WN-35BS
Residual current monitor
for monitoring AC, DC and pulsed DC currents
in earthed and resistance earthed systems
Software version D309 V1.0x
RCMA421H_D00069_00_M_XXEN/05.2014
Bender GmbH & Co. KG
P.O. Box 1161 • 35301 Gruenberg • Germany
Londorfer Str. 65 • 35305 Gruenberg • Germany
Tel.: +49 6401 807-0
Fax: +49 6401 807-259
E-Mail: info@bender.de
Web: http://www.bender.de
RCMA421H_D00069_00_M_XXEN/05.2014 3
Table of Contents
4 RCMA421H_D00069_00_M_XXEN/05.2014
1. Making effective use of this document
To make it easier for you to understand and revisit certain sections of text and
instructions in the manual, we have used symbols to identify important in-
structions and information. Examples of how such symbols are used appear
below:
RCMA421H_D00069_00_M_XXEN/05.2014 5
Making effective use of this document
6 RCMA421H_D00069_00_M_XXEN/05.2014
2. Safety instructions
RCMA421H_D00069_00_M_XXEN/05.2014 7
Safety instructions
8 RCMA421H_D00069_00_M_XXEN/05.2014
3. Function
RCMA421H_D00069_00_M_XXEN/05.2014 9
Function
The device will check the circuit for the presence of residual currents even dur-
ing the self test.
An external measuring current transformer (e.g. WN-35BS) is used for residual
current measurement. The actual measured value is indicated on the LCD. If
the rated residual operating current of 6 mA is exceeded, the alarm relay K2
will change to the alarm state and the TRP alarm LED will light up.
Once the alarm relay has switched, the residual current must fall to less than
the rated residual operating current.
If it does not, error code E.04 will appear on the display and the ERR alarm LED
will flash. This means that the connected contactor has not shut down the
faulty circuit.
If the residual current falls below the release value, the error will continue to
be signalled due to the permanently activated fault memory. The alarm relay
K2 will not switch back to the initial state and the TRP alarm LED will not go
out until the reset button R is pressed or the power supply voltage is interrupt-
ed.
Parameters are assigned to the device via the LCD and the control buttons on
the front panel; this function can be password-protected.
10 RCMA421H_D00069_00_M_XXEN/05.2014
Function
3.2.5 Malfunction
In the event of an internal malfunction, the TPD alarm LED will light and the
ERR alarm LED will flash. An error code will appear on the display until the fault
is removed. Refer to page 30 for details about error codes.
RCMA421H_D00069_00_M_XXEN/05.2014 11
Function
12 RCMA421H_D00069_00_M_XXEN/05.2014
4. Installation and connection
Make sure that the installation area has been de-energised and
ensure compliance with the regulations for working on electri-
cal installations.
The front plate cover is easy to open at the lower part marked by an arrow.
RCMA421H_D00069_00_M_XXEN/05.2014 13
Installation and connection
35
99,50
71
42
57
90
79
4,6
37 0
Dimensions in mm
14 RCMA421H_D00069_00_M_XXEN/05.2014
Installation and connection
21 22 24
T2 T T/R R T/R R
T
Terminal Connections
A1, A2 Connection to the power supply
1 Bush for measuring current transformer's connecting cable
T1, T2 Test connections for internal monitoring circuit
T, T/R, R Connections for external test and reset button
21, 22, 24 Alarm relay K2: Connection to contactor or load switch
WN-…BS Measuring current transformers
K1 Recommended contactors are listed in the table on page 31
RCMA421H_D00069_00_M_XXEN/05.2014 15
Installation and connection
Pin Pin
Colour Colour
assignment assignment
brown K1 black I1
orange K2 red I2
pink T violet T
4.3 Commissioning
Checks must be carried out prior to commissioning to ensure that the residual
current monitor, the external measuring current transformer and the associ-
ated contactors and peripherals have been connected correctly.
16 RCMA421H_D00069_00_M_XXEN/05.2014
5. Operation and configuration
RCMA421H_D00069_00_M_XXEN/05.2014 17
Operation and configuration
18 RCMA421H_D00069_00_M_XXEN/05.2014
Operation and configuration
Call up menu/submenu
Apply modified parameter value
ENTER/ Press and hold down button for
Menu more than 1.5 seconds: Call up
MENU menu/exit menu/go to next highest
submenu
RCMA421H_D00069_00_M_XXEN/05.2014 19
Operation and configuration
The text “tES“ appears on the display along with all avail-
able display elements.
20 RCMA421H_D00069_00_M_XXEN/05.2014
Operation and configuration
RCMA421H_D00069_00_M_XXEN/05.2014 21
Operation and configuration
22 RCMA421H_D00069_00_M_XXEN/05.2014
Operation and configuration
Change pa-
Change/activate/ Change/apply
SEt menu Select submenu
deactivate param.
rameter value
param.
display
1. Activate
password
protection
and assign
password (3-
digit numeri-
cal code)
2. Change pass-
word
RCMA421H_D00069_00_M_XXEN/05.2014 23
Operation and configuration
Change pa-
Change/activate/ Change/apply
SEt menu Select submenu
deactivate param.
rameter value
param.
display
3. Deactivate
password
protection
4. Switch sub-
menu
5. Restore
factory set-
ting
6. Switch sub-
menu
7. System menu
(is locked)
24 RCMA421H_D00069_00_M_XXEN/05.2014
Operation and configuration
Change pa-
Change/activate/ Change/apply
SEt menu Select submenu
deactivate param.
rameter value
param.
display
8. Switch sub-
menu
9. Go back to
SEt menu
5.7.4 Querying and erasing the fault memory in the HIS menu
1. Select the HIS menu.
2. Select the saved error and erase if applicable.
3. To go back to the menu level, press and hold down the ENTER button
for more than 1.5 seconds.
1. Error:
Rated residual operating cur-
rent exceeded
RCMA421H_D00069_00_M_XXEN/05.2014 25
Operation and configuration
26 RCMA421H_D00069_00_M_XXEN/05.2014
6. Technical data
RCMA421H_D00069_00_M_XXEN/05.2014 27
Technical data
Displays, memory
Display range. AC/DC measured value ........................................................................................................ 0…40 mA
Resolution of setting ........................................................................................................................................... 0.1 mA
Error of indication 0…20 Hz ...................................................................................... -33 %…+100 % / ± 2 digits
Error of indication 20…90 Hz .................................................................................................. 0…20% / ± 2 digits
Error of indication 90…150 Hz ................................................................................................. ±17.5 % / ± 2 digits
Error of indication at IΔ < 2 mA..................................................................................................................... ± 7 digits
Measured value memory for alarm value (HiS) ................................................................... Measured values data set
Password .................................................................................................................................... off / 0…999/ 0 (off)*
Cable length, WN-35BS measuring current transformer
Cable length ............................................................................................................................................................ 0.5m
Switching elements
Number of switching elements .................................................................................................. 1 changeover contact
Operating principle ........................................................................................................................... N/C operation n.c.
Electrical service life under rated operating conditions........................................................... 10000 switching cycles
Contact data acc. to IEC 60947-5-1
Utilisation category...............................................................AC-13..........AC-14......... DC-12......... DC-12 ....... DC-12
Rated operational voltage......................................................230V .......... 230V ............ 24V .......... 110V ........ 220 V
Rated operational voltage UL ................................................200V .......... 200V ............ 24V .......... 110V ........ 200 V
Rated operational current..........................................................5 A...............3 A.............. 1 A........... 0.2 A ......... 0.1 A
Minimum contact rating ........................................................................................................... 1 mA at AC/DC ≥ 10 V
Environment / EMC
EMC ....................................................................................................................................................................... UL943
Operating temperature ...................................................................................................................... -35 ºC…+66 ºC
Climatic class acc. to IEC 60721
Stationary use (IEC 60721-3-3) ........................................................ 3K5 (except condensation and formation of ice)
Transport (IEC 60721-3-2) ............................................................... 2K3 (except condensation and formation of ice)
Long-term storage (IEC 60721-3-1) ................................................ 1K4 (except condensation and formation of ice)
Classification of mechanical conditions acc. to IEC 60721:
Stationary use (IEC 60721-3-3) ...............................................................................................................................3M4
Transport (IEC 60721-3-2) ..................................................................................................................................... 2M2
Long-term storage (IEC 60721-3-1) ...................................................................................................................... 1M3
28 RCMA421H_D00069_00_M_XXEN/05.2014
Technical data
Connection
For UL application................................................................................................ use 60/70°C copper conductors only
Connection type ............................................................................................................................... screw terminals
rigid/ flexible/ conductor sizes ................................................................. 0.2…4 / 0.2…2.5 mm2 / AWG 24…12
Multi-conductor connection (2 conductors with the same cross section)
rigid, flexible ....................................................................................................................... 0.2…1.5 / 0.2…1.5 mm2
Stripped length ............................................................................................................................................. 8…9 mm
Tightening torque.................................................................................................................................... 0.5…0.6 Nm
Connection type ....................................................................................................................... push-wire terminals
Connection properties:
rigid ........................................................................................................................... 0.2…2.5 mm2 (AWG 24…14)
Flexible without ferrules ........................................................................................... 0.2…2.5 mm2 (AWG 24…14)
Flexible with ferrules ................................................................................................ 0.2…1.5 mm2 (AWG 24…16)
Stripped length ................................................................................................................................................... 10 mm
Opening force........................................................................................................................................................... 50 N
Test opening, diameter....................................................................................................................................... 2.1 mm
Other
Operating mode continuous operation
Position of normal use.......................................................................................................................... display-oriented
Degree of protection, internal components (IEC 60529) .........................................................................................IP30
Degree of protection, terminals (IEC 60529) ............................................................................................................IP20
Enclosure material .................................................................................................................................... polycarbonate
Flammability class ............................................................................................................................................. UL94V-0
DIN rail mounting acc. to................................................................................................................................. IEC 60715
Screw fixing.......................................................................................................................... 2 x M4 with mounting clip
Software version ............................................................................................................................................ D309 V1.0
Weight RCMA421H ........................................................................................................................................... ≤ 150 g
Weight WN-35BS ............................................................................................................................................. ≤ 355 g
( )* = factory setting
RCMA421H_D00069_00_M_XXEN/05.2014 29
Technical data
After removing the CT mains connector, the error code E.03 / E.04 alternately
appears on the display.
The error code will be erased automatically once the error has been
eliminated.
30 RCMA421H_D00069_00_M_XXEN/05.2014
Technical data
A16-30-10-84 3 1
A26-30-10-84 3 1
A40-30-10-84 3 1
A75-30-00-84 3
A110-30-00-84 3
A145-30-00-84 3
A16-30-10-34 3 1
A26-30-10-34 3 1
A40-30-10-34 3 1
A75-30-00-34 3
A110-30-00-34 3
A145-30-00-34 3
A16-40-00-84 4
A26-40-00-84 4
A45-40-00-84 4
A75-40-00-84 4
EK150* -40-22 4 2 2
A16-40-00-34 4
A26-40-00-34 4
A45-40-00-34 4
A75-40-00-34 4
EK150** -40-22 4 2 2
RCMA421H_D00069_00_M_XXEN/05.2014 31
Technical data
264; 0,0250
CLASS A 60Hz ac
30; 0,560
6; 5,594
260
240
220
200
180
160
140
I / mA
120
100
80
60
40
20
0
10,00
1,00
0,10
0,01
T/s
32 RCMA421H_D00069_00_M_XXEN/05.2014
Technical data
RCMA421H-D2
AC/DC 70…300 V
Supply voltage Us*
AC 42…460 Hz
RCMA421H accessories
Mounting clip for screw fixing (1 per device)........................................................................................... B 9806 0008
RCMA421H_D00069_00_M_XXEN/05.2014 33
Technical data
34 RCMA421H_D00069_00_M_XXEN/05.2014
INDEX
A I
Accessories 33 Installation and connection 13
B M
Button functions 19 Malfunction 11
Manual, target group 5
C Menu, settings 21
Commissioning 16 Multi-conductor connection 29
Conductor colours for measuring current
transformer 16 O
Operation and configuration 17
D Ordering information 33
Description of function 9
Device features 9 P
Device test 9 Parameter setting
Dimension diagrams 13 - Activating or deactivating the pass-
word protection 23
E Password protection 11
Error codes 30 Push-wire terminal 29
F Q
Factory setting 12, 16 Querying and erasing the fault memory 25
Quick query of the rated residual operating
H current 10
HiS menu 25
History memory 12 R
How to use this manual 5 Recommended contactors 31
Response times 32
Restore factory settings 24
RCMA421H_D00069_00_M_XXEN/05.2014 35
RS-485 interface 13
S
screw terminals 29
Self test, automatic 11
Self test, manual 11, 20
Set bus address 23
SEt menu 23
T
Technical data 27
To call up the menu 20
To exit the menu 20
W
Wiring diagram 15
Work activities on electrical installations 7