Condition of testing.
- Engine to be stopped.
- Hydraulic pressure available on engine. (start-up pump’s running)
- All Ok Test takes between 20-30 Minutes.
Go to MOP A or B
Click on Access and change access level to Chief level. Password “BADOIT”.
Open “System View I/O Test” under Maintenance menu.
Open Channel No. 70 and apply the value to 0.0 V. By using the arrows. 0.0V is always full ahead.
Open Channel No. 30 and No. 34 , and write down the Electrical Value and Process value
- Channel No. 30 Electrical value_________________mA (Value shall be between 3.5 to 20.5 mA)
-Channel No. 30 Process value _________________% (expected value app. 100%)
- Channel No. 34 Electrical value_________________mA (Value shall be between 3.5 to 20.5 mA)
- Channel No. 34 Process value _________________% (expected value app. 100%)
1. MPC ACUx and measure output voltage ch70 terminal B, C. The measurement should be 0.0V.- If
not OK; change MPC. If OK continuous to measure the Amplifier terminal plug with 4 connectors.
Terminal A,B= 0.0V (If not app. 0.0V change FIVA Amp)and Terminal C,D should be steady 24V(If
not OK, check cabling from J9 (MPC) to J90 (amplifier)).
2. If swash plate feedback ch 34 is unstable. Loosen below plug with swash plate feedback- Open up
the plug too (remove the screw) and check that the wires are firm connected. Check the cabling at
the Swash plate feedback amplifier and check cabling J34. OK ?
The plug is just behind protecting metal
3. If Prop. valve ch 30 is unstable. Loosen below plug with Prop valve feedback too (remove the
screw) and check that the wires are correct connected. Check the cabling at the prop valve
feedback amplifier and check cabling to J30. OK ?
Open Channel No. 70 and change the value to 2.6 V. By using the arrows
Open Channel No. 30 and No. 34 , and write down the Electrical Value and Process value
- Channel No. 30 Electrical value_________________mA (Value shall be between 3.5 to 20.5 mA)
-Channel No. 30 Process value _________________% (expected value app. -100%)
- Channel No. 34 Electrical value_________________mA (Value shall be between 3.5 to 20.5 mA)
- Channel No. 34 Process value _________________% (expected value app. -100%)
1. MPC ACUx and measure output voltage ch70 terminal B, C. The measurement should be 2.6V.- If
not OK; change MPC. Amplifier: Terminal A,B= App.7.5V (If not app. 7.5V change Prop. Amp(If more
than 20V there is no or bad connection to Prop. valve)and Terminal C,D should be steady 24V(If not
OK, check cabling from J9 (MPC) to J90 (amplifier)).
Loosen ctrl plug on the proportional valve:
2. If one or both feedback signals are unstable. And all connectors are checked and feedback signals
within limits. Suggest you exchange MPC with good working MPC- Other ACU?. If the problem
moves with the MPC- The problem is MPC ch.30 or ch.34 . If you have limited time change MPC
with spare. Observe- OK?
Change the MPC (ACUx) back to Normal. MPC will restart in normal mode