Académique Documents
Professionnel Documents
Culture Documents
condensed between the ICP and the accumulator, the significant losses in throughput, as well as severe
downstream pH will generally be higher than at the under-deposit corrosion.
ICP. Because of this reason, and the natural pH
As it can be determined from the situation described
variability discussed above, a control range for the
above, a natural consequence of manual pH
accumulator of 5.5-6.5 is generally recommended.
measurement and neutralizer pump adjustment in the
overhead is that both transient chloride and amine
case study variations are often missed, contributing to the
A U.S. refiner had been experiencing severe amine described problems. Prior to the availability of
chloride salting and associated corrosion in their reliable in-line data-gathering devices; coupled with
overhead trays over the past several years. This was automated, real-time chemical feed equipment, this
true, even though a relatively small amount of inefficient practice of manual control has historically
neutralizing amine was being fed (< 1 gpd, or 3.8 lpd). been the norm.
solution
To address the problems described above, the SUEZ
TrueSense for Process – Crude Overhead Monitoring
System, or COMS, was installed and commissioned.
This system has the capability to accurately monitor
pH and adjust the neutralizer pump automatically in
real-time. The on-board wireless gateway also allows
connectivity with SUEZ’s InSight* platform, which is a
cloud-based knowledge management system for
constant monitoring and visualization of results.
Example of fouling in a crude unit overhead system
caused by amine salting.
Page 2 CS1442EN.docx
The InSight knowledge management system demonstrated the minimal variation between COMS’ two on-board pH probes.
CS1442EN.docx Page 3