Vous êtes sur la page 1sur 4

www.reinhausen.

com
VACUTAP® V V
On-Load Tap-Changer
for Regulating Transformers
VACUTAP® V V – An Investment which Pays for Itself

• Maintenance-free up to 300,000 operations


– no time based maintenance
– maintenance-free for more or less all network applications
– dramatically reduction of life-cycle-costs
– increased transformer availability
• No oil carbonisation
• No oil-filter plant
• No contact change
• No arcing in the insulating oil
• Extended lifespan of the insultating oil

Step voltage
2000
Ui (in V)

For process application


please contact MR.

1500

1000
V V 250 V V 400 V V 600

500

0
0 50 100 150 200 250 300 350 400 450 500 550 600
Network application
Process application
Iu (in A)

Our Experience – Your Safety

Absolutely reliable up-to-date technology is what MR customers


1000
can expect. Back in the eighties we began the developement of the V V 250 V V 400 V V 600
PSt (in kVA)

vacuum switching technology. Our comprehensive know-how from


Switching capacity
more than 120,000 on-load tap-changers sold made us the pioneers 500

in this innovative technology. The result is the VACUTAP® range of


on-load tap-changers, high-tech products with MR’s proven quality. 0
This quality is ensured by the vacuum-interrupters, which have been 0 50 100 150 200 250 300 350 400 450 500 550 600
Network application
developed according to our strict guidelines and which have been Iu (in A)
Process application
tried and tested in operation for many years.
Technical Specifications of VACUTAP® V V
On-load tap-changer VV III VV III VV III VV III VV III VV III VV I VV I
250 Y 250 D 400 Y 400 D 600 Y 600 D 401 3) 401 3)
Number of poles 3 3 3 3 3 3 1
and application neutral at any neutral at any neutral at any at any position
point position on point position on point position on on the winding
the winding the winding the winding
Max. rated through-current 250 400 600 400
Ium (in A)
Rated withstand current 4 5 6 5
(in kA)
Rated duration of 3 3 3 3
short-circuits (in s)
Rated peak withstand current 10 12.5 15 12.5
(in kA)
Max. rated step voltage 2000 2000 … 1700 1) 2000 … 1000 1) 2000 … 1700 1)
Ui (in V)
Switching capacity (in kVA) See PSt-/Iu-Diagram
Rated frequency 50 … 60 Hz
Number of operating positions without change-over selector: max. of 12, with change-over selector: max. of 23 with change-over selector: max. of 23
Rated insulation level
Highest voltage for 40 76 40 76 1454) 40 76 40 76 1454) 40 76 40 76 1454) 76 1454)
equipment Um (in kV)2)
Rated lightning impulse with- 200 350 200 350 650 200 350 200 350 650 200 350 200 350 650 350 650
stand voltage (in kV, 1.2/50)
AC withstand voltage 70 140 70 140 275 70 140 70 140 275 70 140 70 140 275 140 275
(in kV, 50 Hz, 1 min)
Rated withstand voltages of See table 3 in the Technical Data of the VV (TD 203).
the inner insulation
Oil compartment Sealed up to 0.3 bar continuous differential pressure (0.6 bar test pressure), head and cover of the on-load tap-changer are vacuum-proof.
Temperature range The VACUTAP® VV on-load tap-changer can be operated within the rated load range with oil temperatures of - 25 ˚C to + 105 ˚C.
1) See also Ui-/Iu-Diagram
2) In acc. w. VDE 0111, part 1: r. m. s. value of the phase-phase voltage for which a piece of equipment ist rated for its insulation
3) 600 A design on request
4) A maximum operating voltage of 132 kV + 15 % = 151.8 kV is permitted when the test voltages of the 145 kV class are not exceeded.

Installation lengths
3-pole VV III 1-pole VV I
Y 40 kV D 40 kV Y 76 kV D 76 kV D 145 kV 76 kV 145 kV
250, 400, 600 A 250, 400, 600 A 250, 400, 600 A 250, 400, 600 A 250, 400, 600 A 400 A 400 A
h = 1628 mm h = 1628 mm h = 1810 mm h = 1810 mm h = 2224 mm h = 816 mm h = 978 mm
© Maschinenfabrik Reinhausen GmbH Phone (+49) 9 41/40 90-0
www.reinhausen.com Falkensteinstrasse 8 Fax (+49) 9 41/40 90-111
93059 Regensburg, Germany E-mail sales@reinhausen.com

Please note: The data in our publications may differ from the data of devices delivered.
We reserve the right to make changes without notice.
IN169/07en – 0107/2000 – 169/07/01/0 – F0053806 · dp · Printed in Germany