Industry Committee for
Emergency Lighting
Emergency lighting
1 Types of product
The aim of emergency lighting is to enable lumens. In addition to fittings designed for normal luminaires for emergency use.
people to exit quickly, safely and without interior use in corridors, specialised Compliance with this standard is important
panic from any location in a building to a luminaires are available for vandal-resistant, to ensure that, when the fitting has been
place of safety in the event of an emergency weatherproof and exit sign applications. converted, the components are all kept
involving failure of the normal lighting within their rated temperature limits and
b) emergency variant of normal lighting
supply. This is met by providing sufficient that European legislative requirements for
illuminance along the escape routes, For aesthetic reasons, it is becoming electromagnetic compatibility and CE
typically of at least 1 lux, to enable the increasingly popular to use an emergency marking are observed.
occupants to use the most direct path and to variant of the normal lighting. In these
c) central power systems
avoid obstacles and, where necessary, fittings, a charger, changeover device and
installing illuminated safety signs. inverter are located in the luminaire, For larger buildings, particularly those with
together with a rechargeable battery. In the large open areas, central power systems
In addition, safety equipment, such as fire
event of a supply failure, the emergency are often used. In these products, a single
alarm call points and extinguishers, must be
circuit connects the stored power to one of large battery supplies a considerable
adequately illuminated so they can be
the normal mains lamps. It then continues number of remote, or slave, luminaires. In
located and used if needed. Specific areas
to provide illumination, normally at 200 to the past, most of these systems used a DC
of high risk and any relevant control rooms
300 lumens, which is a lower level than output from the battery feeding luminaries,
need a higher level of illumination to enable
when supplied from the mains. fitted with integral inverters, but now it is
the processes in these areas to be shut
also common to convert the battery output
down safely in an emergency. This form of product can either be supplied
to AC at source and then distribute a 230V
as an option by the manufacturer of the
Emergency systems for a particular AC supply to selected normal fluorescent
mains lighting, or fitted by specialist
application have to be designed to cater for lighting luminaires. These luminaires can
installers, who should conduct the
an appropriate duration for the application. then be operated at full light output from
modification in accordance with the Industry
This is normally 3 hours for premises that the central power system.
Committee for Emergency Lighting (ICEL)
are not to be evacuated immediately in the standard, ICEL 1004: The modification of
event of a supply failure. This particularly
applies to premises for entertainment, or
those with a sleeping risk, such as hotels or
hospitals. Systems used in premises that
will be evacuated immediately may only
require 1 hour of duration, but most
operators still use the standard 3-hour
units. This avoids having to wait for 24
hours while the batteries recharge before
re-entering the building after the mains
have been restored.
Some applications, such as theatres, where
the normal lighting may be dimmed, require
the lamp to be illuminated at all times that
the building is occupied. This is called
maintained operation. For most sites, non-
maintained operation, where the lamp is only
illuminated in a supply failure, is acceptable.
There are three main types of emergency
lighting product:
a) self-contained dedicated luminaires
These use an integral rechargeable battery to
store power, which in an emergency supplies
the lamp. The lamp is typically a low wattage
fluorescent with an output of 100 to 200
57
FP_APRIL.LIGHTING copy.LIGHTING 25/3/04 3:56 PM Page 58
F i r e P r o t e c t i o n D a t a
F i r e P r o t e c t i o n D a t a
59