Vitodens 300
Type WB3A, 49 and 66 kW
Gas fired wall mounted condensing boiler
natural gas and LPG version
VITODENS 300
Safety instructions
prevention of accidents,
! Important information
This symbol warns against the
risk of material losses and
& the TRGI, TRF and special regula-
Work on gas equipment must only be & Close the gas shut-off valve.
carried out by a registered gas fitter. & Remove all personnel from
than those designated on the type tions of your local gas sup-
plate. That contractor will then plier which can be found on
arrange for the relevant approval in the gas meter.
that country. & Notify your heating contrac-
Electrical work must only be carried tor from outside the building.
out by a qualified electrician.
The system must be commissioned by
the system installer or a qualified per-
5692 550 GB
Index
Coding
Code 1........................................................................................................ 38
Code 2........................................................................................................ 42
Resetting the coding to the delivered condition ........................................... 62
Service scans
Service level summary ................................................................................ 63
Temperatures, boiler coding card and brief scans ....................................... 64
Checking outputs (relay test) ...................................................................... 68
Scanning operating conditions and sensors ................................................ 70
Troubleshooting
Calling up fault code history ........................................................................ 73
Call up current fault codes .......................................................................... 73
Checking and acknowledging faults ............................................................ 75
Repairs ...................................................................................................... 85
Function description
Constant temperature control units ............................................................. 95
Weather-compensated control units ............................................................ 96
Extensions for external connections (accessory) ......................................... 98
Control functions ........................................................................................ 102
Designs
Connection and wiring diagrams – internal connections .............................. 107
Connection and wiring diagrams – external connections .............................. 109
Certificates
Declaration of conformity ............................................................................ 125
Manufacturer's certificate according to the 1st BImSchV [Germany]............. 126
5692 550 GB
Commissioning steps
Inspection steps
Maintenance steps Page
! ! !
• 1. Filling the heating system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
• 2. Venting the boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
• 3. Venting the heating system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
• 4. Filling the siphon with water . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
• 5. Checking the electrical mains connection
• 6. Language selection (if required) - only for the
weather-compensated control units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
• • 7. Setting the time and date (if required) - only for
weather-compensated control units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
• • 8. Checking the gas type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
• 9. Changing the gas type (see separate installation
instructions)
• • • 10. Function sequence and possible faults . . . . . . . . . . . . . . . . . . . . . . . 10
• • • 11. Checking static and supply pressure ........................... 12
• • • 12. Checking the CO 2 settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
• 13. Setting the max. output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
• • • 14. Checking all connections on the primary and DHW
side for leaks
• • • 15. Checking the burner (recording values on
page 118 of commissioning report)
• 16. Checking the balanced flue system for soundness
(annular gap check) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
• • 17. Removing the burner and checking the burner
gasket (replace gasket every two years) . . . . . . . . . . . . . . . . . . . . . . 18
• • 18. Checking the burner gauze assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
• • 19. Checking and adjusting the ignition and ionisation
5692 550 GB
electrodes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
3.
! Important information
Unsuitable fill water
increases the level of depos-
its and corrosion and may
lead to boiler damage.
& Thoroughly flush the entire
ble quality.
& Soften fill water harder
1. Close the gas shut-off valve and 2. Activate the venting program via
start the control unit. coding address 2F:1.
Note
To call up code 1 and for setting the
coding address, see page 38.
For function and sequence of the
venting program, see page 103.
Setting the time and date (if required) - only for weather-com-
pensated control units
Note
During commissioning, or after prolonged time out of use, it may be necessary
to set the time and date.
! Important information
The natural gas version cannot be
converted to LPG.
1. Enquire about the gas type and 3. If these details do not match the
Wobbe index (Wo) from your local fuel provided, the burner must be
mains gas or LPG supplier. converted according to the details
provided by the mains gas or the
Note LPG supplier.
In the delivered condition, Vito-
dens 300 is set up for natural gas E See separate conversion kit
or LPG P. installation instructions.
Natural gas E version:
The boiler can be operated in the After conversion from
Wobbe index range 12.0 to & Natural gas E or LPG P to nat-
2. Compare the gas category (gas The boiler can be operated in the
type) and gas group with the details Wobbe index range 12.0 to
on the label on the gas train and 16.1 kWh/m 3 (43.2 to 58.0 MJ/
the cap plate. m 3).
Note
To call up code 1 and for setting the
coding address, see page 38.
10
Yes
Yes
Yes
Yes
Yes
5692 550 GB
11
Yes
Danger
Higher CO emissions can lead to poisoning.
Measure the CO value before and after any work on gas equipment to
prevent any health hazards and to ensure the perfect operational condi-
tion of the system.
12
5. Start up boiler.
Note
During commissioning, the boiler
can enter a fault state because of
airlocks in the gas pipe. After
approx. 5 seconds, press E to
reset the burner.
Note
Use suitable test equipment with a
resolution of at least 0.1 mbar to
measure the supply pressure.
13
Danger
Gas escaping from the test
nipple leads to a risk of
explosion.
Check test nipple A for
soundness.
Vitodens 300 is factory-set for natural gas E or LPG P. The natural gas E version
can be converted to natural gas LL using a conversion kit. The LPG P version
can be converted to natural gas E or LL using a conversion kit.
During commissioning or maintenance, check the CO 2 level at the boiler adap-
tor.
Note
The MatriX burner for Vitodens 300 is preset for the entire gas group. Therefore,
5692 550 GB
14
Compare the actual CO 2 value with the above CO 2 value ranges for the indivi-
dual gas groups (check the gas group with your mains gas or LPG supplier).
If the actual CO 2 value deviates by more than 1 % for natural gas or 0.5 % for
LPG, proceed as follows:
& Check whether the correct gas restrictor has been installed.
& Check the balanced flue system for soundness, see page 17.
Weather-compensated control
units:
& Press both keys 9 and d simul-
"Basic load".
15
2.
Weather-compensated control
units:
& With a/b in the display, select
"Full load".
Note
The max. output can be limited for heating operation. You can limit the output
via the modulation range.
2. Press both K and F simulta- 5. Record the settings for max. output
neously until 100 flashes on the on the additional type plate
display, (equals 100 % of the rated included with the technical docu-
output) and A appears. On mentation. Affix the type plate next
weather-compensated control to the original type plate on top of
units, the display additionally the boiler.
shows "Max. output".
Note
3. With a/b select the required The output can also be limited for
5692 550 GB
value in % of rated output as max. DHW loading. For this, change coding
output. address 6F in code 2.
16
17
! Important information
Prevent damage to the wire
mesh.
Never rest the burner on the
gauze assembly.
18
1. Remove electrodes A.
Note
Torque: 4.5 Nm
19
1. Check the electrodes for wear and 3. Check all clearances. If the gaps
contamination. are not as specified or the electro-
des are damaged, replace and
2. Clean the electrodes with a small align the electrodes together with
brush (not with a wire brush) or new gaskets. Tighten the electrode
emery paper. fixing screws with 2 Nm.
! Important information
Wire mesh
do not damage.
5692 550 GB
20
! Important information
Scratches on parts which
are in contact with flue
gases can lead to corrosion.
Only use plastic brushes and
NOT wire brushes.
Apply a solvent-/potassium-free
cleaning agent if residues remain:
& Remove soot deposits with alka-
discolouration (yellow-brown)
with slightly acidic, chloride-free
cleaning agents based on phos-
phoric acid (e.g. Antox 75 E).
& Thoroughly flush with water.
Note
Fauch 600 and Antox 75 E are sup-
plied by:
Hebro Chemie GmbH
Rostocker Straße 40
D 41199 Mönchengladbach
c: Intec Bassersdorf AG
Grindelstrasse 12
Postfach
CH-8303 Bassersdorf
21
Danger
Escaping gas leads to a risk
of explosion.
Check all fittings for sound-
ness.
Danger
Escaping gas leads to a risk of
explosion.
Check gas equipment for
soundness.
5692 550 GB
22
2.
Weather-compensated control
units:
& Press K and d simultaneously
"Full load".
Note
The minimum ionisation current
should be at least 5 µA as soon as
the flame is established (approx. 2 -
3 seconds after opening the gas
train).
A Adaptor line (available as acces-
sory) 3. If the ionisation current is < 5 µA\;
B Control unit cable & Check the electrode gap, see
page 19.
& Check the control unit power sup-
ply.
23
Note
The control unit must be matched to the system equipment. Various system
components are automatically recognised by the control unit, and codes are
automatically set.
& For selection of an appropriate design, see the following diagrams.
System design 1
24
System design 2
With/without DHW heating with 1 heating circuit with mixer and system
separation
25
System design 3
With/without DHW heating with low loss header, 1 heating circuit without
mixer and 1 heating circuit with mixer
26
27
System design 4
With/without DHW heating with 3 or more heating circuits with mixer and
low loss header
28
29
System design 5
30
Note
Codes for multi-boiler system, see
Vitotronic 333 installation and operat-
ing instructions.
Installation instructions
LON communication module
Note
Data transfer via the LON system can take 2 to 3 minutes.
Adjust the user number via coding In a LON system, the same number
address 77 (see below). cannot be allocated twice.
Only possible, if all users are connected, and the control unit is encoded as fault
manager (code 79:1).
31
& The LON user number must be encoded in all control units (see page 31).
& The fault manager user list must be up to date (see page 31).
5692 550 GB
*1 In each heating system, only one Vitotronic may be encoded as fault manager.
32
is no communication between
both devices. Check LON con-
nection.
The heating curves illustrate the rela- Settings in the delivered condition:
tionship between the outside tem- & Slope = 1.4
33
34
35
The system installer must hand the operating instructions to the system user
and instruct them in the operation of the system.
36
The red fault indicator flashes when the limits set via coding address 21 and 23
have been reached. As regards the operating interface display:
& For constant temperature control units, the hours run (subject to setting) or
Note
Set code 24:1 and then code 24:0, if maintenance is implemented before main-
tenance is displayed; the set maintenance parameters for hours run and interval
are then reset to 0.
37
Code 1
Call up code 1
5692 550 GB
38
Code 1 (cont.)
Summary
Codes
Code 1 (cont.)
Note
Allocate each number
only once.
DHW priority A1
A2:2 DHW cylinder priority A2:0 Without cylinder priority
applicable to heating for heating circuit pump
circuit pump and mixer
DHW priority M2
A2:2 DHW cylinder priority A2:0 Without DHW cylinder
applicable to heating priority applicable to
circuit pump and mixer heating circuit pump and
mixer
A2:1 DHW cylinder priority
only applicable to mixer
A2:3 Modulating DHW cylinder
to priority
A2:15
Summer econ. A1
5692 550 GB
Code 1 (cont.)
Code 2
Calling up code 2
Overall summary
The coding addresses are grouped in accordance with the following function
ranges. The respective function range is displayed.
Scroll through the ranges in the following sequence with a or b.
Note
Codes, which are not relevant because of the equipment level of your heating
system or because of settings of other codes, will not be displayed.
For heating systems with 1 heating circuit without mixer and 1 heating circuit
with mixer, initially the possible coding addresses A0 to F7 are scrolled for the
heating circuit without mixer A1, then those for the heating circuit with mixer M2.
5692 550 GB
42
Code 2 (cont.)
Codes
coding card
*1 Only for constant temperature control units.
43
Code 2 (cont.)
Code 2 (cont.)
45
Code 2 (cont.)
Code 2 (cont.)
47
Code 2 (cont.)
Code 2 (cont.)
to set value 2
*1 Only for constant temperature control units.
*2 Only for weather-compensated control units.
49
Code 2 (cont.)
Note
Allocate each number
only once.
ing, as option
*1 Only for weather-compensated control units.
*2 Only for constant temperature control units.
50
Code 2 (cont.)
Code 2 (cont.)
Code 2 (cont.)
Note
When selecting a value
below 1 °C there will be
a risk of pipes outside
the thermal insulation
envelope of the house
freezing-up. The
standby mode, in parti-
cular, should be
observed, e.g. during
holidays.
5692 550 GB
Code 2 (cont.)
Note
When selecting a value
below 1 °C there will be a
risk of pipes outside the
thermal insulation envel-
ope of the house freez-
ing-up. The standby
mode, in particular,
should be observed, e.g.
during holidays.
5692 550 GB
Code 2 (cont.)
Code 2 (cont.)
control mode
or
& after cylinder loading
(for 20 min.)
or
& if there is a risk of frost.
5692 550 GB
Code 2 (cont.)
*1 Only
for weather-compensated control units.
*2 Changethe coding for the heating circuit without mixer A1 or for mixer circuit M2, if the
remote control unit affects that heating circuit.
57
Code 2 (cont.)
*1 Only
for weather-compensated control units.
*2 Change the coding for the heating circuit without mixer A1 or for mixer circuit M2, if the
remote control unit affects that heating circuit.
58
Code 2 (cont.)
Code 2 (cont.)
Note
Observe the screed dry-
ing supplier's instruc-
tions.
achieved
& Operating condition
Code 2 (cont.)
*3 Inheating program rw, the party mode ends automatically when changing over to
operation with standard room temperature.
*4 Only for constant temperature control units.
61
Code 2 (cont.)
5692 550 GB
63
The following values can be scanned, subject to the actual equipment level:
to
Brief scan 8
5692 550 GB
64
Display screen
Brief
scan
control-
ler
65
Display screen
Brief
scan
66
Display screen
Brief scan
67
Display screen
Brief scan
d Variable Software
speed version
pump Variable
0: excl. speed pump
1: Wilo
2: Grund-
fos
Subject to the actual equipment level, the following relay outputs can be con-
trolled:
Display Description
Basic load Burner modulation lower output
Full load Burner modulation upper output
Heating valve Diverter valve set to heating mode
Valve central pos. Changeover valve in central position (fill)
DHW valve Diverter valve set to DHW mode
Int. pump ON Int. pump/output 20 ON
Close mixer Mixer extension
Open mixer Mixer extension
Heating circ. pump M2 ON Mixer extension
Output int. Internal extension
Heating circ. pump A1 ON Ext. extension
Cylinder loading pump ON Ext. extension
5692 550 GB
68
Display Description
Solar pump ON Vitosolic
Subject to the actual equipment level, the following relay outputs can be con-
trolled:
Display Description
1 Burner modulation lower output
2 Burner modulation upper output
3 Diverter valve set to heating mode
4 Valve in central position
5 Valve set to DHW mode
6 Internal pump/output 20 ON
10 Output sK internal extension
11 Heating circuit pump A1 external extension
12 Cylinder loading pump external extension
13 DHW circulation pump external extension
14 Central fault external extension
5692 550 GB
69
*1 Resethours run and burner starts after maintenance has been completed. You can reset
the hours run to 0 by pressing e.
70
1. Press c. 3. Press c.
5692 550 GB
72
The most recent 10 faults are saved and may be called up.
3. Press d.
73
3. Acknowledge fault.
3. Acknowledge fault.
74
weather-compensated control
units)
C Fault number
D Fault code
75
Note
The fault can be acknowledged
with d. The fault message in the dis-
play will be hidden, but the red fault
indicator U continues to flash. A new
fault message will be displayed if an
Constant temperature control units acknowledged fault is not removed by
the following morning.
perature sensor
lead break
76
9b X X Sensor S3 lead
break
77
78
DIP switch
settings
79
circuit M2
80
81
82
83
84
Repairs
85
Repairs (cont.)
5692 550 GB
86
Repairs (cont.)
87
Repairs (cont.)
Danger
The boiler temperature sen-
sor is immersed in the heat-
ing water (risk of scalding).
Drain the boiler before repla-
cing the sensor.
The flue gas temperature sensor locks out the boiler when the permissible flue
gas temperature is exceeded. The lockout can be reset no sooner than after 20
minutes by pressing reset E.
Note
The equipment will also be locked out again for 20 minutes if the mains power
supply is switched OFF. 5692 550 GB
88
Repairs (cont.)
89
Repairs (cont.)
thermocouple A.
& Check the continuity of the thermo-
Check the sensor in case of fault messages concerning the differential pressure
sensor:
& Correct installation
90
Repairs (cont.)
91
Repairs (cont.)
92
Repairs (cont.)
Note
A Rotational direction switch The flow temperature sensor must
B ON/OFF switch 8 now sense a higher temperature. If
the temperature falls, either the
motor is turning in the wrong direc-
tion or the mixer set is incorrectly
fitted.
93
Repairs (cont.)
Vitotronic 050 is connected with the control unit via the LON system. To test the
connection, implement a user check on the boiler control unit (see page 32).
5692 550 GB
94
Confirmation/acknowledgement
95
5692 550 GB
96
97
Internal extension H1
The internal extension is integrated & Central fault message (code 53:0)
into the control unit housing. As alter- & Cylinder loading pump (code 53:3)
native, the following functions can be & DHW circulation pump (code 53:1)
connected to relay output sK. The & Heating circuit pump for heating cir-
98
Internal extension H2
The internal extension is integrated & Central fault message (code 53:0)
into the control unit housing. As alter- & Cylinder loading pump (code 53:3)
native, the following functions can be & DHW circulation pump (code 53:1)
connected to relay output sK. The & Heating circuit pump for heating cir-
99
External extension H1
100
External extension H2
101
Control functions
102
External blocking
External demand
The "External demand" function is In coding address 9b, you can select
connected via the external extension the minimum set boiler water tem-
input "aVD". perature in case of external demand.
In coding address 34 you can select
the influence the signal "Ext. demand"
should have on the connected circula-
tion pumps.
Venting program
Filling program
Note
Close the gas shut-off valve when
operating the filling program.
5692 550 GB
103
Screed function
104
105
5692 550 GB
106
107
5692 550 GB
108
109
5692 550 GB
110
Parts lists
006 Burner (with item 007, 009 to 044 Pressure gauge and fem. con-
019, 021, 022, 023 and 046) nection
007 Burner gauze assembly 046 Differential pressure sensor
008 Electronic box – radial fan 047 Grommet
009 Radial fan 048 Safety springs
012 Gas pipe (incl. gaskets) 049 Thermocouple
013 Conversion kit for natural gas E 050 Temperature sensor
(gas restrictor) 052 Expansion vessel connection
014 Conversion kit for natural gas LL 054 Locking bracket
(gas restrictor) 055 Gravity brake
015 Conversion kit for LPG (gas 056 Flue gas temperature sensor
restrictor) 057 Vitodens control unit
016 Gas train 058 Rear cover
017 Ignition unit 059 Support
018 Gas pipe 060 Damper
019 Burner insulating ring 061 Pressure gauge retainer
021 Burner gauze assembly gasket, 062 Clip
large 063 Hinge
022 Burner profile packing 064 Coding card
023 Burner gauze assembly gasket 065 Fuse
024 Heat exchanger 066 Operating interface for constant
025 Boiler adaptor temperature operation
026 Lip seal Ø 150 067 Operating interface for weather-
027 Lip seal Ø 100 compensated operation
028 Plug 069 Outside temperature sensor
029 Quick-acting air vent valve 090 Micro switch
030 Grommet
031 Flow switch Wearing parts
032 Diaphragm safety valve 010 Ignition electrode
033 Siphon 011 Ionisation electrode
034 Condensate hose
035 Ball valve Parts not shown
036 Return pipe extension 001 Operating instructions for con-
037 Sealing panel stant temperature operation
038 Edge protector 002 Operating instructions for
5692 550 GB
111
5692 550 GB
112
113
5692 550 GB
114
115
5692 550 GB
116
117
Commissioning/service reports
Date:
By:
Static pressure mbar max. 57.5 mbar
Oxygen content O 2
& at lower rated output % by
vol.
& at upper rated output % by
vol.
118
119
Oxygen content O 2
& at lower rated output % by
vol.
& at upper rated output % by
vol.
120
121
Oxygen content O 2
& at lower rated output % by
vol.
& at upper rated output % by
vol.
122
123
Specification
*1 The supply values are only for reference (e.g. in the gas contract application) or to esti-
5692 550 GB
mate the supplementary volumetric settings. Because of factory settings, the gas pres-
sure must not be altered from these values. Reference: 15 °C, 1013 mbar.
*2 Max. limit to EnEV.
124
Declaration of conformity
We, Viessmann Werke GmbH & Co KG, D-35107 Allendorf, declare as sole
responsible body, that the product
Vitodens 300
125
We, Viessmann Werke GmbH & Co KG, D-35107 Allendorf, confirm that the fol-
lowing product meets the NO x limits specified by 1st BImSchV Paragraph 7 (2)
[Germany]:
Vitodens 300
5692 550 GB
126
Keyword index
A F
Adjusting the room temperature . . . . 35 Fault history . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Fault messages . . . . . . . . . . . . . . . . . . . . . 73, 75
B Filling the system . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Boiler temperature sensor . . . . . . . . . . . . . 87 Finding faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Brief scans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64 Flue gas temperature sensor . . . . . . . . . 89
Burner gauze assembly . . . . . . . . . . . . . . . . 19 Function descriptions . . . . . . . . . . . . . . . . . . . 95
Burner installation . . . . . . . . . . . . . . . . . . . . . . . . 21 Fuse . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
Burner removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
G
C Gas combination valve . . . . . . . . . . . . . . . . . 13
Checking the differential pressure Gas supply pressure . . . . . . . . . . . . . . . . . . . . 13
sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90 Gas type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Cleaning agent . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Cleaning the combustion chamber . 21 H
Code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38 Heating curve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Code 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38 Heating curve slope . . . . . . . . . . . . . . . . . . . . . 34
Code 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42 Heating surfaces . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Coding during commissioning . . . . . . . 24
Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 I
Condensate drain . . . . . . . . . . . . . . . . . . . . . . . . . 22 Ignition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Cylinder temperature sensor . . . . . . . . . 87 Ignition electrodes . . . . . . . . . . . . . . . . . . . . . . . . 19
Ionisation current . . . . . . . . . . . . . . . . . . . . . . . . . 23
D Ionisation electrode . . . . . . . . . . . . . . . . . . . . . . 19
Declaration of conformity . . . . . . . . . . . . 125
Deleting codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62 L
Language selection . . . . . . . . . . . . . . . . . . . . . . . 9
E Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Extension kit for heating circuit with Level heating curve . . . . . . . . . . . . . . . . . . . . . . 34
mixer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93 LON communication module . . . . . . . . . 31
Extension LON system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
& external . . . . . . . . . . . . . . . . . . . . . . . . . . 100, 101 LON user check . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
& internal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98, 99
O
Operating mode changeover . . . . . . . 102
Outside temperature sensor . . . . . . . . . . 85
5692 550 GB
P
Parts list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
Product characteristics . . . . . . . . . . . . . . . 124
127
R T
Relay test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68 Temperature scans . . . . . . . . . . . . . . . . . . . . . . . 64
Resetting the coding to the delivered Testing functions . . . . . . . . . . . . . . . . . . . . . . . . . . 68
condition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62 Testing outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Thermocouple . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
S
Safety chain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90 V
Scanning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64 Venting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Scanning operating conditions . . . . . . 70 Venting program . . . . . . . . . . . . . . . . . . . . . . . . 103
Scanning sensors . . . . . . . . . . . . . . . . . . . . . . . . 70 Vitotronic 050 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Screed drying . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Screed function . . . . . . . . . . . . . . . . . . . . . . . . . . 104 W
Service level summary . . . . . . . . . . . . . . . . . 63 Wiring diagrams . . . . . . . . . . . . . . . . . . . . . . . . . 107
Service report . . . . . . . . . . . . . 118, 120, 122
Setting the date . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Setting the output . . . . . . . . . . . . . . . . . . . . . . . . . 16
Setting the time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Setting up LON user numbers . . . . . . . 31
Siphon . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Slope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Soundness test, balanced flue
system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
Static pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Supply pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
System designs . . . . . . . . . . . . . . . . . . . . . 24, 39
System pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
5692 550 GB
128
129
130
131
12.3 to 49 kW 16.6 to 66 kW
Natural gas version Natural gas version
from serial no. from serial no.
7176 778 3 00001 7176 779 3 00001
LPG version LPG version
from serial no. from serial no.
7176 780 3 00001 7176 781 3 00001
Viessmann Limited
5692 550 GB
132