The receiver tank from truck deliveries as designed has a capacity of 10m 3, although a
typical volume delivery of 9000 gallons (34.065m3) of diesel will be transferred per
delivery. The purpose of the tank is to be a staging unit that will pump up the fuel to the
main storage unit until the volume reaches a quarter or half of its total capacity. The
dimensions are decided by the designer himself since the standard tank dimensions for
aboveground tanks does not cover the capacity of the receiver (API lowest standard
capacity of 90m3, where the capacity of the receiver is only 10m 3). The tank will be
For calculating the dimensions, an assumed diameter of 1.5m is used. The assumed
𝐷2
𝑉𝐴𝑅/𝑂𝑇 =𝜋 𝐿
4
(1.5)2
10 𝑚3 = 𝜋 𝐿
4
𝑳 = 𝟓. 𝟔𝟔 𝒎
For ullage of 30%, the length will be increased to 6m (10.6m 3 actual volume), which will