Vous êtes sur la page 1sur 52

for

Pleasant &
Healthy
Air-Distribution

www.dasco.com.kw

ISO 9001:2000

Product Bulletin 136-D Louvers


Pleasant .. Serene..
YOU & DASCO...

Since 1964

Partners for good health


www.dasco.com.kw
INTRODUCTION

Dasco manufacture a variety types of louvers designed for


intake, exhaust and control air movement applications.

www.dasco.com.kw
Their strong, clean lines and careful workmanship enhance
the appearance of the building, whether it is industrial,
commercial or domestic. While most of the louvers are
mainly manufactured in complete lines of extruded
aluminium blades, and to complement or accentuate
architectural feature, such as round, arched and angular
structures, Dasco can offer and modify special
louvers incorporating virtually any combination of round,
diagonal and rectilinearframe segments to be suitable for
different applications and architectural requirements.

Introduction
PRODUCT RANGE

GENERAL
It is well understood in HVAC engineering, that a proper air conditioning or ventilating system
can not operate efficiently without an efficient air movement component device. Hence, louver
have been always considered as one of the most important air terminal devices which utilize and
control the flow of air in and out of the buildings. Louver structure “frame and blades” can also
be modified and reinforced to withstand excessive loads and to play a role in effective weather
protection.
Plenty of louver blades have been re-developed and many others newly designed to permit and
help louversto be complied in many of the recent engineering applications.

Different types of Dasco louver blades

Fresh Air Louver Sand Louver

Product Range
Sand Louver Sand Trap Louver

www.dasco.com.kw
(Special heavy duty type)

Pressure Relief Louver Penthouse Louver


(Gravity Shutter)

Sightproof Louver Drainable Louver

Stormproof Louver Acoustic Louver

Product Range
FRESH AIR LOUVERS

GENERAL
Dasco fresh air louvers (DFL-11H) are
considered as an architectural air inlets and
outlets with a remarkable clean and aesthetically
pleasing appearance. They are widely and
successfully used for central airconditioning,
ventilation and industrial ventilation systems.
These louvers have a low resistance to air flow
and high free area, making them a preferred
choice for installations which require high air Fresh Air Louver (DFL - 11H)
flow.
DESCRIPTION
DFL-11H louvers have a 2 inch deep fixed horizontal vanes (blades) which are carefully designed
to get low pressure drop, maximum free area and to prevent wind and rain-water penetration.
They are available in1.25” flanged (flat or curved) frame which in turn is mechanically joined to
give the highest rigidity and strength. Louvers can be supplied as optional with galvanized bird or
aluminium insect screen, volume control damper and air filter of 1”, 2” or 4” thickness. The filters
are accessable from the side or backward of the louver depending upon type of installation and must
be specified by the customers. These louvers are available in standard given sizes however, they
can be supplied in other requested sizes and architectural shapes upon customers requirements.

MATERIAL AND FINISH


DFL-11H louvers are made of heavy gauge
extruded aluminium profiles. They are available
in white polyester powder coated finish or any
other RAL standard colour upon customer’s
request. Bird screens are made of galvanized
expanded metal sheets, however dampers are
made of extruded aluminium profiles.

Fresh Air Louver With Flat Frame


(DFL - 11HFF)

Fresh Air Louvers


PRODUCT CODE

Dasco Fresh Air Louvers DFL - 11H -W -H -C

Width in inch.

www.dasco.com.kw
Height in inch.

Accessories:
B :Bird screen
D :Volume Control Damper (VCD)
BD :Bird screen & VCD.
I :Insect Screen.
F1 :Aluminium Filter 1” thick.
F2 :Aluminium Filter 2” thick.
F4 :Aluminium Filter 4” thick.
Use the code of DFL-11HFF to refer to Dasco fresh air louver with flat frame.
Example:
DFL - 11H - 16 - 20 - BD:
Dasco fresh air intake louver size 16” x 20” with bird screen and volume control damper (VCD).

DFL - 11H - 40 - 20 - BDF2:


Dasco fresh air intake louver size 40”x20” with bird screen, volume control damper (VCD) and
2” thick aluminium filter.
Note: Always specify the horizontal dimension first.

Octagonal Louver Triangular Louver Arched Louver

SPECIAL ARCHITECTURAL LOUVERS

Fresh Air Louvers


DIMENSIONAL DATA

Dasco Fresh Air Louver with curved frame (DFL - 11H)

Dasco Fresh Air Louver with flat frame (DFL - 11HFF)

DFL - 11H - F2 DFL - 11H - B

Dimensional Data
DEFINITIONS & SELECTION PROCEDURE

DEFINITIONS
Face velocity : Is the air stream velocity measured at the face of a louver in FPM.
CFM : Is the air flow rate in cubic feet per minute.
Effective free area : Is in ft2 , and is related to the other parameters by the equation :

www.dasco.com.kw
CFM = Free Area x Face velocity
= Ak x Vk
Total pressure drop : Is the sum of static pressure and velocity pressure given in inches W.G

SELECTION PROCEDURE
Example:
Louver size required for an exhaust requirements of 1600 CFM with a total pressure drop of
0.016” W.G.
1) From the pressure requirement table 1 it shows that a 400 FPM velocity results an exhaust
pressure drop of 0.016 W.G.
2) Determine the effective free area.

Effective free area Ak = CFM


Vk

1600 2
= = 4.0 ft
400
3) From table 2 the 4.0 ft2 effective free area is suitable for the following sizes: 28” x 54”,
48” x 30” ... etc.

Note:
For other louver sizes not shown in table 2. The approximate effective free area in square feet can
be calculated by using the following formula:-

Effective free area (Ak) = (0.5H - 0.25) x (W-0.125)


where, H is Height in ft and W is Width in ft.

Definitions & Selection


PERFORMANCE DATA

PRESSURE REQUIREMENT

Table No. 1. Total pressure drop in inches of water as a function of face velocity in FPM for DFL-11H

EFFECTIVE FREE AREA

Table No. 2. Effective free area in ft2 (Ak factor) for DFL-11H

Performance Data
SAND LOUVERS

GENERAL
Dasco sand louver DSL-12H are architectural
air inlets. They are widely used for building
exteriors and are suitable for different HVAC

www.dasco.com.kw
and industrial applications to prevent sand
entry. The blades are carefully designed to
provide a low resistance to air flow and a high
free area.

Sand Louver (DSL - 12H)

DESCRIPTION
DSL-12H louvers have 2 inch deep horizontal fixed blades designed carefully for low pressure
drop and to prevent entry of sand. The frame is 1.25” wide (flat or curved) flanged type and is
mechanically joined to give a rugged construction to the louver. These louvers are available as
optional with galvanized bird screen, aluminum type air filter in 1”, 2” and 4” thickness and
volume control damper. They are manufactured in a wide range of standard sizes however, they
can be supplied in non-standard sizes, depths or architectural shapes to suit customers requirements.

MATERIAL AND FINISH


DSL-12H sand louvers are made of heavy
extruded aluminium profiles. They are available
in white polyester powder coated finish or any
other RAL standard colour upon customer’s
request. Bird screens are made of galvanized
expanded metal sheets

Sand Louver With Flat Frame


(DSL - 12HFF)

Sand Louvers
PRODUCT CODE

Dasco Sand Louver DSL - 12H -W -H -C

Width in inch.
Height in inch.

Accessories:
B :Bird screen
D :Volume Control Damper (VCD)
BD :Bird screen & VCD.
I :Insect Screen.
F1 :Aluminium Filter 1” thick.
F2 :Aluminium Filter 2” thick.
F4 :Aluminium Filter 4” thick.

Use the code of DSL-12HFF to refer to Dasco sand louver with flat frame.

Example:
• DSL - 12H - 30 - 18 - B:
Dasco Sand Louver - size 30” x 18” with bird screen.
• DSL - 12 H - 24 - 20 BDF1:
Dasco Sand Louver - size 24” x 20” with bird screen, volume control damper and 1” thick
aluminium filter.

A special assembly of sand louver with a bird


screen, volume control damper and a washa-
able aluminium filter. (All are enclosed in a
galvanized box).

Example: DSL-12H - W - H - BDF2

10

Sand Louvers
DIMENSIONAL DATA

www.dasco.com.kw
Dasco Sand Louver with curved frame - (DSL - 12H)

Dasco Sand Louver with flat frame - (DSL - 12HFF)

SELECTION PROCEDURE
To select a suitable size of a sand louver (DSL-12H) for a certain application, follow exactly the same
procedure as been explained previously.

Note
For louver sizes not shown in table 5. The approximate effective free area in square feet can be calculated
by using the following formula:-

Effective free area (Ak) = (0.45 H-0.08) x (W-0.1)

Where, H is Height in ft and W is Width in ft.

11

Dimensional Data
PERFORMANCE DATA

AVAILABLE STANDARD SIZES

Table No. 3 DSL-12H standard sizes available (HxW) in inches.

PRESSURE REQUIREMENT

Table No. 4 Intake pressure drop in inches of water as a function of face velocity in FPM for DSL-12H.

EFFECTIVE FREE AREA

Table No. 5. Effective free area in ft2 (AK factor) for DSL-12H.

12

Performance Data
SAND LOUVERS (HEAVY DUTY TYPE)

GENERAL
Dasco sand louvers DSLH-12H are considered as an architectural air inlets. They have wide deep heavy
aluminium blades suitable to be used for building exteriors and are very efficient to prevent sand entry.
They are used for different HVAC and industrial applications. Special blades are carefully designed to

www.dasco.com.kw
provide a low resistance to air flow and high free area.

DESCRIPTION
DSLH - 12H sand louvers have 4 inch deep horizontal fixed blades designed carefully for low pressure
drop and to prevent entry of sand. The frame is 45 mm wide, 2mm thick and is mechanically joined to
give a rugged construction to the louver. These louvers are available as optional with galvanized bird
screen, aluminium type air filter in 1”, 2” and 4” thickness and volume control damper. They are manuf-
factured in a wide range of standard sizes however, they can be supplied in non-standard sizes, depths or
architectural shapes to suit customers requirements.

Sand Louver - Heavy Duty Type Sand Louver - Heavy Duty Type With Filter
(DSLH - 12H) (DSLH - 12H - F2)

13

Sand Louvers (Heavy Duty)


MATERIAL AND FINISH
DSLH-12H sand louvers are made of an extra heavy extruded aluminium profiles. They are available in
white polyester powder coated finish or any other RAL standard colour upon customer’s request. Bird
screens are made of galvanized expended metal sheets.

PRODUCT CODE

Dasco Sand Louver Heavy Duty type DSL - 12H -W -H -C

Width in inch.
Height in inch.

Accessories:
B:Bird screen
D :Volume Control Damper (VCD)
BD :Bird screen & VCD.
I :Insect Screen.
F1 :Aluminium Filter 1” thick.
F2 :Aluminium Filter 2” thick.
F4 :Aluminium Filter 4” thick.

Use the code of DSLH-12HFF to refer to Dasco sand louver with flat frame.

14

Sand Louvers (Heavy Duty)


Example:
• DSL - 12H - 40 - 24 - B:
Dasco Sand Louver Heavy duty type - size 40” x 24” with bird screen.
• DSL - 12 H - 30 - 24 BDF2:

www.dasco.com.kw
Dasco Sand Louver Heavy duty type - size 24” x 20” with bird screen, volume control damper
and 2” thick aluminium filter.

DSLH - 12H-W-H-BDF2 (Back View)

A special assembly of Dasco sand louver - heavy duty type - with a bird screen, volume control
damper and a washable aluminium filter. (All are enclosed in a galvanized box).

Model: DSLH - 12H - W - H - BDF2

15

Sand Louvers (Heavy Duty)


DIMENSIONAL DATA

Dasco Sand Louver - heavy duty type DSLH-12H

SELECTION PROCEDURE
To Select a suitable size of a sand louver (DSLH-12H) for a certain application, follow exactly the
same procedure as been explained previously.

Note
For louver sizes not shown in table 8. The approximate effective free area in square feet can be calculated
by using the following formula:
Effective free area (Ak) = (0.55H - 0.76) x (W - 0.27)
Where, H is Height in ft and W is Width in ft.

1. Dasco Sand Louver


(Extruded Aluminium)

2. Bird Screen (Galvanized)

3. Volume Control Damper


(Galvanized) with side
quadrant (manual type)

4. 2” Thick Aluminium washa-


able filter removable from
the side.

DSLH - 12H DSL - 12H

16

Dimensional Data
PERFORMANCE DATA

AVAILABLE STANDARD SIZES

www.dasco.com.kw
Table No. 6 DSLH-12H standard sizes available (HxW) in inches.

PRESSURE REQUIREMENT

Table No. 7 Intake pressure drop in inches of water as a function of face velocity in FPM for DSLH-12H.

EFFECTIVE FREE AREA

Table No. 8. Effective free area in ft2 (Ak factor) for DSLH-12H.

17

Performance Data
SAND TRAP LOUVERS

GENERAL

Dasco sand trap louvers DSL-8X are designed


for fresh air intake applications to separate
air-borne sand and dust from the stream of
air. They are provided with a self emptying
sand drain holes at the base. Blades are also
arranged in a way to provide a low resistance
to air flow and a high free area.

Sand Trap Louver (DSL - 8AL)

DESCRIPTION

DSL-8X sand trap louvers are manufactured from extruded aluminium profiles as standard and are
available in a wide range of sizes for all intake capacities. Blades are of 4” deep aluminium profiles
as standard. However, other blade depths are also available upon customer’s request (1.5”, 1.75”
and 2”). The frame is 3” wide and is perfectly joined to give a rugged construction to the louver.
Smaller 2” width frames are also available. Another optional sand trap louvers are completely cons-
structed from galvanized steel. Galvanized bird screens are also available as accessories.

MATERIAL AND FINISH

DSL-8X sand trap louvers are made of heavy


gauge extruded aluminium profiles. They are
available in white polyester powder coated fini-
ish or any other RAL standard colour upon
customer’s request.
Galvanized steel sand trap louvers are also
available as optional with:-
Frames : 18 gauge
DSL - 8AL (2” Width Frame)
Blades : 20 gauge

18

Sand Trap Louvers


PRODUCT CODE
Dasco Sand Trap louver DSL - 8X - W - H - C

MATERIAL :
AL: Aluminium construction
GL: Galvanized construction

www.dasco.com.kw
Width in inch.

Height in inch.
ACCESSORIES:
B :Galvanized Bird Screen.
D :Volume Control Damper (VCD)
BD :Bird screen & VCD.
I :Insect Screen.
F1 :Aluminium Filter 1” thick.
F2 :Aluminium Filter 2” thick.
F4 :Aluminium Filter 4” thick.

Example:
• DSL - 8AL - 24 - 24 - B:
Dasco Aluminium Sand Trap Louver size 24” x 24” with bird screen.
• DSL - 8GL - 18 - 30 - BF2:
Dasco Galvanized Sand Trap Louver size 18” x 30” with bird screen and 2” thick aluminium
filter.

DIMENSIONAL DATA

Dasco Sand Trap Louver (DSL - 8AL)

19

Sand Trap Louvers


PERFORMANCE DATA

Pressure Requirement

Table No. 9 Total pressure drop in inches of water as a function of face velocity in FPM for DSL-8X.

EFFECTIVE FREE AREA

Table No. 10. Effective free area in ft2 (Ak factor) for DSL-8X

DSL - 8AL

20

Performance Data
ACOUSTIC LOUVERS

GENERAL
Dasco Acoustic Louvers DACL - 20H are
designed for sound attenuation and for air intake
or extract to atmosphere for air-conditioning

www.dasco.com.kw
plants, enclosed car parking areas, electrical / diesel
generating plants, etc.

STANDARD CONSTRUCTION
Acoustic Louver (DACL - 20H)
Frame : Galvanized Steel Sheet,
Gauge #: 18 (1.31 mmthick)
Baffles : The Baffles are inclined at 40˚
and resistance to water ingress
with acoustic properties. Made
from insulating material (1” thick
x 16 Kg/m2 Fiberglass) which is
inert, incombustible and non-
hygroscopic. They are covered on
the underside with a perforated
G.I. sheet, Gauge #: 22 (0.85mm
thick).
Blade : Galvanized Steel Sheet, Gauge
#: 22 (0.85 mm thick)
Acoustic Louver Section
Wire Mesh : Expanded Galvanized Steel
(Back View)
Sheet, Gauge #: 22 (0.85 mm
thick) as standard.
Finish : White colour for frame & blades as standard. Painted under Electrostatic
Polyester Powder Coated System. Other colours are available upon request.

Note
The Acoustic Louvers are made in one section up to 1,200mm x 2,100mm. Any larger sizes are
manufactured in sections for assembly at site.

21

Acoustic Louvers
PRODUCT CODE DIMENSIONAL DATA
Dasco Sand Acoustic Louver DACL-20H-W - H - C

Width in inch.

Height in inch.
ACCESSORIES:
B :Bird Screen.
FINISH
G :Galvanized
P :Powder Coated

Acoustic Louver (DACL - 20H)

Table No. 11. DACL-20H standard sizes available (HxW) in inches.

22

Acoustic Louvers
PRESSURE RELIEF LOUVERS - GRAVITY SHUTTERS

GENERAL
Dasco pressure relief louvers DPRL-33 are
widely used to maintain constant level of
pressure inside pressurized rooms by relieving

www.dasco.com.kw
excess air when it exceeds the desired limits.
The blades are designed and positioned in such
a way to permit automatic lifting to relieve the
pressure in the room and then to drop back to
the closed position by gravity when the room
pressure is normalized. DPRL-33 louvers can
Pressure Relief Louver
also be used at duct terminations to prevent
(DPRL - 33)
backdrafts when air moving devices (fans) are
switched off.
They are generally installed at exhaust ducts in
painting plants, diesel g enerator rooms,
ventilation systems and kitchen hoods.

DESCRIPTION
Dasco pressure relief louvers-gravity shutters - (DPRL-33) are made of light weight horizontal
pivoted blades, so designed to seal air leakages when closed and to reduce noise generation when
opened. The frame is a flanged rugged type (curved or flat) 1.25” wide.
They are available in standard sizes and are also manufactured (as optional) in non-standard sizes
upon customers requirements.
Galvanized bird screen are also provided as accessories.

23

Pressure Relief Louvers


MATERIAL AND FINISH
DASCO pressure relief louvers DPRL-33 are made of extruded aluminium profiles. They are
available in white polyester powder coated finish or any other RAL standard colour upon customer’s
request. Bird screens are made of galvanized expanded metal sheets.

PRODUCT CODE
Dasco Pressure Relief Louver DPRL - 33 - W - H - C

Width in inch.
Height in inch.

ACCESSORIES:
B :Galvanized Bird Screen.
D :Volume Control Damper (VCD)

Example:
DPRL - 33 - 24 - 30 - B:
DASCO pressure relief louver size 24”x30” with bird screen.

DPRL - 33 (totally closed) DPRL - 33 (100% opened blades)

24

Pressure Relief Louvers


DIMENSIONAL DATA

www.dasco.com.kw
Dasco Pressure Relief Louver - gravity shutter (DPRL - 33)

AVAILABLE STANDARD SIZES

Table No. 12 DPRL-33 standard sizes available (HxW) in inches.

DPRL - 33 (totally closed) DPRL - 33 (100% opened blades)

25

Dimensional Data
DEFINITIONS & SELECTION PROCEDURE

DEFINITIONS
Face velocity : Is the air stream velocity measured at the face of a louver in FPM.
CFM : Is the air flow rate in cubic feet per minute.
Effective free area : Is in ft2 , and is related to the other parameters by the equation :
CFM = Free Area x Face velocity
= Ak x Vk
Total pressure drop : Is the sum of static pressure and velocity pressure given in inches W.G

SELECTION PROCEDURE
Example:
Louver size required for an exhaust requirements of 1250 CFM with a total pressure drop of
0.13” W.G.
1) From the pressure requirement table 13 it shows that a 500 FPM velocity results an exhaust
pressure drop of 0.13” W.G.
2) Determine the effective free area.

Effective free area Ak = CFM


Vk

1250 2
= = 2.5 ft
500
3) From table 14 the 2.5 ft2 effective free area is suitable for the following sizes:
32” x 14”, 28” x 16” ... etc.

Note:
For other louver sizes not shown in table 14, the approximate effective free area in square feet can
be calculated by using the following formula:-

Effective free area (Ak) = (0.9H - 0.05) x (W-0.1) (100% open blades)
where, H is Height in ft and W is Width in ft.

26

Definitions & Selection


PERFORMANCE DATA

PRESSURE REQUIREMENT

Table No. 13 Exhaust pressure drop in inches of water as a function of face velocity in FPM for DPRL-33.

www.dasco.com.kw
(Values are for 100% opened blades)

EFFECTIVE FREE AREA

Table No. 14. Effective free area in ft2 (Ak factor) for DPRL-33. (Values are for 100% opened blades)

DPRL-33 DPRL-33 (special circular shape)

27

Performance Data
PENTHOUSE LOUVERS

GENERAL
Dasco penthouse louvers DPHL - 13H are considered as typical louver units for both air intake and
exhaust applications.
They are designed and built to become a permanent part of the building. They maintain their pleasant
appearance and effective weather protection as a result of their rugged, durable, extruded aluminium
construction and careful workmanship. They are usually furnished with either mullion or mitered
corners and incorporate the normal Dasco fresh air louver blades DFL-11H as standard. However,
any other type of Dasco louver blades can also be used as optional.

Penthouse Louver (DPHL - 13H) Penthouse Louvers (DPHL - 13H)


With Mullion Corner With Mitered Corner

DESCRIPTION
DPHL - 13H penthouse louvers have as a standard 2” deep fixed horizontal blades. The blades are
carefully designed to get low pressure drop, maximum free area and to prevent rain-water penetration.
They are available in 1.25” flanged frame and are built and mounted to an internal framing with
mullion corners. The integral framing mullion structures are furnished with a standard 1.6” x 1.6”
extruded aluminium profiles. For the other mitered corners type penthouse louvers, blades are
beveled and welded internally at the end. The top of the penthouses are covered with flat or pitched
roofs of aluminium sheets. All of the four louver sides are of removable type for easy maintenance
purposes. Penthouse louvers can also be supplied as optional with galvanized bird or insect screens
and / or aluminium washable air filters of 1”, 2”, or 4” thickness.

28

Penthouse Louvers
MATERIAL AND FINISH
DPHL - 13H penthouse louvers are made of heavy gauge extruded aluminium profiles. They are
available in white polyester powder coated finish or any other RAL standard colour upon
customer’s request. Structural mullion corners are of strong aluminium profiles while roof tops
are of aluminium sheets as a standard.

www.dasco.com.kw
However, galvanized roofs are also available upon request.
Bird screens are made of galvanized expanded metal sheets.

PRODUCT CODE
DASCO Penthouse Louver DPHL-13H - W - L - H - C

Width in inch.
Length in inch.
Height in inch.
ACCESSORIES:
B : Bird Screen
I :Insect Screen
F :Aluminium Filter 1” thick.
F2 :Aluminium Filter 2” thick.
F4 :Aluminium Filter 4” thick.

Example:
DPHL-13H - 18 - 18 - 24 - B:
Dasco penthouse louver with 18” x 18” basement
size, 24” height and bird screen.

DPHL - 13H - 24 - 18 - 36 - BF2:


Dasco penthouse louver with 24” x 18” basement
size, 36” height, bird screen and 2” thick aluminium air filter.

29

Penthouse Louvers
DEFINITIONS

DEFINITIONS
Face velocity : Is the air stream velocity measured at the face of a louver in FPM
and it corresponds to the effective free area.
CFM : Is the air flow rate in cubic feet per minute.
Effective free area : Is in ft2 , and is related to the other parameters by the equation :
CFM = Free Area x Face velocity
= Ak x Vk
Penthouse louver perimeter : Is the inside basement perimeter in feet and is calculated from:
P= 2W + 2L, W and L are the horizontal dimensions of the penthouse
louver.
Total pressure drop : Is the sum of static pressure and velocity pressure given in inches W.G

DPHL - 13H - F2

30

Definitions
DIMENSIONAL DATA

www.dasco.com.kw
DPHL - 13H (with mullion corners)

DPHL - 13H (with mitered corners)

31

Dimensional Data
SELECTION PROCEDURE

Example:
Select a penthouse louver for an exhaust requirements of 3300 CFM with a total pressure drop
of 0.1” W.G.
1) From the pressure requirement table 15 it shows that an 800 FPM velocity results an exhaust
pressure drop of 0.1” W.G.
2) Determine the effective free area:

Effective free area Ak = CFM


Vk

3300 2
= = 4.125 ft
800
3) From table 16 the 4.125 ft2 effective free area is suitable for the following penthouse
louver’s sizes:
• P = 5 ft, H = 28 inch.
Could be suitable for a penthouse basement dimensions of (WxL) - 12” x 18”.
• P = 6 ft, H = 24 inch.
Could be suitable for a penthouse basement dimensions of (WxL) - 12”x24” or 18” x 18”
depending on the duct size.

Note:
For the penthouse louver sizes not shown in table 16. The approximate effective free area in
square feet can be calculated by using the following formula.:-
Effective free area (Ak) = (H-0.5) x (0.5P-0.25)
Where, H is height in ft and P is Inside Perimeter in ft.

PRESSURE REQUIREMENT

Table No. 15 Pressure drop in inches of water as a function of face velocity


through the free area in FPM for DPHL-13H.

32

Selection Procedure
Table No. 16. Effective free area in ft2 (Ak Factor) for DPHL - 13H

Performance Data
PERFORMANCE DATA

33
www.dasco.com.kw
SIGHTPROOF LOUVERS

GENERAL

Dasco sightproof louvers DSPL-16H are


mainly designed to protect air intake and
exhaust openings in building exterior walls.
They are considered as an architectural air
inlets and outlets with a remarkable continuous
horizontal appearance make them preferred
by most architects. The blades are carefully
designed to provide high free area, maximum
resistance to rain and extreme weather conditions
with minimum resistance to airflow.
Sightproof Louver (DSPL - 16H)

DESCRIPTION
DSPL-16H louvers have 3 inch deep heavy gauge horizontal blades of 2 mm thick aluminium
extruded profiles. They are carefully designed to get low pressure drop, maximum free area and to
prevent rain water penetration by diverting water along blade troughs. They are available in 1.6”
flanged curved frame of heavy gauge aluminium profile which in turn is mechanically joined to
give the heighest rigidity and strength. Louvers can be supplied as optional with galvanized bird
or aluminium insect screen, volume control damper and aluminium air filter of 1”, 2” or 4” thickness.
The filters are accessable from the side or backward of the louver depending upon type of
installation and must be specified by the customer. These louvers are available in standard given
sizes, however they can also be supplied in other requested sizes and architectural shapes upon
customers requirements.

MATERIAL AND FINISH


DSPL-16H louver are made of heavy gauge extruded aluminium profiles of 2 mm thickness.
They are available in white polyester powder coated finish or any other RAL standard colour upon
customer’s request.
Bird screens are made of galvanized expanded metal sheets.

34

Sightproof Louvers
PRODUCT CODE
Dasco Sightproof Louver DSPL - 16H - W - H - C

Width in inch.
Height in inch.

www.dasco.com.kw
ACCESSORIES:
B : Bird Screen
D :Volume Control Damper (VCD)
BD :Bird screen & VCD.
I :Insect Screen
F1 :Aluminium Filter 1” thick.
F2 :Aluminium Filter 2” thick.
F3 :Aluminium Filter 4” thick. DIMENSIONAL DATA

Example:
• DSPL - 16H - 24 - 30 - B:
Dasco sightproof louver size 24” x 30” with
bird screen.

• DSPL - 16H - 18 - 36 - BDF2


DASCO sightproof louver size 18” x 36” with
bird screen, volume control damper (VCD) and
2” thick aluminium filter.

Dasco Sightproof Louver DSPL - 16H

35

Sightproof Louvers
SELECTION PROCEDURE

Example:
Louver size required for an exhaust requirements of 2200 CFM with a total pressure drop of
0.08” W.G.
1) From the pressure requirement table 18 it shows that a 550 FPM velocity results an exhaust
pressure drop of 0.08” W.G. (Approximately).
2) Determine the effective free area.

Effective free area Ak = CFM


Vk

2200 2
= = 4.0 ft
550
3) From table 19 the 4.0 ft2 effective area is mostly suitable for the size 60” x 30”.

Note:
For other louver sizes not shown in table 19. The approximate effective free area in square feet
can be calculated by using the following formula:-
Effective free area (Ak) = (0.36H-0.13) x (W-0.05)
Where, H is Height in ft and W is Width in ft.

AVAILABLE STANDARD SIZES

Table No. 17 DSPL-16H standard sizes available (HxW) in inches.

36

Selection Procedure
PERFORMANCE DATA

PRESSURE REQUIREMENT

Table No. 18 Total pressure drop in inches of water as a function of face velocity in FPM for DSPL-16H.

www.dasco.com.kw
EFFECTIVE FREE AREA

Table No. 19. Effective free area in ft2 (Ak factor) for DSPL-16H.

DSPL - 16H DSPL - 16H


(Cross Section)

37

Performance Data
STATIONARY DRAINABLE LOUVERS

GENERAL
Dasco stationary drainable louvers DSDL-18H
are considered as high performance louvers
designed for both intake and exhaust
applications. The unique configuration of the
louver blades gives them a remarkable drainable
effect. These louvers are the most efficient in
minimizing water penetration. They are carefully
designed to provide high free area, maximum
resistance to rain with minimum resistance to
airflow.
Stationary Drainable Louver
(DSDL - 18H)

DESCRIPTION
DSDL-18H louvers have 3 inch deep heavy gauge horizontal blades of 2 mm thick aluminium
extruded profile. They are carefully designed to get low pressure drop, maximum free area and to
prevent rain water penetration with a high performance drainable effect.
They are available in 1.6” flanged curved frame of heavy gauge aluminium extruded profile which
in turn is mechanically joined to give the highest rigidity and strength. Louvers can be supplied
with galvanized bird or aluminium insect screen, volume control damper and aluminium air filter of
1”, 2” or 4” thickness. The filters are accessable from the side or backward of the louver
depending upon type of installation and must be specified by the customer. These louvers are
available in standard given sizes, however they can also be supplied in other requested sizes and
architectural shapes upon customers requirements.

MATERIAL AND FINISH


DSDL - 18H louvers are made of heavy gauge extruded aluminium profiles of 2 mm thickness.
They are available in white polyester powder coated finish or any other RAL standard colour upon
customer’s request. Bird screens are made of galvanized expanded metal sheets.

38

Drainable Louvers
PRODUCT CODE
Dasco Stationary Drainable Louver DSPL - 18H - W - H - C

Width in inch.
Height in inch.

www.dasco.com.kw
ACCESSORIES:
B : Bird Screen
D :Volume Control Damper (VCD)
BD :Bird screen & VCD.
I :Insect Screen
F1 :Aluminium Filter 1” thick.
F2 :Aluminium Filter 2” thick.
F3 :Aluminium Filter 4” thick. DIMENSIONAL DATA

Example:
• DSDL - 18H - 30 - 36 - B:
DASCO stationary drainable louver size
30” x 36 with bird screen.

• DSDL - 18H - 18 - 36 - BDF1:


DASCO stationary drainable louver size 18” x 36”
with bird screen, volume control damper (VCD)
and 1” thick aluminium filter.

Dasco Stationary Drainable Louver


(DSDL - 18H)

39

Drainable Louvers
SELECTION PROCEDURE

Example:
Louver size required for an exhaust requirements of 500 CFM with a total pressure drop of 0.04”
W.G.
1) From the pressure requirement table 21 it shows that a 500 FPM velocity results an exhaust
pressure drop of 0.04” W.G.
2) Determine the effective free area:
Effective free area Ak = CFM
Vk

500 2
= = 1.0 ft
500
2
3) From table 22 the 1.0 ft effective area is mostly suitable for the size: 18” x 24”, 12” x 48” ...etc.
Note:
For other louver sizes not shown in table 22. The approximate effective free area in square feet can
be calculated by using the following formula:-
Effective free area (Ak) = (0.575H-0.30) x (W-0.15)
Where, H is Height in ft and W is Width in ft.

AVAILABLE STANDARD SIZES

Table No. 20 DSDL-18H standard sizes available (HxW) in inches.

40

Selection Procedure
PERFORMANCE DATA

PRESSURE REQUIREMENT

Table No. 21 Total pressure drop in inches of water as a function of face velocity in FPM for DSDL-18H.

www.dasco.com.kw
EFFECTIVE FREE AREA

Table No. 22. Effective free area in ft2 (Ak factor) for DSDL-18H.

DSDL - 18H
(Cross section)
DSDL - 18H

41

Performance Data
STATIONARY STORMPROOF LOUVERS

GENERAL
Dasco stationary stormproof louvers DSSL-19H
are mainly designed to protect air intake and
exhaust openings in building exterior walls and
are recommended for applications where low
water penetration is required. They are carefully
designed to provide high free area, maximum
resistance to rain and extreme weather conditions
with minimum resistance to airflow.

Stationary Stormproof Louver


(DSSL - 19H)
DESCRIPTION
DSSL - 19H louvers have heavy gauge horizontal blades of 1.8 mm thick aluminium extruded
profile. They are carefully designed to get low pressure drop, maximum free area and to prevent
rain water penetration with high efficiency to extreme weather conditions.
They are available in 1.6” flanged curved frame of heavy gauge aluminium extruded profile which
in turn is mechanically joined to give the highest rigidity and strength. Louvers can be supplied
with galvanized bird or aluminium insect screen, volume control damper and aluminium air filter
of 1”, 2” and 4” thickness. The filters are accessable from the side or backward of the louver
depending upon type of installation and must be specified by the customer.
These louvers are available in standard given sizes, however they can also be supplied in other
requested sizes and architectural shapes upon customers requirements.

MATERIAL AND FINISH


DSSL - 19H louvers are made of heavy gauge extruded aluminium profiles. They are available in
white polyester powder coated finish or any other RAL standard colour upon customer’s request.
Bird screens are made of galvanized expanded metal sheets.

42

Stormproof Louvers
PRODUCT CODE
Dasco Stationary Stormproof Louver DSSL - 19H - W - H - C

Width in inch.
Height in inch.

www.dasco.com.kw
ACCESSORIES:
B : Bird Screen
D :Volume Control Damper (VCD)
BD :Bird screen & VCD.
I :Insect Screen
F1 :Aluminium Filter 1” thick.
F2 :Aluminium Filter 2” thick.
F3 :Aluminium Filter 4” thick. DIMENSIONAL DATA

Example:
• DSSL -19H - 24 - 36 - BF1:
DASCO stormproof louver size 24” x 36” with
bird screen and I” thick aluminium filter.

• DSSL - 19H - 48 - 48 - BDF2


DASCO stormproof louver size 48”x48” with bird
screen, volume control damper (VCD) and 2” thick
aluminium filter.

Dasco Stationary Stormproof Louver


DSSL - 19H

43

Stormproof Louvers
SELECTION PROCEDURE

Example:
Louver size required for an exhaust requirements of 1200 CFM with a total pressure drop of
0.07” W.G.
1) From the pressure requirement table 24 it shows that a 600 FPM velocity results an exhaust
pressure drop of 0.07” W.G.
2) Determine the effective free area:
Effective free area Ak = CFM
Vk

1200 2
= = 2.0 ft
600
2
3) From table 25 the 2.0 ft effective area is mostly suitable for the size 42” x 18”.
Note:
For other louver sizes not shown in table 25. The approximate effective free area in square feet can
be calculated by using the following formula:-
Effective free area (Ak) = (0.58H-0.34) x (W-0.3)
Where, H is Height in ft and W is Width in ft.

AVAILABLE STANDARD SIZES

Table No. 23 DSSL-19H standard sizes available (HxW) in inches.

44

Selection Procedure
PERFORMANCE DATA

PRESSURE REQUIREMENT

Table No. 24 Total pressure drop in inches of water as a function of face velocity in FPM for DSSL-19H.

www.dasco.com.kw
EFFECTIVE FREE AREA

Table No. 25. Effective free area in ft2 (Ak factor) for DSSL-19H.

DSSL - 19H
(Cross section)
DSSL - 19H

45

Performance Data
TESTING AND APPROVAL

Different samples from DASCO air terminal devices (Louvers) were tested at ITS
(Intertek Testing Services) labs in accordance with:
• Air diffusion council test code for grilles, registers and diffusers No. ADC 1062:
GRD-84.
• ISO 5219 “Air distribution and air diffusion laboratory aerodynamic testing and
rating of air terminal devices”.
• ANSI/ASHRAE 70-1991, “Method of testing for rating the performance of air
outlets and inlets”.

LOUVERS WERE TESTED FOR:

a. Static pressure in inches W.G.


b. Ak (Area factor).

46

Testing & Approval


COATING WITH POWDER

NOW YOU CAN ACHIEVE OPTIMAL COATING PERFORMANCE


ON ALL PRODUCTS YOU PAINT!

www.dasco.com.kw
DASCO offers a first class service by introducing a wide range of perfect polyester
powder coating on all of its aluminium products of air terminal devices.
The best quality of polyester powder Corro-Coat are used in according to the
international standards (BS,ISO,DIN,ASTM). PE-F architectural grade polyester
powders are used perfectly with pre-treatment, electrostatic spray and curing
in accordance with the above standards recommendations. A complete range of
RAL-Standard colours are always available in addition to a vast range of special
compound colours as per our customers request.
RAL Standard Colour Chart Swatch

47
Now producing relief knots as in natural wood

New Technology Excellence


1. Resistance to high radiation and extreme climatic conditions.
2. It can be used in painting elaborate geometrical shapes producing perfect
quality and aesthetic results.
3. It is the only technology that can replace wood in traditional areas.

New Mahogany - 21

New Mahogany - 22

48
Notes

49
www.dasco.com.kw
Since 1962
Product Bulletin 136-D

P.O. Box: 6192 Hawalli 32036 Kuwait.


Tel: +965 4839911 Fax: +965 4815498
www.dasco.com.kw

Vous aimerez peut-être aussi