Interrupor 3AP1-FI

Copyright© Siemens AG
Página 1 05/2009 Fernando Guio Energy Transmission / High Voltage
Closing Resistor
Operating Mode of the Closing Sequence

A A = main contact B = auxiliary contact


(interrupter Unit) (closing resistor)
Time: 0 ms:
A = open B = open

B
Time: 67 ms:
A = open B =pre-arc
(current flow in closing resistor)

Time: 70 ms:
A = open B = contact
(current flow in closing resistor)

Time: 77 ms:
A = pre-arc B = closed
(resistor is short-circuited)

Time: 80 ms:
A = contact B = closed
(near END-position)

Time: 100 ms:


A = closed B = closed
(END-Position) (END-position)

Copyright© Siemens AG
Página 2 05/2009 Fernando Guio Energy Transmission / High Voltage
Closing Resistor
Operating Mode of the Opening Sequence

A = main contact B = auxiliary contact


A (interrupter Unit) (closing resistor)
Time: 0 ms:
A = closed B = closed

B
Time: 10 ms:
A = closed B = opening

Time: 17 ms:
A = arc B = opening

Time: 34 ms:
A = opening B = opening

Time: 50 ms:
A = open B = opening
(END-Position (near END-position)

Time: 120 ms:


A = open B = open
(END-Position) (END-position)

Copyright© Siemens AG
Página 3 05/2009 Fernando Guio Energy Transmission / High Voltage