Vous êtes sur la page 1sur 6

560 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 20, NO.

2, APRIL 2005

Ampacity Derating Factors for Cables


Buried in Short Segments of Conduit
Pascal Vaucheret, R. A. Hartlein, Senior Member, IEEE, and W. Z. Black, Fellow, IEEE

Abstract—Buried cables are often routed through short seg- equiv- conductor property of a single cable that is ther-
ments of conduit, and when this situation occurs, the ampacity mally equivalent to the conductor property of a
must be reduced or the cable will overheat as a result of the triplexed cable
high thermal resistance created at the location of the conduit.
This problem is examined for extruded cables by using a finite equiv-insul insulation property of a single cable that is ther-
element heat transfer software program to determine the derating mally equivalent to the insulation property of a
in ampacity that cables in conduits must experience in order to triplexed cable
remain below a maximum conductor temperature. The derating insul value for cable insulation material
factors are provided as a function of conduit length, soil resistivity, soil value for surrounding soil.
burial depth and number of cables in the conduit. The results
show that once the length of conduit exceeds about 20 times its
outer diameter, then the ampacity of the circuit must be reduced I. INTRODUCTION
to the value that it would have if the entire length were buried in
the conduit. Factors that result in lower cable ampacities, such
as high soil thermal resistivity and deeper burial depths lead to
larger derating factors.
S INCE the mid 1900’s the accepted calculation of under-
ground cable ampacities has been based on the model pro-
posed by Neher and McGrath [1]. Their thermal model is based
on a number of assumptions that greatly simplify the mathe-
Index Terms—Ampacity, cable in conduit, thermal ratings,
underground cables. matical formulation. Perhaps the most significant assumption
which simplifies the approach is one which considers no vari-
ation in any geometrical or thermal parameter along the length
NOMENCLATURE of the entire cable route. This assumption reduces the formu-
outer diameter of cable [m] lation from a three-dimensional analysis to one of two-dimen-
nominal diameter of conduit [m] sions. The two-dimensional formulation is then further reduced
DF ampacity derating factor to a one-dimensional heat transfer problem by using the prin-
burial depth below the surface [m] ciple of superposition, which utilizes a fictitious heat sink of
current [A] equal strength above the cable at a distance above the earth sur-
length of conduit [m] face equal to the burial depth. With the resulting one-dimen-
heat generation per unit length of circuit [W/m] sional model, solving for the ampacity of the cable is reduced to
radial distance from center of cable [m] a straightforward solution of an algebraic equation. This math-
conduction shape factor ematical approach is the one used to provide values in the am-
temperature [ C] pacity tables [2] and those values are accepted as the standard
Greek Symbols thermal ratings of most underground cable systems.
thermal resistivity [cm C/W] If any changes in the thermal environment exist along the
Subscripts length of a cable installation, the ampacity tables are unable
ambient to provide guidance for determining the ampacity of this more
air value that exists in the air layer inside the conduit complex situation. If the thermal conditions exist for a rela-
conductor tively long segment of the route, it would be prudent, however,
cond value that exists when a conduit is present to rate the entire circuit on the basis of the worst combination of
db value that exists when the cable is direct buried thermal environment. When the poor thermal conditions exist
equiv value for single cable that is thermally equivalent for only a short length of the route, guidance as to the derating
to a triplexed cable the cable must endure is less clear. Unfortunately this situation
is often the case in the field where the cable will frequently be
required to share its underground space with other utilities or
the cable must be routed through a relatively short segment of
Manuscript received December 12, 2003; revised April 25, 2004. Paper no. conduit or pipe. Any variation along the cable route that restricts
TPWRD-00629-2003. heat transfer to the earth will require a deviation from the am-
P. Vaucheret is with ECL-Pechiney-Alcan, Ronchin, France.
R. A. Hartlein is with NEETRAC in the School of Electrical and Computer pacity values provided by the ampacity tables [2].
Engineering, Georgia Institute of Technology, Atlanta, GA 30332 USA. One way to determine the ampacity of a cable route that
W. Z. Black is with the George W. Woodruff School of Mechanical Engi- passes through a region of high thermal resistance would be to
neering, Georgia Institute of Technology, Atlanta, GA 30332 USA (e-mail:
william.black@me.gatech.edu). rate the circuit on the basis that the entire route is surrounded
Digital Object Identifier 10.1109/TPWRD.2005.844358 by the increased thermal resistance. This procedure is obviously
0885-8977/$20.00 © 2005 IEEE
VAUCHERET et al.: AMPACITY DERATING FACTORS FOR CABLES BURIED IN SHORT SEGMENTS OF CONDUIT 561

overly conservative and it will result in a severe penalty of re-


duced ampacity. Another approach would be to ignore the re-
gion of poor heat transfer and assume that the region of in-
creased thermal resistance has a negligible effect on the cable
temperature. This method is a dangerous one, because even a
short length of poor soil or a short length of conduit can lead to
a hot section of cable and the cable could ultimately fail from
unexpectedly high temperatures. Obviously there is some room
for compromise between these two extreme approaches when
the impediment to heat transfer occurs for only a short distance
along the cable route.
When the cable passes through a short segment of poorly con- Fig. 1. Geometry of cable domain.
ducting material, the calculation of the new, reduced ampacity
is not a simple matter and the thermal model must account for The approach to the calculation of derating factors in this
the fact that the heat transfer into the surrounding soil is com- paper differs in a number of respects from the one used in [3].
plex and occurs in three dimensions. Therefore the analysis must The analysis presented here considers a single soil resistivity
account for the increased complexity and the ampacity can no and a single ambient soil temperature that exists far from the
longer be calculated from a simple algebraic expression that is cable. The factor that changes along the length of cable is the
outlined in the Neher-McGrath model. The new approach now presence of a short length of conduit that creates a region of ele-
requires the solution of a complex set of differential equations, vated cable temperature. The penalty to be paid for the presence
and in these cases it is prudent to use commercially available of a short span of conduit is less severe than a change in the soil
thermal software to solve the complex three-dimensional heat resistivity, because the presence of the conduit creates less of a
transfer problem. thermal burden than a change in thermal resistivity of the soil
One of the most common situations that involve a change in the next to the cable.
thermal environment along the cable route involves a cable that is
installed in a short segment of conduit. This situation frequently II. MATHEMATICAL MODEL
occurs when a cable route passes under a road crossing or passes
close to other pipelines or cables. If the conduit is only a short por- The calculation of the ampacity of a cable routed through
tion of the circuit length, the reduction in ampacity will be only a short section of conduit is very complex. The presence of
a fraction of that experienced when the conduit is long. The pur- the conduit compounds the mathematical analysis and creates
pose of this paper is to provide guidance on the amount of reduc- a three-dimensional heat transfer problem for which the tem-
tion in current that underground extruded cables must experience perature distribution around the cable is a function of the axial
when routed through a short segment of conduit. The results will location, distance from the cable and depth below the surface of
also quantify how the derating of the cable is influenced by sev- the earth.
eral variables that are known to affect the cable ampacity, such as
A. Assumptions
the length of conduit , the value for the soil resistivity and
the cable burial depth as shown in Fig. 1. To transform the physical problem into one that is simple
The determination of cable derating factors that result when enough to model mathematically, a number of simplifying as-
the cable route traverses a relative short section of unfavor- sumptions were employed. They include:
able thermal resistance has been addressed previously in [3], — Steady state conditions exist.
although the results reported here are more extensive than those — Cable, soil and conduit properties are independent of tem-
appearing in [3]. In this previous paper the influence of a varying perature and constant.
ambient soil temperature and presence of high resistivity block — The cable shield is open-circuited.
of soil under a roadway are considered. The problem is ap- — All nonmetallic layers in the cable construction are
proached by using a thermal network and it considers heat flow lumped into a single, thermally equivalent layer.
in two dimensions. A network of thermal resistances is produced — The conduit is thin and its thermal resistance is close to
by discretizing the domain in both the radial and longitudinal di- that of the soil, so its thermal resistance is added to the
rections and by replacing the continuous thermal regime with a resistance of the adjacent soil layer.
finite number of discrete thermal resistors. An ampacity derating — The thermal resistance of the air layer in the conduit is a
factor is defined which is identical to the one used here. The function of temperature and is calculated from (41) in [1].
derating factor is calculated for the situation where the length The thermal resistance of the air layer is the only quantity
of high resistance soil layer is varied and the temperature and that varies with the temperature.
thermal resistivity of the soil layer is increased above the values — The single, constant thermal resistance of the air layer is
for the ambient soil layer. Derating factors as restrictive as about evaluated at highest cable temperature that exists in the
50 percent are suggested when the slice of soil is not conducive center of the conduit length. This approximation is used
to the transfer of heat from the cable and the region of high re- because (41) in [1] was developed for the two dimensional
sistance extends more than about 4 m along the length of the case where the temperatures are constant along the cable
cable [3]. axis.
562 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 20, NO. 2, APRIL 2005

— The thermal resistivity of the soil is 90 cm C/W and the through an equivalent parallel thermal circuit. These two factors
ambient soil temperature is 25 C. provide an equivalent single layer of insulation that has 0.390
— The vertical plane through the cable centerline and the times the resistivity of a single triplexed cable. When this result
vertical plane perpendicular to the cable axis at the center is combined with the expression for the thermal resistance of a
of the conduct are adiabatic planes. hollow layer of insulation, the result is
— Regions of the soil that are far from the cable are main-
tained at the ambient soil temperature.
— The cable is located concentrically within the conduit. (1)
This assumption is consistent with the assumption used
to develop (41) in [1].
— The cable installation geometry is identical both inside This equation along with the dimensions of the insulation layer
and outside the conduit. This assumption precludes con- of a single equivalent cable in terms of the dimensions of the
sideration of parallel-spaced cable geometry outside the triplexed cables permits calculation of the equivalent thermal
conduit with a triplexed geometry inside the conduit. resistivity of the insulation layer in terms of the dimensions and
resistivity of a single cable. The equivalent thermal resistivity is
then used in the finite element program to simulate the heat that
B. Finite Element Model
is transferred through triplexed cable geometry.
The finite element software package ANSYS [4] was used
to determine the derating factors. The fact that this program III. MODEL VERIFICATION
has three-dimensional capabilities is important, because the The validity of the finite element program was verified by
derating factors must include the heat that is conducted along comparing program results with simple cable installations that
the axial direction of the cable. The axial conduction promotes have known heat transfer solutions. The first comparison in-
cooling of the cable segments inside the conduit and, if this volved a single, infinitely long cylindrical heat source directly
heat removal is ignored, the derating factors will be overly con- buried at a constant depth below the isothermal surface of the
servative. Therefore when simplified two-dimensional models earth. For this situation, the relationship between the heat dis-
are used to calculate the derating factors, they would suggest sipation per unit length and the temperature rise of the cable
that the cable ampacity should be unnecessarily reduced. surface above the ambient temperature is given by
Finite element software packages with thermal capabilities
are able to solve heat transfer problems that typically consist of (2)
calculating the temperature field for given heat input rates. To
determine the ampacity of a cable system, the inverse problem where the conduction shape factor [6] is
must be solved: that is, the heat input rate (ampacity) must be
determined for an assumed admissible temperature of the con- (3)
ductor. Therefore, the temperature distribution in entire domain
must be iteratively computed for a range of electrical currents For this example case, the finite element model assumed a di-
until the maximum cable temperature reaches the assumed ad- rect buried conductor without any insulation layers. The finite
missible value. Between iterations, the temperature sensitive el- element program was used to calculate the temperature rise for
ements, such as the thermal resistance of the air layer within the several heat generation rates per unit length, soil resistivities and
conduit, must be continually corrected for the newly calculated ratios of burial depths to cable diameters. The calculated values
air temperature. were identical to those given by (2) and (3).
In order to model multiple cables in a conduit with the finite The second check of the validity of the finite element formu-
element program, the triplexed geometry had to be replaced by lation involved comparing the program results with the software
a single equivalent cable that has the same thermal resistance as program CYMCAP [7]. The ampacity values were calculated
the three cables. In order for the single cable to have an equiva- for a 35 kV, 750 kcmil (380 mm ) aluminum conductor cable,
lent conductor cross-sectional area as the three triplexed cables, soil resistivity of 90 cm C/W, a burial depth of 0.917 m and
the conductor must have a radius that is 1.732 times the radius of a conduit diameter of 152 mm. Several different installations
the conductor of a single cable. The diameter of a circle which were used including a single, direct-buried cable and three, di-
circumscribes the three cables was used as the outside insula- rect-buried cables. The ampacities were also calculated for the
tion diameter of the equivalent single cable in the finite element same cable geometries when they were routed through a long
program [1]. Therefore the outer radius of the insulation layer conduit. The finite element values for the 90 C cable ampaci-
on the equivalent single cable is 2.16 times the outer radius of ties are compared with the CYMCAP values in Table I.
one of the actual triplexed cables. The values in Table I show the differences that can be ex-
From [5] the thermal resistivity of the equivalent single insu- pected to exist when comparing two programs, even though the
lation layer is established as a function of the thermal resistivity geometries are extremely complex and there are numerous input
of the cable insulation. Two factors are involved. The first ac- variables that cannot be exactly duplicated in both programs.
counts for the fact that a cable in a triplexed configuration cannot Nevertheless, the two programs agree within 1.7 percent for the
dissipate heat around its entire circumference. The second is a ampacity values and within 4.1 percent for the heat generation
result of considering the heat transfer from the three cables to be rates.
VAUCHERET et al.: AMPACITY DERATING FACTORS FOR CABLES BURIED IN SHORT SEGMENTS OF CONDUIT 563

TABLE I
COMPARISON OF FINITE ELEMENT AMPACITY CALCULATION
WITH THE CYMCAP SOFTWARE PACKAGE

Fig. 2. Cable derating factor as a function of dimensionless conduit length,


L/D, for single and triplexed cables.

conduit with a variable length. The derating factor is plotted as


a function of the dimensionless ratio of conduit length to mean
conduit diameter. The specific values shown are for a 35 kV
cable with a 750 kcmil (380 mm ) aluminum conductor buried
IV. RESULTS at a depth of 0.914 m in a soil with a thermal resistivity of
90 cm C/W and an ambient temperature of 25 C. The der-
The best way to display the ampacity results of the program is ating factors in Fig. 2 show the steep decline in acceptable am-
in the form of dimensionless groups. In this way the ampacity of pacity as the length of the conduit is increased. However once
the cables in the conduit can easily be calculated in terms of the the length of the conduit increases beyond about 20 times its
ampacity of the same cable and same geometry except directly diameter, the cable no longer needs to be further derated. This
buried in the earth. The dimensionless ampacity value will be re- result shows that once the conduit is longer than about 20 times
ferred to as a derating factor defined as the ratio of the ampacity its diameter, the cable is fully derated and its ampacity should
of a cable routed through the short segment of conduit divided be calculated on the basis of the entire cable route being inside
by the ampacity of the same cable with an identical installation a conduit.
geometry, but direct buried in the soil. The cable derating factor
is then B. Effect of Soil Resistivity
(4) For buried cables the soil resistivity is the single most influen-
tial factor that affects the cable ampacity, because the resistance
This definition preserves the ampacity value that has been tra- of the soil is the largest resistance in the thermal circuit. When a
ditionally provided in tables or calculated by accepted software cable is buried in a soil or thermal backfill that encourages heat
packages. Defined in this way, the derating factor can be inter- transfer (that is, a low thermal resistivity material), the penalty
preted as a reduction in the cable ampacity due to the presence of that is suffered when it is routed through a short segment of con-
the conduit. Since the medium in a conduit is usually air with an duit is more severe than when it is placed in a high resistivity
extremely high thermal resistivity ( – cm C/W), soil. In this situation the conduit replaces the good soil with a
the ampacity of the conduit segment of the circuit will be lower layer of high thermal resistance air, which hinders the transfer
than the ampacity value for the direct-buried portion of the cir- of heat to the surrounding soil. On the other hand, if the cable is
cuit. In this situation the derating factor will always be less than routed through a thermally poor high resistivity soil, the reduc-
one. However, if the conduit is filled with a fluidized grout or tion in ampacity resulting from the presence of the conduit is
slurry that completely fills the conduit, remains in place and has less. This trend occurs because the presence of the conduit and
a thermal resistivity less than that of the ambient soil, the pres- air layer replaces a layer of soil that is already poorly conducting
ence of the conduit will result in a region of relatively good heat and causes a diminishing rating penalty. This expected trend in
transfer. In this case the fluid-filled conduit could result in a der- the derating factor is illustrated in Fig. 3. In this figure the de-
ating factor which exceeds one, and the presence of the conduit rating factor is plotted as a function of conduit length and soil
does not represent a thermal bottleneck in the circuit. In this spe- resistivity, and all quantities are nondimensionalized. The con-
cialized case, the terminology of a derating factor is perhaps in- duit length has been divided by the mean conduit diameter and
appropriate and it would be more logical to refer to an ampacity the dimensionless soil resistivity is determined by dividing the
enhancement factor applied to the location of the conduit. soil resistivity by the equivalent thermal resistivity of the cable
insulation layers.
A. Effect of Conduit Length The curves in Fig. 3 assume a single 35 kV, 750 kcmil
An important application of the finite element software is the (380 mm ) aluminum conductor cable buried in 25 C soil to a
determination of the effect of conduit length on the derating of depth of 0.914 m. The conduit is 152 mm in diameter and the
the buried cable. Fig. 2 shows the trend in the cable derating fac- equivalent thermal resistivity of the cable insulation layers is
tors for a single cable and a triplexed cable geometry buried in a 350 cm C/W. The trend in the derating factor is similar to the
564 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 20, NO. 2, APRIL 2005

in (41) of [1]. The empirical constants for air were replaced


by those for oil since no values were provided for water. Even
though the thermal properties for water and oil are different,
the computer results for the derating factor will give the correct
trend when water completely fills the void areas in the con-
duit. It should be noted, however, that the thermal resistivity
of oil ( – cm C/W) is higher than that of water
( – cm C/W) so that conduction of heat through
an oil layer in a conduit is less than conduction of heat through
an identical water-filled conduit. In addition, the convection of
heat through a water layer is greater than through an equivalent
Fig. 3. Cable derating factor as a function of dimensionless conduit length,
oil layer, because the viscosity of water is less than that of oil.
L/D, for several soil resistivities. Therefore if a conduit can be filled with a fluid, water would
be a likely choice, because it would require a smaller derating
than an oil-filled conduit. Since water is superior to oil as a
one shown in Fig. 2. The decrease in cable ampacity disappears
heat transfer fluid, the computer results for oil will provide
when the ratio of conduit length to mean diameter exceeds
derating factors that are larger than exist when the conduit if
about 20 and the derating value asymptotically approaches the
filled with water. One caution should be noted if the derating
rating for a cable in an infinitely long section of conduit. The
factors for fluid-filled conduits are to be applied. The entire
ratings penalty paid by the cables in the lower resistivity soil
void space in the conduit must be filled with the fluid. If the
is more significant than the reduction required when the soil
fluid drains or seeps from the conduit, the derating of the circuit
resistivity is high. For example, the ampacity for a long length
in the conduit must be increased to reflect the increase in local
of conduit is only about 95 percent of its direct-buried value
thermal resistance.
when the soil resistivity is 160 cm C/W and it is about 87 and
79 percent when the soil resistivity decreases to about 90 and For fluid-filled conduits the derating factor approached an
50 cm C/W, respectively. asymptotic value when the ratio of conduit length to mean con-
duit diameter exceeded about 20. The derating factor is approx-
C. Effect of Cable Depth imately one when a single cable was routed through an oil-filled
conduit, because the thermal resistivity of the oil approaches the
As the burial depth increases, the effective thermal resistance resistivity of the native soil that the conduit displaces. When the
of the soil layer surrounding the cable also increases. Therefore conduit is filled with water, the derating factor slightly exceeds
the ampacity of a cable decreases as the cable is buried more one due to the superior heat transfer capabilities of water. These
deeply in the soil. If the presence of a short length of conduit results imply that the presence of the fluid-filled conduit does
is added to the thermal circuit, the ampacity of the cable must not require lowering the ampacity of the cable and the ampacity
be further derated to account for the region of added thermal of the circuit is the same as the ampacity of a direct-buried cable,
resistance that accompanies the presence of the air layer inside regardless of conduit length. However, for the case of a triplexed
the conduit. Cables that are buried at greater depths will be sub- cable in a fluid-filled conduit, the ampacity should be reduced
jected to larger derating factors (smaller ampacity penalty) than by up to about 3 percent when the conduit length
ones buried at shallow depths. This trend in ampacity penalty is ratio exceeds 20. These results clearly indicate that the factor
due to the fact that any factor that reduces the thermal resistance that accounts for the derating of cables in conduit is the trapped
of the circuit (cables buried at shallow depths and cables buried air layer inside the conduit. Once the air layer is replaced by
in low resistivity soil) will produce lower derating factors. a better conducting medium, such as water, the reason for der-
For reasonable cable depths, the computer results have shown ating the cable is removed.
that the influence of the burial depth on the derating factor is Even though the results presented here were calculated on
not significant. For example, decreasing the cable depth from the basis of a single cable design buried in a soil with a single
to 1.22 to 0.61 m creates a percentage decrease in the derating value of thermal resistivity and ambient temperature, the use
factor of less than 1.5 percent for the example case considered in of dimensionless quantities would suggest that the magnitude
the previous section. Therefore the ampacity penalty that must and trend of the derating factors would apply to other cable de-
be paid as the cable is buried shallower in the soil is relatively signs and other installations as well. In other words, the der-
small and it is not greatly influenced by moderate changes in the ating factors presented here can be used for a broad range of
burial depth of the cable. cable designs and a wide variety of cable installations. Further-
more, even though the analysis assumes the poor thermal envi-
D. Fluid-Filled Conduits ronment is caused by a short segment of conduit, the trends in
In practical installations buried conduits are often full of the derating factors should apply to installations for which the
water. The finite element program was used to determine thermal bottleneck is a result of a high resistivity slice of soil.
how the presence of water might affect the cable ampacity This observation is supported by a comparison of the trend in
derating factor for both a single and three cable fluid-filled derating factors presented here and the derating factors given in
conduit. The thermal resistance of the air layer was replaced [3]. Both studies suggest that when a cable route passes through
with a liquid layer by changing the empirical constants used a segment of poor thermal conditions, the ampacity derating
VAUCHERET et al.: AMPACITY DERATING FACTORS FOR CABLES BURIED IN SHORT SEGMENTS OF CONDUIT 565

should be increased as the length of the thermal bottleneck is ACKNOWLEDGMENT


increased. If the axial length of the poor region is more than This work originated as Georgia Tech NEETRAC Baseline
about 20 times the diameter of the conduit (or diameter of the Project 02-202. This support is gratefully acknowledged. The
pipe in pipe-type installations), then the ampacity should be cal- authors would also like to thank Dr. Ronald G. Harley of
culated on the basis of the entire cable route being buried in the Georgia Institute of Technology School of Electrical and Com-
poor environment. This conclusion is the same regardless if the puter Engineering and Mr. Thomas C. Champion of NEETRAC
cable is in a short segment of conduit and the soil resistivity is for their support of this work.
unchanged or if the cable is routed through a dry section of soil
that exists under a roadway. When the poor thermal conditions
REFERENCES
are limited to a shorter section of the cable route, the reduction
[1] J. H. Neher and M. H. McGrath, “The calculation of the temperature rise
in ampacity is less severe and it is a function of the axial length and load capability of cable systems,” AIEE Trans. Power App. Syst., vol.
of the high resistance region. 76, pp. 752–772, Oct. 1957.
The derating factors presented here also corroborate the mag- [2] IEEE Standard Power Cable Ampacity Tables, 1994. IEEE Std. 835-
1994, NY.
nitude of values presented in [3]. Since a change in soil resis- [3] H. Brakelmann and G. Anders, “Ampacity reduction factors for cables
tivity or ambient temperature is a much more severe thermal crossing thermally unfavorable regions,” IEEE Trans. Power Delivery,
bottleneck than experienced by a short span of conduit, their de- vol. 16, no. 4, pp. 444–448, Oct. 2001.
[4] ANSYS Finite Element Simulation Software, ANSYS Inc., Canonsburg,
rating factors are more severe than the ones indicated in Figs. 2 PA.
and 3. Their results indicate that a cable ampacity should be re- [5] R. A. Hartlein, “Heat Transfer from Electric Power Cables Enclosed in
duced by as much as 50 percent when it is routed through a re- Vertical Protective Shields,” M.S. Thesis, School of Mechanical Engi-
neering, Georgia Institute of Technology, Mar. 1982.
gion of higher resistivity soil with increased temperature. When [6] F. Kreith and W. Z. Black, “Basic Heat Transfer,” , N.Y.: Harper and
the installation includes a short segment of conduit, our results Row, Publishers, 1980, p. 91.
would require a reduction of less than 20 percent [7] CYMCAP Power Cable Ampacity Program, CYME International, Inc.,
St. Bruno, Quebec, Canada.
when the soil resistivity is low and the ambient temperature re-
mains unchanged.

Pascal Vaucheret graduated in mechanical engineering from Ecole des Mines


V. CONCLUSION de Douai, France and Lille University of Science and Technology (DEA),
France and in electrical and computer engineering from Supélec, France and
The ampacity of direct-buried cables must be reduced when the Georgia Institute of Technology (MSECE).
they enter a segment of conduit, and the amount of derating de- His professional interests are applied R&D and project management for heavy
pends on the cable geometry, cable construction, burial depth industry. He has worked in the energy field (EDF, NEETRAC) and for material
manufacturers (Usinor, ECL-Pechiney-Alcan) in PR China, the USA, Europe,
and thermal conditions of the soil. A derating factor is defined on and Australia.
the basis of the rated ampacity of a direct-buried cable and this
factor can be used to determine the reduction in ampacity that
must be applied if the cable is to remain below acceptable tem-
R. A. Hartlein (SM’02) is a mechanical engineering graduate of the Georgia
peratures inside the conduit. A finite element package is used to Institute of Technology.
determine derating factors for typical cable constructions and He spent the first years of his career at the Georgia Power Research Center in
common installations. The results provided by the computer Atlanta, Georgia. During that time he conducted research and test programs to
evaluate the wide variety of materials used on electric utility transmission and
model clarify the issue of how the length of conduit will in- distribution systems. He came to Georgia Tech. in 1996 as the Underground Sys-
fluence the ampacity of a buried cable system. The conduit is tems Program Manager, where he develops and manages research and testing
considered “short” if its length is less than 20 times its diam- projects related to electric utility underground cable systems. He actively par-
ticipates in the development of industry standards and specifications for under-
eter. In this case the derating that must be applied to a cable ground cable systems and has served as Chair of the IEEE Insulated Conduc-
ampacity ranges between about 0.80 and 0.95 depending on the tors Committee. He has also authored a number of publications on the subject
specific installation. A length of conduit is said to be “long” of cable aging and operation.
from a thermal standpoint if its length is over 20 times its diam-
eter. In this case the ampacity of the cable must be determined
on the basis of an infinitely long length of conduit. Conditions W. Z. Black (M’77–S’94–F’96) received the B.S. and M.S. degrees in mechan-
ical engineering from the University of Illinois, Urbana-Champaign, IL and the
which result in lower ampacity (greater burial depths, higher soil Ph.D. from Purdue University, West Lafayette, IN.
resistivity) result in less derating of the ampacity or higher der- His research area is heat transfer from electrical systems. He is currently Re-
ating factors. Conduits filled with either water, oil or a material gents’ Professor Emeritus and he was previously a Georgia Power Distinguished
Professor of ME at the Georgia Institute of Technology, Atlanta. Dr. Black
that has a resistivity similar to that of the ambient soil create a is active in IEEE ampacity committees and has published a number of IEEE
condition for which the derating factor approaches one. TRANSACTIONS papers in the ampacity area.

Vous aimerez peut-être aussi