Vous êtes sur la page 1sur 9

Construction and Building Materials 163 (2018) 277–285

Contents lists available at ScienceDirect

Construction and Building Materials


journal homepage: www.elsevier.com/locate/conbuildmat

Effect of temperature on bond characteristics of geopolymer concrete


Hai Yan Zhang a, Venkatesh Kodur b,⇑, Bo Wu a, Jia Yan a, Zhen Sheng Yuan a
a
State Key Laboratory of Subtropical Architecture Science, South China University of Technology, Guangzhou, PR China
b
Department of Civil and Environmental Engieering, Michigan State University, East Lansing, MI, USA

h i g h l i g h t s

 Bond between geopolymer concrete and rebar at elevated temperatures are quantified.
 Bond characteristics of geopolymer concrete is compared with conventional concrete.
 Temperature induced bond strength degradation in geopolymer concrete is evaluated.

a r t i c l e i n f o a b s t r a c t

Article history: This paper presents experimental results on the bond behavior between geopolymer concrete and rebar.
Received 3 July 2017 Pull-out tests on geopolymer concrete specimens embedded with plain and ribbed rebars were carried
Received in revised form 4 November 2017 out at ambient temperature and after exposure to 100, 300, 500 and 700 °C. Two batches of geopolymer
Accepted 6 December 2017
concrete with compressive strength of 48 and 64 MPa respectively, and five rebar diameters (of 10, 12,
Available online 18 December 2017
14, 18 and 25 mm) were used for preparing the test specimens. Comparative benchmark tests were also
conducted on ordinary Portland cement (OPC) concrete specimens. Results from these tests show that
Keywords:
geopolymer concrete exhibits insignificant reduction in bond strength till exposure to 300 °C, but under-
Bond characteristics
Geopolymer concrete
goes significant degradation beyond 300 °C. Data from the tests indicate that rate of bond strength degra-
Rebar dation in geopolymer concrete is close to that of splitting tensile strength, but higher than that of
High temperature compressive strength. Also, results infer that geopolymer concrete exhibits similar or better bond prop-
Pull-out test erties than OPC concrete, both at ambient temperature and after exposure to elevated temperatures. Thus
geopolymer concrete can be a practical alternative to OPC concrete in reinforced concrete structures
when fire resistance is one of the main design considerations.
Ó 2017 Elsevier Ltd. All rights reserved.

1. Introduction There is an estimated 44–64% reduction in greenhouse gas emis-


sions for a typical Australian geopolymer product, compared with
Concrete industry is believed to be one of the major contribu- ordinary Portland cement (OPC) [6].
tors to global warming, and this is mainly attributed to the use Geopolymer concrete is reported to have comparable mechani-
of Portland cement as the binder. Cement production is thought cal properties as that of OPC concrete. A great amount of experi-
to be responsible for about 8% of global CO2 emission, based on mental work in the literature has showed that fly ash based
production data in 2014 [1]. To reduce the environmental impact geopolymer concrete, cured at 60–80 °C temperature, exhibit a
of concrete industry, efforts are on to find alternatives to Portland high early mechanical strength and low dry shrinkage [7], excel-
cement. Geopolymer, a new environmentally friendly inorganic lent fire resistance [8,9], and good durability properties [10,11].
binder, derived by alkaline solution activating aluminosilicate In the case of curing at ambient temperature, fly ash based nano-
source material (such as metakaolin, fly ash and slag), has attracted silica modified geopolymer concrete [12], and metakaolin (MK)-
significant attention in recent years as a practical alternative to fly ash (FA) based geopolymer concrete [13], also show excellent
Portland cement [2–5]. With efficient use of industrial by- mechanical strength, compared to conventional heat cured
products, geopolymer binder greatly reduces greenhouse gas geopolymer concrete and OPC concrete.
(CO2) emissions and energy requirements during its production. For reinforced concrete to be effective as a composite material,
reinforcing bar is to be well bonded to the surrounding concrete.
Therefore, evaluating bond behavior between geopolymer concrete
⇑ Corresponding author. and reinforcing bar is critical for the use of geopolymer concrete as
E-mail address: kodur@egr.msu.edu (V. Kodur).

https://doi.org/10.1016/j.conbuildmat.2017.12.043
0950-0618/Ó 2017 Elsevier Ltd. All rights reserved.
278 H.Y. Zhang et al. / Construction and Building Materials 163 (2018) 277–285

an alternative to OPC concrete in reinforced concrete structures. 2.2. Mix proportions


Many attempts to evaluate bond characteristics between geopoly-
mer concrete and reinforcing bar are reported in the literature Two batches of geopolymer concretes (GC1 and GC2) and two
[14–18], but the experimental data on bond behavior of geopoly- batches of OPC concretes (CC1 and CC2) were used for preparing
mer concrete with reinforcing bar at elevated temperatures are pull-out test specimens. The mix proportions of geopolymer con-
not established. A recent study [19] investigated the influence of crete and OPC concrete are tabulated in Table 2. Geopolymer con-
compressive strength of geopolymer concrete, diameter of cretes were derived by adding alkaline activator into metakaolin
reinforcing bar, concrete cover thickness and anchorage length (MK) and fly ash (FA) blend precursor, and then mixed with coarse
on bond behavior between MK-FA based geopolymer concrete and fine aggregates. Details on preparing geopolymer concrete can
and reinforcing bar at room temperature. The current study be found in Ref. [20]. Slumps of geopolymer concretes GC1 and GC2
presents experimental results on bond behavior of MK-FA based are 173 mm and 97 mm respectively, measured through casting
geopolymer concrete with reinforcing bar after exposure to ele- geopolymer concretes into a standard truncated conical mold.
vated temperatures. These experimental results are of great signif-
icance for the use of geopolymer concrete in building applications
2.3. Specimen preparation and test procedure
where provision of fire resistance is a major design requirement.
Pull-out tests were carried out as per specifications in Chinese
2. Experimental program GB 50152-92 [21] and RILEM standard [22]. The sizes of a typical
test specimen are shown in Fig. 1. The rebar was uniaxially embed-
Direct pull-out tests were conducted on 90 geopolymer con- ded in the center of a geopolymer or OPC concrete cubic block of
crete cubic blocks embedded with reinforcing bars of different size 150 mm  150 mm  150 mm, with a bond length of 5d,
diameters, at ambient and after exposure to elevated tempera- where d is the diameter of the rebar. Six groups of reinforcing bars,
tures, to evaluate the effect of temperature on bond characteristics listed in Table 1, were used in geopolymer concrete specimens, but
of geopolymer concrete. Comparative benchmark bond tests were only R-12 and R-14 rebars were used in OPC concrete specimens.
also conducted on 30 OPC concrete specimens. To prevent local stress concentration at the loading end of the
pull-out rebar, the rebar near the loading end was encased in a
plastic tube with a length of (150-5d) (see Fig. 1).
2.1. Raw materials It is reported that the chemical reaction in geopolymers is a
rapid polymerization process and geopolymers can gain high
Geopolymers used in this study are derived by alkaline-silicate strength at early curing age [20,23]. Fig. 2 presents the comparison
solution activating metakaolin (MK) and fly ash (FA) blend. The on compressive strength development with curing age of geopoly-
chemical composition and particle sizes of MK and FA are detailed mer concrete tested in authors’ previous study and that of OPC
in Ref. [20]. The alkaline-silicate activator with desired SiO2/K2O concrete calculated by the proposed empirical formula in Ref.
molar ratio of 1.0 was formulated by blending commercial [24]. It can be seen from Fig. 2 that the compressive strength of
potassium silicate solution with 15.8 wt% K2O, 24.2 wt% SiO2 and geopolymer concrete at 7-days reached 96% of that at 28-days,
60 wt% H2O (SiO2/K2O molar ratio is 2.4), and potassium hydroxide which is much higher than the strength development rate of OPC
flakes with 95% purity, and tap water. The alkaline-silicate activa- concrete at 7-days (account for 59% of 28-day strength). Therefore,
tor was prepared one day prior to use. geopolymer concrete specimens were only cured for 7 days in a
For generating comparative benchmark data, specimens made tank at a constant 22 °C temperature and 95% humidity before
of ordinary Portland cement (OPC, Grade P.O.32.5) concrete were undertaking pull-out tests. OPC concrete pull-out specimens were
also tested. To enhance the strength of OPC concrete, polycarboxy- cured under same conditions for 28 days.
late superplasticizer was added in the preparation of OPC concrete The reinforcing bar in test specimens was gripped at the bottom
specimens. by a UTM5205X universal material testing machine, and secured at
The coarse aggregates for geopolymer and OPC concretes con- the top through a specially designed loading frame. Two displace-
sisted of graded gravel with sizes of 10–20 mm and fine aggregates ment meters were placed at the free end of the rebar and the sur-
consisted of locally available river sand with a maximum size face of concrete respectively, to monitor the relative displacement
of 2 mm. of the rebar during loading. The reinforcing bar was pulled out
Six groups of rebars, with different surface (plain and ribbed slowly, at a pulling rate of 1.2 mm/min. The pull-out force and dis-
rebars) and different nominal diameters (10, 12, 14, 18 and 25 placement data were recorded during the tests.
mm), were used in geopolymer concrete blocks for pull-out tests. For undertaking pull-out tests on high temperature exposed
The geometric characteristics of ribbed rebars were measured specimens, the specimens were first heated in an electrical furnace,
through a vernier caliper. Samples of rebars were tested through at an incremental heating rate of 5 °C per minute. Two thermocou-
a universal material testing machine to obtain their actual yield ples were mounted on the surface and center of the specimen
and ultimate strength. Full details of rebars, together with their respectively, to evaluate the difference between surface and center
mechanical properties, are presented in Table 1. temperatures during heat exposure. Once the predetermined

Table 1
Geometric characteristics and mechanical properties of rebars.

Group Surface Rib height/spacing Rib phase angle (°) Diameter (mm) Yield strength (MPa) Ultimate strength (MPa)
P-10 Plain – – 10 312.00 502.36
R-10 Ribbed 0.14 45 10 420.64 606.31
R-12 Ribbed 0.14 62 12 470.40 620.15
R-14 Ribbed 0.14 45 14 437.37 600.04
R-18 Ribbed 0.15 45 18 365.15 520.00
R-25 Ribbed 0.16 45 25 445.78 596.79
H.Y. Zhang et al. / Construction and Building Materials 163 (2018) 277–285 279

Table 2
Batch mix proportions of geopolymer concrete and OPC concrete (unit: kg/m3).

Concrete Type Alkaline activator MK FA OPC Water Fine aggregate Coarse aggregate Super-plasticizer
GC1 417 219 219 – – 616 1434 –
GC2 343 226 226 – – 634 1477 –
CC1 – – – 468 145 702 1076 1
CC2 – – – 470 143 636 1181 5

concrete and embed rebars would reduce to very low level at


Displacement meter 700 °C. However, the bond test results presented in the following
sections are better than expected. The difference in bond strength
of geopolymer concrete-rebars and geopolymer mortar-concrete
Bond length

20 substrate is induced by the difference in test method, specimen


size and material properties. A total of 90 geopolymer concrete
pull-out specimens and 30 OPC concrete pull-out specimens were
150

tested to evaluate bond characteristics of geopolymer concrete and


OPC concrete with reinforcing bar respectively. The details of these
specimens are listed in Table 3.
Plastic tube
To investigate the relationship between bond, compressive and
splitting tensile strengths of concrete, compressive and splitting
Reinforcing bar tensile strengths of geopolymer concrete and OPC concrete speci-
130

mens were also tested at ambient and after exposure to target tem-
peratures. The sizes of test specimens for compressive and splitting
F tensile strengths were 100 mm  100 mm  100 mm cubes.

Fig. 1. Typical pull-out test specimen for bond tests.


3. Results and discussion

Data from pull-out tests on geopolymer concrete specimens


60 with different types of concrete and reinforcing bars, at ambient
Compressive Strength (MPa)

and after exposure to high temperatures, is used to quantify the


50 effect of temperature on bond behavior of geopolymer concrete.
The data from tests on OPC concrete specimens were used as the
40 comparing benchmark of bond characteristics of geopolymer
concrete.
30
Geopolymer concrete
20 OPC concrete [24] 3.1. Compressive and splitting tensile strengths

10 Table 4 lists the comparative compressive and splitting tensile


strengths of geopolymer concrete (GC1) and OPC concrete (CC1)
0 at ambient and after exposure to elevated temperatures. It can
0 5 10 15 20 25 30
be seen that the decrease in compressive and splitting tensile
Curing age (day)
strengths of GC1 and CC1 concretes is insignificant till the expo-
Fig. 2. Compressive strength development of geopolymer concrete and OPC sure temperature is up to 300 °C. Especially, a slight increase in
concrete with curing age. strength of GC1 is seen at 300 °C. This slight strength increase in
geopolymer concrete is probably attributed to sintering reaction
of un-reacted fly ash particles in geopolymers [13,26]. When the
target temperature (test temperature) was attained, temperature exposure temperature exceeds 300 °C, significant strength
of the furnace was kept constant for 120 min. From the measured decrease occurs on geopolymer and OPC concretes. Geopolymer
temperature data, thermal stability was achieved throughout the concrete GC1 exhibits similar level of compressive strength as that
specimens (temperature difference (gradient) between surface of OPC concrete CC1 at ambient and after exposure to elevated
and center was less than 10%), after 120-min exposure to the con- temperatures, but relatively higher splitting tensile strength than
stant target temperature. Then the heating in the furnace was that of CC1 concrete. Comparing the retention ratio of compressive
turned-off and the specimens were allowed to cool naturally. After and splitting tensile strength after exposure to elevated tempera-
cooling down to the ambient temperature, the specimens were tures, a higher degradation rate occurred in the splitting tensile
taken out of the furnace and then pull-out tests were conducted, strength of GC1 and CC1 concretes than that of compressive
using the same procedures as those at ambient tests. strength. Geopolymer concrete GC2 and OPC concrete CC2 were
The target temperatures for undertaking pull-out tests include used to prepare pull-out specimens with slightly higher strength
ambient temperature (about 25 °C), 100, 300, 500 and 700 °C. At concrete, to study the influence of compressive strength. The com-
each temperature, three specimens with same concrete type and pressive and splitting tensile strengths of GC2 and CC2 concretes at
same rebar group were tested. The pre-determination of the high- ambient temperature are also presented in Table 4. Geopolymer
est test temperature of 700 °C is based on authors’ previous study concrete GC2 exhibits similar compressive strength with OPC con-
[25]. It was reported that the bond strength of geopolymer mortar crete CC2 at ambient temperature, but a slightly lower splitting
with concrete substrate was almost lost at 700 °C [25]. Therefore, it tensile strength than that of CC2. The strength variation of
had been thought that the bond strength between geopolymer geopolymer concrete GC2 with exposure temperature is not
280 H.Y. Zhang et al. / Construction and Building Materials 163 (2018) 277–285

Table 3
Specimen configurations and test parameters.

Group No. Concrete type Surface of rebar Rebar diameter, d (mm) Concrete cover, c (mm) c/d Test temp. (°C)
GC1-P-10 GC1 Plain 10 70 7.00 25, 100, 300, 500, 700
GC1-R-10 GC1 Ribbed 10 70 7.00
GC1-R-12 GC1 Ribbed 12 69 5.75
GC1-R-18 GC1 Ribbed 18 66 3.67
GC1-R-25 GC1 Ribbed 25 62.5 2.50
CC1-R-12 CC1 Ribbed 12 69 5.75
GC2-R-14 GC2 Ribbed 14 68 4.86
CC2-R-14 CC2 Ribbed 14 68 4.86

Table 4
Compressive and splitting tensile strengths of geopolymer concrete and OPC concrete.

Type of concrete Test temperature Comp. strength Comp. strength retention ratio Tensile Strength Tensile strength retention ratio
T (°C) fcu (MPa) (%) ft (MPa) (%)
GC-1 25 48.13 100 4.85 100
100 48.12 100 4.29 88
300 50.92 106 4.42 91
500 39.90 83 2.69 55
700 26.98 56 1.76 36
CC-1 25 49.78 100 3.09 100
100 46.69 94 2.53 82
300 49.65 100 2.98 96
500 39.9 80 1.79 58
700 27.84 56 0.96 31
GC-2 25 63.92 – 4.24 –
CC-2 25 66.66 – 5.24 –

presented herein, since it is similar with that reported in Ref. [20]. Table 5
Similar to the trend in strength development of high strength OPC Failure modes in specimens at ambient and after exposure to elevated temperatures.
concrete, the temperature-induced strength degradation of
Group No. Test temperature (°C)
geopolymer concrete with higher strength level is more significant
25 100 300 500 700
than that with lower strength level.
GC1-P-10 B B B B B
GC1-R-10 B B B B B
3.2. Failure modes in pull-out tests GC1-R-12 B B B B B
GC1-R-18 S S S-B S-B B
Four types of failure modes were seen during pull-out tests on GC1-R-25 S S S S-B S-B
CC1-R-12 B B B B Spalling
geopolymer concrete specimens: typical splitting failure, bond fail- GC2-R-14 F F S-B S-B S-B
ure (pull-out failure), a combination of splitting and bond failure CC2-R-14 B F, B F, S-B S-B S-B, B
(splitting-bond failure), and rebar fracture. Typical splitting failure
Note: S, B, S-B and F denote splitting, bond, splitting-bond and rebar fracture failure
is characterized by the formation of radial cracks from the rebar respectively.
surface, and quick progression of these cracks in longitudinal direc-
tion, leading to sudden breakage of geopolymer concrete without
much slippage of the rebar. Bond failure is characterized by the in exposure temperatures. However, for specimens in Group
interfacial shear failure between geopolymer concrete and rein- GC2-R-14, the failure modes changed from rebar fracture at ambi-
forcing bar, with significant slippage of the rebar, but without ent temperature to splitting-bond failure when exposure tempera-
any visible splitting cracks. If a specimen failed with significant ture exceeded 300 °C.
slippage of rebar and visible splitting cracks, it was termed as The failure modes in pull-out tests is governed by the minimum
splitting-bond failure. Some specimens, made from high strength of the splitting capacity of geopolymer concrete, the bond capacity
geopolymer concrete (GC2) or OPC concrete (CC2), failed through between geopolymer concrete and rebar, and the tensile capacity
slight slippage and fracture of rebar, but without visible splitting of rebar. The splitting capacity is dependent on the thickness of
cracks. This type of failure was termed as rebar fracture failure. concrete cover and splitting tensile strength of concrete [27], while
The failure mode in each specimen type is listed in Table 5. It the bond capacity is related to the geometric characteristic of the
can be seen from the table that at ambient temperature, bond fail- rebar and compressive strength of concrete. With an increase in
ure occurs on the specimens with smaller rebar diameter and exposure temperature, the compressive and splitting tensile
thicker concrete cover. However, specimens with larger rebar strengths of geopolymer concrete decrease, as discussed above
diameter and thinner concrete cover are more susceptible to split- (see Table 4). In addition, the mechanical properties of rebar also
ting failure. degrade after exposure to elevated temperatures, but the strength
With an increase in the exposure temperature, a change in fail- loss of rebar is lower as compared to that of concrete [28]. There-
ure modes was seen in Group GC1-R-18, GC1-R-25 and GC2-R-14 fore, specimens in Group GC2-R-14 failed through splitting-bond
specimens. Fig. 3 compares relative failure modes in GC1-R-18 failure, when exposed to high temperatures, but not through rebar
specimens after exposure to different temperatures. It can be seen fracture as that at ambient temperature. For specimens in Groups
that the failure modes of GC1-R-18 changed from splitting failure GC1-R-18 and GC1-R-25 after exposure to elevated temperatures,
to splitting-bond failure, and even bond failure, with an increase a significant difference in deformation levels between geopolymer
H.Y. Zhang et al. / Construction and Building Materials 163 (2018) 277–285 281

(a) 25oC (b) 100oC (c) 300oC (d) 500oC (e) 700oC
Fig. 3. Failure patterns in Group GC1-R-18 specimens after exposure to elevated temperatures.

(a) 25oC (b) after exposure to 700oC


Fig. 4. Deformation state at rebar and geopolymer concrete interface after bond tests.

concrete and steel rebar were observed, as shown in Fig. 4. This is 25


due to incompatibility in deformations between geopolymer con-
crete and rebar during thermal expansion under heating state
Bond strength (MPa)

and thermal shrinkage under cooling state. The deformation gap 20


between concrete and rebar, due to differential thermal expansion
and shrinkage, is also reported previously by other authors in pull- 15 GC1-R-10
out tests on ordinary concrete [29]. This difference in deformations
reduces the friction and mechanical bearing between geopolymer 10
concrete and rebar, leading to higher degradation in bond capacity.
The degradation in bond capacity possibly overwhelms that of GC1-P-10
5
splitting capacity. Therefore, the failure modes in specimens from
Groups GC1-R-18 and GC1-R-25 changed from splitting failure at
ambient temperature to splitting-bond or bond failure after high 0
0 100 200 300 400 500 600 700
temperature exposure.
o
Temperature ( C)
3.3. Bond behavior of specimens with different rebar surfaces Fig. 5. Bond strength of specimens with different rebar surfaces.

The interfacial bond stress developed between geopolymer con-


crete and rebar is assumed to be of uniform distribution along the sure temperature was below 300 °C. However, when the tempera-
bond length. The average bond stress can be determined as: ture exceeded 300 °C, a significant decrease in bond strength
occurred in GC1-R-10 and GC1-P-10 specimens. This trend is in
F
s¼ ð1Þ line with that of compressive and splitting tensile strengths of
pdl geopolymer concrete. The significant strength degradation of
where s is the bond stress (MPa), F is the applied load (N), d is the geopolymer concrete between 300 and 500 °C is mainly due to
nominal rebar diameter (mm) and l is bond length (mm). The bond temperature-induced dehydration and dehydroxylation reaction
strength (su) is the calculated average bond stress from the maxi- of geopolymers, together with the thermal incompatibility
mum applied loading during the pull-out tests. The free end slip between geopolymers and aggregates [25].
of the rebar is determined as the difference between the displace- Comparing the bond strength of GC1-R-10 and GC1-P-10 spec-
ment measured by the displacement meter on the free end of the imens, it can be seen that the bond strength of geopolymer con-
rebar and that on the surface of concrete. crete with ribbed rebar (GC1-R-10) is more than twice of that
Fig. 5 presents the relative bond strength of geopolymer con- with plain rebar (GC1-P-10) at ambient temperature. When
crete specimens embedded with plain rebar (GC1-P-10) and ribbed exposed to temperatures above 300 °C, GC1-R-10 and GC1-P-10
rebar (GC1-R-10), as a function of exposure temperature. It can be specimens exhibit a significant degradation in bond strength, with
seen that a slight increase or decrease in bond strength occurred on GC1-P-10 specimens having a higher degradation (rate). The bond
GC1-R-10 and GC1-P-10 specimens respectively, when the expo- strength retention ratio, designated as the ratio of the residual
282 H.Y. Zhang et al. / Construction and Building Materials 163 (2018) 277–285

bond strength after exposure to high temperatures to the bond no significant variation in bond stress but significant increase in
strength tested at ambient temperature, is only 22% and 8% for slippage.
GC1-P-10 specimens at 500 °C and 700 °C respectively, but that From Fig. 6(a), it can be seen that the s-s curves for specimens
of corresponding GC1-R-10 specimens is 44% and 35% respectively. GC1-R-10 at 100 and 300 °C are close to that at ambient tempera-
The lower bond strength retention for specimens embedded ture (25 °C), but the s-s curves at 500 and 700 °C are much differ-
with plain rebars can be explained by the bond mechanism ent. At 500 and 700 °C, the slips of rebars initiated at a lower
between geopolymer concrete and plain rebar. The resistance of loading, and the peak bond stresses are much lower than that at
a plain rebar against pull out is provided by chemical adhesion 25 °C, but the slips corresponding to the peak bond stresses are
and friction between rebar and concrete. Adhesion is lost at early greater.
stages of loading once slip gets initiated. Therefore, the bond The effect of temperature on s-s curves of GC1-P-10 specimens
strength between geopolymer concrete and plain rebar is mainly is slightly different with that of GC1-R-10. With the increasing
determined by the friction. As the exposure temperature is raised, exposure temperature, the peak bond stress and the residual stress
severe deterioration occurs on concrete and significant deforma- at the steady state stage decrease gradually. Compared to Fig. 6(a),
tion incompatibility between concrete and rebar gets developed, the peaks of the s-s curves of GC1-P-10 specimens in Fig. 6 (b) are
which makes the friction weakened. Thus, the resistance of plain sharper, and the slips corresponding to the peak bond stresses are
rebars to pull out decreases significantly with an increase in tem- much lower than those of GC1-R-10 specimens. This is due to the
perature. However, for the specimens embedded with ribbed fact that once the slip is initiated, the chemical adhesion between
rebars, apart from the chemical adhesion and friction, the mechan- geopolymer concrete and rebar is quickly lost, leading to the bond
ical bearing between rebar and concrete plays a prominent role in stress of GC1-P-10 specimens reaching a peak value at a lower slip,
the bond strength. Therefore, GC1-R-10 specimens experienced a and then s-s curves abruptly enter the descending stage. However,
lower degradation (rate) in bond strength. for specimens in Group GC1-R-10, the mechanical bearing is dom-
Fig. 6(a) and (b) present the typical bond stress-slip (s-s) curves inant for bond capacity, while the loss of chemical adhesion has no
of specimens in Groups GC1-R-10 and GC1-P-10 respectively, at significant effect on bond capacity, thus the peaks of s-s curves are
different temperatures. GC1-R-10 and GC1-P-10 specimens all flatter.
failed through pull-out of rebars. As shown in Fig. 6, bond behavior
of these specimens can be characterized under three stages, which
are the ascending stage with a steep increase in bond stress but lit- 3.4. Bond behavior of specimens with different rebar diameters
tle slippage, the descending stage with a quick decrease in bond
stress but a quick increase in slippage, and the steady stage with Bond strength between concrete and rebar is generally believed
to decrease with an increase of rebar diameter, when the specimen
sizes are kept constant [28]. However, there are few studies which
reported that the bond strength increases with rebar diameter
increasing [30]. The bond strength of geopolymer concrete speci-
mens with different rebar diameters is presented in Fig. 7, as a
function of exposure temperature. It can be seen that the bond
strength of specimens with rebar diameters of 10 and 12 mm is
higher than that of 18 and 25 mm, both at ambient and after expo-
sure to elevated temperatures. The specimens with rebar diameter
of 10 and 12 mm failed through pull-out, thus the bond strength of
these specimens is related to the geometric characteristics of
rebars, such as rib spacing, rib height and phase angle. As listed
in Table 1, R-12 rebars have the same rib height/spacing ratio as
R-10 rebars, but higher rib phase angle, which leads to higher bond
strength with geopolymer concrete than that of R-10 rebars. Spec-
imens in Groups GC1-R-18 and GC1-R-25 experienced splitting or
splitting-bond failure prior to the occurrence of bond failure, due
to lower ratio of concrete cover thickness to rebar diameter (c/d).
Therefore, the real bond strength could not be obtained, and the

24
GC1-R-10
GC1-R-12
Bond strength (MPa)

20 GC1-R-18
GC1-R-25
16 d=10
d=18
12
d=25 d=12
8

0
0 100 200 300 400 500 600 700
o
Temperature ( C)
Fig. 6. s-s curves of specimens in Groups GC1-R-10 and GC1-P-10. Fig. 7. Bond strength of specimens with different rebar diameters.
H.Y. Zhang et al. / Construction and Building Materials 163 (2018) 277–285 283

calculated bond strength of GC1-R-18 and GC1-R-25 specimens is 3.5. Comparison of bond behavior of geopolymer concrete and OPC
lower than that of GC1-R-10 and GC1-R-12 specimens. concrete
As illustrated in Fig. 7, the variations of bond strength with
increasing temperature are similar for specimens with different To compare the bond behavior of geopolymer concrete and OPC
rebar diameters. The bond strength in these specimens has no sig- concrete, results from pull-out tests on two batches of geopolymer
nificant reduction when the exposure temperature is below 300 °C, concrete (GC1 and GC2) and two batches of OPC concrete (CC1 and
but exhibit significant degradation above 300 °C. CC2) are utilized. As listed in Table 4, GC1 and CC1 concretes exhib-
Fig. 8 plots the typical s-s curves of specimens in Groups GC1-R- ited similar level of compressive and splitting tensile strengths, but
18 and GC1-R-25, after exposure to elevated temperatures. The GC2 and CC2 concretes had only similar compressive strength but
trends of these curves are much different with those in Fig. 6, different splitting tensile strength. In addition, the compressive
due to different failure modes occurred in these specimens. The strength of GC2 and CC2 concretes was higher than that of GC1
specimens of GC1-R-18 at ambient temperature and after exposure and CC1 concretes.
to 100 °C, and GC1-R-25 at ambient temperature and after expo- Fig. 9 illustrates the bond strength of four groups of specimens,
sure to 100 °C and 300 °C, failed through splitting failure. Splitting including GC1-R-12, CC1-R-12, GC2-R-14 and CC2-R-14, as a func-
failure is characterized by brittle and abrupt failure, and thus the tion of exposure temperature. It can be seen that although GC1 and
s-s curves of these specimens have no descending segment, as well CC1 concretes exhibited similar compressive and splitting tensile
as steady segment. In specimens that experienced splitting-bond strengths, GC1 concrete exhibited higher bond strength than that
failure, such as GC1-R-18 specimens at 300 °C and GC1-R-25 spec- of CC1 concrete, both at ambient and after exposure to elevated
imens at 500 and 700 °C, although the three stages (ascending, temperatures. It should be noted that the pull-out tests were not
descending and steady stage) can be observed on their s-s curves, conducted on CC1-R-12 specimens after exposure to 700 °C, due
the descending stage in them developed in a very short time and to the spalling of OPC concrete in CC1-R-12 specimens during heat-
had higher decreasing rate than those specimens that failed ing. No temperature-induced spalling was seen in any of geopoly-
through pull-out mechanism. This is due to rapid growth of split- mer concrete specimens. Specimens GC2-R-14 and CC2-R-14
ting cracks from interior concrete to the surface, which leads to exhibited close bond strengths. These strengths were higher than
sudden decrease of bond stress and abrupt increase in slippage those of GC1-R-12 and CC1-R-12 specimens, due to the fact that
after the attainment of peak bond stress. In comparison to speci- GC2 and CC2 concretes had higher compressive strength than
mens failing through splitting, specimens experiencing splitting- GC1 and CC1 concretes.
bond failure could still sustain a certain portion of loading due to Fig. 10(a) and (b) compare retention ratio of compressive, split-
friction action, which leads to attaining a steady state on their ting tensile and bond strengths with ribbed rebar (R-12) of GC1
s-s curves. and CC1 concretes after exposure to elevated temperatures. It
can be seen that the trends of compressive, splitting tensile and
bond strengths of GC1 and CC1 concretes, with temperature, are
similar. When the exposure temperature is below 300 °C, there is
only slight degradation in compressive, splitting tensile and bond
strengths of GC1 and CC1 concretes; but when the temperature
exceeds 300 °C, significant degradation in corresponding strength.
Comparing the degradation rates of compressive, splitting tensile
and bond strengths, it can be seen that the degradation rates of
bond and splitting tensile strengths of GC1 and CC1 concretes are
higher than that of compressive strength. The degradation rates
of bond and splitting tensile strengths of GC1 concrete, after expo-
sure to elevated temperatures, are close, except that at 100 °C. Fol-
lowing 100 °C exposure, GC1 concrete has almost no reduction in
bond strength, but 12% reduction in splitting tensile strength.
Fig. 11(a) and (b) present the typical s-s curves of specimens in
Groups GC2-R-14 and CC2-R-14, at different temperatures. The

25
GC1-R-12
GC2 CC2 CC1-R-12
Bond strength (MPa)

20 GC2-R-14
CC2-R-14
GC1
15
CC1
10

0
0 100 200 300 400 500 600 700 800
o
Temperature ( C)
Fig. 9. Comparison of bond strength of geopolymer concrete with that of OPC
Fig. 8. s-s curves of specimens in Groups GC1-R-18 and GC1-R-25. concrete.
284 H.Y. Zhang et al. / Construction and Building Materials 163 (2018) 277–285

Strength retention ratio (%)


100

80

60

40 Compressive strength
Splitting tensile strength
20 Bond strength

0
0 100 200 300 400 500 600 700 800
o
Temperature ( C)
(a) GC1
Strength retention ratio (%)

100

80

60

40
Compressive strength
Splitting tensile strength
20
Bond strength
0
0 100 200 300 400 500 600 700 800
o
Temperature ( C)
(b) CC1
Fig. 10. Strength retention ratio of GC1 and CC1 concretes after exposure to
Fig. 11. s-s curves of GC2-R-14 and CC2-R-14 test specimens.
elevated temperatures.

where T is the highest exposure temperature, sTu is the residual bond


strength between geopolymer concrete and rebar after exposure to
rebars in GC2-R-14 specimens at ambient temperature and after
temperature T, sAu is the bond strength at ambient temperature. The
exposure to 100 °C fractured during pull-out tests, with little slip-
page. Therefore, s-s curves of GC2-R-14 specimens at 25 and 100 °C coefficients in the above expression are obtained through regression
abruptly dropped after the peak stress was reached. Similar trend analysis, with a correlation coefficient (R) of 0.966. The bond
was seen on the s-s curve of CC2-R-14 at 100 °C. Based on the duc- strength between geopolymer concrete and ribbed rebar at ambient
tility attained from yielding (Point A in Fig. 11(a)) to fracture of temperature (sAu ) can be estimated by the proposed model in Ref.
rebars (Point B), an anchorage length of 5d can be regarded as [19].
the critical anchorage length for this type of high strength geopoly- Fig. 12 shows the comparison between experimental and pre-
mer concrete. Comparing Fig. 11(a) and (b), it can be seen that the dicted residual bond strength versus exposure temperature for
trends on s-s curves of GC2-R-14 and CC2-R-14 specimens at 300, geopolymer concrete with ribbed rebars. It can be seen that the
500 and 700 °C are similar, due to similar failure modes occurring predicted results fit well with the test data.
in these specimens (splitting-bond failure), but the slippage of
CC2-R-14 specimen corresponding to similar peak stress as that
Bond strength retention ratio

of GC2-R-14 is larger. This infers that geopolymer concrete exhibits 1.2


similar or better bond behavior than OPC concrete with same
levels of compressive strength. 1.0
4. Prediction model of residual bond strength after high 0.8
temperature exposure Test data of d=10
0.6 Test data of d=12
Polynomial function is often adopted for expressing residual Test data of d=14
bond strength between rebar and OPC concrete exposed to ele- 0.4 Test data of d=18
vated temperatures [28,31]. To evaluate residual bond strength Test data of d=25
between geopolymer concrete and ribbed rebar, as a function of 0.2
Fitting curve
temperature, the following cubic expression on bond strength
retention ratio is developed, utilizing data generated in 0.0
experiments. 0 100 200 300 400 500 600 700
o
sTu Temperature ( C)
¼ 0:96 þ 1:39  103 T  7:06  106 T 2 þ 4:95  109 T 3 ð2Þ
sAu Fig. 12. Comparison of predicted and measured bond strength retention ratio.
H.Y. Zhang et al. / Construction and Building Materials 163 (2018) 277–285 285

5. Conclusions [6] B.C. McLellan, R.P. Williams, J. Lay, A. van Riessen, G.D. Corder, Costs and
carbon emissions for geopolymer pastes in comparison to ordinary Portland
cement, J Clean Prod. 19 (2011) 1080–1090.
To evaluate the effect of temperature on bond characteristics of [7] A.M. Fernandez-Jimenez, A. Palomo, C. Lopez-Hombrados, Engineering
geopolymer concrete, pull-out tests were conducted on large num- properties of alkali-activated fly ash concrete, ACI Mater. J. 103 (2) (2006)
106–112.
ber of specimens with different concrete and rebar types, at ambi-
[8] R. Zhao, J.G. Sanjayan, Geopolymer and Portland cement concretes in
ent and after exposure to elevated temperatures. Based on the test simulated fire, Mag. Concr. Res. 63 (3) (2011) 163–173.
results, the following conclusions can be drawn: [9] Prabir Kumar Sarker, Sean Kelly, Zhitong Yao, Effect of fire exposure on
cracking, spalling and residual strength of fly ash geopolymer concrete, Mater.
Des. 63 (2014) 584–592.
(1) Geopolymer concrete exhibits significant temperature [10] M. Olivia, H. Nikraz, Properties of fly ash geopolymer concrete designed by
induced degradation in bond strength, when exposed to Taguchi method, Mater. Des. 36 (2012) 191–198.
temperatures above 300 °C. [11] D. Hardjito, S.E. Wallah, D.M.J. Sumajouw, B.V. Rangan, On the development of
fly ash-based geopolymer concrete, ACI Mater. J. 101 (6) (2004) 467–472.
(2) Bond strength of geopolymer concrete with ribbed rebar is [12] D. Adak, M. Sarkar, S. Mandal, Structural performance of nano-silica modified
more than twice of that with plain rebar of same diameter fly-ash based geopolymer concrete, Constr. Build. Mater. 135 (2017) 430–439.
at ambient temperature. Also, degradation in bond strength [13] H.Y. Zhang, V. Kodur, B. Wu, L. Cao, S.L. Qi, Comparative thermal and
mechanical performance of geopolymers derived from metakaolin and fly ash,
of geopolymer concrete with ribbed rebar occurs at a lower J. Mater. Civil Eng. 28 (2) (2016) 1–10.
rate with temperature. [14] M. Sofi, J.S.J. van Deventer, P.A. Mendis, G.C. Lukey, Bond performance of
(3) Bond strength of geopolymer concrete decreases at the same reinforcing bars in inorganic polymer concrete (IPC), J. Mater. Sci. 42 (9) (2007)
3107–3116.
rate as that of splitting tensile strength with temperature, [15] P.K. Sarker, Bond strength of reinforcing steel embedded in fly ash-based
but this degradation is at a higher pace than that of com- geopolymer concrete, Mater. Struct. 44 (5) (2011) 1021–1030.
pressive strength. [16] A. Castel, S.J. Foster, Bond strength between blended slag and Class F fly ash
geopolymer concrete with steel reinforcement, Cem. Concr. Res. 72 (2015) 48–
(4) Geopolymer concrete exhibits similar or better bond proper-
53.
ties than ordinary Portland cement concrete with similar [17] R.D. Moser, P.G. Allison, B.A. Williams, C.A. Weiss, A.D. Diaz, E.R. Gore, et al.,
levels of compressive strength. Improvement in the geopolymer-to-steel bond using a reactive vitreous
enamel coating, Constr. Build. Mater. 49 (2013) 62–69.
[18] S. Songpiriyakij, T. Pulngern, P. Pungpremtrakul, C. Jaturapitakkul, Anchorage
of steel bars in concrete by geopolymer paste, Mater. Des. 32 (5) (2011) 3021–
3028.
Acknowledgements [19] H.Y. Zhang, J. Yan, B. Wu, Study on bond behavior between geopolymer
concrete and steel bars, China Civil Eng. J. 49 (7) (2016) 107–115 (In Chinese).
[20] H.Y. Zhang, V. Kodur, S.L. Qi, L. Cao, B. Wu, Development of metakaolin–fly ash
The research presented in this paper is supported by National based geopolymers for fire resistance applications, Constr. Build. Mater. 55
Natural Science Foundation of China (Grant No. 51478195), the (2014) 38–45.
Fundamental Research Funds for the Central Universities [21] National Standard of PRC, Standard Method for Testing of Concrete Structures
(GB 50152-92), China Building Industry Press, Beijing, 1992.
(2015ZZ071), and State Key laboratory of Subtropical Architecture [22] RILEM/CEB/FIP, RC6: Bond Test Reinforcement Steel-Pull Out Test, Georgi
Science, South China University of Technology (Grant No. Publishing Company, 1983.
2016KB15) and Michigan State University. Any opinions, findings, [23] D.L.Y. Kong, J.G. Sanjayan, Damage behavior of geopolymer composites
exposed to elevated temperatures, Cem. Concr. Compos. 30 (10) (2008) 986–
and conclusions or recommendations expressed in this paper are 991.
those of the authors and do not necessarily reflect the views of [24] Z.R. Jiang, Handbook of Construction Calculation, China Architecture &
the sponsors. Building Press, 2007.
[25] H.Y. Zhang, V. Kodur, B. Wu, L. Cao, F. Wang, Thermal behavior and mechanical
properties of geopolymer mortar after exposure to elevated temperatures,
Constr. Build. Mater. 109 (2016) 17–24.
References [26] D.L.Y. Kong, J.G. Sanjayan, K. Sagoe-Crentsil, Comparative performance of
geopolymers made with metakaolin and fly ash after exposure to elevated
[1] J.G.J. Olivier, G. Janssens-Maenhhout, M. Muntean, J.A.H.W. Peters, Trends in temperatures, Cem. Concr. Res. 37 (2007) 1583–1589.
Global CO2 Emissions; 2015 Report, PBL Netherlands Environmental [27] K. Hertz, The anchorage capacity of reinforcing bars at normal and high
Assessment Agency, The Hague, Netherlands, 2015. temperatures, Mag. Concr. Res. 34 (121) (1982) 213–220.
[2] F.U.A. Shaikh, Review of mechanical properties of short fibre reinforced [28] A. Ergun, G. Kurklu, M.S. Baspinar, The effects of material properties on bond
geopolymer composites, Constr. Build. Mater. 43 (2013) 37–49. strength between reinforcing bar and concrete exposed to high temperature,
[3] J. Davidovits, Geopolymers geopolymeric materials, J. Therm. Anal. 35 (2) Constr. Build. Mater. 112 (2016) 691–698.
(1989) 429–441. [29] T. Pothisiri, P. Panedpojaman, Modeling of bonding between steel rebar and
[4] P. Duxson, A. Fernandez-Jimenez, J.L. Provis, G.C. Lukey, A. Palomo, J.S.J. van concrete at elevated temperatures, Constr. Build. Mater. 27 (1) (2012) 130–
Deventer, Geopolymer technology: the current state of the art, J. Mater. Sci. 42 140.
(9) (2007) 2917–2933. [30] B. Singh, G. Ishwarya, M. Gupta, S.K. Bhattacharyya, Geopolymer concrete: a
[5] S.A. Bernal, E.D. Rodriguez, R.M. de Gutierrez, M. Gordillo, J.L. Provis, review of some recent developments, Constr. Build. Mater. 85 (2015) 78–90.
Mechanical and thermal characterisation of geopolymers based on silicate- [31] Z. Huang, Modelling the bond between concrete and reinforcing steel in a fire,
activated metakaolin/slag blends, J. Mater. Sci. 46 (16) (2011) 5477–5486. Eng. Struct. 32 (11) (2010) 3660–3669.

Vous aimerez peut-être aussi