Section 1 – Introduction
Copyright © Carrier Corp. 2005
Technical Development Program
Michael Ho
Version 1.2
Copyright © Carrier Corp. 2005
Menu
Section 1 Introduction
Section 2 Fan Impact
Section 3 Fan Types Used in VAV Systems
Section 4 Centrifugal Fans
Section 5 Axial Fans
Section 6 Fan Volume Control
Section 7 Fan Stability
Section 8 VFD Energy Savings in VAV Systems
Section 9 VAV Fan Control Tracking
and Pressurization
Section 10 Summary
FANS IN VARIABLE
AIR VOLUME SYSTEMS
Introduction
Section 1 – Introduction
Copyright © Carrier Corp. 2005
Variable Air Volume (VAV) System
System
Components:
1. VAV Box with
Heating Coil
2. Zone Thermostat
3. Supply Diffuser
4. Return Grille
5. Duct Static
Pressure Sensor
6. Supply Fan VFD Zone 1 Zone 2 Zone 3 Zone 4
7. Air Handler
8. Supply Duct
Section 1 – Introduction
Copyright © Carrier Corp. 2005
SECTION 2
FANS IN VARIABLE
AIR VOLUME SYSTEMS
Fan Impact
Static Pressure
• Excessive duct pressure C
B
Design A
• Excessive duct leakage
sp
C1 B1
• Excessive sound levels
D1
• Erratic VAV terminal control E1
FANS IN VARIABLE
AIR VOLUME SYSTEMS
FANS IN VARIABLE
AIR VOLUME SYSTEMS
Centrifugal Fans
Inlet
Inlet Cone
Inlet Bell
Inlet Flare
Inlet Nozzle
Venturi
Tip
Rotation
Heel
Characteristics:
• Most commonly used wheel in HVAC
• Light weight – low cost
• Operates at static pressures up to 5 in. wg max
• 24 to 64 blades
• Low rpm (800 to 1200 rpm)
Section 4 – Centrifugal Fans
Copyright © Carrier Corp. 2005
Forward-Curved Centrifugal Fan Characteristics
Dip
Fan Horsepower
Typical
Forward-Curved
rpm Line
cfm
Section 4 – Centrifugal Fans
Copyright © Carrier Corp. 2005
Airfoil Wheel Design
Rotation
Characteristics:
• Blades are curved away from direction of rotation
• Static pressure up to 10 in. wg
• 8 to 18 blades
• High rpm (1500 to 3000 rpm)
Section 4 – Centrifugal Fans
Copyright © Carrier Corp. 2005
Airfoil Centrifugal Fan Characteristics
• Non-overloading
– Horsepower will peak and
begin to drop off
Static Pressure
Fan Horsepower
Typical Airfoil rpm
Line
cfm
Section 4 – Centrifugal Fans
Copyright © Carrier Corp. 2005
Plenum Fan Characteristics
Fan Wheel
Guard
Inlet Cone
Characteristics:
• Single-Width, Single-Inlet (SWSI)
• Operate at static pressures up to 10 in. wg
• Best application with limited space or
when multiple duct discharge is desired
Section 4 – Centrifugal Fans
Copyright © Carrier Corp. 2005
Plenum Fans With Cabinets
Inlet Cone SWSI Plenum Fan Wheel
Fan Cabinet
FANS IN VARIABLE
AIR VOLUME SYSTEMS
Axial Fans
Propeller
Type Impeller
• Axial Wheel
– Air discharged parallel to the shaft
– Air is often redirected via straightening
vanes making the fan a vane axial
FANS IN VARIABLE
AIR VOLUME SYSTEMS
Discharge
Damper
Remote Duct
Static Pressure SP
Sensor
Forward-Curved Fan
Backdraft
Damper
15 20
Dp Design or
rated point (RP)
Dcfm
Airflow
Section 6 – Fan Volume Control
Copyright © Carrier Corp. 2005
Riding the Fan Curve Characteristics
B 3 5 7.5
% Air flow Airflow Fan Static System Fan Static Pressure bhp*** % bhp****
(cfm) Pressure* Static minus System
Pressure** Static Pressure
100% 15,000 4.0 4.0 0 17.8 100%
90% 13,500 4.15 3.24 0.91 15.7 88%
80% 12,000 4.25 2.56 1.96 13.3 75%
70% 10,500 4.3 1.96 2.34 12.0 67%
60% 9,000 4.25 1.44 2.81 9.81 55%
50% 7,500 4.15 1.0 3.15 8.0 45%
* Fan static pressure is from the fan curve
** System static is determined using the second fan law
*** bhp is from the fan curve
**** % bhp is the percent as compared to the maximum bhp
Actuator Shaft
(actuator not
shown)
Inlet Vanes
Fan Bearing
Lube Line for
Bearing
SC
cfm (x 1000)
SC
cfm (x 1000)
USER INTERFACE
3 5
Discharge Dampers
Inlet Guide
Vanes
% Design Airflow
FANS IN VARIABLE
AIR VOLUME SYSTEMS
Fan Stability
Min. cfm =
7500 (MP)
FANS IN VARIABLE
AIR VOLUME SYSTEMS
FANS IN VARIABLE
AIR VOLUME SYSTEMS
Return
Damper
Outdoor
Damper
Return
Damper
Outdoor
Damper
Outside Reference
Pressure Sensor
Inside Space
Pressure Sensor
0.05 in. wg
Section 9 – VAV Fan Control, Tracking,
and Pressurization
Copyright © Carrier Corp. 2005
SECTION 10
FANS IN VARIABLE
AIR VOLUME SYSTEMS
Summary
Section 10 – Summary
Copyright © Carrier Corp. 2005
Work Session
Work Session
1. True or False? The drive losses in an eddy current coupling are less than that in a VFD.
____________________
3. True or False? VAV systems have the ability to track changes in building loads.
____________________
4. Which method of volume control is the most cost effective and efficient?
____________________
Work Session
Copyright © Carrier Corp. 2005
Technical Development Program
Thank You