Vous êtes sur la page 1sur 23

FUNDAMENTAL ELECTRICAL SYSTEM

DESIGN CALCULATIONS AND SYSTEM


ARCHITECTURES
for Commercial and Residential Buildings

MAKATI DEVELOPMENT CORPORATION


GF, Bonifacio Technology Center
st nd
31 Street cor. 2 Avenue, Bonifacio Global City
Taguig 1634, Metro Manila, Philippines
Tel Nos. (02) 717-5500 to 30
www.mdc.com.ph
STANDARD Fundamental Design Calculations
Electrical System
Rev 00 – November 2011

CONTENTS

I. Design Criteria for Main Equipment Sizing

II. Low Voltage Wires and Cables

III. Busduct Sizing

IV. Overcurrent Protection

V. Reserved

VI. Lighting & Power Circuits

VII. Motor Circuits

VIII. Fire Pump Motor Circuit

IX. Power Factor Correction

X. Basic Panelboard Design

XI. Standard Electrical System Architecture


A. Malls
B. BPO
C. High Rise Residential

XII. Reserved

XIII. Reserved

XIV. References

MAKATI DEVELOPMENT CORPORATION


GF, Bonifacio Technology Center
st nd
31 Street cor. 2 Avenue, Bonifacio Global City
Taguig 1634, Metro Manila, Philippines
Tel Nos. (02) 717-5500 to 30
www.mdc.com.ph
STANDARD Fundamental Design Calculations
Electrical System
Rev 00 – November 2011

I. Sizing of Main Equipment

A. General Considerations
The main equipments for the building’s electrical system are the transformers and
generator sets. The sizes of these equipments are determined during the schematic
design stage, which depend on load estimate calculation. The load estimate is derived
from load densities defined for areas in each type of the building to be designed, which
depends on the nature of the building and its corresponding electrical requirement.
1. Transformers
Main transformer is sized based from load estimation after the application of
demand factor defined by the designing electrical engineer.
2. Generator Sets
Generator(s), on the other hand, is/are sized depending on building requirement;
that is, same size as the main transformer(s) if the building is intended to have
100% backup power. Also, generator sets are sized based on ‘standby’ rating.
Below are the common load groups that are considered in load estimation –
1. Lighting – Interior, exterior, normal, emergency.
2. Small Power Loads – Receptacle outlets, appliances.
3. Air-conditioning – Chillers, AHU’s, Fans, etc.
4. Plumbing and Sanitation – Domestic pumps, booster pumps, transfer pumps,
sump pump, water heaters.
5. Fire protection – Fire pumps, FDAS.
6. Transportation – Elevators, Escalators.
7. Food preparation – Cooking, refrigerating, dishwashing, ovens, etc.
8. Special Loads – Loads in theaters, etc
9. Miscellaneous loads – Auxiliary systems, etc

This design calculation standard will only address the following types of building –
1. Residential Buildings
2. Malls
3. BPOs
4. Hotels

B. System Voltage Consideration


The utilization voltage considered in this design calculation standard is 3-phase, four-
wire, 400V / 230 V, 60 Hz. Three phase loads shall be served at 400V, while single
phase loads shall be served at 230V line-to-neutral.

Primary voltage shall be based from available power utility supply.

MAKATI DEVELOPMENT CORPORATION


GF, Bonifacio Technology Center
st nd
31 Street cor. 2 Avenue, Bonifacio Global City
Taguig 1634, Metro Manila, Philippines
Tel Nos. (02) 717-5500 to 30
www.mdc.com.ph
STANDARD Fundamental Design Calculations
Electrical System
Rev 00 – November 2011

C. Prescriptive Design Parameters


The load densities to be used in load estimation and initial main equipment sizing will be
based from the parameters defined below. These parameters were derived from
historical design parameters, code requirements, and actual building performance of
existing Ayala buildings. However, the external designer is given liberty to review and
adjust these parameters based from his experience.

1. Residential Buildings

The load considerations for residential buildings in terms of power are typically the
same – household loads and admin/common area loads.

Split-type ACU A/C Lighting Receptacle Misc Total


Residential (ACCU)
kw / tr tr / sqm pf VA / sqm VA / sqm VA / sqm VA / sqm VA / sqm
Res Units 1.3 0.05 0.8 81 24 8 37 150
Office 1.3 0.06 0.8 90 28 30 0 148
Core Areas (Non-AC) n/a n/a n/a 0 4 4 4 12
Non - food 1.3 0.06 0.8 90 24 8 0 122
Food 1.3 0.10 0.8 163 16 8 18 205
Parking n/a n/a n/a 0 4 4 0 8

2. Malls
Load density considerations for malls are – Retail loads (Food and Non-food), and
common area / admin loads.

Centralized ACU A/C Lighting Receptacle Misc Total


Malls (Chillers)
kw / tr tr / sqm pf VA / sqm VA / sqm VA / sqm VA / sqm VA / sqm
Retail Shop (non-food) 1.26 0.06 0.8 88 24 8 0 120
Food 1.26 0.10 0.8 158 16 8 18 200
Banks / Offices 1.26 0.06 0.8 88 28 30 0 146
Common Areas 1.26 0.05 0.8 79 4 4 4 91
Parking n/a n/a n/a 0 4 4 0 8

For developments having a District Cooling System, the chiller loads are not
included in the building load estimation.

Centralized ACU A/C Lighting Receptacle Misc Total


Malls (DCS)
kw / tr tr / sqm pf VA / sqm VA / sqm VA / sqm VA / sqm VA / sqm
Retail Shop (non-food) 0.56 0.06 0.8 39 24 8 0 71
Food 0.56 0.10 0.8 70 16 8 18 112
Banks / Offices 0.56 0.06 0.8 39 28 30 0 97
Common Areas 0.56 0.05 0.8 35 4 4 4 47
Parking n/a n/a n/a 0 4 4 0 8

MAKATI DEVELOPMENT CORPORATION


GF, Bonifacio Technology Center
st nd
31 Street cor. 2 Avenue, Bonifacio Global City
Taguig 1634, Metro Manila, Philippines
Tel Nos. (02) 717-5500 to 30
www.mdc.com.ph
STANDARD Fundamental Design Calculations
Electrical System
Rev 00 – November 2011

3. BPO Buildings

Design considerations for BPOs are different from typical office buildings. The
occupant density is higher for BPOs resulting from higher cooling and power
requirement. However, the design for BPO is often just ‘core-and-shell’, since
detailed design for tenant spaces are handled by tenants. Therefore, power
allotment for tenant units should be carefully considered to anticipate tenant
power requirement.

Centralized ACU A/C Lighting Receptacle Misc Total


BPO (Chillers)
kw / tr tr / sqm pf VA / sqm VA / sqm VA / sqm VA / sqm VA / sqm
Core Areas 1.26 0.05 0.8 79 4 4 4 91
BPO Offices 1.26 0.10 0.8 158 28 60 0 246
Parking n/a n/a n/a 0 4 4 0 8

For developments having a District Cooling System, the chiller loads are not
included in load estimation.

Centralized ACU A/C Lighting Receptacle Misc Total


BPO (DCS)
kw / tr tr / sqm pf VA / sqm VA / sqm VA / sqm VA / sqm VA / sqm
Core Areas 0.56 0.05 0.8 35 4 4 4 47
BPO Offices 0.56 0.10 0.8 70 28 60 0 158
Parking n/a n/a n/a 0 4 4 0 8

4. Hotels

Centralized ACU A/C Lighting Receptacle Misc Total


Hotel Units
kw / tr tr / sqm pf VA / sqm VA / sqm VA / sqm VA / sqm VA / sqm
Core Areas 1.26 0.05 0.8 79 4 4 4 91
Hotel Units 1.26 0.05 0.8 79 24 8 8 119
Parking n/a n/a n/a 0 4 4 0 8

D. Minimum Demand Factors

1. Residential Buildings
a. Residential Loads = Connected Load x 23% (for 62 units or more)
b. Admin / Common Area Loads = Connected Load x 70%
2. Malls
a. Retail Loads = Connected Load x 70%
b. Admin / Common Area Loads = Connected Load x 70%
3. BPO Buildings
a. Tenant Areas = Connected Load x 80%
b. Common Areas / Admin = Connected Load x 70%
4. Hotels
a. Hotel Unit Areas = Connected Load x 60%
b. Common Areas / Admin = Connected Load x 70%

MAKATI DEVELOPMENT CORPORATION


GF, Bonifacio Technology Center
st nd
31 Street cor. 2 Avenue, Bonifacio Global City
Taguig 1634, Metro Manila, Philippines
Tel Nos. (02) 717-5500 to 30
www.mdc.com.ph
STANDARD Fundamental Design Calculations
Electrical System
Rev 00 – November 2011

II. Low Voltage Wires and Cables

A. Sizing of wires and cables shall be based from the following considerations:
1. Wire/cable sizing should be rated maximum of–
a. 100% for non-continuous (cyclic) loads.
b. 80% for continuous loads (loads that operate for 3hrs or more).
2. Wire/cable shall be sized to meet Code defined voltage drop limits at its
design load current.
a. Voltage Drop Considerations
Where:
VD = Voltage Drop
NV = Nominal Voltage at Source
I = 1.15* FLC for running condition or
I = LRC for starting condition
R = DC resistance ohm/305m
L = Feeder wire length

3. Selected wire/cable temperature rating shall be coordinated with all


temperature limits, particularly at its terminations.
a. Select 60 ˚C temperature rating up to 100A
b. Select 75 ˚C temperature rating for more than 100A
4. Wire/cable short circuit withstand current and time shall be coordinated with
that of its upstream circuit breakers.

B. STANDARD ELECTRICAL WIRING SCHEDULE (Not applicable for motors)


Table VII.1 Standard Wiring Schedule for Low Voltage Systems
ELECTRICAL WIRING SCHEDULE GROUND CONDUIT
OCPD
WIRE CODE WIRE SIZE AMPACITY WIRE IMC/PVC
3Ø 3W+G 3Ø 4W+G 1Ø 2W+G mm2 THWN THHN AT mm2 mm Φ in Φ
T0 Y0 S0 3.5 25 30 20AT 3.5 15 1/2
T1 Y1 S1 5.5 35 40 30AT 3.5 20 3/4
T2 Y2 S2 8 50 55 40AT 5.5 25 1
T3 Y3 S3 14 65 70 50AT 8 25 1
T4 Y4 S4 22 85 90 70AT 8 32 1 1/2
T5 Y5 S5 30 110 115 100AT 8 32 1 1/2
T7 Y6 S7 50 145 150 125AT 14 50 2
T8 Y7 S8 60 160 170 150AT 22 50 2
T9 Y8 S9 80 195 205 175AT 22 50 2
T10 Y9 S10 100 220 225 200AT 30 65 2 1/2
T11 Y10 S11 125 255 265 250AT 30 65 2 1/2
T12 Y11 S12 150 280 295 30 80 3
T13 Y12 S13 175 305 345 300AT 30 80 3
T14 Y13 S14 200 330 355 30 80 3
T15 Y14 S15 250 375 400 400AT 50 90 3 1/2

MAKATI DEVELOPMENT CORPORATION


GF, Bonifacio Technology Center
st nd
31 Street cor. 2 Avenue, Bonifacio Global City
Taguig 1634, Metro Manila, Philippines
Tel Nos. (02) 717-5500 to 30
www.mdc.com.ph
STANDARD Fundamental Design Calculations
Electrical System
Rev 00 – November 2011

C. Allowable Short Circuit Current Calculation

The allowable short circuit current for low-voltage thermoplastic (PVC) insulated
wire/cable is given by-
Where:
Isc = Allowable short circuit current
A = cross sectional area of copper conductors, mm2
t =time of short circuit current, seconds
K = 104.484, computed constant for thermoplastic copper conductor where
the rated wire operating temperature is 75 ˚C and the maximum short circuit
temperature is 150 ˚C

Table VII.1 Maximum Short Circuit Withstand of Low Voltage Cables


CU WIRE
Maximum Short-Circuit Withstand Current in Amperes
SIZE
mm2 1/2 Cycles 1 Cycle 2 Cycles 3 Cycles 4 Cycles 5 Cycles 6 Cycles
3.5 4,006 2,833 2,003 1,635 1,416 1,267 1,156
5.5 6,295 4,451 3,148 2,570 2,226 1,991 1,817
8 9,157 6,475 4,578 3,738 3,237 2,896 2,643
14 16,024 11,331 8,012 6,542 5,665 5,067 4,626
22 25,180 17,805 12,590 10,280 8,903 7,963 7,269
30 34,337 24,280 17,168 14,018 12,140 10,858 9,912
50 57,228 40,466 28,614 23,363 20,233 18,097 16,520
60 68,674 48,560 34,337 28,036 24,280 21,717 19,824
80 91,565 64,746 45,783 37,381 32,373 28,955 26,433
100 114,456 80,933 57,228 46,727 40,466 36,194 33,041
125 143,071 101,166 71,535 58,408 50,583 45,243 41,301
150 171,685 121,399 85,842 70,090 60,700 54,291 49,561
175 200,299 141,633 100,149 81,772 70,816 63,340 57,821
200 228,913 161,866 114,456 93,453 80,933 72,389 66,081
250 286,141 202,332 143,071 116,817 101,166 90,486 82,602

D. SIZING OF CONDUITS

Percent Conductor Fill formula is given by-

Where:
D = interior diameter of conduit
d = diameter of conductor (wire)
n = number of conductors

According to PEC Table 9.1.1.1 the percent fill of (more than two) conductors in a conduit
should not exceed 40%.

MAKATI DEVELOPMENT CORPORATION


GF, Bonifacio Technology Center
st nd
31 Street cor. 2 Avenue, Bonifacio Global City
Taguig 1634, Metro Manila, Philippines
Tel Nos. (02) 717-5500 to 30
www.mdc.com.ph
STANDARD Fundamental Design Calculations
Electrical System
Rev 00 – November 2011

III. BUSDUCT SYSTEM


Busduct system shall be considered to be used for main feeders and risers. Busduct
may be of copper or aluminum conductor material; whichever the project budget
dictates.
A. Busduct Sizing shall be based on the following considerations –

5. The voltage rating of the busduct shall be 600V.


6. The busduct rating shall not be less than the demand load to be served.
7. Voltage drop not exceeding 2% shall be considered in sizing the busduct.
8. The ambient temperature consideration in sizing the busduct shall be 40°C.
9. The kAIC rating of busduct shall be selected to withstand the maximum available
short circuit current and shall be coordinated with that of its upstream OCPD.

IV. Overcurrent Protection not over 600V

Circuit Breakers shall be the standard overcurrent protective devices of equipment and
conductors for low voltage systems. Air Circuit Breakers shall be used for main
switchgears and synchronizing panels. Molded Case Circuit Breakers shall be used for
distribution, power, and lighting panelboards.

A. Sizing of Circuit Breakers shall be based from the following considerations:

1. The next higher size of circuit breaker above the ampacity of the conductors
being protected shall be permitted up to 800A circuit breaker rating except –
a. The conductors being protected supply branch circuit muti-outlet
receptacles.
b. The conductors being protected supply motor branch circuit.

2. Where the circuit breaker exceeds rating over 800A, the ampacity of the
conductor it protects shall be equal or greater than the rating of the circuit
breaker.

3. The interrupting capacity of the circuit breaker shall be greater than the
maximum available three-phase short circuit current.

V. Reserved

MAKATI DEVELOPMENT CORPORATION


GF, Bonifacio Technology Center
st nd
31 Street cor. 2 Avenue, Bonifacio Global City
Taguig 1634, Metro Manila, Philippines
Tel Nos. (02) 717-5500 to 30
www.mdc.com.ph
STANDARD Fundamental Design Calculations
Electrical System
Rev 00 – November 2011

VI. LIGHTING AND RECEPTACLE OUTLET CIRCUIT

A. Lighting Circuits
1. Individual lighting circuit shall be sized on the maximum of 2500VA.
a. If not otherwise specified, each lighting fixture shall be assumed with a
minimum of 100VA rating.
b. A voltage drop not exceeding 3% shall be considered in each branch circuit.
2. Lighting circuit installation shall be in accordance with PEC.
3. Lighting system design criteria shall be based on Ayala Land Inc. Building
Standards.

B. Receptacle Outlet Circuits


1. Individual receptacle outlet circuit shall be sized on the maximum of 1800VA.
a. Each receptacle outlet shall be assumed with a minimum of 180VA rating.
b. A voltage drop not exceeding 3% shall be considered in each branch circuit.
2. Receptacle outlet circuit installation shall be based on PEC and Ayala
Land Inc. Building Standards.

INTENTIONALLY LEFT BLANK

MAKATI DEVELOPMENT CORPORATION


GF, Bonifacio Technology Center
st nd
31 Street cor. 2 Avenue, Bonifacio Global City
Taguig 1634, Metro Manila, Philippines
Tel Nos. (02) 717-5500 to 30
www.mdc.com.ph
STANDARD Fundamental Design Calculations
Electrical System
Rev 00 – November 2011

VII. MOTOR ELECTRICAL DESIGN (NOT applicable for fire pump motor)
A. Motor Electrical System Design shall be based on the following considerations:
1. Size the branch circuit wire not less than 125% of the PEC-defined motor full load
current.
a. Since the operating temperature of motors is above 30°C (i.e., mostly 40°C) , the
branch circuit wire shall be coordinated to this temperature rating, by dividing the
PEC-defined motor full load current to the ambient temperature correction factor,
then sizing the branch circuit wire using this corrected ampacity.
2. Size the motor disconnect not less than 115% of the PEC defined motor full load
current. For uniformity, the size of motor disconnect shall be equal to the ampacity
of the branch circuit wire.
3. From PEC Table 4.30.4.2 size the Inverse time circuit breaker OCPD at 250% of
the PEC defined motor full load current.
4. Motor controller, including overload protection will be the scope of Mechanical /
Sanitary contractor, subject to Electrical Design Engineer’s review.

Table VII.1 Motor Electrical System Design, Sizing of Feeders and Circuit Breakers
Motor HP Full Load Currents, 3Φ SIZE OF WIRES SIZE OF ITCB
hp 230V 400V 460V 230V 400V 460V 230V 400V 460V
1/2 2.2 1.3 1.1 3.5mm2 3.5mm2 3.5mm2 20AT 20AT 20AT
3/4 3.2 1.8 1.6 3.5mm2 3.5mm2 3.5mm2 20AT 20AT 20AT
1 4.2 2.3 2.1 3.5mm2 3.5mm2 3.5mm2 20AT 20AT 20AT
1 1/2 6 3.3 3 3.5mm2 3.5mm2 3.5mm2 20AT 20AT 20AT
2 6.8 4.3 3.4 3.5mm2 3.5mm2 3.5mm2 20AT 20AT 20AT
3 9.6 6.1 4.8 3.5mm2 3.5mm2 3.5mm2 30 AT 20AT 20AT
5 15.2 9.7 7.6 5.5mm2 3.5mm2 3.5mm2 40 AT 30 AT 20AT
7 1/2 22 14 11 8.0 mm2 5.5mm2 3.5mm2 70AT 40 AT 30 AT
10 28 18 14 8.0 mm2 5.5mm2 5.5mm2 70AT 50 AT 40 AT
15 42 27 21 22 mm2 8.0 mm2 5.5mm2 100 AT 70AT 70AT
20 54 34 27 30 mm2 14 mm2 8.0 mm2 150 AT 100 AT 70AT
25 68 44 34 38 mm2 22 mm2 14 mm2 175 AT 125 AT 100 AT
30 80 51 40 38 mm2 30 mm2 22 mm2 200 AT 125 AT 100 AT
50 130 83 65 80 mm2 50 mm2 38 mm2 400 AT 200 AT 175 AT
60 154 103 77 100 mm2 50 mm2 38 mm2 400 AT 300 AT 200AT
75 192 128 96 150 mm2 80 mm2 50 mm2 500 AT 400 AT 250 AT
100 248 165 124 250 mm2 125 mm2 80 mm2 800 AT 500 AT 400 AT
125 312 208 156 2-125mm1 200 mm2 125 mm2 800 AT 600 AT 400 AT
150 360 240 180 2-150mm2 250 mm2 125 mm2 1000 AT 600 AT 500 AT
200 480 320 240 2-250mm2 2-125mm2 250 mm2 1200 AT 800 AT 500 AT
250 - 403 302 2-200 mm2 2-125mm2 1000 AT 800 AT
300 - 482 361 2-250mm2 2-150 mm2 1200 AT 1000 AT

*Based from PEC 4.30.14.4

MAKATI DEVELOPMENT CORPORATION


GF, Bonifacio Technology Center
st nd
31 Street cor. 2 Avenue, Bonifacio Global City
Taguig 1634, Metro Manila, Philippines
Tel Nos. (02) 717-5500 to 30
www.mdc.com.ph
STANDARD Fundamental Design Calculations
Electrical System
Rev 00 – November 2011

B. Airconditioning and Refrigerating Equipment Electrical System Design shall be


based on the following considerations:

1. Size the branch circuit wire not less than 125% of the motor – compressor rated –
load current or the branch – circuit selection current, whichever is greater.

a. Since the operating temperature of motors is above 30°C (i.e., mostly 40°C) , the
branch circuit wire shall be coordinated to this temperature rating, by dividing the
motor – compressor rated – load current to the ambient temperature correction
factor, then size the branch circuit wire using this corrected ampacity.

2. Size the motor disconnect not less than 115% of the motor – compressor rated –
load current. For uniformity, the size of motor disconnect shall be equal to the
ampacity of the branch circuit wire.

3. From PEC Table 4.30.4.2 size the Inverse time circuit breaker OCPD at 250% of
the motor – compressor rated – load current.

4. Motor controller, including overload protection will be the scope of Mechanical /


Sanitary contractor, subject to Electrical Design Engineer’s review.

INTENTIONALLY LEFT BLANK

MAKATI DEVELOPMENT CORPORATION


GF, Bonifacio Technology Center
st nd
31 Street cor. 2 Avenue, Bonifacio Global City
Taguig 1634, Metro Manila, Philippines
Tel Nos. (02) 717-5500 to 30
www.mdc.com.ph
STANDARD Fundamental Design Calculations
Electrical System
Rev 00 – November 2011

VIII. DESIGN FOR MOTOR DRIVEN FIRE PUMP SYSTEM

B. Fire Pump Electrical System shall be designed to meet the following requirements,
as defined in the Philippine Electrical Code:

1. Dedicated overcurrent protective device (OCPD) and disconnecting means must


be sized to indefinitely carry the locked-rotor current of the fire pump motor(s)
and associated pump(s).

2. The circuit components serving the fire pump must be chosen to withstand the
available short circuit current at the point of installation.

3. Fire pump feeder must be sized to have an ampacity of not less than 125% of the
full load current of the fire pump motor(s) and pressure maintenance motor(s),
considering –
a. The feeder conductor ampacity shall be corrected to coordinate with the
fire pump motor’s design ambient temperature.
b. The voltage at the fire pump controller terminal shall not drop more than
15% below nominal voltage during starting conditions.
c. The voltage at the fire pump controller terminal shall not drop more than
5% below the nominal voltage during running conditions when the motor
is operating at 115% of its full load current (capacity).

Table VII.1 Firepump Electrical System Design, Sizing of Feeders and Circuit Breakers
Firepump Motor
Full Load Locked Rotor Size of Maximum
Rated Size of Feeder
Current* Current 380V** OCPD Circuit Length
Horsepower
hp Amp Amp AT sq.mm. m
20 34 204 200 30 300
25 44 264 250 30 300
30 51 306 300 30 300
40 66 396 400 50 300
50 83 498 500 50 300
60 103 618 600 60 300
75 128 768 800 80 300
100 165 990 1000 125 400
125 208 1248 1200 200 400
150 240 1440 1600 250 400
200 320 1920 2000 2-150 500
250 403 2418 3000 2-200 500
*Based from PEC 4.30.14.4
**Assumed 6-times the motor full load current

MAKATI DEVELOPMENT CORPORATION


GF, Bonifacio Technology Center
st nd
31 Street cor. 2 Avenue, Bonifacio Global City
Taguig 1634, Metro Manila, Philippines
Tel Nos. (02) 717-5500 to 30
www.mdc.com.ph
STANDARD Fundamental Design Calculations
Electrical System
Rev 00 – November 2011

C. Schematic Design for Fire Pump

Normal Power Source Feeder


Redundant Power Source Feeder
(in separate route)

Fire Pump ATS

Feeder Tap for


Jockey Pump
Fire Pump Motor
Controller

Fire Pump Motor

Jockey Pump Motor

D. Design Calculation Example

A 150hp Nema Design B fire pump motor has a full load current of 240Amp. Its
associated pressure maintenance pump is rated 5hp having a full load current of
9.7Amp. The maximum ambient operating temperature is 40°C. The power supply is
400V, 3Φ, 60hz.

a. Sizing of feeder wire to the fire pump controller


150hp, 380V, 3Φ FLC
240A x 1.25 = 300A
5hp, 380V, 3Φ FLC
9.70A x 1.25 =12.13A
Total FLC =312.13A, say 312A

And so, the minimum ampacity of feeder conductors is 312A. Correcting the
conductor ampacity to 40°C by dividing 0.88, we yield 354A. Using 75˚C
temperature rating of 600V rated building wires; a 250mm2 copper conductor is
the minimum size as per PEC Table 3.10.1.16

MAKATI DEVELOPMENT CORPORATION


GF, Bonifacio Technology Center
st nd
31 Street cor. 2 Avenue, Bonifacio Global City
Taguig 1634, Metro Manila, Philippines
Tel Nos. (02) 717-5500 to 30
www.mdc.com.ph
STANDARD Fundamental Design Calculations
Electrical System
Rev 00 – November 2011

b. Voltage Drop Considerations


Where:
VD = Voltage Drop
NV = Nominal Voltage at Source
I = 1.15* FLC for running condition or
I = LRC for starting condition
R = DC resistance ohm/305m
L = Feeder wire length

Using the above formula, the feeder wire, 200mm2 copper conductor, must not
exceed 200m length to satisfy both motor starting and running voltage drop
limitations.

c. Sizing of OCPD and ATS


150hp, 380V, 3Φ FLC
240A x 6 = 1,440A (locked rotor current)
5hp, 380V, 3Φ FLC
9.70A x 6 = 58.20A
Total RLC =1,498.20A say, 1,498A

And so, the total locked rotor current is 1,498A, assuming Nema Design B code
F. The next higher standard size of OCPD (circuit breaker) and ATS is
1600AF/AT

INTENTIONALLY LEFT BLANK

MAKATI DEVELOPMENT CORPORATION


GF, Bonifacio Technology Center
st nd
31 Street cor. 2 Avenue, Bonifacio Global City
Taguig 1634, Metro Manila, Philippines
Tel Nos. (02) 717-5500 to 30
www.mdc.com.ph
STANDARD Fundamental Design Calculations
Electrical System
Rev 00 – November 2011

IX. CAPACITOR BANK SIZING

A. Capacitor Bank design shall satisfy the following basic considerations:

1. The size of the capacitor bank should be able to correct system power factor
from 0.8 to 0.95.
2. The ampacity of the capacitor feeder conductor shall not be less than 135% of
the rated current of the capacitor.
3. The capacitor bank shall be provided with a means of discharging stored energy.
4. Capacitor bank specification must consider harmonic in selecting the type of
capacitor, and contactor switches.

Table VIII.1 Capacitor Bank Sizing based from Main Transformer Sizes
Nominal Transformer Power Factor Before Power Factor After Nominal Capacitor
Rating Compensation Compensation Bank Rating
300 0.8 0.95 100
500 0.8 0.95 150
750 0.8 0.95 250
1000 0.8 0.95 300
1500 0.8 0.95 450
2000 0.8 0.95 600
2500 0.8 0.95 750
3000 0.8 0.95 900

B. Schematic Design of Capacitor Bank

To Low Voltage Switchgear


Capacitor Feeder

Capacitor Overcurrent Protection

Discharge Resistor

Capacitor Bank

MAKATI DEVELOPMENT CORPORATION


GF, Bonifacio Technology Center
st nd
31 Street cor. 2 Avenue, Bonifacio Global City
Taguig 1634, Metro Manila, Philippines
Tel Nos. (02) 717-5500 to 30
www.mdc.com.ph
STANDARD Fundamental Design Calculations
Electrical System
Rev 00 – November 2011

C. Design Calculation Procedure

Calculate the size of capacitor bank in a 1MVA electrical system, to be able to


correct the system power from 0.8 to 0.95.

Based from the power triangle,


S = 1000 KVA
Cos Φ1 = 0.8 ; Φ1 = 36.87°
Cos Φ2= 0.95 ; Φ2 = 18.19°

Also,
Sin Φ1 = Q1/S
Q1 = S*sinΦ1
Q2 = S*sinΦ2

Solving for Qc,


Qc = Q1 - Q2
Qc = S (sinΦ1 - sinΦ2)
= 1000(0.6 - 0.312)
Qc = 288 KVAR say, 300kVAR

And so, the rating of the capacitor is 300kVAR. Selecting capacitor sensitivity of 5%-
15%, provide 6 – steps of 50kVAR.

MAKATI DEVELOPMENT CORPORATION


GF, Bonifacio Technology Center
st nd
31 Street cor. 2 Avenue, Bonifacio Global City
Taguig 1634, Metro Manila, Philippines
Tel Nos. (02) 717-5500 to 30
www.mdc.com.ph
STANDARD Fundamental Design Calculations
Electrical System
Rev 00 – November 2011
X. PANELBOARD DESIGN 400 / 230V Systems

A. Design Load Schedule for 3-phase 400 / 230V System

PANEL : DP-TEMPLATE MAIN CIRCUIT BREAKER : 100 AF 80 AT, 3-POLE, CENTER MAIN
FED FROM : (ENCODE PANEL SOURCE) MAIN FEEDER SIZE : Y4 (SEE WIRING LEGEND)
SYSTEM VOLTAGE : 230 VOLTS

BRANCH AMPERE LOAD BRANCH CIRCUIT BREAKER BRANCH CIRCUIT WIRING


CKT VOLT-
LOAD DESCRIPTION AMPERE- AMPERE-
NO. ØAN ØBN ØCN 3Ø AMPERE POLE CODE WIRE RACEWAY
FRAME TRIP
1 (Encode Loads) 12.00 2,760 1P 50 30 S1 THWN PVC SCH 40
2 (Encode Loads) 8.00 1,840 1P 50 20 S0 THWN PVC SCH 40
3 (Encode Loads) 6.52 1,500 1P 50 20 S0 THWN PVC SCH 40
4 (Encode Loads) 6.52 1,500 1P 50 20 S0 THWN PVC SCH 40
5 (Encode Loads) 10.00 2,300 1P 50 20 S0 THWN PVC SCH 40
6 (Encode Loads) 12.00 2,760 1P 50 20 S0 THWN PVC SCH 40
7 (Encode Loads) 5.00 1,150 1P 50 20 S0 THWN PVC SCH 40
8 (Encode Loads) 6.00 1,380 1P 50 20 S0 THWN PVC SCH 40
9 (Encode Loads) 8.00 1,840 1P 50 20 S0 THWN PVC SCH 40
10 (Encode Loads) 8.00 1,840 1P 50 20 S0 THWN PVC SCH 40
11 (Encode Loads) 10.00 2,300 1P 50 20 S0 THWN PVC SCH 40
12 (Encode Loads) 10.00 2,300 1P 50 20 S0 THWN PVC SCH 40
13 - 1P 50 20 S0 THWN PVC SCH 40
14 - 1P 50 20 S0 THWN PVC SCH 40
15 - 1P 50 20 S0 THWN PVC SCH 40
16 - 1P 50 20 S0 THWN PVC SCH 40
17 - 1P 50 20 S0 THWN PVC SCH 40
18 - 1P 50 20 S0 THWN PVC SCH 40

TOTAL CONNECTED LOAD: 31.00 29.04 42.00 0.00 23,469

LOCATION : (ENCODE PANEL LOCATION) MAIN CB KAIC RATING : kAIC


ENCLOSURE : (ENCODE TYPE OF ENCLOSURE, NEMA RATING) BRANCH CB KAIC RATING : kAIC
MOUNTING : (SURFACE, FREE-STANDING, FLUSH-MOUNTED, ETC) APPLIED DEMAND FACTOR : 80 %

Table IX.1 Load Schedule Template 3-phase 400 / 230V System

B. Three-Phase 4-wire + ground 400V / 230V Systems

To 400V 4W+G 3-phase Source

3-Pole Main
Circuit Breaker

to 400V 3-phase Loads,


other panelboards, etc.

to 230V single-phase
Loads

ΦA ΦB ΦC N
G

MAKATI DEVELOPMENT CORPORATION


GF, Bonifacio Technology Center
st nd
31 Street cor. 2 Avenue, Bonifacio Global City
Taguig 1634, Metro Manila, Philippines
Tel Nos. (02) 717-5500 to 30
www.mdc.com.ph
STANDARD Fundamental Design Calculations
Electrical System
Rev 00 – November 2011

XI. STANDARD SYSTEM ARCHITECTURE

MAKATI DEVELOPMENT CORPORATION


GF, Bonifacio Technology Center
st nd
31 Street cor. 2 Avenue, Bonifacio Global City
Taguig 1634, Metro Manila, Philippines
Tel Nos. (02) 717-5500 to 30
www.mdc.com.ph
STANDARD Fundamental Design Calculations
Electrical System
Rev 00 – November 2011

MAKATI DEVELOPMENT CORPORATION


GF, Bonifacio Technology Center
st nd
31 Street cor. 2 Avenue, Bonifacio Global City
Taguig 1634, Metro Manila, Philippines
Tel Nos. (02) 717-5500 to 30
www.mdc.com.ph
STANDARD Fundamental Design Calculations
Electrical System
Rev 00 – November 2011

MAKATI DEVELOPMENT CORPORATION


GF, Bonifacio Technology Center
st nd
31 Street cor. 2 Avenue, Bonifacio Global City
Taguig 1634, Metro Manila, Philippines
Tel Nos. (02) 717-5500 to 30
www.mdc.com.ph
STANDARD Fundamental Design Calculations
Electrical System
Rev 00 – November 2011

MAKATI DEVELOPMENT CORPORATION


GF, Bonifacio Technology Center
st nd
31 Street cor. 2 Avenue, Bonifacio Global City
Taguig 1634, Metro Manila, Philippines
Tel Nos. (02) 717-5500 to 30
www.mdc.com.ph
STANDARD Fundamental Design Calculations
Electrical System
Rev 00 – November 2011

XII. Reserved

XIII. Reserved

XIV. References

MAKATI DEVELOPMENT CORPORATION


GF, Bonifacio Technology Center
st nd
31 Street cor. 2 Avenue, Bonifacio Global City
Taguig 1634, Metro Manila, Philippines
Tel Nos. (02) 717-5500 to 30
www.mdc.com.ph
STANDARD Fundamental Design Calculations
Electrical System
Rev 00 – November 2011

Prepared by:

Nathaniel S. Acosta
Technical Services Engineer

Noted by: Approved by:

Artemio C. Pugat Jr. Roger N. Tiguelo


Electrical Section Head CG-MEPF Head

MAKATI DEVELOPMENT CORPORATION


GF, Bonifacio Technology Center
st nd
31 Street cor. 2 Avenue, Bonifacio Global City
Taguig 1634, Metro Manila, Philippines
Tel Nos. (02) 717-5500 to 30
www.mdc.com.ph

Vous aimerez peut-être aussi