Calcular protecciones, conductores y ductos, y dibujar el diagrama unifilar

para la siguiente instalación:


-1 Motor 2 Hp 220 V
-1 Motor 1 Hp 127 V
-1 Motor ¼ Hp 127 V
-10 Lámparas 127 V
-10 Contactos 127 V

Motor 2 Hp 220 V
𝑃 = 2 ℎ𝑝(746) = 1492 𝑊
𝐼𝑛𝑜𝑚 = 1492 𝑊/220 𝑉 = 6.8 𝐴
𝐼𝑎𝑟𝑟 = 6.8 𝐴(1.25) = 8.5 𝐴
ITM: 2x15 A
Conductor: TW 2 - 14 AWG Fases, 1 – 14 AWG Tierra
Conduit: IMC 1 – 16 (1/2”)

Motor 1 Hp 127 V
𝑃 = 1 ℎ𝑝(746) = 746 𝑊
𝐼𝑛𝑜𝑚 = 746 𝑊/127 𝑉 = 5.9 𝐴
𝐼𝑎𝑟𝑟 = 5.9 𝐴(1.25) = 7.4 𝐴
ITM: 1x15 A
Conductor: TW 1 - 14 AWG Fase, 1 – 14 AWG Neutro, 1 – 14 AWG Tierra
Conduit: IMC 1 – 16 (1/2”)

Motor ¼ Hp 127 V
𝑃 = 0.25 ℎ𝑝(746) = 186.5 𝑊
𝐼𝑛𝑜𝑚 = 186.5 𝑊/127 𝑉 = 1.5 𝐴
𝐼𝑎𝑟𝑟 = 1.5 𝐴(1.25) = 1.9 𝐴
ITM: 1x15 A
Conductor: TW 1 - 14 AWG Fase, 1 – 14 AWG Neutro, 1 – 14 AWG Tierra
Conduit: IMC 1 – 16 (1/2”)

Lámparas 127 V (79 W c/u + 25% consumo del balastro)


𝑃 = 79 𝑊(1.25) = 98.75 𝑊
𝑃𝑡𝑜𝑡𝑎𝑙 = 98.75 𝑊(10) = 987.5 𝑊
𝐼 = 987.5 𝑊/127 𝑉 = 7.8 𝐴
ITM: 1x15 A
Conductor: TW 1 - 14 AWG Fase, 1 – 14 AWG Neutro, 1 – 14 AWG Tierra
Conduit: IMC 1 – 16 (1/2”)
Contactos 127 V (180 W c/u)
𝑃𝑡𝑜𝑡𝑎𝑙 = 180 𝑊(10) = 1800 𝑊
𝐼 = 1800 𝑊/127 𝑉 = 14.2 𝐴
ITM: 1x20 A
Conductor: TW 1 - 12 AWG Fase, 1 – 12 AWG Neutro, 1 – 12 AWG Tierra
Conduit: IMC 1 – 16 (1/2”)

Centro de carga y balanceo de cargas


Se requiere un centro de carga 2F 3H debido al motor bifásico de 2 Hp. Para determinar el
número de circuitos derivados que se requieren del centro de carga, se necesita hacer un
balanceo de cargas para que las fases queden lo más balanceadas posible.
Equipo Carga [W] Circuitos Fase 1 Fase 2
Motor 2 hp 220 v 1492 2 1 1
Motor 1 hp 127 v 746 1 1
Motor 1/4 hp 127 v 186.5 1 1
Contactos 127 v 1800 1 1
Lámparas 127 v 987.5 1 1
Como se necesitan 4 circuitos derivados en 1 fase y 2 en otra, se selecciona un centro de
carga QOD8F 2F3H 8 circuitos derivados.

Diagrama unifilar