battery is mostly in charging mode. Fig. 10(c) an AC/DC rectifier. One DC/AC inverter is used for each
shows that frequency is maintained within its limits as well. generation units. The control algorithms have been realized by
Due to the limitations of the practical implementation, the an OPAL-RT real time simulator. A picture of the practical
real-time simulation has been used to validate the performance setup is shown in Fig. 12. The parameters of the system and
of high power rating systems and for long time periods. The controllers are shown in Table IV. Fig. 13 shows the case
next section describes practical results of short periods with when a fixed PV power is available over the time of the
low power rating systems but covering very different experiment. The initial SOC value is 40%. Fig. 13(a) shows
scenarios. the experimental output power responses of the PV, battery
and auxiliary units while load power is shown in Fig. 13(b).
1 𝑃𝑃𝑉_𝑀𝑃𝑃𝑇
∞ The PV generation is slightly higher than the load and the
1 +
-
X
battery needs to be charged. Therefore, the auxiliary unit is
0 ∆𝜔𝑚𝑎𝑥 +
𝑆𝑂𝐶
used to charge the battery at its maximum charging power of
∆𝜔 𝑃𝑃𝑉
FLC 70W since the SOC is low. Once the SOC becomes around
0
+ 47.58% at about 165s in Fig. 13(c), the auxiliary unit is almost
−1 𝑃𝑎𝑢𝑥 + 𝑃𝑏𝑎𝑡 𝑆𝑂𝐶
SOC
𝑃𝑏𝑎𝑡 𝑚𝑎𝑢𝑥 Calculation stopped as per the FLC command since the PV can supply the
-∞
- whole load and the SOC level is not critical. This saves the
𝑃𝑙𝑜𝑎𝑑
cost of running the auxiliary unit while still satisfying the
system needs. A battery charging current multiplier of 100k to
Fig. 7 Simplified simulation model. 500k is used to speed up the increase in the SOC in order to
decrease the time required for the experiment, but this does
1949-3029 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSTE.2018.2825655, IEEE
Transactions on Sustainable Energy
7
not affect the results’ dynamics in terms of the behavior or the 2500
SOC (%)
distortions/harmonics. Therefore, the high frequency 94.5
noise which comes from the measurements of the bus 93.5 (b)
Frequency (Hz)
50.2
Fig. 14 shows a discharging scenario for the battery with an Fig. 9. Output response for 94.9% SOC case: (a) power (b) frequency
initial SOC value of 51%. Fig. 14(a) shows the experimental (c) SOC.
output power responses of the PV, battery and auxiliary units
3500
along with the load power in Fig. 14(b). The FLC is initially 3000 Used PV
Load
not activated and no load is connected to the system. The PV 2500
Battery
Active Power (W)
2000 Auxiliary
generation is around 30W which is absorbed completely to 1500 Available PV
charge the battery. The load is then applied and the battery 1000
500
starts supplying the power demand shortage as the PV power 0
(a)
is not enough. After t=50s, the FLC is activated and the -500
-1000
auxiliary unit starts providing power according to the drop in 0 2 4 6 8 10 12
41
bus frequency shown in Fig. 14(d). At around t=100s when the 40.8
Time (h)
the battery stops discharging while the auxiliary unit provides 39.4 (b)
39.2
150W which is the difference between the PV and load 39
0 2 4 6 8 10 12
50.5
powers. This way, the minimum SOC limit is preserved. At 50.4
Time (h)
50.1
around 30W only as it is enough for the PV power to charge 50
49.9
the battery at its maximum limit. At t= 440s, PV power is 49.8
and the FLC stops the curtailment to utilize more PV power Fig. 10. Output responses for 40% SOC case and high load: (a) power
for the new load without running the auxiliary unit. (b) frequency (c) SOC.
1949-3029 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSTE.2018.2825655, IEEE
Transactions on Sustainable Energy
8
TABLE IV
EXPERIMENTAL SETUP PARAMETERS
Load
AC Bus
DC / DC DC / AC Inverters parameters PV current controller
Converter Inverter Inverter-side P-controller
L DC 𝐿1 4mH 𝑘𝑝_𝑝𝑣𝑐 0.05
L1 L2 filter inductor gain
C dc Filter I-controller
C 𝐶 25μF 𝑘𝑖_𝑝𝑣𝑐 1
capacitor gain
PV
v pv i pv il vc io Grid-side
𝐿2 2mH Inverter voltage controller
filter inductor
kc sLv
PWM
Nominal Voltage
- - - - 𝑉𝑜 120V 𝑘𝑣 0.01
*
PI pvv PI pvc PWM kv output voltage controller gain
Vpv V
*
1949-3029 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSTE.2018.2825655, IEEE
Transactions on Sustainable Energy
9
Fig. 14. Experimental output responses for 51% SOC case: (a) power (b) load
(c) SOC (d) frequency.
1949-3029 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSTE.2018.2825655, IEEE
Transactions on Sustainable Energy
10
150
Available PV PV
200 PV increased
100
Load dropped
Active Power (W)
P controller on 0
0 Load increased
Battery
-100
Battery P controller on Load dropped
-50
SOC=41.9% SOC=80.2% (a) Load=0 & P controller off (a)
SOC=41.05% -200
-100
0 50 100 150 200 250 300 350 0 25 50 75 100 125 150 175 200
120 Time (s) 400 Time (s)
350
100
300
80
250
Load (W)
Load (W)
60 200
150
40
100
20 (b) (b)
50
0 0
0 50 100 150 200 250 300 350 0 25 50 75 100 125 150 175 200
120 Time (s) 54 Time (s)
100 52
SOCmax 50
80
X: 314.8
SOC (%)
48
SOC (%)
X: 130 Y: 80.21
60 X: 41.9 Y: 50.02
46
Y: 42.33
40 44
X: 31.36 SOCmin
Y: 41.05 42
20 (c) (c)
40
0
0 50 100 150 200 250 300 350 0 25 50 75 100 125 150 175 200
Time (s) 315 Time (s)
314.8
314.8
314.6
314.6
Frequency (rad/s)
Frequency (rad/s)
314.4
314.4
314.2
314.2
314
314
313.8
(d) 313.8
313.6 (d)
0 50 100 150 200 250 300 350 313.6
0 25 50 75 100 125 150 175 200
Time (s) Time (s)
Fig. 15 Experimental output responses for 40% to 95% SOC with Fig. 16 Experimental output responses for 52% SOC with proportional
proportional controller case: (a) power (b) load (c) SOC (d) Frequency controller case: (a) power, (b) load, (c) SOC, (d) Frequency
The proposed controller in the paper assumes an islanded By varying the AC bus frequency, within the standards
microgrid, which has batteries as energy source and one of the allowance, and making use of local droop controllers, the
purposes of the FLC is to prevent the battery SOC and controller is implemented without any communication links
charging/discharging power from exceeding their limits between the microgrid units. The RES unit can properly react
regardless of the variation in the load and intermittent power to curtail its power when needed and the auxiliary unit is left
generated by the RES. If there is no battery in the microgrid, to float on the AC bus so it reacts instantaneously to frequency
there is a need for changing the design of the FLC and amend variation to supply power. The results showed that the
its inputs/outputs and the rules accordingly. In case the battery proposed FLC is capable to satisfy the system requirements
is not available, there will be more usage of the micro gas within the defined constrains. It maintains the SOC and
turbine to satisfy the load demand. Also, in case of excess charging/discharging power of the battery within their limits
power from the PV, the micro gas turbine is still need to run to irrespective of the change in RES/load. The performance has
stabilize the AC bus and PV power curtailment will be crucial. been validated by real time simulation and experimentally.
The performance of the FLC is superior to the performance
VIII. CONCLUSION when compared to a traditional droop control method (i.e.
A fuzzy logic controller has been proposed for power proportional controller in this case) in achieving the required
management of an islanded AC microgrid. The proposed goals. The proportional controller was not always able to
controller combines the FLC and bus-signalling techniques to maintain the SOC and charging/discharging power within their
control the power flow between different energy sources. design limits.
1949-3029 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSTE.2018.2825655, IEEE
Transactions on Sustainable Energy
11
IX. REFERENCES [21] R. AlBadwawi, M. Abusara, and T. Mallick, “A review of hybrid solar
PV and wind energy system,” Smart Sci., vol. 3, no. 3, pp. 127–138,
[1] J. M. Guerrero, J. C. Vasquez, J. Matas, L. G. De Vicuña, and M. Apr. 2015.
Castilla, “Hierarchical control of droop-controlled AC and DC [22] W. R. Issa, M. A. Abusara, and S. M. Sharkh, “Control of transient
microgrids — A general approach toward standardization,” IEEE Trans. power during unintentional islanding of microgrids,” IEEE Trans.
Ind. Electron., vol. 58, no. 1, pp. 158–172, Jan. 2011. Power Electron., vol. 30, no. 8, pp. 4573–4584, Aug. 2015.
[2] L. Meng, E. R. Sanseverino, A. Luna, T. Dragicevic, J. C. Vasquez, and [23] W. Issa, S. Sharkh, T. Mallick, and M. Abusara, “Improved reactive
J. M. Guerrero, “Microgrid supervisory controllers and energy power sharing for parallel-operated inverters in islanded microgrids,” J.
management systems: A literature review,” Renew. Sustain. Energy Power Electron., vol. 16, no. 3, pp. 1152–1162, May 2016.
Rev., vol. 60, pp. 1263–1273, Jul. 2016. [24] X. Lu, J. M. Guerrero, K. Sun, J. C. Vasquez, R. Teodorescu, and L.
[3] A. Chauhan and R. P. Saini, “A review on integrated renewable energy Huang, “Hierarchical control of parallel AC-DC converter interfaces for
system based power generation for stand-alone applications: hybrid microgrids,” IEEE Trans. Smart Grid, pp. 683–692, Jul. 2013.
Configurations, storage options, sizing methodologies and control,” [25] R. Al Badwawi, W. Issa, T. Mallick, and M. Abusara, “Power
Renew. Sustain. Energy Rev., vol. 38, pp. 99–120, Jun. 2014. management of AC islanded microgrids using fuzzy logic,” in IET
[4] R. Al Badwawi, W. Issa, T. Mallick, and M. Abusara, “DC microgrid International Conference on Power Electronics, Machines and Drives
power coordination based on fuzzy logic control,” in 18th European (PEMD), Glasgow, UK, 2016, pp. 1-6.
Conference on Power Electronics and Applications, Karlsruhe, [26] R. AlBadwawi, “Supervisory control and power management of an AC
Germany, 2016, pp. 1–10. microgrid,” Ph.D. dissertation, Dept. Renewable Energy, Univ. of
[5] B. Belvedere, M. Bianchi, A. Borghetti, C. A. Nucci, M. Paolone, and Exeter, Penryn, UK, 2017.
A. Peretto, “A Microcontroller-Based Power Management System for [27] P. Venne, J.-N. Paquin, and J. Belanger, “The what, where and why of
Standalone Microgrids With Hybrid Power Supply,” IEEE Trans. real-time simulation,” Power Energy Soc., vol. 1, pp. 37–49, 2010.
Sustain. Energy, vol. 3, no. 3, pp. 422–431, Jul. 2012. [28] S. K. Khadem, M. Basu, and M. F. Conlon, “Intelligent islanding and
[6] C. Wang and M. H. Nehrir, “Power management of a stand-alone wind / seamless reconnection technique for microgrid with UPQC,” IEEE J.
photovoltaic / fuel cell energy system,” IEEE Trans. Energy Convers., Emerg. Sel. Top. Power Electron., vol. 3, no. 2, pp. 483–492, Jun. 2015.
vol. 23, no. 3, pp. 957–967, Sep. 2008.
[7] H. Mahmood and D. Michaelson, “A power management strategy for
PV / battery hybrid systems in islanded microgrids,” IEEE J. Emerg. Sel. Rashid Al Badwawi received his BEng and MSc
Top. Power Electron., vol. 2, no. 4, pp. 1–14, Dec. 2014. degrees in Electrical and Electronics Engineering
[8] W. Issa, S. Sharkh, T. Mallick, and M. Abusara, “Improved reactive from Sultan Qaboos University, Oman, in 1995 and
power sharing for parallel-operated inverters in islanded microgrids,” J. 2001, respectively; and his PhD in Renewable
Power Electron., vol. 16, no. 3, pp. 1152–1162, May 2016. Energy from University of Exeter, UK in 2017. He
[9] H. Mahmood, “Power management strategies for islanded microgrids,” has broad experience in managing large multi-
Ph.D. dissertation, Dep. Elect. Comp. Eng., Univ. of Western Ontario, discipline Oil/Gas projects (Oct. 1995 - Oct. 2005)
London, Ontario, Canada, 2015. and electrical power projects (Oct 2005 – now). He
[10] W. Issa, A. El Khateb, N. Anani, and M. Abusara, “Smooth mode is currently working as Projects Panning Advisor at
transfer in AC microgrids during unintentional islanding,” Energy Oman Electricity Transmission Company. His
Procedia, vol. 134, pp. 12–20, Oct. 2017. research interests include renewable energy, energy management, microgrids,
[11] W. R. Issa, A. H. El Khateb, M. A. Abusara, and T. K. Mallick, “Control power electronics and fuzzy logic controller.
strategy for uninterrupted microgrid mode transfer during unintentional
islanding scenarios,” IEEE Trans. Ind. Electron., vol. 65, no. 6, pp. Walid R. Issa received his B.Sc. and M.Sc. degrees
4831- 4839, Nov. 2017. in electrical engineering from Islamic University of
[12] M. S. Ismail, M. Moghavvemi, T. M. I. Mahlia, K. M. Muttaqi, and S. Gaza (IUG), Palestine, in 2007 and 2011,
Moghavvemi, “Effective utilization of excess energy in standalone respectively; and his PhD in Renewable Energy from
hybrid renewable energy systems for improving comfort ability and University of Exeter, UK in 2015. He worked as a
reducing cost of energy: A review and analysis,” Renew. Sustain. Energy teaching assistant at IUG, 2007-2010. He was a
Rev., vol. 42, pp. 726–734, 2015. lecturer at University College of Applied Science,
[13] J. de Matos, F. e Silva, and L. Ribeiro, “Power control in AC isolated Palestine, 2009-2011. He is currently a lecturer in
microgrids with renewable energy sources and energy storage systems,” Sheffield Hallam University, UK. His main research
IEEE Trans. Ind. Electron., vol. 62, no. 6, pp. 3490–3498, Jun. 2015. interests include power electronics, digital control, DC/AC and DC/DC
[14] D. Wu, F. Tang, T. Dragicevic, J. C. Vasquez, and J. M. Guerrero, converters and microgrids.
“Autonomous active power control for islanded AC microgrids with
Tapas K. Mallick received the Ph.D. degree from
photovoltaic generation and energy storage system,” IEEE Trans.
Ulster University, Coleraine, U.K. in 2003. From
Energy Convers., vol. 29, no. 4, pp. 882–892, Dec. 2014.
2007 to 2012, he was a Lecturer with Heriot-Watt
[15] D. Wu, J. M. Guerrero, J. C. Vasquez, T. Dragicevic, and F. Tang,
University, Edinburgh, U.K. He is currently a
“Coordinated power control strategy based on primary-frequency-
Professor of renewable energy and Chair in Clean
signaling for islanded microgrids,” 2013 IEEE Energy Convers. Congr.
Technologies with the Environment and
Expo. ECCE 2013, pp. 1033–1038, 2013.
Sustainability Institute of the University of Exeter,
[16] A. Urtasun, E. L. Barrios, P. Sanchis, and L. Marroyo, “Frequency-
Penryn, U.K. His research interests include
based energy-management strategy for stand-alone systems with
renewable energies, concentrating photovoltaics,
distributed battery storage,” IEEE Trans. Power Electron., vol. 30, no. 9,
building integrated photovoltaics, integration of renewables, heat transfer,
pp. 4794–4808, Sep. 2015.
optics, and electrical modeling
[17] F. S. Tidjani, A. Hamadi, A. Chandra, P. Pillay, and A. Ndtoungou,
“Optimization of standalone microgrid considering active damping Mohammad Abusara received his BEng degree
technique and smart power management using fuzzy logic supervisor,” from Birzeit University, Palestine, in 2000 and his
IEEE Trans. Smart Grid, vol. 8, no. 1, pp. 475–484, Jan. 2017. PhD degree from the University of Southampton,
[18] A. Mahesh and K. S. Sandhu, “Hybrid wind/photovoltaic energy system UK, in 2004, both in Electrical Engineering. He is
developments: Critical review and findings,” Renew. Sustain. Energy currently a Senior Lecturer in Renewable Energy at
Rev., vol. 52, pp. 1135–1147, Aug. 2015. the University of Exeter, UK. He has over ten years
[19] D. Arcos-Aviles, J. Pascual, L. Marroyo, P. Sanchis, and F. Guinjoan, of industrial experience with Bowman Power Group,
“Fuzzy logic-based energy management system design for residential Southampton, UK, in the field of research and
grid-connected microgrids,” IEEE Trans. Smart Grid, vol. 9, no. 2, pp. development of digital control of power electronics.
530–543, Mar. 2018. During his years in industry, he designed and
[20] T. T. Teo, T. Logenthiran, W. L. Woo, and K. Abidi, “Fuzzy logic prototyped a number of commercial products that include grid and parallel
control of energy storage system in microgrid operation,” in 2016 IEEE connected inverters, microgrid, DC/DC converters for hybrid vehicles, and
Innovative Smart Grid Technologies - Asia, 2016, pp. 65–70. sensorless drives for high speed permanent magnet machines.
1949-3029 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.