Features: Applications:
* Linear output * Hydrogen and combustible gas leak
* Long life detectors for fuel cells
* Small sensitivity to alcohol
* Sensitive to hydrogen, methane, and
LP gas
The TGS6812-D00 catalytic type gas sensor can detect levels of hydrogen
up to 100%LEL. This sensor features high accuracy, good durability and
stability, quick response, and linear output. This sensor can detect not only
hydrogen, but also methane and LP gas, thus making it an excellent solution
for monitoring gas leakage from staionary fuel cell systems which transform
combustible gases into hydrogen.
As the sensor possesses an adsorbent inside its sensor cap, its cross sensitivity
to organic vapors is small. In addition, TGS6812-D00 is durable against silicone
compounds in harsh environments.
The figure below represents typical sensitivity characteristics, The figure below represents typical temperature dependency
all data having been gathered at standard test conditions (see characteristics at 65%RH. Again, Y-axis is indicated as sensor
reverse side of this sheet). The Y-axis is indicated as sensor output sensitivity -- ∆Vout (mV):
output sensitivity -- ∆Vout (mV): ∆Vout = Vout in gas - Vout in air at 20˚C
∆Vout = Vout in gas - Vout in air
30
H2
60
Methane
20
20
0
Ethanol at 65% RH
Air
0 -10
0 5000 10000 15000 20000 25000 -20 0 20 40 60 80
IMPORTANT NOTE: OPERATING CONDITIONS IN WHICH FIGARO SENSORS ARE USED WILL VARY WITH EACH CUSTOMER’S SPECIFIC APPLICATIONS. FIGARO STRONGLY REC-
OMMENDS CONSULTING OUR TECHNICAL STAFF BEFORE DEPLOYING FIGARO SENSORS IN YOUR APPLICATION AND, IN PARTICULAR, WHEN CUSTOMER’S TARGET GASES
ARE NOT LISTED HEREIN. FIGARO CANNOT ASSUME ANY RESPONSIBILITY FOR ANY USE OF ITS SENSORS IN A PRODUCT OR APPLICATION FOR WHICH SENSOR HAS NOT
BEEN SPECIFICALLY TESTED BY FIGARO.
VH(3.0V) Typical values:
R1 = 1.2kΩ
Basic Measuring Circuit: R2 = 1.2kΩ
VR = 100Ω
4
not sensitive to combustible gases. resistance of this element will increase.
3 Vout
These elements are installed into a This results in an “out-of-balance” signal
“Wheastone Bridge”. A variable resistor across the bridge and a corresponding D R2
2
should be adjusted so that the bridge will change in output voltage which can be
produce a stable baseline signal when measured.
in an environmnet free of combustible GND
Standard circuit
Operating voltage 3.0±0.1V AC/DC
conditions Compensator side
Hydrogen/methane/iso-butane in air
Test gas conditions
at 20±2˚C, 65±5%RH Detector side
Standard test
Circuit conditions 3.0±0.05V AC/DC 2 3
conditions
Conditioning period 4.6±0.1
-10˚C~+70˚C, ≤95%RH
Operating conditions (w/o dew condensation) 3.6±0.1
Compensator side u/m = mm
-10˚C~+80˚C, ≤95%RH <Pin connection>
Storage conditions (w/o dew condensation)
1-4 : Compensator
2-3 : Detector
REV: 10/14