HEATING LOAD

1. Heat Loss or Heat Gain by Thermal Transmission


∆𝒕 𝑨∆𝒕
𝑸𝟏 = ∗ = = 𝑼𝑨∆𝒕 = 𝑼𝑨(𝒕𝒐 − 𝒕𝒊 )
𝑹 𝒕𝒐𝒕 𝑹𝒕𝒐𝒕
where UA = 1⁄𝑅∗ 𝑡𝑜𝑡 , W/K
𝑅 ∗ 𝑡𝑜𝑡 = total thermal resistance, K/W
U = overall heat transfer coefficient, W/m2 ·K
A = surface area, m2
∆t = to – ti = outside-inside temperature difference

Thermal resistance of the unit area of the


k, m ·K/W R, m2 ·K/W U, W/m2 ·K
building
Exterior material
1.39 0.02085
* Stucco, 15 mm
Concrete
0.55 0.0825
* Sand and gravel aggregate, 150 mm 1
Interior material 𝑈=
1.39 0.02085 𝑅𝑡𝑜𝑡
* Plaster/cement material, 15 mm
Air resistance
* Horizontal, heat flow down (outside air film) 0.16
* Vertical, heat flow horizontal (inside air film) 0.12
Rtot 0.4042 2.474
Flat glass
5.9
* Single glass (Summer)
Roofing
0.69
* Sheet, 3mm

a. For exposed wall

Q1a = UA∆t

where U = overall heat transfer coefficient, W/m2 ·°K


A = surface area of the wall, m2
∆t = to – ti = outside-inside temperature difference

Outside air condition:


to = 32oC RH = 60%

Inside air condition:


ti = 21oC RH = 50%

Supply air codition:


ts = 36oC RH = 80%
Transmission Heat Gain for Exposed Wall (Q 1a)
Q 1a = UA∆t
Room Room Exposure U (W/m2·°K) A (m2 ) ∆t (°C) QTh (w all) Q1a / Room
First Floor (Salceda Building)
NW 2.474 18.603 11 506.262
SB 01 SW 2.474 15.963 11 434.417 1486.02
NE 2.474 20.039 11 545.341
SW 2.474 15.963 11 434.417
SB 02 979.758
NE 2.474 20.039 11 545.341
SW 2.474 15.963 11 434.417
SB 03 979.758
NE 2.474 20.039 11 545.341
SW 2.474 7.743 11 210.718
Stock Room 476.898
NE 2.474 9.781 11 266.18
NE 2.474 66.715 11 1815.58
Accreditation Room 3298.405
SW 2.474 54.488 11 1482.82
NW 2.474 15.963 11 434.417
SB 04 979.758
SE 2.474 20.039 11 545.341
NW 2.474 15.963 11 434.417
SB 05 979.758
SE 2.474 20.039 11 545.341
NW 2.474 15.963 11 434.417
SB 06 979.758
SE 2.474 20.039 11 545.341
NE 2.474 15.963 11 434.417
SB 07 979.758
SW 2.474 20.039 11 545.341
NE 2.474 15.963 11 434.417
SB 08 979.758
SW 2.474 20.039 11 545.341
NE 2.474 15.963 11 434.417
SB 09 979.758
SW 2.474 20.039 11 545.341

Office of the Education NE 2.474 7.743 11 210.718


476.898
Department

SW 2.474 9.781 11 266.18


NE 2.474 15.963 11 434.417
SB 11 979.758
SW 2.474 20.039 11 545.341
NE 2.474 15.963 11 434.417
SB 12 979.758
SW 2.474 20.039 11 545.341
NE 2.474 15.963 11 434.417
SB 13 SW 2.474 20.039 11 545.341 1486.02
NW 2.474 18.603 11 506.262
Transmission Heat Gain for Exposed Wall (Q 1a)
Q 1a = UA∆t
Room Room Exposure U (W/m2·°K) A (m2 ) ∆t (°C) QTh (w all) Q1a / Room
Second Floor (Salceda Building)
NW 2.474 18.603 11 506.262
SB 14 SW 2.474 15.963 11 434.417 1486.02
NE 2.474 20.039 11 545.341
SW 2.474 15.963 11 434.417
SB 15 979.758
NE 2.474 20.039 11 545.341
SW 2.474 15.963 11 434.417
SB 16 979.758
NE 2.474 20.039 11 545.341
SW 2.474 15.963 11 434.417
SB 17 979.758
NE 2.474 20.039 11 545.341
SW 2.474 15.963 11 434.417
SB 18 979.758
NE 2.474 20.039 11 545.341
SW 2.474 14.707 11 400.236
Office of the Librarian 877.978
NE 2.474 17.555 11 477.742
NW 2.474 48.843 11 1329.21
Campus Library 3171.03
SE 2.474 67.679 11 1841.82
NE 2.474 54.488 11 1482.82
General Reference Section 3433.277
SW 2.474 71.671 11 1950.46
NE 2.474 7.743 11 210.718
Office 476.898
SW 2.474 9.781 11 266.18
NE 2.474 15.963 11 434.417
SB 21 979.758
SW 2.474 20.039 11 545.341
SB 22 NE 2.474 15.963 11 434.417
979.758
SW 2.474 20.039 11 545.341
NE 2.474 15.963 11 434.417
SB 23 SW 2.474 20.039 11 545.341 1486.02
NW 2.474 18.603 11 506.262
SW 2.474 7.743 11 210.718
Biology Stock Room 476.898
NE 2.474 9.781 11 266.18
Center for Student Services Building
NW 2.474 23.774 11 646.986
Guidance Center SW 2.474 7.413 11 201.729 1127.95
NE 2.474 10.261 11 279.235
College Publication NE 2.474 10.62 11 289.015 289.015
NE 2.474 16.5194 11
NSTP Office
SE 2.474 9.604 11 261.361 261.361
CSC Office SE 2.474 8.083 11 219.96 219.96
NW 2.474 19.716 11 536.551
SE 2.474 19.716 11 536.551
Audio Visual Room 4003.833
SW 2.474 57.006 11 1551.36
NE 2.474 50.686 11 1379.37
NE 2.474 6.791 11 184.808
SE 2.474 2.601 11 70.792
Guard House 648.376
SW 2.474 9.217 11 250.84
NW 2.474 5.216 11 141.937
NE 2.474 40.002 11 1088.61
SE 2.474 17.173 11 467.357
Canteen 3458.976
SW 2.474 40.002 11 1088.61
NW 2.474 29.926 11 814.401

b. For exposed roof

Q1b = UA∆t

where U = overall heat transfer coefficient, W/m2 ·°K


A = surface area of the roof, m2
∆t = to – ti = outside-inside temperature difference

Outside air condition:


to = 32oC RH = 60%

Inside air condition:


ti = 21oC RH = 50%

Supply air codition:


ts = 36oC RH = 80%
Transmission Heat Gain for Exposed Roof (Q1b)
Q1b= UA∆t
∆t
Room A (m2) U (W/m2·°K) Q1b / Room
(°C)
First Floor (Salceda Building)
SB 01 - -
SB 02 - -
SB 03 - -
Stock Room - -
Accredtitation Room - -
SB 04 - -
SB 05 - -
SB 06 - -
SB 07 - -
SB 08 - -
SB 09 - -
Office of the Education Department - -
SB 11 - -
SB 12 - -
SB 13 - -
Second Floor (Salceda Building)
SB 14 51.45 0.69 11 390.506
SB 15 51.45 0.69 11 390.506
SB 16 51.45 0.69 11 390.506
SB 17 51.45 0.69 11 390.506
SB 18 51.45 0.69 11 390.506
Office of the Librarian 39.87 0.69 11 302.613
Campus Library 154.35 0.69 11 1171.517
General Reference Section 155.28 0.69 11 1178.575
Office 24.54 0.69 11 186.259
SB 21 51.45 0.69 11 390.506
SB 22 51.45 0.69 11 390.506
SB 23 51.45 0.69 11 390.506
Biology Stock Room 24.54 0.69 11 186.259
Center for Student Services Building
Guidance Center 34.58 0.69 11 262.4622
College Publication Office 22.84 0.69 11 173.3556
NSTP Office 26.28 0.69 11 199.4652
CSC Office 23.54 0.69 11 178.6686

Audio Visual Room 154.06 0.69 11 1169.3154


Guard House 18.98 0.69 11 144.0582
Canteen 230.84 0.69 11 1752.0756
c. Sensible Heat Gain for Window Glass

Q1c = UA∆t

where U = overall heat transfer coefficient, W/m2 ·°K


A = surface area of the window, m2
∆t = to – ti = outside-inside temperature difference

Outside air condition:


to = 32oC RH = 60%

Inside air condition:


ti = 21oC RH = 50%

Supply air codition:


ts = 36oC RH = 80%
Sensible Heat Gain For Window Glass (Q1c)
Q1c= UA∆t
Window Net Window ∆t
Room Awindow(m2) U (W/m2·K) Q1c
Exposure Area (°C)
First Floor (Salceda Building)
SW 1.62
SB 01 10.62 5.9 11 689.238
NE 9.00
SW 1.62
SB 02 10.62 5.9 11 689.238
NE 9.00
SW 1.62
SB 03 10.62 5.9 11 689.238
NE 9.00
SW 0.81
Stock Room 5.31 5.9 11 344.619
NE 4.50
NE 4.86
Accreditation Room 31.86 5.9 11 2067.714
SW 27.00
NW 9.00
SB 04 10.62 5.9 11 689.238
SE 1.62
NW 9.00
SB 05 10.62 5.9 11 689.238
SE 1.62
NW 9.00
SB 06 10.62 5.9 11 689.238
SE 1.62
NE 9.00
SB 07 10.62 5.9 11 689.238
SW 1.62
NE 9.00
SB 08 10.62 5.9 11 689.238
SW 1.62
NE 9.00
SB 09 10.62 5.9 11 689.238
SW 1.62
Office of the Education NE 0.60
4.979 5.9 11 323.137
Department SW 4.38
SB 11 NE 8.76 9.958 5.9 11 646.274
SW 1.20
NE 8.76
SB 12 9.958 5.9 11 646.274
SW 1.20
NE 8.76
SB 13 9.958 5.9 11 646.274
SW 1.20
Second Floor (Salceda Building)
NE 1.62
SB 14 10.62 5.9 11 689.238
SW 9.00
NE 1.62
SB 15 10.62 5.9 11 689.238
SW 9.00
NE 1.62
SB 16 10.62 5.9 11 689.238
SW 9.00
NE 1.62
SB 17 10.62 5.9 11 689.238
SW 9.00
NE 1.62
SB 18 10.62 5.9 11 689.238
SW 9.00
SW 4.50
Office of the Librarian 5.31 5.9 11 344.619
NE 0.81
NW 27.00
Campus Library 31.86 5.9 11 2067.714
SE 4.86
NE 27.00
General Reference Section 31.86 5.9 11 2067.714
SW 4.86
NE 4.50
Office 5.31 5.9 11 344.619
SW 0.81
NE 9.00
SB 21 10.62 5.9 11 689.238
SW 1.62
NE 9.00
SB 22 10.62 5.9 11 689.238
SW 1.62
NE 9.00
SB 23 10.62 5.9 11 689.238
SW 1.62
NE 4.50
Biology Stock Room 5.31 5.9 11 344.619
SW 0.81
Center for Student Services Building
Guidance Center SW 4.50 4.50 5.9 11 292.050
College Publication Office NE 4.50 4.50 5.9 11 292.050
NSTP Office SE 1.80 1.80 5.9 11 116.820
CSC Office SE 1.80 1.80 5.9 11 116.820

SW 12.00
Audio Visual Room 18 5.9 11 1168.200
NE 6.00
NE 0.99
Guard House SE 0.96 2.1763 5.9 11 141.242
SW 0.22
NE 10.88
Canteen SE 10.88 32.6346 5.9 11 2117.986
SW 10.88
Heat Gain Thru Thermal Transmission (Q1)
Q1 /
Room Q1a Q1b Q1c
Room
First Floor (Salceda Building)
SB 01 1486.020 - 689.238 2175.26
SB 02 979.758 - 689.238 1669.00
SB 03 979.758 - 689.238 1669.00
Stock Room 476.898 - 344.619 821.52
Accreditation Room 3298.405 - 2067.714 5366.12
SB 04 979.758 - 689.238 1669.00
SB 05 979.758 - 689.238 1669.00
SB 06 979.758 - 689.238 1669.00
SB 07 979.758 - 689.238 1669.00
SB 08 979.758 - 689.238 1669.00
SB 09 979.758 - 689.238 1669.00
Office of the Education Department 476.898 - 323.1371 800.04
SB 11 979.758 - 646.2742 1626.03
SB 12 979.758 - 646.2742 1626.03
SB 13 1486.020 - 646.2742 2132.29
Second Floor (Salceda Building)
SB 14 1486.020 390.506 689.238 2565.76
SB 15 979.758 390.506 689.238 2059.50
SB 16 979.758 390.506 689.238 2059.50
SB 17 979.758 390.506 689.238 2059.50
SB 18 979.758 390.506 689.238 2059.50
Office of the Librarian 877.978 302.613 344.619 1525.21
Campus Library 3171.030 1171.517 2067.714 6410.26
General Reference Section 3433.277 1178.575 2067.714 6679.57
Office 476.898 186.259 344.619 1007.78
SB 21 979.758 390.506 689.238 2059.50
SB 22 979.758 390.506 689.238 2059.50
SB 23 1486.020 390.506 689.238 2565.76
Biology Stock Room 476.898 186.259 344.619 1007.78
Center for Student Services Building
Guidance Center 1133.735 262.462 292.050 1688.25
College Publication Office 292.823 173.356 292.050 758.23
NSTP Office 294.455 199.465 116.820 610.74
CSC Office 252.818 178.669 116.820 548.31

Audi Visual Room 4003.833 1169.315 1168.200 6341.35


Guard House 648.376 144.058 141.242 933.68
Canteen 3458.976 1752.076 2117.986 7329.04
2. Sensible heat due to Infiltration

Q2 = 1.23Ṿ∆t

where Ṿ = volumetric flow rate of outside air = (Height)(Area)(Nc), L/s


𝑎𝑖𝑟 𝑐ℎ𝑎𝑛𝑔𝑒𝑠⁄ ℎ𝑜𝑢𝑟⁄ 1000𝐿⁄ ) = 𝐿⁄
Ṿ = (𝑚)(𝑚2 ) ( ℎ𝑜𝑢𝑟) ( 3600𝑠) ( 𝑠
𝑚3
∆t = to – ti = outside-inside temperature difference
Nc = number of air changes = a + bv + c∆t, air changes per hour
where v is wind velocity, use 3.3 m/s and a, b, and c are typical values
presented in Table 4-5 (Stoecker & Jones p. 70)
Quality of Construction a b c
Average 0.20 0.015 0.014

Outside air condition:


to = 32oC RH = 60%

Inside air condition:


ti = 21oC RH = 50%

Supply air codition:


ts = 36oC RH = 80%
Sensible Heat due to Infiltration (Q2)
Q2 = 1.23 Nc Ṿ (to-tI)
ROOM Height (m) Area (m2) Δt (°C) a b c v Nc Ṿ Q2
First Floor (Salceda Building)
SB 01 3.18 45.92 11 0.2 0.015 0.014 3.33 0.40395 16.3853 221.6930
SB 02 3.18 45.92 11 0.2 0.015 0.014 3.33 0.40395 16.3853 221.6930
SB 03 3.18 45.92 11 0.2 0.015 0.014 3.33 0.40395 16.3853 221.6930
Stock Room 3.18 22.52 11 0.2 0.015 0.014 3.33 0.40395 8.03564 108.7222
Accreditation Room 3.18 91.89 11 0.2 0.015 0.014 3.33 0.40395 32.7884 443.6273
SB 04 3.18 45.92 11 0.2 0.015 0.014 3.33 0.40395 16.3853 221.6930
SB 05 3.18 45.92 11 0.2 0.015 0.014 3.33 0.40395 16.3853 221.6930
SB 06 3.18 45.92 11 0.2 0.015 0.014 3.33 0.40395 16.3853 221.6930
SB 07 3.18 45.92 11 0.2 0.015 0.014 3.33 0.40395 16.3853 221.6930
SB 08 3.18 45.92 11 0.2 0.015 0.014 3.33 0.40395 16.3853 221.6930
SB 09 3.18 45.92 11 0.2 0.015 0.014 3.33 0.40395 16.3853 221.6930

Office of the Education Department 3.18 45.92 11 0.2 0.015 0.014 3.33 0.40395 16.3853 221.6930
SB 11 3.18 45.92 11 0.2 0.015 0.014 3.33 0.40395 16.3853 221.6930
SB 12 3.18 69.326 11 0.2 0.015 0.014 3.33 0.40395 24.7371 334.6926
SB 13 3.18 92.726 11 0.2 0.015 0.014 3.33 0.40395 33.0867 447.6634
Second Floor (Salceda Building)
SB 14 3.18 45.92 11 0.2 0.015 0.014 3.33 0.40395 16.3853 221.6930
SB 15 3.18 45.92 11 0.2 0.015 0.014 3.33 0.40395 16.3853 221.6930
SB 16 3.18 45.92 11 0.2 0.015 0.014 3.33 0.40395 16.3853 221.6930
SB 17 3.18 45.92 11 0.2 0.015 0.014 3.33 0.40395 16.3853 221.6930
SB 18 3.18 45.92 11 0.2 0.015 0.014 3.33 0.40395 16.3853 221.6930
Office of the Librarian 3.18 35.33 11 0.2 0.015 0.014 3.33 0.40395 12.6065 170.5665
Campus Library 3.18 139.52 11 0.2 0.015 0.014 3.33 0.40395 49.7839 673.5758
General Reference Section 3.18 149.91 11 0.2 0.015 0.014 3.33 0.40395 53.4913 723.7368
Office 3.18 22.52 11 0.2 0.015 0.014 3.33 0.40395 8.03564 108.7222
SB 21 3.18 45.92 11 0.2 0.015 0.014 3.33 0.40395 16.3853 221.6930
SB 22 3.18 45.92 11 0.2 0.015 0.014 3.33 0.40395 16.3853 221.6930
SB 23 3.18 45.92 11 0.2 0.015 0.014 3.33 0.40395 16.3853 221.6930
Biology Stock Room 3.18 22.52 11 0.2 0.015 0.014 3.33 0.40395 8.03564 108.7222
Center for Student Services Building
Guidance Center 3.12 29.11 11 0.2 0.015 0.014 3.33 0.40395 10.1911 137.8859
College Publication Office 3.12 17.61 11 0.2 0.015 0.014 3.33 0.40395 6.16508 83.4136
NSTP Office 3.12 21.3 11 0.2 0.015 0.014 3.33 0.40395 7.45692 100.8921
CSC Office 3.12 18.45 11 0.2 0.015 0.014 3.33 0.40395 6.45916 87.3924

Audio Visual Room 3.18 134.54 11 0.2 0.015 0.014 3.33 0.40395 48.0069 649.5333
Guard House 2.21 10.0772 11 0.2 0.015 0.014 3.33 0.40395 2.49895 33.8108
Canteen 3.18 160 11 0.2 0.015 0.014 3.33 0.40395 57.0916 772.4493
3. Latent heat due to Infiltration

Q3 = 3000NcṾ(Wo-Wi)

where Ṿ = volumetric flow rate of outside air = (Height)(Area)(Nc), L/s


𝑎𝑖𝑟 𝑐ℎ𝑎𝑛𝑔𝑒𝑠⁄ ℎ𝑜𝑢𝑟⁄ 1000𝐿⁄ ) = 𝐿⁄
Ṿ = (𝑚)(𝑚2 ) ( ℎ𝑜𝑢𝑟) ( 3600𝑠) ( 𝑠
𝑚3
Wo; W i = humidity ratio outside and inside, kgwater to kgair
Nc = number of air changes = a + bv + c∆t, air changes per hour
where v is wind velocity, use 3.3 m/s and a, b, and c are typical values
presented in Table 4-5 (Stoecker & Jones p. 70)

Quality of Construction a b C
Average 0.20 0.015 0.014

Outside air condition:


to = 32oC RH = 60%
using psychrometric chart, we get W o = 0.0193 kgwater / kgair

Inside air condition:


ti = 21oC RH = 50%
using psychrometric chart, we get W i = 0.0083 kgwater / kgair

Supply air codition:


ts = 36oC RH = 80%
using psychrometric chart, we get W s = 0.0308 kgwater / kgair
Latent Heat Load due to Infiltration (Q3)
Q3 = 3000 Nc Ṿ (Wo-Wi)
Height Area
ROOM Wo Wi ΔW a b c v Nc Ṿ Q3
(m) (m2)
First Floor (Salceda Building)
SB 1 3.18 45.92 0.0193 0.0083 0.011 0.2 0.015 0.014 3.33 0.40395 16.3853 540.7145
SB 2 3.18 45.92 0.0193 0.0083 0.011 0.2 0.015 0.014 3.33 0.40395 16.3853 540.7145
SB 3 3.18 45.92 0.0193 0.0083 0.011 0.2 0.015 0.014 3.33 0.40395 16.3853 540.7145
Stock Room 3.18 22.52 0.0193 0.0083 0.011 0.2 0.015 0.014 3.33 0.40395 8.03564 265.1762
Accreditation Room 3.18 91.89 0.0193 0.0083 0.011 0.2 0.015 0.014 3.33 0.40395 32.7884 1082.0178
SB 04 3.18 45.92 0.0193 0.0083 0.011 0.2 0.015 0.014 3.33 0.40395 16.3853 540.7145
SB 05 3.18 45.92 0.0193 0.0083 0.011 0.2 0.015 0.014 3.33 0.40395 16.3853 540.7145
SB 06 3.18 45.92 0.0193 0.0083 0.011 0.2 0.015 0.014 3.33 0.40395 16.3853 540.7145
SB 07 3.18 45.92 0.0193 0.0083 0.011 0.2 0.015 0.014 3.33 0.40395 16.3853 540.7145
SB 08 3.18 45.92 0.0193 0.0083 0.011 0.2 0.015 0.014 3.33 0.40395 16.3853 540.7145
SB 09 3.18 45.92 0.0193 0.0083 0.011 0.2 0.015 0.014 3.33 0.40395 16.3853 540.7145
Office of Education
3.18 45.92 0.0193 0.0083 0.011 0.2 0.015 0.014 3.33 0.40395 16.3853 540.7145
Department
SB 11 3.18 45.92 0.0193 0.0083 0.011 0.2 0.015 0.014 3.33 0.40395 16.3853 540.7145
SB 12 3.18 69.326 0.0193 0.0083 0.011 0.2 0.015 0.014 3.33 0.40395 24.7371 816.3235
SB 13 3.18 92.726 0.0193 0.0083 0.011 0.2 0.015 0.014 3.33 0.40395 33.0867 1091.8619
Second Floor (Salceda Building)
SB 14 3.18 45.92 0.0193 0.0083 0.011 0.2 0.015 0.014 3.33 0.40395 16.3853 540.7145
SB 15 3.18 45.92 0.0193 0.0083 0.011 0.2 0.015 0.014 3.33 0.40395 16.3853 540.7145
SB 16 3.18 45.92 0.0193 0.0083 0.011 0.2 0.015 0.014 3.33 0.40395 16.3853 540.7145
SB 17 3.18 45.92 0.0193 0.0083 0.011 0.2 0.015 0.014 3.33 0.40395 16.3853 540.7145
SB 18 3.18 45.92 0.0193 0.0083 0.011 0.2 0.015 0.014 3.33 0.40395 16.3853 540.7145
Office of the Librarian 3.18 35.33 0.0193 0.0083 0.011 0.2 0.015 0.014 3.33 0.40395 12.6065 416.0158
Campus Library 3.18 139.52 0.0193 0.0083 0.011 0.2 0.015 0.014 3.33 0.40395 49.7839 1642.8679
General Reference
3.18 149.91 0.0193 0.0083 0.011 0.2 0.015 0.014 3.33 0.40395 53.4913 1765.2116
Section
Office 3.18 22.52 0.0193 0.0083 0.011 0.2 0.015 0.014 3.33 0.40395 8.03564 265.1762
SB 21 3.18 45.92 0.0193 0.0083 0.011 0.2 0.015 0.014 3.33 0.40395 16.3853 540.7145
SB 22 3.18 45.92 0.0193 0.0083 0.011 0.2 0.015 0.014 3.33 0.40395 16.3853 540.7145
SB 23 3.18 45.92 0.0193 0.0083 0.011 0.2 0.015 0.014 3.33 0.40395 16.3853 540.7145
Biology Stock Room 3.18 22.52 0.0193 0.0083 0.011 0.2 0.015 0.014 3.33 0.40395 8.03564 265.1762
Center for Student Services Building
Guidance Center 3.12 29.11 0.0158 0.01 0.0058 0.2 0.015 0.014 3.33 0.40395 10.1911 177.3255
College Publication
3.12 17.61 0.0158 0.01 0.0058 0.2 0.015 0.014 3.33 0.40395 6.16508 107.2725
Office
NSTP Office 3.12 21.3 0.0158 0.01 0.0058 0.2 0.015 0.014 3.33 0.40395 7.45692 129.7504
CSC Office 3.12 18.45 0.0158 0.01 0.0058 0.2 0.015 0.014 3.33 0.40395 6.45916 112.3894

Audio Visual Room 3.18 134.54 0.0193 0.0083 0.011 0.2 0.015 0.014 3.33 0.40395 48.0069 1584.2277
Guard House 2.21 10.0772 0.0193 0.0083 0.011 0.2 0.015 0.014 3.33 0.40395 2.49895 82.4653
Canteen 3.18 160 0.0193 0.0083 0.011 0.2 0.015 0.014 3.33 0.40395 57.0916 1884.0228
COOLING LOADS

4. Internal Heat Gain from Lamps

Q4 = (QTY) (LR) (Fu) (Fb) (CLF)

where LR = lamp rating, in watts


Fu = utilization factor or fraction installed lamps in use 1.0
Fb = ballast factor, for fluorescent lamps use 1.2, for CFL & LED bulb, use 1.0
CLF = cooling load factor from Table 4-6 (Stoecker & Jones p. 72)
Number of hours after lights are turned on = 9
Fixture Y, 10 hours of operation = 0.96 (CLF)
* For heat-producing equipment it is also necessary to estimate the power used along with the
period and/or frequency of use in a manner similar to that used for lighting. For equipment having little
radiant-energy transmission, the CLF can be assumed equal to 1.0.
Internal Heat Gain from Lamps Additional Heat Gain Q4 /Room

QL = QTY*(Lamp Rating, W)*Fu*Fb*CLF QL(Additional) = 0.20*QTY*Wattage Q4 = QL +


Room
QTY W Fu Fb CLF QL Equipment QTY Wattage QL(Additional) QL(Additional)
First Floor (Salceda Building)
SB 1 8 40 1 1.2 0.96 46.08 Emergency Light 1 3 0.6 46.68
SB 2 8 40 1 1.2 0.96 46.08 Emergency Light 1 3 0.6 46.68
SB 3 8 40 1 1.2 0.96 46.08 Emergency Light 1 3 0.6 46.68
EPSON Printer 1 6 1.2
Stock Room 3 9 1 1 0.96 25.92 147.12
Water Dispenser 1 600 120
Emergency Light 1 3 0.6
4 9 1 1 0.96 34.56
Sound System 1 500 100
Accreditation Room 329.56
Projector 1 180 36
4 10 1 1.2 0.96 38.4
Water dispenser 1 600 120
SB 4 8 9 1 1 0.96 69.12 Emergency Light 1 3 0.6 69.72
SB 5 8 9 1 1 0.96 69.12 Emergency Light 1 3 0.6 69.72
SB 6 8 9 1 1 0.96 69.12 Emergency Light 1 3 0.6 69.72
SB 7 8 7 1 1 0.96 53.76 Emergency Light 1 3 0.6 54.36
SB 8 8 7 1 1 0.96 53.76 Emergency Light 1 3 0.6 54.36
SB 9 8 7 1 1 0.96 53.76 Emergency Light 1 3 0.6 54.36
Emergency Light 1 3 0.6 420.58
WiFi Modem 2 11 4.4
2 9 1 1 0.96 17.28
PC Desktop 2 250 100
Office of the Education CCTV Cameras 2 60 24
Department Water Dispenser 1 600 120 419.98
21" LG TV 1 91.5 18.3
1 5 1 1 0.96 4.8
EPSON Printer 1 6 1.2
Photocopy Machine 1 650 130
SB 11 8 7 1 1 0.96 53.76 Emergency Light 1 3 0.6 54.36
SB 12 8 7 1 1 0.96 53.76 Emergency Light 1 3 0.6 54.36
SB 13 8 7 1 1 0.96 53.76 Emergency Light 1 3 0.6 54.36
Second Floor (Salceda Building)
SB 14 9 9 1 1 0.96 77.76 Emergency Light 1 3 0.6 78.36
SB 15 9 9 1 1 0.96 77.76 Emergency Light 1 3 0.6 78.36
SB 16 9 9 1 1 0.96 77.76 Emergency Light 1 3 0.6 78.36
SB 17 6 40 1 1.2 0.96 276.48 Emergency Light 1 3 0.6 277.08
SB 18 6 40 1 1.2 0.96 276.48 Emergency Light 1 3 0.6 277.08
Office of the Librarian 4 40 1 1.2 0.96 184.32 Emergency Light 1 3 0.6 184.92
CCTV Cameras 4 60 48
Campus Library 24 40 1 1.2 0.96 1105.92 1156.12
WiFi Modem 1 11 2.2
General Reference
24 40 1 1.2 0.96 1105.92 Emergency Light 3 3 1.8 1107.72
Section
Office 3 9 1 1 0.96 25.92 Emergency Light 1 3 0.6 26.52
SB 21 9 9 1 1 0.96 77.76 Emergency Light 1 3 0.6 78.36
SB 22 9 9 1 1 0.96 77.76 Emergency Light 1 3 0.6 78.36
SB 23 9 9 1 1 0.96 77.76 Emergency Light 1 3 0.6 78.36
EPSON Printer 1 6 1.2
Biology Stock Room 3 9 1 1 0.96 25.92 147.12
Water Dispenser 1 600 120
Center for Student Services Building
Sound System 1 245 49
1 9 1 1 0.96 8.64
EPSON Printer 1 6 1.2
Guidance Center 157.60
LG Television 1 28 5.6
2 40 1 1.2 0.96 92.16
Radio 1 5 1
College Publication Office 2 40 1 1.2 0.96 92.16 EPSON Printer 1 6 1.2 93.36
NSTP Office 2 40 1 1.2 0.96 92.16 Emergency Light 1 3 0.6 92.76
Emergency Light 1 3 0.6
CSC Office 2 40 1 1.2 0.96 92.16 EPSON Printer 1 6 1.2 213.96
Water Dispenser 1 600 120
Sound System 1 245 49
Audio Visual Room 20 9 1 1 0.96 172.8 Projector 1 180 36 297.80
Computer Set 1 200 40
2 12 1 1.2 0.96 27.648 Water Dispenser 1 600 120
1 9 1 1.2 0.96 10.368 Radio 1 5 1
Guard House 859.09
2 40 1 1.2 0.96 92.16 Electric Heater 1 3000 600
1 6 1 1.2 0.96 6.912 LED Clock 1 5 1
Freezer 1 300 60
Canteen 12 9 1 1.2 0.96 124.416 Water Dispenser 2 500 200 404.42
TV 1 100 20
5. Occupant Sensible Cooling Load

Q5 = (G/P)S(NP)(CLF)

where (G/P)S = gain per person W, sensible Table 4-7 (Stoecker & Jones p. 73)
= Heat gain per person + sensible heat gain (%)
Np = number of occupants
CLF = sensible-heat cooling load factor for people in Table 4-9
(Stoecker & Jones p. 74)

Building Hours after Total Hours in Space


each entry 6 8 12
into space CLF
Room 08 00 0.84
Office 07 00 0.82
Canteen 07 00 0.82
Audio Visual
09 00 0.21
Room
Guard House 05 00 0.79
Stock Room 08 00 0.26
Library 08 00 0.84
Occupant Sensible Cooling Load (Q5)
Q5 = (G/P)s*Np*CLFp
Room (G/P)S Np (CLF)p Q5/Room
First Floor (Salceda Building)
SB 1 160 55 0.84 7392.00
SB 2 160 55 0.84 7392.00
SB 3 160 55 0.84 7392.00
Stock Room 160 3 0.26 124.80
Accreditation Room 160 50 0.21 1680.00
SB 4 160 44 0.84 5913.60
SB 5 160 44 0.84 5913.60
SB 6 160 44 0.84 5913.60
SB 7 160 44 0.84 5913.60
SB 8 160 44 0.84 5913.60
SB 9 160 44 0.84 5913.60
Office of the Education Department 232.5 10 0.82 1906.50
SB 11 160 55 0.84 7392.00
SB 12 160 55 0.84 7392.00
SB 13 160 55 0.84 7392.00
Second Floor (Salceda Building)
SB 14 160 44 0.84 5913.60
SB 15 160 44 0.84 5913.60
SB 16 160 44 0.84 5913.60
SB 17 160 44 0.84 5913.60
SB 18 160 44 0.84 5913.60
Office of the Librarian 232.5 2 0.82 381.30
Campus Library 160 110 0.84 14784.00
General Reference Section 160 88 0.84 11827.20
Office 232.5 5 0.82 953.25
SB 21 160 44 0.84 5913.60
SB 22 160 44 0.84 5913.60
SB 23 160 44 0.84 5913.60
Biology Stock Room 160 5 0.26 41.60
Center for Student Services Building
Guidance Center 232.5 9 0.82 1715.85
College publication Office 232.5 11 0.82 2097.15
NSTP Office 232.5 8 0.82 1525.20
CSC Office 232.5 11 0.82 2097.15

Audio Visual Room 160 220 0.21 7392.00


Guard House 160 5 0.79 632.00
Canteen 160 110 0.82 14432.00
6. Occupant Latent Cooling Load

Q6 = (G/P)L(Np)(CLF)

where (G/P)L = gain per person W, latent Table 4-7 (Stoecker & Jones p. 73)
Np = number of occupants
CLF = latent-heat cooling load factor is 1.0
Occupant Latent Cooling Load (Q6)
Q6 = (G/P)L*Np
ROOM (G/P)L Np (CLF)p Q6/Room
First Floor (Salceda Building)
SB 1 100 55 1 5500.00
SB 2 100 55 1 5500.00
SB 3 100 55 1 5500.00
Stock Room 100 3 1 300.00
Accreditation Room 100 50 1 5000.00
SB 4 100 44 1 4400.00
SB 5 100 44 1 4400.00
SB 6 100 44 1 4400.00
SB 7 100 44 1 4400.00
SB 8 100 44 1 4400.00
SB 9 100 44 1 4400.00
Office of the Education Department 233.5 10 1 2335.00
SB 11 100 55 1 5500.00
SB 12 100 55 1 5500.00
SB 13 100 55 1 5500.00
Second Floor (Salceda Building)
SB 14 100 44 1 4400.00
SB 15 100 44 1 4400.00
SB 16 100 44 1 4400.00
SB 17 100 44 1 4400.00
SB 18 100 44 1 4400.00
Office of the Librarian 150 2 1 300.00
Campus Library 100 110 1 11000.00
General Reference Section 100 88 1 8800.00
Office 150 5 1 750.00
SB 21 100 44 1 4400.00
SB 22 100 44 1 4400.00
SB 23 100 44 1 4400.00
Biology Stock Room 100 5 1 500.00
Center for Student Services Building
Guidance Center 150 9 1 1350.00
College Publication Office 150 11 1 1650.00
NSTP Office 150 8 1 1200.00
CSC Office 150 11 1 1650.00

Audio Visual Room 100 220 1 22000.00


Guard House 100 5 1 500.00
Canteen 100 110 1 11000.00
7. Solar loads through transparent surfaces

Q7 = (SHGFmax)(SC)(A)(CLF)

where A = area exposed, m2


SHGFmax = solar-heat gain factor for sunlit glass (maximum value), Table 4-10
(Stoecker & Jones p. 75)
CLF = cooling load factor, Table 4-12 (Stoecker & Jones p. 77)
SC = shading coefficient Table 4-11 (Stoecker & Jones p. 76)

Maximum solar-heat gain factor for sunlit glass

32o North Latitude


Months NE/NW SE/SW
April, August 450 580

Shading coefficient

Shading coefficient
Type of Glass Thickness, mm No indoor Venetian Blinds Roller shades
shading Light Light
Single glass,
3 1.00 0.55 0.25
regular sheet

Peak solar loading on an east-facing room occurs at 10:00 A.M. (1000H) while for a west-
facing room the maximum solar loading occurs at 2:00 P.M. (1400H).
Cooling-load factor for glass with interior shading, north latitude

Solar time, Window facing


H NE NW SW SE
1000 0.37 0.79
1400 0.30 0.17
Solar Load Calculation Thru Transparent Surfaces (Q7)
Q7 = (SHGFmax)(SC)(A)(CLF)
Q7/
Room Window Facing SHGFmax(W/m2) SC Awindow(m2) CLF Qsg
room
First Floor (Salceda Building)
SW 450 1 1.62 - 729.00
SB 1 5949.00
NE 580 1 9.00 - 5220.00
SW 450 1 1.62 - 729.00
SB 2 5949.00
NE 580 1 9.00 - 5220.00
SW 450 1 1.62 - 729.00
SB 3 5949.00
NE 580 1 9.00 - 5220.00
SW 450 1 0.81 - 364.50
Stock Room 2974.50
NE 580 1 4.50 - 2610.00
NE 450 0.25 4.86 0.37 202.30
Accreditation Room 3138.55
SW 580 0.25 27.00 0.75 2936.25
NW 450 1 9.00 - 4050.00
SB 4 4989.60
SE 580 1 1.62 - 939.60
NW 450 1 9.00 - 4050.00
SB 5 4779.00
SE 450 1 1.62 - 729.00
NW 580 1 9.00 - 5220.00
SB 6 5949.00
SE 450 1 1.62 - 729.00
NE 580 1 9.00 - 5220.00
SB 7 5949.00
SW 450 1 1.62 - 729.00
NE 450 1 9.00 - 4050.00
SB 8 4989.60
SW 580 1 1.62 - 939.60
NE 580 1 9.00 - 5220.00
SB 9 5949.00
SW 450 1 1.62 - 729.00
Office of the Education NE 450 0.25 0.60 0.37 24.93
501.26
Department SW 580 0.25 4.38 0.75 476.33
SB 11 NE 450 1 8.76 - 3942.00 4636.84
SW 580 1 1.20 - 694.84
NE 450 1 8.76 - 3942.00
SB 12 4636.84
SW 580 1 1.20 - 694.84
NE 450 1 8.76 - 3942.00
SB 13 4636.84
SW 580 1 1.20 - 694.84
Second Floor (Salceda Building)
NE 450 1 1.62 - 729.00
SB 14 5949.00
SW 580 1 9.00 - 5220.00
NE 450 1 1.62 - 729.00
SB 15 5949.00
SW 580 1 9.00 - 5220.00
NE 450 1 1.62 - 729.00
SB 16 5949.00
SW 580 1 9.00 - 5220.00
NE 450 1 1.62 - 729.00
SB 17 5949.00
SW 580 1 9.00 - 5220.00
NE 450 1 1.62 - 729.00
SB 18 5949.00
SW 580 1 9.00 - 5220.00
SW 580 0.25 4.50 0.75 489.38 387.73
Office of the Librarian
NE 450 0.25 0.81 0.37 33.72
NW 450 0.25 27.00 0.30 911.25
Campus Library 1467.96
SE 580 0.25 4.86 0.79 556.71
NE 450 0.25 27.00 0.37 1123.88
General Reference Section 1652.40
SW 580 0.25 4.86 0.75 528.53
NE 450 0.25 4.50 0.37 187.31
Office 539.66
SW 580 1 0.81 0.75 352.35
NE 450 1 9.00 - 4050.00
SB 21 4989.60
SW 580 1 1.62 - 939.60
NE 450 1 9.00 - 4050.00
SB 22 4989.60
SW 580 1 1.62 - 939.60
NE 450 1 9.00 - 4050.00
SB 23 4989.60
SW 580 1 1.62 - 939.60
NE 450 1 4.50 - 2025.00
Biology Stock Room 2535.30
SW 630 1 0.81 - 510.30
Center for Student Services Building
Guidance Center SW 450 0.55 4.37 0.19 205.50 198.65
College Publication Office NE 450 0.55 4.37 0.37 400.18 386.84
NSTP Office SE 450 0.55 0.6 0.79 117.32 113.40
CSC Office SE 450 0.55 0.6 0.79 117.32 113.40

NE 450 0.55 6 0.37 549.45


Audio Visual Room 1339.47
SW 630 0.55 12 0.19 790.02
NE 450 0.55 0.9942 0.37 91.04
SE 630 0.55 0.9627 0.79 263.52
Guard House 411.59
NW 450 0.55 0 0.30 0.00
SW 630 0.55 0.2194 0.75 57.02
NE 450 0.55 10.8782 0.37 996.17
SE 630 0.55 10.8782 0.79 2977.74
Canteen 6800.89
SW 630 0.55 10.8782 0.75 2826.97
NW 450 0.55 0 0.30 0.00
8. Solar Heat Gain for Roof

Q8 = UA(CLTD)

where U = overall heat transfer coefficient, W/m2 ·°K


A = surface area of the roof, m2
CLTD = cooling-load temperature difference for flat roofs, Table 4-14
(Stoecker & Jones p. 81)

Cooling-load temperature difference for flat roof

Roof type Solar time (1200H)


Roofs without suspended ceilings
1 (Steel sheet with 25mm to 50 mm 40
insulation) Roofs with suspended ceilings
35
Peak solar loading on flat roofs occurs at 12:00 NN (1200H).
Solar Heat Gain for Roof (Q8)
Q8 = UA(CLTD)
Aroof,
ROOM U (W/m2·K) CLTD Q8/Room
m2
First Floor (Salceda Building)
SB 1 0.69 -
SB 2 0.69 -
SB 3 0.69 -
Stock room 0.69 -
Accreditation Room 0.69 -
SB 4 0.69 -
SB 5 0.69 -
SB 6 0.69 -
SB 7 0.69 -
SB 8 0.69 -
SB 9 0.69 -
Office of the Education Department 0.69 -
SB 11 0.69 -
SB 12 0.69 -
SB 13 0.69 -
Second Floor (Salceda Building)
SB 14 0.69 51.45 35 1242.52
SB 15 0.69 51.45 35 1242.52
SB 16 0.69 51.45 35 1242.52
SB 17 0.69 51.45 35 1242.52
SB 18 0.69 51.45 35 1242.52
Office of the Librarian 0.69 39.87 28 770.29
Campus Library 0.69 154.35 35 3727.55
General Reference Section 0.69 155.28 28 3000.01
Office 0.69 24.54 28 474.11
SB 21 0.69 51.45 35 1242.52
SB 22 0.69 51.45 35 1242.52
SB 23 0.69 51.45 35 1242.52
Biology Stock Room 0.69 24.54 35 592.64
Center for Student Services Building
Guidance Center 0.69 34.58 34 811.25
College Publication Office 0.69 22.84 34 535.83
NSTP Office 0.69 26.28 34 616.53
CSC Office 0.69 23.54 34 552.25
Audio Visual Room 0.69 154.06 35 3720.55
Guard House 0.69 18.98 28 366.69
Canteen 0.69 230.84 28 4459.83
9. Solar Heat Gain for Opaque Wall

Q9 = UA(CLTD)

where U = overall heat transfer coefficient, W/m2 ·°K


A = surface area of the wall, m2
CLTD = cooling-load temperature difference for sunlit walls, Table 4-15
(Stoecker & Jones p. 82-83)

Cooling-load temperature difference for sunlit wall

Solar Orientation
Wall type
time, H NE NW SE SW
C (200-mm 1000 7 7
concrete with
interior and
1400 6 7
exterior finish)
Peak solar loading on an east-facing room occurs at 10:00 A.M. (1000H) while for a west-facing
room the maximum solar loading occurs at 2:00 P.M. (1400H).
Solar Heat Gain for Opaque Wall (Q9)
Q9 = UA(CLTD)
Room Room Exposure U (W/m2- °K) A (m2) CLTD Q Q9/Room
First Floor (Salceda Building)
NW 2.474 18.603 6 276.143
SB 1 SW 2.474 15.963 7 276.447 899.63
NE 2.474 20.039 7 347.035
SW 2.474 15.963 7 276.447
SB 2 623.48
NE 2.474 20.039 7 347.035
SW 2.474 15.963 7 276.447
SB 3 623.48
NE 2.474 20.039 7 347.035
SW 2.474 7.743 7 134.093
Stock Room 303.48
NE 2.474 9.781 7 169.387
NE 2.474 66.715 7 1155.370
Accreditation Room 2098.98
SW 2.474 54.488 7 943.615
NW 2.474 15.963 6 236.955
SB 4 583.99
SE 2.474 20.039 7 347.035
NW 2.474 15.963 6 236.955
SB 5 583.99
SE 2.474 20.039 7 347.035
NW 2.474 15.963 6 236.955
SB 6 583.99
SE 2.474 20.039 7 347.035
NE 2.474 15.963 7 276.447
SB 7 623.48
SW 2.474 20.039 7 347.035
NE 2.474 15.963 7 276.447
SB 8 623.48
SW 2.474 20.039 7 347.035
NE 2.474 15.963 7 276.447
SB 9 623.48
SW 2.474 20.039 7 347.035
Office of the Education NE 2.474 7.743 7 134.093
303.48
Department SW 2.474 9.781 7 169.387
SB 11 NE 2.474 15.963 7 276.447 623.48
SW 2.474 20.039 7 347.035
NE 2.474 15.963 7 276.447
SB 12 623.48
SW 2.474 20.039 7 347.035
NE 2.474 15.963 7 276.447
SB 13 SW 2.474 20.039 7 347.035 899.63
NW 2.474 18.603 6 276.143
Second Floor (Salceda Building)
NW 2.474 18.603 6 276.143
SB 14 SW 2.474 15.963 7 276.447 899.63
NE 2.474 20.039 7 347.035
SW 2.474 15.963 7 276.447
SB 15 623.48
NE 2.474 20.039 7 347.035
SW 2.474 15.963 7 276.447
SB 16 623.48
NE 2.474 20.039 7 347.035
SW 2.474 15.963 7 276.447
SB 17 623.48
NE 2.474 20.039 7 347.035
SW 2.474 15.963 7 276.447
SB 18 623.48
NE 2.474 20.039 7 347.035
SW 2.474 14.707 7 254.696
Office of the Librarian 558.71
NE 2.474 17.555 7 304.017
NW 2.474 48.843 6 725.025
Campus Library 1897.09
SE 2.474 67.679 7 1172.065
NE 2.474 54.488 7 943.615
General Reference Section 2184.81
SW 2.474 71.671 7 1241.198
NE 2.474 7.743 7 134.093
Office 303.48
SW 2.474 9.781 7 169.387
NE 2.474 15.963 7 276.447
SB 21 623.48
SW 2.474 20.039 7 347.035
NE 2.474 15.963 7 276.447
SB 22 623.48
SW 2.474 20.039 7 347.035
NE 2.474 15.963 7 276.447
SB 23 SW 2.474 20.039 7 347.035 552.59
NW 2.474 18.603 6 276.143
SW 2.474 7.743 7 134.093
Biology Stock Room 303.48
NE 2.474 9.781 7 169.387
Center for Student Services Building
NW 2.474 23.774 6 352.901
Guidance Center SW 2.474 7.413 7 128.373 658.97
NE 2.474 10.261 7 177.695
College Publication Office NE 2.474 10.620 7 183.919 183.92
NE 2.474 16.519 7 286.083
NSTP Office 452.40
SE 2.474 9.604 7 166.320
CSC Office SE 2.474 8.083 7 139.974 139.97

NW 2.474 19.716 6 292.664


SE 2.474 19.716 7 341.442
Audio Visual Room 2499.12
SW 2.474 57.006 7 987.230
NE 2.474 50.686 7 877.780
NE 2.474 6.791 7 117.605
SE 2.474 2.601 7 45.049
Guard House 399.70
SW 2.474 9.217 7 159.625
NW 2.474 5.216 6 77.420
NE 2.474 40.002 7 692.751
SE 2.474 17.173 7 297.409
Canteen 2127.13
SW 2.474 40.002 7 692.751
NW 2.474 29.926 6 444.219
Cooling and Heating Loads
Heating Loads Qheat, Cooling Loads Qcooling, Qtotal
Building Room
Q1 Q2 Q3 W Q4 Q5 Q6 Q7 Q8 Q9 W (kW)
SB 1 2175.26 221.6930 540.7145 2937.67 46.68 7392.00 5500.00 5949.00 - 899.63 19787.3 22.72
SB 2 1669.00 221.6930 540.7145 2431.40 46.68 7392.00 5500.00 5949.00 - 623.48 19511.2 21.94
SB 3 1669.00 221.6930 540.7145 2431.40 46.68 7392.00 5500.00 5949.00 - 623.48 19511.2 21.94
Stock Room 821.52 108.7222 265.1762 1195.42 147.12 124.80 300.00 2974.50 - 303.48 3849.9 5.05
Accreditation
5366.12 443.6273 1082.0178 6891.76 329.56 1680.00 5000.00 3138.55 - 2098.98 12247.1 19.14
Room
SB 4 1669.00 221.6930 540.7145 2431.40 69.72 5913.60 4400.00 4989.60 - 583.99 15956.9 18.39
SB 5 1669.00 221.6930 540.7145 2431.40 69.72 5913.60 4400.00 4779.00 - 583.99 15746.3 18.18
Salceda SB 6 1669.00 221.6930 540.7145 2431.40 69.72 5913.60 4400.00 5949.00 - 583.99 16916.3 19.35
Building
SB 7 1669.00 221.6930 540.7145 2431.40 54.36 5913.60 4400.00 5949.00 - 623.48 16940.4 19.37
First Floor
SB 8 1669.00 221.6930 540.7145 2431.40 54.36 5913.60 4400.00 4989.60 - 623.48 15981 18.41
SB 9 1669.00 221.6930 540.7145 2431.40 54.36 5913.60 4400.00 5949.00 - 623.48 16940.4 19.37
Office of the
Education 800.04 221.6930 540.7145 1562.44 420.58 1906.50 2335.00 501.26 - 303.48 5466.82 7.03
Department
SB 11 1626.03 221.6930 540.7145 2388.44 54.36 7392.00 5500.00 4636.84 - 623.48 18206.7 20.60
SB 12 1626.03 334.6926 816.3235 2777.05 54.36 7392.00 5500.00 4636.84 - 623.48 18206.7 20.98
SB 13 2132.29 447.6634 1091.8619 3671.82 54.36 7392.00 5500.00 4636.84 - 899.63 18482.8 22.15
SB 14 2565.76 221.6930 540.7145 3328.17 78.36 5913.60 4400.00 5949.00 1242.52 899.63 18483.1 21.81
SB 15 2059.50 221.6930 540.7145 2821.91 78.36 5913.60 4400.00 5949.00 1242.52 623.48 18207 21.03
SB 16 2059.50 221.6930 540.7145 2821.91 78.36 5913.60 4400.00 5949.00 1242.52 623.48 18207 21.03
Salceda
Building SB 17 2059.50 221.6930 540.7145 2821.91 277.08 5913.60 4400.00 5949.00 1242.52 623.48 18405.7 21.23
Second SB 18 2059.50 221.6930 540.7145 2821.91 277.08 5913.60 4400.00 5949.00 1242.52 623.48 18405.7 21.23
Floor Office of the
1525.21 170.5665 416.0158 2111.79 184.92 381.30 300.00 387.73 962.86 558.71 2775.52 4.89
Librarian
Campus
6410.26 673.5758 1642.8679 8726.70 1156.12 14784.00 11000.00 1467.96 3727.55 1897.09 34032.7 42.76
Library
General
Reference 6679.57 723.7368 1765.2116 9168.51 1107.72 11827.20 8800.00 1652.40 3750.01 2184.81 29322.1 38.49
Section
Office 1007.78 108.7222 265.1762 1381.67 26.52 953.25 750.00 539.66 592.64 303.48 3165.55 4.55
SB 21 2059.50 221.6930 540.7145 2821.91 78.36 5913.60 4400.00 4989.60 1242.52 623.48 17247.6 20.07
SB 22 2059.50 221.6930 540.7145 2821.91 78.36 5913.60 4400.00 4989.60 1242.52 623.48 17247.6 20.07
SB 23 2565.76 221.6930 540.7145 3328.17 78.36 5913.60 4400.00 4989.60 1242.52 552.59 17176.7 20.50
Biology
1007.78 108.7222 265.1762 1381.67 147.12 41.60 500.00 2535.30 592.64 303.48 4120.14 5.50
Stock Room
Guidance
1688.25 137.8859 177.3255 2003.46 157.6 1715.85 1350.00 198.65 954.41 658.97 5035.48 7.04
Center
Center For College
Student Publication 758.23 83.4136 107.2725 948.91 93.36 2097.15 1650.00 386.84 630.38 183.92 5041.66 5.99
Services Office
Building NSTP Office 610.74 100.8921 129.7504 841.38 92.76 1525.20 1200.00 113.40 725.33 452.40 4109.1 4.95
CSC Office 548.31 87.3924 112.3894 748.09 213.96 2097.15 1650.00 113.40 649.70 139.97 4864.19 5.61
Audio Visual
6341.35 649.5333 1584.2277 8575.11 297.8 7392.00 22000.00 1339.47 3720.55 2499.12 37248.9 45.82
Room
Guard
933.68 33.8108 82.4653 1049.95 859.088 632.00 500.00 411.59 458.37 399.70 3260.74 4.31
House
Canteen 7329.04 772.4493 1884.0228 9985.51 404.416 14432.00 11000.00 6800.89 5574.79 2127.13 40339.2 50.32
Operational or Power, Phase, Frequency,
Building Room Installed Ventilation Units QTY
Under-Repair W Φ Hz

SB 01 Orbit Fan Operational 2 100 1 60


SB 02 Orbit Fan Operational 2 100 1 60
SB 03 Orbit Fan Operational 2 100 1 60
Stock Room Orbit Fan Operational 2 100 1 60
Male Comfort Room Ceiling mounted exhaust fan 8" Operational 1 26 1 60
Female Comfort Room Ceiling mounted exhaust fan 8" Operational 1 26 1 60
Orbit Fan Operational 1 100 1 60
Accreditation Room
Split-type AC unit Operational 1 4175 1 60
Comfort Room Ceiling mounted exhaust fan 8" Operational 1 26 1 60
SB 04 Orbit Fan Operational 2 100 1 60
SB 05 Orbit Fan Operational 2 100 1 60
Salceda SB 06 Orbit Fan Operational 2 100 1 60
Building First
Floor SB 07 Orbit Fan Operational 2 100 1 60
SB 08 Orbit Fan Operational 2 100 1 60
SB 09 Orbit Fan Operational 2 100 1 60
Male Comfort Room Ceiling mounted exhaust fan 8" Operational 1 26 1 60
Female Comfort Room Ceiling mounted exhaust fan 8" Operational 1 26 1 60
Stand Fan Operational 1 75 1 60
Office of the Education Orbit Fan Operational 1 100 1 60
Department Wall Fan Operational 1 50 1 60
Split-type AC unit Under-Repair 1 4175 1 60
SB 11 Orbit Fan Operational 2 100 1 60
SB 12 Orbit Fan Operational 2 100 1 60
SB 13 Orbit Fan Operational 2 100 1 60
SB 14 Orbit Fan Operational 2 100 1 60
Salceda SB 15 Orbit Fan Operational 2 100 1 60
Building
Second Floor SB 16 Orbit Fan Operational 2 100 1 60
Female Comfort Room Ceiling mounted exhaust fan 8" Operational 1 26 1 60
Male Comfort Room Ceiling mounted exhaust fan 8" Operational 1 26 1 60
SB 17 Orbit Fan Operational 2 100 1 60
SB 18 Orbit Fan Operational 2 100 1 60
Office of the Librarian Stand Fan Operational 1 62 1 60
Comfort Room Ceiling mounted exhaust fan 8" Operational 1 26 1 60
Orbit Fan Operational 4 100 1 60
Campus Library Stand Fan Operational 1 62 1 60
Exhaust Fan Operational 3 70 1 60
General Reference Orbit Fan Operational 4 100 1 60
Section Electric Fan Operational 8 75 1 60
Comfort Room Ceiling mounted exhaust fan 8" Operational 1 26 1 60
Office Orbit Fan Operational 1 100 1 60
SB 21 Orbit Fan Operational 2 100 1 60
SB 22 Orbit Fan Operational 2 100 1 60
SB 23 Orbit Fan Operational 2 100 1 60
Biology Stock Room Orbit Fan Operational 2 100 1 60
Female Comfort Room Exhaust window
Male Comfort Room Exhaust window
Open Lounge Wall Fan Operational 1 50 1 60
Window-type AC unit Operational 1 745.7 1 60
Center For Heavy-duty Stand Fan Operational 1 295 1 60
Student Guidance Center
Wall Fan Operational 1 50 1 60
Services
Building Box Fan Operational 1 100 1 60
College Publication Office Stand Fan Operational 1 62 1 60
NSTP Office Window-type AC unit Operational 1 745.7 1 60
Stand Fan Operational 1 62 1 60
CSC Office
Wall Fan Operational 1 55 1 60
Female Comfort Room Exhaust window
Audio Visual Male Comfort Room Exhaust window
Room Split-type AC unit Operational 1 4175 1 60
Floor Area
Orbit Fan Operational 4 100 1 60
Comfort Room Exhaust window 1
Guard House
Floor Area Orbit Fan Operational 1 100 1 60
Floor Area Orbit Fan Operational 4 100 1 60
Canteen
Comfort Room Exhaust window