Vous êtes sur la page 1sur 6

Relationship between

Sound Pressure
and Sound Power Levels
If we wish to know the sound power It is exactly the same for a fan. The
transmitted through a fan and ducting manufacturer can give the Fan Sound
system, it is preferable to take measure- Power Level (analogous to the kilowatts
ments ‘induct’ in accordance with ISO of a fire) and the user can then deter-
5136. Sometimes, however, it is necessary mine the Sound Pressure Level (analo-
to know the noise around the fan, which gous to the temperature) at a particular
may have broken out through its casing position, based on the dimensions of the
and local ducting or been emitted room, the position of the fan, the mate-
through an open inlet and/or outlet. rials of the room and their absorptive or
reflective properties.
In practice, the room dimensions will be
such that this noise will be absorbed or Unfortunately, both Fan Sound Power
reflected by the floor, walls and ceiling. If Levels and Sound Pressure Levels are
the room were fully anechoic, then all the expressed in decibels, but they are not
W. T. W. CORY sound would be absorbed by these surfa- the same decibels.
Chairman of the Eurovent ces. If the walls were hard, then the room
WG 1 “Fans” would be termed reverberant, and all the The decibel is only used to compress a
sound would be reflected. (Effectively, this wide range of absolute values into a
would mean that the same noise would manageable range. It is not an absolute
be measured more then once!). unit, but is a ratio. Without a reference
level, it means nothing. Its use is not
Real rooms are usually neither fully confined to acoustics and indeed it is
reverberant nor fully anechoic, but some- widely quoted in electro-technology,
where in between. It is then extremely vibration and in physics generally.
difficult to find a suitable position for
measuring the noise from a particular The definition of a decibel is:
Quantity measured
fan.
dB = 10 log10 ( Reference level )
The manufacturer is often asked to state
the Sound Pressure Level of his fan for a • For Fan Sound Power Levels the
particular duty. If the request for such reference level is 10 –12 Watts
information is specified at a particular • For Sound Pressure levels the reference
distance, then it might be anticipated that level is 2 ⫻ 10 –5 Pascals
an unambiguous answer could be given.
This is far from the case and qualifica- Thus, Fan Sound Power Level and Sound
tions to the answer have to be made Pressure Level are completely different
which may or may not be appropriate in quantities and should not be confused.
a real life situation. For preference, the former should be suf-
fixed with a W i.e. dBW, but this is rarely
To take the analogy of an electric fire, observed. Even rarer is to give the refe-
the manufacturer can specify its power in rence level, which is also unambiguous.
kilowatts, but the purchaser will need to
determine what particular temperature It will therefore be realised that the
will be achieved at a givean position in a Sound Pressure Level at a particular
room. This will be based on his expe- point in a room containing a fan can
rience or by calculation. Distance from only really be determined by the user,
the fire, its position in the room, how based on his particular knowledge of
well the room is insulated, whether there how and where the fan is installed.
are any reflective surfaces etc., etc., will However, specialist acoustical knowledge
all have an influence on the result. is not always available and the informa-

4
tion which follows is given to assist the NOTE 1 All of these symbols may be
user to make the necessary calculations. used to indicate levels in one third-
octave or octave frequency bands as
well as overall sound power levels and
Fan sound power levels vary according
A-weighted sound power levels provided
to installation category, whether measu-
that the sound power to which the sym-
red on the inlet or outlet, or breakout
bols relate is clearly defined.
from the casing together with any
ancillary motor noise. There are therefore
NOTE 2 Where noise from the drive may
at least noise levels associated with a fan
contribute to the noise radiated from
as follows:
a casing then this should be clearly stated
1) LW (Atot) by the addition of +dr e.g., LW (Dcas + dr).
total sound power level of a fan type
A installation (includes the contribu- NOTE 3 Not all of the above levels need
tions from the inlet, outlet, fan to be measured for a particular fan.
casing and drive).
The system designer needs to ask the fan
2) LW (Ain) manufacturer for the Sound Power Level
free-inlet sound power level; type A appropriate to the particular Installation
installation. Category for which the fan is to be used
and for the particular position at which it
3) LW (Aout)
will be measured. This will be determi-
free-outlet sound power level; type A
ned by whether the fan is fully ducted or
installation.
has an open inlet or outlet.
4) LW (Bin)
free-inlet sound power level; type B The formula connecting the sound pres-
installation. sure and sound power in a real room is:

5) LW (Bout)
free-outlet sound power level; type B
SPL = SWL + 10 log [ 4␲Q ␪r +
2
4
Rc ]
installation. Where:
6) LW (Bin+cas) SPL = Sound pressure level
free-inlet sound power level plus dB re 2 ⫻ 10 –5 Pa
casing radiated noise; type B installa- SWL = Sound power level
tion. dBW re 10 –12 W
7) LW (Bout) r = distance from the source m
ducted outlet sound power level; Q␪ = directivity factor of the source in
type B installation. the direction of r
S␣ av
8) LW (Cin) Rc = room constant = m2
1 – ␣ av
ducted inlet sound power level;
type C installation. S = total surface are of the room m2
9) LW (Cout) ␣ av = average absorption coefficient in
free-outlet sound power level; the room
type C installation
10) LW (Cout+cas) Position of source Directivity
free-outlet sound power level plus factor Q⍜
casing radiated noise; type C instal-
Near centre of room 1
lation.
11) LW (Din) At centre of floor 2
ducted inlet sound power level;
type D installation.
Centre of edge between
floor and wall 4
12) LW (Dout)
ducted outlet sound power level; Corner between two
type D installation. walls and floor 8
13) LW (Dcas)
casing radiated sound power level; Values of the directivity factor, assuming
type D installation. an unidentified source in a large room

5
The first term in brackets in the formula The value of the average absorption
is a measure of the direct sound under coefficient ␣ av can be calculated. If we
so call “free-field” conditions whilst the have an area S, of material in the room
second term is a measure of the reflected having an absorption coefficient ␣ 1, and
sound. area S2 with absorption coefficient ␣ 2, and
1
If the fan were positioned in the absolute so on, ␣ av = (S1 ␣1 + S2 ␣2 + S3 ␣3 + etc)
S
centre of a room i.e. equidistant from ␣ not only varies with the material, but
floor and ceiling, and equidistant from all also differs according to the frequency of
parallel walls, then for a small source the noise. It is therefore necessary to
relative to the room size, the sound calculate the SPL from the SWL in each
could be expected to radiate freely and frequency.
almost equally in all directions. The mea-
surement surface would then be the sur- Typical values of absorption coefficient ␣
face of a sphere i.e. 4␲r2 and the directi-
vity factor would be Q⍜ = 1. For special proprietary acoustic materials
and all other surface finishes, refer to the
If the fan were placed in the geometric manufacturers. If pressed, certain fan
centre of the floor for example, the manufacturers will quote the sound pres-
sound would only be radiated over a half sure level of their units at a specified dis-
sphere with a surface area of 2␲r 2. The tance – usually 1.5m or 3 impeller diame-
general formula could still be used by ters under ‘free field conditions’ and
making Q⍜ = 2. assuming spherical propagation. These
would exist if the fan were suspended
If the fan were placed at one side of the in space and there were no adjacent
room but still at the middle of a wall, floor or walls to either absorb or reflect
then the sound would be radiated over a the noise. Using the formula above,
quarter sphere with a surface area of ␲r 2. Q⍜ = 1 and Rc →⬁.
The general formula can then be used by 4
Thus SPL = SWL + 10 log =
making Q⍜ = 4. 4 ␲ r2
SWL – 10 log4 ␲ r 2
If the fan were placed in the corner of
the room at floor level then the sound and if r = 1.5 then SPL = SWL – 14.5 dB.
would be radiated over an eighth of the
␲r2 .
sphere with a surface area of The Other manufacturers calculate for ‘hemis-
2
general formula can then be used by pherical’ propagation under the same
making Q⍜ = 8. free field conditions, i.e. it is assumed
that the fan is mounted on a hard reflec-
It will be realised that whilst the sound ting floor. Q⍜ then equals 2.
power output of the fan for a specific duty Thus SPL = SWL + 10 log 2
=
will remain unchanged, the sound pres- 4 ␲ r2
sure level at a particular position as measu- SWL – 10 log2␲ r 2
red by a noise meter, for this reason
alone could vary by 10 log 8 = 9 dB, and if r = 1.5 then SPL = SWL – 11.5 dB.
according to where the installer decided
to site the fan. If the noise had a particu- For three diameters, knowing the impel-
larly enhanced directivity, or if the aspect ler diameter in metres, the difference in
ratio(s) of the room dimensions were far both cases may be calculated. Whilst
from even, then this value could be even these figures may be used as a basis for
more. Should the sound be reflected or comparison between different units cal-
absorbed, then it becomes more difficult culated in the same manner, it must be
to make the calculation, but further diffe- realised that the SPLs measured on site
rences of up to 20 dB between Sound with a meter may be either above or
Pressure Level and Fan Sound Power below these values. The actual result is
Level are possible. The system designer as much a function of the room cha-
must calculate the Sound Pressure Level racteristics as of the fan. The analogy
within the room, based on the Fan of an electric fire in a room with or
Sound Power Level provided by the Fan without heat losses should be remem-
manufacturer, the position of the fan bered. The internal areas of modern
within the room and the materials of commercial and industrial buildings have
the room walls, floor and ceiling, all of hard boundary surfaces which cause a
which he will know or will have high proportion of sound energy incident
decided. upon them to be reflected and a high
6
Material 63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz

Brick work .05 .05 .04 .02 .04 .05 .05 .05
Breezeblock .1 .2 .45 .6 .4 .45 .4 .4
Concrete .01 .01 .01 .02 .02 .02 .03 .03
Glazed tiles .05 .05 .05 .05 .05 .05 .05 .05
Plaster .04 .04 .05 .06 .08 .04 .06 .05
Rubber floor tiles .05 .05 .05 .1 .1 .05 .05 .05

reverberant sound pressure level to be Theoretically dBA values apply up to


built up. When this occurs, the sound levels of 55 dB only, dBB for levels
pressure level readings indicated on a between 55-85 dB only and dBC for
sound meter are independent of the higher levels only. dBD is reserved for
distance from the noise source. special noise, e.g., aircraft. However, dBA
is now used almost exclusively whatever
Understanding the difference between the level, and such levels are widely
sound power level and sound pressure quoted in legislation. Engineers should
level, the engineer must also know how check what weighting curves have been
acceptable levels of sound pressure can used by manufacturers and, if necessary
be specified. convert them to a common base before
comparisons are made.
It is inconvenient to quote a series of
sound values for each application. Efforts A, B, C and D weightings are useful for
therefore have been made to express making initial assessments (inexpensive
noise intensity and quality in one single sound level meters are available which
number. The ear reacts differently accor- measure directly on these scales), Unfor-
ding to frequency. All these single figure tunately too much information is lost in
indices therefore mathematically weight combining all the data into one figure for
the sound pressure level values at each it to be of use for calculation and design
octave band according to the ear’s work. Most noise control depends on
response at that frequency. frequency analysis.

dBA, dBB, dBC and dBD sound Sound absorbing or anechoic cham-
pressure levels bers
A, B, C, and D noise levels are an If we wished to make measurements in a
attempt to produce single number and free field without any reflections, then
sound pressure indices. To obtain them the top of a very tall but small cross-sec-
different values are subtracted from the tion flagpole in the middle of the Sahara
sound pressure levels in each of the fre- desert (after it had been raked flat)
quency bands, subtracting most from would probably be ideal. Obviously,
those bands which affect the ear least. there are difficulties and an anechoic
The results are then added logarithmi- room is a reasonable alternative. Here
cally to produce an overall single num- the walls, ceiling and floor are covered in
ber sound level. It must be emphasised, a highly sound absorptive material to
however, that this calculation should be eliminate any reflections. Thus, the SPL
the very last to be carried out i.e. after in any direction may be measured.
the effects of the room materials (reflec-
tive or absorbent) have been calculated Sound reflecting or reverberation
in each octave band. The ‘A’ weighting chamber
is by far the most popular and single This is the opposite of the anechoic
figures are widely quoted in legislation. chamber. All surfaces are made as hard
The ‘C’ weighting indicates the potential as possible to reflect the noise and all the
for hearing damage. The resulting noise walls are made at an angle to each other
levels are known respectively as dBA, so that there are no parallel surfaces.
dBB, dBC, and dBD. Thus the sound energy is uniform throu-
7
ghout the room and a ‘diffuse field’ when the distance is less than the wave-
exists. It is therefore possible to measure length of the lowest frequency emitted or
the SWL, but the SPL measurements in less than twice the greatest dimension of
any direction will be meaningless due to the fan, whichever is the greater. This is
the many reflections. Such rooms are termed the near field and should be
cheaper to build than anechoic chambers avoided.
and are therefore very popular.
Other errors arise if measurements are
made too far from the fan. Reflections
The real room from walls and other objects may be as
In practice we usually wish to make strong as the direct sound. Readings will
measurements in a room that is neither be impossible in this reverberant field. A
anechoic nor reverberant, but some- free field may exist between the reverbe-
where in between. It is then difficult to rant and near field and can be found by
find a suitable position for measuring the seeing if the level drops 6 dB for a dou-
noise from a particular source. When bling in distance from the fan. It is here
determining noise from a single fan, that measurements should be made.
several errors are possible. If you mea- Sometimes, however, conditions are so
sure too closely, the SPL may vary consi- reverberant or the room so small, that a
derably with a small change in position free field will not be present.

8
Fig. 1 – Sound in a free field (above)
and sound incident on a surface (below).

Fig. 2 – Sound in an anechoic chamber. Fig. 4 – Fan in a “real room”.

Fig. 3 – Sound in reverberation


chamber.
9

Vous aimerez peut-être aussi