AREA 277 : INCORRECT DESCRIPTIONS AND PLACEMENT OF INSTRUMENTS,ETC.

POSITION OBSERVATION/COMMENT ACTION TAKEN/REQUIRED/CORRECTION MADE / COMMENT


P-048 Plant Loop description Diff. Press over Scrubber No:2 Demister Indication Loop Description Changed to Scrubber 3
P-068 Plant Loop description Diff. Press over Scrubber No:2 Demister Indication Loop description Changed to Scrubber 4

P-085 PRESSURE ALARM SHOWN ON P&ID AS = PAL-001 Position P-001 deleted changed to PAL-085
L-009 ZSHL-009 IS SHOWN UNDER POSITION Z Should also be under Position L-009 - MOVED
L-029 ZSHL-029 IS SHOWN UNDER POSITION Z Should also be under Position L-029 -MOVED
L-049 ZSHL-049 IS SHOWN UNDER POSITION Z Should also be under Position L-049 - MOVED
L-069 ZSHL-069 IS SHOWN UNDER POSITION Z Should also be under Position L-069 -MOVED.

K-024 KV-024 - VALVE ON P&ID BUT NO. NUMBER "BUBBLE" CORRECTED


ZSH/L-024 UNDER SEPARATE Z-024 POSITION MOVED TO K-POSITIONS

K-001 TO K-066 ALL K POSITIONS IN THIS AREA


ZSH/L UNDER SEPARATE Z POSITIONS SHOULD BE UNDER THE K "PARENT" POSITION TRANSFERRED.
ZSH/L CHANGED TO KZSHL
AREA 296 : INCORRECT DESCRIPTIONS AND PLACEMENT OF INSTRUMENTS,ETC.
POSITION OBSERVATION /COMMENT ACTION TAKEN/REQUIRED/CORRECTION MADE / COMMENT
A-011 ONLY POSITIONS IN DATABASE BUT NO FUNCTIONS CREATED FUNCTIONS & LOOP CREATED
F-005 NO ZSH/ZSL INSTRUMENTS UNDER F-POSITION = UNDER Z MOVED TO POSITION -F-005
POSITION SHOWN AS FXV-022 ON LOOP & ON P&ID IT IS X-022 INSTRUMENTS ON
F-022 DATABASE = XV, XC, XXV, XZHL SITE TO ADVISE STATUS - F or X ??
F-092 Loop exists on COMOS. Loop drawing not received from site. Position not on IO List. Site to advise
F-122 NO ZSH/ZSL INSTRUMENTS UNDER F-POSITION = UNDER Z MOVED
F-223 NO IN LINE FLOW ELEMENT SHOWN ON P&ID SITE TO ADVISE TYPE OF FLOWMETER
F-225 MAGFLO UNDER POSITION F-230 (SHOULD BE F-225) MOVED TO POSITION F-225
F-230 NO LOOP DRAWING RECEIVED INSTRUMENTS ARE ON P&ID
F-323 NO LOOP DRAWING RECEIVED INSTRUMENTS ARE ON P&ID
F-324 NO LOOP DRAWING RECEIVED INSTRUMENTS ARE ON P&ID
F-325 NO LOOP DRAWING RECEIVED INSTRUMENTS ARE ON P&ID
F-335 NO LOOP DRAWING RECEIVED INSTRUMENTS ARE ON P&ID
F-340 NO LOOP DRAWING RECEIVED INSTRUMENTS ARE ON P&ID
F-343 NO LOOP DRAWING RECEIVED INSTRUMENTS ARE ON P&ID

I-061 to I-322 NO LOOP DRAWINGS RECEIVED INSTRUMENTS ARE ON P&ID - ARE LOOPS REQUIRED FOR THESE POSITIONS?

K-006 to K-310 LIMITS FOR THESE VALVES ZSHL WERE CREATED UNDER SEPARATE Z-POSITIONS SHOULD BE UNDER THE K- POSITION - TOTAL 0F 34 MOVED
K-051 NO LOOP DRAWING RECEIVED SITE TO ADVISE REQUIRED ACTION
K-131 Loop Reads Crystalliser Trans Air Drier No.2 "Inlet Valve" Changed toCrystalliser Trans Air Drier No.1 Inlet Valve
K-131 Loop Reads Crystalliser Trans Air Drier No.2 "Discharge Valve" Changed to Crystalliser Trans Air Drier No.1 "Discharge Valve"
K-153 LOOP 296-K-153 NO POSITION OR INSTRUMENTS IN DATABASE SITE TO ADVISE REQUIRED ACTION - POSITION CREATED
K-195 LOOP 296-K-195 NO POSITION OR INSTRUMENTS IN DATABASE SITE TO ADVISE REQUIRED ACTION - POSITION CREATED
K-201 to K-310 NO LOOP
LOOPS DRAWINGS
SHOWS ON/OFF RECEIVED (TOTAL
VALVE WITH OF 6-POSITIONS
LIMITS EXIST INMODULATING
THE P&ID SHOWS DATABASE) VALVE SITE TO ADVISE REQUIRED ACTION
L-016 (PY) SITE TO ADVISE CORRECT TYPE
L-087 LEVEL VALVE LIMITS UNDER Z-POSITION MOVED TO L-POSITION
L-206 NO LOOP DRAWING RECEIVED SITE TO ADVISE REQUIRED ACTION

L-229 LOOP DWG RECEIVED BUT NO POSITION L-229 OR INSTRUMENTS IN DATABASE SITE TO ADVISE REQUIRED ACTION
L-312 to L-350 NO LOOP DRAWING RECEIVED SITE TO ADVISE REQUIRED ACTION

PIT-1-015 (2 x POSITIONS UNDER P-015?) = DUPLICATE AND NOT PART OF THIS LOOP -
P-015 NEW L-POSITION MUST BE ALLOCATED TO CANCELL DUPLICATION SITE TO ADVISE REQUIRED ACTION
P-077 LOOP DWG RECEIVED BUT NO POSITION L-077 OR INSTRUMENTS IN DATABASE SITE TO INVESTIGATE AND ADVISE LOCATION OF INSTRUMENT
P-187 LOOP DWG RECEIVED BUT NO POSITION P-187 OR INSTRUMENTS IN DATABASE SITE TO INVESTIGATE AND ADVISE LOCATION OF INSTRUMENT

P-330 NO LOOP DRAWING RECEIVED SITE TO ADVISE REQUIRED ACTION


P-332 LOOP IN DATABASE BUT INSTRUMENTS NOT ON A P&ID??? SITE TO INVESTIGATE AND ADVISE LOCATION OF INSTRUMENT
P-341 NO LOOP DRAWING RECEIVED SITE TO ADVISE REQUIRED ACTION
P-344 NO LOOP DRAWING RECEIVED SITE TO ADVISE REQUIRED ACTION
P-345 NO LOOP DRAWING RECEIVED SITE TO ADVISE REQUIRED ACTION

S-210 LOOP DWG RECEIVED BUT NO POSITION S-210 OR INSTRUMENTS IN DATABASE SITE TO INVESTIGATE AND ADVISE LOCATION OF INSTRUMENT
S-211 LOOP DWG RECEIVED BUT NO POSITION S-211 OR INSTRUMENTS IN DATABASE SITE TO INVESTIGATE AND ADVISE LOCATION OF INSTRUMENT
S-211 LOOP DWG RECEIVED BUT NO POSITION S-212 OR INSTRUMENTS IN DATABASE SITE TO INVESTIGATE AND ADVISE LOCATION OF INSTRUMENT
S-231 NO LOOP DRAWING RECEIVED SITE TO ADVISE REQUIRED ACTION
S-346 NO LOOP DRAWING RECEIVED SITE TO ADVISE REQUIRED ACTION

ADDITIONAL INSTRUMENTS WERE CREATED UNDER THIS POSITION USING


UNDERSCORE TE_1-038 THIS IS NOT PERMITTED IN COMOS. IS THIS A COMBINATION
OF INSTRUMENTS?? IF NOT, SEPARATE POSITION MUST BE ALLOCATED. ALSO SEE
T-038 SIMILAR T-042. SITE TO ADVISE REQUIRED ACTION

SUGGESTION : AS TDAH-039 MEASURES THE DIFFERENTIAL TEMPERATURE


BETWEEN T-004 & T-039 THESE INSTRUMENTS BE COMBINED UNDER ONE P-
POSITION WITH THE INLET AND OUTLET ELEMENTS PLACED UNDER A & B
T-039 & 004 TDAH-039 MEASURES THE DIFFERENTIAL TEMPERATURE BETWEEN T-004 & T-039 RESPECTIVELY.

ADDITIONAL INSTRUMENTS WERE CREATED UNDER THIS POSITION USING


UNDERSCORE TE_1-042 THIS IS NOT PERMITTED IN COMOS. IS THIS A COMBINATION
T-042 OF INSTRUMENTS?? IF NOT, SEPARATE POSITION MUST BE ALLOCATED. SITE TO ADVISE REQUIRED ACTION

T-197 NO LOOP DRAWING RECEIVED SITE TO ADVISE REQUIRED ACTION


T-311 to T-326 NO LOOP DRAWINGS RECEIVED SITE TO ADVISE REQUIRED ACTION
T-334 NO LOOP DRAWING RECEIVED SITE TO ADVISE REQUIRED ACTION
T-342 NO LOOP DRAWING RECEIVED SITE TO ADVISE REQUIRED ACTION
T-343 CREATED BY SITE TO CANCELL OUT DUPLICATION (ASA) LOOP DRAWING REQUIRED SITE TO PROVIDE LOOP DWG.
V-315 NO LOOP DRAWING RECEIVED SITE TO ADVISE REQUIRED ACTION

X-003 ZSHL-003 IS SHOWN UNDER POSITION Z MOVED TO X-POSITION


X-026 ZSHL-026 IS SHOWN UNDER POSITION Z MOVED TO X-POSITION
X-206 LOOP RECEIVED BUT NO POSITION OR INSTUMENTS IN DATABASE SITE TO INVESTIGATE AND ADVISE LOCATION OF INSTRUMENT
X-207 LOOP RECEIVED BUT NO POSITION OR INSTUMENTS IN DATABASE SITE TO INVESTIGATE AND ADVISE LOCATION OF INSTRUMENT

X-209 to X-213 NO LOOP DRAWINGS RECEIVED - ARE LOOPS REQUIRED? SITE TO ADVISE REQUIRED ACTION

ALL Z-POSTIONS THAT CONTAINED THE LIMITS FOR VALVES HAVE BEEN MOVED TO
CORRECT POSITIONS AND THE VACANT Z-POSITIONS HAVE BEEN DELETED.
ALL THE FOLLOWING INSTRUMENTS (ON THE MVR FAN) ARE SHOWN ON THE RBMR LOOP DRAWINGS TO
BE WIRED TO EQUIPMENT BOXES 296-EQ-201 AND 202 RESPECTIVELY. WHAT ARE THESE BOXES?
296-FSL-157
296-FSL-158
296-FSL-197
296-LSL-170
296-LSL-171
296-PSL-169
296-PDSL-187
296-TT-159
296-TT-160
296-TT-166
296-TT-183
296-TT-186
296-VT-167
296-TT-163
296-TT-164
296-TT-165
in the file it is called a terminal strip