NO Area serving Unit Tag


Air Volume
1 Telephone Room GF-SP-VRV-01 200
2 Training Room GF-FCU-VRV-02 300
3 Waiting Room, roomcentral Lobby GF-FCU-VRV-03 & 05 650

4 Corridor4, Ablution Room, Female & Male Toilet GF-FCU-VRV-04 417

5 Pantry Dining Room GF-FCU-VRV-06 300

6 Open Office NE corridor 2 GF-FCU-VRV-07 533


7 GM Room NE GF-SP-VRV-08 142
8 Meeting Room NE GF-SP-VRV-09 142
9 Waiting Room, roomcentral Lobby GF-FCU-VRV-10 & 14 650
Open Office SE
corridor1 File Room
10 GF-FCU-VRV-11 573
SE Air Lock Room
Post air Lock
11 GM Room SE GF-SP-VRV-12 142
12 Meetring room GF-SP-VRV-13 142
13 Meetring Room SW GF-SP-VRV-15 142
14 GM Room SW GF-VRV-16 142
Fire Room SW
15 Open office SW GF-FCU-VRV-17 325
Corridor 5

SI.NO Area serving Unit Tag Supply air Volume


1 Ground Floor ERU-01 954
Indoor Unit
Type
Tonnage (Tr) Kw QTY
1.28 4.5 1 Wall Mounted VRV Split Unit
1.59 5.6 1 Ceiling Suspended & concealed VRV unit
3.98 14.0 2 Ceiling Suspended & concealed VRV unit

2.55 9.0 1 Ceiling Suspended & concealed VRV unit

1.59 5.6 1 Ceiling Suspended & concealed VRV unit

3.18 11.2 1 Ceiling Suspended & concealed VRV unit


1.03 3.6 1 Wall Mounted VRV Split Unit
1.03 3.6 1 Wall Mounted VRV Split Unit
3.98 14.0 2 Ceiling Suspended & concealed VRV unit

3.18 11.18 1 Ceiling Suspended & concealed VRV unit

1.03 3.6 1 Wall Mounted VRV Split Unit


1.03 3.6 1 Wall Mounted VRV Split Unit
1.03 3.6 1 Wall Mounted VRV Split Unit
1.03 3.6 1 Wall Mounted VRV Split Unit

2.01 7.1 1 Ceiling Suspended & concealed VRV unit

Exhaust air Volume Qty Supply Air Diffuser Return Air Diffuser
859 1 6 X 160 l/s 6 X 145 l/s
Outdoor Unit Supply Air Return Air
Capacity Unit Tag QTY Diffuser Diffuser
N/A N/A
3 X 100 l/s 3 X 100 l/s
2 X SLBG 650 l/s 2 X RLBG 650 l/s

GF-VRV-OUU-01 2 X 110 l/s 2 X 110 l/s


22 HP (10 HP+12 HP) 1 1 X 80 l/s 1 X 120 l/s
GF-VRV-ODU-02
3 X 40 l/s 2 X 40 l/s
2 X 90 l/s 2 X 90 l/s
1 X 51 l/s 1 X 51 l/s
6X 89 l/s 6X 89 l/s
N/A N/A
N/A N/A
2 X SLBG 650 l/s 2 X SLBG 650 l/s

4 X 100 l/s 5 X 100 l/s


1 x 59 l/s 1 x 59 l/s
1 x 114 l/s 1 x 114 l/s
GF-VRV-OUU-03
24 HP (12 HP + 12 HP) 1
GF-VRV-ODU-04 N/A N/A
N/A N/A
N/A N/A
N/A N/A

4 X 81 l/s 5 X 81 l/s
Thickness
Metal Density
Duct waste factor
Insulation waste factor

Room Tag

Training Room GF-FCU-VRV-02

Waiting Room, roomcentral Lobby GF-FCU-VRV-03 & 05 & 10 & 14

Corridor4, Ablution Room, Female & Male Toilet GF-FCU-VRV-04

Pantry Dining Room GF-FCU-VRV-06

Open Office SE
corridor1 File Room GF-FCU-VRV-11
SE Air Lock Room
Post air Lock

Fire Room SW
Open office SW GF-FCU-VRV-17
Corridor 5
Fire Room SW
Open office SW GF-FCU-VRV-17
Corridor 5

Thickness
Metal Density
Duct waste factor
Insulation waste factor

Administration building ERU


mm 2
kg/m3 1590
% 28%
% 10%

Flow rate Width Hight length Section Velocity Duct weight


l/s mm mm m m2 m/s kg
300 400 250 2 0.1 3 11
200 300 200 4.2 0.06 3.3 18
100 200 200 3 0.04 2.5 10
39

l/s mm mm m m2 m/s kg
650 450 300 20 0.135 4.8 123
217 200 200 10 0.04 5.4 33
156

l/s mm mm m m2 m/s kg
160 350 200 5 0.07 2.3 23
260 350 200 7 0.07 3.7 32
40 300 100 4 0.03 1.3 14
69

l/s mm mm m m2 m/s kg
300 350 200 6 0.07 4.3 27
51 300 100 3 0.03 1.7 10
90 300 100 2 0.03 3.0 7
44

l/s mm mm m m2 m/s kg
573 450 250 6 0.1125 5.1 35
373 400 250 6 0.1 3.7 32
273 400 200 8 0.08 3.4 40
100 300 100 13 0.03 3.3 43
150

l/s mm mm m m2 m/s kg
325 350 250 6 0.0875 3.7 30
163 350 100 9 0.035 4.7 33
81 300 100 10 0.03 2.7 33
96

mm 2
kg/m3 1590
% 28%
% 10%

Diameter Lenght Tickness Duct weight Insulation area


mm m m3 kg m2
200 148.5 0.186610604 380 32.67
300 61.7 0.11630176 237 20.361
616 53.0

1170
Insulation area
m2
3
5
3
11

m2
33
9
42

m2
7
9
4
20

m2
8
3
2
13

m2
10
9
11
12
42

m2
8
9
9
26

207
Administration Building

Indoor Unit
NO Area serving Unit Tag Air
Tonnage
Volume QTY
(Tr)
(L/s)
1 Telephone Room GF-SP-VRV-01 200 1.28 1
2 Training Room GF-FCU-VRV-02 300 1.59 1
Waiting Room,
3 roomcentral GF-FCU-VRV-03 & 05 650 3.98 2
Lobby
Corridor4
Ablution Room
4 GF-FCU-VRV-04 417 2.55 1
Female & Male
Toilet
Pantry Dining
5 GF-FCU-VRV-06 300 1.59 1
Room
Open Office NE
6 GF-FCU-VRV-07 533 3.18 1
corridor 2
7 GM Room NE GF-SP-VRV-08 142 1.03 1
Meeting Room
8 GF-SP-VRV-09 142 1.03 1
NERoom,
Waiting
9 roomcentral GF-FCU-VRV-10 & 14 650 3.98 2
Lobby
Open Office SE
corridor1 File
Room
10 GF-FCU-VRV-11 573 3.18 1
SE Air Lock
Room
Post air Lock
11 GM Room SE GF-SP-VRV-12 142 1.03 1
12 Meetring room GF-SP-VRV-13 142 1.03 1
Meetring Room
13 GF-SP-VRV-15 142 1.03 1
SW
14 GM Room SW GF-VRV-16 142 1.03 1
Fire Room SW
15 Open office SW GF-FCU-VRV-17 325 2.01 1
Corridor 5

Operating & Controls Building

Indoor Unit
SI.NO Area serving Unit Tag Air Tonnage
QTY
Volume (Tr)
1 Drinking Pantry GF-FCU-VRV-01 533 3.18 1
Air Lock Room,
2 GF-FCU-VRV-02 1200 7.95 1
Central Lobby
3 Meeting Roor GF-SP-VRV-03 294 2.01 1
Ablution, Prayer
4 GF-FCU-VRV-04 325 2.01 1
Room
Depot
5 GF-FCU-VRV-05 766 3.98 1
Equipment
Crew Male
6 Toilet, Lockers GF-FCU-VRV-06 533 3.18 1
Change room5
7 Telephone Room GF-SP-VRV-07 142 1.025 1
ITP-2 control
Room
8 File Room, FF-FCU-VRV-01 533 3.18 1
Sperintendent
ITP-2
9 Central Lobby FF-FCU-VRV-02 & 06 966 6.36 2
File Room ITP-1
Control Room,
10 FF-FCU-VRV-03 417 2.55 1
Superintendent
ITP-1
Operation
11 FF-SP-VRV-04 142 1.025 1
manager
Depot Control
Room
12 File Room FF-FCU-VRV-05 650 3.98 1
Superintendent
Office-Depot
13 Panty FF-FCU-VRV-07 142 1.025 1
14 Meeting Room-1 FF-FCU-VRV-08 300 1.59 1
Staff Male Toilet
Female Toilet
15 FF-FCU-VRV-09 417 2.55 1
Waitting Lounge
& Corridor

Electrical Building

Indoor Unit
SI.NO Area serving Unit Tag Air Tonnage
QTY
Volume (Tr)
1 PLC room GF-FCU-VRV-01 766 3.98 1

GF-FCU-VRV-02 & 03 1200 7.95 2

2 L.V Panel Room


GF-FCU-VRV-04 & 05 1200 7.95 2

GF-FCU-VRV-06, 07 &
1200 7.95 3
08

3 PMCC Room 2
GF-FCU-VRV-09, 10 &
3 PMCC Room 2 1200 7.95 3
11

GF-FCU-VRV-12, 13 &
1200 7.95 3
14

GF-FCU-VRV-15, 16 &
1200 7.95 3
17

4 PMCC Room GF-FCU-VRV-18, 19 &


1200 7.95 3
20

GF-FCU-VRV-21 & 22 1200 7.95 2

GF-FCU-VRV-23 & 24 933 6.36 2


GF-FCU-VRV-25, 26 &
1200 7.95 3
27
Transformer-1 &
5 GF-FCU-VRV-29 1200 7.95 1
02
GF-FCU-VRV-30 966 6.36 1

6 H.V Room GF-FCU-VRV-28 1200 7.95 1

Vehicle Service Building

Indoor Unit
SI.NO Area serving Unit Tag Air Tonnage
QTY
Volume (Tr)
1 Store 1 GF-SP-VRV-01 317 2.01 1
2 Store 2 GF-SP-VRV-02 317 2.01 1
3 Stores Office GF-SP-VRV-03 133 0.8 1
4 Corridor GF-SP-VRV-04 133 0.8 1
5 Office - 1 GF-SP-VRV-05 200 1.28 1
6 Office - 2 GF-SP-VRV-06 142 1.025 1
7 Office - 3 GF-SP-VRV-07 142 1.025 1
8 Work Shop GF-SP-VRV-08 651 3.97 1
stration Building

Outdoor Unit
Type
Capacity Unit Tag QTY

Wall Mounted VRV Split Unit


Ceiling Suspended & concealed
VRV unit
Ceiling Suspended & concealed
VRV unit

22 HP (10
Ceiling Suspended & concealed GF-VRV-OUU-01
HP+12 1
VRV unit GF-VRV-ODU-02
HP)

Ceiling Suspended & concealed


VRV unit
Ceiling Suspended & concealed
VRV unit
Wall Mounted VRV Split Unit
Wall Mounted VRV Split Unit
Ceiling Suspended & concealed
VRV unit

Ceiling Suspended & concealed


VRV unit 24 HP (12
GF-VRV-OUU-03
HP + 12 1
GF-VRV-ODU-04
HP)
Wall Mounted VRV Split Unit
Wall Mounted VRV Split Unit
Wall Mounted VRV Split Unit
Wall Mounted VRV Split Unit

Ceiling Suspended & concealed


VRV unit

& Controls Building

Outdoor Unit
Type
Capacity Unit Tag QTY
Ceiling Suspended & concealed
VRV unit
Ceiling Suspended & concealed
VRV unit

28 HP
GF-VRV-ODU-01
(10 HP +
GF-VRV-ODU-02 1
10 HP +
GF-VRV-ODU-03
Wall Mounted VRV Split Unit
Ceiling Suspended & concealed 28 HP
GF-VRV-ODU-01
VRV unit (10 HP +
GF-VRV-ODU-02 1
Ceiling Suspended & concealed 10 HP +
GF-VRV-ODU-03
VRV unit 8 HP)
Ceiling Suspended & concealed
VRV unit

Wall Mounted VRV Split Unit

Ceiling Suspended & concealed


VRV unit

Ceiling Suspended & concealed


VRV unit

Ceiling Suspended & concealed


VRV unit

Wall Mounted VRV Split Unit 36 HP


FF-VRV-ODU-01
(12 HP +
FF-VRV-ODU-02 1
12 HP +
FF-VRV-ODU-03
Ceiling Suspended & concealed 12 HP)
VRV unit

Wall Mounted VRV Split Unit


Ceiling Suspended & concealed
VRV unit

Ceiling Suspended & concealed


VRV unit

trical Building

Outdoor Unit
Type
Capacity Unit Tag QTY
Ceiling Suspended & decorative 26 HP
FF-VRV-ODU-01
VRV unit (10 HP +
FF-VRV-ODU-02 1
Ceiling Suspended & decorative 8 HP +
FF-VRV-ODU-03
VRV unit 8HP)
20 HP
Ceiling Suspended & decorative FF-VRV-ODU-04
(12 HP + 1
VRV unit FF-VRV-ODU-05
8 HP)
30 HP
FF-VRV-ODU-06
Ceiling Suspended & decorative (12 HP +
FF-VRV-ODU-07 1
VRV unit 10 HP +
FF-VRV-ODU-08
8HP)
30 HP
FF-VRV-ODU-09
Ceiling Suspended & decorative (12 HP +
FF-VRV-ODU-10 1
VRV unit 10 HP +
FF-VRV-ODU-11
8HP)
30 HP
FF-VRV-ODU-12
Ceiling Suspended & decorative (12 HP +
FF-VRV-ODU-13 1
VRV unit 10 HP +
FF-VRV-ODU-14
8HP)
30 HP
FF-VRV-ODU-15
Ceiling Suspended & decorative (12 HP +
FF-VRV-ODU-16 1
VRV unit 10 HP +
FF-VRV-ODU-17
8HP)
30 HP
FF-VRV-ODU-18
Ceiling Suspended & decorative (12 HP +
FF-VRV-ODU-19 1
VRV unit 10 HP +
FF-VRV-ODU-20
8HP)
Ceiling Suspended & decorative 36 HP
FF-VRV-ODU-21
VRV unit (12 HP +
FF-VRV-ODU-22 1
Ceiling Suspended & decorative 12 HP +
FF-VRV-ODU-23
VRV unit 12HP)
Ceiling Suspended & decorative 30 HP
FF-VRV-ODU-24
VRV unit (12 HP +
FF-VRV-ODU-25 1
Ceiling Suspended & decorative 10 HP +
FF-VRV-ODU-26
VRV unit 8HP)
Ceiling Suspended & decorative 28 HP
FF-VRV-ODU-27
VRV unit (10 HP +
FF-VRV-ODU-28 1
Ceiling Suspended & decorative 10 HP +
FF-VRV-ODU-29
VRV unit 8HP)

Service Building

Outdoor Unit
Type
Capacity Unit Tag QTY
Wall Mounted VRV Split Unit
Wall Mounted VRV Split Unit
Wall Mounted VRV Split Unit
Wall Mounted VRV Split Unit 16 HP (8
GF-VRV-OUU-01
HP + 8 1
Wall Mounted VRV Split Unit GF-VRV-ODU-02
HP)
Wall Mounted VRV Split Unit
Wall Mounted VRV Split Unit
Wall Mounted VRV Split Unit
Administration Building

Indoor Unit
NO Area serving Unit Tag Air
Tonnage
Volume QTY
(Tr)
(L/s)
1 Electrical RoomGF-SP-IDU-01 & 02 317 2 2
2 Sever Room NE GF-SP-IDU-03 250 1.5 1
3 Server Room SE GF-SP-IDU-04 250 1.5 1
4 Server Room SW GF-SP-IDU-05 250 1.5 1

Operation & Controls Building

Indoor Unit
SI.NO Area serving Unit Tag
Air VolumeTonnage (Tr)QTY
1 Electrical Room GF-SP-IDU-01 317 2 2
2 Sever Room FF-SP-IDU-03 250 1.5 1
3 Electrical Room GF-SP-IDU-04 250 1.5 1
4 Server Room SW GF-SP-IDU-05 250 1.5 1
4 Server Room SW GF-SP-IDU-05 250 1.5 1

Electrical Substation Building

Indoor Unit
SI.NO Area serving Unit Tag
Air VolumeTonnage (Tr)QTY
1 Battery Room GF-SP-IDU-01 142 1 1

Vehicle Service Building

Indoor Unit
SI.NO Area serving Unit Tag
Air VolumeTonnage (Tr)QTY
1 Electrical Room GF-SP-IDU-01 330 2 1

Guard House

Indoor Unit
SI.NO Area serving Unit Tag
Air VolumeTonnage (Tr)QTY
1 Guard House GF-SP-IDU-01 250 1.5 1
Security Cabin

Indoor Unit
SI.NO Area serving Unit Tag
Air VolumeTonnage (Tr)QTY
1 Security Cabine GF-SP-IDU-01 142 1 1
n Building

Outdoor Unit
Type Capacit
y Unit Tag QTY
(Tr) GF-SP-ODU-01 &
High wall Split Unit 2 02 2
High wall Split Unit 1.5 GF-SP-ODU-03 1
High wall Split Unit 1.5 GF-SP-ODU-04 1
High wall Split Unit 1.5 GF-SP-ODU-05 1

trols Building

Outdoor Unit
Type
Capacity (Tr) Unit Tag QTY
GF-SP-ODU-01 &
High wall Split Unit 2 2
02
High wall Split Unit 1.5 GF-SP-ODU-03 1
High wall Split Unit 1.5 GF-SP-ODU-04 1
High wall Split Unit 1.5 GF-SP-ODU-05 1
High wall Split Unit 1.5 GF-SP-ODU-05 1

ation Building

Outdoor Unit
Type
Capacity (Tr) Unit Tag QTY
High wall Split Unit 1 GF-SP-ODU-01 1

ce Building

Outdoor Unit
Type
Capacity (Tr) Unit Tag QTY
High wall Split Unit 2 GF-SP-ODU-01 1

House

Outdoor Unit
Type
Capacity (Tr) Unit Tag QTY
High wall Split Unit 1.5 GF-SP-ODU-01 1
Cabin

Outdoor Unit
Type
Capacity (Tr) Unit Tag QTY
High wall Split Unit 1 GF-SP-ODU-01 1
Electrical Substation Building

SI.NO Area serving Unit Tag Air Volume (L/s) ESP (Pa)
1 Battery Room WEF-01 200 50

Vehicle Service Building

SI.NO Area serving Unit Tag Air Volume (L/s) ESP (Pa)
1 Toilet WEF-01 105 50
2 Oil storage WEF-02 140 50
3 Paint Store WEF-03 150 50
4 Battery Store WEF-04 150 50
5 Type Store WEF-05 215 50
6 Sample Room WEF-06 85 50
7 Equipment Plant Room WEF-07 275 50
8 Tool Room 95 50
WAF-01
9 Grinding Room 95 50

Guard House

SI.NO Area serving Unit Tag Air Volume (L/s) ESP (Pa)
1 Toilet WEF-01 35 50
Qty
1.0

Qty
1
1
1
1
1
1
1
1
1

Qty
1.0
Administration Building

Supply air Exhaust air


SI.NO Area servingUnit Tag
Volume (L/s) Volume (L/s)
1 Ground FloorERU-01 954 859

Operation & Controls Building

Supply air Exhaust air


SI.NO Area servingUnit Tag
Volume (L/s) Volume (L/s)
Ground
1 Floor & ERU-01 1470 1323
First Floor
Qty

1.0

Qty

1.0