For: STEELGUARD™651

Required intumescent Dry Film Thickness (dft) in millimetres


(mm) of STEELGUARD™ 651 for rectangular / square hollow
section beams, with three sided exposure

This appendix forms part of Certificate Number 1192m, Issue 2, issued to:

PPG Coatings Europe BV


Oceanenweg 2
1047 BB Amsterdam
The Netherlands

on 9 September 2016

To check the validity of the Certificate and Appendix please visit www.redbooklive.com

This Appendix is part of the Product Approval Certificate and shall not be distributed separately.

The certificate and this appendix are issued subject to terms and conditions. For details visit
www.redbooklive.com/terms

LPCB is part of BRE Global Ltd, Garston, Watford, WD25 9XX


T: +44 (0)333 321 8811 F: +44 (0)1923 664603 E: enquiries@breglobal.com

BF1305MTA-A Rev 0.0 Page A5-1 of 2 ©BRE Global Ltd. 2015


LPCB Ref. Number 1192m/01

Table 1 Required thickness (mm) of Steelguard 651 applied to rectangular hollow section beams, for a fire
resistance period of 30 minutes
Design temperature (°C)
Section factor
(m-1) 350 400 450 500 550 600 620 650 700
70 1.949 1.949 1.949 1.949 1.949 1.949 1.949 1.949 1.949
75 1.949 1.949 1.949 1.949 1.949 1.949 1.949 1.949 1.949
80 1.949 1.949 1.949 1.949 1.949 1.949 1.949 1.949 1.949
85 1.949 1.949 1.949 1.949 1.949 1.949 1.949 1.949 1.949
90 1.949 1.949 1.949 1.949 1.949 1.949 1.949 1.949 1.949
95 1.949 1.949 1.949 1.949 1.949 1.949 1.949 1.949 1.949
100 1.949 1.949 1.949 1.949 1.949 1.949 1.949 1.949 1.949
105 1.949 1.949 1.949 1.949 1.949 1.949 1.949 1.949 1.949
110 1.949 1.949 1.949 1.949 1.949 1.949 1.949 1.949 1.949
115 1.949 1.949 1.949 1.949 1.949 1.949 1.949 1.949 1.949
120 1.949 1.949 1.949 1.949 1.949 1.949 1.949 1.949 1.949
125 1.949 1.949 1.949 1.949 1.949 1.949 1.949 1.949 1.949
130 1.949 1.949 1.949 1.949 1.949 1.949 1.949 1.949 1.949
135 1.949 1.949 1.949 1.949 1.949 1.949 1.949 1.949 1.949
140 1.949 1.949 1.949 1.949 1.949 1.949 1.949 1.949 1.949
145 1.949 1.949 1.949 1.949 1.949 1.949 1.949 1.949 1.949
150 1.949 1.949 1.949 1.949 1.949 1.949 1.949 1.949 1.949
155 1.949 1.949 1.949 1.949 1.949 1.949 1.949 1.949 1.949
160 1.949 1.949 1.949 1.949 1.949 1.949 1.949 1.949 1.949
165 1.949 1.949 1.949 1.949 1.949 1.949 1.949 1.949 1.949
170 1.949 1.949 1.949 1.949 1.949 1.949 1.949 1.949 1.949
175 1.949 1.949 1.949 1.949 1.949 1.949 1.949 1.949 1.949
Table 2 Required thickness (mm) of Steelguard 651 applied to rectangular hollow section beams, for a fire
resistance period of 60 minutes
Design temperature (°C)
Section factor
(m-1) 350 400 450 500 550 600 620 650 700
70 1.949 1.949 1.949 1.949 1.949 1.949 1.949 1.949 1.949
75 1.949 1.949 1.949 1.949 1.949 1.949 1.949 1.949 1.949
80 1.949 1.949 1.949 1.949 1.949 1.949 1.949 1.949 1.949
85 2.038 1.971 1.949 1.949 1.949 1.949 1.949 1.949 1.949
90 2.326 2.240 1.949 1.949 1.949 1.949 1.949 1.949 1.949
95 2.613 2.508 1.949 1.949 1.949 1.949 1.949 1.949 1.949
100 2.901 2.777 1.949 1.949 1.949 1.949 1.949 1.949 1.949
105 3.189 3.046 2.065 1.949 1.949 1.949 1.949 1.949 1.949
110 3.476 3.315 2.412 1.949 1.949 1.949 1.949 1.949 1.949
115 3.764 3.584 2.758 1.949 1.949 1.949 1.949 1.949 1.949
120 4.051 3.853 3.105 2.161 1.949 1.949 1.949 1.949 1.949
125 4.339 4.122 3.451 2.580 1.949 1.949 1.949 1.949 1.949
130 4.626 4.390 3.798 2.999 2.273 2.238 1.949 1.949 1.949
135 4.914 4.659 4.145 3.418 2.720 2.612 2.133 1.949 1.949
140 5.201 4.928 4.491 3.837 3.168 2.987 2.526 2.151 1.949
145 5.489 5.197 4.838 4.256 3.615 3.361 2.919 2.545 1.989
150 - 5.466 5.185 4.675 4.063 3.736 3.312 2.938 2.370
155 - - 5.531 5.094 4.510 4.110 3.705 3.332 2.751
160 - - - 5.513 4.958 4.485 4.097 3.725 3.132
165 - - - - 5.405 4.860 4.490 4.119 3.513
170 - - - - - 5.234 4.883 4.512 3.894
175 - - - - - 5.609 5.276 4.906 4.275

BF 1305MTA-A Rev 0.0 Page A5-2 of 2 ©BRE Global Ltd. 2015