Wherever the max and min values are not listed on the
construction drawings, it is expected that the contractor would
know that the maximum value had to be equal to the total of the cfm values listed for the diffusers connected to the applicable VAV terminal box. Though this may work for the maximum value, many different procedures are utilized to determine what the applicable minimum value should be. One method is to set the minimum values at 30 to 33% of the maximum value. Though this method may be close to the required value, it may fall short in providing the amount of air required for good Interior Air Quality and/or good humidity control and low load. For this reason, the maximum and minimum terminal box values should always be selected by the design engineer and shown on the design drawings. In several situations reported to the NRC by SMACNA contractors, where the minimum terminal box was not shown on the drawings, the contractors elected to set the terminal boxes in many areas at 30% of the maximum value. Only after comfort problems developed did the contractors find out that the actual design was based on minimums in many of the rooms to be set at 50% of the maximum value. Had this value been shown on the drawings at the design stage, much fighting and money could have been saved rather than having to make the corrections after the fact. In one major high rise building reported to the NRC, close to 500 perimeter boxes were set up by the contractor at 30% of the maximum value since the minimum value was not shown on the drawings and the contractor was in the middle of commissioning the HVAC systems to meet a move-in dead line. After the units were set up, the engineers came forth to notify all involved that the terminal boxes should have been set with a zero minimum flow value. After the terminal boxes were then set up at the zero flow minimum, interior air problems were reported by the majority of occupants. Many dollars later, and in the middle of a litigation, the contractor was paid to go back and set the terminal boxes back to 30% of the maximum value. To accommodate the increase in minimum flow, the supply temperature in these areas had to be reset to a higher value which in turn created humidifies exceeding 60%. This presented both additional comfort and health problems.