Correct Metrosil selection ensures that the system is held to
1
a safe clamping voltage under fault conditions, whilst having β
negligible effect on the measurement accuracy of the relay. VrmV2
Irms = 0.52
C
CHOOSING THE CORRECT METROSIL
The procedure for selecting the correct relay Metrosil type is Use minimum C value and β of 0.25
broken down into the following 5 step process:-
Equation 2 - For applied sinusoidal currents:-
Step 1 - Identify the relevant tables for the application
Vpeak = 1.09C(Irms) β
For a 1A CT with maximum internal secondary fault currents of
up to 50Arms, tables 1 and 2 apply (see page 2). Use maximum C value and β of 0.25.
For a 5A CT with maximum internal secondary fault currents of Operating conditions for the majority of high impedance relays
up to 150Arms, tables 3 and 4 apply (see page 3). offered by M&I Materials Ltd are given within this data sheet.
Where your condition requirements are not covered, M&I
Step 2 - Identify the Metrosil type code Materials can recommend other Metrosils.
Using the maximum relay setting voltage and maximum To take advantage of this service, please supply the following
internal secondary fault current, identify the recommended information:-
Metrosil type code from tables 1 or 3. • Nominal rating of the CT (1A, 5A)
• Relay setting voltage (across the relay and stabilising
For a 1A CT, decide if a single pole or a triple pole (3-phase) resistor)
Metrosil type is required. • Maximum permissible leakage current at relay setting
voltage
Step 3 - Check the maximum permissible leakage • Maximum secondary internal fault current
• Maximum permissible clamping voltage under fault
At the relay setting voltage, check that the maximum conditions
leakage current for the identified Metrosil type is within the • Maximum fault time duration, if > 0.5 seconds
permissible limits of the relay system. • CT Ratio, particularly the secondary rating
Any recommendation or suggestion relating to the use, storage, handling or properties of the products supplied by the M&I Materials Group of Companies
either in sales and technical literature or in response to a specific enquiry or otherwise is given in good faith, but it is for the customer to satisfy itself of the
suitability of the product for its own particular purposes. © M&I Materials 2018.
JANUARY 2018
PAGE 2/4
125
185
300
1088/R2/600A/S1 1195/R1/600A/S3/I
325
125 19
256/R4/600A/S1
175 73 405/495 1435 45 30 22 200
802/600A/S3/I
185 90
1088/R2/600A/S1 300 30
810/990 2870 39 30 17 350
1195/R1/600A/S3/I 325 50
6315/R0/600A/S1
400 55 990/1210 3500* 46 26 19 425
6324/R0/600A/S3/I
Table 2 - Leakage Current, Protection Voltage and Short Time Currents for 1A Relay Metrosils with Maximum Internal Secondary Fault Current of 50Arms
*600A-A/S1/6315 will hold to 3400Vpk at peak of 46Arms and 3000Vpk at peak of 30Arms
All properties quoted in this table are typical values and do not constitute a specification
Any recommendation or suggestion relating to the use, storage, handling or properties of the products supplied by the M&I Materials Group of Companies
either in sales and technical literature or in response to a specific enquiry or otherwise is given in good faith, but it is for the customer to satisfy itself of the
suitability of the product for its own particular purposes. © M&I Materials 2018.
JANUARY 2018
PAGE 3/4
250 1220/R2/600A/S2/P
1214/R2/600A/S1 1215/R2/600A/S2/P
275 1221/R0/600A/S3/P
250 40
1214/R2/600A/S1 670/800 2120 50 25 18 290
275 50
250 75
1215/R2/600A/S2/P 570/670 2120 90 50 35 290
275 100
Table 4 - Leakage Current, Protection Voltage and Short Time Currents for 5A Relay Metrosils with Maximum Internal Secondary Fault Current of 150Arms
All properties quoted in this table are typical values and do not constitute a specification
Any recommendation or suggestion relating to the use, storage, handling or properties of the products supplied by the M&I Materials Group of Companies
either in sales and technical literature or in response to a specific enquiry or otherwise is given in good faith, but it is for the customer to satisfy itself of the
suitability of the product for its own particular purposes. © M&I Materials 2018.
JANUARY 2018
PAGE 4/4
80°
M6 ISO Terminals
152mm 180mm
60°
M6 ISO Terminals
10
1m
m
107mm
Insulating Spacer
190mm ±/-7mm
152mm 240mm
80°
M6 ISO Terminals
10
1m
107mm
m
240mm
metrosil.com
SALES ENQUIRIES TECHNICAL ENQUIRIES
Tel: +44 (0)161 864 5456 Tel: +44 (0)161 864 5462
e-mail: metrosilsales@mimaterials.com e-mail: metrosiltech@mimaterials.com
Any recommendation or suggestion relating to the use, storage, handling or properties of the products supplied by the M&I Materials Group of Companies
either in sales and technical literature or in response to a specific enquiry or otherwise is given in good faith, but it is for the customer to satisfy itself of the
suitability of the product for its own particular purposes. © M&I Materials 2018.