Académique Documents
Professionnel Documents
Culture Documents
UNIT 11
ELECTRIC MOTOR
CONTROLLER (PART II)
OBJECTIVES
GENERAL OBJECTIVE
SPECIFIC OBJECTIVES
INPUT
Emmm….. What is a
PROTECTION????
An over current is a current greater than the rated current of the circuit it may occur in
two ways:
(a) as an overloads current
(b) as a short circuit or fault current
Because of these, each motor must have an over load and short circuit protections.
Overload Protection
Figure 11.1: A typical across the line starter for an induction motor
(Source: Electrical Machinery Fundamentals (3rd edition) Stephen J. Chapman)
Over load protection for the motor is provided by devices labeled OL in the Figure 11.1.
These overload protection devices consist of two parts, an overload heater element and
overload contacts.
Under normal conditions, overload contacts are shut. However when the temperature of
the heater elements rises far enough, the OL contacts open, deenergizing the M relay,
which in turn opens normally open M contacts and removes power from motor.
ELECTRICAL MACHINERY & CONTROL E3106/11/4
ACTIVITY 11 A
11.1 Define the protection in electrical by using the words given below.
FEEDBACK TO ACTIVITY 11 A
11.1 to be protected against mechanical damage, the effects of the environment and
electrical over currents, to be installed in such a fashion that person and/or
livestock are protected from the dangers that such an electrical installation may
create.
11.2
ELECTRICAL MACHINERY & CONTROL E3106/11/7
INPUT
Notice from the Figure 11.1 that the control power for the M relay comes from directly
across the line to the motor. If the voltage applied to the motor falls too much, the voltage
applied to the M relay will also fall and the relay de-energized. The M contacts then
open, removing power from the motor terminals.
ELECTRICAL MACHINERY & CONTROL E3106/11/8
ACTIVITY 11 B
11.3 Based on the circuit given, explain the operation of the circuit.
11.4 What is the device used to protect the system from under voltage fault.
ELECTRICAL MACHINERY & CONTROL E3106/11/9
FEEDBACK TO ACTIVITY 11 B
11.3 When the start button is pushed, the coil becomes energized and its normally open
(N/O) contacts close. When the start button is released the coil remains energized
via its own N/O contacts. These are known as the hold-on contacts. The coil can
be only de-energized by opening the circuit by the used of the stop button or by a
considerable reduction or loss of voltage. When this happens, the N/O contacts
open, and even if the voltage is restored or the circuit is made complete again, the
coil will remain de-energized until the start button is pushed again.
11.4 isolator
ELECTRICAL MACHINERY & CONTROL E3106/11/10
INPUT
2. Every method of over current protection should be based on the prospective short
circuit current.
operates must not exceed 1.45 times the lowest current carrying capacity of any
circuit conductor.
6. Effective and accessible means of isolation must be provided at the origin of the
installation to cut off all voltage as may be necessary to prevent danger.
ACTIVITY 11 C
11.6 What must you do if you want to make installation to two or more detached
buildings?
ELECTRICAL MACHINERY & CONTROL E3106/11/13
FEEDBACK TO ACTIVITY 11 C
11.6 when installation serves two or more detached buildings (i.e house detached
garage) means of isolation must be provided in each building
ELECTRICAL MACHINERY & CONTROL E3106/11/14
SELF-ASSESMENT
You are approaching success. TRY all the questions ini this self-assessment section and
check your answers with those given in the feedback on Self-Assessment given on the
next page.
If you face any problem,
discuss it with your
lecturer
Question 11-1
Question 11-2
Question 11-3
A. If you are an electrical contractor, what must you know about the IEE rules if you
want in installing the power system.
ELECTRICAL MACHINERY & CONTROL E3106/11/15
FEEDBACK TO SELF-ASSESMENT
Question 11-1
Refer from the note 11.1
Question 11-2
Refer from the note 11.2
Question 11-3
Refer from the note 11.3