Construction Inspection Services LLC

Property Inspection Report


Cover Page

1307 Colony Rd, Conway, SC 29526


Inspection prepared for: Adam Wood
Date of Inspection: 5/16/2017 Time: 5:00
Age of Home: 1956 Size: 1600
Weather: Clear

Inspector: Jarrette Jacobs


License #RBI-48639
4320 Long Ave , Conway, SC 29526
Phone: 843-222-3536
Email: constructioninspectionservices@sccoast.net
Construction Inspection Services LLC 1307 Colony Rd, Conway, SC

Report Summary
Report Summary
The summary below consists of potentially significant findings. These findings can be a safety
hazard, a deficiency requiring a major expenses to correct or items I would like to draw extra
attention to. The summary is not a complete listing of all the findings in the report, and reflects the
opinion of the inspector. Please review all of the pages of the report as the summary alone does not
explain all the issues. All repairs must be done by a licensed &bonded trade or profession. I
recommend obtaining a copy of all receipts, warranties and permits for the work done.
Bathroom
Page 8 Item: 6 Exhaust Fan • The fan terminates improperly in the attic. This can create
excessive moisture. Recommend directing the vent towards
the exterior to allow for proper ventilation.
Kitchen
Page 10 Item: 6 Cook top condition • SAFETY CONCERN: Free standing range missing anti-tip
bracket/device. Should be installed.
Page 11 Item: 13 Electrical • Unsafe wiring under kitchen sink
Laundry
Page 12 Item: 5 Plumbing • Laundry plumbing recessed into the wall and valves are not
easily accessible
Heat/AC
Page 14 Item: 1 AC Compress • The air conditioner is near the end of its life expectancy and
Condition will need to be replaced soon.
Page 14 Item: 2 Air Supply • Duckwork is dirty
Garage
Page 17 Item: 1 Roof Condition • Metal carport is unsafe
Roof
Page 19 Item: 1 Roof Condition • Appears to be some damage to the metal roof. Flashing not
installed properly.
Page 19 Item: 2 Flashing • Roofing contractor used silicone to flash roof transitions.
This is not the proper method of flashing for roofing materials
Page 21 Item: 3 Chimney • Flashing at base of chimney appears to need some
maintenance to ensure a continued waterproof seal.
Attic
Page 21 Item: 5 Electrical • Electrical Box Covers missing or damaged, which is a
potential shock or electrocution hazard.
Exterior Areas
Page 23 Item: 3 Siding Condition • Vinyl siding damage. Recommend repair or replacement of
damaged sections to keep moisture and insects from harming
structure.
Foundation
Page 25 Item: 3 Ventilation • Inadequate venting observed in crawlspace, suggest
installing additional vents for proper moisture control.
Grounds
Page 26 Item: 2 Grading • The exterior grading is improperly sloped towards the
foundation at the right rear corner. Water can intrude into the
interior. Recommend creating the proper slope away from the
foundation to allow for proper drainage.

Page 1 of 31
Construction Inspection Services LLC 1307 Colony Rd, Conway, SC

Page 26 Item: 7 Grounds Electrical • Wire ends are outside of a Junction Box, which is a potential
shock or electrocution hazard.
Page 27 Item: 8 GFCI • Outdoor receptacles are not GFCI protected, need to be
updated.
Basement/Crawlspace
Page 29 Item: 6 Framing • Deterioration/ damage of one or more floor joist noted.
Recommend review and repair by a Qualified Contractor to
evaluate load bearing members.
• Floor joists not properly supported at load bearing points.
Installation of joist hanger's or other means of support are
needed. Recommend review and repair by a qualified
contractor.
• Visible evidence of Wood Destroying Organisms observed.
Recommend obtaining a termite inspection to confirm that no
active infestation exists.
• Damage from what appears to be caused by Wood
Destroying Organisms is noted, Recommend review of
support structure by a Qualified Contractor.
• Support post/blocks appear to lack proper footing to support
load, Review by a qualified foundation contractor is
recommended.
Page 30 Item: 9 Piers • Unprofessional upgrades/repairs have been performed at
support posts/beam location. Recommend review and proper
repairs by a qualified contractor.
• Support post/blocks appear to lack proper footing to support
load, Review by a qualified foundation contractor is
recommended.
Page 31 Item: 10 Basement/Crawlsp • One or more areas of the heat ductwork is
ace Ductwork damaged/deteriorated/not attached. Recommend review and
repairs by a qualified HVAC contractor to enhance homes
heating efficiency.

Page 2 of 31
Construction Inspection Services LLC 1307 Colony Rd, Conway, SC

We appreciate the opportunity to conduct this inspection for you! Please carefully read your entire
Inspection Report. Call us after you have reviewed your report, so we can go over any questions
you may have. Remember, when the inspection is completed and the report is delivered, we are still
available to you for any questions you may have, throughout the entire closing process.
Properties being inspected do not "Pass" or "Fail.” - The following report is based on an inspection
of the visible portion of the structure; inspection may be limited by vegetation and possessions.
Depending upon the age of the property, some items like GFI outlets may not be installed; this
report will focus on safety and function, not current code. This report identifies specific non-
code, non-cosmetic concerns that the inspector feels may need further investigation or repair.
For your safety and liability purposes, we recommend that licensed contractors evaluate and repair
any critical concerns and defects. Note that this report is a snapshot in time. We recommend
that you or your representative carry out a final walk-through inspection immediately before
closing to check the condition of the property, using this report as a guide.

Page 3 of 31
Construction Inspection Services LLC 1307 Colony Rd, Conway, SC

Inspection Details
1. Attendance
In Attendance: Client present
2. Home Type
Home Type: Single Family Home
3. Occupancy
Occupancy: Occupied - Furnished

Page 4 of 31
Construction Inspection Services LLC 1307 Colony Rd, Conway, SC

Interior Areas
The Interior section covers areas of the house that are not considered part of the Bathrooms,
Bedrooms, Kitchen or areas covered elsewhere in the report. Interior areas usually consist of
hallways, foyer, and other open areas. Within these areas the inspector is performing a visual
inspection and will report visible damage, wear and tear, and moisture problems if seen. Personal
items in the structure may prevent the inspector from viewing all areas on the interior.

The inspector does not usually test for mold or other hazardous materials. A qualified expert should
be consulted if you would like further testing.
1. Ceiling Fans
Good Fair Poor N/A None

2. Door Bell
Good Fair Poor N/A None

3. Doors
Good Fair Poor N/A None

4. Electrical
Good Fair Poor N/A None

5. Smoke Detectors
Good Fair Poor N/A None

6. Ceiling Condition
Good Fair Poor N/A None

7. Wall Condition
Good Fair Poor N/A None

8. Fireplace
Good Fair Poor N/A None

9. Window Condition
Good Fair Poor N/A None

Page 5 of 31
Construction Inspection Services LLC 1307 Colony Rd, Conway, SC

Bedrooms
The main area of inspection in the bedrooms is the structural system. This means that all walls,
ceilings and floors will be inspected. Doors and windows will also be investigated for damage and
normal operation. Personal items in the bedroom may prevent all areas to be inspected as the
inspector will not move personal items.
1. Ceiling Fans
Good Fair Poor N/A None

2. Closets
Good Fair Poor N/A None

3. Doors
Good Fair Poor N/A None

4. Electrical
Good Fair Poor N/A None

open grounds
5. Floor Condition
Good Fair Poor N/A None

6. Smoke Detectors
Good Fair Poor N/A None

7. Wall Condition
Good Fair Poor N/A None

Page 6 of 31
Construction Inspection Services LLC 1307 Colony Rd, Conway, SC

8. Window Condition
Good Fair Poor N/A None

9. Ceiling Condition
Good Fair Poor N/A None

Page 7 of 31
Construction Inspection Services LLC 1307 Colony Rd, Conway, SC

Bathroom
Bathrooms can consist of many features from jacuzzi tubs and showers to toilets and bidets.
Because of all the plumbing involved it is an important area of the house to look over. Moisture in the
air and leaks can cause mildew, wallpaper and paint to peel, and other problems. The home
inspector will identify as many issues as possible but some problems may be undetectable due to
problems within the walls or under the flooring..
1. Ceiling Condition
Good Fair Poor N/A None

2. Counters
Good Fair Poor N/A None

3. Doors
Good Fair Poor N/A None

4. Electrical
Good Fair Poor N/A None

5. GFCI
Good Fair Poor N/A None

6. Exhaust Fan
Good Fair Poor N/A None
Observations:
X • The fan terminates improperly in the attic. This can create excessive
moisture. Recommend directing the vent towards the exterior to allow for
proper ventilation.

Page 8 of 31
Construction Inspection Services LLC 1307 Colony Rd, Conway, SC

7. Floor Condition
Good Fair Poor N/A None

8. Mirrors
Good Fair Poor N/A None

9. Plumbing
Good Fair Poor N/A None

10. Showers
Good Fair Poor N/A None

11. Shower Walls


Good Fair Poor N/A None

12. Bath Tubs


Good Fair Poor N/A None

13. Enclosure
Good Fair Poor N/A None

14. Sinks
Good Fair Poor N/A None

15. Toilets
Good Fair Poor N/A None

Page 9 of 31
Construction Inspection Services LLC 1307 Colony Rd, Conway, SC

Kitchen
The kitchen is used for food preparation and often for entertainment. Kitchens typically include a
stove, dishwasher, sink and other appliances.
1. Cabinets
Good Fair Poor N/A None

2. Counters
Good Fair Poor N/A None

3. Dishwasher
Good Fair Poor N/A None

4. Doors
Good Fair Poor N/A None

5. Microwave
Good Fair Poor N/A None

6. Cook top condition


Good Fair Poor N/A None
Observations:
X • SAFETY CONCERN: Free standing range missing anti-tip bracket/device.
Should be installed.

7. Oven & Range


Good Fair Poor N/A None

Page 10 of 31
Construction Inspection Services LLC 1307 Colony Rd, Conway, SC

8. Sinks
Good Fair Poor N/A None

9. Vent Condition
Good Fair Poor N/A None

10. Floor Condition


Good Fair Poor N/A None

11. Plumbing
Good Fair Poor N/A None

12. Ceiling Condition


Good Fair Poor N/A None

13. Electrical
Good Fair Poor N/A None
Observations:
X • Unsafe wiring under kitchen sink

unsafe wiring
14. GFCI
Good Fair Poor N/A None

15. Wall Condition


Good Fair Poor N/A None

Page 11 of 31
Construction Inspection Services LLC 1307 Colony Rd, Conway, SC

Laundry
1. Dryer Vent
Good Fair Poor N/A None

duct tape holding dryer vent


2. Electrical
Good Fair Poor N/A None

3. GFCI
Good Fair Poor N/A None

4. Floor Condition
Good Fair Poor N/A None

5. Plumbing
Good Fair Poor N/A None
Observations:
X • Laundry plumbing recessed into the wall and valves are not easily
accessible

Page 12 of 31
Construction Inspection Services LLC 1307 Colony Rd, Conway, SC

6. Wall Condition
Good Fair Poor N/A None

7. Ceiling Condition
Good Fair Poor N/A None

8. Doors
Good Fair Poor N/A None

Page 13 of 31
Construction Inspection Services LLC 1307 Colony Rd, Conway, SC

Heat/AC
The heating, ventilation, and air conditioning and cooling system (often referred to as HVAC) is the
climate control system for the structure. The goal of these systems is to keep the occupants at a
comfortable level while maintaining indoor air quality, ventilation while keeping maintenance costs at
a minimum. The HVAC system is usually powered by electricity and natural gas, but can also be
powered by other sources such as butane, oil, propane, solar panels, or wood.

The inspector will usually test the heating and air conditioner using the thermostat or other controls.
For a more thorough investigation of the system please contact a licensed HVAC service person.
1. AC Compress Condition
Good Fair Poor N/A None
Observations:
X • The air conditioner is near the end of its life expectancy and will need to be
replaced soon.

a/c unit needs replacing


2. Air Supply
Good Fair Poor N/A None
Observations:
X • Duckwork is dirty

air return is dirty

Page 14 of 31
Construction Inspection Services LLC 1307 Colony Rd, Conway, SC

3. Registers
Good Fair Poor N/A None

4. Filters
Good Fair Poor N/A None

5. Thermostats
Good Fair Poor N/A None

Page 15 of 31
Construction Inspection Services LLC 1307 Colony Rd, Conway, SC

Water Heater
1. Water Heater Condition
Good Fair Poor N/A None

2. TPRV
Good Fair Poor N/A None

3. Number Of Gallons
Good Fair Poor N/A None
Observations:
X • 50 gallons

4. Plumbing
Good Fair Poor N/A None

5. Overflow Condition
Good Fair Poor N/A None

Page 16 of 31
Construction Inspection Services LLC 1307 Colony Rd, Conway, SC

Garage
1. Roof Condition
Good Fair Poor N/A None
Observations:
X • Metal carport is unsafe

Page 17 of 31
Construction Inspection Services LLC 1307 Colony Rd, Conway, SC

Electrical
1. Electrical Panel
Good Fair Poor N/A None

disconnect too low on deck, unsafe to service or work in panel box


2. Main Amp Breaker
Good Fair Poor N/A None
Observations:
X • 200 amp

3. Breakers in off position


Good Fair Poor N/A None
Observations:
X •0

4. Breakers
Good Fair Poor N/A None

Page 18 of 31
Construction Inspection Services LLC 1307 Colony Rd, Conway, SC

Roof
1. Roof Condition
Good Fair Poor N/A None
Observations:
X • Appears to be some damage to the metal roof. Flashing not installed
properly.

2. Flashing
Good Fair Poor N/A None
Observations:
X • Roofing contractor used silicone to flash roof transitions. This is not the
proper method of flashing for roofing materials

Page 19 of 31
Construction Inspection Services LLC 1307 Colony Rd, Conway, SC

silicone caulking

3. Chimney
Good Fair Poor N/A None
Observations:
X • Flashing at base of chimney appears to need some maintenance to ensure
a continued waterproof seal.
Page 20 of 31
Construction Inspection Services LLC 1307 Colony Rd, Conway, SC

Attic
1. Access
Good Fair Poor N/A None

2. Structure
Good Fair Poor N/A None

3. Ventilation
Good Fair Poor N/A None

4. Vent Screens
Good Fair Poor N/A None

5. Electrical
Good Fair Poor N/A None
Observations:
X • Electrical Box Covers missing or damaged, which is a potential shock or
electrocution hazard.

6. Insulation Condition
Good Fair Poor N/A None
Depth: Insulation averages about 4-6 inches in depth; more recommended.
X

Page 21 of 31
Construction Inspection Services LLC 1307 Colony Rd, Conway, SC

Page 22 of 31
Construction Inspection Services LLC 1307 Colony Rd, Conway, SC

Exterior Areas
1. Doors
Good Fair Poor N/A None

2. Window Condition
Good Fair Poor N/A None

3. Siding Condition
Good Fair Poor N/A None
Observations:
X • Vinyl siding damage. Recommend repair or replacement of damaged
sections to keep moisture and insects from harming structure.

Page 23 of 31
Construction Inspection Services LLC 1307 Colony Rd, Conway, SC

bowed siding

4. Eaves & Facia


Good Fair Poor N/A None

5. Exterior Paint
Good Fair Poor N/A None

Page 24 of 31
Construction Inspection Services LLC 1307 Colony Rd, Conway, SC

Foundation
1. Slab Foundation
Good Fair Poor N/A None

2. Foundation Perimeter
Good Fair Poor N/A None

3. Ventilation
Good Fair Poor N/A None
Observations:
X • Inadequate venting observed in crawlspace, suggest installing additional
vents for proper moisture control.
4. Vent Screens
Good Fair Poor N/A None

5. Access Panel
Good Fair Poor N/A None

Page 25 of 31
Construction Inspection Services LLC 1307 Colony Rd, Conway, SC

Grounds
1. Driveway and Walkway Condition
Good Fair Poor N/A None

2. Grading
Good Fair Poor N/A None
Observations:
X • The exterior grading is improperly sloped towards the foundation at the right
rear corner. Water can intrude into the interior. Recommend creating the
proper slope away from the foundation to allow for proper drainage.

3. Vegetation Observations
Good Fair Poor N/A None

4. Gate Condition
Good Fair Poor N/A None

5. Patio and Porch Deck


Good Fair Poor N/A None

6. Stairs & Handrail


Good Fair Poor N/A None

7. Grounds Electrical
Good Fair Poor N/A None
Observations:
X • Wire ends are outside of a Junction Box, which is a potential shock or
electrocution hazard.

Page 26 of 31
Construction Inspection Services LLC 1307 Colony Rd, Conway, SC

unsafe wiring, wrong size wire


8. GFCI
Good Fair Poor N/A None
Observations:
X • Outdoor receptacles are not GFCI protected, need to be updated.

no power
9. Water Pressure
Good Fair Poor N/A None

10. Pressure Regulator


Good Fair Poor N/A None

11. Exterior Faucet Condition


Good Fair Poor N/A None

Page 27 of 31
Construction Inspection Services LLC 1307 Colony Rd, Conway, SC

Basement/Crawlspace
1. Insulation
Good Fair Poor N/A None

missing insulation no insulation


2. Plumbing Materials
Good Fair Poor N/A None

3. Basement Electric
Good Fair Poor N/A None

4. GFCI
Good Fair Poor N/A None

5. Access
Good Fair Poor N/A None

6. Framing
Good Fair Poor N/A None
Observations:
X • Deterioration/ damage of one or more floor joist noted. Recommend review
and repair by a Qualified Contractor to evaluate load bearing members.
• Floor joists not properly supported at load bearing points. Installation of joist
hanger's or other means of support are needed. Recommend review and
repair by a qualified contractor.
• Visible evidence of Wood Destroying Organisms observed. Recommend
obtaining a termite inspection to confirm that no active infestation exists.
• Damage from what appears to be caused by Wood Destroying Organisms
is noted, Recommend review of support structure by a Qualified Contractor.
• Support post/blocks appear to lack proper footing to support load, Review
by a qualified foundation contractor is recommended.

Page 28 of 31
Construction Inspection Services LLC 1307 Colony Rd, Conway, SC

rotten beam horizontal 4x4 post supporting floor

floor shoring damaged and wet floor joist

leaning blocks termite damage

Page 29 of 31
Construction Inspection Services LLC 1307 Colony Rd, Conway, SC

7. Subfloor
Good Fair Poor N/A None

8. Columns
Good Fair Poor N/A None

9. Piers
Good Fair Poor N/A None
Observations:
X • Unprofessional upgrades/repairs have been performed at support
posts/beam location. Recommend review and proper repairs by a qualified
contractor.
• Support post/blocks appear to lack proper footing to support load, Review
by a qualified foundation contractor is recommended.

blocking installed wrong

Page 30 of 31
Construction Inspection Services LLC 1307 Colony Rd, Conway, SC

10. Basement/Crawlspace Ductwork


Good Fair Poor N/A None
Observations:
X • One or more areas of the heat ductwork is damaged/deteriorated/not
attached. Recommend review and repairs by a qualified HVAC contractor to
enhance homes heating efficiency.

duct work on ground and broken

Page 31 of 31