MiCOM P543, P544, P545, P546

Version History
Firmware and Service Manual
Relay type: P54x …
Software
Version Hardware Original S1 Technical
Description of Changes
Suffix Date of Issue Compatibility Documentation
Major Minor
01 A A Feb 2000 First release to production V1.07 or Later TG8613A
9 PSB. Three settings added to set zone 6 to increase flexibility
9 Protection address. Universal address added
9 SEF & EF. Polarizing voltage setting range increased
9 Thermal. Setting range increased
9 Trip conversion logic. 3 DDB signals added to simplify logic
for users
02 A A Mar 2000 V1.08 or Later TG8613B
9 Distance. Min polarizing voltage increased to prevent tripping
for close up three phase faults
9 Check sync. angle measurement improved
9 PSB. Text for power swing indication improved
9 Include pole discrepancy logic to P543
9 Susceptance setting corrected
9 German text changed
9 Spanish text changed
9 Changes to DDB names & properties
9 Improvements in auto-reclose and reset from lockout code
03 A A May 2000 V1.09 or Later TG8613B
9 Changes to pole dead & trip conversion logic
9 Changes to P544 circuit breaker fail logic

P54x/EN VH/I74
9 Added DDB for CS103 test mode

(VH) 16-1
8 Recommend upgrading to 03B software or later
VH